SHEM-08.03 Material Handling1
SHEM-08.03 Material Handling1
Page 2 of 35
TABLE OF CONTENTS
1. PURPOSE
2. SCOPE
5. PROCEDURE
7. CONTROL OF RECORD
8. COMPETENCY
9. CONTINUAL IMPROVEMENT
11. ATTACHMENTS
Classification: Internal Use
Page 3 of 35
1. PURPOSE:
The purpose of this sub-element is to ensure that effective systems exist covering
material handling and storage and to provide detailed requirements and guidance
towards world-class processes and best practices/best available techniques for
handling and storage of materials in a compliant and safe manner at normal
operation, maintenance, TA’s etc to ensure safety and well-being to all.
2. SCOPE:
This management system applies to all activities and locations where people are
required to handle and/or store materials and manual handling of materials within
Petrokemya premises including permanent buildings, installations and locations as
well as temporary activities and locations.
GLOSSARY DEFINITION
BS British Standard
Page 4 of 35
GLOSSARY DEFINITION
of pressure.
Any vessel of 227 liters (60 US gallons) or less capacity used for
Container
transporting or storing liquids.
Deutsches Institut für Normung (The German institute for
DIN
standardization).
ECM Enterprise Content Management
An area of a building separated from the remainder of the
building by construction having a fire resistance rating of at
Fire Area least 1 hour and having all communicating openings into other
areas protected by assemblies having a fire resistance rating of
at least 1 hour.
The concentration (in percent) of a gas or vapor in air at which
flame will propagate. When the concentration is below the
Flammable Limits Lower explosive limit (LEL), the mixture is too lean; when above
or Explosive Range the upper explosive limit (UEL), the mixture is too rich. The
concentrations between the LEL and the UEL are called the
'flammable limits’ or ‘explosive range'.
Any liquid having a flash point (closed cup) below 37.8°C (100°F)
and having a vapor pressure not exceeding 40 psia (absolute
Flammable Liquid
pressure measured in pounds per square inch) at 37.8°C
(100°F).
The minimum temperature at which a liquid gives off vapor
within a test vessel in sufficient concentration to form an
ignitable mixture with air near the surface of the liquid. Although
Flash Point
other properties influence the relative hazards of flammable
liquids, the flash point is the most significant factor. The relative
hazard increases as the flash point decreases.
FM Factory Mutual
Page 5 of 35
GLOSSARY DEFINITION
LEL Lower Explosive Limit
Any item which is used to secure a load to lifting appliances but
which is not in itself capable of lifting or lowering loads such as:
Chain sling shackle
Lifting Gear Fiber sling eyebolt
(Tackle) Girder clip swivel
Hook ring
Spreader beam plate lifting clamp
Wire rope sling link
Line Management Supervisors, Managers, and Senior Managers.
Management Detailed procedures or policies that explain the implementation
System methodology to meet the requirement of SABIC OMS standard.
MOC Management of Change
Page 6 of 35
GLOSSARY DEFINITION
expected results.
An individual responsible for the coordination of OMS
OMS Specialist development and implementation, who interfaces with OMS
element owners and management.
OMS Sponsor Petrokemya President or his delegate.
A subject matter expert who is accountable for the
OMS Sub-Element internalization of applicable requirements for specific Sub OMS
Leader Management system, usually within the line management roles
of the organization.
OSHA Occupational Safety and Health Administration, USA
PK Petrokemya
Any closed vessel having a liquid capacity over 227 liters (60
Portable Tank
U.S. gallons) and not intended for fixed installation.
PPE Personal Protective Equipment
QA Quality Assurance
Page 7 of 35
GLOSSARY DEFINITION
safely relieve internal pressure when subjected to fire exposure.
Page 8 of 35
GLOSSARY DEFINITION
certificate issued by the manufacturer.
