Technical 1/79

Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation
I. Purpose: For the designer, site debugging, maintenance personnel
II. Failure Code List of TCD
No. Content Rank Class Hold
TCD 10 50B ON Failure A1 ◎
TCD 11 10T ON Failure A1 ◎
TCD 12 15B ON Failure A1 ◎
TCD 13 SDC Abnormal Running A2
TCD 14 System Halted From MICON A2
TCD 15 SDA halted A2
TCD 16 Abnormal principal and subordinate parallel A2
communication
TCD 17 Abnormal SDA, SDC serial communication A3
TCD 18 50BC Failure or E. Stop is cut off A3
TCD 19 99G Failure A3
TCD 20 Double Input BUFFER Failure A1 ○
TCD 21 Overload current found (IPM FAULT) A1 ○
TCD 22 Overload voltage found A1
TCD 23 SDC Safeguard switch abnormal A2 ○
TCD 24 Aided MICONMICON DRAM ERROR A2 ○
TCD 25 Aided MICON EEPROM ERROR A2 ○
TCD 26 DSP SUM ERROR A1 ○
TCD 27 Frequency Failure Found A1 ○
TCD 28 P15V Voltage Abnormal A2 ◎
TCD 29 Main MICON EEPROM ERROR A1 ◎
TCD 30 Main MICON NVSRAM ERROR A2 ○
TCD 31 DSP DRAM ERROR A2 ○
TCD 32 Restraining Circuit Abnormal A1
TCD 33 Abnormal BDCC voltage A2 ○
TCD 34 Low voltage Found A2
TCD 35 40G, 40D ON Failure A3 ◎

Prepared Tao 2004.12.08 Mark History Date Corrected by Approved


by Xinkang by
1
Checked Shen 2004.12.09 Amend TCD37、46、51 05.07.04 Zhang Hong Hao
by Yongqiang Xianghong
Approved Hong Hao 2004.12.09
by

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No. 2/79
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation

No. Content Description Rank Class Hold


TCD 36 SDC Operation Mode Error C1
TCD 37 Reverse Running Found A2 ○
TCD 38 DSP Halt Found A2
TCD 39 100R ON/OFF Failure A1 ○
TCD 40 ROTARY ENCODER Failure A2 ○
TCD 41 Low Speed OVER SPEED A2 ○
TCD 42 50B OFF Failure A1
TCD 43 SPD Circuit Failure A1 ○

48V Power supply of SDCLAN Board Abnormal C1

OPBLAN-I24B OR I48A Failure C1


TCD 44
SDCLAN-I24B OR I48A Failure C1
Communication between SDCLAN and OPBLAN Broken C1
TCD 45 BKSW Action Check A1 ◎

1 TCD 46 Open Lock over 3 times A2 ◎


TCD 47 Load Circuit Error Found C1
TCD 48
TCD 49
TCD 50 High Speed OVER SPEED A2 ○
TCD 51 Speed Deviation Found A2 ○
TCD 52 10T OFF Failure A1
TCD 53 15B OFF Failure A1
TCD 54 RE Failure (U, V, W phase angle abnormal) A1 ◎
TCD 55 Large HCT Off Set Deviation A1 ◎
TCD 56
TCD 57 Mg. B two-phrase power supply abnormal A1 ◎
TCD 58 DLAN Halt C1
TCD 59 Building Height > 9m,No Conducting Board Found A2 ◎
TCD 60 Step Height TABLE SUM ERROR B1
TCD 61
TCD 62 Positions of same time abnormal B2
TCD 63 SDS ON Failure B2
TCD 64 SDS Speed Abnormal Found A1

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No. 3/79
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation

No Content Description Rank Class Hold


TCD 65 40D Abnormal OFF During Running E

TCD 66 40G Abnormal OFF During Running E


TCD 67 Close Door Failure in Flat Layer (40D or 40G NOT on) E
TCD 68 SDA halt over 8 times A2 ○
TCD 69 SDA RAM ERROR A2 ○
TCD 70 Shared RAM ERROR A2 ○
TCD 71 Main MICON Halt A2 ○
TCD 72 Aided MICON Halt over 8 times A2 ○
TCD 73 FML POSI OPEN Failure B1 ○
TCD 74 Frequency Save-out Running A2 ○
TCD 75 POWER MODULE Over Heat B2
TCD 76 Abnormal Micro-speed Running time C1
TCD 77 Door Motor Over heat C1
TCD 78 Door Machine Abnormal A2
TCD 79
TCD80
TCD 81 Photoelectricity POSI OPEN Failure E
TCD 82 Photoelectricity POSI Short-circuit Failure E
TCD 83
TCD 84 OLS ON Failure C2
TCD 85 CLS ON Failure C2
TCD 86 Abnormal Open-door action Found E
TCD 87 Abnormal Close-door action Found C2
TCD 88 Lost power found E
TCD 89
TCD 90
TCD 91 DZ POSI OPEN Failure (Qianniao, Through) A1
TCD 92 DZ POSI Short Failure (Qianniao, Through) A1
TCD 93
TCD 94
TCD 95 Final Failure Level
TCD 96 Final Failure Elevator Position

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No. 4/79
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation

No Content Description Rank Class Hold


TCD 97 Elevator Failure Final Speed
TCD 98 Save-out running times
TCD 99 Final Main TCD

Description:
◎:Failure elimination,After the main power supply switches from OFF-ON,operate MODE 2 to clear
TCD, and then return to normal operation.
○:Failure elimination,operate MODE 2 to clear TCD or after the main power supply switches from
OFF-ON, and then return to normal operation.
Because the failures found by the MICON system program can be ranked into five categories (A~E)
according to importance.
And the different Failure rank corresponds to different limited actions. The ranks are listed below:
RANK Function Sub Content
A1 Functions Disable ( 50B , 10T
Unable to run(Abnormal Stop)Can’t be
A CUT)
restarted.
A2 Can’t be re-started(10 CUT)
B1 SAFETY DRIVE after stop for 3
Unable to run(Abnormal Stop)Can’t be
B seconds
restarted.
B2 Low speed run.
Stop at the nearest step, and can’t be C1 Functions Disabled(50B CUT)
C
restarted C2 Can’t be re-started.(10 CUT)
D Remove from group management D Elevator runs in a single manner
E No effect of running. E Indicate by LED

5/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation
III. TCD Failure code specific instructions:
Failure
TCD Content HOLD
Class
10 A1 50B ON Failure ◎

Check 50B Relay should be OFF but this does not mean 50B Relay ON failure. Elevator should be
purpose stopped immediately, to avoid low reliability of the braking system.
After three minutes of no calling, main Micon through MZ50B contributes to Buffer to
Check control 50B Relay, and check MX50B and SX50B enter force Buffer signal to define
whether 50B Relay is normal.
condition Namely when MZ50B contributes Buffer OFF, but MX50B and SX50B enter force Buffer is
not off within 200ms, then abnormal has been checked.
Reset After removing failure and FFB cuts OFF-ON, run recovery through operating MODE2 to
Mode eliminate TCD.
Inspection Items:
1. Whether enter force Buffer has ON Failure Check
Whether main MX50B ($CA01) and the data of sub SX50B ($CD21) acting along with 50B
Relay’s ON-OFF is synchronous.
※Through operating MODE 22 to observe MX50B ($CA01)、SX50B ($CD21)

2. 50B Relay’s LED Check


(1) When 50B Relay is on, 50B LED is bright.
(2) When 50B Relay is off, 50B LED is off.
3. 50B Relay status Check:
The validation of 50B Relay’s lock, connecting point twist, fusing, and layout short circuit and so
on.
4. Arrange wire between SMPU PCB and FIOR PCB; Check whether MUD and FOD Connect has
poor connection.
5. SFIOR PCB Replacement
When the first item or the second item is abnormal but the fourth is alright, expressing SFIOR
contributes to poor Buffer, replacing SFIOR PCB.
6.SMPU PCB Replacement
After replacing SFIOR, if PCB is still running abnormally this a result of a faulty SMPU PCB.
Replace SMPU PCB.

6/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation
Failure
TCD Content HOLD
Class
11 A1 10T ON Failure ◎

Check When 10T main contactor is not off in time, expressing 10T main contact machine ON
Failure. In order to avoid low reliability of resisting system, elevator should be stopped
Purpose immediately.

When elevator stops through MZ10T contributes to Buffer to control 10T Ctt Turn OFF and
Check check MX10Tand SX10T enter force Buffer signal to define whether 10T Ctt acts normally.
Condition That is when MZ10T contributes to Buffer OFF but MX10T and SX10T enter force Buffer
is not off within 500 ms, then abnormalities have been checked.
Reset After failure is eliminated and FFB had switched OFF-ON, run recovery through operating
Mode MODE2 to clear TCD.

Inspection Items:
1. Whether enter force Buffer has ON Failure Check:
Whether main MX10T ($CA02) and the data of sub SX10T ($CD22) acting along with 10T main
contact machine is synchronous.
※Through operating MODE 22 to observe MX50B($CA01)、SX50B($CD21).

2. Voltage check of 10T main contact machine:


(1) The power of 10T main contact machine uses: the voltage between RECT FUSE and GD. →
DC 48V.
(2) When MZ10T is ON, the voltage between COIL (+) end and COIL (−) end of 10T main contact
machine is → DC 48V.
(3) During stop and open status, the voltage between COIL (−) end and GD48 of 10T main contact
machine is → DC 48V.

3. Status check of 10T main contactor:


The validation of 10T main contact machine locking, connecting point twisting, fusing, and layout
short-circuit and so on.

4. Arranging wire between SMPU PCB and FIOR PCB; Check whether MUD and FOD Connect has
poor connection. Arranging wire between SMPU PCB and FIOR PCB; Check whether MUD and
FOD Connect has poor connection.

5.SFIOR PCB Replacement


When the first item or the second item is abnormal but the fourth is ok, it means the SFIOR’s
contribution Buffer is not good, replacing SFIOR PCB.

6.SMPU PCB Replacement


If the abnormality still occurs after the replacement of SFIOR PCB, it means the SMPU PCB is not
good, and the SMPU PCB should be replaced.

7/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
12 A1 15B ON Failure ◎
When 15B contactor is not off in time, expressing 15B contact machine ON Failure. In order
Check to avoid an accident from happening, the elevator should be stopped immediately. When
Purpose 15B contact machine is not off in time, expressing 15B contact machine ON Failure. In order
to avoid an accident from happening, the elevator should be stopped immediately.
When the elevator stops through SZ15B contribution Buffer to control 15B Ctt Turn OFF
Check and check MX15B and SX15B enter force Buffer signal to define whether 15B Ctt acts
normally.
Condition That is when SZ15B contributes to Buffer OFF but MX15B and SX15B enter force Buffer is
not off within 500 ms, then abnormalities have been found.
Reset After failure is eliminated and FFB has switched to OFF-ON, run recovery through operating
Mode MODE2 to clear TCD.

Inspection Items:
1. Whether enter force Buffer has ON Failure Check:
Whether main MX15B ($CA00) and the data of sub SX15B ($CD20) acts along with 15B contact
machine is synchronous.
※MX15B($CA00)、SX15B($CD20) are operating, MODE 22 to be observed.

2. Voltage check of 15B contactor:


(1) The power of 15B contactor: the voltage between RECT FUSE and GD. → DC 48V.
(2) When SZ115B is ON, the voltage between COIL (+) end and COIL (−) end of 15B contactor is
→ DC 48V.
(3) During stop and under open status, the voltage between COIL (−) end and GD48 of 15B contact
machine is → DC 48V.

3. 15B contactor status Check:


The validation of 15B contactor locking, connecting point twist, fusing, and layout short-circuit and
so on.

4. Arrange wire between SMPU PCB and FIOR PCB; Check whether MUD and FOD Connect has
bad connection.

5.SFIOR PCB Replacement


When the first item or the second item is abnormal but the fourth is ok, it means the SFIOR’s
contribution Buffer is not good, replacing SFIOR PCB.

6.SMPU PCB Replacement


If the abnormality still occurs after the replacement of SFIOR PCB, it means the SMPU PCB is not
good, so replace the SMPU PCB.

8/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
13 A2 Abnormal SDC Running ----
Check After starting, the serial communication between SDC and SDA is unable to be managed.
Purpose Abnormality is found, and elevators cannot be restarted.
Check After starting, SDA sends Check code to SDC waiting for SDC to response. If SDC cannot
Condition respond within 500ms then define SDC sudden break.
Reset
Mode After failure is eliminated, running can automatically be recovered.

Inspection Items:
1. Check of LED (on the SMPU PCB) for SDA communication:
(1) TXD、RXD light is not on or bright. Check whether SDC PCB or CABLE wire is broken off.
(2) RXD light is slight illumination; the receipt is normal.
(3) Whether U39 IC of SDC PCB is properly inserted.

2. Check of broken wire of SDA communication cable:


The validation of broken cable or bad connection of communication cable.

3. Whether SDC PCB’s WDT on, off acts normally

4. Check of SDC PCB’s Power:


Whether the lamps of P22 LED and P5 LED of P48 LED are illuminated: light on →normal, light
off→ abnormal.

