Professional Documents
Culture Documents
Daikin Applied Maverick II Mps 15 50 Ton
Daikin Applied Maverick II Mps 15 50 Ton
2 IM 1058-5
General Information
General Information
This manual provides general information about the “F” Unit Nameplate
vintage Daikin McQuay Commercial Packaged Rooftop Unit
model MPS. In addition to an overall description of the unit, The unit nameplate is located on the outside of the main
it includes mechanical and electrical installation procedures, control box door. It includes the unit model number, serial
commissioning procedures, sequence of operation number, electrical characteristics, and refrigerant charge.
information, and maintenance instructions.
The MicroTech® III rooftop unit controller is available on Hazard Identification Information
“F” vintage rooftop units. For a detailed description of the
MicroTech III components, input/output configurations, field DANGER
wiring options and requirements, and service procedures, Dangers indicate a hazardous situation which will result in
see OM 920. For operation and information on using and death or serious injury if not avoided.
programming the MicroTech III unit controller, refer to the
appropriate operation manual (see Table 1.
WARNING
For a description of operation and information on using
Warnings indicate potentially hazardous situations, which can
the keypad to view data and set parameters, refer to the result in property damage, severe personal injury, or death if
appropriate program-specific operation manual (see Table 1). not avoided.
Design vintage
• 15F
• 20/26G
• 30–50 F
IM 1058-5 3
Mechanical Installation
Mechanical Installation
Service Clearance
Allow service clearances as approximately indicated in
Figure 1. Also, Daikin McQuay recommends providing a
roof walkway to the rooftop unit as well as along each side of
the unit that provides access to most controls and serviceable
components.
* 62-75 Ton
Fan and Gas/Electric/Hot Water
Energy Recovery Wheel Heaters can be removed from
(ERW) Fan Assembly either side
Fan
Assembly
(removal from
this side only)
15-50 Ton
B
Optional Hot
Water Heat
(removal from
this side only*)
60.00
A
(1524 mm)
4 IM 1058-5
Mechanical Installation
Mechanical Installation
IM 1058-5 5
Mechanical Installation
Assembly Instructions
Assembly of a typical roof curb is shown in Figure 2.
1. Set curbing parts A thru G per dimensions shown 4. Position curb assembly over roof openings. Curb must
over roof opening or on a level surface. Note location be level within 0.25 inches from side to side and 1.50
of supply air opening. Check alignment of all mating inches over its length. Check that top surface of curb is
screw holes. flat with no bowing or sagging.
2. Screw curbing parts together using fasteners provided. 5. Weld curb assembly in place. Caulk all seams
Leave all screws loose until curb is checked to be square. watertight. Remove backing from 0.25 × 1.50 wide
3. Square entire curbing assembly and securely tighten all gasket and apply to surfaces shown by crosshatching.
screws. 6. Check that electrical connections are coordinated.
6 IM 1058-5
Mechanical Installation
IM 1058-5 7
Mechanical Installation
71.38
87.25 [1813 mm]
[2216 mm]
(INSIDE CURB)
2.00
[51 mm] 1.25 1.63 1.00
[32 mm] TYP [41 mm] [25 mm]
63.69
[1610 mm] 19.00
93.70 [483 mm]
[2380 mm]
171.18 (INSIDE CURB)
[4348 mm]
PLAN VIEW
2.00
[51 mm]
1.00
[26 mm]
3.75
[95 mm] 0.38
1.00
[26 mm] [9.7 mm] F
0.38
[9.7 mm]
2.00
[51 mm] 23.86
[606 mm]
KNOCKOUT DETAIL
8 IM 1058-5
Mechanical Installation
2.00
[51 mm]
71.38
[1813 mm]
87.25
[2216 mm]
(INSIDE CURB)
PLAN VIEW
2.00
[51 mm]
1.00
[25 mm]
3.75
[95 mm] 0.38
[9.7 mm]
F
2.00 0.38
[51 mm] [9.7 mm]
28.92
[735 mm]
IM 1058-5 9
Mechanical Installation
10 IM 1058-5
Mechanical Installation
IM 1058-5 11
Mechanical Installation
12 IM 1058-5
Mechanical Installation
IM 1058-5 13
Mechanical Installation
Table 4: Weight Distribution Locations (see Figure 10) Table 5: Weight Distribution Locations (see Figure 11)
Unit Distance Unit Distance
(tons) L1 L2 L3 L4 (tons) L1 L2 L3
040–050 42.2 66.6 58.3 60.9 015–035 35.5 62.0 52.0
040–050 40.0 69.0 89.0
Table 7: Heat Section Weights Table 10: Additional Weights - Motors/Exhaust Fans
Weights (lbs)
(015–020)
Unit
(tons) High Gas Low Gas Electric Hot Water Additional Motor Unit Additional Exhaust
Heat Heat Heat Heat HP Weight (lbs) (tons) Fan Weight (lbs)
015 200 100 120 195 1 0 15–20 150
017 200 100 120 195 1.5 9
020 200 100 120 195 2 9
026 270 135 270 291 3 32
030 270 135 270 291 5 43
035 270 135 270 291
040 350 175 350 307 Table 11: Additional Weights - Motors/Exhaust Fans
050 350 175 350 307 (026–050)
Table 8: Curb Weights HP Additional Motor
Weight (lbs) Unit (tons) Additional Exhaust
Fan Weight (lbs)
Table 9: Energy Recovery Section Weights Table 12: Additional Weights for 6-Row DX Coil and
HGRH Coil
Unit Size (tons) Weight (lbs)
015–020 1200 Unit Size Weight (lbs)
026–035 1540 (tons) 6 Row DX HGRH
040–050 1000 15–20 118 70
26–35 164 82
40 187 92
50 231 92
14 IM 1058-5
Mechanical Installation
Figure 10: Rigging the Unit (MPS 026– 035 Example) Condensate Drain Pipe Connection
The unit is provided with a 1" male NPT condensate drain
connection. For proper drainage, level the unit and drain pan
side to side and install a P-trap.
Figure 12 shows the layout of the condensate drain
connection. The distance from the drain pan outlet to the
horizontal run of the P-trap should be a distance of twice the
static pressure in the drain pan.
Example: If the static pressure as measured in the drain pan
is 1.5", then the distance between the drain outlet and the
horizontal run should be 3".
Draining condensate directly onto the roof may be acceptable;
refer to local codes. Provide a small drip pad of stone, mortar,
wood, or metal to protect the roof against possible damage.
If condensate is piped into the building drainage system, pitch
the drain line away from the unit a minimum of 1/8" per foot.
The drain line must penetrate the roof external to the unit.
Refer to local codes for additional requirements. Sealed drain
lines require venting to provide proper condensate flow.
Where the cooling coils have intermediate condensate pans
on the face of the evaporator coil, copper tubes near both
Figure 11: Rigging the Unit (MPS 040–050 Example) ends of the coil supply drainage to the main drain pan. Verify
G the tubes are in place and open before putting the unit into
E operation.
A C
Periodically clean to prevent microbial growth/algae buildup
from plugging the drain and causing the drain pan to
overflow. Clean drain pans to prevent the spread of disease.
H Cleaning should be performed by qualified personnel.
F
WARNING
D L4
Drain pans must be cleaned periodically. Material in uncleaned
L3
B drain pans can cause disease. Cleaning should be performed
by qualified personnel.
L2
L1
Figure 12: Condensate Drain Connection
IM 1058-5 15
Mechanical Installation
CAUTION
Transportation, rigging, or maintenance can damage the
unit’s weather seal. Periodically inspect the unit for leakage.
Linkage Standing moisture can promote microbial growth, disease, or
damage to the equipment and building
Installing Ductwork
On vertical-supply/vertical-return units, if a Daikin McQuay
Actuator
roof curb is not used, the installing contractor should make an
airtight connection by attaching field fabricated duct collars
to the bottom surface of the unit’s duct opening. Do not
support the total weight of the duct work from the unit. See
roof curb layouts in Figure 3 on page 7, Figure 4 on page
8 or Figure 5 on page 9.
WARNING
Mold can cause personal injury. Materials such as gypsum
wall board can promote mold growth when damp. Such
materials must be protected from moisture that can enter units
during maintenance or normal operation.
16 IM 1058-5
Mechanical Installation
Installing Duct Static Pressure Sensor Taps Figure 14: Static Pressure Tubing Knockout Location
For all VAV units, duct static pressure taps must be field
installed and connected to the static pressure sensor 1 (SPS1)
in the unit. Sensor SPS1 is standard on VAV units and is
located in the main control panel.
Carefully locate and install the duct static pressure sensing
tap. Improperly locating or installing the sensing tap causes
unsatisfactory operation of the entire variable air volume
system. Below are pressure tap location and installation
recommendations. The installation must comply with local
code requirements.
1. Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
2. Use different colored tubing for the duct pressure (HI)
and reference pressure (LO) taps, or tag the tubes.
Figure 15: Duct Static Pressure Sensing Tubing
Daikin McQuay recommends 3/16" ID tubing.
Installation Main Control Panel Condenser Section
3. Locate the duct pressure (HI) tap near the end of a long
duct to ensure that all terminal box take-offs along the
run have adequate static pressure.
4. Locate the duct tap in a nonturbulent flow area of the
duct. Keep it several duct diameters away from take-off
points, bends, neckdowns, attenuators, vanes, or other
HI Line
irregularities. LO Line
SPS1
Roof
5. Use a static pressure tip (Dwyer A302 or equivalent) or
the bare end of the plastic tubing for the duct tap. (If the Remote Sense Point
duct is lined inside, use a static pressure tip device.)
6. Install the duct tap so that it senses only static pressure To Sensor Ductwork
(Remote Location)
(not velocity pressure). If a bare tube end is used, HI Input
Rubber
it must be smooth, square (not cut at an angle) and Grommet
perpendicular to the airstream (see Figure 15). To Sensor
LO Input
Tubing Extends
7. Locate the reference pressure (LO) tap near the duct Through Approx. 1/8”
pressure tap within the building. If the tap is not connected
to the sensor, unsatisfactory operation will result.
8. Route the tubes through the curb and feed them into the Pressure Sensing
unit through the knockout in the bottom of the control Tubing
panel (see Figure 14). Connect the tubes to appropriate
barbed fittings (on SPS1) in the control panel. (Fittings
are sized to accept 3/16" ID tubing.)
