Professional Documents
Culture Documents
Catalogo
Catalogo
A special climatic test room used for artificial pro- An advanced 3D parametric software allows the engi-
duct ageing can help to individuate the critical neering of each very component within a project and
components which could successively turn faulty, quickly obtain true prototypes for features checking and
keeping our actual defect level always low (in characteristic design verification.
2000 the defective return rate was of 0,07% on
our total domestic sales).
INDEX
DOMESTIC SERIES
Axial fans
Centrifugal fans
INDUSTRIAL SERIES
Axial fans
Centrifugal fans
: Extraction : Application
2 tecnologia dell’aria
INDEX
Centrifugal fans
RC S page 88 RC page 92
Timertronic page 109 Grille AC, TURBO - Backdraught Shutters AC, page 67
TURBO, TURBO PLAST - Duct Clump AC, TURBO,
Speed controllers TURBO PLAST - Industrial and Domestic Controllers
Reducer CAA - Connector square to
Radio Transmitter and Radio Reciver page 110 page 112
round CAA - Angled outlet CAA
Light kit - Speed controllers
Shutter CAA
tecnologia dell’aria 3
GUIDE TO AIR EXTRACTION
Room Ventilation Where ventilation is necessary
The rooms in which people live and carry
out their various activities must be ventilated
for health and hygiene reasons.
Households
Lungs need air that, even though not as
pure as that in the country, is at least free kitchens, bathrooms, living
from dense smoke, steam, carbon dioxide, areas, cellars, that have few if
toxic fumes etc. any windows or openings, and
Moreover our sense of smell requires that small rooms in which people
the air does not smell bad. remain for a long period of time.
In addition polluted air ruins all that is
found in a room, including furniture, cov-
erings, wall paint, and so forth.
4 tecnologia dell’aria
GUIDE TO AIR EXTRACTION
The ventilation subdivides themselves in
three large categories, differentiating themsel-
How to choose your extractor fan
ves for Power. Formal procedure of installation
and Type of application.
Helicoidal ventilators
Axial bladed ventilators that move large
volume of air at low pressure. They can be
installed on glass and on wall when the
duct is short and directed to outside.
Helicoidal ventilator
Centrifugal ventilators
Radial bladed ventilator that moves limi-
ted volumes of air at high pressure. They
can move columns of air through long
ducts.
90°
Centrifugal ventilator
tecnologia dell’aria 5
GUIDE TO AIR EXTRACTION
The recommended air changes here below have to be understood as an approximate indication only. For further
information pls refer to the local country rules.
The following values are drawn from Prospect 111 contained in UNI 10339:95 standard.
In function from the type of premises, its possible to extract the air reciprocation (m3/h) necessary for every indivi-
dual environment found in chart.
• The calculation in base to the “crowd”, it is carried out multiplying the exchanges per person (m3/h) for the num-
ber of persons that normally are presented in the referred premises.
• The calculation in base to the “surface”, it is carried out multiplying the changes (m3/h x m2) for the surface of
the same premises.
• The calculation in base to the “volume”, it is obtained by multiplying the value in table for the cubic of the pre-
mises in (m3). The air that is being extracted from the premises, such as kitchens, bathrooms, services.
Hospitalization 11 40
Ward 11 40
Sterile enviroment 11 40
Hospital Toilets 8
Ref. prospect III UNI 10339:1995 UNI Ente Nazionale Italiano di Unificazione. www.uni.com http://www.uni.com/it/mondo_uni/punti_uni.htm).
6 tecnologia dell’aria
GUIDE TO AIR EXTRACTION
Flow rate
ROOMS’ CATEGORY Ref. No. People Ref. mq Ref. mc
Show room 6 22
Museum, Reading room 5,5 20
Building library, Church 6 22
church Toilets 8
Bar 11 40
Dining room 10 36
Bar,
Dancing 16,5 60
restaurant,
Kitchen 16,5
dancing
Toilets
Basement 9 33
Hypermarket
Flat 6,5 24
Commercial Barber’s shop 14 51
building Shops
Clothes shop 11,5 42
Grocery 9 33
Public zone 10 36
Swimming room 2,5
Swimmin-
Changing room 8
pool Sauna 2,5
Bowling
Sport 10 36
Playground 16,5 59
building Spectator zone 6,5 23
Gym
Dressing room 8
Toilets 8
Nursery school 4 14
Primary school 5 18
Junior school 6 22
Secondary school 7 25
University 7 25
Schools Toilets 8
Library 6 22
Music room 7 25
Laboratory 7 25
Teachers’ room 6 22
tecnologia dell’aria 7
GUIDE TO AIR EXTRACTION
How to choose your
extractor fan
The following three cases represent the
majority of common situations illustrating
the choice of extractor fans. Case 1
The following controls are recommended
for each installation as it is important not
to fit an appliance that is either too small,
therefore ineffective, or too big, therefore
excessively noisy.
CASE 1
Duct: hole leads directly outside.
Household kitchen for 2-4 people
Flow rate necessary: 130/150 m3/h.
Axial- flow fans with around 200 m3/h rate
are used when the hole leads directly out-
side. Various appliances suitable for this
type of room can be found in the catalogue:
Standard 12 and Minimatic 12 (130 m3/h)
wall mounted, or Ventil 15 (195 m3/h)
window mounted.
CASE 2
Duct: 15 m long pipe Ø 100 mm
Public toilet 2x2x3 m on ground floor of a
block of flats
Room volume: 12 m3
Air changes: 15/hour
Flow rate necessary: 180 m3/h
Firstly a centrifugal fan(Compact or
Aspirodor) with a flow rate slightly above
180 m3/h must be used with a long duct.
For example, the Compact 200 has a flow
rate of 156 m3/h and therefore is insuffi-
cient.
The Aspirodor 200 which can deliver a flow
rate of 200 m3/h could be suitable in this
case.
However certain corrections must be made
to the flow rate beforehand.
Table B shows resistances data per metre of
duct, in relation to its section, and the flow
rate necessary is shown for this purpose.
By referring to the right side of the diagram Case 2
along the flow rate axis find the 180 m3
flow rate and the intersection where it cuts
through the diagonal line showing the
100 mm diameter ducting.
8 tecnologia dell’aria
GUIDE TO AIR EXTRACTION
CASE 3
An office area, with false ceiling, ducting of 120 mm diameter, for 2 meters
in horizontal position, between ceiling and soffit, and 8 meters in vertical
with one bend between the two features. For this type of premises, the
Pressure losses for bends extraction air capacity is determined by multiplying the air capacity for
and elbows every person then is brought back in the table of the air reciprocations, for
the number of normally present persons in the office. Suppose that in our
Pressure Pressure office 6 persons normally are present.
loss for loss for Necessary capacity = 40 x 8 = 280 m3/h.
Speed bend elbow
If it is necessary now to calculate, of course taking in such consideration,
m/sec (mm H2O) (mm H2O) the losses of load of the ducting. From table B, left to right side, entering
1 0,01 0,1 from 280 m3/h value, and continue until you cross the blue line in diago-
nal of diameter 120 mm. Coming down to intersection strut frame in ver-
2 0,05 0,35 tical way, it is found a 0,6 mm H2O for every meter of ducting and besides
3 0,1 0,8 the diagonal of velocity of the air value of 7 m/s (rounded off if exceeded).
4 0,2 1,4
5 0,3 2 Multiplying the total lenght of the duct (10 meters) for the value of 0,6, you
obtain 6 mm H2O.
6 0,4 3 To this, you have to add the load of each bend, that is taken from the table A.
7 0,5 4 A value of velocity of 7 m/s is found on bends that individualizes to a loss
8 0,7 5,5 of load of 0,5 mm H2O.
The total loss is 6 + 0,5 = 6,5 mm H2O.
9 0,9 7
10 1,1 9 That’s serves as an individualize extractor that to a course of 280 m3/h gives
15 2,5 20 a pressure of 6,5 mm H2O. Such a combination of values, are searched on
the diagram of the characteristic curve of the product, that is restored on
20 4,5 35
pages of the centrifugal extractors.
30 10 65 As it can be verified, for the type of indicated installation, the product Turbo
125 can be applied.
Table A
tecnologia dell’aria 9
GUIDE TO AIR EXTRACTION
Table B: Diagram for fan choice
Duct Diameter in mm
50.000
00
1.1 40.000
00
1.0
30.000
900
800 20.000
50
700
40
600
30
25
10.000
500
20
8.000
15
6.000
400
5.000
360
4.000
10
320
9
8
3.000
280
7
6
240 2.000
5
4
200
180
3
2,5
1.000
160
800
2
140
120 500
400
100
300
1,5
80
200
100
80
60
50
0,01 0,02 0,03 0,04 0,06 0,08 0,1 0,2 0,3 0,4 0,6 0,8 1 2 3 4 6 8 10
Pressure losses in mm H2O per metre of duct
10 tecnologia dell’aria
GUIDE TO AIR EXTRACTION
Installation System
a) Air suction through extraction
This is the most widely used method
owing to its simplicity.
The polluted air is not channelled into the
adjacent rooms but carried outside by one or
more extractor fans.
YES
Fresh air enters the rooms through cracks
in the doors and windows and, if necessary,
through appropriate air intakes covered
NO
with grilles.
These last ones are recommended when
the room is airtight and powerful extractor
fans are installed. It is better that air intakes
and windows or doors that are often left
open, are as far away as possible from the
extractor fan, so that the incoming air does
not become outgoing air immediately and
vice-versa. YES NO YES
b) Pressure extraction
This fan lets new air go into the room by
taking it from the outside and creating a a)
higher pressure inside that forces the pollut-
ed air through the provided openings.
This system must see that the polluted air is
carried outside and not into other rooms. YES NO YES
Air currents are not created as the inside
pressure is higher than that outside.
c) Air suction through extraction and pressure b)
tecnologia dell’aria 11
GUIDE TO AIR EXTRACTION
Maintenance Grilles
Maintenance consists of periodically cleaning the impellers and all It is better to have one or two grilles to protect the extractor fan
other parts in contact with the flow of air created by the extractor when it is not in operation.
fan. Polluted air deposits grease and dust on the impeller and One inside, for manual or automatic operation, that does not
grille. This layer of dirt unbalances the impeller making the allow air changes with the outside when the extractor fan is
motor less efficient, putting it under excessive pressure and mak- turned off. This grille is a part of the appliance and therefore
ing it more noisy. should be obtained when purchasing.
Cleaning consists in removing the grease with a damp sponge (not
The outside grille is generally of the gravitational type. It pro-
wet) and soap, after disconnecting the appliance and taking care
tects the mechanism and circuits of the appliance against external
not to wet and damage the electric parts of the extractor fan.
atmospheric conditions, and prevents air changes when there is
not an internal grille.
Abbreviations
= Product I.M.Q approved.
(Istituto Italiano del Marchio di Qualità) = Double insulated product
= Explosion proof
IPX4 = Splash proof (EN 60529)
= Keymark
12 tecnologia dell’aria
DOMESTIC FANS
tecnologia dell’aria 13
“LOW PROFILE” FANS
SERIES
14 tecnologia dell’aria
“LOW PROFILE” FANS
SERIES
•Axial fans to extract air directly outside or
through ducting.
Dimensions
Suitable for wall, ceiling and window
(through window kit accessory) installa- A C D
tions.
• “Slim grille” with original and innovati-
IPX4
ve design.
• Quick and functional installation throu-
gh “click assembly” of the fan.
• All models are supplied with “operating
øE
B
warning light”. 03
• Two fixing screws to allow easy installa-
tion on the wall.
• Reduced internal wall dimensions to
allow installation where the bend of ducting
is close to the outlet of the product.
• The range is composed of 22 models in
100-120-150 mm, standard, Timer, PIR, Model A B C D E
SERIE IN 10/4 160 160 53 18 Ø100
HT, 12Volt version and motor with ball bea-
SERIE IN 12/5 180 180 53 19 Ø120
ring in some models.
SERIE IN 15/6 210 210 66 20 Ø150
• Very high performances in terms of flow
rate, low dB (A) and low power consump-
tion due to a precise study of optimisation of • Performance and noise tests on product samples (IN 10/4, IN 12/5, IN 15/6
motor-impeller combination. models) carried out by IMQ laboratory.
Performance tests in accordance with • Careful selection of components: ABS + filled polypropylene.
Standard UNI 10531 • Protection grade: IPX4 in accordance with Standard EN 60529.
Noise tests in accordance with Standard • Double insulated product, electric ground is not necessary.
UNI EN ISO 3741 • Voltage: 220-240V, 50Hz.
• In accordance with Standard EN 60335-2-80
• International Approval Keymark, issued by IMQ.
• Working temperature 45°C.
Technical Data
Hole Flow rate Max.Press. Weight
Model Rif. W V-Hz dB (A) 3m
diameter mm m3/h mm H20 Kg
IN 10/4 OW 501 9 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 T OW 507 6 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN BB 10/4 OW 525 8 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN BB 10/4 T OW 528 2 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 HT OW 543 1 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 PIR OW 546 4 100 105 13 220-240 V 50Hz 2,8 35,6 0,5
IN 12/5 OW 502 7 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN 12/5 T OW 508 4 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN BB 12/5 OW 526 6 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN BB 12/5 T OW 529 0 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN 12/5 HT OW 544 9 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN 12/5 PIR OW 547 2 120 180 18 220-240 V 50Hz 4,6 38,8 0,6
IN 15/6 OW 503 5 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
IN 15/6 T OW 509 2 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
IN BB 15/6 OW 527 4 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
IN BB 15/6 T OW 530 8 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
IN 15/6 HT OW 545 6 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
IN 15/6 PIR OW 548 0 150 330 30 220-240 V 50Hz 6,2 42,2 0,8
tecnologia dell’aria 15
FANS WITH “AUTOMATIC SHUTTER”
A SERIES
16 tecnologia dell’aria
FANS WITH “AUTOMATIC SHUTTER”
A SERIES
Axial fans to extract air directly outside or
through ducting.
Dimensions
Suitable for wall, ceiling and window
A C D
(through window kit accessory) installa-
tions.
