601.0 Scope.
601.1 Ducts and plenums that are portions of a heating, cooling, absorption or
evaporative cooling, or product conveying system shall comply with the
requirements of this chapter.
601.2 Sizing Requirements. Duct systems used with blower type equipment
that are portions of a heating, cooling, absorption, evaporative cooling, or outdoor
air ventilation system shall be sized in accordance with ASHRAE Fundamentals,
ACCA and SMACNA, or by other approved methods.
Exception: Duct sizing calculations are not required for existing duct systems.
602.0 Material.
602.1 General. Supply air, return air, and outside air for heating, cooling, or
evaporative cooling systems shall be conducted through duct systems constructed of
metal as set forth in Tables 6-1, 6-2, 6-3, 6-4, 6-7, 6-8, 6-9, and 6-10, or metal ducts
complying with UMC Standard No. 62 or the referenced HVAC duct construction
standard in Chapter 29. Rectangular ducts in excess of two (2) inches W.G. shall
comply with UMC Standard No. 62 or the referenced HVAC duct construction
standard in Chapter 29. Ducts, plenums, and fittings may be constructed of concrete,
clay, or ceramics when Installed in the ground or in a concrete slab, provided the
joints are tightly sealed.
Corridors shall not be used to convey air to or from rooms if the corridor is required
to be of fire resistive construction per the Building Code. When gypsum products
are exposed in ducts or plenums, the air temperature shall be restricted to a range
from 50°F (10°C) to 125°F (52°C), and moisture content shall be controlled so that
the material is not adversely affected. For the purpose of this section, gypsum
products shall not be exposed in ducts serving as supply from evaporative coolers,
and in other air-handling systems regulated by this chapter when the temperature of
the gypsum product will be below the dew point temperature.
Exhaust ducts under positive pressure and venting systems shall not extend into or
pass through ducts or plenums. For appliance vents and chimneys, see Chapter 8.
Exceptions:
(1) Air filters meeting the requirements of Sections 311.2 and 503.3.
(4) Electrical wiring in plenums shall comply with NFPA 70, National
Electrical Code. Electrical wires and cables and optical fiber cables shall be
listed and labeled as suitable for use in plenums and shall have a flame spread
distance not greater than five (5) feet (1,524 mm), an average optical density not
greater than 0.15, and a peak optical density not greater than 0.5, when tested in
accordance with NFPA 262, Flame Travel and Smoke of Wires and Cables for
use in air handling spaces.
(8)Smoke detectors.
10) Materials in a Group H, H-5, fabrication area including the areas above
and below the fabrication area sharing a common air re-circulation path with the
fabrication area.
602.3 Factory Made Air Ducts. Factory made air ducts shall be approved for
the use intended or shall conform to the requirements of the referenced standard for
air ducts in Chapter 29. Each portion of a factory made air duct system shall be
identified by the manufacturer with a label or other suitable compliance with
identification indicating referenced standard for air ducts in Chapter 29 and its class
designation.These ducts shall be listed and shall be installed in accordance with the
terms of their listing and the requirements of UMC Standard No. 65. Flexible air
connectors are not permitted
602.3.1 projects and including clinics and supply, return or exhaust air
terminal devices to rigid duct systems. Where constant volume, variable volume
or mixing boxes are utilized, flexible duct of not more than 10 feet (3048 mm),
may be used on the inlet side for alignment. An internal impervious liner shall
be provided to isolate insulation material from conditioned air.
602.4 Joints and Seams of Ducts. Joints of duct by systems shall be made
substantially airtight by means of tapes, mastics, gasketing, or other means.
Crimp joints for round ducts shall have a contact lap of at least 11/2 inch (38
mm) and shall be mechanically fastened by means of at least three (3) sheet metal
screws equally spaced around the joint, or an equivalent fastening method.
Joints and seams for 0.016 inch (0.41 mm) (No. 28 gauge) and 0.013 inch (0.33
mm) (No. 30 gauge) residential rectangular ducts shall be as specified in Table 6-1
for 0.019 inch (0.48 mm) (No. 26 gauge) material.
Joints and seams for rectangular duct systems shall be as specified in Table 6-1.
Joints and seams for flat oval ducts and round ducts in other than single dwelling
units shall be as specified in Table 6-8. Joints and seams and all reinforcements for
factory made air ducts and plenums shall meet with the conditions of prior approval
in accordance with the installation instructions that shall accompany the product.
