Professional Documents
Culture Documents
Multi-Layer Smart Fault Protection For Secure Smart Grids
Multi-Layer Smart Fault Protection For Secure Smart Grids
Multi-Layer Smart Fault Protection For Secure Smart Grids
Abstract—The trend toward Smart grid (SG) is increasing sig- with high penetration of DG-based inverters are highlighted
nificantly by incorporating Distributed Generators (DGs), which in [4].
leads to new challenges, especially in protection systems. SGs Switching to an SG will make power more adaptable to
should strengthen robust environments against cybersecurity
threats. So, the cybersecurity of future SGs is essential. This demand increase, ability to integrate DGs, efficient, and reli-
paper proposes a multi-layer protection scheme for the Medium able. However, the potential for power grid risks significantly
Voltage (MV) Distribution System (DS), especially with reconfig- raised. As a result, electric operators must be vigilant and
urable SGs. The main protection algorithm is based on Artificial establish multiple levels of protection. So, there is an increase
Intelligence (AI), utilizing the communication between all pro- in the research effort to improve SG protection [5], [6], [7].
tective devices (PDs) in the grid, whereas as backup protection,
another AI algorithm employs the communication between the In [8], [9], a survey regarding SG vulnerability points and
PDs in the same line. Then, as alternative protection to provide types is presented. Also, [10], [11] investigate cyber-security
the protection system with another level of security in case of in SGs to diagnose the potential vulnerabilities along with their
communication issues or cyberattacks, a third algorithm based impact. In [12], the threats and potential solutions of SGs have
on the local data of each PDs is proposed. Both simulations using been analyzed, focusing on cyberattack types. The dynamic
MATLAB S IMULINK and experimental results utilizing a scaled
physical grid validated the protection algorithms. The scaled grid behaviors of SGs are moderated and evaluated to address this
has been designed for the smart grid in order to test the behavior problem, which is influenced by DGs or system reconfigu-
of the protection scheme experimentally. ration to distinguish between natural smart grid changes and
Index Terms—Artificial neural network-based relay, distribu- real-time attacks [13]. In [14], new ways for detecting mis-
tion system, microgrids, medium voltage distribution system, leading data cyber-attacks in the physical layers of smart grids
protection strategies, smart grid protection. have been developed. However, this strategy depends on the
analysis of the protection data, which is time-consuming.
Standards prescribe that DGs should be disconnected if the
I. I NTRODUCTION CB supplying the feeder connected to the DGs is tripped, as
ECENTLY, a significant increase in the Distributed mentioned in [15]. Utility requirements justify anti-islanding
R Generator (DG) penetration in the Distribution System
(DS) has been noticed, especially with the presence of new
protection; however, it reduces the DG’s benefits. Anti-islanding
protection is one of the main concerns in grids with DG, and
loads. So, maintaining the DG connected to the DS during its solution continues to be an issue, although several passive
faults becomes essential. Therefore, achieving a Smart Grid and active approaches can be found. However, these methods
(SG) protection scheme has been critical, particularly with can face several limitations as setting the thresholds must be
microgrid incorporation. However, there are several barriers chosen strictly, may create power quality problems, slow detec-
to completing this task [1]. The DG penetrations into DS can tion time, and some challenges to implementation [16]. With
affect the power flow on the grid due to several power gener- high DG penetration, the DG disconnection will be minimized
ation points, as well as the relay short-circuits current value, in the near future; under the circumstances of no islanding
which influences the Protective Devices (PDs) settings [2], [3]. occurring. So, DGs should be allowed to exploit them using a
The difficulties in detecting fault current and voltage profiles droop-based control to make them behave as traditional syn-
chronous generators with huge inertia [17]. However, in the
Manuscript received 21 April 2022; revised 19 August 2022 and event of islanding and a reclosing operation is performed,
7 November 2022; accepted 12 December 2022. Date of publication
16 December 2022; date of current version 21 June 2023. Paper no. one of the following scenarios must be satisfied. (1) The DGs
TSG-00553-2022. (Corresponding author: Mostafa Bakkar.) inside the island are disconnected. According to IEEE Standard
Mostafa Bakkar, Santiago Bogarra, and Felipe Córcoles are with 1547-2018, the DG must identify the island and trip within
the Department of Electrical Engineering, Polytechnical University in
Catalonia, 08222 Terrassa, Spain (e-mail: mostafa.bakkar@upc.edu; two seconds of its development [18]. (2) A synchronism check
santiago.bogarra@upc.edu; felipe.corcoles@upc.edu). is performed [19]. Synchronizing check relay supervises the
Javier Iglesias is with ABB Power Grids Spain S.A.U., 28037 Madrid, closing of circuit breakers and does not allow improper syn-
Spain (e-mail: javier.iglesias@hitachienergy.com).
