CLIENT- DUGDA CONSTRUCTION PLC

PROJECT GET-AS REAL ESTATE


TEST OBJECT Concret Cube(15*15*15)
LAB. NO. 50378/2019
SLUMP (mm) 36
CLASS OF CONCRETE C-30
CEMENT TYPE DANGOTE OPC
REPORTED ON 5/7/2019

TIPS SHOULD CAREFULLY CONSIDERED DURING THE USE THIS MXI DESIGN TEM

- NEVER TOUCH THE CELLS WITH YELLOW BACKGROUND


- THE DATA WITH RED BACKGROUND SHOULD BE CAREFULLY FILLED IN ACCORDANCE WITH THE DESIG

ABBREVATIONS

Ga=weighted average specificgravity of combined fine and coarse aggregate


GC=specific gravity of cement(3.15)

CM=cement requirment,kg/m3
WM =mixing water requirment,kg/m3
UM= unit weight of mixture
HIS MXI DESIGN TEMPLATE

ANCE WITH THE DESIGN REQUIREMENT


Err:509
ORGINAL (Air dried) -

OVEN DRY 3915.04

WASH OVEN DRY

loss

SIEVE SIZE Weight Percentage CUMULATIVE Goveming

Alternate Standard Retained in Retained Wt. Passing % Passing % Retained spec's %

Inches mm. g. g. passing

3 - 0 - 3915.04 100

50 0 0.0 3915.0 100.0 0.0

37.5 0 0.0 3915.0 100.0 0.0

2 25 1801.73 46.0 2113.3 54.0 46.0

19.5 1232.94 31.5 880.4 22.5 77.5

3/4 12.5 676.98 17.3 203.4 5.2 94.8

3/8 9.5 163.67 4.2 39.7 1.0 99.0

No.4 4.75 15.38 0.4 24.3 0.6 99.4

No.10 2.36 2.8 0.1 21.5 0.6 99.4

No.30 1.18 0 0.0 21.5 0.6 99.4

0.600 0.0 0.0 21.5 0.6 99.4

0.300 0.0 0.0 21.5 0.6 99.4

0.150 0.0 0.0 21.5 0.6 99.4

Pan 21.54 0.6 914.0

Wash Loss 0.0

Total 3915.04 100.0

Nominal Aggregate Size 37.5 4.0

GaddisE
I. Recommended slump for various type of construction
slump,mm
Type of construction maximum
Renforced foundation wals and footing 75
Plain footings,caissons and substructure walls 75
Beams and renforced walls 100
Building columns 100
Pavements and slabs 75
Mass concrete 75

II. Appropriate mixing water and air content requirments of slump and nominal m

Water,kg/m3 of concrete for indicated nominal maximum sizes of aggreg


Slump,mm 9.6 12.5 19 25 37.5
Non - air - entrained concrete
25 to50 207 199 190 179 166
75 to 100 228 216 205 193 181
150to 175 243 228 216 202 190
Appropriate amount of entrapped air in non
- air entrained concrete percent 3 2.5 2 1.5 1

III. Relationships between water - cement ratio and compressive strength of conc

water cement ratio by mass


Non air
Compresive strength at 28 days Mpa Air entrained
entrained
concrete
40 concrete
0.42 -
35 0.47 0.39
30 0.54 0.45
25 0.61 0.52
20 0.69 0.60
15 0.79 0.70

IV. 6
Volume of dry rodded coarse aggregete per unit
Nominal maximum size of volume of concrete for different finness moduli of
fine aggregate
aggregate , mm 2.40 2.60 2.80 3.00
9.5 0.50 0.48 0.46 0.44
12.5 0.59 0.57 0.55 0.53
19 0.66 0.64 0.62 0.6
25 0.71 0.69 0.67 0.65
37.5 0.75 0.73 0.71 0.69
50 0.78 0.76 0.74 0.72
75 0.82 0.80 0.78 0.76
150 0.87 0.85 0.83 0.81
V. Estimate of Mass of Fresh Concrete
Nominal maximum size of
First estimate of concrete unit mass,kg/m3
aggregate,mm
Non air entrained concrete
Air entrained concrete
9.5 2280 2200
12.5 2310 2230
19 2345 2275
25 2380 2290
37.5 2410 2350
50 2445 2345
75 2490 2405
150 2530 2435
slump,mm
minimum
25
25
25
25
25
25

f slump and nominal maximum size of aggregates

minal maximum sizes of aggregate


50 75 150
ed concrete
154 130 113
169 145 124
190 160 -

1 0.3 0.2

essive strength of concrete

nt ratio by mass
Air entrained
concrete
-
0.39
0.45 460
0.52
0.60 276.7
0.70
Concrete Mix Design
concrete strength class required to designed
Concrete class
Concrete Concrete
C-10 10 C-30 30
C-15 15 C-35 35
C-20 20 C-40 40
C-25 25 C-50 50

