Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 50

ASSET DETAILS AND CONDITION ASSESSMENT

Interchange Project
ASSET INFORMATION
Interchange Area Z53-111 Assessment of Irrigation system

S/N Equipment Asset Description

Specifications
Brand: Grundfos
RPM - 3500 /3 Phase /60 Hz
Type: CSP - 300 /3
Vertical high pressure U: 230 V/380Y
1 Q min: 3526
Pump(2 units) H (m): 64.5 - 81.8
Volts :220-380-440V

P2
- 5.50 KW

Specifications
Brand:AQUASYSTEM
PRESSURE TANK
2
(1 UNIT)
Max.Press. 10.0 bar
Test Press. 14.3 bar
Temp.range - 10C/+100 C
Specifications
Flow Meter (
Brand:SENSUS
1 UNIT)
Typ WP - Dynamc 100
Qn - 230 m³/h

Specifications
Brand - PEDROLLO
Q : 50 - 450
H : 51.5 m
3 Phase / 4 kw / 5.5 HP / 60HZ
S1 : 3450 min
Volt : 220V
Centrifugal Pump
Amp: 20.5
( 1 UNIT)

Specifications
Brand : LG WILSON
Model : P50 - 3
Rated Voltage : 220/127
Phase : 3
Generator ( Rated Frequency : 60 HZ
3
1 UNIT) Rated power : 56.30 KVA /45 KW
50.00 KVA / 40 KW
Rated RPM : 1800
Specifications
HUNTER ACC
Brand:HUNTER
( 1 UNIT)
ACC CONTROLLER

Specifications
Pump Controller
panel Brand:HI - TECH
( 1 UNIT)

Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 32 UNITS)
HUNTER for decoder
Specifications
Gate Valve
Brand:PEGLER for gate valve 2"
(1 UNIT)

Specifications
Gate Valve
Brand:PEGLER for gate valve 4"
(1 UNIT)

Specifications
Quick Coupler valve
Brand: HUNTER
(10 UNITS)
Potable water tank
Specifications
Units are buried
(6 UNITS)

Isolation Valve
Specifications
Units are buried
(7 UNITS)

Driplines and bubbler Specifications


Bubbler and Dripper
Dripper and bubbler Specifications
Dripline and dripper

Driplines Specifications
Dripline

Driplines Specifications
Dripline
Specifications
Pressure Switch Brand : Telemecanique
3 phase 3 kw 400v
1 phase 1.5 230v
(2 UNITS) 20A

Water Filter
Specifications
( 1 unit ) Brand : ARMAS
CONDITION ASSESSMENT REPORT
erchange Project
ET INFORMATION
ent of Irrigation system

Photo Comments

1.Pumps are dusty.


2.Need regular preventive
maintenance.
3.pumps have water leakage.
4.pump room lot of mud and dirt.
5.pressure gauge not working
properly it clogged.

1.Pressure gauge not working and


have water inside .
2.Unit are dusty
1.Unit are Dusty.
2.Need regular preventive
maintenance.

1.Pump is not working


2. Have electrical cable but not
connected in the float valve.
3. Unit are dusty.
4. Unit need regular preventive
maintenance.

1.Generator are dusty.


2. unit have diesel leakage in the
base plate.
3. Need regular preventive
maintenance.
4.Generator set are not working and
the electrical cable are
disconnected.
1.Unit indicate decoder alarm
2.Unit is dusty.
3.Need regular preventive
maintenance.

1. Electrical control pump panel is


dusty
2.Need regular preventive
maintenance.

1. Valve box lot of dust and garbage


inside.
2.Need regular preventive
maintenance.
3.1 unit of solenoid valve has water
leakage.
4.no water strainer install inside in
the valve box.
5.need gravel beddings for the
solenoid and gate valve.
6- Need to chek if its working durin
automatic operation
1.Gate valve no valve box.
2.Valve is buried.
3- not check yet if working or not

1.Gate valve no valve box.


2.Valve is buried.
3- not check yet if working or not

1. Unit are dusty.


2.need to clean and check it if work
properly.
1.water come from delivery tanker.
2.no pipe tube for monitoring the
water level
3.manual refilling of water.
4 Inside of water tank are dusty.
5.Need preventive maintenance
6.they used wooden stick for
measuring the water level.
7- need to check if any cracking or
leaking or disconeccted

1.No valve key for incase on /off the


valve.

1.For palm trees they use bubbler


and dripper.
2.tube pipe are damaged and
clogged it.
1.For tree they use dripperalso it
clogged
2.tube pipe are damaged and
clogged it.

1.Dripline are clogged.