• Grille provided with internal automatic
shutter.
IPX4
• Original and innovative design
• All models are supplied with “operating
øE
B
warning light”.
• Quick and functional installation throu-
gh “click assembly” of the fan. 03
• Two fixing screws to allow easy installa-
tion on the wall.
• Internal wall dimensions have been
reduced to allow easy installation when
Model A B C D E
using ducting and bends.
SERIE IN 10/4 A 160 160 53 42 Ø100
• The range is composed of 24 models in
SERIE IN 12/5 A 180 180 53 43 Ø120
100-120-150 mm, standard, Timer, SERIE IN 15/6 A 210 210 66 44 Ø150
Humidistat and PIR version and motor
with ball bearing in some models.
• Very high performances in terms of flow • Careful selection of components: ABS + filled polypropylene.
rate, low dB (A) and low power consump- • Protection grade: IPX4 in accordance with Standard EN 60529.
tion due to a precise study of optimisation of • Double insulated product, electric ground is not necessary.
motor-impeller combination. • Voltage: 220-240V, 50Hz.
• In accordance with Standard EN 60335-2-80.
• International Approval Keymark, issued by IMQ.
• Working temperature 45°C.
Technical Data
Hole Flow rate Max.Press. Weight
Model Rif. W V-Hz dB (A) 3m
diameter mm m3/h mm H20 Kg
IN 10/4 A OW 504 3 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN 10/4 A T OW 516 7 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN 10/4 A HT OW 519 1 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN 10/4 A PIR OW 522 5 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN BB 10/4 A OW 531 6 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN BB 10/4 A T OW 534 0 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN BB 10/4 A HT OW 537 3 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN BB 10/4 A PIR OW 540 7 100 110 16 220-240 V 50Hz 2,8 35,6 0,6
IN 12/5 A OW 505 0 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN 12/5 A T OW 517 5 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN 12/5 A HT OW 520 9 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN 12/5 A PIR OW 523 3 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN BB 12/5 A OW 532 4 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN BB 12/5 A T OW 535 7 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN BB 12/5 A HT OW 538 1 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN BB 12/5 A PIR OW 541 5 120 185 21 220-240 V 50Hz 4,2 38,8 0,7
IN 15/6 A OW 506 8 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN 15/6 A T OW 518 3 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN 15/6 A HT OW 521 7 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN 15/6 A PIR OW 524 1 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN BB 15/6 A OW 533 2 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN BB 15/6 A T OW 536 5 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN BB 15/6 A HT OW 539 9 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
IN BB 15/6 A PIR OW 542 3 150 340 33 220-240 V 50Hz 6,2 42,2 0,9
tecnologia dell’aria 17
TECHNICAL FEATURES – FUNCTIONS – APPLICATIONS
SERIES FANS
18 tecnologia dell’aria
SELV 12V
SERIES FANS
• This is the SELV (Safety Extra Low
Voltage) version working at 12V AC. of the
Transformer dimensions
axial fan model IN 10/4, designed to convey
air and fumes directly outside.
• This fan can be installed within the saftey 124,8 67
zones 1 and 2, as defined by the norm IEC
364-7 part 7, where the risk related to elec-
trical connections is very high.
• The very low power voltage of the IN 10/4
SELV, in combination of a dedicated tran-
104,8
sformer supplied with the fan, permits the
installation even in proximity of the bath
tub or the shower, because the eventual
direct contact with the fan does not pose any
threat of electrical danger.
The supply unit must be installed within
zone 3.
Please refer to page 43 for a detailed expla-
nation of the meaning of the different safety
zones.
Changing the supply unit model to connect with the fan, it is possible to have the
240 cm 60 cm SELV
4 different versions available:
Zone 3 Zone 2 Fan
1) Basic: fan + supply unit.
Zone 1 2) Pull Cord: fan + supply unit equipped with a pull cord for ON/OFF operation.
225 cm
3) Timer: fan + supply unit equipped with electronic control to change the delay
Switch before turning off the fan (delay adjustable from 2 to 30 minutes).
4) HT: fan + supply unit equipped with electronic control to turn ON/OFF the fan
automatically depending on the level of ambient relative humidity, with adjustable
rmer
Transfo
delay before turn off.
Technical Data
Flow Rate Max.Press. Weight
Model Rif. W V-Hz dB (A) 3m
m3/h mm H20 Kg
IN 10/4 SELV 12 V OW 557 1 105 15 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 SELV 12 V Pull Cord OW 560 5 105 15 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 SELV 12 V Timer OW 558 9 105 15 220-240 V 50Hz 2,8 35,6 0,5
IN 10/4 SELV 12 V HT OW 559 7 105 15 220-240 V 50Hz 2,8 35,6 0,5
Accessories IN series
Window kit
A B
Kit accessory for window and panel application.
Window Kit is suitable for installation in a single, double glazing
window glass or wood panel, from 3 to a thickness of 20 mm.
Model Ref. A B
A
hole diameter
Kit Finestra 10/4 OW 591 0 155 31 132,5÷145
Kit Finestra 12/5 OW 592 8 175 31 152,5÷165
Kit Finestra 15/6 OW 593 6 211 31 186÷195
tecnologia dell’aria 19
“LOW PROFILE” SMALL AXIAL FANS
9/3,5”
20 tecnologia dell’aria
“LOW PROFILE” SMALL AXIAL FANS
9/3,5”
• Axial fans to extract air directly outside or
Dimensions
through ducting.
• Exit spigot diameter 92 mm.
• Installation allowed also on ducts with
diameter less than 100 mm. IPX4
• Limited dimensions granting easy fitting
in uncomfortable position.
• Ideally suitable for wall/panel and ceiling
mounted installations. 03
• High performances/noise level ratio.
• Careful selection of components: ABS +
filled polypropylene.
in 9 T
Model A B C D
• When switched on, the fan has no delay
IN 9/3.5 121,5 ø 92 63 21
and remains on after being switched off
IN 9/3.5 T 121,5 ø 92 63 21
according to the preset time on the electronic
timer.
The time is adjustable from 3 to 25 minu-
• Noise tests on product samples carried out by IMQ laboratory.
tes.
• Careful selection of components: ABS + filled polypropylene.
• Protection grade: IPX4 in accordance with Standard EN 60529.
• Double insulated product, electric ground is not necessary.
• Voltage: 220-240V, 50Hz.
• In accordance with Standard EN 60335-2-80
• International Approval Keymark, issued by IMQ.
• Working temperature 45°C.
Technical Data
Hole diameter Flow rate Max.Press. Weight
Model Rif. W V-Hz dB (A) 3m
mm m3/h Pa Kg
IN 9/3.5 OW 555 5 92,5 ÷100 75 11 220-240 28 31,6 0,4
tecnologia dell’aria 21
AXIAL FANS - IPX4
STANDARD
22 tecnologia dell’aria
AXIAL FANS - IPX4
STANDARD
• Axial fans to extract air and fumes direct-
ly outside.
Dimensions
• Can be wall, ceiling and panel mounted. B C D
• Grille made in shining ABS material.
• In accordance with EN 60335-2-80.
• Standard T (10-12-15) - With elec- IPX4
tronic timer adjustable from 2 to 20 min-
utes approx.
ØE
A
Except
• Standard 8T - With Timermatic (page Standard
109). Pull-Cord
Technical Data
Hole diameter Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
mm m3/h and frequency mm H2O kg
STANDARD 8 OW 847 6 80÷100 35 15 220-240V 50Hz 36 0,4
STANDARD 8 T OW 848 4 80÷100 35 15 220-240V 50Hz 36 0,4
STANDARD 10 HT OW 011 9 100 88 21 220-240V 50Hz 2,5 39 0,5
STANDARD 12 HT OW 162 0 120 125 23 220-240V 50Hz 4 39 0,65
STANDARD 10 OW 157 0 100 88 21 220-240V 50Hz 2,5 39 0,5
STANDARD 12 OW 158 8 120 125 23 220-240V 50Hz 4 39 0,65
STANDARD 15 OW 161 2 150 230 36 220-240V 50Hz 4,2 44 1
STANDARD 10 T OW 159 6 100 88 21 220-240V 50Hz 2,5 39 0,5
STANDARD 12 T OW 160 4 120 125 23 220-240V 50Hz 4 39 0,65
STANDARD 15 T OW 164 6 150 230 36 220-240V 50Hz 4,2 44 1
STANDARD 10 Pull-Cord OW 175 2 100 88 21 220-240V 50Hz 2,5 39 0,5
STANDARD 12 Pull-Cord OW 947 4 120 125 23 220-240V 50Hz 4 39 0,65
tecnologia dell’aria 23
AXIAL FANS WITH AUTOMATIC SHUTTER - IPX4
STANDARDMATIC & MINIMATIC
24 tecnologia dell’aria
AXIAL FANS WITH AUTOMATIC SHUTTER - IPX4
STANDARDMATIC & MINIMATIC
• Axial fans to extract air and fumes directly
outside with automatic opening of shutter.
Dimensions
• Can be wall, ceiling and panel mounted.
• In accordance with EN 60335-2-80.
• Grille made in shining ABS material.
• IPX4 protected for areas with high
humidity.
ØE
• Standardmatic T and Minimatic T,
with electronic timer adjustable from 2 to 20 IPX4
minutes approx.
B C D
• All Standardmatic and Minimatic 10
and 12 have threaded spigots to allow panel
Model A B C D E
mounting by locking ring.
Standardmatic - Minimatic10/10T 154 154 45 51 ø 98
• Minimatic range, motor with ball Standardmatic - Minimatic12/12T 174 174 45 51 ø 118
bearings. Standardmatic - Minimatic15/15T 210 210 62 54 ø 146
Technical Data
Hole Flow rare Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and frequency mm H2O kg
MINIMATIC 10 OW 185 1 100 90 14 220-240V 50Hz 3 38 0,7
MINIMATIC 10T OW 186 9 100 90 14 220-240V 50Hz 3 38 0,7
MINIMATIC 12 OW 187 7 120 130 21 220-240V 50Hz 4 39 0,85
MINIMATIC 12T OW 189 3 120 130 21 220-240V 50Hz 4 39 0,85
MINIMATIC 15 OW 845 0 150 230 45 220-240V 50Hz 4,2 44 1,2
MINIMATIC 15T OW 846 8 150 230 45 220-240V 50Hz 4,2 44 1,2
STANDARDMATIC 10 OW 166 1 100 90 21 220-240V 50Hz 2,5 38 0,7
STANDARDMATIC 10T OW 167 9 100 90 21 220-240V 50Hz 2,5 38 0,7
STANDARDMATIC 12 OW 168 7 120 130 23 220-240V 50Hz 4,2 39 0,85
STANDARDMATIC 12T OW 169 5 120 130 23 220-240V 50Hz 4,2 39 0,85
STANDARDMATIC 15 OW 170 3 150 230 36 220-240V 50Hz 4,2 44 1,2
STANDARDMATIC 15T OW 171 1 150 230 36 220-240V 50Hz 4,2 44 1,2
tecnologia dell’aria 25
LONG LIFE AXIAL FANS - IPX4
MINI
26 tecnologia dell’aria
LONG LIFE AXIAL FANS - IPX4
MINI
• Axial fans to extract air and fumes direct-
ly outside.
Dimensions
• Can be wall, ceiling and panel mounted.
• Grille made in shining ABS material.
B C D
• Motor with ball bearings.
• In accordance with EN 60335-2-80.
ØE
A
• Mini Sensor - The fan starts automatical-
ly when the infrared sensor detects a presence
in the room. When the room is vacated the
timer takes control keeping the fan operating
for a preset time. Model A B C D E
• Operates in either in the light or in the Mini 10 /10 T / 10 Sensor 154 154 45 36 ø 98
dark with a radius of 8 metres.
Mini 12 /12 T / 12 Sensor 174 174 45 36 ø 118
• Thanks to its completely automatic
functioning is particularly suitable for
rooms used by the general public.
Technical Data
Hole diameter Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
mm m3/h and frequency mm H2O kg
MINI 10 OW 137 2 100 85 14 220-240V 50Hz 2,8 38 0,5
MINI 12 OW 138 0 120 125 21 220-240V 50Hz 4 39 0,65
MINI 10 T OW 141 4 100 85 14 220-240V 50Hz 2,8 38 0,5
MINI 12 T OW 142 2 120 125 21 220-240V 50Hz 4 39 0,65
MINI 10 SENSOR OW 121 6 100 85 14 220-240V 50Hz 2,8 38 0,5
MINI 12 SENSOR OW 122 4 120 125 21 220-240V 50Hz 4 39 0,65
tecnologia dell’aria 27
AXIAL FANS WITH MANUAL AND AUTOMATIC SHUTTER
VENTIL & VENTIMATIC
28 tecnologia dell’aria
AXIAL FANS WITH MANUAL AND AUTOMATIC SHUTTER
VENTIL & VENTIMATIC
• Axial fans to extract air and fumes directly
outside.
Dimensions
• Window or panel installation with
thickness up to 5mm.
• Grille made in shining ABS material.
• Rain proof external grille.
• In accordance with EN 60335-2-80.
A
IPX4
A
• For Ventil range, manual opening and
closing of shutter.
Model A B C D
Ventil 10 - Ventimatic 10 154 154 77 29
Ventil 12 - Ventimatic 12 174 174 74 29
Ventil 15 - Ventimatic 15 210 210 99 29
Ventimatic range
Splashproof fans for areas
with high humidity.
Technical Data
Window hole Flow rate Nominal Voltage Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and Frequency kg
VENTIL 10 OW 840 1 135÷145 68 20 220-240V 50Hz 42 0,9
VENTIL 12 OW 841 9 155÷165 100 21 220-240V 50Hz 42 1
VENTIL 15 OW 842 7 186÷195 155 30 220-240V 50Hz 43 1,6
VENTIMATIC 10 OW 110 9 135÷145 68 20 220-240V 50Hz 42 0,9
VENTIMATIC 12 OW 111 7 155÷165 100 21 220-240V 50Hz 42 1
VENTIMATIC 15 OW 112 5 186÷195 155 30 220-240V 50Hz 43 1,6
tecnologia dell’aria 29
COMMERCIAL FANS
VENTILOR
30 tecnologia dell’aria
COMMERCIAL FANS
VENTILOR
• Axial fans to extract air and fumes directly
outside.