Wael Al Hanaineh is with the Department of Electrical Engineering, chronizing [20]. (3) The inverter can endure the transients of
Polytechnical University in Catalonia, 08019 Barcelona, Spain (e-mail: an out-of-synchronism reclosing. Inverter tripping should not
wael.hasan.ahmad.al.hanaineh@upc.edu). occur if the Phase Locked Loop (PLL) loses synchronism.
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TSG.2022.3229848. Within a couple of cycles, the PLL should resynchronize with
Digital Object Identifier 10.1109/TSG.2022.3229848 the grid and be able to inject the demanded current [21].
1949-3053
c 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
3126 IEEE TRANSACTIONS ON SMART GRID, VOL. 14, NO. 4, JULY 2023
Artificial Intelligent techniques significantly improve the The major benefits of this system are that it consolidates the
protection of SGs especially utilizing communication, due entire system’s security into a single device, performing state
to the introduction of standards such as IEC 61850 and estimation and security evaluations. On the other side, com-
Ethernet-based communication capabilities [22] or wireless munication issues or CE unit failure will result in a loss of
networks [23]. In addition, adaptive protection allows relays to protection while restoring services. In order to improve the
respond to changes in the DS. However, the complexity of this system’s redundancy, ZO is cooperating with CE. Every PD
process is significant, and an appropriate communication chan- decides locally, utilizing the data acquired from the peer PD
nel is required, particularly with grid reconfigurations and DG on the same line. The significant advantages of this algorithm
penetration into DS. In [24], [25], [26], [27], [28], different are its flexibility to adapt to any alterations in the grid and the
proposals to use communication to update the OverCurrent less training time compared to CE.
Relay (OCR) and Differential relay (DR) settings with the However, both protection strategies are based on commu-
incorporation of DG have been presented. Another idea is nication; therefore, as a continuation of the author’s previous
to use a multi-agent technique to adapt the settings of OCR work, regarding overcurrent protection based on ANNs for
and DR [29], [30]. However, the complexity of relay settings smart distribution networks, a third-level protection strategy is
adjustment under different grid scenarios remains a limitation. proposed in this paper, as shown in Fig. 2. This third level of
Various backup protection strategies have been proposed. As protection is named Local algorithm (LO), which functions as
in [31], [32], a device failure detection algorithm is proposed supporting and alternative protection to provide the protection
based on communication between PDs. However, the limi- system with a high degree of dependability in case of com-
tations of communication problems have not been avoided. munication or cyber-attacks vulnerabilities. The LO is based
It can be concluded that the protection strategies based on on the local information of each PD and without any commu-
communication can have severe limitations if the communica- nication between PDs. This protection strategy allows for the
tion system is interrupted due to system faults, discrepancies, location and isolation of faults considering various types of
and hacking. So, backup protection is needed. In [33], a fault faults, changing load consumption, DG penetration, different
location strategy depends on the ratio of positive and negative- fault locations, low and high fault resistance, which provide
sequence voltages; however, the inverter-based DG has not more secure and redundant protection. The LO compared to
been considered. other protection algorithms, can provide a more secure, alter-
Another trend is to propose strategies to back up and support native supportive, and more economical protection strategy as
communication failure. Mainly because using communication no communication is needed; moreover, it is easy to be adapted
in the protection strategies introduces more challenges [34]. to different grids without the need for training. In addition, LO
In addition, to protect smart grids, different privacy issues and guarantees protection if the other two levels of protection do
security requirements need to be discussed [35], [36]. In [37], not function properly.
a differential pilot protection is proposed to avoid commu- Since the proposed LO algorithm is based on reclosing
nication problems. This approach employs a multiresolution operations, therefore in the case of islanding, a synchronism
morphological gradient to determine the arrival time of the check should perform; otherwise, the DGs on the island are
fault traveling wave and a nonlinear filtering algorithm to pre- disconnected.