Closure systems for rigid air ducts and plenums shall be listed in accordance with
UL 181A, Standard for Closure Systems for Use with Rigid Air for Ducts and Air
Connectors.Closure systems for flexible air ducts shall be listed in accordance with
UL 181B, Standard for Closure Systems for Use with Flexible Air Ducts and Air
Connectors.
602.5 Metal. Every duct, plenum, or fitting of metal shall comply with Table 6-
1 or 6-8.
Exceptions:
(1) Ducts, plenums, and fittings for systems serving single dwelling units
may comply comply with Table 6-9. complying with UMC
(1) Duct systems complying with the UMC Standard 62 or the referenced
HVAC duct construction standard in Chapter 29, with prior approval.
603.0 Quality of Material. Galvanized steel shall be of lock forming quality with a
minimum coating of 1.25 ounces of zinc per square 3 foot (0.04 kg/m ) conforming
to the requirements of UMC Standard No. 22.
604.1 General. Air ducts installed under a floor in a crawl space shall be
installed so as to maintain a vertical clearance of eighteen (18) inches for all
portions of the duct that would obstruct access any part of the crawl space.
604.2 Metal Ducts. Ducts shall be securely fastened in place at each change of
direction and as set forth in Table 6-7. Vertical rectangular ducts and vertical round
ducts shall be supported as set forth in Table 6-7, Part A. Riser ducts shall be held in
place by means of metal straps or angles and channels to secure the riser to the
structure.
Metal ducts shall be installed with at least four (4) inches (102 mm) separation
from earth. Metal ducts when installed in or under a concrete slab shall be encased
in at least two (2) inches (51 mm) of concrete.
Supports for rectangular ducts as set forth in Table 6-7, when suspended from
above, shall be installed on two opposite sides of each duct and shall be riveted,
bolted, or metal screwed to each side of the duct at not more than the intervals
specified.
Horizontal round ducts forty (40) inches (1,016 mm) or less in diameter when
suspended from above shall be supported at intervals not more than as set forth in
Table 6-7 with one hanger installed to comply with the requirements listed below
604.2.2 Circular bands shall be not less than one (1) inch (25.4 mm)
wide nor less than equivalent to the gauge of the duct material it supports.
Exception: Ducts ten (10) inches (254 mm) and less in diameter may be
supported by No. 18 gauge galvanized steel wire.
604.3 Factory Made Air Ducts. Listed Class 0 or Class 1 factory made air
ducts may be installed in any occupancy covered by this code. Factory made air
ducts shall not be used for vertical risers in air duct systems serving more than
two stories. Such ducts shall not penetrate construction where fire dampers are
required. Factory made air ducts shall be installed with at least Tour (4) inches
(102 mm) of separation from earth except when installed as a liner inside of
concrete tile, or metal pipe; they shall be protected from physical damage. The
temperature of the air to be conveyed in any of these classes of ducts shall not
exceed 250°F (122°C).
605.0 Insulation of Ducts. Supply and return air ducts and plenums of a
cooling system shall be insulated to achieve the minimum thermal (R) value as set
forth in Tables 6-6 A and B. Cold air ducts shall be insulated wherever necessary or
to prevent condensation problems.
Approved materials shall be installed within ducts and plenums for insulating,
sound deadening, or other purposes. Materials have a mold shall humidity, and
erosion resistant surface that meets the requirements of the referenced standard for
air ducts in Chapter 29. Duct liners in systems operating with air velocities
exceeding 2000 feet per minute (10.16 m/s) shall be fastened with both adhesive and
mechanical fasteners, and exposed edges shall have adequate treatment to withstand
the operating velocity.
Insulation applied to the surface of ducts, including duct coverings, linings,
tapes, located in buildings shall have a flame spread index not greater than twenty-
five (25) and a smoke developed index not greater than fifty (50),when tested in
accordance with NFPA 255, Method of Test of Burning Characteristics of Building
Materials, or in accordance with ASTM E 84, Surface Burning Characteristics of
Building Materials, accordance with the provisions of UL 723, Test for Burning
Characteristics Materials. The specimen preparation and mounting procedures of
ASTME 2231, Specimen Preparation and Mounting of Pipe and Duct Insulation
Materials to Assess Surface Burning Characteristics, shall be used. Air duct
coverings and linings shall not flame glow, smolder, or smoke when tested in
accordance with ASTM C 411, Hot Surface Performance of High Temperature
Thermal Insulation, at the temperature to which they are exposed in service. In no
case shall the test temperature be below 250°F (121°C).