5. If the above clauses are normal, replace SDC PCB.

6. After replacement of SDC PCB, if it still cannot run normally, replace the SMPU PCB.

9/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
14 A2 Out-of-service of Sub MICON ----
Check Due to the reasons such as noise disturbance, the sub-Micon is suddenly broken, the WDT
Purpose lamp is off, and Elevator is forbidden to run because a failure has been found.
When unclear reasons cause sub Micon sudden break, after main Micon instantly checks and
Check forbids the elevator to run and after 2 seconds re-sensing whether sub Micon is running
Condition normally, if sub Micon has already recovered and sub-Micon’s sudden break time is less
than eight, then elevator will run normally again.
Reset
After the failure is eliminated, it will automatically start running again.
Mode

Inspection Items:
1. Check if the U32 and U33 IC of SMPU PCB haven been inserted properly, and if the lines and
parts are correct.

2. Verification of ON and OFF status of SWDT LED of Sub-Micon


Lamp ON → Normal, Lamp OFF → Abnormal

3. When the switch of main power is toggled between ON-OFF, verify the actions of ON and OFF of
SWDT LED of Sub-Micon.
If the SWDT LED can’t be started again (OFF), replace the SMPU PCB.

10/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
15 A2 Out-of-service of SDA OFF ----
Check Due to reasons such as noise disturbance and the SDA is suddenly broken, the elevator is
Purpose forbidden to run because a failure of main Micon has been found.
When the main Micon requests SDA to share the right of use (BUS) of RAM, while the SDA
can’t give the right of use or SDA can’t refresh the information shared with the RAM within
Check 200ms, the SDA is regarded as out-of-service.
Condition At that time, the main Micon will actively reset SDA, and re-check SDA after two seconds.
If the SDA has restored to normal status and when the times of out-of-service of SDA had
reached 8 times, the elevator will continuously run normally.
Reset After the failure is eliminated, it will automatically restore the running.
Mode

Inspection Items:
1. Check if SDA/WEE785 (U34 IC over the SMPU PCB) has been inserted properly, and if the lines
and parts are correct.

2. When the No.1 item is normal, replace the SMPU PCB.

11/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
16 A2 Abnormal Main and Sub Parallel Communication ----

Check Due to reasons such as noise disturbance, the main and sub parallel communication is
Purpose from beingthe
abnormal; elevator’s running is prohibited to prevent the reliability of safeguard system
decreased.
Every 20ms, the main and sub Micon will communicate one time, and the sub Micon will
re-transfer the commands of parallel ports of main Micon from Dual-Port RAM to the main
Check Micon, and the main Micon will use Dual-Port RAM to check if the commands sent by itself
Condition are correct. If the command of main Micon and the response command are not consistent
after 200ms, it can be inferred that the main and sub-Micon parallel communication is
abnormal, and the running of the elevator is forbidden.
Reset After the failure is eliminated, it will automatically restore the running.
Mode

Inspection Items:
1. Check if the parallel communication of SMPU PCB and the Dual-Port RAM have been inserted
properly, and that the lines and parts are correct.

2. Re-download the EEPROM information of main and sub Micon.

3. When the No.1 item and the No.2 item are normal, replace the SMPU PCB.

12/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
17 A3 Abnormal Parallel Communication of SDA and SDC ----

Check Due to reasons such as noise disturbance, the parallel communication of SDA and SDC is
abnormal, and the elevator’s running is prohibited from preventing the error action of signal
Purpose and from increasing the reliability of the safeguard system.
After power-on, when the SDA and SDC reach the communication agreement, the
communication is interrupted or the communication inspection code has an error due to the
Check uncertain reasons of SDA and SDC such as Noise under the running status of elevator, SDA
Condition will try to reach the communication agreement with SDC, if the SDC has no response after 9
times of SDA Retry, it will regard as the parallel communication of SDA and SDC is
abnormal, and the running of the elevator is prohibited.
Reset
Mode After the failure is eliminated, it will automatically start running.

Inspection Items:
1. Check of SDC PCB’s Power
(1) If the 5P LED of SDC PCB is illuminated (lamp on/normal).
(2) If the 22P LED of SDC PCB is illuminated (lamp on/normal).
(3) Confirm if the P5V and P22V of SDC PCB are normal.

2. Check of Cage RX LED for SDA’s Communication:


(1) LED lamp doesn’t illuminate: Check if U34 IC of SMPU PCB has been inserted properly and if
there is a broken Cable.
(2) LED lamp illuminates slightly; receiving is normal.
(3) LED lamp illuminates brightly; the TXD cable connects reverse with RXD cable.

3. Check for broken SDA SDC communication cable:


Check if there is broken communication cable or bad connection.

4. It the above items are normal, replace the SDC PCB.

5. If it can’t run normally after the replacement of SDC PCB, replace the SMPU PCB.

13/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
18 A3 50BC Failure or Switch of E. Stop is cut ----
Check The safety circuit of 50BC hasn’t been applied due to the abnormality, and the elevator’s
Purpose running is prohibited to increase the reliability of safeguard system.
1. Abnormality is detected because the safety circuit of 50BC hasn’t been applied due to the
Check actions of safety devices such as FLS, overrunning governor, and escape hole.
Condition 2. It also will record when the switch of E. Stop is being toggled, while it doesn’t belong to
the abnormality.
Reset
Mode After the failure is eliminated, it will automatically restore the running.
Inspection Items:
1. TCD 19 is also being detected, directly inspect the TCD 19, and the below 2~6 items are free of
being inspected.
2. TCD 19 hasn’t been detected
The stop switch of cage top and stop switch of inside cage are cut-off, and confirm if PLS of top cage
is acted.
3. If the 50BC LED of SFIOR PCB is applied (Lamp ON→applied, Lamp OFF not applied).
4. Lay cables between SMPU PCB and FIOR PCB; check if there is bad connection of MUD and FOD
Connect.
5. If the above items are normal, replace the SFIOR PCB.
6. Replacement of SMPU PCB
After the replacement of SFIOR PCB, if there is the occurrence of abnormality, it means the SMPU
PCB is not good, and replace the SMPU PCB.

Skeleton

Lock Device of Working Platform of UAY1 Cage

Top Inside
FLS GRS MHS SCS PLS E.STOP STOP

X50BC
CA03

X99G
CA06

14/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
19 A3 99GFailure ----

Check The safety circuit of 99G hasn’t been applied due to the abnormality, and the elevator’s
Purpose running is prohibited to increase the reliability of safeguard system.
Check Abnormality is detected because the safety circuit of 99G hasn’t been applied due to the
Condition actions of safety devices such as FLS, overrunning governor, and escape hole.
Reset
Mode After the failure is eliminated, it will automatically restore the running.
Inspection Items:
1. Check if FLS、GRS、MHS、SCS are acted.

2. Check if 99G LED of SFIOR PCB is acted (Lamp ON→Acted, Lamp OFF Not Acted).

3. Lay cables between SMPU PCB and FIOR PCB; and check if there is bad connection of MUD
and FOD Connect.

4. If the above items are normal, replace the SFIOR PCB

5. Replacement of SMPU PCB


After the replacement of SFIOR PCB, if there is the occurrence of abnormality, it means the
SMPU PCB is not good, and replace the SMPU PCB.

Skeleton

Lock Device of Working Platform of

Top Inside
FLS GRS MHS SCS PLS E.STOP STOP
X50BC
CA03

X99G
CA06

15/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
20 A1 Double Application BUFFER Failure ○

Check Check if the signals of double application of main and sub Micon are consistent, and failure
Purpose is found in order to increase the reliability of safeguard system.

The SFIOR important safety signal read from Micon every 20ms will be transferred to main
Check Micon via Dual-Port RAM (IDT 7134), and main Micon will compare the SFIOR important
Condition RAM, if theyread
safety signal by itself and the SFIOR important safety signal of sub Micon of Dual-Port
are not consistent, failure will be found after 200ms, and the running of
elevator is prohibited.

Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the lamps of Watch Dog of main and sub Micon of SMPU PCB and lamps of MWDT
and SWDT are illuminated normally.
Lamp ON → Normal, Lamp OFF → Abnormal
2. Lay cables between SMPU PCB and FIOR PCB; and check if there is bad connection of MUD
and FOD Connect.
3. Check if the data of main Micon and sub Micon are consistent, and operate MODE 22 SET to
check.
Compare the main Micon ($CA01~$CA0E) and sub Micon ($CD20~$CD2E) one by one.
e.g. The Address CA01 should conform to Data of CD20 (CODES of Addresses refers to the Sheet
of Main Micon Device).
※Operate the $CA01~$CA0E and $CD20~$CD2E and observe MODE 22.
4. If the above items are normal, replace the SFIOR PCB
5. Replacement of SMPU PCB
After the replacement of SFIOR PCB, if there is the occurrence of abnormality, it means the
SMPU PCB is not good, and replace the SMPU PCB.

Skeleton

Main Micon

ZX15BM=ZX15BS 200ms TCD 20


C10A

16/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
21 A1 Over current Check (IPM FAULT) ○

Check To prevent the main transistor (IGBT) from burning out, inspect the three phase U, V, W
Purpose current,of
current circuit of motor by the Hall CT (HCT U/V) or drive IC (EXB841). When it is over
the elevator will be immediately come to an emergency stop, and can’t be started.
1. IPM Fault Output: Include the protection actions such as over current, short-circuit
current, under-voltage and overheat of interior of IPM;
2. Hall CT (HCT U/V) Inspection: IGBT module U,V phase current, feedback control and
Check over current inspection;
Condition 3. In addition, drive IC(EXB841)-(IGD PCB之U21~U29) of 150m/min elevator; IGBT
module output, and short-circuit protection.
※The value of over current will be governed by the specification of IGBT and the setting
value of turns of HCT.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON,
Mode running will resume.
Inspection Items:
1. Lay cables between SMPU PCB and BDC PCB; and check if there is bad connection of MUG and
BCE Connect;
2. Check the working voltage of SMPU PCB; If +5V, +15V, -15V are normal;
3. The inspection mode when the IGBT is normal will be as per the below table.

(+) (-) 数位电表DIODE档


Digital multimeter DIODE
G C
E C 0.2~0.5V Rg
Over as indicated on the
C E OVER电表所示
multimeter
Over as indicated on the
G C OVER电表所示
multimeter

C G
Over as indicated on
OVER电表所示
multimeter
the Rge
Over as indicated on the
G E OVER电表所示
multimeter
E
Over as indicated on the
E G OVER电表所示
multimeter

(1) Please note that the input impedance of IGBT is very higher, it is easily to be damaged by
body’s static when it is Open status within GE, and pay attention during handling period.
(2) If the IGBT has been damaged, the damage ratio of the corresponding Rg and drive IC
(EXB841) is 90%, and they should be replaced simultaneously.
(3) After power on and before the running of elevator, measure the voltage between G1 and E1,
or between G2 and E2 of BC, BCJ, BCK, BCL of BDC board, and the voltage should be
about −4V~−5V (Don’t cause the short-circuit between measuring points). If there is no
problem for the voltage between measuring points, replace the BDC board or the drive IC
(EXB841) of board.

17/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

22 A1 Over voltage Inspection -----

There is a failure at the feedback power consumption circuit. In order to protect such
Check assemblies as the smooth capacitance of main circuit and IPM (IGBT), design the optical
Purpose coupling inspection circuit. When the abnormal over voltage is detected, the elevator will be
stopped immediately, and the re-start is not allowed.
Check When the DC voltage of INV main circuit is detected, and the DC voltage exceeds the
Condition setting value of OVBRA, the action of over voltage will be detected.
Reset
After the Failure is eliminated, the running will be automatically resumed.
Mode

Inspection Items:
1. Lay cables between SMPU PCB and BDC PCB, and check if there is bad connection of MUG and
BCE Connect.
2. Confirmation of feedback action;
When the feedback action is occurred (below 50% is up with light-cage, or over 50% is down with
heavy-cage. It should sound the click prodded by the feedback resistance.
3. Check if there is broken cable at the feedback resistance circuit.
4. Check the working voltage.
Check if the setting value of action voltage of feedback IGBT inside the BDC PCB is correct.
Setting values: 380V system: DC10.2V; 220V system DC5.7V; Adjust the OVBR resistance.
※KWH meter measuring points: Between 1 Pin and 5 Pin of TESTOB Connect (1 Pin is positive
and 5 Pin is negative).
※SW OFF the speed governor prior to measurement to prevent the power-on measurement after the
running of the elevator.
5. IGBT Test;(When the IGBT is normal, temporarily disconnect the wiring between the feedback
resistance and IPM)
(+) (-) 数位电表DIODE档
Digital multimeter DIODE

U,V,W,B P 0.2~0.5V
Over as indicated on the
P U,V,W,B OVER电表所示
multimeter
Over as indicated on the
N U,V,W 0.2~0.5V
multimeter
Over as indicated on the
N B OVER电表所示
multimeter
Over as indicated on the
U,V,W,B N OVER电表所示
multimeter

(1) Please note that the input impedance of IGBT is very higher, it is easily to be damaged by
body’s static when it is Open status within GE, and pay attention during handling period.
(2) If the IGBT has been damaged, the damage ratio of the corresponding Rg and drive IC
(EXB841) is 90%, and they should be replaced simultaneously.
6. Check the appearance of BDC PCB. If the reason is not clear, replace the BDC PCB. 18/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

23 A2 Abnormality of SDC Protection Switch ○

Check There is failure at the safety contact of protection switch and the force is applied falsely, the
Purpose elevator is not allowed to run in order to increase the reliability of safeguard system.
Detect the force application status of protection switch every 20ms. Because the safety
Check contact of protection switch is double-force application, when SDC finds the signal of
Condition double-force application of protection switch is not reasonable, the failure will be detected
after 100ms.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the contact of protection switch of cage is normal.
Check if normal ON and normal OFF of interior contacts of protection switch is damaged.
2. Check the wiring of Connect:
Check the insert status of OAK Connect of SDC PCB and check if there is broken cable or bad
connection.
3. Replace the SDC PCB if the above items are normal.