IM 1058-5 17
Mechanical Installation
Installing Building Static Pressure Sensor Figure 16: Outdoor Static Pressure Tubing Installation
Taps
If a unit has building static pressure control capability, you
must field install and connect static pressure taps to the static
pressure sensor SPS2 in the unit. This sensor is located at the
bottom of the main control panel next to SPS1.
Carefully locate and install the two static pressure sensing
taps. Improper location or installation of the sensor taps
causes unsatisfactory operation. Below are pressure tap
location and installation recommendations for both building
envelope and lab, or “space within a space” pressure control
applications. The installation must comply with local code
requirements.
CAUTION
Fragile sensor fittings. If you must remove tubing from a
pressure sensor fitting, use care. Do not use excessive force Lab Pressurization Applications
or wrench the tubing back and forth to remove or the fitting
can break off and damage sensor. 1. Install a “T” fitting with a leak-tight removable cap
in each tube near the sensor fitting. This facilitates
Building Pressurization Applications connecting a manometer or pressure gauge if testing is
required.
1. Install a tee fitting with a leak-tight removable cap
in each tube near the sensor fitting. This facilitates 2. Use different colored tubing for the controlled space
connecting a manometer or pressure gauge if testing is pressure (high) and reference pressure (low) taps, or tag
required. the tubes.
2. Locate the building pressure (high) tap in the area that 3. Regardless whether the controlled space is positive or
requires the closest control. Typically, this is a ground negative with respect to its reference, locate the high
level floor that has doors to the outside. pressure tap in the controlled space (the setpoint can be
set between -0.2" and 0.2" wc).
3. Locate the building tap so it is not influenced by any
source of moving air (velocity pressure). These sources 4. Locate the reference pressure (low) tap in the area
may include air diffusers or outside doors. surrounding the controlled space. Not locating the
reference tap to the sensor results in unsatisfactory
4. Route the building tap tube through the curb and feed it operation.
into the unit through the knockout in the bottom of the
control panel (refer to Figure 14). Connect the 3/16" ID 5. Locate both taps so they are not influenced by any
tube to the (high) fitting for sensor SPS2. source of moving air (velocity pressure). These sources
may include air diffusers or doors between the high and
5. Locate the reference pressure (low) tap on the roof. low pressure areas.
Keep it away from the condenser fans, walls, or
anything else that may cause air turbulence. Mount it 6. Route the building tap tube between the curb and
high enough above the roof so it is not affected by snow. the supply duct and feed it into the unit through the
Not connecting the reference tap to the sensor results in knockout in the bottom of the control panel.
unsatisfactory operation. 7. Connect the tube to the (high) fitting for sensor SPS2.
6. Use an outdoor static pressure tip (Dwyer A306 or
equivalent) to minimize the adverse effects of wind.
Place some type of screen over the sensor to keep out
insects. Loosely packed cotton works well.
7. Route the outdoor tap tube out of the main control panel
through a small field-cut opening in the upright. Seal
the penetration to prevent water from entering. Connect
the 3/16" ID tube to the (low) fitting for sensor SPS2.
18 IM 1058-5
Electrical Installation
Electrical Installation
CAUTION
Provide proper line voltage and phase balance. Improper line
voltage or excessive phase imbalance constitutes product
abuse. It can cause severe damage to the unit's electrical
components.
IM 1058-5 19
Electrical Installation
Electrical Installation
20 IM 1058-5
Preparing Unit for Operation
Preparing Unit for Operation
IM 1058-5 21
Optional Gas Heat
Optional Gas Heat
22 IM 1058-5
Optional Gas Heat
Optional Gas Heat
IM 1058-5 23
Optional Gas Heat
Installation
IMPORTANT
Outdoor Air (OA) Hood
This furnace must be installed by an experienced The OA hood (Figure 22) is not installed at the factory
professional installation company that employs fully becauseit would increase the width of the unit beyond the
trained and experienced technicians. Install the furnace allowableshipping width. The hood is shipped in a box in the
in accordance with the manufacturer's instructions and fansection.
local codes. In the absence of local codes, follow the The OA hoods must be installed over the outdoor air openings.
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the CSA
B149.1, Natural Gas and Propane Installation Code. 1. Remove and discard the shipping covers.
2. Position the hood over the OA openings.
WARNING 3. Line assembly holes up.
Sharp edges hazard. Can cause personal injury or death. 4. Install screws to fasten the OA hood.
Sheet metal parts, self-tapping screws, clips, and similar
itemsinherently have sharp edges, and it is necessary that The OA hoods must be installed before the furnace is operated.
theinstaller exercise caution when handling these items.
Figure 22: Outdoor Air (OA) Hood Installation
Flue Box
The flue box (Figure 21) is not installed at the factory because
it would increase the width of the unit beyond the allowable
shipping width.
The flue box must be installed over the combustion exhaust
openings. All holes are prepunched, the fasteners are
furnished and everything is shipped inside the fan section.
1. Remove and discard the shipping covers.
2. Position the flue box over the exhaust openings.
3. Line assembly holes up.
4. Install screws to fasten the flue box to the side of the unit.
24 IM 1058-5
Optional Gas Heat
7.0" (177.8)
IM 1058-5 25
Optional Gas Heat
Table 17: Specific Gravity Other Than 0.60 Sequence of Operation (Staged Control)
Specific Gravity Multiplier
Low Heat Option (2 Stage Control)
0.50 1.100
0.60 1.000 The following details the sequence of operation for the low
0.70 0.936 heat option.
0.80 0.867
1. Unit DDC control calls for heat.
0.90 0.816
1.00 0.775 2. Furnace DDC control module receives a call for heat.
Propane-Air
1.10 0.740
3. High limit switch is checked for safe condition.
Propane 4. Proof of airflow switch is check for combustion airflow.
1.55 0.622
Butane
5. 60 second prepurge cycle starts.
2.00 0.547 6. Spark ignitor is activated for 3 seconds.
7. Gas valve receives a command for stage 1 of heat.
Table 18: Pressure Drop Other Than 0.3"
8. Burner is ignited.
Pressure Drop Multiplier Pressure Multiplier
0.1 0.577 1.0 1.83
9. Unit DDC controller calls for stage 2 of heat.
0.2 0.815 2.0 2.58 10. Furnace DDC controller receives a stage 2 heat command.
0.3 1.000 3.0 3.16
0.4 1.16 4.0 3.65 11. Gas valve receives a command for stage 2 of heat.
0.6 1.42 6.0 4.47
High Heat Option (4 Stage Control)
0.8 1.64 8.0 5.15
For a unit with the optional high heat the above sequence is
followed for the first two stages.
For the remaining 2 stages the above procedure is repeated on
the second furnace module.
26 IM 1058-5
Optional Gas Heat
2. Furnace DDC control module receives a call for heat. 1. Unit DDC controller calls for heat.
3. Furnace safety switches and DDC control are checked 2. Top Furnace DDC control module receives a call for heat.
for safe conditions. 3. High limit switch is checked for safe condition.
4. 45 second prepurge cycle starts. Proof of airflow switch 4. Proof of airflow switch is checked for combustion airflow.
is checked for combustion airflows. 5. 45 second prepurge cycle starts.
5. Spark ignitor is activated. 6. Spark ignitor is activated.
6. Gas valve receives a signal to open fully. 7. Gas valve receives a signal to open fully.
7. Burner is ignited and runs for 20 seconds in high fire. 8. Burner is ignited and runs for 30 seconds in high fire
NOTE: If call for heat is interrupted during this timing, the
furnace will be locked in for the 20 seconds cycle. 9. Modulating burner gas valve and induction blower
motor receives a signal to modulate burner output to
8. Gas valve and induction blower motor receives a signal match the unit discharge air temperature setting.
to modulate burner output to match the unit discharge
air temperature setting. 10. If modulating burner is unable to meet discharge
temperature set point, furnace DDC control calls for
third stage of heating. The top furnace is reduced to
low (50%) fire. The bottom furnace is sequenced on per
stage furnaces sequence of operation (steps 2 - 8).
11. Staged burner gas valve receives a signal to open to 50%.
12. Modulating burner gas valve and induction blower
motor receives a signal to modulate burner output to
match the unit discharge air temperature setting.
13. If stage 3 and modulating furnace is unable to meet
discharge temperature setpoint, furnace DDC controller
calls for stage 4 heat. The bottom furnace will stage up
to high fire and the modulating furnace will reduce to
50% operation.
14. Staged burner gas valve receives a signal to open fully.
15. Modulating furnace's gas valve and induction blower
motor receives a signal to modulate burner output to
match the unit discharge air temperature setting.
IM 1058-5 27
Optional Gas Heat
Start-Up Procedures
Start-up and service of this equipment must be performed Start-Up Responsibility
by trained and experienced technicians. It is highly
The start-up organization is responsible for determining that
recommended that the initial start-up and future service be
the furnace, as installed and as applied, will operate within
performed by Daikin McQuay trained technicians who are
the limits specified on the furnace rating plate.
familiar with working on live equipment. A representative of
the owner or the operator of the equipment should be present 1. The furnace must not operate at an airflow below the
during start-up to receive instructions in the operation, care specified Minimum Airflow CFM (refer to Table 15
and adjustment of the unit. on page 22). On variable air volume systems it must
be determined that the furnace will not be operated
WARNING if or when system cfm is reduced below the specified
Overheating or failure of the gas supply to shut off can minimum airflow cfm.
cause equipment damage, severe personal injury or 2. It must be established that the gas supply is within the
death. Turn off the manual gas valve to the appliance before proper pressure range (refer to Table 15 on page 22).
shutting off the electrical supply.
Operating Procedures
DANGER
Before Start-Up
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal 1. Notify inspectors or representatives who may be
injury, or loss of life. required to be present during start-up of gas fuel
A. This appliance does not have a pilot. It is equipped with equipment. These could include the gas utility company,
an ignition device which automatically lights the burner. Do city gas inspectors, heating inspectors, etc.
not try to light the burner by hand. 2. Review the equipment and service literature and
B. Before operating, smell all around the appliance area for become familiar with the location and purpose of the
gas. Be sure to smell next to the floor because some gas furnace controls. Determine where the gas and power
is heavier than air and will settle on the floor. can be turned off at the unit and before the unit.
What to do if you smell gas: 3. Determine that power is connected to the unit and
• Do not try to light any appliance. available.