Dimensions
• For installation in windows, double
glazing and panels up to 50 mm.
• Rain proof external grille.
• In accordance with EN 60335-2-80.
• In shining ABS material.
A
• Ventilor 20/8 M - Manual immediate
opening and closing of shutter.
• Ventilor 20/8 AR - 25/10 AR
• Automatic and silent opening and closing
of shutter. C D B
• Warning operating light.
Model A B C D
Ventilor 20/8 M - 20/8 AR 280 280 94 30
Ventilor 25/10 AR 335 335 128 33
Model Ref.
Double glazing kit Ventilor 20/8 OW 804 7
Double glazing kit Ventilor 25/10 OW 805 4
Built in kit for speed controller OW 905 2
Wall fixing kit Ventilor OW 191 9
Kit for Radio Transmission. RG 5 AR
RG 5 AR OW 315 4
Kit for Radio Transmission OW 913 6
Technical Data
Hole Flow rate Nominal Voltage Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and Frequency kg
VENTILOR 20/8 M OW 188 5 225÷235 450 50 220-240V 50/60Hz 58 2,4
VENTILOR 20/8 AR OW 190 1 225÷235 450 50 220-240V 50/60Hz 58 2,4
VENTILOR 25/10 AR OW 192 7 275÷285 750 60 220-240V 50/60Hz 59 5,6
tecnologia dell’aria 31
AUTOMATIC VENTILATION SYSTEMS
VENTILOR 25/10 E
32 tecnologia dell’aria
AUTOMATIC VENTILATION SYSTEMS
VENTILOR 25/10 E
• Axial fans to extract air and fumes direct-
ly outside.
Dimensions
• For installation in window, double
glazing, panel and wall with thickness up
to 50 mm.
• With optional fittings also in double
window or wall.
A
• It is controlled by TRM 3 radio remote
control.
• Allows a safety personalized code to be set
up in order to avoid interferences with other
users having installed similar products
C D B
working on 433.92 Mhz frequency.
• Rain proof external grille.
• In accordance with EN 60335-2-80 and Model A B C D
Electromagnetic Compatibility (EMC)
Ventilor 25/10 E 335 335 128 33
Standards.
• In shining ABS material.
Accessories:
• Transmitter TRM 3.
• Double glazing kit Ventilor.
• Wall fixing kit. Eight LED indicators: 1 stand by, Individual fans or different
1 reception, 1 reverse and 5 groups of fans can be con-
Model Ref. speeds. trolled by a single radio trans-
Double glazing kit Ventilor 25/10 OW 805 4 mitter (for details see separate
Radio Transmitter TRM3 OW 916 9
TRM 3 entry).
Wall fixing kit Ventilor OW 191 9
Technical Data
Hole Flow rate Nominal Voltage Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and Frequency kg
VENTILOR 25/10 E OW 228 9 275÷285 750 60 220-240 50Hz 59 5,6
tecnologia dell’aria 33
COMMERCIAL FANS
SMART 23/9 & 30/12
34 tecnologia dell’aria
COMMERCIAL FANS
SMART 23/9 & 30/12
• Axial fan for window, wall or panel
installation for medium and big domestic
Dimensions
and commercial requirements. D
B
23/9
The automatic shutter mechanism is AR Wall
extremely silenced and reliable.
• SMART 23/9 M is provided with a man-
ual opening version.
• SMART 23/9 and 30/12 Control with A C
a 3 speed + reversibility 12V electronic con-
troller.
D
• Including 2 special gaskets to prevent SMART 23/9 AR Wall
A C
Model A B C D
• Motor with ball bearings. Smart 23/9 M 321 331 141 30
• According to EN 60335-2-80 norms.
Smart 23/9 AR 321 331 141 30
• In the 12” CONTROL version, we can
connect various sensors (air quality, humi- Smart 23/9 CONTROL 321 331 141 30
dity, PIR) for a complete and automatic self Smart 23/9 WALL 424 434 242-316 30
adjusting functioning. Smart 30/12 AR 375 385 148 30
Smart 30/12 CONTROL 375 385 148 30
Technical Data
Hole Flow rate Nominal Voltage
Model W dB (A) 3 m Weight kg
diameter mm m3/h and Frequency
ALL MODELS SMART 23/9(Except Wall) 254÷262 750 40 220-240V 50/60Hz 47 3,7
ALL MODELS SMART 30/12 324÷337 1.350 75 220-240V 50/60Hz 51 6,6
SMART 23/9 WALL 375÷385 750 40 220-240V 50/60Hz 47 7
Ref. - Codes
AR AR M Control Control Control
Model
Automatic Reversible Wall Manual Grey Briar Wood Black
SMART 23/9 Ref. OW 720 5 Ref. OW 726 2 Ref. OW 721 3 Ref. OW 722 1 Ref. OW 724 7 Ref. OW 723 9
SMART 30/12 Ref. OW 714 8 - - Ref. OW 715 5 Ref. OW 719 7 Ref. OW 717 1
tecnologia dell’aria 35
COMMERCIAL FANS
SMART 23/9 & 30/12
B
C A
Model ø A mm B mm C mm
SMART 23/9 254/262 210 230
SMART 30/12 324/337 245 245
Easy and quick installation on win- Easy removal of the front grille by
Big tolerance on the window glass diameter dow glass through a special assembly untightening the 2 safety screws and
hole, which allows to overcome to some cutting fixing system by click springs and final with a simple finger pressure on both
errors or adapt the fan to any existing hole. screw blocking. fan sides.
All models from the SMART series are suit-
able for installation in a single, double glaz-
FLOW RATES m3/h (with RG5 AR controller)
ing window glass or wood panel, up to a
thickness of 48 mm. Model I° Speed II° Speed III° Speed IV° Speed V° Speed
375 mm
36 tecnologia dell’aria
COMMERCIAL FANS
SMART 23/9 & 30/12 CONTROL
Available in 3 colours:
220/240V 12V
50/60 Hz
Grey
SENSOR
(for automatic
operation)
12V
Black
SMART
Control
Electronic Controller
Briar Wood The use of a 12V Electronic Controller is of extreme importance because it allows
the SMART 23/9 and 30/12 CONTROL series to be installed in any unsafe and
electrically hazardous place like wet floors, water splashes, high level of humid-
ity etc. In fact the System (according to the CEI 64.8 norm) gives a total electric
security to the installation, dividing the 220/240V main line of the fan from the
12V of the electronic controller.
tecnologia dell’aria 37
IN-LINE AXIAL DUCT FANS - IPX4
TB
38 tecnologia dell’aria
IN-LINE AXIAL DUCT FANS - IPX4
TB
• In-line axial fans for installation into
ducting with diameter 10, 12 and 15 cm.
Dimensions
• Can be used to extract air, to intake air or
as a booster to increase airflow in an exist-
ing installation.
• Body in thermoplastic material.
• Impeller in polypropylene.
• Induction motor. Impedance protection IPX4
øA
øA
øC
on models TB 10 and TB 12, thermal pro-
tection on model TB 15.
• Protected against water splashes, IPX4.
• Low consumption and noise makes the
fan suitable for any use. B
Accessories:
• See page 108 and 109
Model øA B øC
TB 10 96 97 55
TB 12 116 97 55
TB 15 147 113 55
6 59
Static Pressure (mm H2O)
5 49
3 29
2 20
1 TB 12 10
TB 15
TB 10
0 0
0 50 100 150 200 250 300
Flow rate (m3/h)
Technical Data
Tube diameter Flow rate Max Press. Nominal voltage and Nom. curr. dB (A) Weight
Model Ref. W RPM
ø mm m3/h mm. H2O frequency Amp. at 230V 2m kg
TB 10 OW 184 4 100 80 3 15 220-240V 50Hz 0,09 42 2500 0,5
TB 12 OW 194 3 120 130 3,5 15 220-240V 50Hz 0,1 43 2200 0,6
TB 15 OW 195 0 150 250 5,5 25 220-240V 50Hz 0,2 50 2400 0,7
tecnologia dell’aria 39
HELICO CENTRIFUGAL EXTRACTOR FANS
SILENTE
40 tecnologia dell’aria
HELICO CENTRIFUGAL EXTRACTOR FANS
SILENTE
• Centrifugal fans to extract air and fumes
directly outside or through long ducts. Can
Dimensions
be installed in holes with diameter 10, 12
and 15 cm. Low sound level with high per-
formance. In ABS material.
In accordance with EN 60335-2-80.
• Silente T - With electronic timer adjustable
ØE
from 2 to 20 minutes. IPX4
A
• Silente HT - The fan starts automatical-
ly when the humidity level in the room is CL III
(Silente 12 V)
higher than the pre-determined humidity
level on the potentiometer which allow to
C D B
adjust from 40% to 90%.
• Silente Sensor - The fan starts automatically
when the infrared sensor detects a presence in the
Model A B C D E
room, when the room is vacated the timer takes
control keeping the fan operating for a preset time. All SILENTE models 184 184 101,5 8,5 ø 98
• Silente 12 Volt - In addition to the techni-
cal and functional features of the basic model
it is manufactured with a very low power Flow rate (ft. 3/min.)
10 50 90 130
voltage (SELV). 12
• Silente 12 Volt T: With electronic timer 110
adjustable from 2 to 20 minutes.
9
Static pressure (mm H2O)
80
6
50
Silente 12 V
20
0 0
0 20 40 60 80
Flow rate (m3/h)
Technical Data
Hole Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and frequency mm H2O kg
SILENTE OW 865 8 100÷150 75 19 220-240V 50Hz 12 36 0,9
SILENTE 12 Volt OW 870 8 100÷150 60 15 220-240V 50Hz 10 36 0,9
SILENTE 12 Volt T OW 871 6 100÷150 60 15 220-240V 50Hz 10 36 0,9
SILENTE T OW 867 4 100÷150 75 19 220-240V 50Hz 12 36 0,9
SILENTE Sensor OW 866 6 100÷150 75 19 220-240V 50Hz 12 36 0,9
SILENTE HT OW 868 2 100÷150 75 19 220-240V 50Hz 12 36 0,9
tecnologia dell’aria 41
HELICO CENTRIFUGAL EXTRACTOR FANS
SILENTE
For all models
• Supplied with washable filter assuring
long life of the motor and remarkable pro-
tection to the impeller.
• With anti-vibration gasket made of elas-
tomer which fits on uneven surfaces and
allows installation in holes with diameter
10, 12 and 15 cm.
• Quick installation as all components are
clicked together.
• The template inside packaging allows a
precise mounting on wall.
Low sound level. Splashproof fans for areas
• The reduced protrusion of the exit spigot
36 decibel. with high humidity.
allows you to install the unit into ducting
with curves placed immediately behind the
exit hole.
• Silente T - Easy timer adjustment by
small control knob.
• Silente H - Humidity level adjustable
from 40% to 90% and electronic timer
adjustable from 2 to 20 minutes.
Both controls are adjusted by small knobs.
• Silente Sensor - It is extremely simple to
install since it is connected to the electrical
system with just two wires, thus eliminating The captive fixing screws in Integral back draught shutter.
the connections that normally need to be special cone shaped housing
made to the light and the light switch. to allow for any necessary
Easy timer adjustment by small control knob. adjustment during installa-
tion in walls or ceiling.
Anti-vibration gasket
made of elastomer.
Washable filter.
42 tecnologia dell’aria
HELICO CENTRIFUGAL EXTRACTOR FANS
SILENTE SELV 12V
• Can be installed in safety zones 1 and 2 as
Installation example of SELV Fan.
established by the IEC 364- 7 where risk of
electrical contact is high.
• 220÷240/12V~ transformer, in accor-
dance with IEC 742 class II, IP22 protected
with safety thermostat.
• The very low power voltage of the Silente
12 Volt, (SELV - Safety Extra Low Voltage),
with the use of a special transformer sup- 240 cm 60 cm SELV
plied with the fan, permits installation even Zone 3 Zone 2 Fan
225 cm
threat of electrical danger.
Switch
rmer
Transfo
IEC 364-7 standard, on Part 7 contains a section dedicated to “Locations containing a bath tub or shower basin” where, says the text
“ the risk of electric shock is increased by a reduction in body resistance and contact of the body with earth potential”.
In order to avoid this high risk of electric shock the standard classifies in the room different zones and for each zone prescribes different
installation limits of electrical components.
The standard describes the different zones as follows:
• Zone 0: is the interior of the bath tub or shower basin.
• Zone 1: is limited by the vertical plane circumscribing the bath tub or shower basin, by the floor and the horizontal plane 2.25 m. above
the floor.
• Zone 2: is limited by the vertical plane external to Zone 1 and the parallel vertical plane 0,60 m. external to Zone 1, by floor and the
horizontal plane 2,25 m. above the floor.
• Zone 3: is limited by the vertical plane external to Zone 2 and the parallel vertical plane 2,40 m. external to Zone 2, by floor and the
horizontal plane 2,25 m. above the floor.
For each zone the standard makes a list of the prescriptions for the electrical equipment that may be or may not be installed as follows:
• In zone 0, only electrical appliances specially intended for use in a bath tub are permitted.
• In zone 1, only water heaters or SELV type appliances (Safety Extra Low Voltage) may be installed.
• In zone 2 only water heaters, and Class II luminaires or SELV type appliances may be installed.
• In zone 3 there are no limits for installation of electrical equipment, but anyway the eventual “ Switchgear and Controlgear” must be
as follows: supplied individually by an isolating transformer, supplied by SELV, protected by a residual current protective device with a
residual operating current not exceeding 0,03 A.
tecnologia dell’aria 43
CENTRIFUGAL FANS - IPX4
COMPACT
44 tecnologia dell’aria
CENTRIFUGAL FANS - IPX4
COMPACT
• Centrifugal fans to extract air and fumes
through ducting or pipes. Dimensions
• Can be ceiling mounted and with an
optional accessory (Window Kit) can be also
glass mounted.