Factory made air ducts and faced insulation intended for installation on the exterior
of ducts shall be legibly printed with the name of the manufacturer, the thermal
resistance (R) value at installed thickness, and the flame spread index and smoke
developed index of the composite material.
606.1 Smoke Dampers. Smoke dampers shall comply with the standards
for leakage rated dampers referenced in Chapter 29, and shall be approved when
installed in accordance with manufacturer' installation instructions required by
the Building Code. Smoke dampers shall be labeled by an approved agency.
606.2 Fire Dampers. Fire dampers shall comply with the standard for fire
dampers referenced in Chapter 29, and shall be installed in accordance with the
approved manufacturer's installation when required by the Building Code. Fire
dampers shall have been tested for closure under airflow conditions and shall be
labeled for both maximum airflow permitted and direction of flow. When more
than one damper is installed at a point in a single air path, the entire airflow
shall be assumed to be passing through the smallest damper area. Fire than one
damper is installed at a point in a single air to be Fire dampers shall be labeled
by an approved agency. Duct-work shall be connected to damper sleeves or
assemblies in accordance with the fire damper manufacturer's installation
instructions.
Exceptions:
607.1 General. Perforated ceilings may be used for air supply within the
limitations of this section. Exit corridors, when required to be of fire resistive
construction by the Building Code, shall not have ventilating ceilings.
608.0 Use of Under Floor Space as Supply Plenum. An underfloor space may
be used as a supply plenum, provided:
608.1 The use of under floor space shall be limited to not more than two
stories in height. Except for the floor immediately above the under floor
plenum, supply ducts shall be provided extending from the plenum to registers
on other floor levels. Exception: In flood hazard areas, under floor spaces shall
not be used as supply plenums unless the flood opening requirements in the
Building Code are satisfied.
608.2 Such spaces shall be cleaned of all loose combustible scrap material
and shall be tightly and substantially enclosed.
608.3 The enclosing material of the under floor space, including the
sidewall insulation, shall be not more flammable than one (1) inch (25.4 mm)
(nominal) wood boards (flame spread index of 200. Installation of foam plastics
is regulated by the Building Code.
608.4 Access shall be through an opening in the floor and shall be not less
than twenty-four (24) inches by twenty-four (24) inches (610 mm x 610 mm).
608.5 A noncombustible receptacle shall be placed below each floor
opening into the air chamber, and such receptacle shall conform to the
following:
608.5.2 The area of the receptacle shall extend three (3) inches (76
mm) beyond the opening on all sides.
608.5.3 The perimeter of the receptacle shall have a vertical lip at least
one (1) inch (25.4 mm) high at the open sides if it is at the level of the
bottom of the joists, or three (3) inches (76 mm) high if the receptacle is
suspended.
608.6 Floor registers shall be designed for easy removal in order to give access
for cleaning the receptacles.
608.7 Exterior walls and interior stud partitions shall be fire stopped at the
floor.
608.8 Each wall register shall be connected to the air chamber by a register box
or boot.
608.9 The entire ground surface of the under floor space shall be covered with a
vapor barrier having a minimum thickness of four (4) mils (0.1016 mm) and a flame
spread index of 200 or less.
608.10 Fuel gas lines and plumbing waste clean outs are not located within the
space.
(1) When the space supplied by the air moving equipment is served by a total
coverage smoke detection system complying with the Fire Code, interconnection to
such system may be used to accomplish the required shutoff.
(2) Automatic shutoff is not required when all occupied rooms served by the air
handling equipment have direct exit to the exterior and the travel distance does not
exceed 100 feet (30,480 mm).
(3) Automatic shutoff is not required for Group R, Division 3 and Group U
Occupancy.
(4) Automatic shutoff is not required for approved smoke control systems or
where analysis demonstrates shutoff would create a greater hazard, such as may be
encountered in air moving equipment supplying specialized portions of Group H
Occupancy. Such equipment shall be required to have smoke detection with remote
indication and manual shutoff capability at an approved location.(5) Smoke
detectors that are factory installed in listed air moving equipment may be used in
lieu of smoke detectors installed in the main supply air duct served by such
equipment.
701.1 General.
701.1.1 Air for combustion, ventilation, and dilution of flue gases for gas
utilization equipment installed in buildings shall be gas obtained by application
of one of the methods covered in Sections 701.2 through 701.8.3. Gas
utilization equipment of other than natural draft and Category I vented
appliances shall be and provided with combustion, ventilation, and dilution air
in accordance with the equipment manufacturer's instructions. Where
infiltration does not provide the necessary air, outdoor air shall be introduced in
accordance with methods covered in Sections 701.4 through 701.8.3.