• Do not touch any electric switch, do not 4. Determine that the gas piping, meter, and service
use any phone in your building. regulator have been installed, tested, and meet the
• Immediately call your gas supplier from a equipment requirements.
phone in a neighboring building. Follow 5. Determine that proper instruments will be available for
the gas supplier's instructions. the start-up. A proper start-up requires the following:
• If you cannot reach your gas supplier, voltmeter, manometer or gauges with ranges for both
call the fire department. manifold pressure and inlet gas pressure.
C. Use only your hand to push in or turn the gas control knob.
Start-Up Preliminary
Never use tools. If the knob will not push in or turn by hand,
don't try to repair it, call a qualified service technician. Close gas main.
Force or attempted repair may result in a fire or explosion.
1. Check the burner fan wheel for binding, rubbing, or
D. Do not use this appliance if any part has been under water. loose setscrews.
Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system 2. Check power.
and any gas control which has been under water. 3. Purge the gas lines.
4. Leak check. Using a rich soap-water mixture and a
brush, check the gas lines for leaks. Correct all leaks
before starting furnace.
28 IM 1058-5
Optional Gas Heat
Start-Up Service
1. Set the thermostat to the lowest setting. The furnace DDC controller has diagnostic information for
2. Turn off all electric power to the appliance. troubleshooting the furnace operation. The ignition control
module has a LED light that will flash when an abnormal
3. This appliance is equipped with an ignition device condition occurs. See Table 19 and Table 20 for an explanation
which automatically lights the burner. Do NOT try to of the diagnostic information.
light the pilot by hand.
4. Open the control access panel. Maintenance
5. Turn the gas control clockwise to “OFF”. Planned maintenance is the best way to avoid unnecessary
6. Wait five (5) minutes to clear out any gas. Then, smell expense and inconvenience. Have this system inspected
for gas, including near the floor. If you smell gas, STOP! at regular intervals by a trained and experienced service
Follow step “B” in the DANGER label on this page. If technician. The following service intervals are typical for
you don't smell gas, proceed to the next step. average situations but will have to be adjusted to suit your
particular circumstances.
7. Turn the gas control counter-clockwise to “ON”.
Fuel pressure settings and control settings should be made
8. Close the control access panel.
only by persons thoroughly experienced with the burner and
9. Turn on all electric power to the appliance. control system, and must not be tampered with by persons
10. Set thermostat to desired setting. without such experience.
11. If the furnace will not operate, refer to Turning off Always replace covers on burner controls and boxes as the
Gas to the Unit, and call your service technician or gas electrical contacts are sensitive to dust and dirt. Perform
supplier. maintenance of controls, gas valves, and other components in
accordance with instructions contained in the manufacturer's
Turning off Gas to the Unit bulletins.
1. Set the thermostat to the lowest setting. Monthly
2. Turn off all electrical power to the appliance if service Check air filters and replace if dirty.
is to be performed.
3. Open the control access panel. Twice Yearly
4. Turn the gas control knob clockwise to “OFF”. Do 1. Burner Air - Check burner fan wheel for dirt buildup and
not force. lint. Check combustion air intake louver and flue box for
dirt buildup and accumulation of windborne debris.
5. Close the control access panel.
2. Cleaning - Inspect flue tubes and combustion chamber,
cleaning as required. Keep burner vestibule clean. Dirt
and debris can result in burner air blockages.
Yearly
Gas Train -Check all valves, piping and connections for
leakage. Inspect and clean flame rod, ignition electrode, and
burner manifold.
Condensate Pan/Drain/P-Trap - Check pan, drain, and p-trap.
IM 1058-5 29
Optional Gas Heat
Figure 24: Typical Staged Gas Furnace Electrical Schematic with Sensor
L1 L2 Gnd
B W Gr
W B
1 115VAC 2
40VA
W
B BL Y
24VAC
G
1016-427
COM
Ignition Module Y
C 2 Stage Gas
Y C
Valve
MV
BL MV HI
PS1
OR
APS 2
W
Y
1
X R
BL Y
R
HV
OR
Igniter
FS
W
Flame Sensor
L1 IND
W B Comb Fan W
Motor
30 IM 1058-5
Optional Gas Heat
Figure 25: Typical Modulating Gas Furnace Electrical Schematic with Sensor
L1 L2
WHT BLK
115 VAC
40VA
Combustion
J5 24VAC
Board BLU
24VAC
WH T
GND Modulating
Comm Po rt
Gas Valve
MOD RED
RTN
WHT
BLK
RED
ROS1 ROS2 J3 MOD
OR G
MV BLU
Limit
OR G RTN
BRN
APS MV
GRY
Switch
Press
115 VAC
24V AC
BLK WHT DSI
T7
MJ
Board
HS I
R Hot WH T RED
T5
WHT
+ Spark Electrode
input signal
+
0-10V DC
BLK
- - Neutral WH T
J8 T4
Inducer
Gn d
Pre ssu re T6
+ Tr ansducer
Sensing hose
to fan
Variable Furnace Controller Table 20: LED Indicator and Fault Conditions
Daikin McQuay's furnace controller is
LED Diagnostic Informatio an electronic
n device Indicator Fault Condition
that delivers full control
Flash(esof )the modulating furnace. Control
C olor Condition No power or control hardware fault Indicator Fault
Steady Off
includes sequencing, ignition,
Of f safety,
N/A modulation
N o power toof the l
Contro Condition
Steady
control valve, and the On draft
induced Re dmotor.
C ontrol Faultto
Inputs Detected
the or no 24VAC power Steady On Control fault detected or no 24 VAC power
1 Re d C ombustion f an motor energiz ed, Pressure switch open Combustion fan motor energized, pressure switch open
1 Flash
furnace control board are 2 an a 0-10V
Re d signal. The analog
Inducer air pressure reads above ze ro level w hen the inducerInducerisair
of pressure
f reads above zero level when the
signal will modulate the3 burner down Re d toF25%
lame isofON
full
whenload.
it should be OFF or 2 Flashes
flame is OFF when it should be ON inducer is off
Safety inputs include pressure
4 lineReand
d electrical
G as valve ONconnection
when it should be OFF or OFF when it should be ON
Flame is on when is should be off or flame is off when it
5 Re d S afety rela y ON w hen it should be OFF3orFlashes
OFF when it should be ON should be on
from the airflow proofing 6 switch and
Re d electrical connection
E xcessi ve plenum temperature Gas valve is on when is should be off or gas valve is off
from the rollout switches.7 ControlRe board
d outputs
High are toopen
limit switch theor fuse open 4 Flashes when it should be on
igniter board, modulating 8 gas valve, Re dandP to the sw
ressure induce
itch fadraft
iled to operate or m odulation current
5 Flashes
is incorrect
Safety relay is on when it should be off or safety relay is off
9 Re d S afety startup fa iled to validate induc er air pat h when it should be on
motor. Slow Green Normal operation -No call for heat 6 Flashes Excessive plenum temperature
1 G reen Call for heat
Ignition Control Module
2 LEDG Diagnostics
reen Gas ON -ca ll for heat
7 Flashes High limit switch is open or fuse is open
Pressure switch failed to operate or modulation current is
3 8 Flashes
The following LED indicators canG reen Gas ON -no ca ll for heat
be used to diagnose faults incorrect
Rapi d Amber Retr y
associated with the modulating gas furnace. Slow Flash Normal operation - no call for heat
1 Slow Flash Call for heat
2 Slow Flashes Gas on - call for heat
3 Slow Flashes Gas on - no call for heat
Rapid Flash Retry
IM 1058-5 31
Optional Electric Heat
Optional Electric Heat
32 IM 1058-5
Optional Modulating Hot Gas Reheat
Optional Modulating Hot Gas Reheat
IM 1058-5 33
Optional Modulating Hot Gas Reheat
Optional Modulating Hot Gas Reheat
34 IM 1058-5
Optional Modulating Hot Gas Reheat
• Lead/Lag Arrangement w/ MHGRH (when applicable) • In the reheat mode, the minimum position for the reheat
—— Alternate staging with circuit #1 as lead will be the valves is 10% (1.0 Vdc). The controller will modulate the
standard default arrangement. reheat valves from this starting position.
—— During cooling mode, circuit #1 will lead and load • Reheat valve(s) must be at 0% (0 Vdc) position before
up before starting circuit #2. starting the first compressor in the reheat circuit to
prevent pressure spikes.
—— During reheat mode, circuit #2 will lead and load up
before starting circuit #1. • Upon termination of dehumidification (reheat), the
maximum ramp down or decay rate of the reheat control
—— For reheat operation, compressor(s) in circuit
valves shall be 1% per sec (or 0.1V per sec).
#2 must be active. If the unit is operating in the
cooling mode when a call for dehumidification/ • Upon termination of dehumidification (reheat), staging
reheat arises,circuit #2 will become the lead and of compressor(s) is delayed for 1 minute after reheat
the controller will bring on an additional stage of capacity = 0% (0 Vdc).
coolingfor dehumidification. If any compressors • Every 24 hours, the reheat control valves will be driven
in circuit #1 are operating at this moment they to their maximum position (10Vdc) and then returned
will be switched over to compressors in circuit #2. to their normal operating position (0Vdc). If unit is
Dehumidification operation is disabled if circuit #2 is operating in cooling or dehumidification (reheat) at the
disabled for any reason. prescribed time it will be deferred to the next time.
• Dehumidification status can now be found under the
MTIII main system menu. Reheat capacity (valve
position) can also be found under the main system menu,
display based on percentage (0-100%).
IM 1058-5 35
Optional Hot Water Heat
Optional Hot Water Heat
Return Unit A B C D
015–020 64.5 8.5 8.5 28.5
026–035 64.5 8.5 8.5 28.5
040–050 90.2 8.5 8.5 28.5
D
C Condenser End
Supply
B
A
36 IM 1058-5
Optional Hot Water Heat
Optional Hot Water Heat
IM 1058-5 37
Optional Hot Water Heat
38 IM 1058-5
Optional Energy Recovery Wheel
Optional Energy Recovery Wheel
IM 1058-5 39
Optional Energy Recovery Wheel
Optional Energy Recovery Wheel
(1) Currently, only the Over-Under configuration is offered on Daikin McQuay roof-top systems and air handlers.
Exhaust Air
40 IM 1058-5
Optional Energy Recovery Wheel
IM 1058-5 41
Optional Outdoor Air Monitor
Optional Outdoor Air Monitor
42 IM 1058-5
Optional Outdoor Air Monitor
Optional Outdoor Air Monitor
Transmitter
Connector
IM 1058-5 43
Optional Outdoor Air Monitor
44 IM 1058-5
Optional Outdoor Air Monitor
IMPORTANT
Fluctuations in the airflow output signal are normal. Laboratory
research indicates that dampening true fluctuations will
result in poor control and a larger dead-band of operation.