19/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

24 A2 Sub MICON Dual-Port RAM ERROR ----

The sub-Micon will check sum every 40ms the Dual-Port RAM (U40-IDT 7134) of the main
and sub Micon. The major purpose is to prevent the information from being transferred
Check
falsely due to the damage of Dule-Prot RAM. The failure will be detected when there is Sum
Purpose
Error,and the elevator is not allowed to run in order to increase the reliability of safeguard
system.
The information transfers between the main and the sub-Micon relies on the Dual-Port
Check RAM. Normally the usage life of RAM is limitless. In order to avoid the occurrence of
Condition possible damage that will cause the failure of system, the main and the sub Micon will check
mutually if the write code is correct to prevent the accident from being occurred.
Reset
After the Failure is eliminated, the running will be automatically resumed.
Mode

Inspection Items:
1. Check if the sub Micon Dual-Port RAM/IDT 7134 (SMPU PCB上U5 IC) is inserted properly, and
check the lines and elements concerned are correct.
2. Re-download the programs of main and sub Micon EEPROM.
3. Check if the sub Micon EPROM and main Micon (SMPU PCB上U32,U33,U31 IC) is inserted
properly, and check the lines and elements concerned are correct.
4. Replace the SMPU PCB if the above items are normal.

20/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

25 A2 Sub MICON EEPROM ERROR ----

The information stored in the EEPROM is the important sample values, and it is possible
Check that the factors such as outside noise will change the information inside the EEPROM, which
Purpose will result in the false action of elevator. So it is very important to re-check the information
inside the EEPROM.
Avoid the specification Table of Motor is incorrect, which will result in the abnormal
running of elevator, and the assemblies will be damaged due to the abnormal running.
Check
Therefore, the sub-Micon will Check Sum every 40ms the EEPROM/AT28C16 (U48) of the
Condition
sub Micon. The failure will be detected when there is Sum Error and the running of the
elevator is prohibited.
Reset
After the Failure is eliminated, running will automatically resume.
Mode

Inspection Items:
1. Check if the EEPROM/AT28C64 (U10 IC of SMPU PCB) is inserted properly, and check the lines
and elements concerned are correct.
2. It the No.1 item is normal, re-Down-Load the sample Table of the sub Micon.
3. Replace the SMPU PCB if the above two items are normal.

21/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

26 A1 DSP SUM ERROR ○

Check Avoid the failure of DSP program code for the control of Motor, which will result in the
Purpose abnormal running.
After starting up, the sub Micon will download the DSP program code into the Dual-Port
RAM/IDT7143 (U56) and will subsequently inspect if the DSP program code filled in the
Check Dual-Port RAM is correct. When there is error, the failure will be detected, the running of
Condition elevator is prohibited.
The reasons result in the abnormality are as following: Damage of Dual-Port RAM, and the
error download information due to the Noise disturbance.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the DSP sample parameters wrote into the Dual-Port RAM/IDT7143 (U9 IC of SMPU
PCB) is inserted properly, and check if the lines and elements concerned are correct.
2. It the No.1 item is normal, re-Down-Load the sample Table of the sub Micon.
3. Replace the SMPU PCB if the above two items are normal.

22/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
27 A1 Inspection of Many Occurrences’ Failure ○

Avoiding running will automatically resume after the continuous repeated occurrence of
Check
rescue running within the short time, which will result in the abnormal running. Such
Purpose
important Failure will limit the times of occurrence of Failure within certain period.
1. When the accumulated times of inspection of any one of TCD11, TCD12, TCD16,
TCD17, TCD22, TCD32, TCD34 exceeds 6 times within ten minutes, namely the TCD27
will be produced when the 6th rescue running is occurred, which will not automatically reset.
Check 2. When the accumulated times of inspection of any one of TCD62, TCD63, TCD64 at
Condition anytime period exceeds three times, namely the TCD27 will be produced when the 3rd rescue
running is occurred, which will not automatically reset.
※The main power FFB toggles OFF-ON, or operates MODE2 to clear TCD. The
accumulated times will automatically return to zero.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1.Failure Monitor Content Readout:
Analyze the occurrence status of Failure, and investigate the cause of Failure.

23/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

28 A2 Abnormal P15V Voltage ◎

Check The abnormality is detected when there is loss Failure at the P15V reference voltage, and the
Purpose start-up of elevator is prohibited.
Check Detect the P15V circuit voltage at the MPU side, and it will be regarded as the abnormality if
Condition the status of no voltage lasts continuously over one second.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will be resumed.
Inspection Items:
1. Check the Connect and MIC locked status of P15V and N15V.
2. The loss of P15V will cause the Rotary encoder can’t be acted, the failure of HCT, the failure of
over current protection, and the failure of power-off protection.
The assemblies will be burnt out if the elevator is started at that time.

AVR F-MPU

P15 MUC1

GND MUC2

N15 MCU3

P5 MCU4

GND MCU5

24/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

29 A1 Main MICON EEPROM ERROR ◎

The information stored in the EEPROM are important sample values, and it is possible that
Check factors such as outside noise will change the information inside the EEPROM, which will
Purpose result in the false action of the elevator. So it is very important to re-check the information
inside the EEPROM.
Avoid the specification Table of Motor is incorrect, which will result in the abnormal
Check running of elevator. The main Micon will Check Sum every 20ms the EEPROM (U48 -
Condition AT28C16) of the main Micon. The failure will be detected when there is Sum Error and the
running of the elevator is prohibited.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode running will resume.
Inspection Items:
1. Check if the EEPROM/AT28C64 (U2 IC of SMPU PCB) is inserted properly, and check the lines
and elements concerned are correct.
2. It the No.1 item is normal, re-Down-Load the sample Table of the main Micon.
3. Replace the SMPU PCB if the above two items are normal.

25/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

30 A2 Main MICON NVSRAM ERROR ○

The NVSRAM (U26-DS1644) IC of the main Micon contains the battery with lifetime of 20
years and RAM. For the elevator, the stored information is very important, and the stored
Check information is as follows:
Purpose (a) The level value of each landing terminal.
(b) Record of the final running status information at the transient period of power off.
(c) Permanent calendar.
The main Micon will Check Sum every 40ms the NVSRAM (U26) of the main Micon. The
Check
failure will be detected when there is Sum Error and the running of the elevator is prohibited
Condition
in order to increase the reliability of safeguard system.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will resume.

Inspection Items:
1. Check if the NVSRAM/DS1644 or BQ4830Y (U28 IC of SMPU PCB) is inserted properly, and
check the lines and elements concerned are correct.
2. If the No.1 item is normal, replace the SMPU PCB.

26/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
31 A2 DSP Dual-Port RAM ERROR ○

The information transfer between the sub Micon and DSP rely on the Dual-Port RAM.
Check Normally the usage life of RAM is limitless. In order to avoid the occurrence of possible
Purpose damage that will cause the failure of system, the main and the sub-Micon will check
mutually if the write code is correct to prevent the accident from being occurred.
The sub-Micon will Check Sum every 40ms the Dual-Port RAM (U56-IDT7143) between
Check the sub Micon and DSP. The failure will be detected when there is Sum Error and the
Condition running of the elevator is prohibited in order to increase the reliability of the safeguard
systems.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will resume.

Inspection Items:
1. Check if the Dual-PortRAM/ITD7143 (U56-IDT7143) (U9 IC of SMPU PCB) is inserted properly,
and check the lines and elements concerned are correct.
2. If the No.1 item is normal, replace the SMPU PCB.

27/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD
Class
Content Relation HOLD

32 A1 Abnormality Detection of Inhibiting Circuit (OPCH) ----

When the over current or over voltage is occurred during running period of elevator, it
Check
should instantly turn off the IGBT (IPM) before 10T OFF to prevent the IGBT (IPM) from
Purpose
being burnt out, and it will immediately stop running or starting.
Check Compare the drive force-in signal of the main Micon and the feedback force-out signal
Condition (OPCH) of BDC, and the failure will be detected after 20ms if they are not consistent.
Reset
After the Failure is eliminated, running will automatically resume.
Mode

Inspection Items:
1. Lay cables between SMPU PCB and BDC PCB; and check if there is bad connection between MUG
and BCE Connect.
2. Normally the detection of TCD 32 is resulted from the over current or over voltage.
Check if there is the Failure record of TCD 21 (over current) or TCD 22 (over voltage) and
investigate the failure reasons of TCD 21 or TCD 22.
3. Replace the BDC PCB if the above items are normal.

28/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

33 A2 Abnormal Voltage of BDCC ○

The abnormality of drive IC of BDC PCB and power voltage of Base Drive will cause the
Check
voltage between IGBT GE is not enough and will burn the IGBT. Therefore, check to see if
Purpose
each group of Switching Power voltage of BDC PCB is very lower.
Detect the voltage at the secondary side of each group of Switching Power of BDC PCB.
When abnormal power is detected and the main Micon detects continuously the abnormality
Check
for 20ms, the elevator will be stopped immediately.
Condition
During abnormal period, the LED of BSVOK will be OFF, and the LED will be ON during
the normal period.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Lay cables between SMPU PCB and BDC PCB; and check if there is bad connection between MUG
and BCE Connect.
2. Check if the power voltage of each group of Switching Power of BDC PCB is normal.
3. Replace the BDC PCB if the above items are normal.

29/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

34 A2 Detection of Short Voltage ----

The voltage of PN BUS is lower, and re-start will cause the main IPM (IGBT) being burnt,
Check
or the feedback IPM (IGBT) being burnt, and detection of broken RSH resistance. It is
Purpose
necessary to check if the voltage of PN BUS is exceptionally lower than before the start-up.
Check The Failure is detected when the voltage between C and E of feedback IPM (IGBT) fell
Condition below a certain value (200V) prior to the start-up of elevator.
Reset
After the Failure is eliminated, running will automatically resume.
Mode
Inspection Items:
1. Lay cables between SMPU PCB and BDC PCB, and check if there is a bad connection between
MUG and BCE.
2.Check the power voltage:
(1) Phase voltages (R,S), (R,T), (S,T) of three phases R, S, and T: Shanghai Tungtay is AC 380V,
and Taiwan Yungtay is AC 220V or 380V.
(2) PN output voltage (the positive and negative ends of 5600uf main capacitance): Shanghai
Tungtay: DC 532V+15%, and Taiwan Tungtay: DC 308V or 532V+15%.
3. Feedback IPM Test (Temporality dismantle the wiring between the feedback resistance and IPM
when the IGBT is normal):
(+) (-) 数位电表DIODE档
Digital mult1meter DIODE

B P 0.2~0.5V
Over as indicated on the
P B OVER电表所示
multimeter
Over as indicated on the
B N OVER电表所示
multimeter
Over as indicated on the
N B OVER电表所示
multimeter

(1) Please note that the input impedance of IGBT is very higher, it is easily to be damaged by
body’s static when it is Open status within GE, and pay attention during handling period.
(2) If the IGBT has been damaged, the damage ratio of the corresponding Rg and drive IC
(EXB841) is 90%, and they should be replaced simultaneously.
4. Replace the BDC PCB if the above items are normal.

30/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

35 A3 40G, 40D ON Failure ◎

Check To avoid the opening-door running, when the cage door is opened completely, if the force-in
signal of connection of 40G or 40D Relay is still ON, which means the Gate Sw or Door Sw
Purpose is short-circuited, running of elevator is prohibited.

Check When the door is opened completely, the door machine will send an action signal of
ZXOLS, and the force-in Buffer of MX40G or MX40D is ON at that time, the Failure is
Condition detected after 200ms, and the running of elevator is prohibited.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will resume.
Inspection Items:
1. Check the status of Gate Sw and Door Sw:
(1) Check if the connection of Gate Sw is obstructed and if there is short-circuit at the wiring.
(2) Check if there is carbonized short-circuit at TIP of Door Sw, and if there is short-circuit at the
wiring. (Including the transient abnormality)
2. Check the status of 40G and 40D Relay:
Check if the 40G and 40D Relays are obstructed, if the connection is bent or melted, and if there is a
short-circuit at the wiring.
3. Check the LED of 40G and 40D Relays
(1) When the door is closed fully, 40G and 40D LED are ON.
(2) When the door is opened, 40G and 40D LED are OFF.
4. Check if there is an ON Failure of the force-in Buffer:
When the leveling door is opened or closed, observe the Data values of MX40G($CA05) and
MX40D($CA04) (81 door is closed fully and 00 door is opened).
When ZXOLS OFF, it will on after 200ms
Main Micon

ZXOL ZT1F ZX40D


TCD35
C505 CF1F CA04 C119
ZX40G

CA05

5. Check the OLS signal of door machine:


When the cage door is opened completely, the OLS LED at the FB-DMC PCB上 is ON (When the
door is opened completely, the door machine will send an OLS signal).
6. Replace SFIOR PCB if the above items are normal.

31/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

36 C1 SDC Operation Mode Failure ----

When the up and down buttons of top cage are obstructed, the elevator will enter into
maintenance mode. Once the landing door is closed, the elevator will automatically run at a
Check
slow-speed, which will be dangerous to the personnel. If it detects that the up and down
Purpose
buttons are obstructed during usual period, the elevator can’t be started after the door is
opened.
When X43OH is ON, if it detects that the time that XONU or XOND is HI exceeds three
seconds, the elevator will stop at one floor with deceleration during running period. It will
Check
stop the running after the door is opened, and the elevator can’t be started during stop period.
Condition
After the TCD is detected, it will automatically resume to normal if XONU or XOND are
LO.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. Check if there is purposely a mistaken operation.
2. Check if the up and down buttons of top cage are obstructed and if there is short-circuit in the
wiring.
3. Check if the force-in Buffer of XONU or XOND is ON Failure.
Observe the Data values of XONU ($C50E) and XOND ($C50F).
※ Operate XONU ($C50E) and XOND ($C50F) and observe MODE 22.

