Calculation-Foe-With New Mech Load - 30-05-2013 (Revised)
Calculation-Foe-With New Mech Load - 30-05-2013 (Revised)
18 2-OPC-9D-014 MDB 3 SMDB3F Cable Tray 20 380 1 4 95 50 137.26 208.54 260.68 350 400 1.880 1.481 0.49 21.97 36
19 2-OPC-9D-015 MDB 3 SMDB3S Cable Tray 25 380 1 4 95 50 109.34 166.12 207.66 350 400 1.872 1.479 0.49 19.72 36
20 2-OPC-9D-016 MDB 3 SMDB3TH Cable Tray 30 380 1 4 240 95 307.09 466.57 583.22 600 600 3.068 1.794 0.81 22.87 36
21 2-OPC-9D-017 SMDB1F LP1-F Cable Tray 14 380 1 4 6 6 25.85 39.28 49.09 60 100 3.410 2.626 0.90 3.60 6
22 2-OPC-9D-018 SMDB1F PP1-F Cable Tray 14 380 1 4 6 6 10.68 16.23 20.28 30 100 1.409 2.099 0.37 3.60 6
23 2-OPC-9D-019 SMDB1F PP1-VAV-F Cable Tray 14 380 1 4 16 10 21.87 33.23 41.54 100 100 1.098 2.017 0.29 7.96 16
24 2-OPC-9D-020 SMDB1F AHU-4 Cable Tray 45 380 1 3 6 6 12.23 18.58 23.23 30 100 5.186 3.093 1.36 1.20 6
25 2-OPC-9D-021 SMDB1F AHU-5 Cable Tray 45 380 1 3 16 10 16.67 25.33 31.66 60 100 2.690 2.436 0.71 3.03 6
26 2-OPC-9D-022 SMDB1F AHU-6 Cable Tray 14 380 1 3 10 6 12.23 18.58 23.23 50 100 0.963 1.982 0.25 5.63 6
27 2-OPC-9D-023 SMDB1F BP-1 Cable Tray 14 380 1 3 6 6 17.78 27.01 33.77 30 100 2.345 2.346 0.62 3.60 6
28 2-OPC-9D-024 SMDB1F BP-2 Cable Tray 40 380 1 3 16 6 51.12 77.67 97.09 100 100 7.333 3.658 1.93 3.38 6
29 2-OPC-9D-025 SMDB1S LP1-S Cable Tray 14 380 1 4 10 6 29.50 44.82 56.03 60 100 2.324 2.556 0.61 5.31 6
30 2-OPC-9D-026 SMDB1S PP1-S Cable Tray 10 380 1 4 10 6 25.83 39.24 49.06 60 100 1.453 2.327 0.38 6.80 10
31 2-OPC-9D-027 SMDB1S PP1-VAV-S Cable Tray 14 380 1 4 10 6 23.56 35.80 44.74 100 100 1.856 2.433 0.49 5.31 6
32 2-OPC-9D-028 SMDB1S AHU-14 Cable Tray 45 380 1 3 16 10 41.12 62.48 78.09 100 100 6.636 3.691 1.75 2.94 6
33 2-OPC-9D-029 SMDB1S AHU-15 Cable Tray 25 380 1 3 16 10 20.56 31.24 39.05 60 100 1.843 2.430 0.49 4.82 6
34 2-OPC-9D-030 SMDB1TH LP1-TH Cable Tray 15 380 1 4 10 6 28.00 42.54 53.18 60 100 2.363 2.808 0.62 5.22 6
35 2-OPC-9D-031 SMDB1TH PP1-TH Cable Tray 15 380 1 4 6 6 24.81 37.69 47.12 50 100 3.507 3.109 0.92 3.35 6
36 2-OPC-9D-032 SMDB1TH PP1-VAV-TH Cable Tray 15 380 1 4 25 16 54.64 83.02 103.77 125 250 1.886 2.683 0.50 9.73 10
37 2-OPC-9D-033 SMDB1TH AHU-22 Cable Tray 46 380 1 3 16 10 24.45 37.15 46.43 60 100 4.034 3.248 1.06 2.95 6
38 2-OPC-9D-034 SMDB1TH AHU-23 Cable Tray 14 380 1 3 10 6 41.12 62.48 78.09 100 100 3.239 3.039 0.85 5.52 6
39 2-OPC-9D-035 SMDB1TH ELEV-1 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 4.074 1.89 3.34 6
40 2-OPC-9D-036 SMDB1TH ELEV-2 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 4.074 1.89 3.34 6
41 2-OPC-9D-037 SMDB2F LP2-F Cable Tray 14 380 1 4 6 6 26.15 39.73 49.66 60 100 3.450 2.918 0.91 3.78 6
42 2-OPC-9D-038 SMDB2F PP2-F Cable Tray 14 380 1 4 16 10 37.67 57.23 71.54 100 100 1.891 2.508 0.50 8.98 10
43 2-OPC-9D-039 SMDB2F PP2-F1 Cable Tray 14 380 1 4 50 35 95.99 145.84 182.30 200 100 1.709 2.460 0.45 17.67 36
44 2-OPC-9D-040 SMDB2F PP2-VAV-F Cable Tray 14 380 1 4 16 10 20.18 30.66 38.33 50 100 1.013 2.277 0.27 8.98 16
45 2-OPC-9D-041 SMDB2F AHU-1 Cable Tray 50 380 1 3 16 10 16.66 25.31 31.64 60 100 2.987 2.796 0.79 2.86 6
46 2-OPC-9D-042 SMDB2F AHU-2 Cable Tray 36 380 1 3 10 6 20.55 31.22 39.03 60 100 4.162 3.105 1.10 2.52 6
47 2-OPC-9D-043 SMDB2F AHU-3 Cable Tray 36 380 1 3 10 6 16.66 25.31 31.64 60 100 3.375 2.898 0.89 2.52 6
48 2-OPC-9D-044 SMDB2F BP-3 Cable Tray 31 380 1 3 10 6 40.00 60.77 75.97 90 100 6.977 3.846 1.84 2.91 6
49 2-OPC-9D-045 SMDB2F BP-4 Cable Tray 50 380 1 3 6 6 17.77 27.00 33.75 50 100 8.372 4.213 2.20 1.10 6
50 2-OPC-9D-046 SMDB2F COMPRESSOR-1 Cable Tray 55 380 1 4 16 10 26.67 40.52 50.65 70 100 5.261 3.394 1.38 2.61 6
51 2-OPC-9D-047 SMDB2F COMPRESSOR-2 Cable Tray 55 380 1 4 16 10 26.67 40.52 50.65 70 100 5.261 3.394 1.38 2.61 6
52 2-OPC-9D-048 SMDB2F DRYER Cable Tray 55 380 1 4 6 6 5.50 8.36 10.45 20 100 2.850 2.760 0.75 1.00 6
53 2-OPC-9D-049 SMDB2F VACCUM PUMP-1 Cable Tray 55 380 1 4 10 6 14.45 21.95 27.44 40 100 4.472 3.187 1.18 1.67 6
54 2-OPC-9D-050 SMDB2F VACCUM PUMP-2 Cable Tray 55 380 1 4 10 6 14.45 21.95 27.44 40 100 4.472 3.187 1.18 1.67 6
55 2-OPC-9D-051 SMDB2S LP2-S Cable Tray 14 380 1 4 10 6 28.20 42.85 53.56 70 100 2.221 2.554 0.58 6.15 10
56 2-OPC-9D-052 SMDB2S PP2-S Cable Tray 14 380 1 4 10 6 29.81 45.29 56.61 60 100 2.348 2.587 0.62 6.15 10
57 2-OPC-9D-053 SMDB2S PP2-S1 Cable Tray 14 380 1 4 50 35 95.99 145.84 182.30 200 250 1.709 2.419 0.45 18.17 36
58 2-OPC-9D-054 SMDB2S PP2-VAV-S Cable Tray 14 380 1 4 16 10 14.45 21.95 27.44 50 100 0.726 2.160 0.19 9.11 10
59 2-OPC-9D-055 SMDB2S PP2-S2 Cable Tray 40 380 1 4 50 50 101.99 154.96 193.70 250 250 5.188 3.335 1.37 9.07 16
60 2-OPC-9D-056 SMDB2S PP2-S3 Cable Tray 40 380 1 4 35 25 77.99 118.49 148.12 200 250 5.262 3.354 1.38 7.15 10
61 2-OPC-9D-057 SMDB2S AHU-11 Cable Tray 48 380 1 3 10 6 12.23 18.58 23.23 50 100 3.303 2.838 0.87 1.92 6
62 2-OPC-9D-058 SMDB2S AHU-12 Cable Tray 40 380 1 3 10 6 16.67 25.33 31.66 60 100 3.752 2.957 0.99 2.29 6
63 2-OPC-9D-059 SMDB2S AHU-13 Cable Tray 40 380 1 3 10 6 16.67 25.33 31.66 50 100 3.752 2.957 0.99 2.29 6
PROJECT:- FACULTY OF ENGINEERING PART-1
KING FIZAL UNIVERSITY DAMMAM
CABLE SCHEDULE
SHORT
CABLE SIZE AS PER SIZE OF ECC ACTUAL CIRCUIT BREAKER CIRCUIT BREAKER % SHORT CIRCUIT
METHOD OF CABLE LENGTH IN VOLTAGE IN CURRENT IN CURRENT * VOLTAGE DROP % VOLTAGE CIRCUIT
SL NO CABLE ID FROM TO NO OF RUNS NO OF CORES LOAD IN RATING AT IN RATING AF IN ACCUMULATED CURRENT FOR
INSTALLATION MTRS VOLTS DESIGN IN MM2 IN MM2 AMPS 25% IN AMPS IN V DROP CURRENT IN
KVA AMPS AMPS VOLTAGE BREAKER(ISC) IN KA
ISC
64 2-OPC-9D-060 SMDB2TH LP2-TH Cable Tray 14 380 1 4 6 6 23.00 34.94 43.68 60 100 3.034 3.352 0.80 3.67 6
65 2-OPC-9D-061 SMDB2TH PP2-TH Cable Tray 14 380 1 4 10 10 31.49 47.84 59.81 60 100 2.480 3.207 0.65 5.80 10
66 2-OPC-9D-062 SMDB2TH PP2-VAV-TH Cable Tray 14 380 1 4 10 10 41.50 63.05 78.82 100 100 3.269 3.414 0.86 5.80 10
67 2-OPC-9D-063 SMDB2TH AHU-18 Cable Tray 50 380 1 3 35 16 33.34 50.65 63.32 160 250 2.812 3.294 0.74 5.55 6
68 2-OPC-9D-064 SMDB2TH AHU-19 Cable Tray 50 380 1 3 10 6 16.67 25.33 31.66 50 100 4.690 3.788 1.23 1.81 6
69 2-OPC-9D-065 SMDB2TH AHU-20 Cable Tray 45 380 1 3 10 6 16.67 25.33 31.66 50 100 4.221 3.665 1.11 2.00 6
70 2-OPC-9D-066 SMDB2TH AHU-21 Cable Tray 45 380 1 3 10 6 24.45 37.15 46.43 50 100 6.191 4.183 1.63 2.00 6
71 2-OPC-9D-067 SMDB2TH ELEV-3 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 4.074 1.89 3.34 6
72 2-OPC-9D-068 SMDB2TH ELEV-4 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 4.074 1.89 3.34 6
73 2-OPC-9D-069 SMDB2TH ELEV-7 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 4.074 1.89 3.34 6
