Professional Documents
Culture Documents
Issue# 8 Sizing of CB
Issue# 8 Sizing of CB
Issue# 8 Sizing of CB
design
Issue 8
Single-Pole Short-Circuit
Interruption of Molded-
Case Circuit Breakers
Design Advisory
Committee:
Mark Bidinger
Jerry Blanchard
5 UL incorporated
ANSI Standard C37
into the UL 1558
Single-Pole Short- Standard for
Andy Foerster Circuit
Scott Jordan switchgear in 1982
Interruption of
Jeff Qualkenbush Molded-Case and into the UL 1066
Hal Theobald Circuit Breakers standard for low-
Joseph Weigel voltage power circuit
Troy Wurth
With the existing breakers in 1985.
testing standards, These two UL
MCCBs are fully standards provide the
suitable for application basis for third-party
on the various systems witnessing and
when used properly certification to the
within their ratings for ANSI standard.
any condition of a
single fault.The
corner-grounded delta
system is an exception
to this statement.
Questions have been
raised regarding the
capability and
necessity of the circuit
breaker to interrupt a
second, simultaneous
fault.
2
Sizing a
Circuit Breaker
One of the most often asked questions is, Since the current path (including both the
“How do I size a circuit breaker?” A circuit breaker and the conductor) reacts to
commonly misunderstood fact about circuit heat, the overall operating temperature of the
breakers is related to the percentage of equipment becomes a factor in sizing a circuit
loading permitted by the National Electrical breaker in an enclosure. Other factors that
Code (NEC) and the design of the circuit may impact equipment operating temperature
breaker, and why the two may be different. include:
Let’s investigate both aspects.
• Size and location of the enclosure
Circuit Breaker Design
A circuit breaker is designed and evaluated • More than one current carrying device
to carry 100 percent of its rated current for housed in the same enclosure
an indefinite period of time under standard
• Level of current each device is carrying
test conditions. These conditions, per UL
489 (Underwriters Laboratories Standard for • Environmental conditions in the area of the
Molded-Case Circuit Breakers and Circuit equipment
Breaker Enclosures), include mounting a
circuit breaker in free air (i.e., with no Consequently, simply designing a circuit
enclosure) where ambient temperature is breaker to hold 100 percent of its rated
held at 40° C (approximately 104° F). current only addresses a portion of the
Under these conditions, molded-case circuit concern. The equipment must be able to
breakers (MCCBs) are required to not trip safely sustain the heat generated by all
at rated current. sources, without exceeding the temperature
limits in the product test standard. Both of
However, a circuit breaker most frequently is these factors are accounted for by the sizing
applied to equipment at 80 percent of its rules imposed by the NEC.
rated current under NEC Section 384-16
(d). If you understand why this requirement The NEC recognizes that over current
is in place, you’ll be able to apply circuit protective devices will be affected by heat in
breakers correctly. the system. As such, defines the concept of
continuous loads and the 80 percent rule to
Circuit Breaker Characteristic try and offset the effects of heat in the system
Trip Curves when sizing a circuit breaker.
Circuit breaker characteristic trip curves
document how long it takes for specific Continuous Loads
circuit breakers to trip, depending on the To better understand the sizing aspects of a
level of current. Figure 1 shows a typical circuit breaker, you must first clearly
curve for a thermal-magnetic circuit breaker. understand the concept of continuous loads.
The curved portion at the top represents the In Article 100, the NEC defines continuous
time it takes for the circuit breaker to trip on loads as “a load where the maximum current
overload. An overload condition will cause is expected to continue for three hours or
heat buildup around the current path, within more.” It’s critical to understand that this is
the circuit breaker as well as along the power a load at its maximum current uninterrupted
conductors. This heat, which is generated by for at least three hours. Office lighting
the current flow, is actually what causes the typically meets this qualification.
circuit breaker to trip in this region, not
simply the magnitude of the current flow.
This portion of the curve is said to have an
inverse time characteristic, which means the
circuit breaker will trip in less time at higher
levels of current flow.