Exceptions:(1) This provision shall not apply to direct- vent appliances. (2)
Type 1 clothes dryers that are provided with makeup air in accordance with
Section 504.3.2.
701.1.2 Gas appliances of other than natural draft design and other than
Category I vented appliances shall be provided with combustion, ventilation,
and dilution air in accordance with the appliance [NFPA 54: 9.3.1.2].
manufacturer's instructions.
701.1.4 Makeup air requirements for the operation of exhaust fans, kitchen
ventilation systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion-air requirements.
[NFPA 54: 9.3.1.5].
701.2 Indoor Combustion Air. The required volume of indoor air shall be
determined in accordance with the method in section 701.2.1 or 701.2.1.1, except
that where the air infiltration rate is known to be less than 0.40 ACH, the method in
Section 701.2.1.1 shall be used. The total required volume shall be the Sum of the
required volume calculated for all appliances located within the space. Rooms
communicating directly with the space in which the appliances are installed through
openings not furnished with doors, and through combustion air openings sized and
located in accordance with Section 701.3.1, are considered a part of the required
volume. [NFPA 54: 9.3.2].
a)Required Volume other ≥ (21 ft.3/ ACH) x I other 1,000 Btu/hr) Equation 701.2.1.1
WHERE : Iother = all other appliances other than fan-assisted input in Btu per
hour fan-assisted appliance other input in Btu per hour
701.2.2 Known Air Infiltration Rate Method. Where the air infiltration
rate of a structure is known, the minimum required volume shall be determined
as follows [NFPA 54: 9.3.2.21:
(1) For appliances having other than fan- assisted combustion systems:
calculate using equation 701.2.1.1(a) but no smaller than thirty-five (35) cubic
feet 3 per 1,000 Btu/hour (3.4 m /kW). [NFPA 54: 9.3.2.2(1)]
701.3.1 Openings used to connect indoor spaces shall be sized and located in
accordance with the following [NFPA 54: 9.3.2.3]:
(1) Combining spaces on the same story. Each opening shall have a minimum
free area of 1in./1,000 Btu/h. (220 2 3 mm /kW) of the total input rating of all gas
utilization equipment in the space, 2 but not less than 100 in. (0.06 m ).One opening
shall commence within twelve (12) inches (300 mm) of the top, and one opening
shall commence within twelve (12)in. (300 mm) of the bottom of the enclosure. (See
Figure 7-1.) The minimum dimension of air openings shall be not less than three (3)
inches (80 mm). [NFPA 54: 9.3.2.3(1)]
(1) The ratio of interior spaces shall be the available volume of all
communicating divided by the required spaces volume.[NFPA 54:9.3.4(3)
(a)].
(2) The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.
[NFPA 54:9.3.4(3)(b)].
(3) The minimum size of outdoor opening(s) shall be the full size of
outdoor opening(s) calculated in accordance with multiplied The dimension of
air openings shall not be (3) Section reduction 701.4, by the factor. minimum
less than three inches (80 mm).[NFPA 54:9.3.4(3)(c)].
701.8.1 Where exhaust fans are installed, are additional air shall be
provided to replace the exhausted air. [NFPA 54:9.3.6.1].
(A) Louvers and openings for Grilles. The required size of combustion,
ventilation, and dilution air shall be based on the net free area of the free area
through a and each opening. Where design of louver, grille or screen is known,
it shall be used in calculating the size opening required to provide the free area
specified. Where the louver and grille design and free area are not known, it
shall be assumed that wood louvers will have a 25 percent free area and metal
louvers and grilles will have a 75 percent free area. Non-motorized louvers and
grilles shall be fixed in the open position. [NFPA 54:9.3.7.1].
(B) Minimum Screen Mesh Size. Screens shall not be smaller 54:9.3.7.2].
701.10 Combustion Air Ducts. Combustion air ducts shall comply with the
following [NFPA 54:9.3.8]:
(1) Ducts shall be of galvanized steel or a material having equivalent corrosion
resistance, strength, and rigidity. [NFPA 54:9.3.8.1]
(4) Ducts shall not service both upper and lower combustion air openings where
both such openings are used. The separation between ducts serving upper and lower
combustion-air openings shall be maintained to the source of combustion air.