ØE
• In ABS material. Except
• In accordance with EN 60335-2-80. 300T
A
• Compact T - With built-in electronic
timer adjustable from 2 to 20 minutes. IPX4
300
120
200
10
60
100
0 0
0 60 120 180 240 300
Flow rate (m3/h)
Technical Data
Hole Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and frequency mm H2O kg
COMPACT 100 OW 850 0 100÷120 85 45 220-240V 50Hz 12,5 40 1,3
COMPACT 200 OW 852 6 100÷120 156 76 220-240V 50Hz 20 45 1,8
COMPACT 300 OW 854 2 100÷120 250 95 220-240V 50Hz 40 54 2,3
COMPACT 100 T OW 851 8 100÷120 85 45 220-240V 50Hz 12,5 40 1,3
COMPACT 200 T OW 853 4 100÷120 156 76 220-240V 50Hz 20 45 1,8
COMPACT 300 T OW 945 8 100÷120 250 95 220-240V 50Hz 40 54 2,3
COMPACT 100 H OW 862 5 100÷120 85 45 220-240V 50Hz 12,5 40 1,3
COMPACT 200 H OW 863 3 100÷120 156 76 220-240V 50Hz 20 45 1,8
COMPACT 300 H OW 864 1 100÷120 250 95 220-240V 50Hz 40 54 2,3
COMPACT 100 SENSOR OW 123 2 100÷120 85 45 220-240V 50Hz 12,5 40 1,3
tecnologia dell’aria 45
CENTRIFUGAL FANS - IPX4
COMPACT
With anti-vibration
gasket made of
elastomer which fits
on uneven surfaces.
46 tecnologia dell’aria
CENTRIFUGAL FANS - IPX4
COMPACT
tecnologia dell’aria 47
CENTRIFUGAL IN LINE FANS
ASPIRODOR 165
48 tecnologia dell’aria
CENTRIFUGAL IN LINE FANS
ASPIRODOR 165
• Centrifugal fans to extract air and fumes
through ducts or pipes.
Dimensions
• Can be easily installed in-line (replacing
a part of the pipe) or in angle (replacing a B D
E
F
• In ABS material.
C
ØF
ØE
Model A B C D E F
Aspirodor 165 in line 205 205 263 148 ø 126 ø 102
Dual purpose spigots suitable for 100 mm Aspirodor 165 in angle 205 205 242 148 ø 126 ø 102
or 120 mm ducts.
175
15
Fixing bracket with elongated fixing holes to
Static pressure (mm H2O)
10
75
25
0 0
0 40 80 120 160
Flow rate (m /h)
3
Technical Data
Hole Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
diameter mm m3/h and frequency mm H2O kg
ASPIRODOR 165 OW 165 3 100÷120 150 80 220-240V 50Hz 18 51 1,9
tecnologia dell’aria 49
DOUBLE INLET CENTRIFUGAL FANS
ASPIRODOR 200-300-400
50 tecnologia dell’aria
DOUBLE INLET CENTRIFUGAL FANS
ASPIRODOR 200-300-400
• Centrifugal fans to extract air and fumes
through ducts or pipes.
Dimensions
• Can be ceiling and wall mounted.
Aspirodor 200 Aspirodor 300-400
• Supplied with installation flange. A
A
• Double inlet fans.
• In accordance with EN 60335-2-80.
• In ABS material.
B
For all Aspirodor range
C C C C
D D D D
Model A B C D
Mount. holes
32
300
For all Aspirodor range, simple main
connection via external connector box.
Static pressure (mm H2O)
240
24
static pressure (Pa)
400
300
180
16
200
120
0
0 90 180 270 360 450
Flow rate (m3/h)
Technical Data
Hole diameter Flow rate Nominal voltage Max pressure Weight
Model Ref. W dB (A) 3 m
mm mm m3/h and frequency mm H2O kg
ASPIRODOR 200 OW 145 5 100÷150 200 80 220-240V 50Hz 21 49 1,75
ASPIRODOR 300 OW 149 7 100÷150 350 80 220-240V 50Hz 27 53 2,2
ASPIRODOR 400 OW 151 3 100÷150 400 80 220-240V 50Hz 35 55 2,75
tecnologia dell’aria 51
FALSE CEILING MOUNTED CENTRIFUGAL DUCT FANS
INTRA
52 tecnologia dell’aria
FALSE CEILING MOUNTED CENTRIFUGAL DUCT FANS
INTRA
• Centrifugal fan designed for installation in
suspended ceilings and ceilings tiles, allow-
Dimensions
ing ducted extraction to the outside wall.
• Equipped with integral back draugh shutters.
• Can be installed directly on the ceiling
frame. In case the load bearing of the struc-
ture do not allow a direct installation, must
D
C
B
be fixed on the ceiling wall.
A
• In accordance with EN 60335-2-80.
• White ceiling grilles in shining ABS
E
material.
• Totally recessed, maintenance free, motor
mounted on ball bearings. A
Performance (ft.3/min.)
120
11
Static pressure (mm H2O)
Kit with brackets for ceiling mounting 300 Static pressure (Pa)
Intra.
80
200
Modello Ref./Cod. FNGDME 40
Staffe di fissaggio OW 932 6
100
3
Accessory to fix the Intra fan directly to the
ceiling in case the counter ceiling frame do
not allow extra load. 0
0 100 200 300
• Further accessories see page 108.
Performance (m3/h)
Technical Data
Flow rate Nominal voltage and Max
Model Ref. W dB (A) 3 m Weight kg
m3/h frequency pressure mm H2O
INTRA 100 OW 918 5 95 30 220-240V 50Hz 14 31 2,2
INTRA 200 OW 919 3 190 35 220-240V 50Hz 9 39 3,4
INTRA 300 OW 920 1 270 45 220-240V 50Hz 12 40 3,5
tecnologia dell’aria 53
FALSE CEILING MOUNTED CENTRIFUGAL DUCT FANS
INTRA
Air replacement in closed rooms is quite
important for a good comfort of the present
people. Sometimes, in commercial or public
buildings, offices or other working places, a
correct air change is not easy to achieve.
But in case these premises are equipped with
a false ceiling, we can then solve this prob-
lem in a very simple and rather cheap way:
installing an INTRA into the false ceiling.
INTRA is the best and cheapest solution for
a ceiling mounted fan.
Fan easily unhanged for cleaning or External grille made of shining ABS plas-
maintenance purposes, leaving the hous- tic material with a stylish and innovative
ing fixed to the ceiling and connected to the design, suitable for installation in various
duct. ceiling depth sizes.
54 tecnologia dell’aria
FALSE CEILING MOUNTED CENTRIFUGAL DUCT FANS
INTRA
The fan should remain installed exactly
at same level than the ceiling boards above
Positioning
one or various work stations and be con-
nected with the outside wall through flexi-
ble and cheap ducting which can be fixed
directly to the ceiling wall or layed on the
ceiling boards if the structure is strong
enough.
False Ceiling
Fig. 3
tecnologia dell’aria 55
INDUSTRIAL FANS
56 tecnologia dell’aria
IMPELLER HOUSING ROTATION
Exit direction and rotation viewed from the motor side
(Norm AMCA standard 99-2406-83)
Rotation anti clockwise CCW
tecnologia dell’aria 57
STANDARD AXIAL FANS
EB
58 tecnologia dell’aria
STANDARD AXIAL FANS
EB
• Axial fans for wall or panel mounting to
convey air and fumes directly outside or Dimensions
through short ducts.
• Temperature 55 °C. A F
• Also suitable for application on machines C B G
D
where a forced ventilation or air suction is .
r.a
required.
øa
• Safety protection grille.
• Body and grille in steel protected by an
epoxy-based anticorrosive paint.
• Impeller in ABS material.
ØE
• Induction motor, class F, IP 44 protected.
• Model EB 504, IP54 protected.
• In accordance with the essential require-
ments of 89/392/CE directive concerning
machines, and with European Standards
EN 292 part I and II, UNI EN 294 and
IEC 204-1 and 2.
• Industrial regulators available (see page 86). Model A B C D øE F G r.a. øa Kg
EB 25 4M 96 70 9 8 260 340 290 12 7 3,4
Reversibiliy: EB 30 4M 111 70 9 10 312 390 340 15 9 4,5
• Single-phase: only model EB 504 M. EB 35 4M 98 90 10 12 365 460 410 15 9 5,2
• Three-phase: all the models. EB 40 4M 108 90 10 12 415 510 460 15 9 6,4
EB 50 4M 145 90 10 15 515 630 580 15 11 8,5
Accessories:
• See page 111. EB 25 4T 125 70 9 8 260 340 290 15 11 4,0
EB 30 4T 125 70 9 10 312 390 340 15 7 4,6
EB 35 4T 125 90 10 12 365 460 410 15 9 5,5
EB 40 4T 125 90 10 12 415 510 460 15 9 6,0
EB 50 4T 145 90 10 15 515 630 580 15 11 8,4
Technical Data
Motor Flow rate Max press. Nominal curr. A. dB (A)
Model Ref. Motor N° Poles W Hz RPM
protection m3/h mm H2O at 230V at 400V 2m
EB 25 4M OW 450 9 IP44 single-phase 900 10 4 85 50 0,57 - 55 1300
EB 30 4M OW 451 7 IP44 single-phase 1500 9 4 100 50 0,79 - 59 1300
EB 35 4M OW 452 5 IP44 single-phase 2250 10 4 120 50 0,49 - 63 1300
EB 40 4M OW 453 3 IP44 single-phase 2900 9 4 145 50 0,63 - 66 1260
EB 50 4M OW 455 8 IP54 single-phase 4500 14 4 260 50 1,40 - 72 1300
EB 25 4T OW 496 2 IP44 three-phase 900 10 4 45 50 0,20 0,12 55 1300
EB 30 4T OW 497 0 IP44 three-phase 1500 9 4 60 50 0,24 0,14 59 1300
EB 35 4T OW 498 8 IP44 three-phase 2250 10 4 95 50 0,39 0,23 63 1300
EB 40 4T OW 499 6 IP44 three-phase 2900 9 4 130 50 0,47 0,27 66 1280
EB 50 4T OW 456 6 IP54 three-phase 4500 14 4 230 50 1,00 0,57 72 1300
tecnologia dell’aria 59
COMPACT AXIAL FANS
EC
60 tecnologia dell’aria
COMPACT AXIAL FANS
EC
• Axial fans for wall or panel mounting to
convey air and fumes directly outside or
Dimensions
through short ducts. C D
• Temperature 55 °C. A E
B G
• Also suitable for application on machines
where a forced ventilation or air suction is øa
øa
required.
• Safety protection grille.
• Body and impeller in steel protected by an
H
epoxy-based anticorrosive paint.
• Zinc plated steel blade, statically and
dynamically balanced. EC 20-25
• Induction motor with external rotor on
ball bearings. C
A E D
• Compact fans with low sound level com- B G F
H
IEC 204-1 and 2.
• Industrial regulators available (see page 86).
Reversibility: EC 30-60
• Single-phase: all the models except for
EC 204 M - EC 254 M. Model A B C D E F G øH r.a. øa
• Three-phase: all the models. EC 20 4M/T 280 230 64 64 54 8 207 15 7
EC 25 4M/T 340 290 72 64 70 8 259 15 7
Accessories: EC 30 4M/T 390 340 93 70 57,5 10 311 15 9
• See page 111. EC 35 4M/T 460 410 104 67 85 35 12 363 15 9
EC 40 4M/T 510 460 117 67 85 35 12 413 15 11
EC 50 4T 630 580 138 90 96 15 513 15 11
EC 60 6T 815 765 138 100 96 15 640 25 11
Technical Data
Motor Flow rate Max press. N° Nom. current in A. dB (A)
Model Ref. Motor W Hz RPM
protection m3/h mm H2O Poles at 230V at 400V 2m
EC 20 2M OW 459 0 IP44 single-phase 950 16 2 60 50/60 0,30 - 61 2740
EC 20 4M OW 460 8 IP44 single-phase 400 8 4 40 50/60 0,30 - 48 1350
EC 25 4M OW 461 6 IP44 single-phase 1000 10 4 70 50/60 0,50 - 54 1400
EC 30 4M OW 462 4 IP44 single-phase 1900 12 4 90 50/60 0,60 - 58 1370
EC 35 4M OW 463 2 IP44 single-phase 3200 10 4 150 50/60 0,60 - 64 1370
EC 40 4M OW 465 7 IP44 single-phase 4300 16 4 180 50/60 0,80 - 63 1390
EC 20 4T OW 490 5 IP44 three-phase 500 7,5 4 20 50/60 0,17 0,10 47 1450
EC 25 4T OW 491 3 IP44 three-phase 1000 10 4 30 50/60 0,17 0,10 54 1420
EC 30 4T OW 492 1 IP44 three-phase 1900 10 4 90 50/60 0,35 0,20 62 1370
EC 35 4T OW 493 9 IP44 three-phase 3200 19 4 150 50/60 0,60 0,35 65 1400
EC 40 4T OW 494 7 IP44 three-phase 4300 16 4 150 50/60 0,80 0,50 66 1400
EC 50 4T OW 467 3 IP54 three-phase 8700 35 4 760 50/60 3,30 1,90 72 1440
EC 60 6T OW 469 9 IP54 three-phase 11200 26 6 520 50/60 2,20 1,30 70 990
tecnologia dell’aria 61
IN LINE CENTRIFUGAL DUCT FANS
TURBO PLAST
62 tecnologia dell’aria
IN LINE CENTRIFUGAL DUCT FANS
TURBO PLAST
New range of centrifugal fans to convey in
ducts air with a maximum temperature of Dimensions
55°C.
• Suitable for domestic, commercial and
A
industrial applications. G ØB
• Frame completely made in VO polymeric
materials to guarantee the highest level of
D
flame resistance. H
IPX4
• Motor support in high resistance glass fil-
led nylon with air fins incorporated. F
E
Mounting bracket integrated with the pro-
duct that allows installation in any position.