Therefore, the use of the dampening filters in control devices
is not recommended. Warnings indicate potentially hazardous
situations, which can result in property damage, severe
personal injury, or death if not avoided.
IM 1058-5 45
Optional Outdoor Air Monitor
46 IM 1058-5
Optional Outdoor Air Monitor
IM 1058-5 47
Unit Options
Unit Options
HI LO
TO LEAVING
HI
AIR SIDE OF
THE FILTERS LO
HI DHL
LO
PC7
TO SUPPLY
FAN PLENUM
48 IM 1058-5
Unit Options
Unit Options
VOLTAGE PRI.
460V LINE
IM 1058-5 49
Wiring Diagrams
Wiring Diagrams
50 IM 1058-5
Wiring Diagrams
Wiring Diagrams
IM 1058-5 51
Wiring Diagrams
52 IM 1058-5
Wiring Diagrams
IM 1058-5 53
Wiring Diagrams
54 IM 1058-5
Wiring Diagrams
IM 1058-5 55
Wiring Diagrams
56 IM 1058-5
Wiring Diagrams
IM 1058-5 57
Wiring Diagrams
58 IM 1058-5
Wiring Diagrams
IM 1058-5 59
Wiring Diagrams
60 IM 1058-5
Wiring Diagrams
IM 1058-5 61
Wiring Diagrams
62 IM 1058-5
Wiring Diagrams
IM 1058-5 63
Wiring Diagrams
64 IM 1058-5
Wiring Diagrams
IM 1058-5 65
Sequence of Operation
Sequence of Operation
Operating States
The transition from any operating state to another is Heating
graphically represented in Figure 57.
The unit's heating mode of operation is controlled by the
control temperature and the heating setpoint temperature. The
Figure 57: State Diagram unit goes into the heating mode of operation by analyzing the
control temperature.
Any Other State
The control temperature can be either the return temperature
or the space temperature.
The return temperature is typically used for VAV units and
OFF
the space temperature is typically used for CAV units.
The unit goes into the heating mode of operation when the
control temperature (return or space temperature) is below the
heating setpoint by more than ½ the deadband.
Start Up
Example – If the heating setpoint is 68.0°F and the deadband
is 1.0°F, the unit will not go into the heating mode of
operation until the control temperature reaches 67.4°F.
Economizer Recirculation Heating
When this takes place, the heating mode of operation will
begin and the 1st stage of heating operation will start. The
next stage, up or down, will take place after 4 minutes. This
“4 minutes” is called the stage timer. The gas or electric
Fan Only
heat module will continue to stage up as long as the control
temperature is below the heating setpoint by more than ½ the
heating setpoint deadband. The unit will stage down if the
maximum discharge air temperature of 120°F is reached. Gas
Mechanical
Minimum DAT
units with one gas valve have 2 stages of heating and units
Cooling
with two gas valves have 4 stages of heating.
Minimum DAT
Start Up This control mode is designed to temper the air in the
With a “start up” command from the “Off” State the unit will ductwork when in heating mode. When the unit is in the “Fan
default into the “Start Up” state of operation for 3 minutes. Only” state and the Discharge Air Temperature is less than
During this time, the fan is off. the minimum discharge air temperature limit, “Minimum
DAT” control is initiated. The unit will turn on minimum heat
until the discharge air temperature exceeds the limit.
Recirculation
Next, the unit will transition into the “Recirculation” state of
operation for another 3 minutes. During this time, the outside
air damper will close and the fan will turn on, thereby mixing
the air in the ductwork and the space.
Fan Only
The outside air damper will modulate to the minimum
position and based upon the sensor inputs, the unit will go
into one of the four running states - “Heating,” “Cooling,”
“Economizing,” or “Minimum DAT.” If the control
temperature is between its setpoint and its dead band, the unit
will remain in the “Fan Only” state.
66 IM 1058-5
Sequence of Operation
Sequence of Operation
Mechanical Cooling
Constant Volume (Space Comfort Controller) The unit controller will turn on the next stage of compressor
The control temperature for a CAV unit is typically the operation, or turn off a stage of compressor operation, to
space temperature. A space temperature sensor must be field maintain the discharge air temperature setpoint within the
installed into the occupied space and connected to the unit deadband. When a compressor stage turns on, the next
controller. compressor stage up or down will not take place for the next 4
minutes. This “4 minutes” is called the stage timer.
The unit goes into the cooling mode of operation when the
control temperature (space temperature) is above the cooling When a cooling stage is initiated no further operation will
setpoint by more than ½ the deadband. take place within the stage timer limit. Reference the Cooling
Setup menu for the adjustable stage time value. In the above
Example – the cooling setpoint is set to 70.0°F and the
example, the unit will stage down or turn off the cooling
deadband is 1.0°F, the unit will not go into the cooling mode
mode of operation when the return temperature reaches
of operation until the space sensor reaches 70.6°F.
69.4°F.
When this takes place, the cooling mode of operation will
begin and the 1st stage of compressor operation will start.
Economizer
The unit controller will turn on the next stage of compressor
When the economizer is enabled, the outside air temperature
operation, or turn off a stage of compressor operation,
is below the changeover setpoint, and the differential enthalpy
to maintain the cooling setpoint temperature within the
switch (if installed) is made, the economizer becomes the
deadband. When a compressor stage turns on, the next
first stage of cooling. It will modulate to control to either the
compressor stage, up or down, will not take place for the
discharge air temperature (VAV) or space temperature (CV).
next 4 minutes. This “4 minutes” is called the stage time.
Reference the “Cooling Setup” menu for the adjustable stage Every 4 minutes, the unit can then either add mechanical
time value. cooling if the economizer is at 100% open, continue
When a cooling stage is initiated no further operation will economizing, or if the control temperature is satisfied, return
take place within the stage timer limit. In the above example, to minimum position and transition back to “Fan Only” mode.
the unit will stage down or turn off the cooling mode of If the enthalpy switch breaks or the outside air warms, the
operation when the cooling setpoint reaches 69.4°F. unit will exit economizing and continue to mechanically cool
while returning to the minimum position for ventilation.
Variable Air Volume (Discharge Air Controller)
The unit's cooling mode of operation is controlled by the
control temperature, the change-over temperature, and the
discharge air temperature. The unit goes into the cooling
mode of operation by analyzing the control temperature.
The control temperature for a VAV system is the return
temperature.
The unit goes into the cooling mode of operation when
the control temperature (return temperature) is above the
changeover setpoint by more than ½ the deadband.
Example – If the change over temperature is 70.0°F and the
deadband is 1.0°F, the unit will not go into the cooling mode
of operation until the return temperature reaches 70.6°F.
When this takes place, the cooling mode of operation will
begin and the 1st stage of compressor operation will start.
IM 1058-5 67
Check, Test, and Start Procedures
Check, Test, and Start Procedures
68 IM 1058-5
Check, Test, and Start Procedures
Check, Test, and Start Procedures
IM 1058-5 69
Check, Test, and Start Procedures
Scroll Compressor Rotational Direction 4. Verify that the condenser fans are cycling and rotating
properly (blowing air upward). When the compressor
Scroll compressors only compress in one rotational direction.
starts, at least one condenser fan should also start.
Three-phase compressors rotate in either direction depending
upon phasing of the power to L1, L2, and L3. Since there 5. Check the oil level in the compressor sightglass.
is a 50/50 chance of connecting power to cause rotation in If low oil is observed, it is possible that liquid
the reverse direction, verify that the compressor rotates refrigerant is returning to the compressor. Check the
in the proper direction after the system is installed. If the suction superheat, see “Expansion Valve Superheat
compressor is rotating properly, suction pressure drops and Adjustment” below. It should be between 10°F (5.5°C)
discharge pressure rises when the compressor is energized. If and 13°F (7.2°C). See “Expansion Valve Superheat
the compressor is rotating in reverse, the sound level is louder Adjustment” below.
and current draw is reduced substantially. After several 6. Verify that the condenser refrigerant subcooling at full
minutes of operation, the compressor’s internal protector capacity is between 13°F and 20°F.
trips.
All three-phase compressors are wired the same internally. Checking Subcooling
Therefore, once the correct phasing is determined for a Following are recommendations for checking subcooling:
specific system or installation, connecting properly phased
1. Run unit until it reaches steady state. Close the unit
power leads to the same terminals should maintain proper
section doors. Running the unit with its doors open will
rotation direction.
affect system operation.
Perform the Following Procedure: 2. Measure the discharge gas pressure at the compressor
1. At the keypad, set the cooling setpoint low enough so discharge gauge port with an accurate gauge. Use this
that the controller will call for cooling. pressure to determine the saturation temperature of the
refrigerant.
2. Verify that compressor #1 starts. If the compressor
motor hums but does not run, verify that it is getting 3. Measure liquid temperature accurately by attaching
three-phase power. a thermocouple to the liquid line tube leaving the
condenser coil. Insulate the tube and thermocouple for
3. The compressor should operate continuously while more accurate results.
there is a call for cooling. If the compressor cycles
on and off on its low pressure switch, perform the 4. Subtract the measured liquid temperature from the
following: saturation temperature to determine the subcooling.
a. Verify that the circuit is not short of refrigerant. 5. As a general rule, high subcooling indicates that the
circuit is low on charge. Low subcooling generally
b. Check for low airflow across the evaporator coil. indicates that the circuit has too much charge.
c. Check for clogged filters.
NOTICE
d. Check for restricted ductwork.
Venting refrigerant to atmosphere is not allowed per most
e. Check for very low temperature return air entering local laws and/or codes.
the unit.
f. Verify that the liquid line components, expansion
valve, and distributor tubes are feeding the
evaporator coil.
g. Verify that all air handling section panels are closed.
70 IM 1058-5
Check, Test, and Start Procedures
Fixed Pitch
Must be Sheave
parallel
IM 1058-5 71
Check, Test, and Start Procedures
WARNING
Keep hands away from rotating wheel! Contact with rotating
wheel can cause physical injury.
72 IM 1058-5
Final Control Settings
Final Control Settings
IM 1058-5 73
Maintenance
Maintenance
74 IM 1058-5
Maintenance
Maintenance
WARNING
Prior to cleaning the unit, turn off and lock out the main power
switch to the unit and open all access panels.
