2.10
OPENpredictor™ System Hardware
‘The hardware is installed within a 19-inch rack containing the electronics. The
electronics convert the analogue signals from the transducers into digital
data, which is transferred to a database on the Server PC.
10.1 The RO2000 Signature Processing Unit (SPU)
‘The ROZ000 SPU is the heart of the system as it executes all measurements
and data transfer to other parts of the system. Up to three SPUs can be
located in a standard instrumentation rack. Each RO2000 contains:
+ 1 pes. RO2010 Communication Processor Module (CPM), see section
2.10.2.
+ 1 to 10 pes. RO2020 Signal Processing Module (SPM), see section 2.10.3.
* 1 pcs. Integrated Power Supply, placed on the rear panel behind the
motherboard. It is fused with one 230V/10 Amp T (slow) fuse placed on
the rear panel of RO2000 in a small drawer below the power inlet
connector. The normal maximum power consumption is 6 Amps.
‘+ Aseparate Cooling Unit mounted below each RO2000 Unit with 3 fans and
a 'Power' lamp. The ‘Power’ lamp is connected to +12VDC from the
R02000 power supply, which also powers the fans.
+ Various installation dependent accessories: Cable terminal blocks, relays,
galvanic isolators, etc.
(1): RO 2000 with one RO 2010
and one to ten RO 2020.
(2): Cooling unit with ‘Power’
lamp.
19” OPENpredictor™ rack with one RO2000.
Rebooting the SPU is described in section 2.9.2.
2004/10/14 OPENpredictor™ 2.7.2 Operator's Guide Issue 1.8 Page 2-492.10.2 The RO2010 Communication Processor Module
(cPM)
‘The RO2010 CPM controls all internal and external data communication from
‘and to the SPU. It controls the data communication between the RO2020
Signal Processing Modules (SPM) and the OPENpredictor™ Server.
Each RO2010 contains: -
+ Ethernet port.
‘+ Port to control external relays.
+ Slots for expansion of memory and number of ports.
‘+ LED's for operation indication, Reset button.
The lamps, controls and inputs are: -
Console (3) Service connector used by ROVSING Dynamics
ANS personnel when setting-up the system.
Ethernet (8) Standard 10/100 Mb/s Ethernet connector.
Upper Reset button (Not to be used.)
(located left of the ‘Fail’
and 'Run’ lamps)
Lower Reset button Pressing the button will reboot the SPU - see
(located left of the section 2.9.2.3.
‘Auxiliary’ and ‘Seria’ WARNING: While rebooting, no measurements
lamps) will be performed,
It performs a hot boot of the built-in CPM
equivalent to the CPM boot after a power failure.
Fail lamp Green: Lights in case of fault.
Run lamp : Lights/flashes due to data activity.
Auxillary lamp : Lights/fiashes due to data activity on the
Auxiliary module.
Serial lamp Green: Lights/flashes due to data activity on any
of the serial module ports.
“auxillary’ module ‘Optional module card position. May be used for
(4-7, reserved) a second serial port module (see below) or e.g.
a PCMCIA card docking station.
‘Serial’ module ‘Optional module card position for a RO2021
(1-3) Serial Port Upgrade with 3 RS232/RS485 serial
ports:
Serial 3: RS232.
Serial 1 & 2: RS485.
(There is one more unused port on the rear
panel).
‘There are several possible applications, but the
ports are typically used for
‘+ control of a Warning Relay Unit.
‘+ receiving data from a PLC using the Modbus
Interface.
2004/10/14 OPENpredictor™ 2.7.2 Operator's Guide Issue 1.8 Page 2-502.10.3 The RO2020 Signal Processor Module (SPM)
‘The RO2020 SPM executes all defined measurements and transfers results
Internally to the RO2010 CPM.
+ Each RO2020 contains:
+ 8 Analogue inputs
+ Power supply for transducers
+ LED's for operation indication,
‘The lamps and inputs are: =
‘Power’ lamp (left lamp) _| Lights when the module receives power.
"Run' lamp (right lamp) | Lights/flashes due to data activity on any of
the inputs.
8 pcs. analogue ‘Input’ | Each analogue input is connected to a fast A/D
connectors converter. The SPM has its own on-board
signal-processing units, which also calculates
signatures defined in the measurement set-up,
e.g. FFT, FRF, STA calculations, Digital
transducer signals like tachometer-pulses are
handled as analogue voltages.