TIP DESIGNED CONCRETE 30

TIP CEMENT TYPE = DANGOTE OPC


CONCRETE CLASS C-30
Aggregate Raw Data
Sr.NO coarse aggregate Fine Aggregate
1 SSD 2.6 2.45
2 NMC 1.3 4.8
3 W.ab 1.2 1.25
4 nominal size 37.5 FM 3.4
5 Dry Rodded 1630 1285
NOMINAL SIZE 37.5 FM 3.4

Amount of Water Required


Amount of Water Per m3 of Fresh Concrete 166.0

Water Cement Ratio


W/C 0.415

Amount of cement needed per m3 of fresh concrete

Cement per 1m3 of fresh concrete = 400

Unit mass of fresh concrete kg/m3(UM)=

UM = 2410.0
Amount of Course Aggregate Needed per m3 of concrete

C. aggregate Mass =
percenatge of course aggregate needed
NOMINALaggregate size RATIO MASS

37.5 0.69 1125

THE TRIAL MIX PROPORTION FOR THE 1M 3 OF CONCRETE

CEMENT 400
WATER 166.0
COURSE AGGREGATE 1124.7

FINE AGGREAGTE 719.3

THE TRIAL MIX PROPORTION FOR THE 0.027M 3 OF CONCRETE


USING MASS METHOD

CEMENT 10.8
WATER 3.8
COURSE AGGREGATE 30.7
FINE AGGREAGTE 19.7

TIP THE AMOUNT OF WATER ADDED IN ML= 1700


SLUMP VALUE = 36

CEMENT 400
WATER 203.3
COURSE AGGREGATE 1138.7
FINE AGGREAGTE 728.3

THE TRIAL MIX PROPORTION FOR THE 1M 3 OF CONCRETE


USING VOLUME METHOD USING LOOSE UNIT WEIGHT

INGREDIENT UNIT WEIGHT LOOSE VOLUME


CEMENT 1300 0.31
COURSE AGGREGATE 1429 0.80
FINE AGGREGATE 1305 0.56

MIX PROPORTION
Mix proportion, loose

METHOD Water Cement F. agg C. agg


BY MASS 0.51 1 1.10 1.0
BY VOLUME 1 2.2 3.1

METHOD Water Cement F. agg C. agg


BY MASS 0.51 1 1.10 1.0
BY VOLUME 1 2.0 3.0

METHOD Water Cement F. agg C. agg


BY MASS 0.51 1 2.00 3.0
BY VOLUME 1 2boxes 3boxes

METHOD Water Cement F. agg C. agg


BY MASS 0.51 1 2boxes 3boxes
BY VOLUME 1 7boxes 7boxes
OPC PPC
Ga 2.6 2.6

Gc 3.15 3.15

TE OPC

Ga=weighted average specificgravity of combined fine and coarse aggregat


GC=specific gravity of cement(3.15)

Where CM=cement requirment,kg/m3


WM =mixing water requirment,kg/m3

0.73
0.75

FALSE

A=air ,percentcontent
CRETE

course aggregate fine Aggregate water

1138.7 728.3 140.360867673852

ONCRETE

0.003375
F 0.027 0.02025

CRETE
IGHT

LOOSE VOLUME PER BAG


0.032
0.100
0.070
ed fine and coarse aggregate
0.01*10.8

8.95
TEST RESULT FOR NATURAL SAND

I. SIEVE ANALYSIS (ASTM C136)


PARTICLE SIZE DISTRIBUTION CURVE
100

90

80

SIEVE SIZE %
70
(MM.) PASSED
60
9.50 100

% PASS
4.75 93 50

2.36 78 40

1.18 60 30

0.60 23
20

0.30 4
10

0.15 1
0
100.00 10.00 1.00 0.10 0.01

PARTICLE SIZE IN mm

II. SILT AND CLAY CONTENT , ORGANIC IMPURITIES,SOUNDNESS & UNIT WEIGHT (NATURAL SAND)

No. Test Type Sample source Test Method Test Result

1 Silt ans Clay Content,% ASTM C117 4.34

-
2 Organic Impurities ASTM C40 O2
3 Soundness AASHTO T-104 5.00
4 Unit Weight,kg/m3 ASTM C29 1310.00 -