2.mostly of dripline are damaged.

1.Dripline are clogged.


2.mostly of dripline are damaged.
1.Units are dusty.
2.Pressure gauge are not working
properly not same reading to other
pressure gauge.
3 out of calibration.

1.Units are dusty.


2.No battery for the controller.
3.Need regular preventive
maintenance.
4.Have water leakage in the body
filter.
5.Pressure gauge not working
during irrigation.
ASSET DETAILS AND CONDITION ASSESSMEN
Diriyah Interchange Project
ASSET INFORMATION
Interchange Area Z13-110 Assessment of Irrigation system

S/N Equipment Asset Description

Specifications
Brand: Grundfos
RPM - 3500 /3 Phase /60 Hz
Type: CSP - 300 /3
Vertical high pressure U: 230 V/380Y
1 Pump Q min: 3526
(2 units) H (m): 64.5 - 81.8
Volts :220-380-440V

P2
- 5.50 KW

Specifications
Brand: NEMA
PRESSURE TANK
2 Max.Press. 10.0
(1 UNIT)
bar
Test Press. 14.3 bar
Temp.range - 10C/+100 C
Water Filter
Specifications
( 1 unit ) Brand : ARMAS

Specifications
Flow meter (
Brand:SENSUS
1 UNIT)
Typ WP - Dynamc 100
Qn - 230 m³/h

Specifications
Brand : LG WILSON
Model : P50 - 3
Rated Voltage : 220/127
Phase : 3
Generator ( Rated Frequency : 60 HZ
3
1 UNIT) Rated power : 56.30 KVA /45 KW
50.00 KVA / 40 KW
Rated RPM : 1800
Specifications
HUNTER ACC
Brand:HUNTER
( 1 UNIT)
ACC CONTROLLER

Specifications
Pump Controller
panel Brand:HI - TECH
( 1 UNIT)

Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 39 UNITS)
HUNTER for decoder
Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 39 UNITS)
HUNTER for decoder

Specifications

Brand:PEGLER for gate valve 1"


Gate Valve HUNTER for solenoid valve
(1 UNIT) MAIS for valve box.
HUNTER for decoder

Specifications
Quick Coupler valve
Brand: HUNTER
(10 UNITS)
Potable water tank
Specifications
Units are buried
(4 UNITS)

Specifications
Pressure Switch Brand : Telemecanique
3 phase 3 kw 400v
1 phase 1.5 230v
(2 UNITS) 20A

Driplines and Dripper Specifications


Bubbler and Dripper
Dripper and bubbler Specifications
Dripline and dripper

Driplines Specifications
Dripline
AND CONDITION ASSESSMENT REPORT
iyah Interchange Project
ASSET INFORMATION
essment of Irrigation system

Photo Comments

1.Pumps are dusty.


2.One of the pump have water
leakage in the body.
3.need regular preventive
maintenance.
4.Pump surrounding in the body has
corroded due of continue water leak.

1.Unit are dusty.


1.Unit are Dusty.
2. The vent pipe is broken.
3.have water leakage in the lack
collar.
4.Need regular preventive
maintenance.
5.Have water leakage in the collar of
body filter.
6.the pressure gauge is not working
not same reading in the pump
pressure gauge.

1.Unit are Dusty.


2.Need regular preventive
maintenance.

1.Generator are dusty.


2. Unit have diesel leakage in the
base plate
3. Need regular preventive
maintenance.
1.Unit is dusty
2.Need regular preventive
maintenance

1. Electrical control pump panel is


dusty
2.Need regular preventive
maintenance.

1. Valve box lot of dust and garbage


inside.
2.valve no, 18 and #22 valve box
are broken and damaged.
3.need gravel beddings for the
solenoid and gate valve.
4.no water strainer install inside in
the valve box.
5- need to check if it working in
automatic mode during operation
1. Valve box lot of dust and garbage
inside.
2.need gravel beddings for the
solenoid and gate valve.
3.No water strainer install inside in
the valve box.
4. valve box are dusty.
5- need to check if it working in
automatic mode

1.No gravel bedding for the solenoid


and gate valve inside
2.Valve box are dusty.

1. Unit are dusty.


2.need to clean and check it if work
properly.
3- no key
1.water come from delivery tanker.
2.no pipe tube for monitoring the
water level
3.manual refilling of water.
4 Inside of water tank are dusty.
5.Need preventive maintenance
6.they used wooden stick for
measuring the water level.
7- need to check if any cracking or
leaking or disconeccted

1.Units are dusty need to clean.


