Commissioning Checklist Format
Commissioning Checklist Format
TESTING AND
25/02/2023
COMMISSIONING DATE
COMMISSIONING
Sanjeeth
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER
INDOOR SERIAL NUMBER
INDOOR LOCATION /
Royal Enfield Showroom Mezanine Floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER
OUTDOOR SERIAL NUMBER
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 24
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE V
FREQUENCY(Hz) 50 Hz
CURRENT A
RUN TEST PARAMETRES
SET TEMPERATURE Deg C
ROOM TEMPERATURE Deg C
GRILL TEMPERATURE Deg C
Page 1 of 12
COMMISSIONING REPORT OF
TRANE DUCTABLE SPLIT TYPE AC
UNIT 4
Contract Title: HVAC Units Installation, Royal Enfield Showroom,Salwa Road.
AMBIENT TEMPERATURE Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI)
DISCHARGE PRESSURE(PSI)
Page 2 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
2/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB181
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB088
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 3 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
2/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB180
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB079
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 4 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
3/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB111
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0119
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 5 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
3/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB078
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0183
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 6 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
3/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB0182
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0034
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 7 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
4/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB0102
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0090
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 8 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
4-10-2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB0171
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0169
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 9 of 12
COMMISSIONING REPORT OF
SPLIT TYPE AC UNIT
Contract Title: HVAC Units Installation, Army base camp, Vodafone office,Salwa.
DUCTABLE UNIT LOCATION Army base camp vodafone project,
TESTING AND
4/10/2022
COMMISSIONING DATE
COMMISSIONING
Sharikh Khan
TECHNICIAN
INDOOR / OUTDOOR
INDOOR MODEL NUMBER AS36CS4S
INDOOR SERIAL NUMBER AS36CS4SJB0039
INDOOR LOCATION /
Vodafone office.First floor
REFERENCE NUMBER
OUTDOOR MODEL NUMBER AS36CS4S
OUTDOOR SERIAL NUMBER AS36CS4SJB0087
OUTDOOR LOCATION /
Rooftop
REFERENCE
REFRIGERANT CIRCUIT
PRESSURE TEST WITH DRAIN
YES
NITROGEN
PRESSURE HOLD FOR 4
YES
HOURS
LEAK TESTED YES
VACUUM ACHIEVED YES
VACUUM HOLD YES
REFRIGERANT
REFRIGERANT TYPE R410a
FACTORY REFRIGERANT
2.150 Kg
CHARGE(Kg)
ADDITIONAL REFRIGERANT
NO
ADDED(Kg)
REFRIGERANT LEAK TEST YES
POWER SUPPLY
VOLTAGE 240 V
FREQUENCY(Hz) 50 Hz
CURRENT 11.23 A
RUN TEST PARAMETRES
SET TEMPERATURE 20 Deg C
ROOM TEMPERATURE 22 Deg C
AMBIENT TEMP 26 Deg C
CONDENSATE REMOVAL OK
CIRCUIT
SUCTION PRESSURE(PSI) 120
DISCHARGE PRESSURE(PSI) N/A
Page 10 of 12
Main Contractor Client Sub Contractor
COMMISSIONING REPORT
DATE 25/02/2023
SCOPE OF WORK HVAC Ductable Units Installation, Royal Enfield Showroom,Salwa Road.
BRAND Trane 5 TR
QUANTITY 4Nos
Page 11 of 12