III. SPECIFIC GRAVITY AND WATER ABSORPTION (ASTM C128)

Bulk Apparent Water

Sample source
Sr. Material Type specific specific Absorption

No. gravity gravity (%)


(SSD)

1 Project site Natural Sand 2.45 2.53 2.06

REPORTED BY : APPROVED BY :

CLIENT : DUGDA CONSTRUCTION PLC

PROJECT : GET-AS REAL ESTATE


TEST OBJECT : Natural Sand
SAMPLE SOURCE : -
GEOTECHNICAL ENGINEERING SERVICE LAB. NO. : 50378/2019
P.O.Box 110246, Addis Ababa Ethiopia TEST FOR : Quality
Tel., +251 11 860 36 99, +251 11 860 37 83/84, Fax: +251 860 36 99 REPORTED ON : 14/05/2019
E-mail: ar-con@ethionet.et
TEST RESULT FOR COARSE AGGREGATE

I. SIEVE ANALYSIS (ASTM C136)

PARTICLE SIZE DISTRIBUTION CURVE


100.00
SIEVE SIZE %
(MM.) PASSED 90.00

50.00 100.00
37.50 100.00 80.00

25.00 53.98
70.00
19.50 22.49
12.50 5.20 60.00

9.50 1.01

% PASS
50.00
4.75 0.62
2.36 0.55 40.00

30.00

20.00

10.00

0.00
100.00 10.00 1.00 0.10 0.01

PARTICLE SIZE IN mm

II. FLAKINESS INDEX, SOUNDNESS,ACV & UNIT WEIGHT.

No. Test Type Sample source Test Method Test Result

1 Fakiness Index % BS 812 17.88

Aggregate Crushiing
2 AASHTO T-210 23.02
Value

3 Soundness - AASHTO T-104 0.3

Unit weight,Rodded
1630
(kg/m3)
4 ASTM C29
Unit weight,Loss(kg/m3) 1430

III. SPECIFIC GRAVITY AND WATER ABSORPTION (ASTM C127)

Bulk specific Apparent specific Water


Sr. No. Sample source Material Type
gravity (SSD) gravity Absorption (%)

Coarse
1 Project Site 2.64 2.70 1.24
Aggregate

REPORTED BY : APPROVED BY :

CLIENT: DUGDA CONSTRUCTION PLC

PROJECT: GET-AS REAL ESTATE


TEST OBJECT: Coarse Aggregate (02)
SAMPLE SOURCE: -
GEOTECHNICAL ENGINEERING SERVICE LAB. NO.: 50378/2019
P.O.Box 110246, Addis Ababa Ethiopia TEST FOR: Quality Test
Tel., +251 11 860 36 99, +251 11 860 37 83/84, Fax: +251 860 36 99 REPORTED ON: 14/05/2019
E-mail: ar-con@ethionet.et

722147250.xlsx
TEST RESULT OF CONCRETE COMPRESSIVE STRENGTH

Compressive Strength
SR No. Date Poured Date Tested AGE (days) Load (KN) Compressive Strength (kg/cm2)
(MPA)

1 16/09/2019 23/09/2019 7 695.08 314.91 30.89

2 16/09/2019 23/09/2019 7 680.48 308.29 30.24

3 16/09/2019 23/09/2019 7 686.36 310.96 30.50

AVG. 311.39 30.55

REMARK:- Type of cement used Dangote Opc


Class of concrete C-30
Slump(mm) 39
-The given proportion will work if the original materials will not be changed.
Amount of material in kg in Cubic meter of fresh concrete
-During the trial mix 50% natural sand and 50% aggregate "00" is used

Coarse aggregate 1138.68


Fine aggregate 728.31
Cement 400.00
Water 203.32

Ingredient Proportion per one bag of cement (50 kg)

Cement 1 bag (50 Kg)