UL Underwriters Laboratories
Table 2 Glossary, Formulae & Definitions
Classification: Internal Use
Page 9 of 35
Third-party contractor
EHSS Senior Manager
department Manager
SHEM-08.03 EL/SEL
Department Senior
Maintenance staff
staff
SMT
Evaluate applicability of
4.1 A C R - R - - - -
this sub-element
Develop L3 documents to
4.2 adequately implement this A R R - R I I I I
sub-element
Ensure adequate
4.3 implementation of this sub- A R R R C R R R R
element
Identify training
4.4 A R R - R I I I I
requirements
Develop and track
4.5 A R - - R - - - -
performance indicators
Identify all regulatory
4.6 requirements relating to A I I R - I I I I
this management system
Comply with all regulatory
4.7 requirements relating to A R R - - R R R R
this management system
Perform periodic
inspections to verify
ongoing compliance with
4.8 A R R - - I I I I
regulatory and internal
requirements relating to
this management system
Periodically meets with
4.9 system administrator for A R R R R I I I I
reviewing OMS Action Plan
Classification: Internal Use
Page 10 of 35
Third-party contractor
EHSS Senior Manager
department Manager
SHEM-08.03 EL/SEL
Department Senior
Maintenance staff
Concerned
Manager
staff
SMT
and KPI progress and
update.
Ensure to have SOP for
equipment Purging by
steam. Consider related
4.10 A R R - - I I - -
hazard such as vacuum,
hot service, steam
hammering.
Identification for nitrogen
sign on storage tank and
4.11 A R R - - I I - -
equipment under nitrogen
purge are executed.
Maintain Special PPE
4.12 cabinet in the required A R R - - I I - -
area.
Follow Portable container
4.13 - A R - - R R - R
storage instructions
Ensure to develop SMP for
4.14 A A R - - R R - R
manual Safe lifting
Ensure employees trained
4.15 A R R R R I I I I
on SHEM-08.03
Develop SOP for Gas
4.16 A R R - - I I - -
cylinder handling
Develop SOP/guidelines for
4.17 process purging, N2, A R R - - I I - -
Steam, etc.
Ensure Safe Nitrogen
Handling during normal
4.18 A R R - - R R - R
operation & T/A SHEM-
08.03
Complete checklist to
4.19 ensure all material storage - A R - - R R R R
are safe.
Follow SOP before chemical
4.20 - A R - - I R - -
loading or unloading
Be aware about safe
4.21 A R R - - R R R R
handling of material to
Classification: Internal Use
Page 11 of 35
Third-party contractor
EHSS Senior Manager
department Manager
SHEM-08.03 EL/SEL
Department Senior
Maintenance staff
Concerned
Manager
staff
SMT
prevent injury & incident.
Page 12 of 35
5. PROCEDURE
5.1 Material Handling and Storage
All Storage of all materials shall comply with the following requirements:
5.1.1 PPE Requirement and Availability during Chemical Handling:
5.1.1.1 Area Owner will ensure that his area is having Special PPE cabinet
in the most suitable location. It consists of special personal
protective equipment (respiratory protection and chemical-
resistant suit, safety goggles & rubber gloves).
5.1.1.2 The Concerned department Manager shall ensures that these PPE
are checked on a periodic basis and part of safety task book.
5.1.1.3 Operation areas who deal with pyrophoric materials shall have
special PPE cabinet for pyrophoric material special suit and other
PPE.
5.1.1.4 The PPE in this cabinet is checked as part of call file checklist
record.
5.1.2 Area Sr. manager shall ensure relevant identification labels and warning
signs shall be in place for all stored materials.
5.1.3 All Tanks and pressure vessels shall be labeled by Owner with name and
hazard classification of the material stored, in accordance with the
applicable local standards/regulatory requirements. In the absence of
any local standards/regulatory requirements, NFPA 704 Standards
requirements shall be followed.
5.1.4 All Piping shall be labeled by Owner in a manner that allows relevant
personnel to quickly identify the service/contents of the piping. Piping
that handles hazardous materials/non-hazardous shall at least be clearly
labeled with name, flow direction and color coding scheme of the
material as per local regulation/standards.
5.1.5 Temporary and permanent storage of all materials shall be neat and
orderly.
5.1.6 Unobstructed access and movement shall be provided by owner to fire
hoses and extinguishers as well as for firefighting personnel.
5.1.7 Exits and aisle ways shall be kept clear at all times.
5.1.8 Storage racks shall be secured to the floor / wall and secured to each
other.
5.1.9 Damaged racks shall not be used for storage.
5.1.10 Step ladders and mobile ladders shall be made available to assist access
to material on racks at high elevations. Employees shall not be allowed
to climb racks.