Example 1
50A continuous load and 125A
non-continuous load
Example 2 Read the rule closely. The 125 percent sizing of the OPCD (or 80
percent loading) is only applicable when continuous loads are
300A non-continuous load involved. Circuit breakers and other OCPDs can be sized at 100
percent of their rating for non-continuous load applications.
A 300A OCPD is acceptable. A 100%-
rated device is not needed since the load 100 Percent-Rated Devices
in non-continuous. The NEC does recognize complete assemblies (including the
OCPDs) that are listed for operation at 100 percent of their rating for
continuous loads. This means that the equipment has undergone
additional testing to verify that it can handle the additional heat rise
Example 3 associated with this level of operation.
200A continuous load A 100 percent-rated circuit breaker and the end use equipment have
OCPD = 100% non-continuous load + been tested to verify that the additional heat generated by the 100
125% continuous load percent continuous loading conditions is safely dissipated. Other
equipment specifications also are driven by the need to dissipate the
(1.00 x 0A) + (1.25 x 200A) = 250A heat associated with the level of heat rise achieved during 100
percent-rated testing. In cases where the temperature at the circuit
Therefore, a 250A OCPD is needed. If a breaker wiring terminals exceeds 50° C during 100 percent rated
100%-rated circuit breaker is selected, a testing, UL 489 requires the use of 90° C insulated wire (sized at the
200A rating is permitted. 75° C ampacity) with these circuit breakers. The circuit breaker must
be marked as such by the manufacturer.
4
Single Pole
Short-Circuit Interruption of
Molded-Case
Circuit Breakers
With the existing testing standards, the which all phase poles are involved in
molded-case circuit breaker (MCCB) is fully interruption in a bolted-fault condition. No
suitable for application on the various individual pole short circuit tests are required
systems when used properly within its ratings except as tested for one-pole units.
for any condition of a single fault. The
corner-grounded delta system is an exception Three-Phase Tests Applied To One-Pole
to this statement and requires that special Interruption. One of the first points to be
care be exercised. Questions have been raised
regarding the capability and necessity of the aware of is that in the three-phase
circuit breaker to interrupt a second, interruption at its interrupting rating, each
simultaneous fault. An examination of each individual pole of a three-pole MCCB
system can provide some guidelines for interrupts the specified available current at
application. phase voltage. Because of the closing angle,
that is the electrical angle at which the short
Voltage Convention circuit is initiated, one pole of the three will
Systems and voltages applied in the U.S. are interrupt a maximum offset (asymmetrical)
detailed in Chapter 3 of the IEEE Red Book. current condition, even though the closing is
A straight rating expressed as a 240V or permitted to be random.
480V would imply a system operating with
no line-to-line voltage exceeding the rating The two operations of this test demonstrate
number and with no leg broken for a the capability of the design to interrupt the
grounding connection (Figure 1 (c) and (d) toughest individual pole conditions at phase
are examples). In a slash rating expressed as voltage and at the available current specified.
120/240V or 480Y/277V, the higher number This result means that an individual pole of
is the greatest line-to-line voltage and the this circuit breaker is capable of interrupting a
lower number is the greatest voltage of any short circuit at its interrupting rating at phase
conductor to ground. Check Article 240-85 voltage, but does not indicate performance for
of the National Electrical Code (NEC) for any voltage above phase voltage.
application requirements.
For example, an individual pole of a three-
Individual Pole Circuit pole circuit breaker with a marked
Breaker Tests interrupting rating of 65kA at 480V or at
Industry Standard Tests. Single-pole 480Y/277V is capable of interrupting a single-
MCCBs are tested at their marked pole fault of 65kA at 277V. ANSI/IEEE
interrupting rating at rated voltage. The C37.13 clause 10.1.4 states, “When a circuit
individual poles of a two- and three-pole breaker is applied in such a way on a single-
MCCBs are tested under available current phase circuit that the system voltage
and voltage conditions indicated in Table 1. impressed across a single pole is no greater
Test details appear in the industry standards. than 58 percent, of any one of the rated
maximum available short-circuit current may
Notice that available current for this test be equal to 100 percent of the corresponding
sequence is generally lower than the three-phase short-circuit rating.”
interrupting rating of the MCCB. There is an
additional test sequence in which the MCCB
is tested specifically for its interrupting
rating. In this sequence, multi-pole MCCBs
are tested only in common operations in
5
Table 1
Individual Pole Short Circuit Test Values for Molded-
Case Circuit Breakers
Systems
Assume that the systems in Figure 1 are
grounded at or near the transformer and at
no other place in the system when the
systems are grounded.