process the communicated samples. However, the algorithm In order to validate the proposed LO protection algo-
has been verified for the DC grid. In [38], a strategy based rithm, its behavior has been analyzed and simulated, then
on distance relay using impedance calculation is proposed. demonstrated experimentally. It is essential to highlight that
The strategy can be improved further if it can be made adap- the characteristics of the influence of inverter-based gener-
tive. In [39], a backup protection strategy is proposed based ators have been considered (small transient duration, low
on comparing the phase difference of positive-sequence cur- short-circuit current, and reversible power flow).
rent fault components between the main and slave feeders. As shown in Fig. 2, the multi-layers priority algorithm is
The strategy is focused on transmission lines radial grid for presented. Before running the CE algorithm, the inputs and
non-based inverter DG. In [40], a non-communication dual communication signals from all PDs must be checked for
settings directional OCR is proposed for a DS that requires to availability. If some of the signals did not receive at CE then
be updated in case of reconfiguration. a delay will be formed, and the signals are rechecked utilizing
As the aforementioned studies show, an alternative protec- variable “a” (that goes from 0 → 1) to ensure that the system
tion strategy that can operate for reconfigurable DSs with high is not experiencing a transitory problem. The CE decision is
DG penetration is still needed. The author’s previous work [41] performed if the signals are received (Layer 1). At the same
presents an AI protection scheme based on two strategies. The time, the ZO algorithm will be executed (Layer 2). In this case,
first strategy, the Centralised algorithm (CE), employs commu- the inputs and communication of the peer PDs are sent to ZO;
nication between all protective devices (PDs) in the grid. The then, the decision is performed. Both CE and ZO decisions
second strategy is named Zone algorithm (ZO), based on the are compared to give an extra level of reliability. Moreover,
communication between the PDs in the same line. the third layer of protection (LO algorithm) can be activated
For the CE algorithm, the fundamental concept is to use using two signals the ‘Activation signal and the ‘Emergency
the positive-sequence current (i+ ) data as inputs to the signal’. If the input or communication signals of CE and ZO
CE. Variations in short circuit current in each PD must be from layer 1 and layer 2 are not received (due to vulnera-
included in the Artificial Neural Networks (ANN) training. bility or communication problems), the ‘Activation signal’ is
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
BAKKAR et al.: MULTI-LAYER SMART FAULT PROTECTION FOR SECURE SGs 3127
Fig. 1. Single line diagram of the analyzed DS with DG penetration and LO.
generated automatically at each PD (layer 3). In addition, the 66 kV which is transformed to 20 kV through an HV/MV
LO algorithm at the third layer of protection can be activated transformer, isolated using a zig-zag transformer to create an
manually using an external signal called an ‘Emergency sig- artificial neutral (YNd11 grounded through zig-zag) [42]. The
nal’. This signal is generated at each PD, as shown in the red rated power of the grid is 25 MVA, where various DGs are
box of Fig. 2 (layer 3). connected at different buses through an MV/LV transformer
First, the proposed LO protection algorithm is presented. configuration (D11yg). Table I shows the grid parameters.
Second, the validation analysis of the proposed protection Each PD consists of a relay where the algorithm is executed
algorithm is discussed. Third, the experimental results are and a CB. The relay structure is presented in the right corner
discussed. Finally, the conclusion of the paper is presented. of Fig. 1.
The main focus of this paper is to study the effect of a
high penetration level of inverter-based DGs. However, in the
II. L OCAL P ROTECTION A LGORITHM case of a grid with rotating machines operating as DGs,
LO is an alternative protection (third layer) algorithm for the the proposed algorithm is able to function as well, because
first two layers of protection, which supports the SG in case of the current imposed from the rotating generators should be
vulnerability due to loss of communication between controllers higher and maintained for a longer time than in the case of
and PDs or cyberattacks. In this algorithm, all communications inverter-based DGs [25]. Therefore, during a fault, a reduc-
between the PDs are not required; then, the protection system tion in the voltage is observed, and the same strategy of LO
can work properly in case of communication loss. Each PD algorithm is applied.