5.1.11 Incompatible materials are not allowed to be stored together.
5.1.12 Smoking shall be prohibited in storage areas.
Classification: Internal Use
Page 13 of 35
5.1.13 Area owner shall ensure clear identification of the materials and
maximum quantities allowed to be stored in storage locations (or
sometimes even in specific cabinets/shelves) is important to prevent
unnecessary risks. Assistance shall be provided when moving excessive
loads. In general, objects over 23 kilograms (50.7 pounds) shall be
handled by two or more employees depending upon the shape of the
object.
5.1.14 Storage of material shall comply with the following requirements:
5.1.14.1 0.5 m to 1.0 m clearance shall be maintained under sprinklers.
Automatic sprinkler system controls and electrical panel boxes
shall be kept free and unobstructed
5.1.14.2 Storage of flammable liquids in open containers shall not be
permitted.
5.1.14.3 The requirements for containers shall be as per the applicable
standards/regulations.
5.1.14.4 In the absence of any applicable standards/regulations, Factory
Mutual-Approved or Underwriters Laboratories-Listed container
less than 18.9 liters (5 gallons) in capacity, which has a spring-
closing lid and spout cover and so designed that it will safely
relieve internal pressure when subjected to fire exposure, shall
be used.
5.1.15 Rolling objects on open shelves shall be blocked or wedged. In multiple
decking, heavier material shall be stored on the lower levels.
5.1.16 Area owner shall ensure adequate aisles shall be maintained for
unobstructed access. In the absence of any applicable standards/
regulations, it shall be in accordance with the following requirements:
5.1.16.1 Access aisles of at least 1.2 meters shall be maintained
5.1.16.2 Within indoor liquid storage areas, main aisles shall be a
minimum of 2.4 meters wide
5.1.16.3 Access ways in outside storage areas shall be a minimum of 3.6
meters wide
5.2 Flammable Material Handling and Storage
5.2.1 All department Sr. Manager shall ensure an adequate procedures (SMPs,
SOPs) are in place to safely handle flammable materials.
5.2.2 Each user must ensure Hot Work Permit procedure and SOP/SMP is in
compliance before loading or transferring flammable Liquid. Failure to
follow the procedure will lead to potential of having fire & cause injury.
The SOP for loading or unloading of specific chemicals shall include
appropriate personal protection equipment that must be use and the
details of that operation (SOP criteria as linked to SHEM-03: Standard
Operating & Maintenance Procedures). Petrokemya maintains an
updated list of hazardous materials being transport by road in & out of
their site.
Classification: Internal Use
Page 14 of 35
5.2.3 Updated hazard rating (fire, health, reactivity & special) labels as per
NFPA 704 requirements data for all Petrokemya hazardous chemicals are
available in ECM.
5.2.4 Operation Manger is responsible to ensure that all shifts shall maintain a
visual check, if any discrepancies, an immediate report to area Sr.
Manager to be done by Operation supervisor.
5.2.5 Operation supervisor is responsible to ensure the grounding maintained
for ISO tank & truck loading & unloading as per SOP. This is to prevent
static electricity build up during transfer, which is potential for fire.
5.2.6 Smoking (including the use of electronic cigarettes) and carrying of
matches, lighters, and other spark-producing devices shall not be
permitted in any area where flammable liquids are stored, handled, or
used.
5.2.7 Area owner shall ensure “No Smoking” signs shall be clearly posted in
such areas.
5.2.8 Area owner shall ensure flammable liquid containers and storage tanks
shall be posted with hazard identification labels as per applicable
standards/regulations. In the absence of any local
standards/regulations, the labels shall be as per NFPA 704
requirements.
5.2.9 Area owner shall ensure flammable liquid containers installed for filling
shall be electrically grounded and bonded to prevent static electricity
from causing a spark. The bond or ground or both shall be physically
applied or shall be assured by the nature of the installation.
5.2.10 Area owner shall ensure electrical grounding and bonding systems shall
be included in preventive maintenance schedules to ensure the systems
are regularly checked for electrical continuity. In addition, the exposed
visible portions of grounding and bonding systems shall be visually
inspected by the employee before each liquid transfer.
