V050004902
Version:A00
Equipment
Mass of equipment mp kg
Fyp N
Fzp N
Load
Wind load(34m/s) pr Pa
Standard adopted:
Level::
Damping ratio:
m
Horizontal acceleration Ag Ag = 16.181
2
s
3. Calculation and analysis
Equipment
2 2 3
Terminal load Fp := Fxp + Fyp = 1.458 10 N
3
Fzp = 1 10 N
3
Weight load Wp := mp 9.8 = 3.205 10 N
3
Horizontal load Np := Fxwp + Fxeqp + Fp = 9.531 10 N
4
Vp := Fyeqp + Wp + Fzp = 1.055 10 N
Vertical load
4.Check of insulator
D 2 - d 2
A1 := 3.14
p p
= 3.14 10
4
mm
2
Section area: 4
D 4 - d 4
Moment of inertia: I := 3.14
p p
= 7.85 10
7
mm
4
64
D 4 - d 4
p p
Bending modulus of Winsulator := 3.14
5 3
= 7.85 10 mm
Section : 32 Dp
Mp 1000 Vp
MPa
Stress: σinsulator := + = 8.149
2 Winsulator 2 A1
(
Conclusion of insulator := if σinsulator < 49 , "OK" , "no" )
Conclusion of insulator = "OK"
5. Check of connecting bolt
Distance lo mm
2
Aeo mm
Effective area
3.14 D 4
o 3 4
Moment of inertia of Io := = 3.215 10 mm
64
single bolt:
2
lo 6 3
Moment of inertia of Ito := Io + Aeo no = 5.094 10 mm
2
all bolts:
Ito 4 3
Bending modulus of Wto := 2 = 6.408 10 mm
section of all bolts: lo
Mp 1000 Vp
Stress for support(MPa): σt := + = 104.336 MPa
2 Wto 2 no Aeo
( )
(
Conclusion of bolt := if σt < 400 , "OK" , "no" )
Conclusion of bolt = "OK"