74 2-OPC-9D-070 SMDB3F LP3-F Cable Tray 15 380 1 4 6 6 23.40 35.55 44.44 50 100 3.307 2.351 0.87 3.33 6
75 2-OPC-9D-071 SMDB3F PP3-F Cable Tray 15 380 1 4 6 6 12.93 19.65 24.56 40 100 1.828 1.962 0.48 3.33 6
76 2-OPC-9D-072 SMDB3F PP3-VAV-F Cable Tray 15 380 1 4 16 16 17.40 26.44 33.05 50 100 0.936 1.727 0.25 7.36 16
77 2-OPC-9D-073 SMDB3F AHU-7 Cable Tray 60.5 380 1 3 6 6 8.34 12.67 15.84 40 100 4.754 2.732 1.25 0.90 6
78 2-OPC-9D-074 SMDB3F AHU-8 Cable Tray 60.5 380 1 3 10 6 16.67 25.33 31.66 50 100 5.674 2.974 1.49 1.48 6
79 2-OPC-9D-075 SMDB3F AHU-9 Cable Tray 50 380 1 3 10 6 16.67 25.33 31.66 50 100 4.690 2.715 1.23 1.78 6
80 2-OPC-9D-076 SMDB3F AHU-10 Cable Tray 50 380 1 3 6 6 4.45 6.76 8.45 30 100 2.097 2.033 0.55 1.08 6
81 2-OPC-9D-077 SMDB3F BP-5 Cable Tray 60.5 380 1 3 6 6 6.67 10.13 12.67 30 100 3.802 2.482 1.00 0.90 6
82 2-OPC-9D-078 SMDB3F BP-6 Cable Tray 50 380 1 3 16 6 41.12 62.48 78.09 90 100 7.373 3.421 1.94 2.72 6
83 2-OPC-9D-079 SMDB3S LP3-S Cable Tray 50 380 1 4 10 6 22.58 34.31 42.88 50 100 6.352 3.151 1.67 1.76 6
84 2-OPC-9D-080 SMDB3S PP3-S Cable Tray 50 380 1 4 10 6 17.33 26.33 32.91 50 100 4.875 2.762 1.28 1.76 6
85 2-OPC-9D-081 SMDB3S PP3-VAV-S Cable Tray 10 380 1 4 16 16 18.05 27.42 34.28 50 100 0.647 1.649 0.17 9.12 16
86 2-OPC-9D-082 SMDB3S AHU-16 Cable Tray 60 380 1 3 16 10 33.34 50.65 63.32 70 100 7.174 3.367 1.89 2.27 6
87 2-OPC-9D-083 SMDB3S AHU-17 Cable Tray 70 380 1 3 16 10 20.56 31.24 39.05 60 100 5.161 2.837 1.36 1.97 6
88 2-OPC-9D-084 SMDB3TH LP3-TH Cable Tray 15 380 1 4 10 6 24.60 37.38 46.72 60 100 2.076 2.340 0.55 5.41 6
89 2-OPC-9D-085 SMDB3TH PP3-TH Cable Tray 15 380 1 4 10 6 29.05 37.38 46.72 60 100 2.076 2.340 0.55 5.41 6
90 2-OPC-9D-086 SMDB3TH PP3-VAV-TH Cable Tray 15 380 1 4 16 10 39.26 59.65 74.56 100 100 2.112 2.350 0.56 7.77 10
91 2-OPC-9D-087 SMDB3TH AHU-24 Cable Tray 65 380 1 3 10 6 20.56 31.24 39.05 60 100 4.793 3.055 1.26 2.17 6
92 2-OPC-9D-088 SMDB3TH AHU-25 Cable Tray 60 380 1 3 10 6 16.67 25.33 31.66 60 100 5.628 3.275 1.48 1.51 6
93 2-OPC-9D-089 SMDB3TH AHU-26 Cable Tray 60 380 1 3 16 10 33.34 50.65 63.32 70 100 7.174 3.682 1.89 2.34 6
94 2-OPC-9D-090 SMDB3TH ELEV-5 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 3.681 1.89 3.34 6
95 2-OPC-9D-091 SMDB3TH ELEV-6 Cable Tray 40 380 1 4 16 6 50.00 75.97 94.96 125 250 7.173 3.681 1.89 3.34 6
96 2-OPC-9D-092 SMDB3TH ELEV-8 Cable Tray 40 380 1 4 16 10 50.00 75.97 94.96 125 250 7.173 3.681 1.89 3.34 6
97 2-OPC-9D-093 EMDB SEMDB1 Cable Tray 111 380 1 4 50 25 48.70 73.99 92.49 125 250 6.875 2.286 1.81 3.73 6
98 2-OPC-9D-094 EMDB SEMDB2 Cable Tray 180 380 1 4 185 120 92.66 140.78 175.98 200 250 6.730 2.248 1.77 6.82 10
99 2-OPC-9D-095 EMDB SEMDB3 Cable Tray 75 380 1 4 35 16 40.82 62.02 77.52 100 100 5.164 1.836 1.36 4.09 6
100 2-OPC-9D-096 SEMDB1 ELP1-F Cable Tray 20 380 1 4 4 4 9.65 14.66 18.33 30 100 2.711 2.999 0.71 1.25 6
101 2-OPC-9D-097 SEMDB1 EPP1-F Cable Tray 10 380 1 4 4 4 5.16 7.84 9.80 30 100 0.725 2.477 0.19 1.88 6
102 2-OPC-9D-098 SEMDB1 ELP1-S Cable Tray 24 380 1 4 4 4 9.45 14.36 17.95 30 100 3.186 3.124 0.84 1.10 6
103 2-OPC-9D-099 SEMDB1 EPP1-S Cable Tray 24 380 1 4 4 4 10.08 15.31 19.14 30 100 3.398 3.180 0.89 1.10 6
104 2-OPC-9D-100 SEMDB1 ELP1-TH Cable Tray 30 380 1 4 4 4 10.10 15.35 19.18 30 100 4.256 3.406 1.12 0.94 6
105 2-OPC-9D-101 SEMDB1 EPP1-TH Cable Tray 30 380 1 4 4 4 3.56 6.02 7.52 30 100 1.669 2.725 0.44 0.94 6
106 2-OPC-9D-102 SEMDB2 ELP2-F Cable Tray 15 380 1 4 4 4 11.90 18.08 22.60 30 100 2.507 2.907 0.66 1.90 6
107 2-OPC-9D-103 SEMDB2 EPP2-F Cable Tray 15 380 1 4 4 4 11.04 16.77 20.97 30 100 2.326 2.860 0.61 1.90 6
108 2-OPC-9D-104 SEMDB2 ELP2-S Cable Tray 25 380 1 4 4 4 10.85 16.48 20.61 30 100 3.810 3.250 1.00 1.26 6
109 2-OPC-9D-105 SEMDB2 EPP2-S Cable Tray 20 380 1 4 10 6 25.32 38.47 48.09 70 100 2.849 2.997 0.75 1.90 6
110 2-OPC-9D-106 SEMDB2 ELP2-TH Cable Tray 30 380 1 4 4 4 8.65 13.14 16.43 30 100 3.645 3.207 0.96 1.08 6
111 2-OPC-9D-107 SEMDB2 EPP2-TH Cable Tray 30 380 1 4 6 6 13.32 20.24 25.30 50 100 3.765 1.468 0.99 1.82 6
112 2-OPC-9D-108 SEMDB2 MCC-EXF-TER Cable Tray 30 380 1 4 6 6 12.06 20.24 25.30 50 100 3.765 1.468 0.99 1.82 6
113 2-OPC-9D-109 SEMDB3 ELP3-F Cable Tray 15 380 1 4 4 4 9.80 14.89 18.61 30 100 2.065 2.379 0.54 1.55 6
114 2-OPC-9D-110 SEMDB3 EPP3-F Cable Tray 15 380 1 4 4 4 5.16 7.84 9.80 30 100 2.065 2.122 0.29 1.55 6
115 2-OPC-9D-111 SEMDB3 ELP3-S Cable Tray 25 380 1 4 6 6 8.65 13.14 16.43 30 100 2.038 2.372 0.54 1.45 6
116 2-OPC-9D-112 SEMDB3 EPP3-S Cable Tray 25 380 1 4 4 4 7.08 10.76 13.45 30 100 2.486 2.490 0.65 1.10 6
117 2-OPC-9D-113 SEMDB3 ELP3-TH Cable Tray 30 380 1 4 4 4 8.15 12.38 15.48 30 100 3.434 2.739 0.90 0.96 6
118 2-OPC-9D-114 SEMDB3 EPP3-TH Cable Tray 30 380 1 4 4 4 1.68 2.55 3.19 30 100 0.708 0.663 0.19 1.23 6
119 2-OPC-9D-115 MDB UPS UPS-PF-TER Cable Tray 150 380 1 4 50 25 40.00 60.77 75.97 100 100 7.630 4.120 2.01 1.48 6
120 2-OPC-9D-116 MCCSW EWH-1 Cable Tray 50 380 1 4 16 6 27.78 42.21 52.76 60 100 4.981 2.844 1.31 1.47 6
121 2-OPC-9D-117 MCCSW EWH-2(SB) Cable Tray 50 380 1 4 16 6 27.78 42.21 52.76 60 100 4.981 2.844 1.31 1.47 6
122 2-OPC-9D-118 MCCSW HWCP-01 Cable Tray 50 380 1 4 4 4 0.84 1.28 3.19 30 100 0.590 1.688 0.16 0.59 6
123 2-OPC-9D-119 MCCSW HWCP-02(SB) Cable Tray 50 380 1 4 4 4 0.84 1.28 3.19 30 100 0.590 1.688 0.16 0.59 6
ADD OR MODIFY SHEETS
TR.# MAIN DB VOLTAGE LENGTH KVA PF KW
X/R= 6 Z= ( Rt √ 37)
Rt = 0.0006172 Ω
Xt = 0.0037033 Ω
Resistance ( R ) Ω Reactance ( X ) Ω
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
CABLE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method
TRENCH
Ground Temp. ( deg.C) 45 Depth of laying (cm) ------
Power (KW) 2217.33 No.of cables/ circuits in group 9 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.74
Overall derating factor 0.74
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.466 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.12 %
voltage
Accumulated Voltage drop 0.466 + 0.000 = 0.466 Volts
MAIN LT
Upstream Switchboard LOAD MDB-1
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 513.13 No.of cables/ circuits in group 2 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.81
Overall derating factor 0.81
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.388 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.42 %
voltage
Accumulated Voltage drop 5.388 + 0.000 = 5.388 Volts
ARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.90 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.420 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.90 %
voltage
Accumulated Voltage drop 3.420 + #REF! = #REF! Volts
BP 2 0.1296900 0.0033000
TOTAL #REF! #REF!