6
The Solidly Grounded WYE Application
(Figure 1a). This system is by far the most Ground Fault Considerations. Most faults
common system in North America. It is that require interruption of a short circuit by
characterized by the fact that any ground- a single pole of a circuit breaker are ground
faults. A small percentage of them are phase-
1A
fault current is immediately and directly
phase current. If it is a short-circuit to-neutral faults. According to Section 9.2.4
condition, the phase overcurrent protective of the IEEE Gray Book:
device will immediately detect it and open
In solidly grounded systems, the line-to-
Figure 1 the circuit. Ground faults or line-to-neutral
faults are the only kinds of faults that would
become individual-pole faults in this system.
ground bolted fault current value is usually
about the equal to the three-phase bolted
fault current value for the location being
The Impedance-Grounded WYE examined. Under certain conditions, such as
(Figure 1b). This system is commonly used in bolted line-to-ground fault at the secondary
industrial process plants or mills where terminal of the connected transformer, the
unexpected interruption of energy can line-to-ground bolted fault current value can
theoretically exceed the three-phase bolted
1B
interrupt the process flow and be extremely
costly. The impedance in the neutral current value (however, tests show that, in
connection to ground limits the ground fault practical systems, the ground fault often is
current in the event of a single fault to less than the bolted three-phase fault
ground. This system permits a single fault to current). Most often, the ground-fault
ground to exist for a short period of time current due to the relatively high impedance
until the process can be shut down to correct of the ground return circuit (i.e., conduit,
the fault. busway enclosure, grounding conductor,
etc.)
The Ungrounded Delta-System
(Figure 1c). This system is occasionally used The system designer needs to be aware of
1C
in industrial applications. As with the the potential ground-fault current that can
impedance-grounded WYE system, this flow. At the terminals of the transformer, a
system will permit a single ground fault to bolted ground fault can be about the same
exist with minimal flow of ground fault value as a bolted three-phase fault. As the
North American current. distance from the transformer increases, the
Electrical Systems potential magnitude of a ground fault
The Corner-Grounded Delta System decreases with the impedance of the
(Figure 1d). This system is in use in some grounding path. The impedance of the
industrial applications. It has the advantages grounding path will be significantly greater
of not requiring overcurrent protection or than that of the primary conductors.
1D
switching devices in the grounded
conductor. However, a ground fault in any
phase other than the grounded phase will
place a fault on the specified phase at line-
to-line voltage. Exercise extreme care in
Solidly-Grounded WYE System
Application considerations are
straightforward for this most common
system (see Figure 2). Any fault that would
selecting circuit breakers for use with this place a short circuit through an individual
system. pole of a MCCB would be either a line-to-
ground fault or a line-to-neutral fault. In
Grounded Delta Variation either case, the fault would return through
1E
(Figure 1e). In this system, the center ground the neutral. The voltage across the circuit
point is occasionally used to provide the breaker pole would remain phase voltage.
single phase 120/240V system shown in
Figure 1f, which is frequently applied in For example, in a 480Y/277V system, the
residential systems. voltage across the pole would be 277V
during the interruption. This interruption
condition has been fully tested in the three-
phase test as indicated above and in
ANSI/IEEE C37.13. The individual-pole
interrupting capability for any one-pole or
three-pole MCCB for this system is its 7
marked interrupting rating.
A two-pole unit used in this will have been rated MCCBs are generally quite appropriate
Figure 2 tested at values indicated in Table 1. In its
common connected short circuit at its
for application on these systems for several
reasons:
Solidly-grounded interrupting rating, the two poles are sharing
WYE with ground the interruption so that voltage across each • Two simultaneous line-to-ground faults are
pole is roughly one half of line-to-line required to create this condition.
fault
voltage.