[NFPA 54:9.3.8.4].
(6) Intakes for combustion-air ducts located exterior to the building shall have the
lowest side of the combustion-air intake openings located at least twelve (12) inches
vertically from the adjoining grade level. [NFPA 54:9.3.8.8].
(7) Horizontal upper combustion-air ducts shall not slope downward toward the
source of combustion air. [NFPA 54:9.3.8.6].
(8) The remaining space surrounding a chimney liner, gas vent, special gas vent,
or plastic piping installed within a masonry chimney flue metal or factory-built
chimney shall not be used to supply combustion air unless it is listed and shown in
the manufacturer's installation instructions. [NFPA 54:9.3.8.7].
801.0 Scope. The requirements of this chapter shall govern the venting of fuel
burning appliances.
801.1 Venting of Gas Appliances. Low heat gas appliances shall be vented in
accordance with this chapter. Other gas appliances shall be vented in accordance
with NFPA 211 or other applicable standards.
802.0 General.
802.1 This section recognizes that the choice of venting materials and the
methods of installation of venting systems are dependent on the operating
characteristics of the gas utilization equipment. The operating characteristics of
vented gas utilization equipment can be categorized with respect to (1) positive or
negative pressure within the venting system, and (2) whether or not the equipment
generates flue or vent gases that can condense in the venting system. See Section
224.0 for the definition of these vented appliance categories. [NFPA 54:12.2]
802.2.2.8 Room heaters listed for unvented use (see Sections 924.1 and
924.2). [NFPA 54:12.3.2(8))
802.2.2.10 Other equipment unvented use and not provided with flue
collars. [NFPA 54:12.3.2(10)] listed for
Exception: Incinerators.
802.4.2 Plastic Piping.Plastic piping used for venting equipment listed for
use with such venting materials shall be approved. [NFPA 54:12.5.2]
802.4.3 Special Gas Vent. A special gas vent shall be listed and installed in
accordance with the terms of the special gas vent listing and the manufacturers'
instructions. [NFPA 54:12.5.31
Exception:
Masonry chimney flues lined with a chimney lining system
specifically listed for use with listed gas appliances with draft
hoods, Category appliances,and other gas appliances listed for use
with Type B vents shall be permitted. The liner shall be installed in
accordance with the liner manufacturer's instructions and the terms
of the listing. A permanent identifying label shall be attached at the
point where the Connection is to be made to the liner. The label
shall read: This chimney liner is for appliances that burn gas only.
Do not connect to solid or liquid fuel burning appliances or
incinerators."
802.5.2 Termination.
(2) For sizing an individual chimney venting system for a single appliance
with a draft hood, the effective areas of the vent connector and chimney flue
shall be not less than the area of the appliance flue collar or draft hood outlet or
greater than seven times the draft hood outlet area [NFPA 54:12.6.3. 1 (2)]
(3) For sizing a chimney connected to two appliances with draft venting
system hoods, the effective area of the chimney flue shall be not less than the
area of the larger draft hood outlet plus 50 percent of the area of the smaller
draft hood outlet, or greater than seven times the smallest draft hood outlet area.
[NFPA 54:12.6.3.1(3)]
802.5.4.4 When inspection reveals that an existing chimney is not safe for
the intended application, it shall be repaired, rebuilt, lined, relined, or replaced
with a vent or chimney to conform to NFPA 211, Standard for Chimneys,
Fireplaces, Vents, and Solid -Fuel Burning Appliances, and shall be suitable for
the equipment to be attached. [NFPA 54:12.6.4.4]
802.5.5 Chimney Serving Equipment Burning Other Fuels.
802.5.5.4 A single chimney flue serving a listed combination gas and oil
burning appliance shall be sized to properly vent the appliance.
802.5.7 Clean outs. Where a chimney that formerly carried flue products from
liquid or solid fuel burning appliance using fuel gas, an accessible clean out shall be
provided. The clean out shall have a tight fitting cover and be installed so its upper
edge is at least six (6) inches (150 mm) below the lower edge of the lowest chimney
inlet opening. appliances is used with an 802.5.8 Space Surrounding Lining or Vent.
The remaining space surrounding a chimney liner, gas vent, special gas vent, or
plastic piping installed within a masonry chimney flue shall not be used to vent
another appliance.
802.6.1 A gas vent passing through a roof shall extend through the entire
roof flashing, roof jack, or roof thimble and be terminated with a listed
termination cap.