5.2.11 Ground wires shall be uninsulated for ease of inspection for mechanical
damage.
5.2.12 Where possible, interlocking of filling systems shall be installed to help
guarantee electrical continuity.
5.2.13 During flammable liquid filling operations, a wire bond shall be provided
between the storage container and the container being filled. The
bonding wire shall be grounded.
5.2.14 When dispensing from drums, the drums shall comply with the
applicable standards/regulations. In the absence of any applicable
standards/regulations, drums shall be equipped with Factory Mutual-
Approved or Underwriters Laboratories-Listed dispensing devices.
5.2.15 Flammable liquid transfer by means of air pressure acting directly on the
liquid shall be prohibited.
5.2.16 Flammable liquids shall not be stored in open containers. In addition,
containers shall not be stored close to heated pipes or other heat
sources or exposed to the rays of the sun unless the containers are
specifically designed/approved for outside storage.
Classification: Internal Use
Page 15 of 35
5.2.17 Tools, lighting and electrical equipment in areas where flammable liquid
is present shall meet the hazardous area classification requirements.
5.2.18 Flammable liquid storage cabinets shall not have a capacity for more
than 455 liters (120 gallons) of flammable liquids.
5.2.19 No more than three cabinets shall be located together in a single fire
area. Groups of cabinets must be separated by no less than 30 meters.
5.2.20 When flammable liquid storage cabinets are located indoors, vent
openings shall be sealed with securely fitted bungs or must be vented to
the outside. At least one portable fire extinguisher having a rating of not
less than 20-B shall be located outside the door opening into an area
where more than 60 gallons of flammable liquid are stored.
5.2.21 Storage tanks shall be designed, built and installed in accordance with
recognized good engineering standards for their material of
construction.
5.2.22 Special drainage, impounding areas, and/or diking shall be provided to
contain any discharge from aboveground storage tanks as per the
applicable standards/regulations. In the absence of any applicable
standards/regulations, it shall be as per NFPA 30.
5.2.23 Drainage systems shall be designed and operated to prevent discharge
to public waterways, public sewers, or adjoining property.
5.2.24 Department Sr. Manager shall ensure that all his employees, who use,
handle, store, and/or are otherwise exposed to flammable liquids shall
receive hazard communication training including general and chemical-
specific information record.
5.2.25 Department Sr. Manager shall ensure that above ground storage tanks
that are not inherently grounded (e.g. tanks on concrete or non-
conductive supports) shall be provided with a grounding system.
5.2.26 When flammable liquids are transferred from one container to another, a
means of bonding the two containers shall be provided prior to starting
the transfer.
5.2.27 Flammable liquid tank trucks and railroad tank cars shall be electrically
bonded and grounded to the loading rack.
5.2.28 Not more than a 1-day supply of flammable liquids in approved portable
containers (or not more than 95 liters (25 gallons), whichever is greater)
may be stored in a single fire area outside of an approved flammable
liquid storage cabinet.
5.3 Portable containers (material handling & storage):
This section states the requirements mandated by SAF-23, which applies to
flammable/combustible liquids stored in portable containers that individual
capacities do not exceed the following:
1. 60 gal (230 L) capacities for over pack drums
2. 119 gal (450 L) for drums or other containers
3. 660 gal (2500 L) for portable tanks
4. 793 gal (3000 L) for intermediate bulk containers
Classification: Internal Use
Page 16 of 35
5.3.1 Requirements:
1. Portable container materials, their volumes and their characteristics
shall be limited to what is specified in the Table 9.4.3 of NFPA 30
except non-metallic containers shall not be permitted for liquids
whose flash points are lower than 94°C (200 F).
2. Storage of portable containers shall be limited to a single area on the
ground level.
3. It shall not be more than 30 gallons of Class 1A and 120 gallons of
combined Class 1A, 1B, 1C flammable liquids shall be stored in a
single liquid storage cabinet of portable containers.
4. No more than three liquid storage cabinets shall be used in the same
control area for portable containers.
5. Portable containers Location, quantities, storage height, separation
distances, fire protection shall comply with NFPA 30 2018, Refer to
safety engineer for further clarification.