2004/10/14 OPENpredictor™ 2.7.2 Operator's Guide Issue 1.8 Page 2-51‘The RO2O000 Signature Processing
Unit (SPU) is the heart of the
OPENpredictor™ system for Condition
‘Monitoring, with identification of
mechanical, electrical and machinery
process faults, using the RO2021
Signal Processing Modules (SPM)
‘The SPU provides space for up to 10 SPs,
which in total provide a capacity to process
up to 80 analogue signals from different
types of sensors (displacement, acceleration,
pressure, curent, position etc). The unit's
compact design and high channel density
facilitates online monitoring of several
machines with just one SPU, reducing
cabinet space requirements
ANEXO 15 - pag. 4
MI-A1-0358
Application
+ Space for up to ten 802021 Signal
Processing Modules = up to 80 channels
+ Space for one 802010 Communication
Processing Module incuded)
'* Power supply and cooling for RO2010 and
R02021's {inchided|
Aprovado em 06/02/2017
oPENEIE ICCC
SIGNATURE
PROCESSING UNIT
02000
Features and benefits
Simple and robust design
High analogue channel density for
reduced cabinet space
Up to 80 analogue signals from different
machines can be processed
Interface for field digital data
19" standard mounting
Power supply with high Mean Time
Between Failures (MTBF)
‘Wide temperature operation range
Low power consumption
fg Rovsing
WN ovuamicsSPECIFICATIONS
RO2000 Signature Processing Unit
ceNeRaL REUABILITY 202000 incLuDES.
CE cetied [TBF figures 02010 Communication Processor Module
[DAC specications: EN 5008-1, EN 50082-2 Fan: 70,000 Hours (040 0008 Fan
Power supp: 400,000 Hous (040 0006 ower Supply
ELECTRICAL
Power supply ENVIRONMENTAL
‘operation 47-632 Temperature: 0 t0 55% [Operating
Supply voltage: 90-255 Vims 40 to 85°C [Storage)
ower consumption: 100 W Humic 5% to 90K non condensing
{with one put module)
250W PRYSICAL
(With ten input Modules) size 3091300%482 mm (HeDx}
Safety Speciation: EN 60950 Weg ake
Bacilane ME, 1 slot for RO 2010, Rackmatei:—_—Gahanised Stel Pate
10 slots fr RO 2021,
SS
mm
‘Signature Processing Unit (PU) crate ining the Communication Processor
‘Module (SP and shown with 4 Sigal Processing Modules [SPU]
The Signature Processing Unit Crate type RO2000-CR
can be ordered as a spare unit without the R02010,
but including power supply and cooling fan.
DK2730Herlev Tel +45 4650 7200
Denmark Fax +45 4484 6040
Rovsing Dynamics A'S
Marielundve} 41
ANEXO 15 - pag. 2
MI-A1-0358
Info ovsing-dynanics.con
\ertovsing-dynamis.com
‘Sievew of the Signature Processing Unit cate, Notice the addtional space
requied in font and back for cabling
Rovsing
DYMamics
Aprovado em 06/02/2017opEN ICRC
COMMUNICATION
PROCESSOR MODULE
The OPENpredictor™ RO2010
Communication Processor Module
(CPM) is the interface for all RO2000
Signature Processing Unit data. The
02021 module executes advanced data
processing for identifying changes in
signal levels and machinery component
fault symptoms.
A dedicated data reduction methodology
limits data transfer to only those data
containing relevant information, Data is
separated into two main stream functions:
+ Data for operators about important
machinery fault, typically transferred
to process control systems via Modbus
serial lnk via the optional RO2011 Serial
Pott Upgrade Module for the CPM, which
has has 3 ports for communicating data
to and from Process Control Systems or
Programmable Logic Controllers).
+ Data for maintenance engineers about
sill machine fault symptom changes
‘are transfered to the OPENpredictor™
Server via Ethemet TCP/IP, for display
‘and further interpretation by the
‘OPENpredictor™ Concition, Performance
and Reliability Monitoring aplication
software
MI-A1-0358
‘The RO2010 CPM receives the monitoring
strategy from the OPENpredictor™ Server
‘and controls the operation ofthe RO2021
‘Signal Processing Modules (SPM). When
‘changes in machine operational state are
Identified, the CPM transfers the required
signal processing methods to the SPI's
with respect to the measurement types,
averaging time and frequency range
required, The first SPM measurement result
is stored as soon as a state change has
‘occurred, and subsequent measurements
are compared with this first measurement,
Changes outside the defined ‘dead
band’ strategy are transferred to the
OPENpredictor™ Server.
‘Alert and alarm levels can be defined for
the measurements triggering both status
change and software messages.