should be able to detect if the fault is located in the pro- The VSI controller’s response was implemented under grid
tected line or another line by using only the local information faults combining the capabilities of LVRT and the specifi-
of the PD. The algorithm uses the sequence components of cations of the Spanish grid code. Two scenarios have been
voltages of each PD during fault conditions. Furthermore the considered: the first imposes only a positive-sequence current,
developed algorithm can be applied to other DS grid configu- and the second imposes both positive and negative-sequence
rations. In Fig. 1, the single-line diagram of the analyzed DS currents. The strategies have been studied to offer more
is shown, with DG penetration. The HV grid rated voltage is reactive power injections, which will help to support the grid
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
3128 IEEE TRANSACTIONS ON SMART GRID, VOL. 14, NO. 4, JULY 2023
TABLE I
G RID PARAMETERS
TABLE II
ANN FAULT C LASSIFICATION PARAMETERS in Fig. 3. In the pre-processing stage, the three abc instanta-
neous fundamental voltages (va (t), vb (t), and vc (t)) are divided
by the base values of the system in order always to obtain pu
values that are easier to adapt to the ANN to different grid volt-
age levels. In distribution grids, the allowable voltage drops
equal 7.5% [44]; therefore, if the voltage drop at any phase is
less than 0.925 pu, this will be considered a fault. This value
can be adjustable depending on the condition of the analyzed
grid. In order to identify the ground fault, the zero-sequence
voltage is used (v0 ), which is obtained from the abc voltages,
as in the case of two-phase fault, the zero-sequence voltage is
approximately equal to 0; however, in the case of two-phase
to ground faults, the zero-sequence voltage is larger than 0.
These data are sent to an ANN to make the correct decision,
corresponding to the fault type (0 → no fault, and 10 →
three-phase fault) as seen in Fig. 3. Table II shows the trained
fault classification ANN parameters. The ANN is trained for
about 1000 cases to manage parameter changes that impact
the algorithm’s decision.
B. LO Algorithm Procedure
The values of the sequence voltages at each bus have been
Fig. 3. Flowchart of fault classification algorithm.
utilized by the LO algorithm. By using the under-voltage relay,
two points with the same voltage are obtained, which means
during symmetrical and unsymmetrical faults [31]. Different two PDs could disconnect simultaneously. So, to disconnect
control strategies for a grid-connected inverter have been only the PD at the faulted line, an improvement with an addi-
employed, and the output voltage behavior during symmetri- tional algorithm will be used named the recloser algorithm.
cal and unsymmetrical voltage sags has been analyzed [17]. In The main idea of the algorithm is to open and close after a
addition, the importance of complying with grid code require- specific time interval (delay). The flowchart of the LO algo-
ments for DGs operating in a faulty grid with both balanced rithm is shown in Fig. 4. This flowchart can be explained as
and unbalanced conditions, as well as ensuring the power con- follow: [1] the type of fault is determined, [2] depending on
verter voltage and current limits are not exceeded have been the type of fault (symmetrical or unsymmetrical), the positive-
demonstrated [43]. sequence voltage (v+ ) or the negative-sequence voltage (v− )
Different fault location algorithm has been used for each is utilized to tripped the two PDs with the same voltage, [3]
type of fault. Because the sequence components would change one of the two tripped PDs is connected, if the PD is exposed
based on the fault type (symmetrical/unsymmetrical), a fault to the fault then it trips, [4] then the other PD is connected
classification technique is essential before implementing the after a delay to test the fault existence that is explained in
proposed LO algorithm. During any type of fault, the three Section II-C.
phases are disconnected in the MV grid. In the case of a single-phase fault, one end of the faulted
line can be located by using negative-sequence voltage during
the fault. During the fault, the negative-sequence voltage of the
A. Fault Classification Algorithm two PDs at one end of the faulted line (DL3) will be higher
In this work, ANN is chosen to be the tool to identify the than any other negative-sequence voltage values of other lines;
fault type. The main merit of using ANN in this application then the recloser algorithm will be implemented to disconnect
is the fast and reliable decision and the availability to use the the PD at the faulted line. Therefore, the highest value means
same ANN in different grid voltage levels; then, a prepro- faster disconnection. The next step is disconnecting the PD
cessing stage will be implemented, adapting the input signals. with the highest negative-sequence voltage and analyzing the
The flowchart of the fault classification algorithm is shown grid after the disconnection. After the disconnection of one end
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
BAKKAR et al.: MULTI-LAYER SMART FAULT PROTECTION FOR SECURE SGs 3129
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
3130 IEEE TRANSACTIONS ON SMART GRID, VOL. 14, NO. 4, JULY 2023
Fig. 8. Recloser algorithm explanation when the fault (a) at the end of the
DL, (b) at the middle of the DL.