• The second fault must be on the supply
However, in most cases, the two-pole unit side of the MCCB and on a different phase.
has exactly the same construction as the
three-pole unit and would have an • One or both of the faults is likely to be an
interrupting capability equivalent to that of arcing fault with a significant voltage drop
the corresponding three-pole unit. across it, reducing the available fault current
level. Ground faults are generally high
Impedance-Grounded WYE System impedance faults as indicated in IEEE
This system is different than the solidly Standard 241, 9.2.5. [8]
grounded system addressed in Figure 2 as
A second ground fault at point B will create To further reduce the potential for an
a fault condition of line-to-line voltage that occurrence that may be beyond the capability
will be shared by two MCCBs, N and M. of the MCCB:
The two poles will be sharing the • Detect ground faults and remove them
interruption so that it is not an individual quickly. Sustained ground faults are unsafe
pole interruption. regardless of protection provided.
• Consider series protection of load-side
A second ground fault at point C is on the circuit breakers by overcurrent protective
same phase as the one at point A. It does not devices on their supply side.
create a high-level short-circuit condition.
Low-voltage power circuit breakers and many
A second ground fault at point D does create fusible systems are capable of interrupting the
the potential for the major fault identified higher level ground faults should the designer
above that will be interrupted by one pole of wish to consider them at points in the system.
MCCB M. However, recall that any fault of
concern will be at a level above 8.7kA. At Ungrounded Delta System
this high level, device L may also open in Though ungrounded delta systems have
series with MCCB M and may provide a largely been replaced by the impedance
degree of series protection for MCCB M. If grounded WYE in new installations, many are
the two devices are series rated, full series
protection will be provided, though this is
still in operation. Figure 6
not the condition for which series ratings Corner-grounded delta system Ungrounded delta
were developed. If MCCB L has ground This system has the special characteristic that
fault protection and the fault level is a high one phase is already grounded. A ground
level short circuit, MCCB L will open fault on any ungrounded phase places the full
without an intentional delay along with line-to-line voltage fault on the circuit breaker
MCCB M and may share the interruption. pole in that phase. That is, the second
simultaneous fault is not needed to create the
A second fault at point E, which is a line-to- individual-pole short-circuit. For that reason,
line-to-ground fault, will result in a line-to- the circuit breaker should not be used on
line voltage fault across the pole of MCCB circuits capable of delivering a greater fault
M but will cause MCCB L to open also to current than the level at which individual
share the interruption. Much of the fault poles were short-circuit tested at line-to-line
current will be shunted through point E. voltage.
A second ground fault at point F does create 9
the potential for the major fault that will be
interrupted by one pole of MCCB M.
Figure 7
Corner-grounded
Corner-grounded delta system Conditions in which a line-to-line voltage
This system has the special characteristic fault above the tested level could occur
that one phase is already grounded. A involve two simultaneous ground faults.
ground fault on any ungrounded phase These conditions apply to systems in Figures
places the full line-to-line voltage fault on 1(b) and 1(c) and in some cases to two-pole
a the circuit breaker pole in that phase. That
is, the second simultaneous fault is not
MCCBs in Figure 1(e). The possibility of
this occurrence is minimized by rapid
needed to create the individual-pole short- removal of the first ground fault. The NEC
circuit. For that reason, the circuit breaker does not anticipate protection for conditions
should not be used on circuits capable of other than a single fault.
delivering a greater fault current than the
level at which individual poles were short- Ground fault current is frequently limited
circuit tested at line-to-line voltage. considerably by arc impedance plus ground
path impedance. Experience suggests that
b Protection schemes use either the 3 or 2-
pole units depicted in Figures 7(a) and 7(b),
respectively. With either configuration, the
the ground fault impedance is high. The
system engineer must consider the entire
system and how it is to be operated in
individual pole interrupting ability must be determining whether massive, simultaneous
suitable for the maximum single-phase fault faults to ground are an issue.
current that can be delivered. Some
manufacturers provide circuit breakers rated The corner-grounded delta system of Figure
specifically for application on these systems. 1(d) is one that requires special attention
The 2-pole units are required by NEC 240- and application of MCCBs specifically rated
85 to be marked “1F - 3F” indicating that for that application or de-rated to provided
they have been tested to interrupt a bolted necessary short-circuit protection.