802.6.2 A gas vent shall terminate in accordance with one of the following:
(1) Above the roof surface with a listed cap or listed roof assembly.
Gas vents twelve (12) inches (300 mm) in size or smaller with listed caps
shall be permitted to be terminated in accordance with Figure provided they
are at least eight (8) feet (2.4 m) from a vertical wall or similar obstruction.
All other gas vents shall terminate not less than two (2) feet (0.6 m) above
the highest point where they pass through the roof and at least two (2) feet
(0.6 m) higher than any portion of a building within ten (10) feet (3.1 m).
802.6.2.6 A gas vent shall terminate at least three (3) feet (0.9 m)
above a forced air inlet located within ten (10) feet (3.0 m). [NFPA
54:12.7.2 (7)]
(3) For sizing a gas vent connected to two appliances, with draft
effective area of the vent shall be not less than the area of the larger
draft hood outlet plus 50 percent of the area of the smaller draft hood
outlet or hoods the greater than seven times the smaller draft hood
outlet area.
(1) The available total height (H) for each rooms shall have an adequate
supply of for segment of a multistory venting system is the vertical distance
between the level of the highest draft hood outlet or flue collar on that floor
and the center line of the next highest interconnection tee. (See Figure 8-4.)
(2) The size of the connector for a segment is determined from its
equipment connector rise, and shall not be smaller than the draft hood outlet
or flue collar size.
(3) The size of the common vertical vent utilization heat input gas and
available (3) segment, and of the interconnection tee at the base of that
segment, shall be based on the total gas utilization equipment heat input
entering that segment and its available total height.
802.7 Single Wall Metal Pipe. Highest point where passes through a roof
802.7.2.1 Single wall metal pipe shall roof shall extend without
interruption terminate at least five (5) feet (1.5 m) in through the roof
flashing, roof jacket, or vertical height above the highest equipment
draft hood outlet or flue collar. connected roof thimble
802.7.3 Size of Single Wall Metal Pipe. Single wall metal piping shall
comply with the following requirements:
(2) For a venting system for a single appliance with a draft hood,
the areas of the connector and the pipe each shall be less than the area
of the not appliance flue collar or draft hood outlet, whichever is
smaller. The vent area shall not be greater than seven times the draft
hood outlet area.
802.7.3.2 Where a single wall metal pipe is used and has a shape
other than round, it shall have an equivalent effective area equal to the
effective area of the round pipe for which it is substituted and the
minimum internal dimension of the pipe shall be two (2) inches (50
mm).
802.10.2 Materials.
(b) Galvanized sheet steel not less than 0.018 in. (0.46 mm)
thick.
(d) Stainless steel sheet not less than 0.012 in. (0.31 mm)
thick.
(e) Smooth having resistance to heat and Corrosion equal to or
greater than that of b, c, or d above. ) A listed vent connector.
connectors for listed gas having draft hoods and interior wall metal
pipe vent connectors shall not be covered with insulation.
Exception: connectors shall be installed according to the terms of
their listing. Listed insulated vent
802.10.3.2 For a single appliance having more than one draft hood
outlet or flue collar, the manifold shall be constructed according to the
instructions of the appliance manufacturer. Where there are no instructions,
the manifold shall be designed and constructed in accordance with
approved engineering practices. As an alternate method, the effective area
of the manifold shall equal the combined area of the flue collars or draft
hood outlets and the vent connectors shall have a minimum one (1) foot
(0.3 m) rise.
802.10.8 Slope. A vent connector shall be installed without any dips or sags
and shall slope upward toward the vent or chimney at least 1/4 in./ft. (20
mm/m). Exception: Vent connectors attached to a mechanical draft system
installed in accordance with the manufacturers' instructions.
802.10.10 Support. A vent connector shall be the supported for the design and
weight of the material employed to maintain clearances and prevent physical
damage and separation of joints. Connection.
802.10.14.1 A vent connector shall not pass through any ceiling, floor, or
fire resistance rated wall. A single-wall metal pipe connector shall not pass
through any interior wall. rated wall.
Exception:
Vent connectors made of listed Type B or Type L vent material and
serving listed equipment with draft hoods and other equipment listed for
use with Type B gas vents that pass through walls or partitions constructed
of combustible material shall be installed with not less than the listed
clearance to combustible material.
(1) For listed appliances equipped with draft hoods and appliances
listed for use with Type B gas vents, the thimble shall be a minimum of
four (4) inches (100 mm) larger in diameter than the vent connector.