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
BAKKAR et al.: MULTI-LAYER SMART FAULT PROTECTION FOR SECURE SGs 3131
Fig. 9. abc voltages, abc currents, and trip signals for LO (a) with 2 DGs during 1 ph to ground (AG) at DL5, (b) without DG during 2 ph (BC) at DL1.
the fault, and when it closes again, it will still have exposed
to the fault, and as a consequence PD9 will trip, after that
at (0.935 s) (Fig. 9(a)) PD8 will be connected again and at
that time the fault will be cleared so it will remain connected.
The same idea is repeated for PD10 and PD11, because they
are connected to the same bus, so both will measure the same
negative-sequence voltage. Then, using the recloser algorithm,
PD10 will be connected first, then trips as it is exposed to
the fault, unlike PD11, which will be connected after a delay
(0.015 s).
In order to verify the effectiveness of the LO algorithm,
the sequence components of the PDs with the corresponding
trip time have been presented as seen in Fig. 9. For example,
if a two-phase fault occurred at DL1, the negative-sequence
voltage at PD1 is equal v− = 0.88 pu, and at PD2 is equal
v− = 0.94 pu. These values correspond to a trip time equal
t = 0.14 s for PD1, and t = 0.12 s for PD2, as shown on the
right side of Fig. 9.
A more precise interpretation of the LO with the recloser
process could be obtained from Fig. 10 when a symmetri-
cal fault occurs at DL3. These figures show the fault and
trip signals in all the PDs connected to buses at the end of
the faulted line. As seen in Fig. 10(a), the protection algo-
rithm depends on the definite-time curve corresponding to the
positive-sequence voltage. The fault signal at PD4 and PD5 is
the same because they are connected to the same bus (bus 3). Fig. 10. Analyzed grid with 2 DGs during 3 ph (abc) at DL3, (a) fault,
The same happens for PD6 and PD7 connected to bus 4. (b) trip.
Fig. 10(b) shows the trip signals of the same PDs. It is shown
that the two PDs connected to the same bus trip at the same
time, in this case, PD6 and PD7 have the first disconnection conclusion can be obtained during an unsymmetrical fault; the
because they have the same minimum positive-sequence value, only difference is that the protection algorithm, in this case,
and PD4 and PD5 have the second disconnection because the depends on the negative-sequence voltage.
positive-sequence value is higher than for the other two PDs A wide range of fault resistance (r) values have been tested
(PD6 and PD7). After that, the recloser algorithm is applied by from milliohms to several ohms; for example, Fig. 11 corre-
connecting PD6, which is exposed to the fault, so it trips again. sponds to a single-phase to ground fault (BG) at DL4 with r =
After the disconnection of PD6, PD7 is connected, then PD7 5 , and r = 0.1 . As seen in Fig. 11, the change in the fault
is not exposed to the fault, and it does not trip. The previous resistance affects the value of the trip time as the sequence
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
3132 IEEE TRANSACTIONS ON SMART GRID, VOL. 14, NO. 4, JULY 2023
Fig. 11. abc voltages, abc currents, and trip signals for LO with 2 DGs during single-phase to ground fault (BG) at DL4 (a) with fault resistance r = 5 ,
(b) with fault resistance r = 0.1 .
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
BAKKAR et al.: MULTI-LAYER SMART FAULT PROTECTION FOR SECURE SGs 3133
TABLE III
C OMPARISON B ETWEEN R EAL G RID AND L ABORATORY G RID
PARAMETERS
TABLE IV
L ABORATORY S YSTEM PARAMETERS
Fig. 14. Digital output of LO with DG during Three-phase fault at F1 and F2.
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.
