Professional Documents
Culture Documents
Final Exam
Final Exam
Final Exam
EE 413- EE Electives 1
Final Examination (First term, SY 2022-2023)
B Phase-to-phase
B Transformer
C Overhead lines
D Underground cable
4.Which portion of the power system is least prone to faults?
A Alternator
B Switchgear
C Transformers
D Overhead lines
5.The magnitude of fault current depends upon
A Total impedance up to fault
B Phase-to-phase
C Two-phase-to ground
B Double-line-to-ground fault
C Line-to-line fault
D Single-line-to-ground fault
8.For a fault at the terminals of synchronous generator, the fault current is maximum for a
A 3-phase fault
C Line-to-ground fault
D Line-to-line fault
9.Series reactors are used to
A Improve the transmission efficiency
B Negative-sequence components.
C Zero-sequence components.
B 33.3 A
C 66.6 A
D 100 A
C Line-to-line
B Delta/star
C Star/grounded star
D Delta/delta
23.If the positive, negative ? and zero-sequence reactance of an element of a power system are 0.3, 0.3 and 0.8
pu respectively, then the element would be a
A Synchronous generator
B Synchronous motor
C Static load
D Transmission line
24.If all the sequence voltages at the fault point in a power system are equal, then the fault is a
A Three-phase fault
C Line-to-line fault
B L - L - L
C L - L
D L - L - G
26.The zero-sequence current of a generator for line-to ground fault is j2.4 pu. Then the current through the
neutral during the fault is
A J2.4 pu
B J0.8 pu
C J7.2 pu
D J0.24 pu
27.One current transformer (CT) is mounted over a 3-phase, 3-core cable with its sheath and armour removed from
the portion covered by the CT. an ammeter placed in the CT secondary would measure
A The positive-sequence current
B 4.033 ohm
C 5.5 ohm
D 12.1 ohm
29.The zero sequence driving point reactance at the bus is
A 2.2 ohm
B 4.84 ohm
C 18.18 ohm
D 22.72 ohm
30.The primary function of a fuse is to
A Open the circuit
C No ageing effect
B Arcing time
D None of these
33.If a combination of HRC fuse and a circuit breaker is employed, the circuit breaker operates for
A Short-circuit current
B Isolator
C Circuit breaker
D Air-break switch
35.A Circuit breaker normally operates
A When the power is to be supplied
C Relay operates then successively the isolator and the Circuit breaker
D Isolator operates, then successively the Relay and the Circuit breaker
37.The initiation of electric arc at the instant of contact separation is caused by
A Thermionic emission of electrons
B Copper
C Silver
D Tungsten
39.The heat produced at the contact point owing to flow of electric current is least affected by
A Temperature of the surrounding medium
B Contact resistance
B Contact resistance
C Thermal conductivity
D None of these
41.In a Circuit Breaker Contact wipe is necessary
A To decrease the speed of opening of the CB
B Non-inflammability
B Energizing of the trip circuit and the arc extinction on an opening operation.
D Energizing of the trip circuit and the parting of primary arc contacts.
49. The total clearing time for a high speed circuit breaker is around
A Few minutes
B Few seconds
C 1 to 2 cycles
D 5 to 20 cycles
50.The resistance of an electric arc can be increased by
A Increasing the concentration of ionized particles.
B Power factor
C Armature reaction
D All of these
53.In a circuit breaker the current that exists at the instant of contact separation is called the ________
current.
A The Re-striking current
C Quenching arc
D None of above
58.The chances of arc interruption in subsequent current zeros
A Increase in case of ABCB but decrease in OCB.
C non-repeated duty
B 0.5 s
C 50 Ms
D 100 Ms
63.The minimum oil circuit breaker has less volume of oil because
A The oil between the breaker contacts has greater strength.
C Solid insulation is provided for insulating the contacts from the earth.
B Gas cylinders.
D Solid form.
70.The current chopping tendency is minimised by using Sulphur hexafluoride gas at relatively
A Low pressure and high viscosity.
B Temperature
C Short circuit
D Overvoltage
73.For remote operation, the circuit breaker must be equipped with
A Inverse time trip
B Shunt trip
D All of these
74.Which of the following circuit breakers is generally used in railway electrification?
A Air-blast circuit breaker
B Air-blast CB
C Vacuum CB
D Sulphur hexafluoride CB
76.Keeping in view the cost and overall effectiveness, the following circuit breaker is best suited for
capacitor bank switching
A Vacuum
B Air-blast
C Sulphur hexafluoride
D Oil
77.Which of the following circuit breakers has the lowest voltage range?