6. The storage area of portable containers shall be graded to divert
possible spills away from buildings or surrounded by a curb at least 6
in. (150 mm) high.
7. For portable containers, the curbed area shall have a storm drainage
system.
8. Storage area shall be protected against tampering and trespassing.
9. Storage area shall be kept free of weeds, debris and other
combustible materials for a distance of at least 10 ft. (3 m) around the
perimeter of the stored materials.
10. A canopy shall be provided over the storage area. The canopy shall
allow dissipation of heat or dispersion of flammable vapors and fire-
fighting access and control.
5.4 Gas Cylinder Handling and Storage
5.4.1 Initial inspection check list (Attachment 3) for receiving compressed gas
cylinders shall be used to check the condition of the cylinders by Material
department or the other department who are directly receiving it from
vendor/supplier. Unsafe cylinders not matching the criteria of the
attachment 3 shall reject back to the vendors. The reason for rejection
shall be communicated to the vendor by email and PK material section
with reporting of eSHEM. The reporter of eSHEM shall ensure to provide
all the details as per attachment 5 of this management system record.
5.4.2 Initial inspection checklist (Attachment 3) shall be recorded for one (1)
year from the date of inspection by Material department or other
departments who are directly receiving by vendor.
Classification: Internal Use
Page 17 of 35
Page 18 of 35
5.4.17 Cylinders shall be free from corrosion, pitting, dents or other signs of
physical damage
5.4.18 Protective safety caps shall be in place (hand-tight) when delivered or
when the cylinder is not in use
5.4.19 Material safety data sheet (also known as a safety data sheet) must be
available or provided by the vendor
5.4.20 Cylinder fittings and valves shall meet the applicable standards /
regulations
5.4.21 Cylinder hoses for fuel gas service shall meet the applicable standards /
regulations. In the absence of any applicable standards/regulations, they
shall meet the following requirements:
5.4.21.1 Specification IP-7 for Rubber Welding Hose, Compressed Gas
Association and Rubber Manufacturer Association shall be
complied with.
5.4.21.2 Fuel gas hoses shall be red in color, oxygen hoses green, and
inert gas and air black.
5.4.22 When parallel lengths of oxygen and fuel gas hose are taped together
for convenience and to prevent tangling, not more than 4 inches per foot
shall be covered in tape
5.4.23 Hoses showing leaks, burns, areas of wear or other serious defects shall
be replaced.
5.4.24 Pressure-reducing regulators shall meet the applicable standards/
regulations. In the absence of any applicable standards/regulations, they
shall meet the following requirements:
5.4.24.1 Only Underwriters Laboratories (UL)-listed or Factory Mutual
(FM)-approved pressure-reducing regulators shall be used
5.4.24.2 Pressure-reducing regulators shall be used for the gas and
pressures for which they are labeled
5.4.24.3 Cylinder flash-back protection shall meet the applicable
standards/regulations. In the absence of any applicable
standards/regulations, it shall be provided on oxy-acetylene
lines by a UL-approved flame arrestor to prevent burn-back into
hoses and the regulator.
5.4.25 Cylinders shall be stored in accordance with applicable standards /
regulations. In the absence of any applicable standards/regulations,
cylinder storage shall meet the following requirements:
5.4.25.1 Smoking and open flames shall not be permitted in storage
areas or within 20 ft. (6.1 m) of storage areas.
5.4.25.2 Cylinder storage areas shall be fenced off and clearly marked
with 'NO SMOKING' and 'NO OPEN FLAME' signs
5.4.26 A separate area shall be provided for each individual material stored.
The name of the material in each storage area shall be prominently
posted
5.4.27 Gas cylinders shall be stored a minimum distance of 20 ft. (6.1 m) from
storage of flammable and combustible liquids and solids
Classification: Internal Use
Page 19 of 35
5.4.28 Oxygen cylinders shall be stored at least 6 meters away from cylinders
containing combustible gases, or from any highly combustible materials.
Exception: The minimum separation distance for the cylinders shall not
apply when they are separated by masonry walls with a fire resistance
rating of 2 hours
5.4.29 Different flammable gases shall be permitted to be stored together in a
group
5.4.30 Cylinders shall be stored where they are not exposed to physical
damage, tampering by unauthorized persons, or subject to
temperatures above 54°C (130°F)
5.4.31 Liquefied flammable gas cylinders shall be stored in the upright position
or such that the pressure relief valve is on the vapor space of the
cylinder.