Fine Aggregate 2 boxes
Aggregate 3 boxes
Box Size, cm 40*50*16

Reported by : Approved by :

CLIENT : DUGDA CONSTRUCTION PLC


PROJECT : GET-AS REAL ESTATE
TEST OBJECT : Concret Cube(15*15*15)
LAB. NO. : 50378/2019
GEOTECHNICAL ENGINEERING SERVICE SLUMP (mm) : 39
P.O.Box 110246, Addis Ababa Ethiopia CLASS OF CONCRETE : C-30
Tel., +251 11 860 36 99, +251 11 860 37 83/84, Fax: +251 860 36 99 CEMENT TYPE : DANGOTE OPC
E-mail: ar-con@ethionet.et REPORTED ON : 23/09/2019
TEST RESULT OF CONCRETE COMPRESSIVE STRENGTH

Compressive
Compressive
SR No. Date Poured Date Tested AGE (days) Load (KN) Strength
Strength (MPa)
(kg/cm2)

1 01/07/2019 29/07/2019 28 625.67 283.46 27.81

2 01/07/2019 29/07/2019 28 624.30 282.84 27.75

3 01/07/2019 29/07/2019 28 649.66 294.33 28.87

AVG. 286.88 28.14

REMARK:- Type of cement used HABESHA Ppc


Class of concrete C - 30
Slump(mm) 40
- The given proportion will work if the original materials will not be changed.
Amount of material in kg in Cubic meter of fresh concrete

Coarse aggregate 1184.00


Fine aggregate 698.10
Cement 400.00

Water 118.52

Ingredient Proportion per one bag of cement (50 kg)

Cement 1 bag (50 Kg)


Fine Aggregate 2 boxes

Aggregate 3 boxes

Box Size, cm 40*50*17

Reported by : Approved by :

CLIENT Solomon
Silte Tilahun B.C
Development association G+9 Mixed use
PROJECT Building
TEST OBJECT Concret Cube(15*15*15)
LAB. NO. 49586/2019
GEOTECHNICAL ENGINEERING SERVICE SLUMP (mm) 40
P.O.Box 110246, Addis Ababa Ethiopia CLASS OF CONCRETE C - 30
Tel., +251 11 860 36 99, +251 11 860 37 83/84, Fax: +251 860 36 99 CEMENT TYPE HABESHA Ppc
E-mail: ar-con@ethionet.et REPORTED ON 29/07/2019
TEST RESULT OF C

SR No. Date Poured

1 01/07/2019
2 01/07/2019
3 01/07/2019

REMARK:- Type of cement used


Class of concrete
Slump(mm)
- The given proportion will work
Amount of material in kg in Cu

Coarse aggregate
Fine aggregate
Cement
Water

Ingredient Proportion per one

Cement
Fine Aggregate
Aggregate
Box Size, cm

Reported by :
GEOTECHNICAL ENGINEERING SERVICE
P.O.Box 110246, Addis Ababa Ethiopia

Tel., +251 11 860 36 99, +251 11 860 37 83/84, Fax: +251 860 36 99

E-mail: ar-con@ethionet.et
RESULT OF CONCRETE COMPRESSIVE STRENG

Date Tested AGE (days) Load (KN)

29/07/2019 28 625.67
29/07/2019 28 624.30
29/07/2019 28 649.66
AVG.

ent used HABESHA Ppc


ncrete C - 30
40
roportion will work if the original materials will not be
aterial in kg in Cubic meter of fresh concrete

egate 1184.00
ate 698.10
400.00
118.52

Proportion per one bag of cement (50 kg)

1 bag (50 Kg)


2 boxes
3 boxes
40*50*17

CLIENT
PROJECT
TEST OBJECT
LAB. NO.
SERVICE SLUMP (mm)
a CLASS OF CONCRETE
+251 860 36 99 CEMENT TYPE
REPORTED ON
ESSIVE STRENGTH

Compressive Compressive
Strength Strength
(kg/cm2) (kg/cm2)
283.46 27.81
282.84 27.75
294.33 28.87
286.88 28.14

rials will not be changed.


oncrete
Approved by :

Solomon Tilahun B.C


Silte Development association G+9 Mixed use
Building
Concret Cube(15*15*15)
49586/2019
40
C - 30
HABESHA Ppc
29/07/2019