2X25MW GTG +2X100TPH HRSG Charger Sizing Calculation-

PROJECT AT RCF LTD. THAL, CPP Unit


ALIBAUG, RAIGAD (MH)

BATTERY CHARGER SIZING

Float Mode

Continueous load on battery ( from Load cycle ) 4778.9000 Watts

Load Current ( At Float Charging voltage of 1.4 V)= (


Continuous load on battery/1.4*no. of cells) 39.6919 A

Trickle Charging Current (5 mA / Ah) for 180 AH battery 0.9 A


Rating of Float Charger 40.592 A
Float charger with margin (100 % ) 81.18372093
Float charger Rating selected 85 A

Boost Charger
Current reqd to charge the batteries
within 10Hrs (20 % of 180 AH Capacity) 36 A
Boost charger with margin (100 % ) 72
Boost Charger rating Selected 75 A

Float charger Rating 85 A


Boost charger Rating 75 A