• Motors on ball bearings with thermopro-
D
tector.
ØC ØB
• Product protection IPX4.
• Eletrical box with IPX5 protection.
• Electrical box with incorporated safety
grilles both on inlet and outlet openings.
• In case of duct installations it is possible
Model A øB øC D E F G H Kg
easily remove the grill from the ducted side,
Turbo Plast 100 287 98 275 17 70 242 282 12 2,6
increasing then the product performances.
• Double insulated product, electric groun- Turbo Plast 125 287 123 275 24 70 242 282 12 2,6
ding it is not necessary. Turbo Plast 150 287 148 275 32 70 242 282 12 2,6
• Motor speed can be regulated with an Turbo Plast 160 287 158 275 33 70 242 282 12 2,6
optional electronic regulator (see page 67).
• In accordance with EN 60335-2-80.
Accessories
• See page 67 A = with two grilles B = with one grille
Turbo Plast 100 Turbo Plast 125 Turbo Plast 150 Turbo Plast 160
35 35 35 35
Static Pressure (mm H2O)
30 30 30 30
25 25 25 25
20 20 20 20
15 15 15 15
B B B B
10 10 10 10
A
5 A 5 5 5
A A
0 0 0 0
0 50 100 150 200 250 0 100 200 300 400 0 150 300 400 500 0 150 300 450 600
Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h)
Technical Data
Flow rate Max press. dB (A) Corr. Nom. in
Model Ref. W Hz RPM
1 griglia 2 griglie mm. H2O 3m (*) Amp. a 230V
Turbo Plast 100 OW 372 5 250 220 31 75 50 48 0.30 2680
Turbo Plast 125 OW 375 8 370 310 30 75 50 48 0.33 2560
Turbo Plast 150 OW 386 5 460 400 29 75 50 49 0.39 2450
Turbo Plast 160 OW 387 3 500 450 29 75 50 50 0.40 2450
tecnologia dell’aria 63
IN LINE CENTRIFUGAL DUCT FANS
TURBO
64 tecnologia dell’aria
IN LINE CENTRIFUGAL DUCT FANS
TURBO
Range of centrifugal high performances fans
to convey in ducts air or fumes with a maxi- Dimensions
mum temperature of 55°C.
Suitable for applications in domestic, com-
A
mercial and industrial such as bathrooms, G ØB
D
• Complete range of inlet and outlet diame- H
IPX4
ters to allow the installations in most stan-
dard sizes of commercial ducts. F
E
• The range is composed by 14 models either
in standard version with high performances
then in ES version that offers a good noise
D
level and a reduction in energy consumption ØC ØB
Technical Data
Flow rate Max Press. dB (A) Nom. Curr. in A.
Model Ref. W 230 V Hz RPM
m3/h mm. H2O 3m (*) at 230V
Turbo 100 ES OW 371 7 210 30 55 50 45 0.25 2000
Turbo 100 OW 370 9 270 30 75 50 53 0.35 2600
Turbo 125 ES OW 374 1 290 29 55 50 45 0.25 1850
Turbo 125 OW 373 3 400 29 75 50 52 0.38 2530
Turbo 150 ES OW 377 4 370 27 55 50 42 0.25 1850
Turbo 150 OW 376 6 500 29 75 50 52 0.38 2530
Turbo 160 ES OW 378 2 540 28 75 50 52 0.38 2500
Turbo 160 OW 379 0 710 37 90 50/60 56 0.43 2500
Turbo 200 ES OW 380 8 730 30 90 50/60 56 0.42 2550
Turbo 200 OW 381 6 1050 55 180 50/60 58 0.78 2550
Turbo 250 OW 383 2 1200 56 180 50/60 59 0.78 2590
Turbo 315 ES OW 385 7 1250 50 180 50/60 59 0.78 2600
Turbo 315 OW 384 0 1400 65 280 50/60 59 1.24 2500
Aeraulic performances
36 36 36 45
Static Pressure (mm H2O)
24 24 24 30
150
100 125 160
12 12 12 15
100 ES
125 ES 150 ES
0 0 0 0
0 75 150 225 300 0 112 225 337 450 0 150 300 450 600 0 200 400 600 800
Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h)
36 60 70 80
Static Pressure (mm H2O)
24 24 48 44
200 250 315
160 ES
12 12 24 27
200 ES 315 ES
0 0 0 0
0 150 300 450 600 0 300 600 900 1200 0 350 700 1050 1400 0 400 800 1200 1600
Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h)
66 tecnologia dell’aria
ACCESSORIES - INDUSTRIAL SERIES -
Protection grille
Safety protection grille to protect appliance from any accidental contact. Made of in zinc plated steel. Fixing screws included.
Model Ref. øA B øa
TURBO 100 OW 608 2 100 20 4,5
TURBO 125 OW 609 0 125 20 4,5
A
AC/TURBO 150 OW 610 8 150 20 4,5
øa
TURBO 160 OW 629 8 160 20 4,5
AC/TURBO 200 OW 611 6 200 20 4,5
B
TURBO 250 OW 612 4 250 20 4,5
TURBO 315 OW 613 2 315 20 4,5
Backdraught shutter
Shutters open automatically with air flow. Zinc plated body. Aluminum shutters.
Model Ref. A øB
TURBO/TURBO PLAST 100 OW 622 3 77 94
TURBO/TURBO PLAST 125 OW 623 1 90 119
øB
AC/TURBO//TURBO PLAST 150 OW 624 9 102 144
TURBO/TURBO PLAST 160 OW 621 5 100 156
A
AC/TURBO 200 OW 625 6 127 194
TURBO250 OW 626 4 152 244
TURBO 315 OW 627 2 185 309
Duct clamp
Made of zinc plated steel. Neoprene rubber gasket.
Model Ref. øA B C øa
TURBO/TURBO PLAST 100 OW 614 0 105 40 20 7
TURBO/TURBO PLAST 125 OW 615 7 130 40 20 7
øA
øA
øa
105
A
tecnologia dell’aria 67
CENTRIFUGAL ANGLE FANS
AC
68 tecnologia dell’aria
CENTRIFUGAL ANGLE FANS
AC
• Centrifugal duct fans at angle to extract
air or non dusty fumes.
Dimensions
• Also suitable for application on machines
where a forced ventilation or air suction is A
required.
• Steel plated body protected by an epoxy-
based anticorrosive paint.
H
• Zinc plated steel blade statically and
dynamically balanced.
• Long life product due to motors on ball
B
bearings.
ØC
• In accordance with the essential require-
ments of 89/392/CE directive concerning
machines, and with European rules
G
EN 292 part and II, UNI EN 294 and IEC
E
204-1 and 2.
• Industrial Regulators available (see page 86). ØC
ØD
30
Static Pressure (mm H2O)
25
20
15
10
AC 200
AC 150
5
0
0 100 200 300 400 500 600 700 800 900
Flow rate (m3/h)
Technical Data
Motor Flow rate Max.Press. N° Nom. curr. in A. dB (A)
Model Ref. Motor W Hz RPM
protection m3/h mm H2O Poles at 230V at400V 2m
AC 150 2M OW 446 7 IP44 single-phase 360 14 2 140 50 0,55 - 62 2700
AC 150 2T OW 447 5 tecnologia
IP44 dell’aria
three-phase 360 14 2 140 50 0,54 0,31 62 2700
AC 200 2M OW 448 3 IP54 single-phase 620 27 2 350 50 1,5 - 70 2700
AC 200 2T OW 449 1 IP54 three-phase 830 27 2 350 50 1,68 0,95 70 2700
tecnologia dell’aria 69
BASIC CENTRIFUGAL FANS
CB
70 tecnologia dell’aria
BASIC CENTRIFUGAL FANS
CB
• Centrifugal duct fans to extract air and
fumes through medium/long sized ducts.
Dimensions
• Also suitable for application on machines
where a forced ventilation or air suction is
required.
• Steel plated body protected by an epoxy- Matching Flange
40
CB 220
CB 230
20
CB 210
0 200 400 600 800 1000 1200 1400 1600
Flow rate (m3/h)
Technical Data
Motor Flow rate Max.Press. Nom. Curr. in A. dB (A)
Model Ref. Motor N° Poles W Hz RPM
protection m3/h mm H2O at 230V at 400V 2m
CB 210 2M OW 410 3 IP22 single-phase 210 22 2 67 50 0,29 - 64 2800
tecnologia dell’aria
0
CB 210 2T OW 411 1 IP22 three-phase 210 22 2 67 50 0,26 0,15 64 2800
CB 220 2M OW 412 9 IP22 single-phase 380 35 2 115 50 0,49 - 68 2500
CB 220 2T OW 413 7 IP22 three-phase 380 35 2 110 50 0,36 0,21 68 2500
CB 230 2M OW 414 5 IP55 single-phase 1000 69 2 590 50 3,00 - 76 2750
CB 230 2T OW 415 2 IP55 three-phase 1000 69 2 400 50 1,40 0,80 76 2750
CB 240 2M OW 416 0 IP55 single-phase 1450 90 2 850 50 4,30 - 83 2750
CB 240 2T OW 417 8 IP55 three-phase 1450 90 2 800 50 2,73 1,57 83 2750
tecnologia dell’aria 71
SILENT CENTRIFUGAL FANS
CS
72 tecnologia dell’aria
SILENT CENTRIFUGAL FANS
CS
• Centrifugal silenced duct fans to extract
large air volumes and non dusty fumes. Dimensions
• Also suitable for application on machines
where a forced ventilation or air suction is
required.
• Steel plated body protected by an epoxy- Matching Flange
based anticorrosive paint.
• Zinc plated steel blade statically and
dynamically balanced for improved perfor-
mance.
• Particularly quiet in relation to the
remarkable performances.
• 4 poles induction motor with ball bear-
ings and IP55 motor protection.
• Impeller housing can be installed in any
different position with possibility of opposite
rotation (on request, see table page 57).
The standard product is supplied with Model A B øC D E F G H Y K I L M N O P Q R S T U z øa øb Kg
impeller housing position CCW 270. CS310 4M 96 94 180 91 127 122 247 - 63 42 183 - 319 - - 135 135 114 114 88 88 4 8,2 - 8
• Fans with specialised motors are avail- CS310 4T 96 94 180 91 127 122 247 - 63 42 183 - 319 - - 135 135 114 114 88 88 4 8,2 - 7
able on request i.e. Flameproof, Tropicalised,
High temperature, etc. CS320 4M 112 112 200 117 146 150 300 - 63 45 183 - 340 - - 152 152 126 126 100 100 4 8,2 - 7,5
• In accordance with the essential require- CS320 4T 112 112 200 117 146 150 300 - 63 45 183 - 340 - - 152 152 126 126 100 100 4 8,2 - 7
ments of 89/392/CE directive concerning CS330 4T 141 141 250 139 147 188 371 - 71 40 204 - 385 - - 191 191 165 165 134 134 4 8,2 - 13
machines, and with European Standards
CS340 4T 181 164 250 162 178 222 446 - 80 45 224 - 433 - - 225 235 195 205 161 170 4 8,2 - 18
EN 292 part I and II, UNI EN 294 and
IEC 204-1 and 2. CS350 4T 202 194 315 192 210 260 517 244 80 50 224 232 468 120 146 255 255 225 225 191 191 4 8,2 11 22
• Industrial regulators available (see page 86). CS360 4T 202 194 315 192 210 260 517 244 90 50 252 232 496 120 152 255 255 225 225 191 191 4 8,2 11 25
CS370 4T 253 221 355 210 230 250 571 278 100 49 305 266 575 150 176 284 305 254 275 213 244 4 10,2 11 38
For models CS 350, 360, 370 and 380:
• Mounted on rigid base support to make CS380 4T 299 249 400 280 300 370 744 350 112 60 324 325 633 170 185 310 360 280 330 241 295 8 9 11 75
installation easier.
40 120
Static Pressure
Static Pressure
100
30
CS 330 80
(mm H2O)
(mm H2O)
20 60
CS 320 CS 370 CS 380
40
10 CS 360
CS 310 20 CS 340 CS 350
0 0
0 200 400 600 800 1000 1200 1400 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Flow rate (m3/h) Flow rate (m3/h)
Technical Data
Motor Flow rate Max. Press. Nom.current in Amp. dB(A) Motor
Model Ref. Motor N° Poles W Hz RPM
protection mov. m3/h mm H2O at 230V at 400V 2 m Support
CS 310 4M OW 420 2 IP55 single-phase 500 16 4 200 50 1,0 - 64 1400 NO
tecnologia dell’aria
CS 310 4T OW 421 0 IP55 three-phase 500 16 4 160 50 1,0 0,59 64 1400 NO
CS 320 4M OW 422 8 IP55 single-phase 720 21 4 250 50 1,7 - 67 1400 NO
CS 320 4T OW 423 6 IP55 three-phase 720 21 4 250 50 1,7 1,0 67 1400 NO
CS 330 4T OW 424 4 IP55 three-phase 1500 38 4 500 50 1,9 1,1 70 1400 NO
CS 340 4T OW 425 1 IP55 three-phase 1900 47 4 1250 50 3,8 2,2 73 1400 NO
CS 350 4T OW 426 9 IP55 three-phase 2900 50 4 1900 50 5,3 3,1 76 1400 YES
CS 360 4T OW 427 7 IP55 three-phase 4100 60 4 2600 50 7,6 4,4 80 1400 YES
CS 370 4T OW 428 5 IP55 three-phase 5600 73 4 3200 50 10,0 5,8 84 1400 YES
CS 380 4T OW 429 3 IP55 three-phase 9100 105 4 4800 50 18,40 10,60 88 1430 YES
tecnologia dell’aria 73
STAINLESS STEEL CENTRIFUGAL FANS
CAI
74 tecnologia dell’aria
STAINLESS STEEL CENTRIFUGAL FANS
CAI
• Centrifugal duct fans to extract air and
fumes with chemical and corrosive agents
Dimensions
or for salt ambients.
• Body and impeller in AISI 304 stainless
steel.