Where there is a run of not less than six (6) feet (1.8 m) of vent
connector. Where there is a run of not less than six (6) feet (1.8 m) of
vent connector in the opening between the draft hood outlet and the
thimble shall be a minimum of two (2) inches(50 mm) larger in
diameter than the vent connector.
802.10.14.3 Vent connectors for medium heat equipment shall not pass
through walls or partitions constructed of combustible material. [NFPA
54:10.10.14.3]
802.11 Vent Connectors for Category 1, Category I1, and Category IV Gas
Utilization Equipment. (See Section 802.4.) [NFPA 54:10.11]
802.15 Obstructions. Devices that retard the flow of vent gases shall not be
installed in a vent connector, chimney, or vent. The following shall not be be
Considered as obstructions:
(1) Draft regulators and safety controls specifically listed for installation in
venting systems and installed in accordance with the terms of their listing.
(2) Approved draft regulators and safety controls designed and installed in
accordance with approved engineering methods.
(3) Listed operated vent dampers installed in accordance with the terms of
their listing. Vent dampers serving listed appliances installed heat reclaimers
and automatically
(4) in accordance with Sections 803.1 and 803.2.1 or other approved
engineering methods.
803.1 These venting tables shall not be used where obstructions (see
Section 802.15) are installed in the venting system. The installation of vents
serving listed appliances with vent dampers shall be in manufacturer's
instructions or in accordance with the following:
803.1.1 Where the vent size determined from the tables is smaller than
the appliance draft hood outlet or flue collar, the use of the smaller size
shall be permitted provided that the installation complies with all of the
following requirements:
(1) The total vent height (H) is at least ten (10) feet (3 m).
(2)Vents for appliance draft hood outlet or flue diameter or smaller are
not reduced feet(3 m). (300mm) in collars twelve (12) inches more than one
table size.
(3)Vents for appliance draft hood outlets mm) in diameter are not
reduced more than o flue collars larger than twelve (12) inches (300 two
table sizes.
(5)The draft hood outlet is greater than four (4) (5) inches (100 mm) in
diameter. connect a three (3) diameter vent to a four (4) inches (100 mm)
diameter draft hood outlet. This provision shall not apply to fan assisted
appliances. Do not connect a three inches (80 mm) diameter vent to a four
(4) inches (100 mm) diameter draft hood outlet. This provision shall not
apply to fan assisted appliances.
803.1.3 Zero (0) lateral (L) shall apply only to a straight vertical vent
attached to a top outlet draft hood or flue collar.
803.1.5 For appliances with more than one input rate, Min)determined
from the tables shall be less than the lowest appliance input rating, and the
maximum vent capacity (FAN Max/NAT Max) determined from the tables
shall be greater than the highest appliance rating input. the minimum vent
capacity
803.1.6 Listed corrugated metallic chimney liner systems in masonry
chimneys shall be sized by using Table 85 or 86 for Type B vents, with the
maximum capacity reduced by 20 percent (0.80maximum capacity) and the
minimum capacity as shown in Table 85 or 86. Corrugated metallic liner
systems installed with bends or offsets shall have their maximum capacity
further reduced in accordance with Section 803.1.2. The 20 percent
reduction for corrugated metallic chimney liner systems includes an
allowance for one long radius 90 degree turn at the bottom of the liner.
803.1.7 Where the vertical vent has a larger diameter than the vent
connector, the vertical vent diameter shall be used to determine the
minimum vent capacity, and the connector diameter shall be used to
determine the maximum vent capacity. The flow area of the vertical vent
shall not exceed seven times the flow area of the listed appliance
categorized vent area, flue collar area, or draft hood outlet area unless
designed in accordance with approved engineering methods.
(2) The vent connector length is limited to1- 1/2 feet for each
inch (180 mm/mm) of vent connector diameter.
(4) The input rating is less than the maximum capacity given
in Table 87.
(5) For a water heater, the outdoor design temperature shall not
be less than 5F (-15C).
803.1.9 Corrugated vent connectors shall not be smaller than the listed
appliance categorized vent diameter, flue collar diameter, or draft hood
outlet diameter.
803.1.10 Vent connectors shall not be up-sized more than two sizes
greater than the listed appliance categorized vent diameter, flue collar
diameter, or draft hood outlet diameter.