5.4.32 Cylinders shall be stored away from stairs and in assigned places where
they will not be knocked over or damaged by passing or falling objects.
5.4.33 Petrokemya staff shall comply with the applicable standards/regulations
regarding handling and use of cylinders. Also, the following good
practices for cylinder handling and use shall be followed:
5.4.33.1 Contents of a gas cylinder shall be verified and the properties
of the gas shall be known before using.
5.4.33.2 Where compressed gas cylinders are designed to accept valve
protective caps, the user shall keep such caps on compressed
gas cylinders at all times except when being filled or
connected for use.
5.4.33.3 Leaking cylinders with the valve fully closed shall if possible be
removed to a location remote from other cylinders or work
area.
5.4.33.4 A leaking cylinder, or a cylinder that has been exposed to fire,
shall not be transported without consulting the supplier for
advice under these circumstances.
5.4.33.5 Lubrication of any cylinder’s valves and fittings with oil or
grease shall never be done because it is unnecessary and
highly dangerous.
5.4.33.6 Cylinder valves shall be closed before moving cylinders.
Cylinders shall also be appropriately secured.
5.4.33.7 Valve protection caps shall not be used for lifting cylinders
5.4.33.8 Cylinders shall be kept far enough away from welding or
cutting operations that sparks, hot slag or flame do not reach
them.
5.4.33.9 Cylinders shall be secured while connected to a portable
welding machine to prevent them from being knocked over or
thrown off in transit.
5.4.33.10 Cylinder shall not be lifted to an elevation with ropes wrapped
around them. Cylinders shall instead be lifted using a cage
with correct lifting lugs.
Classification: Internal Use
Page 20 of 35
5.4.33.11
Empty cylinders shall not be disposed of. They shall be
removed promptly from the plant areas and returned to the
empty cylinder racks provided. Only the owner of a cylinder
shall authorize its disposal.
5.5 Usage of Gas cylinders Hoses & fitting:
5.5.1 Only trained and qualified person is allowed to work on gas cylinder.
Any component part or hoses related to gas cylinder must be original
and it shall be approved & certified, fabricated ones are not accepted.
Only Underwriters Laboratories (UL) listed or Factory Mutual (FM)
approved pressure reducing regulators shall be used.
5.5.2 Before a regulator removed from a cylinder, the cylinder valve shall be
closed and the regulator relieved of gas pressure. The valve cap shall be
replaced, the cylinder clearly marked as "empty," and returned to a
storage area for pickup by the supplier.
5.5.3 Concerned Operation/Maintenance Sr. manager shall ensure
development SOP/SMP procedure for any work involved with gas
cylinder replacement. Such as CO Cylinder Replacement in Poly area &
Fabrication Group Welding Activity.
5.5.4 Analyzer specialist maintains SMP for work involving gas cylinders
replacement including Analyzer shelter gas cylinders also.
5.5.5 QA Analyst maintains SOP for work involving gas cylinders replacement
for QAD area.
5.5.6 Gauges used for oxygen service shall be marked, “USE NO OIL OR
GREASE”.
5.5.7 When regulators or parts of regulators, including gauges, need repair,
the work shall be performed by skilled mechanics who have been
properly instructed.
5.5.8 Cylinders shall be stored where were not exposed to physical damage,
tampering by unauthorized persons, or subject to temperatures above
54°C (130°F).
5.6 Handling of Specific Materials
Dept. Sr. Manager shall ensure that all his personnel potentially exposed to
hazardous chemicals/materials shall adequately trained by their depts. in the
safe use of such chemicals/materials before they are allowed to work with
them.
5.6.1 Identification of Workplace Hazard
5.6.1.1 Carbon Monoxide (CO) = a chemical compound consisting of
one carbon and one oxygen.
5.6.1.2 CO is a colorless, odorless, and flammable gas at room
temperature. Therefore, it has no WARNING properties!
5.6.1.3 The most likely route of exposure is through inhalation.
5.6.1.4 One of the most dangerous industrial hazards. Its Time
Weighted Average (TWA) concentration is 25 ppm.