32/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation
Failure
TCD Content HOLD
Class

37 A2 Reversion Detection ○

During reverse detection (sometimes it is not the pure reversed running of motor), the
following cases may occur:
Check (a) The phases of power of motor is connected incorrectly.
Purpose (b) The two signal wires of the Rotary encoder are reversed.
(c) The setting parameter of motor is not correct.
(d) IPM (IGBT) is burnt or Rotary encoder is damaged.
The signal of Rotary encoder will detect the main Micon, and will judge the actual running
direction of elevator. 1. When the actual running direction is not consistent with the
Check command direction of the main and the sub Micon, the speed is over 8m/min, and the
Condition command direction is still not same as the actual direction after 120ms, the failure is
1 detected; 2. The feedback running direction is contrary to the speed command direction, and
feedback feed is over 8m/min, and Failure is detected after it lasted for 150ms.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will resume.
Inspection Items:
1. Check the reverse detection at the commission site:
(1) Induction Motor- According to M/C hanging mode, determine exchange the wiring of ψA and
ψB or exchange the wiring of two phases of U and W.
(2) PM Motor - According to the RE and motor wiring mode (It is defined as the exchange of U and
V if it is necessary to exchange the motor wiring) shown in the figure below.
2. Check the reversion detection at the maintenance site:
(1) Observe the steel cable on the Sheave - When the starting compensation is confirmed, check if
there is fundamental reversal at the cage, and if the running direction is correct.
(2) Check if there are abnormalities at the IGBT and BDCC of the main circuit, and replace them if
there is damage.
(3) Replace the SMPU PCB if item (1) and item (2) are normal.
3. Replace the Rotary encoder if it the replacement of SMPU PCB is invalid.

MPU Terminal MPU Terminal


Red
红 Red
pin1 P5 红
Black
黑 pin1 P5 Black
G 黑
Green
绿 G
A Motor input of control cabinet
Green
绿
绿/黑
Green/Black ENCODER A
/A 蓝
Blue Power Terminal /A 绿/黑
Green/Black
ENCODER Motor Input of Control Cabinet
B Blue

Blue/Black
蓝/黑 B Power Terminal
/B U Blue/Black
蓝/黑

Yellow U /B 黄
Yellow
Z Yellow/Black V PM Z
黄/黑 Yellow/Black
/Z V MOTOR /Z
黄/黑 U
S S U
S W S V PM

Brown
W 棕
Brown V MOTOR
pin1 U Brown/Black
pin1 U W
/U
棕/黑
/U
Brown/Black
棕/黑 W
Gray
灰 灰
Gray
V 灰/黑
Gray/Black V 灰/黑
Gray/Black
/V 白 /V
White 白
White
W White/Black W
白/黑 White/Black
白/黑
/W /W
PM Motor is left-hang PM Motor is right-hang

33/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class

38 A2 DSP Failure Detection ----

Check Due to the reasons such as noise disturbance, the sub Micon is suddenly broken, the WDT
Purpose lamp is off, and Elevator is forbidden to be run because of failure has been found.
When the cause of the sub-Micon sudden failure is unclear after the main Micon check
Check instantly stops the elevator from running and after 2 seconds reassessing whether the
Condition sub-Micon is running normally, if sub-Micon has already recovered and sub- Micon’s
sudden break times less than eight then elevator is running normally again.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1.Check the ON status of DSP Check Sum LED.
LED ON→DSP Normal, LED OFF→DSP Failure。
2. The main power supply toggles ON-OFF, and re-check the ON action status of DSP Check Sum
LED.
If DSP can’t ON normally, replace the SMPU PCB.

34/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

39 A1 100R ON/OFF Failure ○

When 100R Relay is not OFF in time, expressing 100R Relay ON Failure. In order to avoid
Check reliability of safeguard system is weakened, the elevator should be stopped immediately.
Purpose When 100R Relay is not ON in time, expressing 100R Relay OFF Failure. In order to avoid
reliability of the safeguard system is weakened, the elevator should be stopped immediately.
Check if the action of 100R Relay is normal via MZ100R force-out Buffer controls 100R
Relay Turn ON/OFF and detects the force-in Buffer signals of MX100R and SX100R.
Check That is when:
(1) MZ100R force-out Buffer ON, while the force-in Buffer of MX10T and SX10T are not
Condition ON within 200ms, the failure is detected.
(2) MZ100R force-out Buffer OFF, while the force-in Buffer of MX10T and SX10T are not
OFF within 200ms, a failure is detected.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the force-in Buffer has ON Failure or OFF Failure:
If the Data of the main MX100R ($CA07) and the sub SX100R ($CD27) will act simultaneously
with the ON-OFF of 100R Relay.
※ 100R Relay will ON only at the Running Open and Micro Leveling stages.
※ Operate the MX100R ($CA07) and the SX100R ($CD27) and observe MODE 22.
2. Check the LED of 100R Relay:
(1) When the 100R Relay is ON, the 100R LED is ON.
(2) When the 100R Relay is OFF, the 100R LED is OFF.
3. Check the status of 100R Relay:
(1) Check if the 100R Relay is obstructed, if the connection is bent or melted, or if there is
short-circuit in the wiring.
(2) Check if the coil of 100R Relay is broken, if the contact of the connection is not good, or if
there is short-circuit in the wiring.
4. Lay cables between SMPU PCB and FIOR PCB, and check if there is a bad connection between
MUG and FOD Connect.
5.SFIOR PCB Replacement
If item 1 or item 2 is not good, while the item 4 is good, it means the force-out Buffer of SFIOR is
not good, and you need to replace the SFIOR PCB.
6.SMPU PCB Replacement
After the SFIOR PCB is replaced, if the failure is still occurring, it means the SMPU PCB is not
good, and the SMPU PCB should be replaced.

35/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
40 A2 ROTARY ENCODER Failure ○

When running command of elevator is issued, the Rotary encoder will produce the Pulse due
Check
to rotation, and the quantity of Pulse represents the running distance and the speed. When
Purpose
Rotary encoder is damaged and the Pulse can’t be produced, the Failure is detected.
Detection during starting period; Running command ON, Rotary encoder will output the
Check Pulse after 1.5 seconds, and it is zero detection.
Condition Detection during running period; After runs for over 2 seconds, and the speed command of
over 15m/s is issued, the Pulse force-in of Rotary encoder is still zero.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will resume.
Inspection Items:
1. Check the wiring of Rotary encoder:
5VRE terminal of SMPU PCB; Check if there is bad connection or faulty wiring.
2. Check the voltage of P15V:
MUF Connect on the SMPU PCB; the voltage between Pin1 and Pin2 is +15V.
3. Replace the worn or faulty body of the Rotary encoder.
4. IReplace the SMPU PCB if the above items are normal.

MPU Terminal
MPU Terminal pin1 Red
P5 Black
pin1 P5 Red G
Black
黑 Green
G A
Green Green/Black ENCODER
A Motor input of control cabinet
/A
Green/Black ENCODER B Blue Motor input of control cabinet
/A Power Terminal Blue/Black
Blue /B Power Terminal
B Yellow
Blue/Black
/B PM Motor isUleft-hangU Z PM Motor is right-hang
Yellow/Black
Z Yellow /Z U
Yellow/Black V PM S U
/Z V MOTOR
S V PM
S V
S W Brown MOTOR
W pin1 U W
Brown /U Brown/Black W
pin1 U Gray
Brown/Black V
/U 灰 Gray/Black
Gray /V
V Gray/Black White
W
/V White /W White/Black
W
White/Black
/W

36/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
41 A2 Low-speed OVER SPEED ----

The vector control 『speed feedback』of motor will make the actual running speed of
Check elevators follow the speed command of the Micon, and the speed allowance value of
maintenance running should not be over 120%. If the speed allowance exceeds 120%, the
Purpose Micon will issue the emergency stop command to prevent the accident from being happened.
It will not exceed ± 50% of rated ALP running speed during the running period of ALP.
1. During the maintenance running at cage top or inside cage, the sub Micon will compare
the speed command value and the speed feedback value. If the actual running speed of
elevator exceeds 15m/min, and the speed feedback value is greater than over 25% of
speed command value and it is still greater than 25% after 250ms, the sub Micon will
Check
Condition 2. detect the failure.
The running speed of ALP is abnormal, which exceeds ±
3. 50% of rated speed, and lasts for over four seconds.
The running speed of ALP should not be greater than 7.5m/min and should not be less
than 2.5m/min.
Reset After the failure is eliminated, it will automatically resume running.
Mode

Inspection Items:
1. Measurement of actual speed:
(1) MODE 27 SET read-out speed.
(2) Use auto meter to measure the maintenance running speed.
(3) If the speed values of item 1 and item 2 are within 125%, a Failure is still detected, which means
the speed detection circuit is not good.
(4) When the speed values of item 1 and item 2 exceed 125%, the speed safeguard circuit is not
good.
Re-Down Load the DSP sample value of the sub Micon and re-check them.
2. Investigate the reversion and department during the low-speed starting period:
Check the load detection and the adjustment value of starting compensations.
3. Observe the running speed of ALP:
MODE 27 SET read-out speed
4. Replace the faulty body of Rotary encoder.

37/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
42 A1 50B OFF Failure ----

Check 50B Relay should be ON but not, means 50B Relay OFF failure. Elevator should be stopped
Purpose immediately, avoiding low reliability of safeguard system.

After three minutes of no calling, main Micon through MZ50B contribute Buffer to control
Check 50B Relay OFF-ON, and check MX50B and SX50B enter force Buffer signal to define
whether 50B Relay is normal.
Condition Namely when MZ50B contributes Buffer ON, but MX50B and SX50B enter force Buffer is
not ON within 200ms then abnormal has been checked.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. Whether the enter force Buffer has an ON Failure Check
Whether the main MX50B ($CA01) and the data of sub SX50B ($CD21) acts along with 50B
Relay’s ON-OFF is synchronous.
※ By operating MODE 22 to observe MX50B ($CA01)、SX50B ($CD21)

2. 50B Relay’s LED Check


(1) When 50B Relay is on, 50B LED is bright.
(2) When 50B Relay is off, 50B LED is out.
3. 50B Relay status Check:
The validation of 50B Relay’s lock, connecting point twist, fusing, and layout short-circuit and so
on.
4. Arranging wire between SMPU PCB and FIOR PCB. Check whether MUD and FOD Connect has
a poor connection.
5. SFIOR PCB Replacement
When the first item or the second item is abnormal but the fourth is okaythis shows that the SFIOR
contributes Buffer’s faultiness, so you must replace the SFIOR PCB.
6.SMPU PCB Replacement
If, after replacing the SFIOR PCB, there are still abnormities, this means the SMPU PCB is faulty.
Replace the SMPU PCB.

38/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
43 A1 SPD Circuit Failure ○

SPD circuit is designed inside the FPGA (U68-PLSI1024), when the IC Failure, it is possible
Check that the speed command has issued while the speed feedback value is zero, or the speed
Purpose command value is not consistent with the speed feedback value, which will result in
abnormal running. Therefore, design the SPD circuit to detect the Failure.
Check When the speed command had reached over 8 m/min and the actual speed detected by the
Condition Pulse amplitude width is still 0m/min, the failure will be detected after 500ms.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.
Inspection Items:
1. Check the wiring of Rotary encoder:
5VRE terminal of SMPU PCB; Check if there is bad connection or fallen wiring.
2. Check the voltage of P15V:
MUF Connect on the SMPU PCB; the voltage between Pin1 and Pin2 is +15V.
3. Replace the bad body of Rotary encoder.
4. Replace the SMPU PCB if the above items are normal.

MPU Terminal MPU Terminal


Red
红 Red
pin1 P5 pin1 红
Black
黑 P5 黑
G Green
绿 G
Black
A Green
绿
Green/Black ENCODER Motor Input of Control Cabinet A Green/Black
/A Blue
蓝 Power Terminal /A
ENCODER
B B Blue
蓝 Motor Input of Control Cabinet
Blue/Black U
/B U /B Blue/Black Power Terminal
Yellow Yellow

Z V PM Z
Yellow/Black Yellow/Black
/Z S V MOTOR /Z U
S S U
W S V PM
Brown
棕 W V MOTOR
Brown

pin1 U pin1 U W
/U
Brown/Black
/U Brown/Black W

Gray 灰
Gray
V Gray/Black V Gray/Black
/V White /V
W White
W
White/Black White/Black
/W /W

PM Motor is left-hang PM Motor is right-hang

39/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class
Abnormal P48V Power of SDCLAN Board
44 C2 OPBLAN-I24B or I48AFailure ----
SDCLAN-I24B or I48AFailure
1. Prevent the elevator from being trapped in an uncertain operation status. When it is
detected that the P48V power of SDCLAN board is loss, the elevator will decelerate at
the nearest level and the landing door will be opened, and the elevator can’t be started.
2. Prevent the elevator from being trapped in an uncertain operation status. When it is
detected that the I24B or I48A IC of OPBLAN PCB is abnormal, the elevator will
Check decelerate at the nearest level and the landing door will be opened, and the elevator can’t
Purpose be started.
3. Prevent the elevator from being entering an uncertain operation status. When it is
detected that the I24B or I48A IC of SDCLAN PCB is abnormal, the elevator will
decelerate at the nearest level and the landing door will be opened, and the elevator can’t
be started.
1. Detect the P48V circuit voltage at the SDC side. If the status of no voltage lasts for more
than one second, it will be regarded as abnormal.
2. Detected there is Failure at I24B or I48A IC of OPBLAN PCB. If the status lasts for
Check more than one second, it will be regarded as abnormal.
Condition 3. Detected there is Failure at I24B or I48A IC of SDCLAN PCB. If the status lasts for
more than one second, it will be regarded as abnormal.
※ The above Failure detection will inform the MPU via SDC LAN, and the TCD 44 will be
produced.
Reset
Mode After the failure is eliminated, it will automatically resume running.