Total Impedance Z =√ (R² + X²)
=√ ( 0.003929
= )² + ( 0.011349
#REF! )² = 0.014 Ω ohm
ARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 167.81 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.051 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.28 %
voltage
Accumulated Voltage drop 1.051 + #REF! = #REF! Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 46.44 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.831 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.83 %
voltage
Accumulated Voltage drop 1.831 + 0.569 = 2.400 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.41 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.990 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.81 %
voltage
Accumulated Voltage drop 3.990 + 0.569 = 4.559 Volts
= 3.0 KA
FOR 1 PH PANEL
BACK
SELECT PH R
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: LAB-1
PANEL NAME: PP-1G MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : L-26 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 36 MAIN CIRCUIT BREAKER: 125 250 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 CRYOSTAT 1026 1026 2 20 100 1 1026 * 693 1 100 20 2 693 693 CENTRIFUGE 2 3X4
3 1026 1026 . 1 1026 * 693 1 693 693 4
3X4 5 EMBED CENTER 900 900 1 20 100 1 900 * 675 1 100 20 1 675 675 FUME HOOD 6 3X4
3X4 7 TISSUE 846 846 2 20 100 1 846 * 1170 1 100 20 1 1170 1170 ANALYZER 8 3X4
9 846 846 . 1 846 * 990 1 100 20 1 990 990 CONV.SKT 10 3X4
3X4 11 WAX OVEN 1026 1026 2 20 100 1 1026 * 100 20 2 0 SPARE 12
13 1026 1026 . 1 1026 * 0 14
3X4 15 MICROTOME 900 900 1 20 100 1 900 * 1125 1 100 20 2 1125 1125 SECTION FLOT 16 3X4
3X4 17 FUME HOOD 837 837 1 20 100 1 837 * 1125 1 1125 1125 18
3X4 19 EDF 414 414 1 20 100 1 414 * 675 1 100 20 1 675 675 FUME HOOD 20 3X4
3X4 21 REF 1170 1170 1 20 100 1 1170 * 1026 1 100 20 2 1026 1026 CRYOSTAT 22 3X4
3X4 23 ANALYZER 1350 1350 1 20 100 1 1350 * 1026 1 1026 1026 24
3X4 25 MICROTOME 1170 1170 1 20 100 1 1170 * 1395 1 100 20 1 1395 1395 REF 26 3X4
27 SPARE 1 20 100 * 900 1 100 20 1 900 900 FUME HOOD 28 3X4
3X4 29 REF 1260 1260 1 20 100 1 1260 * 1350 1 100 20 1 1350 1350 FUME HOOD 30 3X4
3X4 31 CONV.SKT 972 972 1 20 100 1 972 * 270 1 100 20 1 270 270 SCANINIG 32 3X4
33 SPARE 900 1 100 20 1 900 900 MICROTOME 34 3X4
35 SPARE 100 20 1 0 SPARE 36
SUB.TOTAL CON.LOAD(W) 14769 5454 3942 5373 4203 5634 4176 14013 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 14769 5454 3942 5373 4203 5634 4176 14013 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 28782 W.
DEMAND FACTOR 1.00
TOTAL DEMAND LOAD 28782 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : LAB-1 Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 33.56 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.351 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.07 %
voltage
Accumulated Voltage drop 2.351 + 0.569 = 2.919 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 28.76 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.259 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.57 %
voltage
Accumulated Voltage drop 1.259 + 0.569 = 1.828 Volts
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 FUME HOOD 675 675 1 20 100 1 675 * 100 20 2 0 SPARE 2
3X4 3 CHEM ANALYZER 693 693 1 20 100 1 693 * 0 4
3X4 5 BENCH TOP 562.5 562.5 2 20 100 1 562.5 * 777.6 0.6 100 20 1 1296 1296 CONV.SKT 6 3X4
7 562.5 562.5 . 1 562.5 * 583.2 0.6 100 20 1 972 972 CONV.SKT 8 3X4
3X4 9 REF 477 477 2 20 100 1 477 * 680.4 0.6 100 20 1 1134 1134 CONV.SKT 10 3X4
11 477 477 . 1 477 * 414 1 100 20 1 414 414 EDF 12 3X4
3X4 13 FLM ILLUMINATOR 1287 1287 1 20 100 1 1287 * 445.5 1 100 20 1 445.5 445.5 CELL COUNTER 14 3X4
15 SPARE 0 2 20 100 * 1152 1 100 20 2 1152 1152 WATER BATH 16 3X4
17 0 . * 1152 1 1152 1152 18
3X4 19 MICROWAVE 1026 1026 2 20 100 1 1026 * 846 1 100 20 2 846 846 WATER BATH 20 3X4
21 1026 1026 . 1 1026 * 846 1 846 846 22
3X4 23 DRY BATH,PC 450 450 1 20 100 1 450 * 630 1 100 20 1 630 630 COLLECTOR 24 3X4
5X4 25 STERILIZER 900 900 3 20 100 1 900 * 100 20 1 0 SPARE 26
27 900 900 . 1 900 * 540 1 100 20 2 540 540 GLASS BLOWER 28 3X4
29 900 900 . 1 900 * 540 1 540 540 30
SUB.TOTAL CON.LOAD(W) 9936 4450.5 3096 2389.5 2263.5 3672 4032 9967.5 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 9936 4450.5 3096 2389.5 1874.7 3218.4 3513.6 8606.7 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 19903.5 W.
DEMAND FACTOR 0.93
TOTAL DEMAND LOAD 18542.7 W.
FOR 1 PH PANEL
BACK
SELECT PH R
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: LAB-1
PANEL NAME: 8PP-WLG MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : WET LAB TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 30 MAIN CIRCUIT BREAKER: 70 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 FUME HOOD 675 675 1 20 100 1 675 * 706.5 1 100 20 1 706.5 706.5 ANALYTICAL 2 3X4
3X4 3 CHEM. ANALYZER 693 693 1 20 100 1 693 * 972 1 100 20 1 972 972 STIRRER 4 3X4
3X4 5 BENCH TOP 562.5 562.5 2 20 100 1 562.5 * 675 1 100 20 2 675 675 REF 6 3X4
7 562.5 562.5 . 1 562.5 * 675 1 675 675 8 3X4
3X4 9 REF 477 477 2 20 100 1 477 * 1026 1 100 20 2 1026 1026 LAB OVEN 10 3X4
11 477 477 . 1 477 * 1026 1 1026 1026 12 3X4
3X4 13 TOUCH MIXER 1251 1251 1 20 100 1 1251 * 445.5 1 100 20 1 445.5 445.5 CELL COUNTER 14 3X4
3X4 15 CENTRIFUGE 405 405 2 20 100 1 405 * 1152 1 100 20 2 1152 1152 REF 16 3X4
17 405 405 . 1 405 * 1152 1 1152 1152 18 3X4
3X4 19 MICROWAVE 1026 1026 2 20 100 1 1026 * 846 1 100 20 2 846 846 WATER BATH 20 3X4
21 1026 1026 . 1 1026 * 846 1 846 846 22 3X4
3X4 23 DRY BATH 450 450 1 20 100 1 450 * 630 1 100 20 1 630 630 COLLECTOR 24 3X4
3X4 25 OUTLETS 810 810 1 20 100 0.6 486 * 100 20 2 0 SPARE 26 3X4
27 SPARE 0 1 20 100 * 0 28 3X4
29 SPARE 0 1 20 100 * 777.6 0.6 100 20 1 1296 1296 OUTLETS 30 3X4
SUB.TOTAL CON.LOAD(W) 8820 4324.5 2601 1894.5 2673 3996 4779 11448 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 8496 4000.5 2601 1894.5 2673 3996 4260.6 10929.6 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 20268 W.
DEMAND FACTOR 0.96
TOTAL DEMAND LOAD 19425.6 W.
FOR 1 PH PANEL
BACK
SELECT PH R
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: LAB-1
PANEL NAME: PP-TG MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : ROOM#G-08 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 36 MAIN CIRCUIT BREAKER: 100 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
5X6 1 EF-1 1440 1440 3 30 100 1 1440 * 1440 1 100 30 3 1440 1440 EF-2 2 5X6
3 1440 1440 . 1 1440 * 1440 1 1440 1440 4
5 1440 1440 . 1 1440 * 1440 1 1440 1440 6
5X4 7 EF-5 855 855 3 20 100 1 855 * 1674 1 100 30 1 1674 1674 EF-3 8 3X6
9 855 855 . 1 855 * 1674 1 100 30 1 1674 1674 EF-4 10 3X6
11 855 855 . 1 855 * 855 1 100 20 1 855 855 EF-6 12 3X4
3X4 13 EF-17 150 150 1 20 100 1 150 * 3899.7 1 100 30 3 3899.7 3899.7 DISTILLER UNIT 14 5X6
3X4 15CHILLER MACHINE 1500 1500 1 20 100 1 1500 * 3899.7 1 3899.7 3899.7 16
3X4 17 EF-7,7A&EF-4A 1080 1080 1 20 100 0.8 864 * 3899.7 1 3899.7 3899.7 18
5X25 19 EWH-1 7200 7200 3 60 100 1 7200 * 855 1 100 20 3 855 855 BOOSTER PUMP 20 5X4
21 7200 7200 . 1 7200 * 855 1 855 855 22
23 7200 7200 . 1 7200 * 855 1 855 855 24
5X16 25 EWH-3 5400 5400 3 40 100 1 5400 * 373 1 100 30 3 373 373 CIRCULATING 26 3X4
27 5400 5400 . 1 5400 * 0 28
29 5400 5400 . 1 5400 * 0 30
3X4 31 CP-1 630 630 1 20 100 1 630 * 100 20 3 0 SPARE 32
3X4 33 CP-3 423 423 1 20 100 1 423 * 0 34
35 SPARE 0 1 20 100 * 0 36
SUB.TOTAL CON.LOAD(W) 48468 15675 16818 15975 8241.7 7868.7 7049.7 23160.1 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 48252 15675 16818 15759 8241.7 7868.7 7049.7 23160.1 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 71628.1 W.