IM 1058-5 75
Maintenance
76 IM 1058-5
Maintenance
WARNING
If an overload or a fault current interruption occurs, check
circuits to determine the cause of the interruption. If a fault
condition exits, examine the controller. If damaged, replace it
to reduce the risk of fire or electrical shock.
IM 1058-5 77
Maintenance
78 IM 1058-5
Maintenance
Loss of input phase (relay Red LED - flash twice, off, flash twice,
deenergized) off, etc.
Red LED - flash twice, off, flash twice,
Voltage unbalance (relay deenergized) off, etc.
High or low voltage (relay de- Red LED - steady on
energized)
Phase reversal (relay deenergized) Red LED - pulse on, off, on, off, etc.
Restart delay (fault cleared, PVM Green LED - pulse on, off, on, off, etc.
pending restart, relay de-energized)
Other features:
• Standard 2% to 8% variable voltage unbalance (“3” in
Figure 67).
• Standard 1 to 500 second variable restart delay (“2”).
• Standard 1 to 30 second trip delay (“4”) (except loss of
phase, which trips at 1 second non-adjustable).
IM 1058-5 79
Maintenance
80 IM 1058-5
Maintenance
Vibration Causes
Bearing Lubrication 1. Wheel imbalance.
CAUTION a. Dirt or debris on wheel blades.
Bearing overheating potential can damage the equipment. b. Loose setscrews in wheel hub or bearing-to-shaft.
Do not overlubricate bearings. Use only a high grade mineral
c. Wheel distorted from overspeed.
grease with a 200°F safe operating temperature.
2. Bent shaft.
Motor Bearings
3. Faulty drive.
Supply Fans
a. Bad V-belts; lumpy, or mismatched.
Supply fan motors should have grease added after every 2000
b. Belt tension too tight or too loose.
hours of operation. Use one of the greases shown in Table 29.
Using the following procedure, relubricate the bearings while 4. Bad bearings or loose bearing hold-down bolts.
the motor is warm, but not running. 5. Motor imbalance.
1. Remove and clean upper and lower grease plugs. 6. Fan section not supported evenly on foundation.
2. Insert a grease fitting into the upper hole and add a
small amount of clean grease with a low pressure gun. Periodic Service and Maintenance
3. Install the lower grease plug. 1. Check all moving parts for wear every six months.
4. Run the motor for five minutes before installing the 2. Check bearing collar, sheave, and wheel hub setscrews,
upper grease plug. sheave capscrews, and bearing hold-down bolts for
tightness every six months.
Condenser Fan and Exhaust Fan
The condenser fan and exhaust fan motors are permanently
lubricated and require no periodic lubrication.
Fan Shaft Bearings
Relubricate fan shaft bearings periodically. Relubricate
according to the schedule on the fan housing. If the bearings
are exposed to wet conditions, wide temperature variations,
or other severe atmospheric conditions, relubricate more
frequently. Use one of the greases shown in Table 29.
While the bearing is at normal operating temperatures,
rotate the fan by hand and add only enough grease to purge
the seals. The seals bleed slightly when this occurs. Do not
overlubricate.
IM 1058-5 81
Maintenance
82 IM 1058-5
Maintenance
CAUTION
Do not use acid based cleaners, aromatic solvents, steam
or temperatures in excess of 170ºF; damage to the wheel
may occur!
IM 1058-5 83
Maintenance
Figure 70: Segment Retaining Clip 6. Install the pulley per the dimensions in Figure 72 and
secure the set screw to the drive shaft
7. Stretch belt over pulley and engage grove.
8. Follow start up procedure on page 72 (procedure
needs to be confirmed).
Series DIM–A
36 1/4"
52 1/4"
64 7/16"
74 7/16"
86 7/16"
84 IM 1058-5
Maintenance
IM 1058-5 85
Maintenance
Table 32: SWSI Airfoil Wheel-to-Funnel Relationship 1. Measure continuity through all fuses.
86 IM 1058-5
Service and Warranty Procedure
Service and Warranty Procedure
The decision to replace the failed portion of the compressor A “return goods” tag will be sent to be included with the
tandem, as opposed to replacing the entire tandem, must be returned material. Enter the information as called for on the
decided based on the following. tag in order to expedite handling at out factories and issuance
of credits. All parts shall be returned to the factory designated
1. In warranty: Warranty only covers replacement of the on the return goods tag, transportation charges prepaid.
failed portion of the tandem.
The return of the part does not constitute an order for
2. Out of warranty: The customer decides whether to replacement. A purchase order for the replacement part
replace the entire tandem or just a portion. must be entered through your nearest Daikin McQuay
3. Some equipment may include the extended 2nd - 5th representative. The order should include the component's part
year compressor warranty option. number and description and the model and serial numbers of
the unit involved.
If it is determined that the failure of the returned part is due to
faulty material or workmanship within the standard warranty
period, credit will be issued on the customer's purchase order.
IM 1058-5 87
Warranty Registration Form
Warranty Registration Form
Complete this form and return to Daikin Applied, Warranty Department, within 10 days to comply with the terms of Daikin Applied Warranty.
Check, Test, and Start Procedure for Maverick II Roof-Mounted Air Conditioners
Circle Yes/No. Mark NA on all items that do not apply to the type of the unit. See the IM bulletin for more information. Make any additional
comments on a separate sheet of paper and attach to this form.
I. INITIAL CHECK
A. Is any shipping damage visible? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
B. Are fan drives properly aligned and beltsproperly adjusted? . . . . . . . . . . . . . . . . . . . Yes No N/A
C. Tightened all setscrews on pulleys, bearings and fans? . . . . . . . . . . . . . . . . . . . . . Yes No N/A
D. Have the hold-down bolts been backed off on spring mounted fan isolators? . . . . . . . . . . . . . Yes No N/A
E. Do fans turn freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
F. Has the discharge static pressure reference line been properly located within the building? . . . . . . . Yes No N/A
G. Electrical service corresponds to unit nameplate? . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Volts _____________ Hertz _____________ Phase _____________
H. Is the main disconnect adequately fused and are fuses installed? . . . . . . . . . . . . . . . . . Yes No N/A
I. Are crankcase heaters operating, and have they been operating 24 hours prior to start-up? . . . . . . . Yes No N/A
J. Are all electrical power connections tight? (Check compressor electrical box.) . . . . . . . . . . . . Yes No N/A
K. Is the condensate drain trapped? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
88 IM 1058-5
Warranty Registration Form
Comments:
IM 1058-5 89
Quality Assurance Survey Report
Installation address:____________________________________________________________________________________________________
Purchasing contractor:__________________________________________________________________________________________________
Address: ____________________________________________________________________________________________
City/State/Zip: _______________________________________________________________________________________
2. How would you rate the overall appearance of the product; i.e., paint, fin damage, etc.?
3. Did all sections of the unit fit together properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
4. Did the cabinet have any air leakage? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
Comments _______________________________________________________________________________________
8. Did the labeling and schematics provide adequate information? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A
9. How would you rate the serviceability of the product?
10. How would you rate the overall quality of the product?
11. How does the quality of Daikin Applied products rank in relation to competitive products?
Comments _______________________________________________________________________________________
Please list any additional comments which could affect the operation of this unit; i.e., shipping damage, failed components, adverse installation
applications, etc. If additional comment space is needed, write the comment(s) on a separate sheet, attach the sheet to this completed Quality
Assurance Survey Report, and return it to the Warranty Department with the completed preceding “Equipment Warranty Registration Form”.
90 IM 1058-5
Warranty Registration Form
Appendix follows
IM 1058-5 91
Appendix – Keypad/Display Menu Structure
The following is a description of the MicroTech III menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration.