Inspection Items of abnormal P48V power of SDCLAN Board:


1. Check the power voltage of P48V circuit, and check the connection status of flat Cable(Y1-13).
2. Check if the P48V Fuse of SDCLAN board is melted.
3. Replace SDCLAN board.

Inspection Items of OPBLAN-I24B or I48Afailure:


1. Check if there is a Failure at the I24B or I48A IC of OPBLAN PCB.
2. Replace OPBLAN PCB.

Inspection Items of SDCLAN-I24B or a I48A Failure:


1. Check if there is a Failure at the I24B or I48A IC of SDCLAN PCB.
2. Replace SDCLAN PCB.

40/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure
TCD Content Relation HOLD
Class

45 A1 BKSW Action Check ◎

Check Brakes will not be released under the status of failure of brake coil. In order to prevent the
brake block from being under the friction status, the running is prohibited and the elevator
Purpose will stop immediately run and can’t be started when the abnormal BKSW is detected.
1. After 15B ON, detect the status of action of brake switch (BKSW). If the force-in signal
of XBKSW1 is Close status, and such status lasts for more than three seconds, the
elevator will stop running immediately and can’t be started again.
2. During normal stop period, detect the status of action of brake switch (BKSW). If the
force-in signal of XBKSW1 is Open status, and such status lasts for more than three
Check seconds, the elevator will stop running immediately and can’t be started again.
Condition 3. When the ON, OFF status of force-in signal of XBKSW1 is different with the force-in
signal of XBKSW2 no matter the elevator is under the status of stop or running, if this
status lasts for more than three seconds, the elevator will stop running immediately and
can’t be started again.
4. When any one of the above items is met, this TCD is produced and it is under HOLD
mode.
Reset After the Failure is eliminated and FFB toggled the OFF-ON, operates MODE 2 to clear
Mode TCD, the running will resume.

Notes:
1. There are two BKSW, one is force-in signal of main Micon of XBKSW1, and the other is force-in
signal of sub Micon of XBKSW2.

Inspection Items:
1. Visually check the status of BKSW LED on the SFIOR board. The LED should be OFF during stop
period, and the LED of BKSW should be ON during running period.
If it is necessary, use KWH meter to measure the action status of BKSW.
2. The main power OFF-ON and the LED of BKSW should be ON continuously after the elevator is
started.
3. Check the wiring status of two BKSW.
4. Check if there is ON Failure or OFF Failure at the force-in Buffer:
If the Data of main XBKSW1 ($CA0F) and sub XBKSW2 ($CD2F) will do contrary action with the
ON-OFF of 15B Ctt.
※When 15B OFF, XBKSW1 and XBKSW2 ON. When 15B ON, XBKSW1 and XBKSW2 OFF.
※Operate XBKSW1 ($CA0F) and XBKSW2 to observe MODE 22.
5. Replace SFIOR PCB.

41/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class

1 46 A2 Three Times Consecutive of Open Lock ◎

When the cage door can’t be opened normally, the elevator will automatically stop at the
Check next destination level or the adjacent floor to try to open normally the cage door. If the cage
Purpose door can’t be opened normally at three floors consecutive, the elevator will be stopped, and
it will remind the passenger to use the interphone to contact with the management room.
Check If the cage door can’t be opened normally at three floors consecutively, a failure will be
Condition detected, and the elevator will be stopped immediately and can’t be started again.
Reset After the Failure is eliminated and FFB toggled the OFF-ON, operate MODE 2 to clear
Mode TCD, the running will resume.
1
Inspection Items:
1. Check the OLS signal of door machine:
At the fully opened position of cage door, OLS LED of FB-DMC PCB上 will be ON (After the
door is fully opened, the door machine will sent the OLS signal).
2 Check the door machine power circuit:
(1) Check if the Dr M/C Fuse of control panel has been melted.
(2) Check if the Dr Cut Sw of top cage has been cut.
3. Check the status of the opening & closing of door machine and the mechanical status of door
machine.
4. If the above items are normal, replace SFIOR PCB.

42/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class

47 C1 Load Detection Circuit Failure ----

Differential transformer Failure or wiring short-circuit or broken circuits are detected to


Check prevent the extremely reversion of flying off from being happened during the startup of
Purpose elevator. When the failure of load detection circuit is detected, the elevator can’t be started
after reduction stop landing.
The voltage of differential transformer will convert the digital load via A/D. If any one group
Check
force-in voltage of two groups is too small, it will be detected consecutively more than 8
Condition
times. (If the NPX force-in voltage is too small, the conversion value is less than 100).
Reset
After the failure is eliminated, it will automatically restore the running.
Mode

Inspection Items:
1. Check if there is any change at the weight detection main Micon ($CD3D) when passengers enter or
exit the cage.
2. Check the fixing, setting and action of differential transformer.
3. Check if the power voltage of differential transformer is about AC24V.
4. Check if there is wrong wiring or broken wiring at the differential transformer.
5. The setting of 0% and 100% of differential transformer hasn’t been finished.
6. Replace the damaged differential transformer.
7. Check if there is wrong wiring at SDC or SFIOR PCB.
8. Replace the SDCLAN PCB.
9. Replace the SFIOR PCB.

43/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
50 A2 High-speed OVER SPEED ○

The setting of high-speed Over Speed reduction circuit is based on:


Check (a) Detection 140% of abnormal mechanical speed of speed governor.
Purpose (b) Detection 130% of abnormal electrical speed of speed governor.
(c) Detection 125% of abnormal Micon speed.
The reasons such as bad speed control circuit during running with high-speed will result in
Check
the speed of elevator exceeds 125% of rated speed, and the failure will be detected (Failure
Condition
is detected before the mechanical action of speed governor).
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.
Inspection Items:
1. Measurement of actual speed:
(1) Read-out speed of MODE 27 SET.
(2) Use speed-meter to measure the running speed of high-speed (Except UAY1).
(3) If the speed values of the item 1 and item 2 are within 125%, the Failure is detected, which
means the speed detection circuit is not good.
(4) If the speed values of item 1 and item 2 exceed 120%, it means the speed control circuit is not
good.
Re-Down Load the DSP sample value of the sub Micon, and re-check it again.
2. Replace the faulty body of the Rotary encoder.

44/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Class Content Relation HOLD

51 A2 Speed Deviation Detection ○


1. The design
1 of NT2 has adopted the full-digital mode, and the detection of speed deviation
value can be performed once 10ms.
2. The detection method will use the speed error value (it should not exceed 25% of
Check command
and the
value of speed) that is the differential value between the speed command value
actual value of speed. When the actual speed value is too larger, it should not exceed
Purpose 12.5% of command value of speed. When the actual speed value is too smaller, it should not
lower 25% of command value of speed.
3. The detection action will be governed by the instruction value. When the instruction value
reaches over 15m/min, the detection action will start.
During high-speed running, if the deviation between the instruction value of speed and the
Check actual speed reaches +12.5% or –25% of phase difference and after it1occurred consecutively
Condition for 120ms, the Failure will be detected to prevent the dangerous from occurring due to speed
deviation.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will resume.

Inspection Items:
1. Measurement of actual speed:
(1) Read-out speed of MODE 27 SET.
(2) Use speed-meter to measure the running speed of high-speed (Except UAY1).
(3) If the speed values of the item 1 and item 2 are within 125%, 75~112.5%, the Failure is
detected, which means the speed detection circuit is not good.
(4) If the speed values of item 1 and item 2 exceed 125%, 75~112.5%, it means the speed control
circuit is not good.
Re-Down Load the DSP sample value of the sub Micon, and re-check it again.
2. Check the wiring of Rotary encoder:
5VRE terminal on the SMPU PCB; Check if there is bad connection or fallen wiring.
3. Check the P15V:
MUF Connect on the SMPU PCB; The voltage between Pin1 and Pin2 is +15V.
4. Replace the bad body of Rotary encoder.
5. If the above items are normal, replace the SMPU PCB.

45/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
52 A1 10T OFF Failure ----

10T main contact should be ON but not, it means 10T main contact has OFF failure.
Check
Elevator should be stopped immediately or the running will not be started, avoiding low
Purpose
reliability of the safeguard system.
During starting period, it will control 10T Ctt Turn-ON through MZ10T force-out Buffer
checks MX10T and SX10T force-in Buffer signals to judge whether the action of 10T Ctt is
Check normal.
Condition Namely when MZ10T force-out Buffer is ON, but MX10T and SX10T force-in Buffer is not
ON within 500ms, then the failure will been checked.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1.Check if the force-in Buffer has OFF Failure
If the Data of main MX10T ($CA02) and sub SX10T ($CD22) are synchronized with ON-OFF of
10T main contact.
※Operate MX10T ($CA02) and SX10T ($CD22) to observe MODE 22.
2. Check the voltage of 10T main contact:
(1) Power for 10T main contact: Voltage between RECT FUSE and GD → DC 48V.
(2) When MZ10T ON, the voltage between COIL (+) end and COIL (−) end of 10T main contact→
DC 48V.
(3) During stopping period and under the status of opening door, the voltage between COIL (-) end
of 10T main contact and GD48 → DC 48V.
3. Check the status of 10T main contact:
Check if there are broken coil, bad contact connection and broken wiring at 10T main contact.
4. Lay wiring between SMPU PCB and FIOR PCB; check if there is a faulty connection between
MUD and FOD.
5.SFIOR PCB Replacement
If titem 1 or item 2 is not good, while the item 4 is good, it means the SFIOR force-out Buffer is
not good, and should be replaced.
6.SMPU PCB Replacement
If the failure still occurs after the replacement of SFIOR PCB, it means the SMPU PCB is not good
and must be replaced.
46/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
53 A1 15B OFF Failure ----
15B contact should be ON but not, it means 15B contact has OFF failure. Elevator should be
Check
stopped immediately or the running will not be started, avoiding low reliability of the
Purpose
safeguard system.
During starting period, it will control 15B Ctt Turn-ON through MZ15B force-out Buffer
checks MX15B and SX15B force-in Buffer signals to judge whether the action of 15B Ctt is
Check
normal.
Condition
Namely when MZ15B force-out Buffer is ON, but MX15B and SX15B force-in Buffer is not
ON within 500ms, then failure will been checked.
Reset
After the failure is eliminated, it will automatically resume running.
Mode

Inspection Items:
1.Check if the force-in Buffer has OFF Failure
If the Data of main MX15B ($CA00) and sub SX15B ($CD20) will act synchronously with
ON-OFF of 15B main contact.
※Operate MX15B ($CA00) and SX15B ($CD20) to observe MODE 22.
2. Check the voltage of 15B main contact:
(1) Power for 15B main contact: Voltage between RECT FUSE and GD → DC 48V.
(2) When SZ15B ON, the voltage between COIL (+) end and COIL (−) end of 15B contact→ DC
48V.
(3) During stopping period and under the status of opening door, the voltage between COIL (-) end
of 15B contact and GD48 → DC 48V.
3. Check the status of 15B contact:
Check if there are broken coil, a faulty connection or broken wiring at 15B contact.
4. Lay wiring between SMPU PCB and FIOR PCB; check if there is a faulty connection between the
MUD and FOD Connect.
5.SFIOR PCB Replacement
If the item 1 or item 2 is not good, while the item 4 is good, it means the SFIOR force-out Buffer is
not good, and it should replace the SFIOR PCB.
6.SMPU PCB Replacement
If the failure is still happened after the replacement of SFIOR PCB, it means the SMPU PCB is not
good and should be replaced.

47/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
54 A1 RE Failure (Abnormal Phase Angles of U,V,W) ◎
During the control period of PM motor, the variable-frequency controller will use the uvw
signal of ENCODER to judge the position of magnetic pole of PM motor, and further sent
Check the correct three-phase voltage to produce one rotating magnetic field. If any one phase is
Purpose damaged, it will result in the rotating magnetic field sent by the controller will not match the
position of magnetic pole of motor, the rotation of motor is not smooth, and the elevator will
sway, and the elevator should be stopped immediately.
1. If the magnetic pole detection Plus of Rotary Encoder are all HI, and it is detected
consecutively for over 1.37ms, the running of elevator should be stopped immediately
and it can’t be started again.
2. If the magnetic pole detection Plus of Rotary Encoder are all LO, and it is detected
Check
consecutively for over 1.37ms, the running of elevator should be stopped immediately
Condition
and it can’t be started again. Note 1.1.
3. If the encoding sequence of Rotary Encoder is not normal, and it is detected
consecutively for over 1.37ms, the running of elevator should be stopped immediately
and it can’t be started again.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will be resumed.