Classification: Internal Use
Page 21 of 35
Page 22 of 35
Caution
Under Nitrogen
Blanket
Figure 1
Caution
DANGER, HAZARDOUS
ATMOSPHERE
NITROGEN PURGE
Figure 2
Classification: Internal Use
Page 23 of 35
Page 24 of 35
Page 25 of 35
Page 26 of 35
Page 27 of 35
Page 28 of 35
5.6.7.3
Pressure testing equipment or pipes using Nitrogen or Air
requires a review by the Stationary section of the technical
division in order to establish guidelines for pressures to be
applied. Use of air for leak testing equipment prior to start up is
not recommended. Steam shall not be used for any pressure or
leak testing.
5.6.7.4 For all other requirements related to hoses, refer to SHEM-
07.07: Hoses Program.
5.7 Manual handling of Materials:
5.7.1 Area owner shall ensure to develop SOP/SMP for manual Safe handling
and lifting.
5.7.2 An ergonomic evaluation shall be carried out on all manual material
handling operations to determine if the job activity shall be redesigned
to reduce the physical and mental stress on the employee.
5.7.3 Advance consideration shall be given to the size, shape, and weight of
materials to be handled and plan the most efficient and safe method to
accomplish the task.
5.7.4 The proper tool shall be provided for the job. Mechanical means shall be
used in lieu of manual lifting where practical. Defective tools and devices
shall not be used or returned to service until repaired.
5.7.5 Employee selection in work assignments shall be matched to the job in
terms of knowledge and physical abilities.
5.7.6 Whenever unusual or hazardous operations are to be performed,
specific safety instructions shall be given that describes how to avoid
injuries prior to performance of the work, and shall warn employees
about possible hazards.
5.7.7 Instructions shall be clear, concise and complete, and terminology shall
be thoroughly explained.
5.7.8 Special efforts shall be taken to prevent hernias and back injuries.
Avoidance of the injuries begins with fitting the job to the worker
(ergonomics) and instruction to the workers in the correct way to do the
work and correction of incorrect behavior. The employee’s first efforts
following safety instruction shall be closely monitored to ensure that
proper lifting methods are used.
5.7.9 Heavy objects shall be pushed and not pulled during transportation.
5.7.10 Personnel shall stand clear of equipment being loaded or unloaded
5.7.11 Correctly-sized carts shall be used for material transportation
5.7.12 Cart wheels shall be chocked when loading or unloading heavy or
cumbersome loads
5.7.13 At least two persons shall perform elevated handling (above head level)
of any piece of equipment that weighs more than 18 kilograms (39.7
pounds).
5.7.14 When two or more persons carry a long object, carry from the same side.
The person in the rear shall give the signals for lifting, carrying or
lowering.
Classification: Internal Use
Page 29 of 35
5.7.15 Never carry an object that prevents you from seeing where you are
going.
5.7.16 Do not throw objects to another person.
5.7.17 Avoid throwing material from elevated positions. If it becomes necessary
to throw material, the area into which material must be thrown shall be
barricaded and guarded to keep persons out.
5.7.18 Keep your hands and fingers out of the ends of pipe or other tubular
materials.
5.7.19 When rolling a drum on its sides push with your hands against the sides
of the drum, never grasp the ends of the barrel or use your feet to push
it.
5.7.20 Use a mechanical aid or get help when you need to upend a full barrel.
5.7.21 Carts shall be driven to the right within Petrokemya facilities.
5.7.22 The aid of second person shall be provided for directing and opening
doors when the size of the load and the size of the cart make this
necessary.
5.7.23 All containers shall be examined for identification and special handling
instructions.
5.7.24 Avoid lifting objects over your head or reaching out to place the object
on a shelf or platform.
5.7.25 Uncrating shall be done with wrecking bars or claw hammers. All
exposed nails shall be removed or bent to prevent injury.
5.7.26 Whenever possible jack handles shall be removed when not in use. Jacks
shall be level and set on firm footing.
5.7.27 Additional planning shall be given to such problems as sharp edges or
shapes of loads, hazardous or fragile material, uneven weight
distribution, and routes of travel while lifting and carrying.