A Sulphur hexafluoride circuit breaker
C Air-blast
D Air break
79.Which of the following circuit breakers has high reliability and negligible maintenance?
A Air-blast
B Sulphur hexafluoride
C Oil
D Vacuum
80.Which of the following circuit breakers take minimum time in installation?
A Air-blast
B Minimum oil
C Bulk oil
D Sulphur hexafluoride
81.Where voltages are high and current to be interrupted is low, the circuit breaker preferred is
A Air-break
B Vacuum
C Oil
D Air-blast
82.The circuit breaker preferred for rural electrification in a country like India with complex network is
A Air-break
B Oil
C Vacuum
D Minimum oil
83.The most suitable circuit breaker for short line fault without switching resistor is
A Minimum oil
B Air-blast
C Sulphur hexafluoride
D Air-break
84.The rating of a circuit breaker is usually determined on the basis of ___________ fault.
A Symmetrical
B Line to line
B 1 s to 2 s.
C 2 s to 3 s.
D Greater than 3 s.
86.Circuit breakers usually operate under
A Steady short-circuit current.
D None of these.
87.The re-striking voltage is measured in
A RMS value
B Peak value
C Instantaneous value
D Average value
88.The making and breaking currents of 3-phase ac circuit breakers in power system are respectively in what
form ?
A Rms value, rms value
C Rms value
B The product of rated symmetrical breaking current (kA) and rated voltage (kV).
D Twice the value of rated current (kA) and rated voltage (kV).
90.The making to breaking current ratio for an EHV circuit breaker is
A More than 1.
B Equal to 1.
C Less than 1.
D A negative number
91.The making capacity of a circuit breaker is
A Less than the symmetrical breaking capacity of the breaker.
B 3,600 A
C 35 kA
D 104.8 kA
93.A three-phase breaker is rated 2,000 MVA, 33 kV. Its making current will be
A 35 kA
B 49 kA
C 70 kA
D 89 kA
94.Which of the following statements is not correct?
A Arc chutes are used in air break circuit breakers.
B Air-blast circuit breakers are employed for high voltage traction system.
B Minimum oil
C Vacuum
B Ingress of moisture
C Spring defective
B Circuit breakers.
B No current
C Charging current
D Load current
103.The oil switches may be
A Remote or manually controlled.
B Used for capacitor switching, street lighting control and automatic disconnect on power failure.
B Ensure circuit breaker is open ? open earthing switch ? close isolator ? close circuit breaker.
B To increase a reach
B Measuring Current
C Measuring Constantly the electrical quantities which differ during normal and abnormal conditions.
D None of the above.
108.The actuating quantity for the relays may be
A Magnitude
B Frequency
C Phase angle
D Any of these
109.The protective relay is provided to
A Provide additional safety to the circuit breaker in its operation.
B Close the contacts when the actuating quantity attains a certain predetermined value.
C Spring tension
D All of these
111.Plug setting of an electromagnetic relay can be altered by varying
A Number of ampere turns.
D None of these.
112.The torque produced in shaded pole structure induction type relay is
A Proportional to the square of the current.
C Induction-cup structure
B Thermal conductivity
C Coefficients of expansion
B Heavy loads
C Earth fault
D All of these
116.Buchholz relay is
A Located in the conservator tank.
B Instrument transformers
C Distribution transformers
D Oil immersed power transformers of rating above 500 kVA
118.The Buchholz relay protects a transformer from
A Types of internal faults
D None of these
119.In an Overcurrent protection the setting of the earth fault relay is
A More than the phase fault relay
B Transformers
C Alternators
B Overloads
D Electromagnetic damping
123.Earth fault relays are
A Directional relays
B Non-Directional relays
D None of these
124.The domains of power system where directional overcurrent relay is indispensable are
A In case of parallel protection
B Positive sequence impedance of the line from relay up to the fault point.
D Zero sequence impedance of the line from relay up to the fault point.
127.If the fault occurs near the relay, the V/I ratio will be
A Lower than that of if the fault occurs away from the relay.
B Induction-cup structure.
D None of above
130.An impedance relay is a
A Voltage restrained overcurrent relay.
B Over reaches
C Reach unaffected
D None of these
133.The structure used in reactance relays is
A Induction cup
B Directional relay
C Differential relay
D None of these
138.A mho relay is a
A Voltage restrained directional relay.