3-phase short circuit using two poles.
Center-point-grounded delta
Figure 8 The system of Figure 8 is seldom used for a
system rated greater than 240 V. Voltage to
ground from the high leg is 0.867 line-to-
Center-point- line voltage. Table 1 short-circuit capability
grounded delta values apply for the pole connected to this
high leg.
Single-phase system
The system shown in Figure 1(f) is the
120/240 V configuration most commonly
encountered. Single pole circuit breakers
rated 120 V or 120/240 V connected line-to-
neutral are fully tested for application on this
system. Two-pole circuit breakers rated
120/240 V or 240 V and connected to each
end of the transformer are fully tested for
application.
Conclusion
Individual-pole tests of MCCBs are done at
standard levels, which are generally lower
than the marked interrupting rating of the
unit. However, three-phase tests done at the
interrupting rating are in some cases a
rigorous test of individual pole capability.
10
Table 2
Molded-case Circuit Breaker Single Pole
Interruption and Application for 3-Phase Systems
System Condition Maximum Voltage 1-Pole MCCB 2-Pole MCCB 3-Pole MCCB
Across Pole
Solidly-grounded Single L-G or L-N VPH Fully tested at IR. Fully tested at IR if Fully tested at IR.
WYE. Figure 1(a). fault. same as 3-pole unit.
Otherwise tested at
VL per Table 1.
Impedance- Single L-G or L-N VPH Fully tested at IR. Fully tested at IR if Fully tested at IR.
grounded WYE. fault. same as 3-pole unit.
Figure 1(b). Otherwise tested at
VL per Table 1.
Impedance- L-G fault on load side VL Fully tested at IR. Tested at Table 1 Tested at Table 1
grounded WYE. of MCCB. Second value. value.
Figure 1(b). simultaneous fault See note 1. See note 1.
on different phase on
line side of MCCB.
Figure 4.
Ungrounded delta. L-G fault on load side VL Fully tested at IR. Tested at Table 1 Tested at Table 1
Figures 1(c) and 6. of MCCB. Second value. value.
simultaneous fault See note 1. See note 1.
on different phase on
line side of MCCB.
Corner-grounded Single L-G fault. VL Fully tested at IR. Tested at Table 1 Tested at Table 1
delta. Figure 1(d). value. value.
Use only MCCBs
marked “1F-3F.”
Center-point Single L-G fault from VPH Fully tested at IR. Tested at Table 1 Tested at Table 1
grounded delta. high leg. value for pole value for pole
Figure 1(e). connected to high connected to high
leg. leg.
Designations:
IR – Interrupting rating VL – Line-to-line voltage VPH - Phase voltage
Notes:
1. Requires two simultaneous faults for current above tested level. Even with simultaneous faults, impedance or additional 11
overcurrent protective device in the fault path limits current level.
ANSI C37 Standard
&
UL 489 Standard
Comparison
Since Ben Franklin discovered electricity, people have been
struggling to harness its energy and use it safely. As the use of
electricity spread into homes and buildings, the need for personal
safety and protection against fires became increasingly clear.
n Performance Testing
The UL 489 and ANSI C37 Standards
UL and ANSI Standards differ in four basic require the same basic tests, including:
areas: philosophy, construction, performance
testing and certification. • Dielectric
• Calibration
n Philosophy • Overload
The scope of the UL 489 MCCB Standard • Temperature
includes miniature circuit breakers (MCBs) • Endurance
and insulated case circuit breakers (ICCBs). • Short-circuit
These circuit breakers are typically rated 10A
to 6,000A and up to 600Vac and 500 Vdc. Both the UL 489 and ANSI C37 Standards
Circuit breakers designed and tested to this demonstrate the circuit breaker’s ability to
standard typically exhibit the following protect conductors under overload or short-
characteristics: circuit conditions. The major differences in
performance testing occur during the details
• Sealed molded case and sequences of the tests for overload,
• Little or no maintenance temperature, endurance and short-circuit
• No user replaceable parts conditions.