5.7.28 Only Petrokemya approved standard pallets shall be used with “Manual
Forklift Pallet Trucks”. Personnel shall ensure SWL of Manual Forklift
Pallet Trucks supersedes the intended load, pallets stability upon
loading/unloading and transport, and sufficient clearances from all sides
of the pallet against the forks and loading/unloading ground.
5.7.29 Employees shall be made familiar with the selected equipment before
the work begins. Instructions shall be clear, concise and complete, and
terminology shall be thoroughly explained.
5.7.30 Adequate clearances shall be observed so that employees can readily
avoid being struck, caught or pinned between moving loads or material
handling equipment.
5.7.31 Material handling equipment capacities shall be observed. When
transferring loads, care shall be taken to avoid shock loading
5.7.32 The seven (7) basic steps of manual handling (Attachment 4) is
mandatory for everyone working in Petrokemya and shall follow to
prevent an injury.
5.8 NON-POWERED EQUIPMENT FOR MATERIAL HANDLING:
5.8.1 Equipment in this category of material handling shall include, but not
limited to, the following examples:
Classification: Internal Use
Page 30 of 35
All the local, regional, national and international regulation requirements applicable
to this management system, and to which Petrokemya subscribes, have been
identified and determined in accordance with Compliance, Assessments and
Evaluation Management System (OMS-232), and incorporated into the management
system or otherwise referenced in Section 10.
The legal/regulatory requirements applicable to this management system are
provided below:
SAF-02 Environmental, Health and Safety Management, HCIS, Ver 2.0, 2017
SAF-06 Plant Layout, Spacing and Access, HCIS, Ver 2.0, 2017
SAF-15 Private Industrial Fleet Vehicle Filling Stations, HCIS, Ver 2.0, 2017
SAF-23 Flammable/Combustible Liquids in Portable Containers, HCIS, Ver 2.0,
2017
Classification: Internal Use
Page 31 of 35
7. CONTROL OF RECORD
The following records are identified and described in the record control requirements
pertaining to this Management system in accordance with Documentation & Control
of Records Management system (OMS-234).
ECM/Record file
5 SHEM-08.03 soft copy OMS EL/SEL 3 year
at EL
ECM/record file
SMP/SOP for material Concerned Department/
6 at the 3 year
handling Department Sr. Manager
department
ECM/record file
Concerned Department/
7 Annual KPI reports at the 1 year
Department Sr. Manager
department
Table 4 Control of Records
8. COMPETENCY
Page 32 of 35
Senior Managers
Management
Department
EHSS Senior
SHEM-08.03
Office Based
Contractors
Maintenance
Type
Employees
Employees
Operations
Employees
Operation
Competency
Manager
EL/SEL
SMT
Hazardous material handling
D D A D D D A D D
expectations
Hazardous material storage
P P A D D D D D D
requirements
Table Error! No text of specified style in document. Competency Matrix
9. CONTINUAL IMPROVEMENT:
Page 33 of 35
10.1 References
• SAF-02 Environmental, Health and Safety Management, HCIS, Ver 2.0,
2017
• SAF-06 Plant Layout, Spacing and Access, HCIS, Ver 2.0, 2017
• SAF-15 Private Industrial Fleet Vehicle Filling Stations, HCIS, Ver 2.0, 2017
• SAF-23 Flammable/Combustible Liquids in Portable Containers, HCIS,
Ver 2.0, 2017
• SAF-24 Hazardous Materials in Portable Containers, HCIS, Ver 2.0, 2017
External Standards and Publications
BS 341-2
DIN 477-6
Classification: Internal Use
Page 34 of 35
NFPA 55
NFPA 30 section 7.2 Requirements (revision 2018)
NFPA 704
National Institute for Occupational Safety and Health (NIOSH) standard
OSHA 29 CFR 1910.101
OSHA 29 CFR 1910.106
OSHA 29 CFR 1910.176
OSHA 29 CFR 1910.1200
SABIC Engineering Standards E11-S03 Bonding and Grounding
Underwriters Laboratories (UL)-Listed Container standard
10.2 Linkage with Other OMS
Input Interface / link Output
OMS-111 Leadership commitment and culture. SHEM-08.03
Page 35 of 35
11. ATTACHMENTS
Attachment 6