MV AC CABLE SCHEDULE

PROJECT DEVELOPER RADIANCE RENEWABLES PVT LTD


OWNERS ENGINEER SGURR ENERGY PVT LTD
EPC CONTRACTOR SOLON INDIA PVT LTD.
PROJECT NAME TN SUNRISE ONE
DOCUMENT TITLE MV AC CABLE SCHEDULE
DOCUMENT NO 052_SIPL_TNSR_EDCAL_014
REVISION R1

resistance@90°c

Cable reactance

Actual Capacity
Rated Capacity
Current(Amps)

%voltage drop
Voltage(Volts)
length per run

% Power Loss
Actual length

Confirmation
Degradation
Total Actual

Total Actual

Power (kW)

No. of Runs
Actual loop

length with
Application

Description

margin (m)
Voltage(V)

length (m)

Cable Size
Total Max
(ohm-km)

(ohm-km)

of Cable

of Cable
per run

Margin
AC/DC

Cable

Cable
S.No.

From

To
33kV 3CX300Sq.mm MultiStrand Al. XLPE Insulation Flat
TRANSFORMER-1 @ ICR 33KV ICOG HT PANEL @ ICR AC 33000 50 10 60 15% 69
Armoured FRLS Outersheath A2XFY (UE) Cable
1 0.13 0.108 109.3 33000 6250 1 0.005% 0.004% 350 0.86 301 Cable Size is OK
33kV 3CX300Sq.mm MultiStrand Al. XLPE Insulation Flat
33KV ICOG HT PANEL @ ICR 33KV 3IN/1OUT MAIN HT PANEL @ MCR AC 33000 350 10 360 15% 414
2 Armoured FRLS Outersheath A2XFY (UE) Cable 0.13 0.108 109.3 33000 6250 1 0.034% 0.026% 350 0.86 301 Cable Size is OK
33kV 3CX300Sq.mm MultiStrand Al. XLPE Insulation Flat
TRANSFORMER-2 @ MCR 33KV 3IN/1OUT MAIN HT PANEL @ MCR AC 33000 50 10 60 15% 69
3 Armoured FRLS Outersheath A2XFY (UE) Cable 0.13 0.108 109.3 33000 6250 1 0.005% 0.004% 350 0.86 301 Cable Size is OK
33kV 3CX300Sq.mm MultiStrand Al. XLPE Insulation Flat
TRANSFORMER-3 @ MCR 33KV 3IN/1OUT MAIN HT PANEL @ MCR AC 33000 40 10 50 15% 58
4 Armoured FRLS Outersheath A2XFY (UE) Cable 0.13 0.108 54.7 33000 3125 1 0.002% 0.001% 350 0.86 301 Cable Size is OK
33kV 3CX300Sq.mm MultiStrand Al. XLPE Insulation Flat
33KV 3IN/1OUT MAIN HT PANEL @ MCR METERING YARD AC 33000 400 10 410 15% 472
Armoured FRLS Outersheath A2XFY (UE) Cable
5 0.13 0.108 273.4 33000 15625 1 0.097% 0.075% 350 0.86 301 Cable Size is OK
Average 0.028% 0.022%
Total 890 940 1081
SUMMARY
1 33kV 3CX300Sqmm. A2XFY AC Cable - FRLS Outer Sheath 1081 Meters

Derating Factors considered for the Calculations

K1(Grouping Factor) - LaId directly at under ground, touching, of 1 cable 1.00

K2(Temp Derating Factor for Ground Temp.) 45 deg C 0.87


K3(Depth of laying) 1200mm 0.99
K4(Soil thermal resistivity) Dry soil 1
Overall Derating Factor K = K1 X K2X K3X K4 0.86