Substation Automation Products

Line distance protection with


Relion® 650 series
REL650
© ABB Group
Slide 1
1MRG002224, November 2010
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 2
Line distance protection with Relion® 650 series
REL650

Ready to use solutions for line


protection applications primarily in sub-
transmission networks:
Quadrilateral (REL650 – A01 & A11)
Mho characteristic (REL650 – A05)
Single breaker for single or double
busbar arrangment
High impedance grounded systems or
directly grounded systems
Overhead lines and cables
Double circuit lines

© ABB Group
November 2010
Slide 3
Line distance protection with Relion® 650 series
REL650

Different communication schemes


Distance protection and residual
overcurrent
Full compatibility in scheme
communications between 650 series
and 670 series or 500 series

Three-phase tripping and auto-


reclosing
Reclosing with or without synchro-
check
Automatic switch onto fault logic
Earth fault protection, for both solid-
grounded and high impedance
grounded systems

© ABB Group
November 2010
Slide 4
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 5
Five zone distance protection function
REL650
Typical operate time: 1.5 cycle
Quadrilateral characteristic
One function block with 5 zones
Full scheme protection
Each zone: Six fault loops

Settings for each zone


Resistive and reactive reach
Positive sequence impedance and line angle
Fault resistance (ph-ph and ph-earth)
Earth return compensation factor (magnitude and
angle, zone 1 and zone 2-5)

Forward, reverse or non-directional


Enable/disable different loops

© ABB Group
November 2010
Slide 6
Distance protection function
REL650

Phase selection
Auxiliary function to the quadrilateral distance
protection function
Phase selection and load enchroachment
Selects proper fault loop in the distance
function
Increases possibility to enlarge the reach on
heavily loaded lines
Current-based selection included

Adaptive load compensation


Prevents overreaching at ph-to-earth faults on
heavily loaded lines

© ABB Group
November 2010
Slide 7
Distance protection function
REL650

Direction impedance
Auxiliary function to the quadrilateral distance
protection function
Determine fault direction forward/reverse
Based on positive sequence voltage with
memory

© ABB Group
November 2010
Slide 8
Distance protection function
REL650

Phase preference logic


Auxiliary function to the quadrilateral distance
protection function
To be used in resonance or high impedance
earthed systems
Inhibit tripping of first single ph-to-earth fault
Achieve correct phase selective tripping at
simultaneous earth-faults on
different lines and
different phases

© ABB Group
November 2010
Slide 9
Distance protection function
REL650

Phase preference logic


“Filter” between phase selection and the
distance protection zones
Detection of cross-country fault
Existence of residual current or
Combination of residual current and residual
voltage or
Combination of residual current and phase-
phase voltage or phase-neutral

Phase preference evaluation


At least two out of three phases faulty
Different operation modes
Two cyclic
Six acyclic

© ABB Group
November 2010
Slide 10
Distance protection function
REL650

Power swing detection


System separation, disconnection of heavy
load or trip big generators might lead to
power swings in the system and
the measured impedance can enter the
operation characteristic and
unwanted trip

Detection of power swings


Based on measurement of delta-time when
passing the characteristic (blue and black line)
Block the distance protection
Block the function when residual currents are
present

© ABB Group
November 2010
Slide 14
Distance protection function
REL650

Switch onto fault logic


Gives instantaneous trip at closing a breaker
onto a fault
Based on voltage and current measurement
Automatic activation using dead line
detection or “close circuit breaker”-
information
Three modes where the tripping is based on
low voltage and current or
Impedance or
a combination of the two above

© ABB Group
November 2010
Slide 15
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 16
Line distance protection REL650
Additional functionality

Disturbance recorder and fault locator


Back-up protection
Overcurrent
Directional/Non-directional Phase &
Residual
Instantaneous or time dependent
Breaker failure
Voltage – 2 step time dependent
Phase & residual
Under or over
Frequency – 1 step
Under, over or rate of change
Thermal overload – 1 time constant
Power – 2 step
Directional under or over power
© ABB Group
November 2010
Slide 17
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 18
Line distance protection with Relion® 650 series
Inputs and outputs