2.Pressure gauge are not working
properly not same reading to other
pressure gauge.
3.Need regular preventive
maintenance.

1.For trees they used dripper.its


clogged
2.Tube pipe are damaged. And
clogged
1.For Palm tree they used dripper ,
need to replaced with bubblers
2.tube pipe are damaged and
clogged

1.Dripline are clogged.


2.mostly of dripline are damaged
and broken.
ASSET DETAILS AND CONDITION ASSESSMEN
Diriyah Farm Project
ASSET INFORMATION
Interchange Area Z63-110 Assessment of Irrigation system

S/N Equipment Asset Description

Specifications
Brand: Grundfos
RPM - 3500 /3 Phase /60 Hz
Type: CSP - 300 /3
Vertical high pressure U: 230 V/380Y
1 Pump Q min: 3526
(2 units) H (m): 64.5 - 81.8
Volts :220-380-440V

P2
- 5.50 KW

Specifications
Brand:AQUASYSTEM
PRESSURE TANK
2
(1 UNIT)
Max.Press. 10.0 bar
Test Press. 14.3 bar
Temp.range - 10C/+100 C
Water Filter
Specifications
( 2 units ) Brand : TECNIDRO

Specifications
Flow meter (
Brand:SENSUS
1 UNIT)
Typ WP - Dynamc 100
Qn - 230 m³/h

Specifications
Brand : LG WILSON
Model : P50 - 3
Rated Voltage : 220/127
Phase : 3
Generator ( Rated Frequency : 60 HZ
3
1 UNIT) Rated power : 56.30 KVA /45 KW
50.00 KVA / 40 KW
Rated RPM : 1800
Specifications
HUNTER ACC
Brand:HUNTER
( 1 UNIT)
ACC CONTROLLER

Specifications
Pump Electrical
Controller panel
Brand:HI - TECH
( 1 UNIT)

Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 15 UNITS)
HUNTER for decoder
Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 15 UNITS)
HUNTER for decoder

Specifications
Pressure Switch Brand : Telemecanique
3 phase 3 kw 400v
1 phase 1.5 230v
(2 UNITS) 20A

Specifications
Quick Coupler valve
Brand: HUNTER
(4 UNITS)
Potable water tank
Specifications
Units are buried
(6 UNITS)

Driplines and tube


Specifications
pipe Bubbler and Dripper

Driplines and bubbler Specifications


Bubbler and Dripper
Driplines Specifications
Dripline

Specifications
Brand - PEDROLLO
Q : 50 - 450
H : 51.5 m
3 Phase / 4 kw / 5.5 HP / 60HZ
S1 : 3450 min
Volt : 220V
Centrifugal Pump
Amp: 20.5
( 1 UNIT)
AND CONDITION ASSESSMENT REPORT
Diriyah Farm Project
ASSET INFORMATION
essment of Irrigation system

Photo Comments

1.Pumps are dusty.


2.Pump room lot of mud and water
inside.
3.need regular preventive
maintenance.
4.pressure gauge are not calibrated

1.Unit are dusty.


2.Pressure tank has no pressure
gauge.
1.Unit are Dusty.
2. need regular preventive
maintenance.
3.Pressure gauge for the filter not
working.
4.have water leakage in the body of
filter.

1.Unit are Dusty.


2.Need regular preventive
maintenance.

1.Generator are dusty.


2. Unit have diesel leakage in the
base plate
3. Need regular preventive
maintenance.
4.Have diesel leakage in the
injection pump.
1.Unit is dusty
2.Need regular preventive
maintenance.

1. Electrical control pump panel is


dusty
2.Need regular preventive
maintenance.

1. Valve box lot of dust and garbage


inside.
2.# 13,14 and #15 valve box are
broken and damaged.
3.need gravel beddings for the
solenoid and gate valve.
4.no water strainer install inside in
the valve box.
1. Valve box lot of dust and garbage
inside.
2.need gravel beddings for the
solenoid and gate valve.
3.No water strainer install inside in
the valve box.

1.Units are dusty need to clean.


2.Pressure gauge are not working
properly not same reading to other
pressure gauge.
3.need regular preventive
maintenance and calibration.

1. Unit are dusty.


2.need to clean and check it if work
properly.
3- no key
1.water come from delivery tanker.
2.no pipe tube for monitoring the
water level
3.manual refilling of water.
4 Inside of water tank are dusty.
5.Need preventive maintenance
6.they used wooden stick for
measuring the water level.need to
check if there are damage or
cracking or disconeccted.

1.For trees they use dripper.


2.Tube pipe are damaged and
clogged.
3.Mostly of tube pipe are damaged.