803.1.14 For vent heights lower than six (6) feet and higher
engineering methods shall be used to calculate vent capacities. [NFPA
54:13.1] than shown in the tables,
803.2.1 These venting tables shall not be used where obstructions (see
Section 802.15) are installed in the venting system. The installation of vents
serving listed appliances with vent dampers shall be in accordance with the
appliance manufacturer's instructions or in accordance with the following:
3 4-1/2
4 6
5 7-1/2
6 9
7 10-1/2
8 12
9 13-1/2
10 15
12 18
14 21
16 24
18 27
20 30
22 33
24 36
803.2.4 Where the vent connectors are combined prior to entering the
vertical portion of the common vent to form a common vent manifold, the
size of the common vent manifold and the common vent shall be
determined by applying a 10 percent reduction (0.90 x maximum common
vent capacity) to the Common Vent Capacity part of the common vent
tables. The length of the common vent connector manifold (LM) shall not
exceed 18 in./in. (180 mm/mm) of common vent connector manifold
diameter (D). (See Figure 8-4.)
803.2.7 The vent connector capacities listed in the Common vent sizing
tables include allowance for two 90 degree elbows. For each additional
elbow up to and including 45degrees, the maximum vent connector capacity
listed in the venting tables shall be reduced by 5 percent.For each elbow
greater than 45 degrees up to and including 90 degrees, the maximum vent
connector capacity listed in the venting tables shall be reduced by 10
percent.
803.2.11 The connector rise (R) for each appliance connector shall be
measured from the draft hood outlet or flue collar to the center line where
the vent gas streams come together.
803.2.13 For multistory installations, available total height (H) for each
segment of the system shall be the vertical distance between the highest
draft hood outlet or flue collar entering that segment and the center line of
the next higher interconnection tee. (See Figure 85.)
803.2.14 The size of the lowest connector and of the vertical vent
leading to the lowest interconnection of a multistory system shall be in
accordance with Table 8-5 or 8-6 for available total height (H) up to the
lowest interconnection. (See Figure 8-6.)
803.2.18 For appliances with more than one input rate, the minimum
vent connector capacity (FAN Minimum) determined from the tables shall
be less than the lowest appliance input rating. and the maximum vent
connector capacity (FAN Maximum or NAT Maximum) determined from
the tables shall be greater than the highest appliance input rating.
803.2.20 Tables 8-10 and 8-11 shall be used for chimneys and vents not
exposed to the outdoors below the roof line. A Type B vent passing through
an unventilated enclosure or chase insulated to a value of not less than R8
shall not be considered to be exposed to the outdoors. Tables 8-16 through
819 shall be used for clay tile lined exterior masonry chimneys, provided all
of the following conditions are met:
(3) The combined appliance input rating is less than the maximum
capacity given by Table 8-16 (for NAT+NAT) or Table 8-18 (for
FAN+NAT).
(4) The input rating of each space heating appliance is greater than
the minimum input rating given by Table 8-17 (for NAT+NAT) or
Table 8-19 (for FAN+NAT).
803.2.22 All combinations of pipe sizes and single wall and double
wall metal pipe shall be allowed within any connector run(s) or within the
common vent provided ALL of the appropriate tables permit ALL of the
desired sizes and types of pipe, as if they were used for the entire length of
the subject connector or vent. Where single wall and Type B double wall
metal pipes are used for vent connectors within the same venting system,
the common vent must be sized wall and Type B double wall metal pipes
are using Table 811 or 813, as appropriate.
Solution:
Table 8-5 is used in the case of an all Type B vent system. However,
since there is no entry in Table 8-5 for a height of 12 ft, interpolation must
be used. Read down the 4 in. diameter NAT Max column to the row
associated with 10 ft. height and 5 ft. lateral to find the capacity value of
77,000 Btu/h. Read further down to the 15 ft. height, 5 ft. lateral row to find
the capacity value of 87,000 Btu/h. The difference between the 15 ft. height
capacity value and the 10 ft. height capacity value is 10,000 Btu/h. The
capacity for a vent system with a 12 ft. height is equal to the capacity for a
10 ft. height plus 2/5 of the difference between the 10 ft. and 15 ft. height
values, or 77,000 + 2/5 x 10,000 81,000 Btu/h. Therefore, a 4 in. diameter
vent can be used in the installation.
803.2.26 For vent heights lower than six (6) feet and higher than shown
in the tables, engineering methods shall be used to calculate vent capacities.
[NFPA 54:13.2].
804.Referenced Publications. The documents or portions of this chapter have been
reproduced from the California Mechanical Code 2007 and NFPA 542006
Standards.