Communication & processor module with


14 binary inputs
Analog module:
4I+1I*+5U (* one sensitive current input)
Two binary in-/output modules as
standard:
2*(9BI+9BO)
Standard: 32 BI and 27 BO
Two binary in-/output modules as option:
optional 2*(9BI+9BO)
Maximum 50 BI and 45 BO
Power supply module with 9 binary
outputs

© ABB Group
November 2010
Slide 19
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 20
REL650 – Ready made application configurations

Ready to use for single breaker station


arrangements
A01: Line protection including
quadrilateral impedance characteristic for
three-phase tripping and autoreclosing
A05: Line protection including Mho
impedance characteristic for three-phase
tripping and autoreclosing
A11: Line protection including
quadrilateral impedance characteristic for
single-phase tripping and autoreclosing

© ABB Group
November 2010
Slide 21
Ready made application configuration
REL650-A01/A11
Enabled functions
REL650-A11
Distance protection
Autorecloser and synchrocheck
Disturbance recorder and Fault locator
Trip circuit and fuse failure supervision
Battery supervision
IOC, OC4, EF4, OV

Disabled functions
Power swing detection
Communication schemes
etc.

© ABB Group
November 2010
Slide 22
Ready made application configuration
Backup protection, REL650-A01/A05/A11

Enabled functions
Overcurrent protection
Instantaneous OC protection
Earth fault protection
Instantaneous EF protection
Overvoltage protection
Switch onto fault
Service value functions
Disabled functions
Pole discordance protection
Breaker failure protection
Thermal overload protection
Stub and broken conductor protection
Under current protection
Under- and overpower protection
Under- and loss of voltage
© ABB Group
November 2010
Slide 23
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 24
Relion®
Complete confidence

The Relion® product family offers widest range of products for


protection, control, measurement and supervision for power systems.
To ensure interoperable and future-proof solutions, Relion products
have been designed to implement the core values of the IEC 61850
standard. With ABB’s leading-edge technology, global application
knowledge and experienced support network, you can be completely
confident that your system performs reliably - in any situation.

© ABB Group
November 2010
Slide 25
Relion® protection and control
Highlights in the family

One common tool for all Relion® products,


Protection and control IED manager PCM600
Covers all applications, from generation and
interconnected transmission grids to
secondary distribution kiosks
The performance of protection and control
IEDs meet the comprehensive IEC 61850
communication tasks, for example, GOOSE
messaging for horizontal communication
The IEDs utilize ABB’s unique connectivity
package concept
The Relion product family provides
configured, pre-configured or fully
customized IEDs

© ABB Group
November 2010
Slide 26
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 27
Line distance protection REL650
Summary

Off-the-shelf, ready-made application solutions


Fast and reliable distance protection
Reliable earth fault protection, for both solid-
grounded and high impedance grounded
systems
The selection in between the two different
grounding systems can be made by settings
Versatile back-up protection (same as in REC)
Over current (phase, residual, neg. seq.)
Over voltage
Thermal overload
Breaker failure

© ABB Group
November 2010
Slide 28
Line distance protection REL650
Summary

Autorecloser with synchrocheck


Scheme communication
Single/Three-phase tripping
Disturbance recorder and fault locator
Successor for REL511/316
Full compatibility in scheme communications
between 670 series and 650 series
Advanced Human Machine Interface
User defined names
Settable CT, VT ratings and binary input pick
up voltage
Full IEC 61850 compatibility
Easy ordering of the product as all
functionality is available as standard

© ABB Group
November 2010
Slide 29
Line distance protection with Relion® 650 series
Contents

Introduction – Line distance protection with Relion® 650 series


Line distance protection functions
Additional functionality
Inputs and outputs
Ready made application configurations
Relion® – Complete confidence
Summary
Technology summary

© ABB Group
November 2010
Slide 30
Features
REL650 - Technology summary

Fully IEC 61850 compliant


Protection and monitoring integrated in
one IED
Extensive self-supervision including
analog channels
Four independent parameter setting
groups
Large HMI for visualization of single line
diagrams and on-line measurements

© ABB Group
November 2010
Slide 31
Features
REL650 - Technology summary

Integrated or detachable HMI with 1-5 m


cable for flexible panel mounting
Ethernet interface for fast and easy
communication with PC
Accurate time-synchronization via
SNTP, DNP 3.0, IEC 60870-5-103 and
IRIG-B serial interface
Signal matrix for easy configuration of
binary and analog signals
User management and authority
handling