• Also suitable for application on machines Matching Flange
• Fans with specialised motors are avail- CAI530 2M 97 98 180 92 128 124 248 63 38 191 327 135 135 114 114 88 88 8 4 8,5
able on request i.e. Flameproof, Tropicalised. CAI530 2T 97 98 180 92 128 124 248 63 38 191 327 135 135 114 114 88 88 8 4 7
• Maximum temperature of exhausted air CAI540 2M 112 110 200 116 145 150 300 71 40 213 363 150 150 125 125 105 105 8 4 9
70°C.
CAI540 2T 112 110 200 116 145 150 300 71 40 213 363 150 150 125 125 105 105 8 4 9
• In accordance with the essential require-
ments of 89/392/CE directive concerning
machines, and with European Standards 100
EN 292 part I and II, UNI EN 294 and
Static Pressure (mm H2O)
60
For models CAI 530 and CAI 540:
• Motor with ball bearings. 40
• IP55 protected. CAI 520
CAI 530
20
CAI 510
0
0 200 400 600 800 1000 1200 1400 1600
Flow rate (m3/h)
Technical Data
Motor Flow rate Max.Press. Nom.Cur. in A. dB (A)
Model Ref. Motor N° Poles W Hz RPM
Protection m3/h mm H2O at 230V at 400V 2m
CAI 510 2M OW 480 6 IP22 single-phase 210 22 2 67 50 0,29 - 64 2800
CAI 510 2T OW 481 4 IP22 three-phase 210 22 2 67 50 0,26 0,15 64 2800
CAI 520 2M OW 482 2 IP22 single-phase 350 33 2 115 50 0,49 - 68 2500
CAI 520 2T OW 483 0 IP22 three-phase 350 33 2 110 50 0,36 0,21 68 2500
CAI 530 2M OW 484 8 IP55 single-phase 1000 69 2 590 50 2,83 - 76 2750
CAI 530 2T OW 485 5 IP55 three-phase 1000 69 2 400 50 1,40 0,80 76 2750
CAI 540 2M OW 486 3 IP55 single-phase 1450 90 2 850 50 4,30 - 83 2750
CAI 540 2T OW 487 1 IP55 three-phase 1450 90 2 800 50 2,73 1,57 83 2750
tecnologia dell’aria 75
ACID PROOF CENTRIFUGAL FANS
CAA
76 tecnologia dell’aria
ACID PROOF CENTRIFUGAL FANS
CAA
• Centrifugal duct fans to extract fumes
with chemical and corrosive agents (sul-
Dimensions
phuric acid, nitric acid, trichloroethylene,
petrol, etc.).
• Also suitable for application on machines
where a forced ventilation or air suction is
required. Matching Flange
• Body and impeller in polypropylene with
nylon hub graphite treated.
• 2 poles or 4 poles induction motors with
ball bearings and IP 55 protection.
• Impeller housing can be installed in any
different position with possibility of opposite
rotation (on request, see table page 57)
(except the model 610).
The standard product is supplied with
impeller housing position CCW 360.
• Fans with specialised motors are avail- A B øC D E F G H Y K I L M N O P Q R S T U V øa øb n.holes
ø a Kg
Model
able on request i.e. Flameproof.
CAA 610 90 90 125 103 109 133 270 130 55 28 179 175 297 130 80 135 135 110 110 85 85 - 7,5 10 4 6
• In accordance with the essential require-
CAA 620 165 135 200 148 148 201 397 200 63 48 220 215 403 170 95 180 210 164 194 130 160 85 7 10 6+2 13
ments of 89/392/CE directive concerning
CAA630 205 165 250 185 180 240 503 250 80 45 245 255 455 175 125 228 266 200 240 160 200 80 7 10 8+2 19
machines, and with European Standards
EN 292 part I and II, UNI EN 294 and CAA640 245 205 315 222 218 293 590 310 90 65 282 234 552 175 155 265 306 241 282 195 240 100 9 12 6+4 31
IEC 204-1 and 2. CAA650 290 235 355 259 268 356 699 320 100 60 315 285 610 200 170 305 356 275 326 225 280 100 9 12 8+4 64
100 100
80 80
Static Pressure
Static Pressure
(mm H2O)
60
40 40
CAA 620.4T CAA 640.4T
CAA 630.4T
20 20
0 0
0 250 500 750 1000 1250 1500 1750 2000 0 1000 2000 3000 4000 5000 6000 7000
Flow rate (m /h) 3
Flow rate (m /h) 3
Technical Data
Motor Max air Max.Press. Nom. cur. A. dB (A) Motor
Model Ref. Motor N° Poles W Hz RPM
Protection mov. m3/h mm H2O at 230V at 400V 2 m Support
CAA 610 2T OW 440 0 IP55 three-phase 550 49 2 220 50/60 0,83 0,48 65 2800 YES
tecnologia dell’aria
CAA 620 2T OW 441 3 IP55 three-phase 2000 103 2 1200 50/60 3,45 2,0 68 2770 YES
CAA 620 4T OW 442 6 IP55 three-phase 1200 26 4 270 50/60 1,18 0,68 55 1400 YES
CAA 630 4T OW 443 4 IP55 three-phase 3000 43 4 800 50/60 2,60 1,5 64 1400 YES
CAA 640 4T OW 444 2 IP55 three-phase 4300 61 4 1300 50/60 4,3 2,5 65 1400 YES
CAA 650 4T OW 445 9 IP55 three-phase 6500 90 4 3300 50/60 10,4 6,0 70 1400 YES
tecnologia dell’aria 77
AXIAL EXPLOSION PROOF FANS
EB Ex-ATEX CESI approval N.03 ATEX 251
78 tecnologia dell’aria
AXIAL EXPLOSION PROOF FANS
EB Ex-ATEX CESI approval N.03 ATEX 251
• Explosion Proof certified Axial Fans for
wall or panel mounting to convey air direc- Dimensions
tly outside or through a short duct com-
pliance to ATEX Directive 94/9/EEC effecti- A F
ve in European Community from July 1st C B G
D
2003. These products are a safe choice for .
r.a
many applications in commercial and
øa
industrial environment where the risk of
explosion is high and where the surroun-
ding atmosphere contains gas, vapors or
steam highly inflammable.
ØE
• The whole product and not just the elec-
trical parts, has been certified by the Italian
Notified Body CESI with certify number
CESI n°03 ATEX 251.
• Reference norms: EN 13463-1: 2003
pr EN 14986: 2005.
• Fan group II, cat. 2 for gases, construction
safety c, max surface temp. T4 (135°C). Model A B C D E F G r.a. øa Kg
• Classified for zones 1 and 2. EB 25 4M Ex-ATEX 205 70 9 8 260 340 290 15 7 10
• This omologation has required specific EB 25 4T Ex-ATEX 205 70 9 8 260 340 290 15 7 9
safety tests and proper examinations on pro-
EB 30 4M Ex-ATEX 205 70 9 10 312 390 340 15 9 10
ducts to verify how the introduced solutions
have satisfied the essential Directive require- EB 30 4T Ex-ATEX 205 70 9 10 312 390 340 15 9 9
ments. EB 35 4M Ex-ATEX 205 85 10 12 365 460 410 15 9 11
• Body built in metal sheet epoxy painted . EB 35 4T Ex-ATEX 205 85 10 12 365 460 410 15 9 10
Impeller statically and dynamically balan- EB 40 4M Ex-ATEX 205 85 10 12 415 510 460 15 11 12
ced in high resistance polymeric material, EB 40 4T Ex-ATEX 205 85 10 12 415 510 460 15 11 11
V0 self extinguishing material with high
EB 50 4M Ex-ATEX 205 90 10 15 515 630 580 15 11 14
electrical conductivity properties.
EB 50 4T Ex-ATEX 205 90 10 15 515 630 580 15 11 13
• Available flow rates from 900 to 4500
m3/h.
• Motor IP55 protected supplied with cable • In accordance with the essential requirements of 89/392/CE Directive concerning
gland for cables from ø10 to ø11,5 mm. machines and with European Standards EN 292 part I e II, EN 294 and IEC 204-
1 and 2.
Technical Data
Flow rate Max press. N° Nominal curr. in A. dB (A)
Model Rif. Marking Motor W RPM
m3/h mm H2O Poles at 230V 400V 2m
EB 25 4M Ex-ATEX OW 354 3 II 2G c T4 single-phase 900 10 4 120 0,70 - 55 1460
EB 25 4T Ex-ATEX OW 357 6 II 2G c T4 three-phase 900 10 4 100 0,67 0,39 55 1460
EB 30 4M Ex-ATEX OW 355 0 II 2G c T4 single-phase 1500 8,3 4 140 0,75 - 59 1400
EB 30 4T Ex-ATEX OW 359 2 II 2G c T4 three-phase 1500 8,3 4 125 0,69 0,40 59 1430
EB 35 4M Ex-ATEX OW 356 8 II 2G c T4 single-phase 2250 10 4 160 0,80 - 62 1350
EB 35 4T Ex-ATEX OW 360 0 II 2G c T4 three-phase 2250 10 4 150 0,72 0,42 63 1400
EB 40 4M Ex-ATEX OW 350 1 II 2G c T4 single-phase 2900 9 4 180 0,85 - 65 1290
EB 40 4T Ex-ATEX OW 361 8 II 2G c T4 three-phase 2900 9 4 180 0,74 0,43 66 1350
EB 50 4M Ex-ATEX OW 351 9 II 2G c T4 single-phase 4500 14 4 210 1,00 - 70 1200
EB 50 4T Ex-ATEX OW 362 6 II 2G c T4 three-phase 4500 14 4 230 0,78 0,45 72 1270
tecnologia dell’aria 79
CENTRIFUGAL EXPLOSION PROOF FANS
CB-CS Ex-ATEX CESI approval n° N.03 ATEX 250
80 tecnologia dell’aria
CENTRIFUGAL EXPLOSION PROOF FANS
CB-CS Ex-ATEX CESI approval n° N.03 ATEX 250
• Explosion Proof Certified Centrifugal fans
to extract air and fumes through medium /
Dimensions
long sized ducts compliance to ATEX
Directive 84/9/EEC effective in European Matching Flange
Community from July 1st 2003.
• These products are a safe choice for many
applications in commercial and industrial
environment where the risk of explosion is
high and where the surrounding atmosphe-
re contains gas, vapors or steam highly
inflammable.
• The whole product and not just the elec-
trical parts, has been certified by the Italian
Notified Body CESI with certify number Model A B øC D E F G H Y K I L M N O P Q R S T U z øa øb Kg.
CESI n°03 ATEX 250. CB 230 2M Ex-ATEX 96 94 180 91 127 122 247 - 63 42 235 - 371 - - 135 135 114 114 88 88 4 8,2 - 13
• Reference norms: EN 13463-1: 2003 CB 230 2T Ex-ATEX 96 94 180 91 127 122 247 - 63 42 235 - 371 - - 135 135 144 114 88 88 4 8,2 - 13
CB 240 2M Ex-ATEX 112 112 200 117 146 150 300 - 71 45 265 - 422 - - 152 152 126 126 100 100 4 8,2 - 19
pr EN 14986: 2005.
CB 240 2T Ex-ATEX 112 112 200 117 146 150 300 - 71 45 265 - 422 - - 152 152 126 126 100 100 4 8,2 - 19
• Fan group II, cat. 2 for gases, construction
CS 310 4M Ex-ATEX 96 96 180 91 127 122 247 - 63 42 235 - 371 - - 135 135 114 114 88 88 4 8,2 - 13
safety c, max surface temp. T3 (200°C).
CS 310 4T Ex-ATEX 96 96 180 91 127 122 247 - 63 42 235 - 371 - - 135 135 114 114 88 88 4 8,2 - 13
• Classified for zones 1 and 2. CS 320 4M Ex-ATEX 112 112 200 117 146 150 230 - 63 45 235 - 392 - - 152 152 126 126 100 100 4 8,2 - 14
• This omologation has required specific CS 320 4T Ex-ATEX 112 112 200 117 146 150 230 - 63 45 235 - 392 - - 152 152 126 126 100 100 4 8,2 - 14
safety tests and proper examinations on pro- CS 330 4T Ex-ATEX 141 141 250 139 147 188 371 - 71 40 265 - 446 - - 191 191 165 165 134 134 4 8,2 - 21
ducts to verify how the introduced solutions CS 340 4T Ex-ATEX 181 164 250 162 178 222 446 - 80 45 276 - 485 - - 225 235 195 205 161 170 4 8,2 - 31
have satisfied the essential Directive require- CS 350 4T Ex-ATEX 202 294 315 192 210 260 517 244 80 50 276 232 520 120 146 255 255 225 225 191 191 4 8,2 11 37
ments. CS 360 4T Ex-ATEX 202 294 315 192 210 260 517 244 90 50 310 232 554 120 152 255 255 225 225 191 191 4 8,2 11 44
• Body built in metal sheet epoxy painted. CS 370 4T Ex-ATEX 249 221 355 210 230 250 571 278 100 49 380 266 650 150 176 284 305 254 275 213 244 4 10,2 11 67
Impeller statically and dynamically balan- CS 380 4T Ex-ATEX 299 249 400 280 300 370 744 350 112 60 400 325 709 170 185 310 360 280 330 241 295 8 9 11 91
ced in Aluminium. • Models CS 350, CS 360, CS 370 and CS 380 are already supplied with rigid base
• Models are available both in mono phase support to make installation easier.
and in three phase versions with 2 and 4 • Standard products are supplied with housing position CCW 270.
poles. These last products are able to assure • On request housing can be supplied in different position as defined by the table at
good performances and a low working noise page 57.
level. • In accordance with the essential requirements of 89/392/CE Directive concerning
• Available flow rates from 500 to 9100 m3/h. machines and with European Standards EN 292 part I and II, EN 294 and IEC
• Motor IP55 protected. 204-1 and 2.