DEMAND FACTOR 1.00
TOTAL DEMAND LOAD 71412.1 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : LAB-1 Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 18.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 10.443 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.18 %
voltage
Accumulated Voltage drop 10.443 + 5.944 = 16.387 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 22.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 13.054 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.72 %
voltage
Accumulated Voltage drop 13.054 + 5.944 = 18.998 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 18.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.460 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.55 %
voltage
Accumulated Voltage drop 7.460 + 5.944 = 13.403 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.595 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.17 %
voltage
Accumulated Voltage drop 5.595 + 5.944 = 11.538 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.357 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.70 %
voltage
Accumulated Voltage drop 3.357 + 5.944 = 9.300 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 2.70 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.119 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.23 %
voltage
Accumulated Voltage drop 1.119 + 5.944 = 7.063 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 4.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.865 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.39 %
voltage
Accumulated Voltage drop 1.865 + 5.944 = 7.809 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 54.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.300 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.52 %
voltage
Accumulated Voltage drop 7.300 + 5.944 = 13.244 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 54.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.300 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.52 %
voltage
Accumulated Voltage drop 7.300 + 5.944 = 13.244 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 47.70 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.606 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.96 %
voltage
Accumulated Voltage drop 4.606 + 5.944 = 10.550 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 36.90 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.650 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.18 %
voltage
Accumulated Voltage drop 5.650 + 5.944 = 11.594 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 40.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.721 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.78 %
voltage
Accumulated Voltage drop 3.721 + 5.944 = 9.665 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 6.75 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.763 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.58 %
voltage
Accumulated Voltage drop 2.763 + 5.944 = 8.707 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.527 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.15 %
voltage
Accumulated Voltage drop 5.527 + 5.944 = 11.470 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 0.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 5.944 = 5.944 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 0.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 5.944 = 5.944 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 0.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 5.944 = 5.944 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 31.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.956 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.45 %
voltage
Accumulated Voltage drop 6.956 + 5.944 = 12.900 Volts
ARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
GR. DIRECT
Thermal resistivity of soil 1.2 air temp.(deg.C) 45 Installation Method
LAID
Ground Temp. ( deg.C) 35 Depth of laying (cm) 80
Power (KW) 601.32 No.of cables/ circuits in group 4 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. 1
Derating factor for variation in burial depth 0.94
Derating factor for variation in thermal resistivity 1
Derating factor for variation in air temp. N/A
Derating factor for grouping 0.63
Overall derating factor 0.5922
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.421 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.34 %
voltage
Accumulated Voltage drop 6.421 + 0.393 = 6.814 Volts
X/R= 6 Z= ( Rt √ 37)
Rt = 0.0026033 Ω
Xt = 0.0156200 Ω
Resistance ( R ) Ω Reactance ( X ) Ω
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 LIGHTING 720 720 1 20 100 1 720 * 540 1 100 20 1 540 540 LIGHTING 2 3X4
3X4 3 LIGHTING 720 720 1 20 100 1 720 * 540 1 100 20 1 540 540 LIGHTING 4 3X4
3X4 5 LIGHTING 720 720 1 20 100 1 720 * 540 1 100 20 1 540 540 LIGHTING 6 3X4
3X4 7 LIGHTING 720 720 1 20 100 1 720 * 630 1 100 20 1 630 630 LIGHTING 8 3X4
3X4 9 LIGHTING 720 720 1 20 100 1 720 * 630 1 100 20 1 630 630 LIGHTING 10 3X4
3X4 11 LIGHTING 720 720 1 20 100 1 720 * 630 1 100 20 1 630 630 LIGHTING 12 3X4
3X4 13 LIGHTING 1134 1134 1 20 100 1 1134 * 1 100 20 1 SPARE 14
3X4 15 LIGHTING 1134 1134 1 20 100 1 1134 * 1 100 20 1 SPARE 16
3X4 17 LIGHTING 1134 1134 1 20 100 1 1134 * 1 100 20 1 SPARE 18
SUB.TOTAL CON.LOAD(W) 7722 2574 2574 2574 1170 1170 1170 3510 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 7722 2574 2574 2574 1170 1170 1170 3510 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 11232 W.
DEMAND FACTOR 1.00
TOTAL DEMAND LOAD 11232 W.
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: PP-2F MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : G-113 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 36 MAIN CIRCUIT BREAKER: 90 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 FUME HOOD 900 900 1 20 100 1 900 * 745 1 100 20 2 745 745 INCUBATOR 2 3X4
3X4 3 FUME HOOD 1350 1350 1 20 100 1 1350 * 745 1 745 745 4
3X4 5 CO2 INCUBATOR 1035 1035 1 20 100 1 1035 * 690 1 100 20 2 690 690 REF 6 3X4
3X4 7 PH METER 783 783 1 20 100 1 783 * 690 1 690 690 8
3X4 9 HYBRIDIZATION 990 990 2 20 100 1 990 * 940 1 100 20 2 940 940 WATER BATH 10 3X4
11 990 990 . 1 990 * 690 1 690 690 12
3X4 13 BENCH TOP 562.5 562.5 2 20 100 1 562.5 * 100 20 3 0 SPARE 14
15 562.5 562.5 . 1 562.5 * 0 16
3X4 17 HYBRIDIZATION 990 990 2 20 100 1 990 * 0 18
19 990 990 . 1 990 * 1200 1 100 20 1 1200 1200 HD 20 3X4
3X4 21 CONV.SKT 1134 1134 1 20 100 0.6 680.4 * 1200 1 100 20 1 1200 1200 HD 22 3X4
3X4 23 EDF&CONV.SKT 1224 1224 1 20 100 0.8 979.2 * 864 0.6 100 20 1 1440 1440 CONV.SKT 24 3X4
3X4 25 CONV.SKT 1134 1134 1 20 100 0.6 680.4 * 500 1 100 20 2 500 500 SEQUENCER 26 3X4
27 SPARE 0 2 20 100 * 500 1 500 500 28
29 0 . * 100 20 3 0 SPARE 30
3X4 31 EDF'S 828 828 1 20 100 0.8 662.4 * 0 32
3X4 33 CONV.SKT 972 972 1 20 100 0.6 583.2 * 0 34
3X4 35 CONV.SKT 1134 1134 1 20 100 0.6 680.4 * 100 20 1 0 SPARE 36
SUB.TOTAL CON.LOAD(W) 15579 5197.5 5008.5 5373 3135 3385 2820 9340 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 13419 4578.3 4166.1 4674.6 3135 3385 2244 8764 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 24919 W.
DEMAND FACTOR 0.89
TOTAL DEMAND LOAD 22183 W.
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: LP-1F MOUNTING : SURFACE 220 /127V,3PH,5W,60HZ.
LOCATION : G-113 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 42 MAIN CIRCUIT BREAKER: 160 250 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 LIGHTING 1260 1260 1 20 100 1 1260 * 1260 1 100 20 1 1260 1260 LIGHTING 2 3X4
3X4 3 LIGHTING 1080 1080 1 20 100 1 1080 * 1080 1 100 20 1 1080 1080 LIGHTING 4 3X4
3X4 5 LIGHTING 1260 1260 1 20 100 1 1260 * 1080 1 100 20 1 1080 1080 LIGHTING 6 3X4
3X4 7 LIGHTING 1260 1260 1 20 100 1 1260 * 1080 1 100 20 1 1080 1080 LIGHTING 8 3X4
3X4 9 LIGHTING 1080 1080 1 20 100 1 1080 * 1170 1 100 20 1 1170 1170 LIGHTING 10 3X4
3X4 11 LIGHTING 1080 1080 1 20 100 1 1080 * 1260 1 100 20 1 1260 1260 LIGHTING 12 3X4
3X4 13 LIGHTING 1170 1170 1 20 100 1 1170 * 1260 1 100 20 1 1260 1260 LIGHTING 14 3X4
3X4 15 LIGHTING 1170 1170 1 20 100 1 1170 * 1080 1 100 20 1 1080 1080 LIGHTING 16 3X4
3X4 17 LIGHTING 1260 1260 1 20 100 1 1260 * 1080 1 100 20 1 1080 1080 LIGHTING 18 3X4
3X4 19 LIGHTING 1260 1260 1 20 100 1 1260 * 1260 1 100 20 1 1260 1260 LIGHTING 20 3X4
3X4 21 LIGHTING 1170 1170 1 20 100 1 1170 * 1170 1 100 20 1 1170 1170 LIGHTING 22 3X4
3X4 23 LIGHTING 1170 1170 1 20 100 1 1170 * 1260 1 100 20 1 1260 1260 LIGHTING 24 3X4
3X4 25 LIGHTING 1260 1260 1 20 100 1 1260 * 1080 1 100 20 1 1080 1080 LIGHTING 26 3X4
3X4 27 LIGHTING 1080 1080 1 20 100 1 1080 * 1170 1 100 20 1 1170 1170 LIGHTING 28 3X4
3X4 29 LIGHTING 1170 1170 1 20 100 1 1170 * 1170 1 100 20 1 1170 1170 LIGHTING 30 3X4
31 SPARE 1 20 100 * 1260 1 100 20 1 1260 1260 LIGHTING 32 3X4
3X4 33 LIGHTING 1215 1215 1 20 100 1 1215 * 1080 1 100 20 1 1080 1080 LIGHTING 34 3X4
3X4 35 LIGHTING 1260 1260 1 20 100 1 1260 * 1170 1 100 20 1 1170 1170 LIGHTING 36 3X4
3X4 37 LIGHTING 1260 1260 1 20 100 1 1260 * 100 20 1 SPARE 38
3X4 39 LIGHTING 1080 1080 1 20 100 1 1080 * 100 20 1 SPARE 40
3X4 41 LIGHTING 720 720 1 20 100 1 720 * 100 20 1 SPARE 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 23265 7470 7875 7920 7200 6750 7020 20970 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 23265 7470 7875 7920 7200 6750 7020 20970 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 44235 W.