3134 IEEE TRANSACTIONS ON SMART GRID, VOL. 14, NO. 4, JULY 2023
[26] J. Tang and P. G. Mclaren, “A wide area differential backup protection Mostafa Bakkar received the B.Sc. degree in
scheme for shipboard application,” IEEE Trans. Power Del., vol. 21, mechatronics engineering from the Alexandria
no. 3, pp. 1183–1190, Jul. 2006. Higher Institute of Engineering and Technology,
[27] E. Sortomme, S. S. Venkata, and J. Mitra, “Microgrid protection using Alexandria, Egypt, in 2008, the M.Sc. degree in elec-
communication-assisted digital relays,” IEEE Trans. Power Del., vol. 25, trical and control engineering from Arab Academy
no. 4, pp. 2789–2796, Oct. 2010. for Science, Technology and Maritime Transport,
[28] T. S. Aghdam, H. K. Karegar, and H. H. Zeineldin, “Transient Alexandria, in 2014, and the Ph.D. degree from the
stability constrained protection coordination for distribution systems Department of Electrical Engineering, Universitat
with DG,” IEEE Trans. Smart Grid, vol. 9, no. 6, pp. 5733–5741, Politècnica de Catalunya, Barcelona, Spain, in
Nov. 2018. February 2022. His research interests include fault
[29] M. S. Rahman, M. A. Mahmud, A. M. T. Oo, and H. R. Pota, “Multi- diagnosis, power system protection, artificial intelli-
agent approach for enhancing security of protection schemes in cyber- gence applications in power systems, smart grids, distributed power genera-
physical energy systems,” IEEE Trans. Ind. Informat., vol. 13, no. 2, tion, grid code integration, inverter control strategies, and renewable energy
pp. 436–447, Apr. 2017. systems.
[30] B. Polajžer, M. Pintarič, M. Rošer, and G. Štumberger, “Protection
of MV closed-loop distribution networks with bi-directional over-
current relays and GOOSE communications,” IEEE Access, vol. 7,
pp. 165884–165896, 2019.
[31] W. Li, Y. Tan, Y. Li, Y. Cao, C. Chen, and M. Zhang, “A new differential Santiago Bogarra was born in Gavá, Spain, in
backup protection strategy for smart distribution networks: A fast and May 1966. He received the Ph.D. degree in elec-
reliable approach,” IEEE Access, vol. 7, pp. 38135–38145, 2019. trical engineering from the Polytechnic University
[32] J. Zare, F. Aminifar, and M. Sanaye-Pasand, “Communication- of Catalonia, Barcelona, Spain, in 2002. Since
constrained regionalization of power systems for synchrophasor-based 1996, he has been with the Polytechnic University
wide-area backup protection scheme,” IEEE Trans. Smart Grid, vol. 6, of Catalonia, where he is an Associate Professor
no. 3, pp. 1530–1538, May 2015. of Electrical Engineering. He has published more
[33] P. Bountouris, H. Guo, D. Tzelepis, I. Abdulhadi, F. Coffele, and than 40 conference and journal papers. His current
C. Booth, “MV faulted section location in distribution systems based on research interests include electric aircraft and dis-
unsynchronized LV measurements,” Electr. Power Energy Syst., vol. 119, tributed generators connected to distributed power
pp. 1–14, Jul. 2020. systems, further main areas of research are lightning
[34] H. F. Habib, C. R. Lashway, and O. A. Mohammed, “A review of com- protection and power system quality.
munication failure impacts on adaptive microgrid protection schemes
and the use of energy storage as a contingency,” IEEE Trans. Ind. Appl.,
vol. 54, no. 2, pp. 1194–1207, Mar./Apr. 2018.
[35] K. G. Boroojeni, M. H. Amini, and S. S. Iyengar, Smart Grids: Security
and Privacy Issues, 1st ed. Cham, Switzerland: Springer. 2017. Felipe Córcoles was born in Almansa, Spain, in
[36] P. Ray and M. Biswal, Microgrid: Operation, Control, Monitoring and 1964. He received the B.S. degree in industrial engi-
Protection, 1st ed. Singapore: Springer, 2020. neering and the Ph.D. degree in engineering from
[37] W. Xiang, H. Zhang, S. Yang, M. Zhou, W. Lin, and J. Wen, “A dif- the Universitat Politècnica de Catalunya, Barcelona,
ferential pilot protection scheme for MMC-based DC grid resilient to Spain, in 1990 and 1998, respectively, where he
communication failure,” IEEE J. Emerg. Sel. Topics Power Electron., has been a Professor with the Electrical Engineering
vol. 9, no. 5, pp. 5631–5645, Oct. 2021. Department since 1992. His research interest lies in
[38] T. S. Sidhu, D. S. Baltazar, R. M. Palomino, and M. S. Sachdev, “A the areas of electrical machines and power system
new approach for calculating zone-2 setting of distance relays and its quality.
use in an adaptive protection system,” IEEE Trans. Power Del., vol. 19,
no. 1, pp. 70–77, Jan. 2004.