92 IM 1058-5
Appendix – Keypad/Display Menu Structure
Commission Unit Manual Control Service Menus Trending Unit Maintenance BMS Communications
Unit Set-Up ► Manual Control= Normal Timer Settings ► Trending Ena= No Operating Hours LON Set-Up ►
Timer Settings ► Supply Fan= Off Operating Hours ► Apply Chgs= No BACnet MSTP Set-Up ►
SAF Set-Up ► SAF Spd Cmd= 0% Save/Restore Settings ► Sample Time= 300s BACnet IP Set-Up ►
RF/EF Set-Up ► INV/OF Ena= Off Active Alarms ► TrendOnOff= Off D-Net Set-Up ►
Htg/Clg ChgOvr Set-Up ► INV Comp= Off Alarm Log ► Export Data= No Network Unit Set-Up ►
Cooling Set-Up ► INV Spd Cmd= 0% Alarm Configuration ► Clear Trend= Done
INV Cmp Set-Up ► Comp 3= Off Analog Input Status ► Points 1–8 (Fixed) ►
Econo Set-Up ► OA Fan= Off Universal I/O Status ► Points 9–24 (from List) ► For more detail go to:
Min OA Set-Up ► OA Fan Cmd= 0% Digital Input Status ► Points 25–27 (with IDs) ► Figure 78, page 100
Heating Set-Up ► 4 Way Valve= Cool Digital Output Status ► Points 28–30 (with IDs) ►
OA Fan Set-Up ► RcvrSol Valve= Closed Network Input Status ►
Exp Valve Set-Up ► BP Sol Valve= Closed Modbus Status ►
Defrost Set-Up ► EVI Cmd= 0% D3 Status ► For more detail go to:
Dehum Set-Up ► EVO Cmd= 0% Sensor Offsets ► Figure 79, page 100
Energy Rec Set-Up ► RF/EF VFD= Off Reset Counte= XXXX
D3 Set-Up ► RF/EF Spd Cmd= 0%
Alarm Configuration ► OAD/Econo= 0%
For more detail go to:
Gas Htg On/Off
Figure 77, page 98
Htg Valve= 0%
SCR Out= 0%
For more detail go to:
Htg Stg 1= Off
Figure 76, page 96
SCR Ena 1= Off
Htg Stg 2= Off
Htg Stg 3= Off
Htg Stg 4= Off
Reheat Valve= 0%
ERec Wheel= Off
ER Whl Cmd= 0%
ER BP Dmpr Cl= Off
ER BP Dmpr Op= Off
Alm Output= Off
Fan Op Out= Off
IM 1058-5 93
Appendix – Keypad/Display Menu Structure
View/Set Unit
Unit Status/Settings ►
Occupancy ►
Temperatures ►
Flow Status ►
SAF Spd Control ►
RF/EF Control ►
Cooling ►
Economizer ►
Min OA Damper ►
Heating ►
Dehumidification ►
Date/Time/Schedules ►
Unit Status/Settings Occupancy Temperatures Flow Status SAF Speed Control RF/EF Control
Unit State= ___________ Occupancy= __________ Control Temp= XXX°F Airflow= ______________ SAF Speed= XXX% RF/EF Cap= XXX%
Unit Status= __________ Occ Mode= Auto/Net Disch Temp= XXX°F Supply Fan= __________ Speed Cmd= XXX% Speed Cmd= XXX%
Dehum Status= ________ OccSrc= _____________ Return Air= XXX°F Ret/Exh Fan= _________ Duct Press= X.Xin Bldg Press- X.XXin
Ctrl Mode= Off UnoccSrc= ___________ Space Temp= XXX°F DuctSP Spt= 1.0in BldgSP Spt= 0.050in
Clg Status= ___________ Tnt Ovrde Tm= 0 min OA Temp= XXX°F IAQ PPM= XXXXPPM
Htg Status= ___________ EF/LC Temp= XXX°F OA Flw= XXXXXCFM
Sup/Htg Status= _______ ER LAT= XXX°F MinOAFlw Spt= 2000CFM
Econo Status= _________ ER EAT= XXX°F Bldg Press= X.XXin
Clg Capacity= XXX% DRT1= XXX°F BldgSP Spt= 0.05in
Htg Capacity= XXX% DRT3= XXX°F
Supl Htg Cap= XXX% SRT= XXX°F
Reheat Cap= XXX% DFT= XXX°F
SAF Speed= XXX% IRT= XXX°F
RF/EF Cap= XXX% ORT= XXX°F
OAD/Econo Cap=XXX%
Rel Humidiy= XXX%
Net Emrg Ovrd= Normal
Net App Mode= Auto
94 IM 1058-5
Appendix – Keypad/Display Menu Structure
IM 1058-5 95
Appendix – Keypad/Display Menu Structure
Figure 76: Commission Unit – Keypad/Display Menu Structure
Commission Unit
Unit Set-Up ►
Timer Settings ►
SAF Set-Up ►
RF/EF Set-Up ►
Htg/Clg ChgOvr Set-Up ►
Cooling Set-Up ►
INV Cmp Set-Up ►
Econo Set-Up ►
Min OA Set-Up ►
Heating Set-Up ► Unit Set-Up Timer Settings SAF Set-Up
OA Fan Set-Up ► Space Sensor= Loc/Net Service Time= 0min SAF Ctrl= DSP 1 ZONE VAV CONTROL CFM CONTROL
Exp Valve Set-Up ► Eng Units= English Start Up= 180s AplyInputChgs= No Min Clg Spd= 40% Min CFM= 0CFM
Defrost Set-Up ► Unit Name= xxxxxxxxxxxx Recirculate= 180s CO2 Input= None Max Clg Spd= 100% Max CFM= 10000CFM
Dehum Set-Up ► Rapid Start= No Zero OA Time= 0min CFM Input= None Min Htg Spd= 40% V/A @ Min CFM= 0V
Energy Rec Set-Up ► Rapid Start Tm= 10min Tnt Override= 120min BSP Input= No Max Htg Spd= 100% V/A @ Max CFM= 10 V
D3 Set-Up ► DO10 Clg= FanOp Post Heat= 0s SPEED CONTROL Space Period= 30s SAF CFM DB= 3%
Alarm Configuration ► Pwd Timeout= 10min Rem SAF Cap= 25% Space Gain= 1.5 SAF CFM Period= 30s
Low DAT= 6min DSP CONTROL Space PAT= 100s SAF CFM Gain= 0.1
ClgStateDelay= 300s DSP DB= 0.1in Space Max Chg= 10% SAF CFM MxChg= 5%
Clg Stg Time= 5min VFD Ramp Time= 60s CO2 CONTROL BSP CONTROL
Htg Stg Time= 5min Min Period= 5s Min PPM= 0PPM BSP DB= 0.01in
MinExStrtTm= 120s Max Spd Chg= 15% Max PPM= 2000PPM BSP Period= 5s
MinExStopTm= 120s V/A @ Min PPM= 0V BSP Gain= 0.2
ER Whl Stg Tm= 5min V/A @ Max PPM= 10V Max Spd Chg= 4%
ER Whl Off Tm= 20min Min SAF PPM= 800PPM SAF SETUP
Max SAF PPM= 1100PPM SAF Ctrl Dly= 30s
Min PPM Spd= 50% Min Speed= 25%
Max PPM Spd= 100% VAVBox Out= _________
Max Vent Speed= 100%
Max SAF RPM= 2600
ECM Status= _________
96 IM 1058-5
Appendix – Keypad/Display Menu Structure
RF/EF Set-Up Htg/Clg ChgOvr Set-Up Cooling Set-Up INV Cmp Set-Up
RF/EF Ctrl= None Ctlr Temp Src= RAT Clg Stage Time= 5min COMPRESSOR STATUS COMPRESSOR SETUP
Rem ExhF Cap= 5% Use Tstat Spt= No Clg DB= 2.0°F Clg State= ____________ Clg Lo OAT Lk= 55°F
BSP DB= 0.010in Occ Clg DB= 2.0°F Clg Lo OAT Lk= 55ºF Htg State= ____________ Htg Lo OAT Lk= 0.0ºF
BSP Period= 5s Clg Period= 60s OAT Diff= 2.0°F INV Cmp Spd= XXX.X% Htg Hi OAT Lk= 55.0ºF
BSP Gain= 0.2s Clg Gain= 0.1 Clg Reset= None INV Spd Cmd= XXX.X% EffHtgOATLk= 55.0ºF
Max Spd Chg= 4% Clg PAT= 600s Min Clg Spt= 55.0°F Comp 3=_____________ OAT Diff= 2ºF
RFEF Ctrl Dly= 30s Max Clg Chg= 5.0°F Min Clg Spt @= 0 Prev Standby= _______ ► INV Period= 20s
Min Speed= 5% Occ Htg DB= 2.0°F Max Clg Spt= 65.0°F Compressor Limiting ► INV Gain= 2.5
MinExStrtTm= 120s Htg Period= 60s Max Clg Spt@= 100 Fault Code Details ►1 INV PAT= 10s
MinExStopTm= 120s Htg Gain= 0.1 Unocc Diff= 3°F INV Port Temp= XXX.XºF INV Max Chg= 15%
MinExOAPos= 5% Htg PAT= 600s INV Fin Temp= XXX.XºF IFB COMM STATUS ►2
MinExSAFCap= 10% Max Htg Chg= 5.0°F
INV Cmp Amps= XX.XA
ExhOnOAPos= 40%
REFRIG CIRCUIT STATUS Date/Time
ExhMxOAPos= 100%
PTS= XXX.Xpsi MM/DD/YYYY HH:MM:SS
Max Vent Spd= 100%
PTD= XXX.Xpsi
Max RFEF RPM= 2600 Compressor Limiting
4 Way Valve=__________
ECM Status= _________ Clg Press Lmtg=_______
RcvrSol Valve=_________
BP Sol Valve=_________ Htg Press Lmtg=_______
C Ratio Lmtg=_________
Ref DLT Lmtg=_________
INV Brd Lmtg=_________
INV Man Dsbl= Enable
Comp3 ManDsbl= Enable
IM 1058-5 97
Appendix – Keypad/Display Menu Structure
Service Menus
Timer Settings ►
Operating Hours ►
Save/Restore Settings ►
Active Alarms ►
Alarm Log ►
Alarm Configuration ►
Analog Input Status ►
Universal I/O Status ►
Digital Input Status ►
Digital Output Status ►
Network Input Status ►
Modbus Status ►
D3 Input Status ► Timer Settings Operating Hours Save/Restore Active Alarms
Sensor Offsets ► Service Time= 0min Supply Fan= XXXXXh Settings Alm Count: xx Clr Alms= No
Reset Counte= XXXX Start Up= 180s Ret/Exh Fan= XXXXXh Save Params= No +Alarm 1: Alarm Type ►
Recirculate= 180s Cmp Cooling= XXXXXh Rstr Params= No +Alarm 2: Alarm Type ►
Zero OA Time= 0min INV Comp= XXXXXh Rstr Factory= No ●
Tnt Override= 120min Comp 3= XXXXXh SaveToCard= No ●
Post Heat= 0s Heating= XXXXXh LoadFromCard= No ●
Pwd Timeout= 10min Cmp Heating= XXXXXh +Alarm 10: Alarm Type ►
Low DAT= 6min Economizer= XXXXXh
ClgStateDelay= 300s Tnt Override= XXXXXh
Bypass Valve= 300s Dehumid= XXXXXh
Clg Stg Time= 5min ER Wheel= XXXXXh
Htg Stg Time= 5min
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
98 IM 1058-5
Appendix – Keypad/Display Menu Structure
Alarm Log Alarm Configuration Analog Input Status Universal I/O Status Digital Input Status Digital Output Status
Log Count: xx Clr Log= No ► ALARM LIMITS MCB Al1= XXXXXXXX MCB X1= XXXXXXXX MCB DI1= ____________ MCB DO1= __________
+/-Alarm 1: Alarm Type ► Hi Disch Temp= 170°F MCB Al2= XXXXXXXX MCB X2= XXXXXXXX MCB DI2= ____________ MCB DO2= __________
+/-Alarm 2: Alarm Type ► Lo Disch Temp= 40°F MCB Al3= XXXXXXXX MCB X3= XXXXXXXX MCB DI3= ____________ MCB DO3= __________
● Hi Return Temp= 120°F MCB X4= XXXXXXXX MCB DI4= ____________ MCB DO4= __________
● ALARM OUT CONFIG MCB X5= XXXXXXXX MCB DI5= ____________ MCB DO5= __________
● Faults= Fast MCB X6= XXXXXXXX MCB DI6= ____________ MCB DO6= __________
+/-Alarm 10: Alarm Type ► Problems= Slow MCB X7= XXXXXXXX EMD DI1= ____________ MCB DO7= __________
Warnings= Off MCB X8= XXXXXXXX MCB DO8= __________
ALARM DELAYS EMB X1= XXXXXXXX MCB DO9= __________
Frz Delay Time= 30s EMB X2= XXXXXXXX MCB DO10= __________
Air Flw Ing=120s EMB X3= XXXXXXXX EMB DO1= __________
Sens Alm Dly= 30s EMB X4= XXXXXXXX EMB DO2= __________
Temp AlmDly= 30s EMB X5= XXXXXXXX EMB DO3= __________
ALARM CONFIG EMB X6= XXXXXXXX EMB DO4= __________
Emerg Stop= ManClr EMB X7= XXXXXXXX EMB DO5= __________
EMB X8= XXXXXXXX EMB DO6= __________
EMD X1= XXXXXXXX EMD DO1= __________
EMD X2= XXXXXXXX EMD DO2= __________
EMD X3= XXXXXXXX EMD DO3= __________
EMD X4= XXXXXXXX EMD DO4= __________
EMD X5= XXXXXXXX EMD DO5= __________
EMD X6= XXXXXXXX EMD DO6= __________
EMD X7= XXXXXXXX
EMD X8= XXXXXXXX
IM 1058-5 99
Appendix – Keypad/Display Menu Structure
BMS Communications
LON Set-Up ►
BACnet MSTP Set-Up ►
BACnet IP Set-Up ►
D-Net Set-Up ►
Network Unit Set-Up ►
Trending
Trending Ena= No
Apply Chgs= No
Sample Time= 300s
TrendOnOff= Off
Export Data= No
Clear Trend= Done
Points 1–8 (Fixed) ►
Points 9–24 (from List) ►
Points 25–27 (with IDs) ►
Points 28–30 (with IDs) ►
Points 1–8 (Fixed) Points 9–24 (from List) Points 25–27 (with IDs) Points 28–30 (with IDs)
Point 1= UnitSt Point 9= None Point 25 Point 28