B Directional relay
C Reactance relay
B Admittance relay
C Mho relay
D Reactance relay
144.The relay used for phase fault protection of short transmission lines is
A Reactance relay
B Impedance relay
C Mho relay
D IDMT relay
145.Mho relay is usually employed for the protection of
A Short lines only
D Any line
146.Where severe synchronising swing occur, the relay employed is
A Impedance relay
B Mho relay
C Reactance relay
D Induction relay
147.Which of the following relays has inherent directional characteristic?
A Mho
B Reactance
C Impedance
B Overcurrent
C Reverse current
D Reverse power
150.Undervoltage relays are mainly used for
A Motor protection
B Transformer protection
C Generators
D All of these
151.In a biased differential relay the bias is defined as a ratio of
A Number of turns of restraining and operating coil.
B Alternators
C Transformers
D All of these
153.Both voltage and current signals are required for
A A plain overcurrent relay
B A differential relay
C A directional relay
B Translay relay
C Thermal relay
D Buchholz relay
155.In the case of transmission line protection, overcurrent relay is used
A Only up to 110 kV.
C Only up to 50 kV.
C Reliability dependent upon the large number of small components and their electrical connections.
B An integrating circuit.
C A transistor switch.
D A differentiating circuit.
161.Two-input phase comparator in a static relay is made up of a
A Transformer amplifier.
C Rectifier bridge.
D Thyristor bridge.
162.The phase comparators in case of static relay and electromechanical relay normally are
A Cosine and sine comparators respectively.
B Transformers
C Transmission lines.
B Transient reactance.
C Synchronous reactance.
B Hydro-generator sets.
D Buchholz relay.
168.The bias factor S in unit protection synchronous generator
A Lies between 0.05 and 0.1 pu.
B Unbalanced load
C Phase reversal
B A transformer
C A transmission line
D A bus bar
180.Earth fault protection for an electric motor is provided by
A Instantaneous overcurrent relay.
B Instantaneous relay having a setting of approximately 30% of motor rated current in the residual
circuits of two CTs.
C Ground wire
B Insulation failure
C Impulse voltage
D Mechanical vibrations
182.Which of the following relays has the capacity of anticipating the possible major fault in a transformer?
A Overcurrent relay
B Differential relay
C Buchholz relay
D Over-fluxing relay
183.Which relay is used to detect and protect internal faults of a transformer?
A Buchholz
B Directional relay
C Thermal relay
D Distance relay
184.To prevent mal operation of differentially connected relay while energising a transformer, the relay
restraining coil is biased with
A Second harmonic current
C Large transformer secondary only when the transformer is switched on in the primary.
D None of the above.
187.In case of power transformer :
A Positive, negative and zero-sequence impedances are all equal.
B Positive and zero-sequence impedances are equal but less than negative-sequence impedance.
C Positive sequence impedance is greater than both negative- and zero-sequence impedances.
D Positive sequence impedance is less than negative - sequence impedance but equal to zero-sequence
impedance.
188.For the protection of transformers, harmonic restraint is used to guard against
A Magnetizing inrush current.
B Unbalanced operation
C Lightning
D Switching overvoltage
189.The connection of CTs are opposite to that of transformer windings so that current in the pilot wires of
two are/have
A Same phase.
B Opposite in phase.
B Rods
C Tubes
B Low cost
B Voltage only
C Has the drawback that there will be complete shutdown when fault occurs on the bus itself.
D None of these.
199.A transmission line is protected by :
A Distance protection.
D Inrush protection.
200.In the case of transmission line protection, overcurrent relay is used
A Only up to 110 kV
B Only up to 220 kV
C Only up to 50 kV
D Only up to 1100 kV
201.Which is the main relay for protecting up to 90% of the transmission line-length in the forward direction?
A Directional overcurrent relay.
B Mho relay.
D Impedance relay.
202.For complete protection of a 3-phase transmission line, we require
A Three-phase and three-earth fault relays.
B 2
C 3
D 6
204.The transmission line distance production relay having the property of being inherently directional is
A Impedance relay
B MHO relay
C OHM relay
D Reactance relay
205.Time graded protection of a radial feeder can be achieved by using
A Definite time relays
C Trip on full-load.
D Trip instantaneously.
212.The frequency of carrier in the carrier current pilot scheme is in the range of
A 1 kHz to 10 kHz
B 10 kHz to 25 kHz
C 25 kHz to 50 kHz
B It is simple.
C It is cheaper in cost.
C Switching resistance in relay restraint circuit at pre-set time intervals by means of timer element.