© ABB Group
November 2010
Slide 32
Configured solutions
REL650 - Technology summary

Single breaker with single-phase


tripping
Single breaker with three-phase tripping
Solid or high impedance earthed
systems (single breaker)

© ABB Group
November 2010
Slide 33
Most important protection functions
REL650 - Technology summary

Distance protection
5 zone full-scheme high-speed line
distance protection with quadrilateral
or Mho characteristics, and with
scheme communication logic and
load encroachment discrimination
Selective phase selection and
automatic switch on to fault logic
Current reversal and weak end
infeed logic
Power swing detection and blocking
Phase preference logic

© ABB Group
November 2010
Slide 34
Most important protection functions
REL650 - Technology summary

Current
Instantaneous phase overcurrent
protection
Instantaneous residual overcurrent
protection
Four step directional phase overcurrent
protection with definite and inverse time
characteristics
Four step residual directional overcurrent
protection with definite and inverse time
characteristics
Two step negative sequence based
directional overcurrent protection

© ABB Group
November 2010
Slide 35
Most important protection functions
REL650 - Technology summary

Current
Directional residual overcurrent
protection with scheme communication
logic
Sensitive directional earth-fault protection
Two step undercurrent protection
Broken conductor check
Thermal overload protection
Breaker failure protection
Stub protection
Pole discordance protection
Power functions
Directional under- and over power
protection
© ABB Group
November 2010
Slide 36
Most important protection functions
REL650 - Technology summary

Voltage
Two step phase- and residual
overvoltage protection with definite and
inverse time characteristics
Two step undervoltage protection with
definite and inverse time characteristics
Loss of voltage check
Frequency protection
Under- and overfrequency protection
Rate-of-change frequency protection

© ABB Group
November 2010
Slide 37
Most important protection functions
REL650 - Technology summary

Power system supervision


Loss of voltage check configured based
on undervoltage protection
Dead line detection included in fuse
failure supervision and switch on to fault
logic

Secondary system supervision


Current circuit supervision
Fuse failure supervision
Breaker close/trip circuit monitoring

© ABB Group
November 2010
Slide 38
Control functions
REL650 - Technology summary

Selective single-phase and three-phase


autorecloser
Synchronizing, synchrocheck and
energizing check
Selectable operator place allocation
Versatile switch with two positions
Selector switch with up to 32 positions

© ABB Group
November 2010
Slide 39
Logic
REL650 - Technology summary

Tripping logic
Trip matrix logic
Configurable logic blocks

© ABB Group
November 2010
Slide 40
Monitoring
REL650 - Technology summary

Disturbance recorder Supervision of AC input


100 disturbances quantities

40 analog channels (30 Insulation gas monitoring


physical and 10 derived) function
96 binary channels Insulation liquid monitoring
Event list for 1000 events function

Disturbance report Circuit breaker condition


monitoring
Event and trip value
recorders Station battery supervision

Fault locator Indication of up to 135 binary


signals via 15 three-color-state
Event counters indication LEDs on up to three
pages

© ABB Group
November 2010
Slide 41
Measurements, metering and communication
REL650 - Technology summary

Measurements
U, I, P, Q, S, f, and cos
AC input quantities with accuracy
better than 0.5%
Metering
Energy metering function for energy
statistics
Pulse counting support for energy
metering
Communication
IEC 61850-8-1 including GOOSE
messaging
DNP 3.0 slave protocol
IEC 60870-5-103 serial communication
© ABB Group
November 2010
Slide 42
Tools and hardware
REL650 - Technology summary

Setting, configuration and disturbance


handling
Protection and control IED manager
PCM600
Hardware
1/2 x 19” 6U height case
10 analog inputs (5 CT and 5 VT inputs)
Universal 1A/5A CT inputs
Communication and processor module
with 14 inputs
Binary input/output module with 9 inputs
and 9 outputs
Possibility to add two optional binary
input/output modules
Power supply modules from 48 to 250 V
DC or 100 to 240 V AC with 9 outputs,
3 of which with trip circuit supervision

© ABB Group
November 2010
Slide 43
© ABB Group
November 2010
Slide 44