Point 2= Clg% Point 10= None ID= F0AF0000 ID= F0AF0000
Point 3= Htg% Point 11= None Type= 0000 Type= 0000
Point 4= SAF% Point 12= None Mem Num= 0100 Mem Num= 0100
Point 5= OAD/Eco% Point 13= None Point 26 Point 29
Point 6= CtrlTmp Point 14= None ID= F0AF0000 ID= F0AF0000
Point 7= DAT Point 15= None Type= 0000 Type= 0000
Point 8= OAT Point 16= None Mem Num= 0100 Mem Num= 0100
Point 17= None Point 27 Point 30
Point 18= None ID= F0AF0000 ID= F0AF0000
Point 19= None Type= 0000 Type= 0000
Point 20= None Mem Num= 0100 Mem Num= 0100
Point 21= None
Point 22= None
Point 23= None
Point 24= None
100 IM 1058-5
Appendix – Keypad/Display Menu Structure
Figure 80: Optional Outdoor Air Monitor – Changing the System of Units
Enter
↑/↓ (Select) Enter (Move →) Enter (Move →) (Action, Move →→)
During
Normal Operation Esc (Move ←) Esc (Move ←) Esc
(Move ←←)
Set Up ↓↑
IP/SI=SI SYS ↑
Comm Set Up ↓↑
Sets system of units to S-I
(MPS, LPS, sq.M., Pa., °C)
Ethernet Set Up ↓↑
Diagnostics ↑
IM 1058-5 101
Appendix – Keypad/Display Menu Structure
Enter (Move →) Enter (Move →) Enter (Move →) Enter (Action, Move →→)
Esc (Normal Operation) Esc (Move ←) Esc (Move ←) Esc (Move ←←)
Set Up ↓↑
1
FS1=5000FPM ↓↑
1
LCD1 U/M=FPM ↓ 1
AR1=0.000 SQF ↓↑ 1
OUT1 U/M=FPM ↓↑ 1
OUT1=4-20mA ↓↑
1
FS1=10000FPM for GF1
or
1
FS1=5000CFM ↓↑
1
FS1=10000CFM for GF1
FS1=5000FPM ↓↑
LCD1 U/M=FPM ↓ AR1=0.00SQF ↑ OUT1 U/M=FPM ↓ 2
OUT1=0–10V ↓
FS1=10000FPM for GF1
or
Set area between In addition, “SW1” must be set
Displays airflow in FPM. 0.00 and 999.99 sq.ft. Area Outputs airflow in FPM. to the VDC position to change FS1=5000CFM ↓↑
affects the LCD display reading airflow output to 0–10VDC.
and output when set for CFM. FS1=10000CFM for GF1
2
OUT1=4–20mA ↑
102 IM 1058-5
Appendix – Keypad/Display Menu Structure
1
FILTER1=0 ↓↑ 1
FLOW BUFF=30 ↓↑ 1
ALT=0 ↓↑ 1
OUT2 TYP=TEMP↓↑ 1
OUT2=4-20mA ↓↑
Adjust Filter1? Set Flow Buff? Set Altitude Set Out2 Type? 3
Set Out2?
OUT2 TYPE=ALRM ↑ 3
OUT2=0-5V ↓↑
3
OUT2=4-20mA ↑
IM 1058-5 103
Daikin McQuay Training and Development
Now that you have made an investment in modern, efficient Daikin McQuay equipment, its care should be
a high priority. For training information on all Daikin McQuay HVAC products, please visit us at
www.DaikinMcQuay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin McQuay equipment is sold pursuant to its standard terms and conditions of sale,
including Limited Product Warranty. Consult your local Daikin McQuay Representative for warranty
details. Refer to Form 933-430285Y. To find your local Daikin McQuay Representative, go to
www.DaikinMcQuay.com.
Aftermarket Services
To find your local parts office, visit www.DaikinMcQuay.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinMcQuay.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinMcQuay.com.
Table of Contents
Introduction
Login
Initial Login
Upon being given access to one or more Daikin Applied units, On only the first login to a particular site, the user is asked to
the user will receive an e-mail directing him or her to login to confirm their Account Information (Figure 4). All information
the system for the first time (Figure 1). Clicking the link in the should be verified, and modified as necessary. Some fields,
e-mail notification brings the user to a webpage prompting noted by a red asterisk, are required, and must have data
to create a password (Figure 2). The password should be entered before proceeding. Clicking ‘Confirm’, takes the user to
entered, then confirmed. Clicking the ‘Save’ button sets the the Site List for the particular site.
new password. When first assigned, all units accessible by the user are
After saving the newly created password, the user is prompted grouped as, ‘Unassigned’ (Figure 5). This indicates that the
to select the desired user role for access (Figure 3). Users individual user has not assigned them to any site. The user
can be provided with any of four roles: Customer, Customer should create a new site, then associate the unit to the site. See
Administrator, Technician, and Technician Administrator. Roles the “Technician Administrator” and “Customer Administrator”
are assigned by an equipment administrator based on the sections for details on managing sites. These sections also
subscription plan purchased and the level of access desired provide all instructions relevant to each of these roles.
for individual users. The difference between a standard user
role and an administrator user role is that administrators can Subsequent Login
invite other users and assign them to specific equipment. An
For subsequent logins, the user only need open a browser
equipment administrator cannot assign a role for which the
and enter the web address for the Intelligent Equipment site.
subscription was not purchased. In short, if only the Customer
As with the initial login, the user will be prompted to select a
subscription plan was purchased for a unit, users assigned
user role for access. See the “Technician Administrator” and
to that unit will only have access to the Customer and/or
“Customer Administrator” sections for details on managing
Customer Administrator roles.
sites. These sections also provide all instructions relevant to
each of these roles.
Technician Administrator
Sites
After logging into the Intelligent Equipment site using either The next screen allows the administrator to define the new
the Technician or Technician Administrator role, the User user’s access to one or more units (Figure 10). Remember
Interface (UI) will display the “Sites” screen (Figure 6), which is that ‘Admin’ access allows the user to invite other users to a
a listing of all sites associated with the user. From this screen, particular unit. Once all units and roles have been selected,
individual site messages are shown, general site information, clicking the ‘Submit’ button finalizes the process. The new user
including a list of units, becomes available by clicking on will receive an email notification of the newly granted access.
the ‘Quick View’ button, and more detailed site information Reports – Selecting ‘Reports’ displays a list of available
becomes available by clicking the ‘View Site’ button. This reports. Once a report type is selected, the screen displays
page also provides the opportunity to add a site to the current several configurable parameters used to customize the report.
hierarchy by clicking the ‘Create Site’ button; see section titled, In the case of an Operational Activity and Settings Change
“Create a Site (3)” on page 9. Report (Figure 11), the user can filter the display by user, unit,
action (such as login, setpoint changes, etc.), and site. The
User Profile (1) user can also filter by a specific date range, using the ‘Time
The “User Profile” button indicates the name of the current Period’ configuration box. By default, all activity is displayed.
user, and the role that was chosen for the current login. By clicking the ‘Export’ button, the user can generate a
Clicking the button reveals a list of actions associated with comprehensive list of all user activity and export the report in
managing a user’s profile (Figure 7). Comma-Separated Values (.csv) format.
Administration – If the logged in as a Technician Profile –Selecting ‘Profile’, under the User Profile button,
Administrator, this selection allows the user to provide other displays Account Information (Figure 12) and allows for
users access to specific units. Making this selection reveals a changing personal information, address information,
“Units” submenu. Clicking the ‘Units’ submenu opens the “Unit organizational information, and passwords. After making the
Overview” screen, which lists all units to which the current user desired changes, the ‘Save’ button must be clicked before they
has access (Figure 8). take effect.
To provide a user access to a specific unit from this list, click Settings – Selecting ‘Settings’, under the User Profile button,
the ‘Invite User’ button. This displays the “Invite User” screen, allows the user to choose English or Metric units of measure
which prompts the administrator to enter an e-mail address for display within the User Interface. Changes do not take
for the new user. After entering the e-mail address, clicking effect until the ‘Save’ button is clicked.
the ‘Search’ button to the right of the field begins a search Log Out – Selecting ‘Log Out’, under the User Profile button,
for the user within the database. If the user does not exist in logs the user out of the current session, and returns them to
the database, a prompt appears asking to add the new user the Intelligent Equipment start page.
(Figure 9).
1 2
5
4 6 7 8 9
Unit Dashboard
The Unit Dashboard (Figure 22) allows the user to view Refresh (C)
current unit status, manage unit schedule, review the unit
alarm log, modify unit setpoints and control, and monitor unit Clicking the ‘Refresh’ button reloads the current display with
live data. Screen content is driven by button selections on the updated data.
left of the User Interface (UI). The initial screen provides a
comprehensive unit overview, with other buttons allowing the Alarm Log (D)
user to choose information specific to the fan, cooling section, The “Alarm Log” header lists the highest priority active alarm.
heating section, maintenance recommendations, and unit Clicking the ‘Alarm Log’ button allows the user to review
controls. Not all button categories apply to all units. the entire list of active and recent unit alarms (Figure 24).