Aprovado em 06/02/2017
‘Application:
+ Data Processing of up to ten RO2021
Signal Processing Modules
Transfer of data from and ta Process
Control Systems & PLCs (via 02011)
Transfer of data from and to
(OPENpredictor™ Server
Time synchronisation with
(OPENpredictor™ Server
+ Galulation of complex algorithms based
on measured and imported data
Sends the configuration to the SPM for
the defined monitoring strategies and
collects, processes the SPM result.
Features and benefits:
‘Supports several interfaces and protocols
to export and import data to and from
Process Control Systems and networks
‘Machine state classification to create
comparable machine condition data for
Fobustness of field comparison, and to
avo false alarms
Rovsing
DYNAmicsData reduction using dead band strategy
{to minimise data throughput to the
OPENpredictor™ Serve, facilitating the use
of low bandwith networks
Temporary data storage avoids data loss
in case communication to the network is
interrupted
Intelligent architecture faciitates
distribution of processing power to those
channels (sensors) and measurements
with high demand and priority
SPECIFICATIONS
Relays
‘Te RO2010 CPM can contro optional
relays via the RO2011 Serial Port Upgrade
Module, using the identified status change.
Arelay’s ‘hold down’ function is supported
in order to avoid relays triggering for short
events. Relays" logic can be applied to
have a combination of measurement results
trigger one relay. This is typically used as
a common relays function for machinery
temperature or over-all vibration level
RO2010 Communication Processor Module
Process data input
“The CPM can import process data from
other systems e.g temperature, pressure
tc. for Performance Monitoring, and
Jogging of operating hours, downtime et.
{or Reliability Monitoring, This canbe used
{or machine state definition but also for
complex calculations resting in ‘virtual
sensor’ results, which canbe treated, stored
and transfered as any other measured or
imported parameter
ELECTRICAL
Power consumption; 25 W max
ENVIRONMENTAL
Temperature 01055,
fowced ar cooling
Humidity 5% 10 90%
non condensing
REUABILTY
rer fig: 122,000 Hours
Rovsing Dynamics NS
Denmark
= pig. 2
ML-A1-0358
DK2730Herlev Tel 445 4690 7200
Fx #45 4484 6040
IWTERFACeS,
‘Modbus:
SerialPort RS 485, Modbus RTU 38.4 Koi/sec
wth R02012)
Ethernet:
[Ethernet TCPP TP Gahanicaly oated
10/100/1000 Mbitisec
Relays (optional)
Response time to activate relays «2 sec [with
02011)
Info@rovsing-dynamics.com
‘wm rovsing-dynamic.com
Aprovado em 06/02/2017
PHYSICAL
Weight: o4tg
size ou
‘oprions
02011 SerialPort Upgrade for Communication
Processor
£02210 Relay uit with 4 8 or 12 reas.
Sr age den te a te
‘ert eft on tne et
Rovsing
DYNAMICS.OPEN I
SERIAL PORT UPGRADE FOR
COMMUNICATION PROCESSOR MODULE
Corre)
‘The OPENpredictor™ RO2O11 Serial Port Application Features and benefits
Upgrade Module provides three additional + Provides 3 additional serial ports to * Compact design, wich does not take
ports to the RO2010 Communication Ro2010 centa rack space
Processor Module (CPM). The RO2OL1 is + Communication to Process Contr + Powered from 802010 Communication
‘optional and facilitates communication ‘ystems and Programmable Logic Processor Module so no external power
to and from Process Control Systems, Controllers supply is needed
Programmable Logic Controllers and the + Control of extemal relays units * Industrial standard protocols for seamless
202210 External Relays Module. The integration
202011 slides into one of the front side + High speed serial communication up to
slots of the CPM. 115 kBaud per port
+ Both export as well as import of data
ANEXO 17- pag. 4 Revsins
MI-A1-0358 Aprovado em 06/02/2017SPECIFICATIONS — R02011
Serial Port Upgrade for Communication Processor Module
Inpurvourpurs
3 MicoD sub miniature connectors, 9 pia
Baud rate 115 KBaud per port
Standar UNRT 16550,
RELAYS SUPPORT
+ RO2210, deh 8ch or 12h External Relays
Module
Rovsing Dynamics A'S 0K-2730 Herlev
Marielundve} 41 Denmark
ANEXO 17 - pag. 2
MI-A1-0358
Tel 445 46907200
Fax +45 4484 6040
\wewnrovsing-dynamics.com
Aprovado em 06/02/2017
{Styne on nb stone
‘een arte nt