DEMAND FACTOR 1.00
TOTAL DEMAND LOAD 44235 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 48.24 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.902 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.86 %
voltage
Accumulated Voltage drop 1.902 + 0.467 = 2.369 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 30.55 No.of cables/ circuits in group 3 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.802 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.36 %
voltage
Accumulated Voltage drop 0.802 + 0.467 = 1.269 Volts
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 HD 1080 1080 1 20 100 1 1080 * 972 1 100 20 1 972 972 CONV.SKT 2 3X4
3X4 3 EDF'S 828 828 1 20 100 0.8 662.4 * 972 1 100 20 1 972 972 CONV.SKT 4 3X4
3X4 5 CONV.SKT 810 810 1 20 100 0.6 486 * 1296 1 100 20 1 1296 1296 CONV.SKT 6 3X4
7 SPARE 0 1 20 100 * 1296 1 100 20 1 1296 1296 CONV.SKT 8 3X4
9 SPARE 0 1 20 100 * 100 20 1 0 SPARE 10
3X4 11 HYBRIDZATION 900 900 2 20 100 1 900 * 100 20 2 0 SPARE 12
3X4 13 900 900 . 1 900 * 0 14
3X4 15 HYBRIDZATION 900 900 2 20 100 1 900 * 450 1 100 20 2 450 450 WASHER DRYER 16 3X4
3X4 17 900 900 . 1 900 * 450 1 450 450 18
3X4 19 WASHER DRYER 900 900 2 20 100 1 900 * 900 1 100 20 3 900 900 STERILIZER 20 5X4
3X4 21 900 900 . 1 900 * 900 1 900 900 22
3X4 23 CENTRIFUGE 873 873 2 20 100 1 873 * 900 1 900 900 24
3X4 25 873 873 . 1 873 * 873 1 100 20 2 873 873 CENTRIFUGE 26 3X4
3X4 27 HIGH SPEED 873 873 2 20 100 1 873 * 873 1 873 873 28
3X4 29 873 873 . 1 873 * 873 1 100 20 2 873 873 SP CENTRIFUGE 30 3X4
31 SPARE 0 1 20 100 * 873 1 873 873 32
3X4 33 CONV.SKT 1134 1134 1 20 100 0.6 680.4 * 792 1 100 20 1 792 792 REF 34 3X4
3X4 35 CONV.SKT 810 810 1 20 100 0.6 486 * 100 20 1 0 SPARE 36
37 38
39 40
41 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 13554 3753 4635 5166 4914 3987 3519 12420 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 12286.8 3753 4015.8 4518 4914 3987 3519 12420 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 25974 W.
DEMAND FACTOR 0.95
TOTAL DEMAND LOAD 24706.8 W.
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: PP-4F MOUNTING : SURFACE 220/127V,3PH,5W,60HZ.
LOCATION : C-112 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 24 MAIN CIRCUIT BREAKER: 60 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 FUME HOOD 1350 1350 1 20 100 1 1350 * 823.5 1 100 20 2 823.5 823.5 ANALY BALANCE 2 3X4
3X4 3 FUME HOOD 900 900 1 20 100 1 900 * 823.5 1 823.5 823.5 4
3X4 5 TOUCH MIXER 540 540 1 20 100 1 540 * 866.7 1 100 20 2 866.7 866.7 CENTRIFUGE 6 3X4
3X4 7 HD 1080 1080 1 20 100 1 1080 * 866.7 1 866.7 866.7 8
3X4 9 FUME HOOD 1350 1350 1 20 100 1 1350 * 562.5 1 100 20 2 562.5 562.5 BENCH TOP 10 3X4
3X4 11 FREEZER 823.5 823.5 2 20 100 1 823.5 * 562.5 1 562.5 562.5 12
13 823.5 823.5 1 823.5 450 1 100 20 1 450 450 GAMMA+PC 14 3X4
3X4 15 HD 1080 1080 1 20 100 1 1080 * 100 20 1 0 SPARE 16
3X4 17 TOUCH MIXER 540 540 1 20 100 1 540 * 450 1 100 20 1 450 450 COUNTER + PC 18 3X4
19 SPARE 0 2 20 100 * 100 20 1 0 SPARE 20
21 0 450 1 100 20 1 450 450 BETA+PC 22 3X4
3X4 23 CONV.SKT 1296 1296 1 20 100 0.6 777.6 * 100 20 1 0 SPARE 24
SUB.TOTAL CON.LOAD(W) 9783 3253.5 3330 3199.5 2140.2 1836 1879.2 5855.4 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 9264.6 3253.5 3330 2681.1 2140.2 1836 1879.2 5855.4 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 15638.4 W.
DEMAND FACTOR 0.97
TOTAL DEMAND LOAD 15120 W.
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: 6PP-DL MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : SEE NOTE-1 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 30 MAIN CIRCUIT BREAKER: 30 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
1 SPARE 675 675 1 20 100 1 675 * 706.5 1 100 20 1 706.5 706.5 SPARE 2
3 SPARE 693 693 1 20 100 1 693 * 972 1 100 20 1 972 972 SPARE 4
5 SPARE 562.5 562.5 2 20 100 1 562.5 * 675 1 100 20 2 675 675 SPARE 6
7 562.5 562.5 . 1 562.5 * 675 1 675 675 8
9 SPARE 477 477 2 20 100 1 477 * 1026 1 100 20 2 1026 1026 SPARE 10
11 477 477 . 1 477 * 1026 1 1026 1026 12
13 SPARE 1251 1251 1 20 100 1 1251 * 445.5 1 100 20 1 445.5 445.5 SPARE 14
15 SPARE 405 405 2 20 100 1 405 * 1152 1 100 20 2 1152 1152 SPARE 16
17 405 405 . 1 405 * 1152 1 1152 1152 18
19 SPARE 1026 1026 2 20 100 1 1026 * 846 1 100 20 2 846 846 SPARE 20
21 1026 1026 . 1 1026 * 846 1 846 846 22
23 SPARE 450 450 1 20 100 1 450 * 630 1 100 20 1 630 630 SPARE 24
25 SPARE 810 810 1 20 100 0.6 486 * 100 20 2 0 SPARE 26
27 SPARE 0 1 20 100 * 0 28
29 SPARE 0 1 20 100 * 777.6 0.6 100 20 1 1296 1296 SPARE 30
31 32
33 34
35 36
37 38
39 40
41 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 8820 4324.5 2601 1894.5 2673 3996 4779 11448 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 8496 4000.5 2601 1894.5 2673 3996 4260.6 10929.6 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 20268 W.
DEMAND FACTOR 0.96
TOTAL DEMAND LOAD 19425.6 W.
FOR 1 PH PANEL
BACK
SELECT PH R
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: 4PP-WLF MOUNTING : SURFACE 220/127 V,3PH,5W,60HZ.
LOCATION : SEE NOTE-1 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 30 MAIN CIRCUIT BREAKER: 70 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 FUME HOOD 675 675 1 20 100 1 675 * 706.5 1 100 20 1 706.5 706.5 ANALYTICAL 2 3X4
3X4 3 CHEM. ANALYZER 693 693 1 20 100 1 693 * 972 1 100 20 1 972 972 STIRRER 4 3X4
3X4 5 BENCH TOP 562.5 562.5 2 20 100 1 562.5 * 675 1 100 20 2 675 675 REF 6 3X4
7 562.5 562.5 . 1 562.5 * 675 1 675 675 8 3X4
3X4 9 REF 477 477 2 20 100 1 477 * 1026 1 100 20 2 1026 1026 LAB OVEN 10 3X4
11 477 477 . 1 477 * 1026 1 1026 1026 12 3X4
3X4 13 TOUCH MIXER 1251 1251 1 20 100 1 1251 * 445.5 1 100 20 1 445.5 445.5 CELL COUNTER 14 3X4
3X4 15 CENTRIFUGE 405 405 2 20 100 1 405 * 1152 1 100 20 2 1152 1152 REF 16 3X4
17 405 405 . 1 405 * 1152 1 1152 1152 18 3X4
3X4 19 MICROWAVE 1026 1026 2 20 100 1 1026 * 846 1 100 20 2 846 846 WATER BATH 20 3X4
21 1026 1026 . 1 1026 * 846 1 846 846 22 3X4
3X4 23 DRY BATH 450 450 1 20 100 1 450 * 630 1 100 20 1 630 630 COLLECTOR 24 3X4
3X4 25 SOCKETS 810 810 1 20 100 0.6 486 * 100 20 2 0 SPARE 26 3X4
27 SPARE 0 1 20 100 * 0 28 3X4
29 SPARE 0 1 20 100 * 777.6 0.6 100 20 1 1296 1296 SOCKETS 30 3X4
SUB.TOTAL CON.LOAD(W) 8820 4324.5 2601 1894.5 2673 3996 4779 11448 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 8496 4000.5 2601 1894.5 2673 3996 4260.6 10929.6 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 20268 W.
DEMAND FACTOR 0.96
TOTAL DEMAND LOAD 19425.6 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.714 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.40 %
voltage
Accumulated Voltage drop 6.714 + 6.814 = 13.527 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 3 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.595 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.17 %
voltage
Accumulated Voltage drop 5.595 + 6.814 = 12.409 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.035 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.05 %
voltage
Accumulated Voltage drop 5.035 + 6.814 = 11.849 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 6.75 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.518 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.52 %
voltage
Accumulated Voltage drop 2.518 + 6.814 = 9.331 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 4.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.678 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.35 %
voltage
Accumulated Voltage drop 1.678 + 6.814 = 8.492 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 13.50 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.357 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.70 %
voltage
Accumulated Voltage drop 3.357 + 6.814 = 10.171 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 34.20 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.284 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.31 %
voltage
Accumulated Voltage drop 6.284 + 6.814 = 13.098 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 36.90 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.650 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.18 %
voltage
Accumulated Voltage drop 5.650 + 6.814 = 12.464 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 34.20 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.713 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.98 %
voltage
Accumulated Voltage drop 4.713 + 6.814 = 11.527 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 17.10 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.300 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.31 %
voltage
Accumulated Voltage drop 6.300 + 6.814 = 13.114 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 20.25 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.423 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.92 %
voltage
Accumulated Voltage drop 4.423 + 6.814 = 11.237 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 23.40 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.408 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.71 %
voltage
Accumulated Voltage drop 3.408 + 6.814 = 10.221 Volts
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
5X4 1 EF-15 1440 1440 3 20 100 0.8 1152 * 684 0.8 100 20 3 855 855 EF-16 2 5X4
3 1440 1440 . 0.8 1152 * 684 0.8 855 855 4
5 1440 1440 . 0.8 1152 * 684 0.8 855 855 6
3X4 7 SF-1 1674 1674 1 20 100 0.8 1339.2 * 684 0.8 100 20 3 855 855 EF-16A 8 5X4
3X4 9 SF-2 1674 1674 1 20 100 0.8 1339.2 * 684 0.8 855 855 10
3X4 11 SF-3 1260 1260 1 20 100 0.8 1008 * 684 0.8 855 855 12
3X4 13 SF-4 1260 1260 1 20 100 0.8 1008 * 100 20 3 SPARE 14
3X4 15 SF-5 1260 1260 1 20 100 0.8 1008 * 16
3X4 17 SF-6 1260 1260 1 20 100 0.8 1008 * 18
19 SPARE 1 20 100 0.8 * 100 20 3 SPARE 20
21 SPARE 1 20 100 0.8 * 22
23 SPARE 1 20 100 0.8 * 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 12708 4374 4374 3960 1710 1710 1710 5130 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 10166.4 3499.2 3499.2 3168 1368 1368 1368 4104 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 17838 W.