[39] F. Zhao, Z. Meng, Y. Li, and C. Liu, “An integrated wide-area
protection scheme for active distribution networks based on fault com-
ponents principle,” Gaodianya Jishu High Voltage Eng., vol. 45, no. 10,
pp. 3092–3100, 2019.
[40] A. A. Balyith, H. M. Sharaf, M. Shaaban, E. F. El-Saadany, and Javier Iglesias received the Master of Science
H. H. Zeineldin, “Non-communication based time-current-voltage dual degree in power systems engineering from the
setting directional overcurrent protection for radial distribution systems Polytechnical University in Catalonia (UPC), Spain,
with DG,” IEEE Access, vol. 8, pp. 190572–190581, 2020. and the Ph.D. degree from the UPC and the
[41] M. Bakkar, S. Bogarra, F. Córcoles, and J. Iglesias, “Overcurrent protec- University of Bath, U.K. He has more than eighteen
tion based on ANNs for smart distribution networks with grid-connected years of experience in the consulting area. He has
VSIs,” IET Gener. Transm. Distrib., vol. 15, no. 7, pp. 1159–1174, conducted planning and power system studies (pro-
2021. tection coordination, harmonic, filter design, stability
[42] SRZ001: Particular Technical Specifications of HV / MV Substations, studies, and integration of renewables) for electri-
Endesa, Madrid, Spain, 2018. cal utilities and independent power producers. From
[43] A. Rolán, S. Bogarra, and M. Bakkar, “Integration of distributed energy February 2021, he is responsible for Global Product
resources to unbalanced grids under voltage sags with grid code compli- Specialist for Solid State Transformer, Medium Voltage DC, and DC grid
ance,” IEEE Trans. Smart Grid, vol. 13, no. 1, pp. 355–366, Jan. 2022, distribution applications.
doi: 10.1109/TSG.2021.3107984.
[44] P.O.12.2: Technical Requirements of Wind Power and Photovoltaic
Facilities (Draft), Red Electra, Madrid, Spain, 2008.
[45] G. Benmouyal et al., “IEEE standard inverse-time characteristic equa-
tions for overcurrent relays,” IEEE Trans. Power Del., vol. 14, no. 3, Wael Al Hanaineh received the B.Sc. degree in
pp. 868–871, Jul. 1999. electrical engineering from the University of Jordan,
[46] VIP400-VIP410, Electrical Network Protection Reference Manual, Jordan, in 2016, and the M.Sc. degree in electri-
Schneider-Electr., Rueil-Malmaison, France, 2013. cal and renewable energy engineering from German
[47] IEC 62271-100: High Voltage Switchgear and Controlgear—Part 100: Jordanian University, Jordan, in 2019. He is cur-
Alternating Current Circuit Breakers, Spanish Assoc. Stand., Madrid, rently pursuing the Ph.D. degree in electrical engi-
Spain, 2021. neering with the Technical University of Catalonia,
[48] A. Rolán, P. Giménez, S. J. Yagüe, S. Bogarra, J. Saura, and M. Bakkar, Barcelona, Spain. His research interests are in the
“Voltage recovery influence on three-phase grid-connected inverters areas of fault detection, power system protection,
under voltage sags,” IET Gener. Transm. Distrib., vol. 13, no. 3, power quality, smart grid applications, electric vehi-
pp. 435–443, 2019, doi: 10.1049/iet-gtd.2018.5607. cles, and integration of renewable energy systems.
Authorized licensed use limited to: K.L. University(F.K.A. Koneru Lakshmaiah College of Engineering). Downloaded on January 05,2024 at 09:57:50 UTC from IEEE Xplore. Restrictions apply.