Inspection Items:
1. When the power of the elevator is ON, CPU will perform the circulation action with the period of
42.7us to check if the decode of uvw of encoder is 7 or 0. If it is 7 or 0, the en_error-counter add 1,
and if it is detected consecutively for 1.37ms, it will send the error message of ENCODER and will
keep the decoding value of previous status. The increase of reduction of angle will be based on the
QEP, en_error-counter will be zeroed after the motor is stopped if the accumulated times hasn’t
reached the setting value.
2. When the power of elevator is ON, CPU will perform the circulation action with the period of
42.7us. When the decoding value of uvw of encoder is changed, compare if the value is reasonable.
If it is reasonable, the en_error-counter add 1, and if it is detected consecutively for 1.37ms, it will
send the error message of ENCODER and will keep the decoding value of previous status. The
increase of reduction of angle will be based on the QEP, en_error-counter will be zeroed after the
motor is stopped if the accumulated times hasn’t reached the setting value.

48/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
55 A1 Too Larger Deviation of HCT Off Set ◎

Avoid the zero point displacement under the status of damaged HCT due to long-time use or
abnormal 5V voltage of Switching Power (namely the DSP input signal voltage is not 2.5V
Check
or the DSP A/D reference voltage is not 5V when the current is zero). The CPU read-in
Purpose
feedback signal is not correct, which will result in the rotation of motor is not smooth, and
the elevator will sway, and the elevator should not be started.
Check After the motor is stopped, and there is no running, the feedback value of HCT should not
Condition exceed “HCT zero point feedback error detection limit value” 300mv.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will be resumed.

Inspection Items:
1. After the stop command of elevator is issued, wait at least more than 2 seconds (the program will
not perform the detection function if it doesn’t reach 2 seconds) in order to ensure the output-enable
has been closed. After that, CPU will perform the circulation action with the period of 42.7us. If it
didn’t detected the running, it will judge if the U phase and V phase of read-in value of A/D
converter is greater than HCT zero point feedback error detection limit value 300mv, if it is true, the
hct_error-counter will add 1, and if it is detected consecutively for one second, it will send the error
message of HCT. If the consecutive period doesn’t reach the detection standard, or the next detection
value is less than the setting value 300mv, the hct_error-counter will be zeroed.

※The permissible compensation limit value of HCT zero feedback


(RANGE_I_OFFSET_AMEND) refer to the adjustment information of parameter of motor of host
machine.

49/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0
Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
57 A1 Mg. B Two-section Type Power Circuit Failure ◎

If Mg. B Two-section Type Power Circuit Failure, the brake will not be released. In order to
Check prevent the brake block from being towed under friction status, if the Mg. B power circuit
Purpose failure is detected, the elevator is prohibited to run, and the elevator will stop the running, and
it can’t be started again.
1. After 15B ON, if it didn’t detected that the MXBKVD is HI within one second, the
elevator will stop running immediately, and it will record as failure and can’t be started
again. (After 15B ON, MXBKVD is still LO).
Check 2. After 15B ON, if it detected that the MXBKVD is HI for over three seconds, the elevator
Condition will stop running immediately, and it will record as failure and can’t be started again.
(After 15B ON, MXBKVD is still HI)
3. When any one of the above items is met, this TCD is produced and it is under HOLD
mode.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will be resumed.
Inspection Items:
1. Use KWH meter to measure the voltage of Mg. B power circuit, and check if the bridge rectifier at
power side is Open Failure.
2. Visually inspect the status of ON of BKHV LED on the SFIOR board, and the lamp should be
illuminated for about one second during the period of starting of elevator.
3. Carefully listen the action status of Mg. B during the period of starting of elevator.
4. Check if U1 SSR has ON Failure or OFF Failure. Check if D2 has through Failure or Open Failure.
5. Check if the two-section type brake voltage detection circuit force-in Buffer (MXBKVD) has
Failure.

※ Description of Mg. B two-section type power circuit:


When 15B starts ON, it will firstly supply full-wave rectified 90V high-voltage to quickly release
Mg. B. After that it will be controlled by SSR. After 0.7 second, it will change to supply half-wave
rectified 45V low-voltage, and it will supply continuously 45V low-voltage until the reduction and
stopping. In such way, it can reduce the current of Mg. B coil one side, and it can quickly brake during
stopping and Mg. B is power off on the other hand. Therefore, it should firstly detect the 90V
high-voltage of MXBKVD after 15B ON, the period is about 0.7 second until the 15B OFF, and it will
detect continuously the 45V low-voltage of XBKHV.

※If the site Mg. B is not two-section type power circuit, it can Disable the detection of this TCD.

50/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
58 C1 DLAN Halted ----

Check Due to the reasons such as noise disturbance, the DLAN is halted, the Failure of main Micon
Purpose is detected, and the running of elevator is stopped.
When DLAN hasn’t REFRESH the information of shared RAM within 200ms, it will regard
the DLAN is halted. At that time, the main Micon will actively Reset DLAN, and re-check
Check
the DLAN after two seconds. If DLAN has restore to normal status, the elevator will
Condition
continuously run. If DLAN hasn’t REFRESHED the shared RAM information, a failure is
detected, and the elevator will be stopped.
Reset
After the failure is eliminated, it will automatically resume running.
Mode

Inspection Items:
1. Check if DLAN/W77E58 (U35 on the SMPU PCB) is inserted properly, and if the lines and parts
concerned are correct.
2. If the item 1 is normal, replace the SMPU PCB.

51/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
59 A2
Relation
No Detection of Induction Board when Floor Height >9m ◎
Design the limit of running time of motor as per the requirements of GB to prevent the
Check hauling wheel from idling. When the elevator runs 15m/m, the running distance is greater
Purpose than 9m, and there is no detection of induction board, the running of elevator will be
stopped.
Check When the running of elevator is rescued, the elevator runs 15m/m, the running distance is
greater than 9m, and there is no detection of induction board, the main Micon will judge that
Condition the running period of motor is exceeded, and the Failure will be detected immediately.
Reset After the Failure is eliminated and FFB toggled OFF-ON, operates MODE 2 to clear TCD,
Mode the running will be resumed.

Inspection Items:
1. Check the detection TCD 59 on commission site:
(1) Investigate if the hauling wheel is idle
The mistaken action of safety pliers and some factors will cause the cage is obstructed.
(2) Investigate if the imaginary level induction board hasn’t been installed.
2. Check TCD 59 on maintenance site:
(1) Investigate if the hauling wheel is idle
The mistaken action of safety pliers and some factors will cause the cage is obstructed.
Check if the hauling wheel is slid fundamentally.
(2) Check if the sample parameter is set incorrectly.
(3) Check if it has FML Posi ON Failure.

52/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
60 B2 Level-height TABLE SUM ERROR ----
1. After re-measure level-height every time, the value of level-height will store into
EEPROM, in addition, it will additionally store one backup at the NVSRAM. In such way,
the failure will be detected if the value of level-height in the EEPROM is different with the
Check
value in the NVSRAM.
Purpose
2. The purpose of the design is to avoid the outside factors to disturb or alter any one value
of level-height in the EEPROM or NVSRAM to result in the Micon uses the wrong value of
level-height.
Calculate the Sum value in the Table of level-height inside the EEPORM every 20ms. A
Check
Failure will be detected if the value of Sum value is not consistent with the value of Sum
Condition
Code.
Reset
After the failure is eliminated, it will automatically resume running.
Mode

Inspection Items:
1. If the EEPROM is not good, replace the SMPU PCB.
2. When the level-height Data write-in is not good
The procedure is wrong or has failed during the measurement of level-height. Re-measure the
level-height as per the correct procedure.
3. During the commission stage, it will toggle as the automatic or special running mode. It will
display that TCD 60 is normal when preparing the measurement of level-height.

53/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
62 B2 Synchronous Position Failure ----
Factors such as error of stopped level cause the judgment of floor is wrong, or the actual
running distance is not conformity with the interior level-height value due to the serious
Check
wear of Sheave during the running period of elevator, or the sliding distance is too long
Purpose
when it is power off, and the Failure will be detected. Avoid a situation where the Open
Zone can’t be detected or the floor confused.
Check If the synchronous position of Digital Floor is wrong, and a Failure is detected if it exceeds
Condition ±320mm than the values in the Level-height Table during floor-height judgment.
Reset
After the failure is eliminated, it will automatically resume running.
Mode

Inspection Items:
1. MODE 67 SET during normal running:
If the examination of the digital Floor Monitor is correct.
2. Investigation of wear of Sheave and sliding distance of Rope.
3. Check the sliding distance when it is power off.
4. e-measure the level height when the item 1, item 2 and item 3 are normal.

54/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
63 B2 SDS ON Failure ----

The connection of SDS is melted and it can’t detect the OFF Failure. Avoid a failed
Check
reduction under the status of invalid FML Posi to prevent the elevator to fly to higher
Purpose
position of lower position.
When the elevator is ascended or descended to the terminal level and reached to certain
Check height (the setting values of SDS1 and SDS2 are different, e.g.: 60m/min SDS1U, SDS1D is
Condition 600mm), in theory, the action of the SDS should be OFF. The ON Failure will be detected
when the SDS can’t be OFF due to uncertain reasons.
Reset
After the failure is eliminated, running will automatically resume.
Mode

Inspection Items:
1.Check the wiring of L limit Sw:
Check the locked status of MIC of SDS and check if there is bad connection of wiring.
2. Carry out visual inspection when the LED of SFIOR PCB is ON:
MSDS2U ($CA08), MSDS1U ($CA09), MSDS2D ($ CA0B), MSDS1D ($ CA0C)
Observe the Data change of force-in Buffer to check if it is same with status of LED ON (81→ON,
00→OFF)
※Observe MODE 22
3. Check if there is bend of action CAM of LIimit Sw.
4. Lay wiring between SMPU PCB and FIOR PCB; Check if there is a bad connection between the
MUD and FOD.

55/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev.
TCD 2.0Failure (POSH,UAY1,e’NT)Content STQ-0291
HOLD
Class No.
Relation
64 A1 Detection of SDS Speed Failure ----
Check To prevent the elevator from flying to a higher position from a lower position when the SDS
Purpose loses the protection function due to the shaking position of SDS.
Compare the actual speed of elevator and the setting speed when the SDS has action (the
Check
setting values of SDS1 and SDS2 are different). The Failure is detected when the actual
Condition
speed is greater or less than certain value of the setting value.
Reset
After the failure is eliminated running will automatically resume.
Mode

Inspection Items:
1.Check the wiring of LIimit Sw:
Check the locked status of MIC of SDS and check if there is a bad connection of wiring.
2. Carry out visual inspection when the LED of SFIOR PCB is ON:
MSDS2U ($CA08), MSDS1U ($CA09), MSDS2D ($ CA0B), MSDS1D ($ CA0C)
Observe the Data change of force-in Buffer to check if it is same with status of LED ON (81→ON,
00→OFF)
※Observe MODE 22
3. Confirm the installation dimensions of SDS Sw:

Name Installation
安 装 尺Dimensions

SDS1(U) Before LEVEL
SDS1(D) 60m/min:600mm
90m/min:600mm
105m/min:600 mm
150m/min:900mm
SDS2(U) Before LEVEL
SDS2(D) 90m/min:2000mm
105m/min:2000 mm
150m/min:2500 mm
ULS
Align with CAM
DLS
FLS(U) Under LEVEL
FLS(D) e’ NT: 170mm UAY1:125 mm

【Note: Please refer to the test instruction of SDS】

56/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
65 E 40D Abnormal OFF during Running Period ----
If X40D is instantly during running period of elevator (Door Sw OFF of landing door during
Check running period), the elevator will be rescued after emergency stop.
Purpose
The occurred instant OFF Failure of X40D can be detected through TCD 65.
After the door is closed properly and the ZXCLS action signal is sent out, if it is detected
Check
that X40D OFF during running period, it means there is OFF Failure at the Door Sw of
Condition
landing door.
Reset After the cause of Failure has been removed and the elevator is rescued to run to the leveling
Mode and the door is opened, running of the elevator will automatically resume.
Inspection Items:
1. Check if the engaging device will collide the coupling wheel of Door Sw of certain landing during
running period.
2. Check if there is a bad connection at the connector of passive door switch of landing.
3. TCD 66 also will be detected if someone uses the tri-angle key to open the landing door during
running period.

57/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
66 E 40G Abnormal OFF during Running Period ----
If X40G is instantly during running period of elevator (Door Sw OFF of landing door during
Check running period), the elevator will be rescued after emergent stopping.
Purpose
The occurred instant OFF Failure of X40G can be detected through TCD 66.
After the door is closed properly and the ZXCLS action signal is sent out, if it detected that
Check
X40G OFF during running period, it means there is OFF Failure at the Door Sw of cage
Condition
door.
Reset After the cause of Failure is disappeared, and the elevator is rescued to run to the leveling
Mode and the door is opened, running will automatically resume.
Inspection Items:
1. Check if there is a bad connection at the connector of Gate Sw of cage door.
2. Check if there is a bad connection at the connector of passive door switch of the landing.