DEMAND FACTOR 0.80
TOTAL DEMAND LOAD 14270.4 W.
FOR 1 PH PANEL
BACK
SELECT PH R
PROJECT NAME: UNIVERSITY OF DAMMAM
BUILDING NAME: FACULTY OF ENGINEERING
PANEL NAME: PP-TF MOUNTING : SURFACE 480/277 V,3PH,5W,60HZ.
LOCATION : ROOM#G-112 TRIP FRAME
FEEDER ENTRY: TOP NO.OF WAYS : 42 MAIN CIRCUIT BREAKER: 100 100 AMP.
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
5X6 1 EF-10 1440 1440 3 30 100 1 1440 * 1440 1 100 30 3 1440 1440 EF-11 2 5X6
3 1440 1440 . 1 1440 * 1440 1 1440 1440 4
5 1440 1440 . 1 1440 * 1440 1 1440 1440 6
5X6 7 EF-9 1440 1440 3 30 100 1 1440 * 1674 1 100 30 1 1674 1674 EF-13 8 3X6
9 1440 1440 . 1 1440 * 1260 1 100 20 1 1260 1260 EF-14 10 3X4
11 1440 1440 . 1 1440 * 855 1 100 20 1 855 855 EF-12 12 3X4
13 SPARE 0 1 20 100 * 3899.7 1 100 30 3 3899.7 3899.7 DISTILLER UNIT 14 5X6
15 SPARE 0 1 20 100 * 3899.7 1 3899.7 3899.7 16
3x4 17 EF-8 855 855 1 20 100 1 855 * 3899.7 1 3899.7 3899.7 18
5X16 19 EWH-2 5400 5400 3 40 100 1 5400 * 855 1 100 20 3 855 855 BOOSTER PUMP 20 5X4
21 5400 5400 . 1 5400 * 855 1 855 855 22
23 5400 5400 . 1 5400 * 855 1 855 855 24
5X10 25 EWH-4 3600 3600 3 30 100 1 3600 * 100 30 3 0 SPARE 26
27 3600 3600 . 1 3600 * 0 28
29 3600 3600 . 1 3600 * 0 30
31 SPARE 0 1 20 100 * 100 20 3 855 855 SPARE 32
3x4 33 CP-3,CP-4 711 711 1 20 100 0.8 568.8 * 855 855 34
35 SPARE 0 1 20 100 * 855 855 36
5X4 37 BOOSTER PUMP 855 855 3 20 100 1 855 * 100 40 3 0 SPARE 38
39 855 855 . 1 855 * 0 40
41 855 855 . 1 855 * 0 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 39771 12735 13446 13590 8723.7 8309.7 7904.7 24938.1 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 39628.8 12735 13303.8 13590 7868.7 7454.7 7049.7 22373.1 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 64709.1 W.
DEMAND FACTOR 0.96
TOTAL DEMAND LOAD 62001.9 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 16.20 No.of cables/ circuits in group 6 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.802 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.17 %
voltage
Accumulated Voltage drop 0.802 + 6.814 = 7.616 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.90 No.of cables/ circuits in group 6 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.821 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.17 %
voltage
Accumulated Voltage drop 0.821 + 6.814 = 7.634 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 31.50 No.of cables/ circuits in group 3 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 8.447 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.76 %
voltage
Accumulated Voltage drop 8.447 + 6.814 = 15.260 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 31.50 No.of cables/ circuits in group 3 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.962 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.24 %
voltage
Accumulated Voltage drop 5.962 + 6.814 = 12.776 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 31.50 No.of cables/ circuits in group 3 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.956 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.45 %
voltage
Accumulated Voltage drop 6.956 + 6.814 = 13.770 Volts
ARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
GR. DIRECT
Thermal resistivity of soil 1.2 air temp.(deg.C) 45 Installation Method
LAID
Ground Temp. ( deg.C) 35 Depth of laying (cm) 80
Power (KW) 268.72 No.of cables/ circuits in group 4 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. 1
Derating factor for variation in burial depth 0.96
Derating factor for variation in thermal resistivity 1
Derating factor for variation in air temp. N/A
Derating factor for grouping 0.63
Overall derating factor 0.6048
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.905 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.23 %
voltage
Accumulated Voltage drop 5.905 + 0.393 = 6.297 Volts
= 16.7 KA
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : DRY TYPE TRANSFORMER PARAMETERS
Transformer 112.5 KVA Z% = 5.5 % FREQ. 60 Hz.
Utilized high voltage 0.48 KV H.V Psc (MVA) 30 MVA
UTILIZED VOLTAGE 220 VOLT
Primary impedence (Zp) =( KV² ) / MVA = 0.0076800 Ω
X/R= 6 Z= ( Rt √ 37)
Rt = 0.0041553 Ω
Xt = 0.0249317 Ω
Resistance ( R ) Ω Reactance ( X ) Ω
1 LP-1CE 8275.5 2709 2376 3191 8275.5 2709 2376 3191 9195 9195 9195 1.00 24 30 100 4 10 50 2.22 1.0
2 LP-2 6772.5 1989 2295 2489 6772.5 1989 2295 2489 7525 7525 7525 1.00 20 30 100 4 10 10 0.52 3.2
3 LP-3 16330.5 5778 5126 5427 16330.5 5778 5126 5427 18145 18145 18145 1.00 48 60 100 4 25 60 2.15 1.8
4 LP-4 11083.5 3902 2984 4199 11083.5 3902 2984 4199 12315 12315 12315 1.00 32 40 100 4 16 60 2.27 1.3
5 PP-1CE 30285 10059 10230 9996 22569 7873 7526 7170 33650 25077 25077 0.75 66 90 100 4 50 10 0.44 4.4
6 PP-AC 2484 738 909 837 2484 738 909 837 2760 2760 2760 1.00 7 30 100 4 10 10 0.31 3.2
7 SMF-01 3700 1233 1233 1233 0 0 0 0 4111 0 0 0.00 0 30 100 1 6 10 0.18 2.4
8 0 0 ##
9 0 0 ##
10 0 0 ##
11 0 0 ##
12 0 0 ##
13 0 0 ##
14 0 0 ##
15 0 0 ##
16 0 0 ##
17 0 0 ##
18 0 0 ##
19 0 0 ##
20 0 0 ##
21 0 0 ##
22 0 0 ##
23 0 0 ##
24 0 0 ##
25 0 0 ##
26 0 0 ##
27 0 0 ##
28 0 0 ##
29 0 0 ##
30 0 0 ##
31 0 0 ##
32 0 0 ##
33 0 0 ##
34 0 0 ##
35 0 0 ##
36 0 0 ##
37 0 0 ##
38 0 0 ##
39 0 0 ##
40 0 0 ##
26408 25152 27371 22989 21215 23311 ##
TOTAL 78931 67515 87701 75017 75017 0.86 ###
33.46% 31.87% 34.68% 34.05% 31.42% 34.53%
CONNECTED LOAD 78.9 KW ###
DEMAND LOAD 67.5 KW
DIVERSITY FACTOR = 0.9
DIVERSIFIED LOAD 60.8 KW WINTER
DIVERSIFIED LOAD 60.8 KW SUMMER
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 8.28 No.of cables/ circuits in group 6 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.468 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.03 %
voltage
Accumulated Voltage drop 4.468 + 0.407 = 4.875 Volts
= 1.0 KA
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 6.77 No.of cables/ circuits in group 6 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.731 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.33 %
voltage
Accumulated Voltage drop 0.731 + 0.407 = 1.138 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 16.33 No.of cables/ circuits in group 6 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.328 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.97 %
voltage
Accumulated Voltage drop 4.328 + 0.407 = 4.734 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.08 No.of cables/ circuits in group 6 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.577 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.08 %
voltage
Accumulated Voltage drop 4.577 + 0.407 = 4.984 Volts
WIRE CT. CONN. CONNECTED LOAD CIRCUIT BREAKER DEM. DEMAND R Y B DEMAND DEM. CIRCUIT BREAKER CONNECTED LOAD CONN. CT. WIRE
SIZE NO. DESCRIPTION LOAD/CT PH."R" PH."Y" PH."B" NO. OF TRIP FRAME FAC. LOAD/PH LOAD/PH FAC. FRA. TRI. NO.OF PH."R" PH."Y" PH."B" LOAD/CT DESCRIPTION NO. SIZE
mm2 WATT WATT WATT WATT POLES AMP. AMP. WATT WATT AMP. AMP. POLES WATT WATT WATT WATT mm2
3X4 1 SOCKETS 810 810 1 20 100 1 810 * 388.8 0.6 100 20 1 648 648 SOCKETS 2 3X4
3X4 3 SOCKETS 486 486 1 20 100 0.6 291.6 * 388.8 0.6 100 20 1 648 648 SOCKETS 4 3X4
3X4 5 SOCKETS 486 486 1 20 100 0.6 291.6 * 388.8 0.6 100 20 1 648 648 SOCKETS 6 3X4
3X4 7 SOCKETS 486 486 1 20 100 0.6 291.6 * 291.6 0.6 100 20 1 486 486 SOCKETS 8 3X4
3X4 9 SOCKETS 810 810 1 20 100 0.6 486 * 291.6 0.6 100 20 1 486 486 SOCKETS 10 3X4
3X4 11 SOCKETS 972 972 1 20 100 0.6 583.2 * 291.6 0.6 100 20 1 486 486 SOCKETS 12 3X4
3X4 13 SOCKETS 324 324 1 20 100 0.6 194.4 * 800 0.8 100 20 1 1000 1000 E.W.H-1 14 3X4
3X4 15 SOCKETS 486 486 1 20 100 0.6 291.6 * 800 0.8 100 20 1 1000 1000 E.W.H-1 16 3X4
3X4 17 SOCKETS 648 648 1 20 100 0.6 388.8 * 583.2 0.6 100 20 1 972 972 SOCKETS 18 3X4
3X4 19 E.W.H-2 1500 1500 1 20 100 0.8 1200 * 450 1 100 20 1 450 450 SOCKETS 20 3X4
3X4 21 E.W.H-2 1500 1500 1 20 100 0.8 1200 * 450 1 100 20 1 450 450 SOCKETS 22 3X4
3X4 23 E.W.H-2 1500 1500 1 20 100 0.8 1200 * 864 0.8 100 20 1 1080 1080 H.D. 24 3X4
3X4 25 E.W.H-2 1500 1500 1 20 100 0.8 1200 * 864 0.8 100 20 1 1080 1080 H.D. 26 3X4
3X4 27 E.W.H-1 1000 1000 1 20 100 0.8 800 * 864 0.8 100 20 1 1080 1080 H.D. 28 3X4
3X4 29 H.D. 1080 1080 1 20 100 0.8 864 * 450 1 100 20 1 450 450 SOCKETS 30 3X4
31 500 500 1 500 ######### 315 1 100 20 1 315 315 ELEC DOOR 32 3X4
BARRIER GATE
5x4 33 500 500 3 20 100 1 500 194.4 0.6 100 20 1 324 324 SOCKETS 34 3X4
CONTROL
35 500 500 1 500 * 194.4 0.6 100 20 1 324 324 SOCKETS 36 3X4
37 1000 1000 3 30 100 0.6 600 * 864 0.8 100 20 1 1080 1080 H.D. 38
5X6 39 STAGE CURTAIN 1000 1000 . 30 100 0.6 600 * 864 0.8 100 20 1 1080 1080 H.D. 40
41 1000 1000 . 30 100 0.6 600 * 450 1 100 20 1 450 450 PROJECTOR EQ. 42
43 44
45 46
47 48
SUB.TOTAL CON.LOAD(W) 18088 6120 5782 6186 5059 5068 4410 14537 SUB.TOTAL CONN.LOAD(W)
SUB.TOTAL DEM.LOAD(W) 13392.8 4796 4169.2 4427.6 3973.4 3852.8 3222 11048.2 SUB.TOTAL DEM.LOAD(W)
TOTAL CONNECTED LOAD 32625 W.