Technical Data
Flow rate Max.Press. N° Nom. cur. A. dB (A)
Model Rif. Marking Motor W RPM
m3/h mm H2O Poles at 230V at 400V 2m
CB 230 2M Ex-ATEX OW 323 8 II 2G c T3 single phase 1000 69 2 450 2,5 - 76 2750
tecnologia dell’aria three-phase
CB 230 2T Ex-ATEX OW 319 6 II 2G c T6 1000 69 2 400 1 0,8 76 2750
CB 240 2M Ex-ATEX OW 324 6 II 2G c T3 single phase 1450 90 2 850 3,8 - 83 2800
CB 240 2T Ex-ATEX OW 320 4 II 2G c T6 three-phase 1450 90 2 800 2,3 1,3 83 2800
CS 310 4M Ex-ATEX OW 325 3 II 2G c T3 single phase 500 16 4 200 1 - 64 1400
CS 310 4T Ex-ATEX OW 326 1 II 2G c T6 three-phase 500 16 4 200 1 0,59 64 1400
CS 320 4M Ex-ATEX OW 327 9 II 2G c T3 single phase 720 21 4 250 1,5 - 67 1400
CS 320 4T Ex-ATEX OW 328 7 II 2G c T6 three-phase 720 21 4 250 1,75 1,00 67 1400
CS 330 4T Ex-ATEX OW 329 5 II 2G c T6 three-phase 1500 38 4 400 1,9 1,1 70 1400
CS 340 4T Ex-ATEX OW 321 2 II 2G c T6 three-phase 1900 47 4 1000 3,5 2,0 73 1400
CS 350 4T Ex-ATEX OW 330 3 II 2G c T6 three-phase 2900 50 4 1400 4 2,31 76 1400
CS 360 4T Ex-ATEX OW 322 0 II 2G c T5 three-phase 4100 60 4 1900 5,7 3,3 80 1400
CS 370 4T Ex-ATEX OW 331 1 II 2G c T5 three-phase 5600 73 4 2500 8,7 5,0 84 1400
CS 380 4T Ex-ATEX OW 338 6 II 2G c T5 three-phase 9100 105 4 4500 15,6 9,0 88 1400
tecnologia dell’aria 81
CENTRIFUGAL ROOF FANS 80°C
TX
82 tecnologia dell’aria
CENTRIFUGAL ROOF FANS 80°C
TX
• Centrifugal roof fans to extract air or
fumes directly or from ducts.
Dimensions
• Medium- high flow rates with pressure to øC
H
• Induction motor with external rotor on
ball bearings, IP 55 protection, class F insu-
F
lation and fitted with cooling impeller.
E
• Zinc-plated steel body and impeller, cover
øM (holes on base)
made in plastic reinforced by incorporated øL
= B =
fibreglass.
A
• Blade statically and dynamically balanced.
• Safety protection grille. Model A B øC E F H øL øM Kg
• In accordance with the essential require- TX 2 T/M 408 358 524 38 100 487 200 11 12
ments of 89/392/CE directive concerning
TX 4 T/M 408 358 524 38 141 527 210 11 13
machines, and with European Standards
EN 292 part I and II, UNI EN 294 and TX 6 T/M 408 358 524 38 153 539 233 11 15
IEC 204-1 and 2. TX 8 T/M 514 464 651 38 197 648 310 11 25
• Electronic regulators available (see page 86). TX 10 T/M 761 699 932 38 195 756 346 13 47
TX 12 T 761 699 932 38 272 833 422 13 62
Accessories: TX 14 T 860 798 1090 38 247 918 477 13 90
• See page 111.
TX 16 T 860 798 1090 38 302 973 538 13 110
25 48 60
20 40 50
Static Pressure
Static Pressure
Static Pressure
32 40
15
TX 6 24 30
(mm H2O)
(mm H2O)
(mm H2O)
10 TX 16
TX 2 16 20
TX 4 TX 10 TX 14
TX 8
5 8 10
TX 12
0 0 0
0 600 1200 1800 2400 0 1500 3000 4500 6000 0 4000 8000 12000 16000
Flow rate (m3/h) Flow rate (m3/h) Flow rate (m3/h)
Technical data
Motor Flow rate Max Press. Nom. curr. in A. dB (A)
Model Ref. Motor Volt 50 Hz N. Poles W RPM
Protection m3/h mm. H2O at 230V at 400V 2m
TX 2 T OW 756 9 IP55 three-phase 400/230 1050 16 4 180 0,78 0,45 48 1460
20 40 60
TX 2 M OW 757 7 IP55 single-phase 230 1050 16 4 180 1,20 - 48 1460
TX 4 T OW 753 6 IP55 three-phase 400/230 1250 22 4 180 0,78 0,45 52 1450
TX 4 M OW 759 3 IP55 single-phase 230 1250 22 4 180 1,20 - 52 1450
TX 6 T OW 760 1 IP55 three-phase 400/230 1900 27 4 190 0,86 0,5 56 1435
TX 6 M OW 761 9 IP55 single-phase 230 1900 27 4 190 1,30 - 56 1435
TX 8 T OW 763 5 IP55 three-phase 400/230 3500 45 4 450 2 1,2 63 1435
TX 8 M OW 762 7 IP55 single-phase 230 3500 45 4 450 2,3 - 63 1435
TX 10 T OW 764 3 IP55 three-phase 400/230 5000 52 4 900 2,2 1,6 64 1410
TX 10 M OW 776 7 IP55 single-phase 230 5000 52 4 900 5,2 - 64 1410
TX 12 T OW 765 0 IP55 three-phase 400/230 7000 36 6 750 3,4 2 61 960
TX 14 T OW 766 8 IP55 three-phase 400/230 11000 48 6 1100 5,2 3 63 960
TX 16 T OW 767 6 IP55 three-phase 400/230 15200 64 6 2200 8,6 5 66 960
tecnologia dell’aria 83
CENTRIFUGAL CHIMNEY FAN
TURBOCAMINO FOR HOT FUMES
84 tecnologia dell’aria
CENTRIFUGAL CHIMNEY FAN
TURBOCAMINO FOR HOT FUMES
286
• For all chimneys with insufficient up-
470
draught.
• Induction motor on ball bearings, IP 54
protection, class F insulation and fitted with
184
cooling impeller.
• Aluminium cover protects the product c 415
from atmospheric conditions. Ø 475
• Zinc plated steel impeller statically and
dynamically balanced.
• Safety protection grille. n° 8 holes ø 11
• In accordance with the essential require-
ments of 89/392/CE directive concerning
machines, and with European Standards 330
UNI 10615, UNI EN 292-1 e 2, UNI EN 357
294, CEI EN 60204-1. 415
• With fixing steel frame.
• Electronic regulator RGE OW3170
included. ø hole from 175 mm adjustable up to 225 mm.
• Industrial regulator available (see page 86).
20
Static Pressure (mm H2O)
15
10
0
0 300 600 900 1200
Technical Data
Motor Motor Flow rate Max Press. Nom. curr. in A dB (A) Weight
Model Ref. N. Poles W Hz RPM
Protection single-phase m3/h mm. H2O at 230V 2m Kg
TURBOCAMINO OW 554 8 IP54 220-240 1200 19,5 4 110 50/60 0,6 52,5 1400 15
tecnologia dell’aria 85
INDUSTRIAL CONTROLLERS
RGT 1 RGT 2
RGM 2 RGM 4
86 tecnologia dell’aria
INDUSTRIAL CONTROLLERS
INDUSTRIAL CONTROLLERS Dimensions
RGM and RGT
• Complete range of speed controllers for the
O.Erre industrial fan assortment.
• Range of 4 models : 2 single-phase and 2 (RGM 2 CST)
B C
tri-phase.
IP55
• The RGM4, RGT1 and RGT2 models are
auto-transformed with a 3 positions opera-
ting selector.
• The RGM2 is an electronic controller
which allows a constant speed control.
• Casing made of thermo-resistant plastic A
material with an excellent protection again-
st corrosive agents. 1
2
3
• IP 55 protection grade.
• All models are equipped with a warning
operating light.
• All models are equipped with an ON /
OFF switch.
• All models are equipped with an adaptable
cable gland, suitable for all kind of wire sizes.
Model Ref. A B C Weight Imax
• Suitable for wall installation.
RGM 2 OW 300 6 108 108 100 0,2 1,6 A
STAR/DELTA SWITCH CONTROL- RGM 4 OW 302 2 250 190 140 5 4A
tecnologia dell’aria 87
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
RC S
88 tecnologia dell’aria
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
RC S
Functional design and “slim” grill are the
Dimensions
main features of the new product range
which have been manufactured to meet all
markets requirements ensuring good perfor-
mance, silent running and fast/easy instal-
lation.
Main features
B
• Axial fans for heat dissipation in enclosu-
E
res supplied with filter of two different pro-
tection grades (IP 44, IP 54), according to
the cabinet specifications.
• Tests of IP protection performed on the
product installed and working, using the kit C
D
A
filter + grille G S correspondent.
• Tests performed in accordance with
European Standards EN 60529, EN Model A B C D øE Kg
60335-2-80. RC 12.15 S 148 148 4,5 67 120 0,6
• The actual guarantee of the IP54 protection RC 14.25 S 250 250 5,5 113 147 1,1
grade is certified by reliable laboratories and RC 20.32 S 318,5 318,5 5,5 160 204 3
available upon request.
• Quick and functional assembly of the fan
on the electrical cabinet through elastic click
hooks and gasket pre-installed on the product.
• Operating temperature: –20°C +50°C.
• Electrical connection through terminal
board.
• Motor with ball bearing to assure long life
of the fan assembly.
• Motor made in ABS self extinguishing
material, grey colour RAL 7032.
• Recyclable materials.
• Easily removable grille to allow quick
replacement of the filter. Model A B C D øE Kg
• Slotted external grilles allow drainage of RC 12.15 S + D 15 S 148 148 25,5 46 120 0,7
condensation.
• Fans in accordance with Standards CEI
17-13/1 (IEC 439-1), EN 60335-2-80.
The performances have been attested by IMQ laboratories.
Technical Data
RC 12.15 S RC 12.15 S RC 14.25 S RC 14.25 S RC 20.32 S RC 20.32 S
Model
IP 44 IP 54 IP 44 IP 54 IP 44 IP 54
Ref./Cod. 110-120 V OW 909 4 OW 933 4 OW 914 4 OW 935 9 OW 911 0 OW 934 2
Ref./Cod. 220-240 V OW 921 9 OW 996 1 OW 923 5 OW 998 7 OW 922 7 OW 997 9
Hz 50/60 50/60 50/60 50/60 50/60 50/60
W 20 20 30 30 35 35
Nom. curr. in Amp. 0,2/0,1 0,2/0,1 0,4/0,2 0,4/0,2 0,3/0,15 0,3/0,15
dB (A) 2 m 42 42 50 50 63 63
Flow rate m3/h 55 50 150 130 450 400
Flow rate m3/h (w/out filter) 100 250 520
tecnologia dell’aria 89
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
FILTERS & GRILLES RC S
Performances RCS + G
RC 12.15 S RC 12.15 S RC 14.25 S RC 14.25 S RC 20.32 S RC 20.32 S
Model + G 15 S + G 15 S + G 25 S + G 25 S + G 32 S + G 32 S
IP 44 IP 54 IP 44 IP 54 IP 44 IP 54
Model A B øC
RC 12.15 S 125 x 125 131 x 131 4,5
RC 14.25 S 223x223 230 ÷ 234 x 230 ÷ 234 4,5
øC
E
Thermostat
Automatically controls the ventilation inside the cabinet.
Temperature regulation: 20 °C ÷ 60 °C.
78 mm
Spacer
mm
Accessory suitable just for model RC 12.15 S which allows movement of the fan assem-
bly towards the outside reducing the internal sizes of the fan to better satisfy any instal-
lation requirements.
Made in self extinguishing material V0 conforming to UL94, the spacer is click fixed
on the support while the fan assembly is fixed on the cabinet through the screws pro-
vided.
90 tecnologia dell’aria
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
SYSTEMA
Main features Functioning
• Ventilation systems designed for cooling
electrical cabinets and enclosures. The outside air is filtered and drawn
• SYSTEMA is composed of: 1) Fan Kit into the lower section of the electrical
including RC fan, grille and filter. 2) Grille for cabinet. After cooling the warm air is
air exhaust. 3) Filter for exhaust grille. drawn out through a grille which is
• SYSTEMA maintains the original protec- situated at the top of the cabinet.
tion grade IP43 o IP44 o IP54 o IP55, of the This process generates considerable
electrical cabinet conforming to Standard advantages in terms of life and quality
EN 60529. of the functioning of the fans.
• The effective guarantee of the protection
grade has been attested by reliable laborato- The internal over-pressure prevents the
possible entry of dust into the cabinets
ries (IMQ, INTEK) who have performed
ensuring better performance of the
tests on products installed and working.
electrical and electronic equipment fit-
• Grey colour RAL 7032. ted within.
Performances
SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA SYSTEMA
Model
10.13 IP44 12.13 IP44 12.13 IP54 14.25 IP43 14.25 IP44 14.25 IP54 14.32 IP44 15.32 IP55 20.32 IP44 20.32 IP55
Ref./Cod. 110-120 V OW 983 9 OW 984 7 OW 973 0 OW 985 4 OW 986 2 OW 993 8 OW 987 0 OW 988 8 OW 989 6 OW 990 4
Ref./Cod. 220-240 V OW 975 5 OW 976 3 OW 974 8 OW 977 1 OW 978 9 OW 992 0 OW 979 7 OW 980 5 OW 981 3 OW 982 1
Flow rate m3/h 24 42 20 115 110 85 130 58 360 136
tecnologia dell’aria 91
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
RC
92 tecnologia dell’aria
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
RC
Main features Dimensions
• Axial fans for heat dissipation in enclosu-
res supplied with grille, without filter.
• Motor mounted on ball bearing to allow
30.000 hours of continuous operation.
• Fans completely made in self extingui-
shing material V0, resistant to temperature
B
from -20°C to +50°C.
E
• The fan assembly RC maintains the origi-
nal protection grade IP43, IP44, IP54, of
the electrical cabinet conforming to
Standard EN 60529.