58/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
Closing Door is Failed during Leveling (40D or 40G is
67 E ----
not ON)
If the X40G is not ON or X40D is not ON when the elevator is level, it belongs to the failed
Check
closing door, and it is different from the Failure detection during the running period of TCD
Purpose
65 and TCD 66.
When the elevator is located at the leveling and after the door is closed properly and the
action signal of ZXCLS is sent out, the X40G is not ON or X40D is not ON due to the bad
Check
connection of Gate Sw or Door Sw, and uncompleted closing landing door due to the
Condition
self-closing force is not enough, and the Close Door Failure is detected after 5 seconds when
the cage door is re-opened.
Reset Open and close the door repeatedly, the running can be started when X40G and X40D are
Mode ON at the same time.
Inspection Items:
1. Check if there is a bad connection at the connector of Gate Sw of cage door or passive door switch
of the cage door.
2. Check if there is a bad connection at the connector of Door Sw of landing door or passive door
switch of the landing door.
3. The landing door is not closed properly due to the self-closing force is not enough
(1) Check if there is dust in the Door Rail and sand in the Sill.
(2) The landing door can’t be closed properly due to the wind gusts from the floor below.
4. TCD 67 also will be detected when the landing door of the previous floor is opened during
maintenance period.

59/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
68 A2 Eight Times of SDA Halted Detected ○
Check If the SDA is stopped because of noise disturbance eight times, a failure will be detected and
Purpose the elevator will not start again.
When main Micon request SDA for sharing the right of use (BUS) of RAM, but the SDA
Check can’t give the right of use, or the SDA can’t refresh the shared RAM information within
Condition 200ms, it will regard the SDA as halted. The elevator is prohibited from running when the
SDA has stopped 8 times.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON,
Mode running will automatically resume.
Inspection Items:
1. Check if the lines and parts of SDA in the SMPU PCB are correct.

2. Verification of ON and OFF status of MWDT LED of main power switch


MWDT LED ON → Normal, MWDT LED OFF → Abnormal

60/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
69 A2 SDA RAM ERROR ○
Check When a Failure of SRAM of SDA is detected, the running of elevator is prohibited in order
Purpose to increase the reliability of the safeguard system.
Check The SDA will perform the Sum Check every 40ms. If there is Sum Error, the Failure will be
Condition detected and the running of elevator is prohibited.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.
Inspection Items:
1. Check if the SRAM/M5M5256 or IDT71256 (U73 IC on the SMPU PCB) is inserted properly, and
check the lines and elements concerned are correct.
2. Replace the SMPU PCB if the item 1 is normal.

61/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
70 A2 Shared RAM ERROR ○
The Data value stored in the shared RAM is very important, the store method uses the shared
method and it is distributed over time, and the SDA and the main Micon will store the
Check necessary information separately. In theory, the lifetime of RAM is limitless, in order to
Purpose increase the reliability, SDA and the main Micon will determine separately if the shared
RAM is good when it reads the interior information or changes the interior information, in
order to ensure the safety of the elevator.
The SDA will perform the Sum Check of RAM shared by the main Micon and SDA every
Check
40ms. If there is Sum Error, the Failure will be detected and the running of elevator is
Condition
prohibited.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the shared RAM/M5M5256 or IDT71256 (U53 IC on the SMPU PCB) is inserted properly,
and check the lines and elements concerned are correct.
2. Replace the SMPU PCB if the item 1 is normal.

62/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
71 A2 Main MICON Halted ○
Check Due to the reasons such as noise disturbance, the main Micon is stopped eight times, and the
Purpose elevator stops running because of a failure has been found.
When it is unclear why the main Micon has stopped, after a sub-Micon check, the elevator
Check will instantly stop running, and after 2 seconds reassessing whether the main Micon is
Condition running normally, if the main Micon has already recovered and main Micon’s stop times are
less than eight then the elevator will run normally again.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.
Inspection Items:
1. Verification the status of MWDT LED of Main-Micon
SWDT ON → Normal, MWDT → Abnormal

2. When the switch of main power is toggled between ON-OFF, verify the actions of MWDT LED
of the Main-Micon.
If the MWDT LED can’t be started again (OFF), replace the SMPU PCB.

63/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
72 A2 Eight Times of Detection of Sub MICON Halted ○
Check Due to the reasons such as noise disturbance, the main Micon is stopped eight times, and the
Purpose elevator is prevented from running because a failure has been found.
When it is unclear why the sub- Micon has stopped, after the main Micon checks instantly
Check prevent the elevator from running and after 2 seconds reassessing whether the sub Micon
Condition running normally, if sub Micon has already recovered and sub Micon’s stop times are less
than eight then the elevator will run normally again.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Check if the U32 and U33 IC of SMPU PCB are inserted properly, and check that the lines and
elements concerned are correct.
2. Verification the status of SWDT LED of Sub-Micon
SWDT ON → Normal, SWDT → Abnormal
3. When the main power switch is toggled between ON-OFF, verify the actions of SWDT LED of
Sub-Micon.
If the SWDT LED can’t be started again (OFF), replace the SMPU PCB.

64/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
73 B1 FML POSI OPEN Failure ○
Check Detection of FML Posi Open Failure (reed switch should be at ON position, while it is not at
Purpose ON position).
1. The Failure will be detected if RM POSI is still not ON after 2 seconds when the Motor
has a running speed of over 10m/min.
Check 2. The quality of FML Posi is related to the safety of elevator. When the FML Posi is
Condition
damaged, a serious accident may occur. Therefore, it is very important to use the timing
capability of Micon to detect the quality of the FML Posi.
Reset After the Failure is eliminated, operates MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.
Inspection Items:
1. Check the body of FML Posi:
Check the wiring of FML Posi, the insert status of MIC, and check if there is a short-circuit at the
Cable.
2. Check the action of force-in Buffer of XFMLP:
Check the Data change status of main Micon XFMLP ($CA0E) when FML Posi cuts the induction
board (81→In, 00→Out)
※Operate to observe MODE 22.
3. Check the power of SDC PCB power.
Check if the power of P48V is normal.

65/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure No.
TCD Content Relation HOLD
Class
74 A2 Number of Rescue Runs ○
Check The elevator stops at a non-opening door area for unknown reasons. Limit the time of rescue
Purpose running.
When a rescue run occurs due to any number of failures and the rescue run has reached three
Check times within 10 minutes, it means the safety factor and the reliability of elevator is reduced.
Condition In order to maintain reliability, stop the elevator to find the reason for error. The elevator can
be restored only after the Failure is eliminated completely.
Reset After the Failure is eliminated, operate MODE 2 to clear TCD or FFB toggles OFF-ON, the
Mode running will be resumed.

Inspection Items:
1. Record the analysis of Failure of other TCD codes and investigation of Failure:
E.g.: Check the Failure of TCD 18, 19, 65, and 66 for several times.
2. Check the following issues when there are consecutive TCD 65 and 66 Failure record:
(1) Check if the engaging device will collide the coupling wheel of Door Sw of certain landing
during running period
(2) Check if there is a bad connection at the connector of passive door switch of landing
(3) Check if there is a bad connection at the connector of Gate Sw of cage door.
(4) Check if there is a bad connection at the connector of Gate Sw of cage passive door.
3. Check the following issues when there are consecutive TCD 18 and 19 Failure record:
(1) Check if there is a bad connection at the connector and wiring of stop switches at pit, top cage,
and inside cage.
(2) Check if there is a bad connection at the connector and wiring of safety switches of PWS, BPS,
FLS and GRS.
4. Check if the customer misuses the elevator:
Check if the stop switch or safety switch inside the cage has been incorrectly toggled.

66/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
75 B2 POWER MODULE Overheat ----
Check Avoid overheating the main transistors. Failure will be detected if the temperature switch
Purpose inside the radiation fin is overheated.
If the temperature of radiation fin is too high (800℃), FTH Sw will act. Open the door after
Check
the elevator is stopped at the nearest level and stop the elevator. The elevator can restore
Condition
normal operation after the temperature of TH Sw has been restored to normal.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. Check the action of cooling fan of main transistors:
The cooling fan of main transistors should keep frequently the operation status (the cooling fan will
automatically stop 5 minutes after no calling.
2. When it uses the DC 24V-cooling FAN, check if there is damage on the assemblies of TRSA1 and
TRSA2 at the SFIOR PCB.
When it uses the AC 110V-cooling FAN, check if there is damage on the U18 assemblies at the
SFIOR PCB.
3. Check if there is ON Failure on the FTH force-in Buffer:
Normally the Data of main Micon ZXOHCH ($CA12) is 00. If there is no action on the FTH,
ZXOHCH will not be ON (81).
※Operate to observe MODE 22.
4. Check the action of temperature Sw (FTH) of transistor:
I fit is not overheated, FTH will not be ON, and the Data of ZXOHCH ($CA12) should be 00.

67/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
76 C1 Abnormality of Micro-speed Running Time ----
Some abnormalities such as the worn of Sheave occurred after long time of use, or the
Check weakening of internal permanent magnet of RM Posi (which will result in the inaccuracy of
application of force) will result in longer micro-speed time. The limitation of micro-speed
Purpose running time; therefore, is set in order to prevent the micro-speed time from longer that will
bump to outside of safety scope.
Check The failure is found when the micro-speed running time exceeds 5 seconds within the
time-interval from the time when the deceleration instruction value is decreased to 2m/min
Condition to the time before stop.
Reset
Mode After the failure is eliminated, it will automatically resume running.
Inspection Items:
1. Check if there is a mistaken action of ULS when it is located at leveling position of the most upper
floor:
Observe the ULS LED on the SMPU PCB under the automatic operation mode when it stops at
the upper floor. The lamp should not be illuminated under normal status.
If the ULS LED is illuminated, and there is calling from the sub-upper floor, the abnormality of
TCD 76 will be found frequently when it is automatically transferred to next down upper floor.
2. Check if there is mistaken action of DLS when it is located at leveling position of the most lower
floor:
Observe the DLS LED on the SMPU PCB under the automatic operation mode when it stops at
the lower floor. The lamp should not be illuminated under normal status.
If the DLS LED is illuminated, and there is no calling from the sub-lower floor, the abnormality of
TCD 76 will be found frequently when it is automatically transferred to next up lower floor.
3. Confirmation of Level Augmenting Data:
MODE 22 SET, readout of Address-($20DA), and the value of Data is about 0B~0C.
4. Action Check of FML Posi:
(1) Confirmation of action of FML Posi (Tool-in→ON, Tool-out→OFF).
(2) Confirmation of relative cutting position between FML Posi and induced plate.
5. Confirmation of Worn of Sheave and Sliding Distance of Rope.
6. Check if there is mistake of setting values of Motor sample, or check if the setting value is proper.
7. Investigation of other causes:
(1) Re-conduct the level height operation.
(2) TCD 76 maybe occurred when there is error of level height value and when the first operation
is stop.
(3) The passenger mistakenly stops the switch in the cage at phase of pre-opening of door when it
is stopped.
(4) Failure is found at Pulse signal when the rotary encoder is under low-speed operation.

68/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
77 C1 Door Machine Motor Overheat ----
Check It will detect the door machine Failure or if door machine motor is overheated due to
Purpose artificial factors. Avoid the coil or elements of the motor from being damaged.
Check When the series thermal switch of door machine motor circuit and the motor are overheated,
Condition the action of switch will be changed from Normal Close to Open.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. If it is equipped with 94BQ at the special type of door machine:
The Data of Address $ 233B should be set as 81. Check if the thermal switch of door machine is
acted, or if the thermal switch is equipped.
※Operate to observe MODE 22.
2. Check the Data value of Address $C502:
If the Data of Address $C502 is 81, it means the door machine is overheated.
※Operate to observe MODE 22.

69/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
TCD Failure Class Content HOLD
Relation
78 A2 Door Machine Failure ----

Check When performing Failure disposal and the machine-room ANN displays TCD 78, it will know that the
Purpose Failure is detected.
Check When E1, E2, E3 Failure is detected on the door machine, it will transfer the Failure message to the main
Condition Micon via SDC.

Reset Mode After the failure is eliminated, it will automatically restore the running.

Inspection Items:
1. Travel Error
(1) E1-1: If Power-off resetting and opening door travel exceed the measured maximum value of travel, the Failure
will be detected.
After the power is switched on, avoid the belt from being fallen or being broken, and prevent the Encoder
Pulse from being calculated always, it will result in the positioning of CLS can’t be found, and the MPU w
issue the reversion command repeatedly due to failed opening door, and the motor is overheated or door
machine is abnormal.
(2) E1-2: If Power-off resetting and closing door travel exceed the measured maximum value of travel, the Failure
will be detected.
After the power is switched on, avoid the belt from falling or being broken, and prevent the Encoder
Pulse from being calculated always, it will result in the positioning of OLS can’t be found, and the
MPU will issue the reversion command repeatedly due to failed closing door, and the motor is
overheated or door machine is abnormal.
(3) E1-3: Under the normal opening door, the Failure will be detected if the travel exceeds the maximum measured
travel.
When the door is closed fully under automatic operation status, if the belt of door machine is fallen or
broken, the motor of door machine will be idled always and cage door can’t be opened when the door
machine received the opening door command from MPU.
(4) E1-4: Under the normal closing door, the Failure will be detected if the travel exceeds the maximum measured trav
When the door is opened fully under automatic operation status, if the belt of door machine has fallen or i
broken, the motor of door machine will be idled always and cage door can’t be opened when the door
machine received the opening door command from MPU.
(5) E1-5: After power-off resetting and 100 times of retry of opening & closing door, it hasn’t finished the failure
detection of positioning of OLS and CLS.
After the power is switched on and when the door machine is looking for CLS and OLS to prevent the
hindrance from outside force or obstruction. If it hasn’t found the positioning of CLS and OLS, it will be
judge as the error of non-reset after 100 times of Retry.
2. Over current Error
(1) E2-1: Over current is occurred when there is force-in of door stop-switch.
(2) E2-2: Over current is occurred when there is no force-in of door stop-switch and the door hasn’t been closed or
opened.
(3) E2-3: Over current is occurred during the running of door
The most common reason for over current of FB-DMC is the transistor Q1~Q6 has been broken, or IC
Failure of IR2130 or it is disturbed by the large current; or part of CLS or OLS has problem, it will be
divided as three categories to facilitate to judge the status when the over current is occurred to eliminate
the Failure.
3. Encoder, Encoder Failure, Motor Failure can’t be started and door machine is obstructed
(1) E3-1: Encoder Pulse hasn’t been changed when the door machine is not the position of CLS or OLS.
Close door repeatedly for 15 times consecutively, the quantity of Pulse hasn’t been changed, and OLS
hasn’t been detected; or open door repeatedly for 15 times consecutively, the quantity of Pulse hasn’t
70/79been
changed, and CLS hasn’t been detected, the E3-1Failure code is produced.