• Good performance and reliability
• Long service life • Overload Testing
Overload Testing is done to demonstrate
The scope of ANSI C 37 LVPCB Standard making and breaking current values that
includes two- or three-pole stationary and might be obtained when initially energizing a
draw-out circuit breakers. The specifications motor load. Each time the circuit breaker is
of these circuit breakers are 254, 508 or 635 closed and opened on a high current load
Vac maximum, fused or unfused, manually (600 percent), the contact surfaces are
or power operated, with or without subjected to arcing and heat. This action
electromechanical or electronic trip units. stimulates an accelerated life test to make
These breakers typically have the following sure the contacts provide adequate
characteristics: conductivity through many operations. The
UL 489 Standard tests all circuit breaker
ratings with significant operations to ensure 13
the design is capable of a long service life The ANSI C37 Standard requires that a
with no maintenance. The ANSI C37 three-pole circuit breaker be tested under
Standard tests circuit breakers rated only up three-phase conditions at the maximum
to 2000A. interrupting rating and also that each
individual pole be tested at 87 percent of the
• Temperature Testing maximum interrupting rating. Both the
The UL 489 Standard allows for two types three-phase and the individual-pole tests are
of ratings. Standard circuit breakers cannot conducted at rated maximum voltages of
exceed a maximum of 50° C temperature 254V, 508V and 635V. The ANSI Standard
rise at the sire terminal connection at 100 also includes a separate sequence to evaluate
percent current in 40° C open air. 100 the short-time withstand current of the
percent rated circuit breakers may have a circuit breaker. The short-time withstand
temperature rise of 60° C at the sire terminal current is a high level current that can be
connection in the smallest allowable maintained for 0.5 seconds without damage
enclosure if the circuit breakers are to the circuit breaker.
connected with wire rated at 90° C wiring
insulation sized to the 75° C chart (Table Certification
310-16, NEC). The ANSI C37 Standard Certification tests to the UL 489 Standard
requires a maximum of 55° C temperature are witnessed by UL engineering
rise at 100 percent in the smallest enclosure representatives. At the successful completion
and a maximum of 85° C temperature rise of the test program, UL permits circuit
on the contacts. breakers to bear a UL Listing mark. These
circuit breakers are required to undergo
• Endurance Testing subsequent follow-up testing on a regular
Circuit breakers tested to the UL 489 basis: quarterly, semiannually or biannually
Standard must pass a significant number of depending on the circuit breaker size and
operations without any maintenance. This quantities produced. All follow up tests are
test verifies that the design is capable of a witnessed by UL field representatives.
long service life. The ANSI C37 Standard
tests circuit breakers for further operations, Certification tests to the UL 1066 Standard
but then allows for maintenance of the (which include the requirements of the ANSI
circuit breaker at relatively short intervals. C37 Standard) are witnessed by UL
(Note: no manufacturer currently offers engineering representatives. At the
225A or 600A frame circuit breakers tested successful completion of both UL test
to ANSI C37). programs, UL permits the circuit breaker to
bear a UL Listing mark, combined with the
• Short-Circuit Testing product identity. While UL conducts follow-
The short-circuit tests reflect differences in up inspections on the UL 1066 Standard
the philosophies between the UL and ANSI tested products to ensure that the
standards. The UL 489 Standard requires construction has not changed from that,
that the tests be conducted at several values which was originally tested, they do not
of short-circuit current. A separate test require subsequent follow-up testing.
sequence evaluates the maximum
interrupting rating claimed by the
manufacturer. Tests are conducted at the
rated voltage(s) of the circuit breaker, which
is typically 240V, 480V or 600V.
Voltage and Current Rated voltage with low, medium and high Rated current at the three voltage levels: 254,
level current. 508 and 635Vac
Operations Open – close/open on all three poles Open – close/open on all three poles. First open
at closing angle to ensure peak current of 2.3 x
rated current in one phase
Open – close/open on each individual pole Open – close/open individual pole at 87% of
at reduced current level rated current
www.SquareD.com
Document Order #0101DM0002