B 33 kV system
D All of these
221.The over-voltage surges in power system may be caused by
A Lightning
B Resonance
C Switching
D All of these
222.The protection against direct lightning strokes and high voltage steep waves is provided by
A Ground wires
B Lightning arresters
D Earthing of neutral
223.Which of the following factors should be considered the design of a transmission line against lightning with
ground wire?
A Mechanical strength of ground wire.
B Capacitor.
D Both high
227.Which of the following is the protective device against lightning over-voltages?
A Rod gaps
B Surge absorbers
C Horn gaps
B Arcing earths
B Lightning surge
D None of these
230.The resistance in a thyrite lightning arrester is
A Varies linearly with the applied voltage
D None of these.
238.Surge absorber ____________ the energy of travelling waves
A Absorbs
B Reflects
C Diverts
C Using cantilever rods on the crossing along-with the areas of ground wire.
B Increases, Decrease.
B Sending end
D Tapping point
243.Travelling voltage wave and current wave have the same waveforms and travel together along the transmission
line at a velocity
A Of sound
B Of light
D An inductor between line and earth or a capacitor in series with the line.
246.If the load impedance is 100 ohm and input impedance is 25 ohm, then the characteristic impedance of the
transmission line is
A 70 ohm
B 60 ohm
C 50 ohm
D 40 ohm
247.The insulation strength of an EHV transmission line is mainly governed by
A Load power factor
B Switching over-voltages
C Harmonics
D Corona
248.The insulation strength for UHV lines (above 500 kV) is decided based on
A Lightning surges
C Switching surges
B More
C Equal
C Atmospheric conditions
B 11 and 33 kV
C 33 and 66 kV
D 66 kV and 132 kV
255.Earthing of transformer neutral through reactance will improve its
A Transient stability
B Solidly earthed
C Resistance earthed
D Reactance earthed
257.Peterson coil is used for
A Grounding of system neutral
B Multiple rods
C Counter poises
D Plates
259.Tower footing resistance of a transmission tower should be
A As high as possible
B As low as possible
C Moderately high
D Moderately low
260.The method of neutral grounding affects the
A Positive-sequence network
B Negative-sequence network
C Zero-sequence network
B Voltage in the healthy phases rise to full line value causing insulation breakdown
C The capacitive current in the faulty phase rises to 3 times its normal value
C Phase angle
B Booster transformer
C Induction regulator
C Stepless voltage variations without arcing or short-circuiting of turns as in the case of transformers
B Resistors
C Reactors
B Capacitor discharge
C Over voltage
D Noise
271.An AC capacitor is to be switched in parallel with AC line using back to back connected thyristor. What is
the firing angle of thyristor for first switching?
A 0 degree
B 180 degree
C 90 degree
D 45 degree
272.In between the generating station (power house) and consumers a number of transformation and switching
stations exist, these are called the
A Switchgears
B Substations
C Intermediate substations
D Transformation stations
273.Which of the following is provided with arcing horns?
A Isolator
B Air-break switch
C Oil switch
B 30 degree
C 70 degree
D 80 degree
283.Which of the following statements is true?
A Steady-state stability limit is greater than transient stability limit.
D No generalisation can be made regarding the equality or otherwise of the steady, state stability limit
and transient stability limit.
284.The methods employed in improving the system stability are
A Increasing the system voltage only
C Stability of power systems in which many machines are connected to infinite bus bar.
D Load distribution between a single machine and load drawn from infinite bus bar.
289.For what value of damping parameter, the transient stability is assured by equal area criterion?
A Independent of systems damping
C DC series motor
D DC compound motor
293.The transient stability limit of a power system can be appreciably increased by introducing
A Series inductance
B Shunt inductance
C Series capacitance
D Shunt capacitance
294.The initial accelerating power (in pu) will be
A 1.0
B 0.6
C 0.56
D 0.4
295.The use of high speed circuit breakers
A Reduces the short circuit current
C Fault calculations
B Making transient stability studies but not for short-circuits studies on the power system.
C Making both short-circuit and transient stability studies on the power system.
D For neither Making short-circuit studies nor transient stability studies on the power system.
299.Load flow studies involve solving simultaneous
A Linear algebraic equations
B Load buses
C Slack buses
D P-V buses
302.If a voltage controlled bus is treated as a load bus, then which one of the following limits would be
violated?
A Voltage
B Active power
C Reactive power
D Phase angle
303.In load-flow analysis, the load connected at a bus is represented as
A Constant current drawn from the bus.
B Power factor
C Power flow
B The system losses will change but complex bus voltages remain unchanged.