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
80 E DUPLEX Communication Failure ----
Check For the over two group-control elevators, bad communication of group control between
Purpose elevators is detected.
Check Bad communication between elevators (including the period of maintenance and when the
Condition main power switch toggles to OFF).
Reset
Abnormal group control, while the elevator can start to run.
Mode
Inspection Items:
1. Check if there is broken Duplex communication and the fixing status.
2. Check the locked status of communication CIP Connect and power Connect of SMPU PCB.
3. Replace the SMPU PCB:
If the item 1 and item 2 are good, while there is still the abnormal communication of Duplex,
replace the SMPU PCB.

71/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
81 E Photoelectric POSI OPEN Failure ----
Check Avoid the abnormal running of micro leveling when there is photoelectric Posi Open
Purpose Failure.
The Failure will be detected if it found that photoelectric Posi XRS21 and XRS22 are all
Check opened during micro leveling running. The elevator will be stopped immediately, and it will
Condition not perform the micro leveling running, while the elevator still runs at a normal high-speed.
※The elevator will detect TCD 82 if there is a running sample of micro leveling.
Reset The elevator still runs at a normal high-speed when it will not perform the micro leveling
Mode running.
Inspection Items:
1. Check the body of photoelectric Posi:
(1) The LED on the photoelectric Posi should be OFF when it is at the leveling position. The LED
should be ON when the induction board is inserting.
(2) Check the wiring of photoelectric Posi, the insert status of MIC, and check if there is
short-circuit at the Cable.
(3) Replace the damaged photoelectric Posi.
2. Check the action of force-in Buffer of XRS21 and XRS22:
Check the Data of main Micon Address XRS21 ($C517) and XRS22 ($C507)的Data (81→In,
00→Out)
※Operate XRS21($C517)、XRS22 ($C507) to observe MODE 22.
3. Check the power of SDC PCB power and check if the power of P48V is normal.

72/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
82 E Photoelectric POSI Short-circuit Failure ----
Check Avoid the abnormal running of micro leveling when there is photoelectric Posi Close
Purpose Failure.
The Failure will be detected if photoelectric Posi still short-circuit after 2 seconds when the
Check Motor is running with speed of over 10m/min.
Condition
※The elevator will detect TCD 82 if there is running sample of micro leveling.
Reset
The elevator still runs at a normal high-speed when there is no micro leveling running.
Mode
Inspection Items:
1. Check the body of photoelectric Posi:
(1) The LED on the photoelectric Posi should be OFF when it is at the leveling position. The LED
should be ON when the induction board is inserting.
(2) Check the wiring of photoelectric Posi, the insert status of MIC, and check if there is
short-circuit at the Cable.
(3) Replace the damaged photoelectric Posi.
2. Check the action of force-in Buffer of XRS21 and XRS22:
Check the Data of main Micon Address XRS21 ($C517) and XRS22 ($C507)的Data (81→In,
00→Out)
※Operate XRS21($C517)、XRS22 ($C507) to observe MODE 22.
3. Check the power of SDC PCB power and check if the power of P48V is normal.

73/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
84 C2 OLS ON Failure ----
Check If there is door machine CLS force-out Relay OFF Failure, the elevator can’t be started
Purpose again.
Check Under the automatic running status, the door machine still sends the signal of detected OLS
Condition when the cage door is closed completely.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. Observe the status of OLS LDE of door machine FB-DMC PCB:
(1) The OLS LED should be ON when the cage door is closed completely.
(2) The OLS LED should be OFF when the cage door leaves the position that the cage door is
closed completely.
2. Investigation of door machine OLS force-out Relay:
Check if there are broken coils and/or short-circuits of connection of OLS force-out Relay.

3. Check if there is something wrong with the door machine control.

74/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
85 C2 CLS ON Failure ----
Check If there is door machine CLS force-out Relay OFF Failure, the elevator can’t be started
Purpose again.
Check In automatic running status, the door machine still sends the signal of detected CLS when
Condition the cage door is opened completely.
Reset
After the failure is eliminated, it will automatically resume running.
Mode
Inspection Items:
1. Observe the status of CLS LDE of door machine FB-DMC PCB:
(1) The CLS LED should be ON when the cage door is closed completely.
(2) The CLS LED should be OFF when the cage door leaves the position that the cage door is closed
completely.
2. Investigation of door machine CLS force-out Relay:
Check if there are broken coils and/or short-circuits of connection of CLS force-out Relay.

3. Check if there is a problem with the door machine control.

75/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
86 E Detection of Abnormal Opening Door Action ----

When the door is opened, an ORS action will occur if there is obstruction, or it will
Check automatically
Purpose periodto avoidclose the door if the action of opening door is not finished after certain
overheating motor or controller of the door machine.
1. In automatic running status, it will automatically close the door and re-open door if there
is an obstruction (such as ORS action) or if the action of opening door is not finished
within 8 seconds. If the action of opening door fails, and if the failure of opening door
repeats eight times, the elevator will show aTCD 86 Failure. Stop the closing the door
Check
Condition 2. and opening door for 15 seconds. This will stop the elevator temporarily.
After the temporary stop, repeat the action of opening door shown in the item 1 until
three times of TCD 86 Failure is detected and after the automatically closing door. The
elevator will run to the next destination level or next landing to try to open the door
normally.
Reset The elevator will run to the next destination level or next landing to try to open the door
Mode normally.
Inspection Items:
1. Measurement of opening door:
The time from the command of opening the door is issued until the cage door is opened
completely should not exceed 8 seconds if the ORS has no any action or the Sill hasn’t been
obstructed by any foreign material.
2. Observe the status of illumination of ORS LDE of door machine of FB-DMC PCB:
When the door is opened and the ORS LDE is ON, it means the ORS has action and it will
automatically close the door.
3. Investigation when the ORS has action:
(1) Check if any foreign material obstructs the Sill.
(2) Check the status of opening & closing of landing door.
(3) Check the status of opening & closing of engagement of cage door and landing door.
(4) Check if the error action of ORS due to the adjustment of ORS is too sensitive.
4. Check if there is a problem regarding the door machine control.
5. Replace the SDC PCB if the above status is determined to be normal.

76/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
87 C2 Detection of Abnormal Closing Door Action ----

Check When the door is closed, an ORS action will occur if there is an obstruction, or it will
Purpose periodto avoidopen
automatically the door if the action of closing door is not finished after a certain
overheating the motor or controller of door machine.
1. In automatic running status, the door will automatically open and close if there is
obstruction (such as ORS action) or if the action of closing door is not finished within 8
seconds. If the action of closing the door still fails, and if the failure of closing the door
Check repeats eight times, a TCD 87Failure will be detected. At that time it stop closing the
Condition door and opening door temporarily for 15 seconds.
2. After the temporary stop, repeat the action of closing the door shown in the item 1 to try
to open the door normally.
Reset
Mode After the failure is eliminated, running will automatically resume.
Inspection Items:
1. Measurement of closing door:
The time from the command of closing door is issued to when the cage door is closed properly
should not exceed 8 seconds if the ORS has no any action or the Sill hasn’t been obstructed by any
foreign material.
2. Observe the status of illumination of ORS LDE of door machine of FB-DMC PCB:
When the door is closed and the ORS LDE is ON, it means the ORS has action and it will
automatically open the door.
3. Investigation when the ORS has action:
(1) Check if any foreign material obstructs the Sill.
(2) Check the status of opening & closing of landing door.
(3) Check the status of opening & closing of engagement of cage door and landing door.
(4) Check the error action of ORS due to the adjustment of ORS is too sensitive.
4. The landing door is not closed properly due to the self-closing force is not enough
(1) Check if there is dust in the Door Rail and sand in the Sill.
(2) The landing door can’t be closed properly due to the wind gusts from the floor below.(3) Check
if there is a bad contact at the cage door switch or cage door passive door switch.
(4) Check if there is a bad contact at the landing door switch or landing door passive door switch.
5. Check if there is problem with the door machine control.
6. Replace the SDC PCB if the above status is judged as normal.

77/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD 78/79
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Relation

TCD Failure Class Content HOLD

88 E Power-off Detection ----

Check During an automatic power off, real-time record the running history of Micon and times of power-off
Purpose before it is power off

When it is power off and Micon measured that the voltage is reduced instantaneously, it will record the
Check power-off (including the cut-off of FFB).
Condition 1. When AC 380V three-phase power is reduced to below AC 322V, the power-off is detected.
2. When AC 220V three-phase power is reduced to below AC 181V, the power-off is detected.

Reset Mode After the power is resumed, running will automatically resume.

Inspection Items:
1. Investigate of no power at primary side of main power switch of control panel or abnormal voltage:
(1) Check if the city power is supplied normally:
E.g.: The city power hasn’t supplied the electricity, the city power supplies the short-phase electricity or very
lower voltage.
(2) Check if there is short-phase of three-phase power at the owner’s side:
E.g.: The power switch at owner’s side is tripped, or cut, or the main power switch is damaged, or the
single-phase doesn’t conduct.
2. Investigation when the three phases at the primary side of main power switch of control panel are normal:
(1) The main power switch of control panel is damaged, or the single-phase doesn’t conduct.
(2) Verification and reasons investigation of melted fuse at primary side of main transformer.
(3) Verification and reasons investigation of damaged coil of main transformer.
3. Verification of detection times of TCD 88 after it is switch-on:
Investigate the status of power-off and switch-on if quantity of the power-off exceeds 10 times (Data 0A).
4. Measure the voltage setting value of low-voltage detection circuit when the detection time of power-off is
abnormal:
Voltage measuring point: FB-BDC PCB 的 TEST V1----4
Adjustable resistance: HUVA
380V standard setting voltage: 8.0±0.05V
220V standard setting voltage: 4.7±0.05V
※380V action mode:
(a) It will be detected when the power voltage is lower than 322V.
(b) After it is detected, it will restore only when the power voltage is greater than 334V.
※220V action mode:
(a) It will be detected when the power voltage is lower than 181V.
(b) After it is detected, it will restore only when the power voltage is greater than 195V.

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
Failure
No.
TCD Content Relation HOLD
Class
91 A1 DZ POSI OPEN Failure (Qianniao,Through) ----
Check Detection of DZ Posi Open Failure (reed switch should be at ON position, while it is not at
Purpose ON position).
When the XDZ1 and XDZ2 actually detect the opening door area of Qianniao, Through
Check level, the failure will be detected if it is different with the setting of sample.
The rescue running of elevator will go to the lowest floor, and the door will be automatically
Condition opened when taking the samples of DZ1 and DZ2 as the datum of opening door.
※Only Qianniao, through elevator will detect the TCD 91.
Reset
Mode After the Failure is eliminated, running will automatically resume.

Inspection Items:
1. Check the body of XDZ Posi:
(1) Confirm the action and setting position of XDZ Posi.
(2) Confirm the wiring of XDZ Posi, and check the insert status of MIC and broken cable.
(3) Replace the damaged XDZ Posi.
2. Confirm the position of XDZ sample.
3. Check the force-application Buffer action of XDZ1 and XDZ2:
The Data change status of XDZ1 ($C540) and XDZ2 ($C541) of the main Micon when the XDZ
Posi cuts the induction plate:
Data 81 in and Data 00 out.
※ Operate XDZ1 ($C540) and XDZ2 ($C541) and observe MODE 22.
4. Check the power supply of SDC PCB:
Check if the P48V power supply is normal.

79/79

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015


Technical
Page No.
Information Failure Code Description of TCD
Classify
Rev. 2.0 (POSH,UAY1,e’NT) STQ-0291
No.
Failure Relation
TCD Content HOLD
Class
92 A1 DZ POSI Short-circuit Failure (Qianniao,Through) ----
Check Detection of DZ Posi Close Failure (reed switch should be at OFF position, which it is not at
Purpose OFF position).
When the speed of Motor is over 10m/min, while DZ Posi a short-circuit still exists after
Check three seconds, a failure will be detected.
Condition
※Only Qianniao, Through elevator will detect the TCD 92.
Reset
After the Failure is eliminated, running will automatically resume7.
Mode
Inspection Items:
1. Check the body of XDZ Posi:
(1) Confirm the action and setting position of XDZ Posi.
(2) Confirm the wiring of XDZ Posi, and check the insert status of MIC and broken cable.
(3) Replace the damaged XDZ Posi.
2. Confirm the position of XDZ sample.
3. Check the force-application Buffer action of XDZ1 and XDZ2:
The Data change status of XDZ1 ($C540) and XDZ2 ($C541) of the main Micon when the XDZ
Posi cuts the induction plate:
Data 81 in and Data 00 out.
4. Check the power supply of SDC PCB:
Check if the P48V power supply is normal.

Keeping Period:Permanent Rev. 1.1 Finished Date:99.02.05 STE-709-015