• Quick installation, easily removable grille to
C D A
allow the maintenance of the filters whilst the
fan is operating.
• Slotted external grilles allow drainage of Model A B C D øE Kg
• Fans in accordance with Standards CEI 17- RC 12.13 130 140 24 74 114 0,6
13/1 (IEC 439-1), EN 60335-2-80. RC 14.25 256 256 29 91 147 1,2
• Grey colour RAL 7032. RC 14.32 323 322 34 145 147 1,6
RC 15.32 323 322 34 145 147 2,6
RC 20.32 323 322 34 140 204 3
Technical Data
Model RC 10.13 RC 12.13 RC 14.25 RC 14.32 RC 15.32 RC 20.32
tecnologia dell’aria 93
VENTILATION FOR ELECTRICAL CABINETS AND THERMAL MANAGEMENT
FILTERS & GRILLES RC
Drilling scheme for Fan Assembly and Grilles
A A
C C
C
D F
F G
B
A
E
ø
B
E
D
B
øE
94 tecnologia dell’aria
SELECTION CHART FOR INSTALLATION
3000
2500
2000
1500
1000
900
Heat dissipation (Watt)
∆T T 3 40K
800
∆T 30K K
5
∆ T
∆
700
25K
600
K
20
K
∆T
500
15
∆T
400
10
∆T
300
5K
∆T
200
100
10 20 30 40 50 60 70 80 90 100 200 300 400 500 600 700
The correct air capacity for appropriate selection of the fan assembly can be determined by consulting the above diagram.
• First determine the following :
- The thermal power dissipated by the electronic equipments.
- The maximum temperature allowed inside the cabinet or enclosure.
- The maximum ambient temperature forseen outside the cabinet or enclosure.
• Calculate the ∆T as the difference between the two temperatures.
• The point at which the horizontal frame line (green) of the dissipated thermal power bisects the diagonal line (blue) of the tem-
perature difference (∆T) will show the vertical line (red) indicating the air capacity required for the necessary dissipation in m3/h.
• Choose the correct fan on the performance table.
Natural heat loss through the cabinet walls should be taken into account.
In order to compensate the reduction of flow rate caused by dirty filters, an increase of 20% to the obtained value is advisable.
tecnologia dell’aria 95
EXTRA SLIM AXIAL FANS
RQ
96 tecnologia dell’aria
EXTRA SLIM AXIAL FANS
RQ
Main features Dimensions
• Extra slim axial fans in direct current
(DC) and alternated current (AC).
• Induction motor fitted with ball bearings.
• Impedence protection on models RQ 50 and
RQ 160. Thermal protection on model RQ 370.
• Specially designed for fitting in electrical
and electronic equipment cabinets and provide
the necessary cooling where spaces for fans are
minimal.
• Body made in nylon reinforced with fiber-
glass for DC models, die-cast aluminium for B øa D
AC models.
A C
• Impeller made in nylon reinforced with
fiberglass.
• Maximum ambient temperature ranging Model ø Foro A B C D øa Kg
from -10°C to +70°C. RQ 50 AC 78 80 71,4 38 3,4 4,3 0,27
• In accordance with the essential requirements RQ 50 DC 78 80 71,5 25 4 4,3 0,1
of the 89/392/CE directive concerning machi- RQ 160 AC 117 119 105 38 3,2 4,3 0,55
nes, and with European Standards EN 292. RQ 160 DC 117 119 105 25,5 5 4,3 0,22
part I and II, EN 294 and IEC 204-1 and 2.
Accessories øa
Filter in poliu-
rethane with grille
in polypropylene.
A
C
Model Ref.
RQ 160 OW 643 9
D
B E
Model Ref.
RQ 50 OW 108 3
RQ 160 OW 109 1
Model ø Foro A B C D E øa Kg
RQ 370 OW 642 1
RQ 370 AC 148 172 150 162 6 38 4,5 0,75
Protection Grille • The DC models are supplied with cables for a direct electrical connection, whilst
Safety Grille for fan protection against solid
the AC models are supplied with a terminal electrical block.
and external bodies.
Technical Data
RQ 50 RQ 50 RQ 160 RQ 160 RQ 50 RQ 50 RQ 160 RQ 160 RQ 370 RQ 370
Model DC
DC DC DC AC AC AC AC AC AC
Ref. OW 585 2 OW 586 0 OW 587 8 OW 588 6 OW 404 6 OW 401 2 OW 405 3 OW 402 0 OW 589 4 OW 584 5
Supply voltage 12 V 24 V 12 V 24 V 110-120 V 220-240 V 110-120 V 220-240 V 110-120 V 220-240 V
Max Flow rate m3/h 60 60 184 184 45 45 138 138 318 318
Hz - - - - 50/60 50/60 50/60 50/60 50/60 50/60
W 2 2 4 4 9 10 15 15 35 35
Nom. curr. in A. 0,17 0,08 0,40 0,18 0,14 0,07 0,22 0,12 0,38 0,19
dB (A) 2 m 26 26 33 33 31 31 34 32 52 48
rpm 3000 3000 2950 2950 2700 2700 2400 2400 2700 2700
tecnologia dell’aria 97
GUIDE TO VENTILATION
Number of fans Possibilities of use
to be installed
The number of ceiling fans to be installed
on large surfaces depends on:
• m2 of surfaces: the number of fans is
directly proportional to the surface;
• distance between ceiling and floor: the
number of fans is inversely proportional
to such a distance.
• fan power and the diameter of their
blades;
• other factors that are difficult and
complicated to calculate, such as the
conformation of the room and walls,
ambient humidity, furnishing and
equipment in the room, outlets, etc.
Direct ventilation
98 tecnologia dell’aria
GUIDE TO VENTILATION
Use of fans Graph for surface of 1000 m2
in winter period
It is well-known that the temperature of
air in a room is higher in the highest layer
(closest to the ceiling) and lower in that
near the floor.
The higher the room, the greater the differ-
ence between the floor and the ceiling, and
the greater the volume of air to be heated to
obtain the desired temperature at the aver-
age height of a person.
Ceiling fans, which in summer give a fresh,
cooling sensation by evaporating humidity
from the surface of the body, in winter
allow significant savings to be made on
heating costs.
These fans push the hot air downwards
making the ambient temperature uniform.
The advantages are particularly consider-
able with industrial installations where
there is a large distance between the floor
and ceiling.
The graph shows how the percentage of
energy saved is calculated in relation to the
difference in temperature between the floor
and ceiling.
Example: there is a 12,5% saving with 3
degrees difference and 24% saving with 8
degrees. All the values indicated refer to
thermally insulated environments.
tecnologia dell’aria 99
CEILING FANS OASIS
Accessories: Dimensions cm
• Transmitter TRM 3
• Receiver RCV 3
• Built in kit for speed controller
• 5 speed controller RG5 OASIS
+ reversibility
B
C
• Electronic controller RGE + reversibility
(this controller operates 4 models simul-
taneously)
A
Model øA B C
R 90 - 3KR 90 90 32 39
R 120 - 3KR 120 120 32 39
R 140 - 3KR 140 - R IPX4 140 32 39
R 150 - 3KR 150 150 32 39
4KR 120 120 32 39
4KR 140 140 32 39
Technical Data
Nominal Voltage Flow rate
Model Ref. W Weight kg
and Frequency m3/h
R 90 OW 240 4 60 230V 50/60Hz 8400 3,9
R 120 OW 241 2 60 230V 50/60Hz 13800 4,0
R 140 OW 242 0 60 230V 50/60Hz 15600 4,1
R 150 OW 243 8 60 230V 50/60Hz 16000 4,1
Technical Data
Nominal Voltage Flow rate
Model Ref. W Weight kg
and Frequency m3/h
3KR 90 OW 245 3 60 230V 50/60Hz 8.000 5,0
3KR 120 OW 246 1 60 230V 50/60Hz 13.500 5,1
3KR 140 OW 247 9 60 230V 50/60Hz 15.000 5,2
3KR 150 OW 248 7 60 230V 50/60Hz 16.000 5,2
SILVER
Accessories:
• Transmitter TRM 3 • Electronic Controller 12 Volt SELV • White - silver - golden Light Kit
• Receiver RCV 3 • 5 speed controller RG5 OASIS • Built in kit for speed controller
Technical Data
ø Flow rate Nominal Voltage Weight
Kind Model Ref. Blades Colour W
Blades m3/h and Frequency kg
4KR 120 Silver Junior OW 250 3 White Aluminium 120 cm White - Silver 10.000 80 230V 50/60Hz 5,2
4KR 140 Silver Senior OW 251 1 White Aluminium 140 cm White - Silver 15.600 80 230V 50/60Hz 5,3
4KR 140 Marilyn OW 252 9 Wood 130 cm White - Golden 10.000 80 230V 50/60Hz 5,4
4KR 140 Colonial OW 254 5 Wood 130 cm Brown - Golden 10.000 80 230V 50/60Hz 5,4
4KR 140 Naomi OW 253 7 Black Aluminium 140 cm Black - Silver 15.600 80 230V 50/60Hz 5,3
NAOMI
MARILYN COLONIAL
Light kit
Created to use a traditional 150 W bulb lamp
low consumption fitted with E 27 connector.
Matched with colour of ceiling fan.
Silver Light kit Golden Light kit
Shanks
New attractive design tuned with classical
decoration.
Suitable for any furnishing requirement.
Accessories:
• 5 speed controller RG5 OASIS + reversibility
• Reversible electronic controller RGE
• Built in kit for speed controller
A
Electromagnetic Compatibility (EMC)
Standards.
• In shining ABS material.
Model A B
RCV 3 123 ø 140
• Can be fitted to any ceiling fan with a
downrod of diameter 19, 2 mm - 3/4”.
Individual fans or
different groups of
fans can be con-
Three LEDS indicate the following functions: trolled by a single
a red LED that the fan is switched on and radio transmitter
working, a green LED the reversibility and (for details see sepa-
another red LED the reception of a transmit- rate TRM 3 entry).
ter command.
Model Ref.
RCV 3 OW 917 7
B
up in order to avoid interferences with other
users having installed similar products
working on 433,92 Mhz frequency.
• In accordance with Electromagnetic
Compatibility (EMC) Standards. A C
Model A B C
TRM 3 42 115 14
Model Ref.
TRM 3 OW 916 9
Gravity shutter
D
A C E
Rain proof gravity shutter to prevent the incoming of air when
the fan is switched off.
Shutters open automatically with air flow when the fan is work-
ing, available in different sizes.
To be fitted on the external wall.
A
B
Model Ref. A B C D E
GRAVITY SHUTTER ø 10 OW 801 3 149 ø 99 25 70 45
GRAVITY SHUTTER ø 12 OW 803 9 149 ø 119 25 70 45
Grille C
Rain proof grille to be fitted on the external wall, available in A D
different sizes.
Completely made in technopolymer.
Model Ref. A B C D
B
A
GRILLE ø 10 OW 800 5 154 ø 99 43 18
GRILLE ø 12 OW 802 1 154 ø 119 43 18
GRILLE ø 15 OW 907 8 208 ø 155 52 28
Locking ring
C Window or panel kit.
A
B
Model Ref. A B C
LOCKING RING ø 10 OW 814 6 100 130 40
LOCKING RING ø 12 OW 815 3 120 150 40
Model Ref. A B C
C
AIR FLOW DEFLECTOR ø 10 OW 699 1 90 100 56
AIR FLOW DEFLECTOR ø 12 OW 662 9 110 120 65
Timertronic
The Timetronic is an electronic timer designed to delay the turn-off operation of any
M1 M2 L N Ls 14’
fans with power as high as 200W. It can be installed inside switch boxes or unat-
M tended connection boxes.
41
32.51
3’ 25’
M1 M2 L N Ls
Electrical connections and timing adjustments can be done without the need to
open the case.
The delay time is adjustable from 3 to
39.5 16.3 25 minutes; no delay is added when
the fan starts.
Model Ref.
TIMERTRONIC OW 340 2
Timermatic
22 19 Self adjusting proportional timer from 4 to 13 minutes approx.
It can be used with any fan up to a max power of 200 W.
28
N L
85
~
Fan
Timer M
Can be installed: Matic
- in a switch box Model Ref.
- in a junction box SW
TIMERMATIC OW 339 4
- inside the appliance
Lamp
105
125 52
Model Ref.
RG 5 AR OW 315 4
RG E OW 317 0
TRM3 RCV3
Model Ref.
12V SELV ELECTRONIC CONTROLLER OW 910 2
Controllers
RG 5 Oasis is suitable to control the ON/OFF function, 5 speeds,
reversibility and the ON/OFF of the light when the light Kit is
installed. RG E, suitable for industrial environments only, is an
electronic controller able to vary the speed continuosly and can
drive the reversibility funcions of the fans. Both controllers can be
recessed through a dedicated accessory.
Model Ref.
RG 5 OASIS OW 316 2
RG E OW 317 0 RG 5 OASIS RG E
A
B
Frame made of technopolymer.
Model Ref. A B C øa øa
B
EC 20 OW 594 4 310 268 52 9 C
A
EB 25 - EC 25 OW 595 1 367 325 52 9
EB 30 - EC 30 OW 596 9 424 382 52 9
EB 35 - EC 35 OW 597 7 481 439 52 9
EB 40 - EC 40 OW 598 5 538 496 52 9
EB 50 - EC 50 OW 599 3 652 610 52 9
EB 60-70 - EC 60 OW 600 9 823 781 52 9
C øA
øB Model Ref. øA øB C
CAA 640 OW 668 6 250 315 147
B
Model Ref. øA B C D
CAA 610 OW 630 6 125 105 90 90 C D
Model Ref. A B C
B C
CAA 610 OW 677 7 90 90 90
CAA 620 OW 678 5 160 165 135
CAA 630 OW 679 3 208 205 165
CAA 640 OW 680 1 260 245 205
CAA 650 OW 681 9 260 290 235
Model Ref. A B C D E D
CAA 630 C
OW 669 4 230 165 265 205 274
E
CAA 640 OW 670 2 263 205 303 245 332
CAA 650 OW 671 1 305 235 355 290 372