1.For palm trees they use dripper. It


must change to bubbler
2.Tube pipe are damaged. And
clogged.
1.Dripline are clogged.
2.mostly of dripline are damaged
and broken.

1.Pump is dusty
2. Unit need regular preventive
maintenance.
ASSET DETAILS AND CONDITION ASSESSMEN
Diriyah Interchange Project
ASSET INFORMATION
Interchange Area Z93-113 Assessment of Irrigation system

S/N Equipment Asset Description

Specifications
Brand: Grundfos
RPM - 3520 - 3550 /3 Phase /60 Hz
U: 220-277
Vertical high pressure /380 -480
1 Pump I : 48.5 -39/28.0-22.4 A
(2 units) Volts :220-380-
440V

P2 - 15.0 KW
Eff. - IE2 90.2% - IE2 91.0%

Specifications
Brand:AQUASYSTEM
PRESSURE TANK
2
(1 UNIT)
Max.Press. 10.0 bar
Test Press. 14.3 bar
Temp.range - 10C/+100 C
Specifications
Flow Meter (
Brand:SENSUS
1 UNIT)
Typ WP - Dynamc 100
Qn - 230 m³/h

Specifications
Brand : LG WILSON
Model : P50 - 3
Rated Voltage : 220/127
Phase : 3
Generator ( Rated Frequency : 60 HZ
3
1 UNIT) Rated power : 56.30 KVA /45 KW
50.00 KVA / 40 KW
Rated RPM : 1800

Specifications
HUNTER ACC
Brand:HUNTER
( 1 UNIT)
ACC CONTROLLER
Specifications
Pump Controller
panel Brand:HI - TECH
( 1 UNIT)

Specifications

Brand:PEGLER for gate valve 1½"


Solenoid valve box
HUNTER for solenoid valve
MAIS for valve box.
( 55 UNITS)
HUNTER for decoder

Specifications
Quick Coupler valve
Brand: HUNTER
(10 UNITS)
Potable water tank
Specifications
Units are buried
(6 UNITS)

Isolation Valve
Specifications
Units are buried
(6 UNITS)

Driplines and bubbler Specifications


Bubbler and Dripper
Dripper and Tube
Specifications
pipe Dripline and dripper

Driplines Specifications
Dripline

Tube pipes Specifications


Tube pipes
Specifications
Brand : Emerson
16 A 230v -AC1
Pressure Switch 6A 240V - AC15
10 (4) A 400V
(1 UNIT) 0.55 kw 1-Motor
1 phase 1.5 230v
20A

Water Filter
Specifications
( 2 units ) Brand : TECNIDRO
AND CONDITION ASSESSMENT REPORT
iyah Interchange Project
ASSET INFORMATION
essment of Irrigation system

Photo Comments

1.Pumps are dusty.


2.Need regular preventive
maintenance.
3.One pump have water leakage in
the body.
4.They also corroded including
nut,bolt and body of the pump.

1.Pressure gauge not working


properly during operation.
2.Unit are dusty.
1.Unit are Dusty.
2.Need regular preventive
maintenance.

1.Generator are dusty.


2. unit have diesel leakage in the
base plate.
3. Need regular preventive
maintenance.

1.Unit is dusty.
2.Need regular preventive
maintenance.
1.Electrical control pump panel is
dusty
2.Need regular preventive
maintenance.

1. Valve box lot of dust and garbage


inside.
2.Need regular preventive
maintenance.
3.1 unit of solenoid valve has water
leakage.
4.no water strainer install inside in
the valve box.
5.no gravel beddings for the
solenoid and gate valve.

1. Unit are dusty.


2.need to clean and check it if work
properly.
3- No key
1.water come from delivery tanker.
2.no pipe tube for monitoring the
water level
3.manual refilling of water.
4 Inside of water tank are dusty.
5.Need preventive maintenance6- all
water tanker not tested , if thereare
damage or cracking or disconeccted

1.No valve key for incase on /off the


valve.

1.For palm trees they use dripper


and already clogged
2.tube pipe are damaged and
clogged it.
1.For tree they use dripper.
2.tube pipe are damaged and
clogged it.

1.Dripline location are misalign


2.mostly of dripline are damaged
and clogged.

1.Dripline are clogged.


2.mostly of dripline are damaged.
1.Units are dusty need to clean.
2.Pressure gauge are not working
properly not same reading to other
pressure gauge.
3.out of calibration.

1.Units are dusty.


2.No battery for the controller.
3.Need regular preventive
maintenance.
4.Have water leakage in the body
filter.
5.Pressure gauge not working
during irrigation.