DEMAND FACTOR 0.75
TOTAL DEMAND LOAD 24441 W.
Project Name : UNIVERSITY OF DAMMAM Date : 28/05/2013
Project No. : 903 Computed By : ENGG ROY RAPHAEL
Building Name : FACULTY OF ENGINEERING Checked By : ENGG SAYE
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 2.48 No.of cables/ circuits in group 6 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.55
Overall derating factor 0.55
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.268 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.12 %
voltage
Accumulated Voltage drop 0.268 + 0.407 = 0.675 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 0.00 No.of cables/ circuits in group 1 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 0.407 = 0.407 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 18.23 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.742 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.20 %
voltage
Accumulated Voltage drop 5.742 + 6.297 = 12.039 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 49.92 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.042 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.84 %
voltage
Accumulated Voltage drop 4.042 + 6.297 = 10.340 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 41.19 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.335 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.69 %
voltage
Accumulated Voltage drop 3.335 + 6.297 = 9.633 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 41.19 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.003 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.04 %
voltage
Accumulated Voltage drop 5.003 + 6.297 = 11.300 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 49.92 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.074 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.47 %
voltage
Accumulated Voltage drop 7.074 + 6.297 = 13.371 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method PIPES IN AIR
Power (KW) 0.00 No.of cables/ circuits in group 1 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 6.297 = 6.297 Volts
ARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
GR. DIRECT
Thermal resistivity of soil 1.2 air temp.(deg.C) 45 Installation Method
LAID
Ground Temp. ( deg.C) 35 Depth of laying (cm) 80
Power (KW) 156.66 No.of cables/ circuits in group 2 Voltage (V) 480
DERATING FACTORS
Derating factor for variation in ground temp. 1
Derating factor for variation in burial depth 0.96
Derating factor for variation in thermal resistivity 1
Derating factor for variation in air temp. N/A
Derating factor for grouping 0.87
Overall derating factor 0.8352
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.113 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.23 %
voltage
Accumulated Voltage drop 1.113 + 0.393 = 1.506 Volts
ARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
GR. DIRECT
Thermal resistivity of soil 1.2 air temp.(deg.C) 45 Installation Method
LAID
Ground Temp. ( deg.C) 35 Depth of laying (cm) 80
Power (KW) 0.75 No.of cables/ circuits in group 1 Voltage (V) 220
DERATING FACTORS
Derating factor for variation in ground temp. 1
Derating factor for variation in burial depth 0.97
Derating factor for variation in thermal resistivity 1
Derating factor for variation in air temp. N/A
Derating factor for grouping N/A
Overall derating factor 0.97
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.135 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.06 %
voltage
Accumulated Voltage drop 0.135 + 6.297 = 6.433 Volts
X/R= 6 Z= ( Rt √ 37)
Rt = 0.0014560 Ω
Xt = 0.0087360 Ω
Resistance ( R ) Ω Reactance ( X ) Ω
0.0014560 0.0087360
X/R= 6 Z= ( Rt √ 37)
Rt = 0.0150161 Ω
Xt = 0.0900967 Ω
Resistance ( R ) Ω Reactance ( X ) Ω
0.0150161 0.0900967
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 0.00 No.of cables/ circuits in group 3 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.000 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.00 %
voltage
Accumulated Voltage drop 0.000 + 0.000 = 0.000 Volts
0.0233000 0.0007850
TOTAL 0.0233000 0.0007850
Total Impedance Z =√ (R² + X²)
=√ ( 0.003929
= 0.011349 )² = 0.014 Ω ohm
)² + (0.0233132
= 9.4 KA
PROJECT-Faculty Of Engineering Part-1,
King Faizal University -Dammam
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 125.61 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.180 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.31 %
voltage
Accumulated Voltage drop 1.180 + 5.388 = 6.568 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 23.27 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.410 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.90 %
voltage
Accumulated Voltage drop 3.410 + 6.568 = 9.978 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.61 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.409 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.37 %
voltage
Accumulated Voltage drop 1.409 + 6.568 = 7.976 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 19.68 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.098 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.29 %
voltage
Accumulated Voltage drop 1.098 + 6.568 = 7.666 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.186 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.36 %
voltage
Accumulated Voltage drop 5.186 + 6.568 = 11.753 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.690 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.71 %
voltage
Accumulated Voltage drop 2.690 + 6.568 = 9.258 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.963 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.25 %
voltage
Accumulated Voltage drop 0.963 + 6.568 = 7.531 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 16.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.345 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.62 %
voltage
Accumulated Voltage drop 2.345 + 6.568 = 8.913 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 46.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.333 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.93 %
voltage
Accumulated Voltage drop 7.333 + 6.568 = 13.901 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 125.25 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.002 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.53 %
voltage
Accumulated Voltage drop 2.002 + 5.388 = 7.389 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 26.55 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.324 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.61 %
voltage
Accumulated Voltage drop 2.324 + 7.389 = 9.713 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 23.25 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.453 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.38 %
voltage
Accumulated Voltage drop 1.453 + 7.389 = 8.843 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 21.20 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.856 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.49 %
voltage
Accumulated Voltage drop 1.856 + 7.389 = 9.245 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 37.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.636 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.75 %
voltage
Accumulated Voltage drop 6.636 + 7.389 = 14.025 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 18.50 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.843 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.49 %
voltage
Accumulated Voltage drop 1.843 + 7.389 = 9.233 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 241.29 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.921 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.77 %
voltage
Accumulated Voltage drop 2.921 + 5.388 = 8.308 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 25.20 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.363 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.62 %
voltage
Accumulated Voltage drop 2.363 + 8.308 = 10.671 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.33 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.507 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.92 %
voltage
Accumulated Voltage drop 3.507 + 8.308 = 11.815 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 49.18 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.886 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.50 %
voltage
Accumulated Voltage drop 1.886 + 8.308 = 10.194 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.034 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.06 %
voltage
Accumulated Voltage drop 4.034 + 8.308 = 12.342 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 37.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.239 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.85 %
voltage
Accumulated Voltage drop 3.239 + 8.308 = 11.547 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 8.308 = 15.481 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 8.308 = 15.481 Volts
MAIN LT
Upstream Switchboard LOAD MDB-2
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 957.40 No.of cables/ circuits in group 5 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.520 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.72 %
voltage
Accumulated Voltage drop 6.520 + 0.000 = 6.520 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 302.10 No.of cables/ circuits in group 2 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.81
Overall derating factor 0.81
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.118 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.29 %
voltage
Accumulated Voltage drop 1.118 + 6.520 = 7.638 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 23.54 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.450 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.91 %
voltage
Accumulated Voltage drop 3.450 + 7.638 = 11.088 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 33.90 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.891 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.50 %
voltage
Accumulated Voltage drop 1.891 + 7.638 = 9.530 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 86.39 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.709 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.45 %
voltage
Accumulated Voltage drop 1.709 + 7.638 = 9.347 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 18.16 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.013 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.27 %
voltage
Accumulated Voltage drop 1.013 + 7.638 = 8.652 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 14.99 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.987 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.79 %
voltage
Accumulated Voltage drop 2.987 + 7.638 = 10.626 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 18.50 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.162 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.10 %
voltage
Accumulated Voltage drop 4.162 + 7.638 = 11.801 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 14.99 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.375 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.89 %
voltage
Accumulated Voltage drop 3.375 + 7.638 = 11.013 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 36.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.977 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.84 %
voltage
Accumulated Voltage drop 6.977 + 7.638 = 14.615 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.99 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 8.372 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.20 %
voltage
Accumulated Voltage drop 8.372 + 7.638 = 16.010 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 24.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.261 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.38 %
voltage
Accumulated Voltage drop 5.261 + 7.638 = 12.899 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 24.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.261 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.38 %
voltage
Accumulated Voltage drop 5.261 + 7.638 = 12.899 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 4.95 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.850 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.75 %
voltage
Accumulated Voltage drop 2.850 + 7.638 = 10.489 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 13.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.472 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.18 %
voltage
Accumulated Voltage drop 4.472 + 7.638 = 12.110 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 13.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.472 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.18 %
voltage
Accumulated Voltage drop 4.472 + 7.638 = 12.110 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 360.79 No.of cables/ circuits in group 3 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.963 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.25 %
voltage
Accumulated Voltage drop 0.963 + 6.520 = 7.483 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 25.38 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.221 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.58 %
voltage
Accumulated Voltage drop 2.221 + 7.483 = 9.705 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 26.83 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.348 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.62 %
voltage
Accumulated Voltage drop 2.348 + 7.483 = 9.831 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 86.39 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.709 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.45 %
voltage
Accumulated Voltage drop 1.709 + 7.483 = 9.192 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 13.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.726 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.19 %
voltage
Accumulated Voltage drop 0.726 + 7.483 = 8.209 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 91.79 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.188 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.37 %
voltage
Accumulated Voltage drop 5.188 + 7.483 = 12.671 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 70.19 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.262 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.38 %
voltage
Accumulated Voltage drop 5.262 + 7.483 = 12.745 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.303 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.87 %
voltage
Accumulated Voltage drop 3.303 + 7.483 = 10.786 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.752 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.99 %
voltage
Accumulated Voltage drop 3.752 + 7.483 = 11.235 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.752 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.99 %
voltage
Accumulated Voltage drop 3.752 + 7.483 = 11.235 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 331.52 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.185 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.84 %
voltage
Accumulated Voltage drop 3.185 + 6.520 = 9.705 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 20.70 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.034 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.80 %
voltage
Accumulated Voltage drop 3.034 + 9.705 = 12.739 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 28.34 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.480 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.65 %
voltage
Accumulated Voltage drop 2.480 + 9.705 = 12.186 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 37.35 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.269 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.86 %
voltage
Accumulated Voltage drop 3.269 + 9.705 = 12.974 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 30.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.812 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.74 %
voltage
Accumulated Voltage drop 2.812 + 9.705 = 12.517 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.690 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.23 %
voltage
Accumulated Voltage drop 4.690 + 9.705 = 14.395 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.221 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.11 %
voltage
Accumulated Voltage drop 4.221 + 9.705 = 13.926 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.191 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.63 %
voltage
Accumulated Voltage drop 6.191 + 9.705 = 15.896 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 8.308 = 15.481 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 8.308 = 15.481 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 8.308 = 15.481 Volts
MAIN LT
Upstream Switchboard LOAD MDB-3
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 1 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 495.68 No.of cables/ circuits in group 2 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.81
Overall derating factor 0.81
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.282 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.86 %
voltage
Accumulated Voltage drop 3.282 + 0.466 = 3.748 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 123.53 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.880 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.49 %
voltage
Accumulated Voltage drop 1.880 + 3.748 = 5.628 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 21.06 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.307 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.87 %
voltage
Accumulated Voltage drop 3.307 + 5.628 = 8.936 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.64 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.828 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.48 %
voltage
Accumulated Voltage drop 1.828 + 5.628 = 7.456 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
CABLE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method
TRENCH
Ground Temp. ( deg.C) ------ Depth of laying (cm) ------
Power (KW) 430.66 No.of cables/ circuits in group 3 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.919 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.24 %
voltage
Accumulated Voltage drop 0.919 + 5.628 = 6.548 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.66 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.936 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.25 %
voltage
Accumulated Voltage drop 0.936 + 5.628 = 6.564 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 7.51 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.754 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.25 %
voltage
Accumulated Voltage drop 4.754 + 5.628 = 10.383 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.674 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.49 %
voltage
Accumulated Voltage drop 5.674 + 5.628 = 11.303 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.690 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.23 %
voltage
Accumulated Voltage drop 4.690 + 5.628 = 10.318 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 4.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.097 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.55 %
voltage
Accumulated Voltage drop 2.097 + 5.628 = 7.725 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 6.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.802 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.00 %
voltage
Accumulated Voltage drop 3.802 + 5.628 = 9.431 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 37.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.373 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.94 %
voltage
Accumulated Voltage drop 7.373 + 5.628 = 13.002 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 98.41 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.872 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.49 %
voltage
Accumulated Voltage drop 1.872 + 3.748 = 5.620 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 20.32 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.352 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.67 %
voltage
Accumulated Voltage drop 6.352 + 5.620 = 11.973 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.60 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.875 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.28 %
voltage
Accumulated Voltage drop 4.875 + 5.620 = 10.496 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
CABLE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method
TRENCH
Ground Temp. ( deg.C) ------ Depth of laying (cm) ------
Power (KW) 430.66 No.of cables/ circuits in group 3 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping 0.7
Overall derating factor 0.7
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.919 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.24 %
voltage
Accumulated Voltage drop 0.919 + 5.620 = 6.540 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 16.25 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.647 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.17 %
voltage
Accumulated Voltage drop 0.647 + 5.620 = 6.268 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 30.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.174 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.174 + 5.620 = 12.794 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 18.50 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.161 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.36 %
voltage
Accumulated Voltage drop 5.161 + 5.620 = 10.782 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 276.38 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.068 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.81 %
voltage
Accumulated Voltage drop 3.068 + 3.748 = 6.817 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.14 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.076 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.55 %
voltage
Accumulated Voltage drop 2.076 + 6.817 = 8.893 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.14 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.076 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.55 %
voltage
Accumulated Voltage drop 2.076 + 6.817 = 8.893 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 35.33 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.112 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.56 %
voltage
Accumulated Voltage drop 2.112 + 6.817 = 8.929 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 18.50 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.793 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.26 %
voltage
Accumulated Voltage drop 4.793 + 6.817 = 11.609 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 15.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.628 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.48 %
voltage
Accumulated Voltage drop 5.628 + 6.817 = 12.444 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 3 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 30.01 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.174 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.174 + 6.817 = 13.991 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 6.817 = 13.989 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 6.817 = 13.989 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 45.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.173 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.89 %
voltage
Accumulated Voltage drop 7.173 + 6.817 = 13.989 Volts
MAIN LT
Upstream Switchboard LOAD EMDB
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 200.05 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.345 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.35 %
voltage
Accumulated Voltage drop 1.345 + 0.466 = 1.811 Volts
= 46.2 KA
PROJECT-Faculty Of Engineering Part-1,
King Faizal University -Dammam
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 43.83 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.875 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.81 %
voltage
Accumulated Voltage drop 6.875 + 1.811 = 8.686 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 8.69 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.711 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.71 %
voltage
Accumulated Voltage drop 2.711 + 8.686 = 11.397 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 4.64 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.725 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.19 %
voltage
Accumulated Voltage drop 0.725 + 8.686 = 9.411 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 8.50 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.186 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.84 %
voltage
Accumulated Voltage drop 3.186 + 8.686 = 11.872 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.07 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.398 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.89 %
voltage
Accumulated Voltage drop 3.398 + 8.686 = 12.084 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.09 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.256 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.12 %
voltage
Accumulated Voltage drop 4.256 + 8.686 = 12.942 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 3.56 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.669 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.44 %
voltage
Accumulated Voltage drop 1.669 + 8.686 = 10.355 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 83.39 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.730 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.77 %
voltage
Accumulated Voltage drop 6.730 + 1.811 = 8.541 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 10.71 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.507 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.66 %
voltage
Accumulated Voltage drop 2.507 + 8.541 = 11.048 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.94 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.326 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.61 %
voltage
Accumulated Voltage drop 2.326 + 8.541 = 10.867 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 9.77 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.810 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.00 %
voltage
Accumulated Voltage drop 3.810 + 8.541 = 12.351 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 22.79 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.849 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.75 %
voltage
Accumulated Voltage drop 2.849 + 8.541 = 11.390 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 7.79 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.645 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.96 %
voltage
Accumulated Voltage drop 3.645 + 8.541 = 12.186 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.99 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.765 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.99 %
voltage
Accumulated Voltage drop 3.765 + 1.811 = 5.577 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 11.99 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.765 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.99 %
voltage
Accumulated Voltage drop 3.765 + 1.811 = 5.577 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 36.74 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.164 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.36 %
voltage
Accumulated Voltage drop 5.164 + 1.811 = 6.976 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 8.82 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.065 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.54 %
voltage
Accumulated Voltage drop 2.065 + 6.976 = 9.040 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 4.64 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 1.087 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.29 %
voltage
Accumulated Voltage drop 1.087 + 6.976 = 8.063 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 7.79 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.038 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.54 %
voltage
Accumulated Voltage drop 2.038 + 6.976 = 9.013 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 6.37 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 2.486 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.65 %
voltage
Accumulated Voltage drop 2.486 + 6.976 = 9.462 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 7.34 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 3.434 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.90 %
voltage
Accumulated Voltage drop 3.434 + 6.976 = 10.410 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 1.51 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.708 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.19 %
voltage
Accumulated Voltage drop 0.708 + 1.811 = 2.519 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 32.40 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 6.213 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.64 %
voltage
Accumulated Voltage drop 6.213 + 1.811 = 8.025 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 36.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 7.630 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 2.01 %
voltage
Accumulated Voltage drop 7.630 + 8.025 = 15.655 Volts
MAIN LT
Upstream Switchboard LOAD MCC SW
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 25.76 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 5.359 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.41 %
voltage
Accumulated Voltage drop 5.359 + 0.466 = 5.825 Volts
= 2.9 KA
PROJECT-Faculty Of Engineering Part-1,
King Faizal University -Dammam
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 25.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.981 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.31 %
voltage
Accumulated Voltage drop 4.981 + 5.825 = 10.806 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 25.00 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.981 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.31 %
voltage
Accumulated Voltage drop 4.981 + 5.825 = 10.806 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 0.76 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.590 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.16 %
voltage
Accumulated Voltage drop 0.590 + 5.825 = 6.415 Volts
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
Thermal resistivity of soil ------ air temp.(deg.C) 40 Installation Method CABLE TRAY
Power (KW) 0.76 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. N/A
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity N/A
Derating factor for variation in air temp. 1
Derating factor for grouping N/A
Overall derating factor 1
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 0.590 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 0.16 %
voltage
Accumulated Voltage drop 0.590 + 5.825 = 6.415 Volts
MAIN LT
Upstream Switchboard LOAD LCP-EXT
PANEL
UNARM. CU
Selected Cable Type
CABLE
No. of cores 4 Insulation XLPE
GR. DIRECT
Thermal resistivity of soil 1.2 air temp.(deg.C) 40 Installation Method
LAID
Ground Temp. ( deg.C) 45 Depth of laying (cm) ------
Power (KW) 25.65 No.of cables/ circuits in group 1 Voltage (V) 380
DERATING FACTORS
Derating factor for variation in ground temp. 0.9
Derating factor for variation in burial depth N/A
Derating factor for variation in thermal resistivity 1
Derating factor for variation in air temp. N/A
Derating factor for grouping N/A
Overall derating factor 0.9
Voltage drop on feeder for 3-ph →√3*I*L*Z/(1000*no.of // cables) for 4.919 Volts
1-ph →2*I*L*Z/(1000*no.of // cables)
% Voltage drop volt.drop*100/ 1.29 %
voltage
Accumulated Voltage drop 4.919 + 0.466 = 5.385 Volts
= 3.1 KA