Each alarm provides a Date, User Name, Alarm Type, and
Current Schedule (A) Alarm Status. If an alarm is no longer active and has been
This section indicates the current active schedule for the unit. acknowledged, its status will show as, “Clear”. If an alarm is
still active, but has been acknowledged, its status should read,
“Acknowledged”. Clicking the ‘Unit Details’ link returns the user
Change Schedule (B) to the Unit Dashboard.
Clicking the ‘Change Schedule’ button allows the user to
select from a list of standard schedules, or create a custom Subscription Status (E)
schedule. If Custom Schedule is chosen, a new dialog box will
open, allowing the user to choose the days and start/end times This section indicates the current subscription status for the unit.
for the schedule, and to give it a name (Figure 23). Clicking
‘Save’ will only save Custom Schedule settings. Clicking ‘Apply
Schedule’ will save and apply the new schedule.
A D
E
B C
Overview Screen
With the “Overview” button selected, a labeled unit graphic is Cooling
displayed (Figure 25). The user can monitor live unit status,
temperatures, capacities, power, and upcoming maintenance. Clicking the ‘Cooling’ header expands a list of current cooling
operating parameters, including the Occupied and Unoccupied
Cooling Setpoints. Clicking the header a second time will
Upcoming Maintenance collapse the list.
A description of upcoming maintenance, along with a date of
last maintenance, is displayed beneath the unit graphic. Heating
Clicking the ‘Heating’ header expands a list of current heating
Overview Info operating parameters, including Occupied and Unoccupied
The “Overview Info” button is selected by default and displays Heating Setpoints. Clicking the header a second time will
the unit graphic. collapse the list.
Documents Power
Clicking the ‘Documents’ button provides a list of manuals Clicking the ‘Power’ header expands a list of current power-
specific to the unit model, along with hyperlinks to access related operating parameters, including Hourly and Daily Power
those documents in the cloud (Figure 26). usage. Clicking the header a second time will collapse the list.
Economizer
Clicking the ‘Economizer’ header expands a list of current
economizer operating parameters, including Economizer
Status and Outside Air Temperature. Clicking the header a
second time will collapse the list.
Air Screen
With the “Air” button selected (Figure 27), a labeled fan graphic Operating Hours
is displayed, and the user can monitor unit temperatures,
statuses, setpoints, and run hours. Clicking the ‘Operating Hours’ header expands a list of current
operating hours for the Economizer and Supply Fan. Clicking
the header a second time will collapse the list.
Fan
The “Fan” button is selected by default and displays the fan Figure 28: Airflow Through Unit
section.
100% Econ
Clicking the ‘100% Econ’ button displays a graphic of the
airflow through the unit (Figure 28).
Unit Overview
Clicking the ‘Unit Overview’ header expands a list of several
current unit operating parameters, including Air Flow Status,
Economizer percentage, Economizer Status, Unit State, and Unit
Status. Clicking the header a second time will collapse the list.
Sensor Setpoints
Clicking the ‘Sensor Setpoints’ header expands a list of current
temperatures, temperature setpoints, pressures, pressure
setpoints, fan capacities, fan speeds, economizer capacities,
and economizer setpoints. Clicking the header a second time
will collapse the list.
Measured Calculated
Clicking the ‘Measured Calculated’ header expands a list of
several current unit operating parameters, including Duct High
Limit switch status, Space Temperature, Fan Speed and VAV
Box Output status. Clicking the header a second time will
collapse the list.
Refrigeration Screen
With the “Refrigeration” button selected, a labeled refrigerant Measured Calculated
system graphic is displayed (Figure 29), and the user can
monitor unit temperatures, statuses, setpoints, and run hours. Clicking the ‘Measured Calculated’ header expands a list of
Depending on unit model, a second close-up view of the several current unit operating parameters, including Cooling
compressor section may be available. Capacity, Cooling Status, Outdoor Air Temperature, and
several refrigerant temperatures. Clicking the header a second
time will collapse the list.
Unit Overview
Clicking the ‘Unit Overview’ header expands a list of several Operating Hours
current unit operating parameters, including Unit State, Unit
Status, and Defrost status. Clicking the header a second time Clicking the ‘Operating Hours’ header expands a list of current
will collapse the list. operating hours for compressor(s). Clicking the header a
second time will collapse the list.
Sensors Setpoints
Clicking the ‘Sensors Setpoints’ header expands a list of current
temperatures, temperature setpoints, and refrigerant pressures.
Clicking the header a second time will collapse the list.
Maintenance Screen
With the “Maintenance” button selected, the user can view Trends
upcoming maintenance, log maintenance activity, and view
trended temperature data (Figure 31). Clicking the ‘Trend’ button displays trended temperatures
for the unit. Data can be viewed for the current hour, day,
month, or year by clicking the appropriate button. Clicking
Maintenance Info the ‘Customize’ button enables the Start and End Date
Clicking the ‘Maintenance Info’ button displays a list fields, allowing the user to enter a trend for a specific date
of upcoming maintenance and a list of recommended range (Figure 34 on page 20). The default trend displays
maintenance intervals. Discharge Air Temperature, Outside Air Temperature, and
Return Air Temperature, but more data points can be added
Log Maintenance to the graph by clicking the ‘Change Data Trends’ button, then
selecting the desired additional points (Figure 35 on page
Clicking the ‘Log Maintenance’ button displays a maintenance
20). Selecting the ‘Graphs’ button also allows the user to
log entry form (Figure 32) and a history of logged maintenance.
select from a pre-defined set of graphed points.
First, the user must choose what type of maintenance to log,
Weekly, Monthly, Bi-Monthly, Four Times a Year, Twice Yearly,
Yearly, or Customer Call, then select the services that were
performed. Additional fields to complete include, Service Date,
Contact Number, Comments, and an indication of further
service being required. An image file, such as a copy of a
service order, can also be attached to the log entry. In addition,
a notification e-mail message can be sent using the “Send
Message” button. The entry is not recorded until the user clicks
the ‘Submit’ button. The current user logged into the system is
automatically tagged as having entered the maintenance issue.
The history of logged maintenance appears at the bottom of
the “Log Maintenance” screen (Figure 33).
Controls Screen
With the “Controls” button selected, the user can monitor a Capacity
number of temperature, pressure, occupancy, mode, and
capacity setpoints, and monitor live unit status, temperatures, Clicking the ‘Capacity’ button allows the user to raise and
and capacities. lower the Supply and Return Fan Capacities, Cooling Capacity,
Heating Capacity, and Economizer Capacity (Figure 38 on
page 22). Prior to making any setting changes, the user
Setpoints Screen should be familiar with the operation manual for the particular
Clicking the ‘Setpoints’ button allows the user to raise and unit.
lower the Discharge Air setpoints, Occupied Changeover
Within the “Capacity” screen, highlighting a question mark icon
setpoints, Duct Pressure setpoint, and Building Pressure
will provide context specific help. Changes do not take effect
setpoint (Figure 36). Prior to making any setpoint changes,
until the “Save Changes” button is clicked. Clicking ‘Reset’
the user should be familiar with the operation manual for the
reverts the settings to their previous values. If desired, clicking
particular unit.
the ‘Send Message’ button allows the user to send an e-mail
Within the “Setpoints” screen, highlighting a question mark informing others of any changes.
icon will provide context specific help. Changes do not take
effect until the “Save Changes” button is clicked. Clicking Unit Overview
‘Reset’ reverts the setpoints to their previous values. If desired,
clicking the ‘Send Message’ button allows the user to send an Clicking the ‘Unit Overview’ header expands a list of current
e-mail informing others of any changes. unit operating parameters, including Occupancy Mode, Air
Flow Status, Unit State, and Unit Status. Clicking the header a
second time will collapse the list.
Operations Screen
Clicking the ‘Operation’ button allows the user to change the Sensors Setpoints
unit “Occupancy and Operation” modes (Figure 37 on page
22). Prior to making any setting changes, the user should be Clicking the ‘Sensor Setpoints’ and ‘Measured Calculated’
familiar with the operation manual for the particular unit. values headers expands a list of current unit capacities,
temperatures and setpoints. Clicking the header a second time
Within the “Operations” screen, highlighting a question mark will collapse the list.
icon will provide context specific help. Changes do not take
effect until the “Save Changes” button is clicked. Clicking
‘Reset’ reverts the settings to their previous values. If desired,
clicking the ‘Send Message’ button allows the user to send an
e-mail informing others of any changes.
Customer Administrator
Sites
After logging into the Intelligent Equipment site using either the The next screen allows the administrator to define the new
Customer or Customer Administrator role, the User Interface user’s access to one or more units (Figure 43 on page
(UI) will navigate to the “Sites” screen (Figure 39), which is a 24). Remember that ‘Admin’ access allows the user to
listing of all sites associated with the user. From this screen, invite other users to a particular unit. Once all units and
individual site messages are shown, general site information roles have been selected, clicking the ‘Submit’ button
becomes available by clicking on the ‘Quick View’ button, finalizes the process. The new user will receive an email
and more detailed site information becomes available by notification of the newly granted access.
clicking the ‘View Details’ button. This page also provides the Profile – Selecting ‘Profile’, under the “User Profile” button,
opportunity to create a new site by selecting the ‘Create Site’ displays Account Information (Figure 44 on page 25) and
button; see section titled, “Create a Site (3)” on page 26. allows for changing personal information, address information,
organizational information, and passwords. After making the
User Profile (1) desired changes, the “Save” button must be clicked before they
The “User Profile” button indicates the name of the current take effect.
user, and the role that was chosen for the current login. Settings – Selecting ‘Settings’, under the “User Profile” button,
Clicking the button reveals a list of actions associated with allows the user to choose English or Metric units of measure
managing a user’s profile (Figure 40 on page 24). for display within the User Interface. Changes do not take
Administration – If the logged in as a Customer Administrator, effect until the “Save” button is clicked.
this selection allows the user to provide other users access to Log Out – Selecting ‘Log Out’, under the “User Profile” button,
specific units. Making this selection reveals a “Units” submenu. logs the user out of the current session, and returns them to
Clicking the ‘Units’ submenu opens the “Units Overview” the Intelligent Equipment start page.
screen, which lists all units to which the current user has
access (Figure 41 on page 24).
To provide a user access to a specific unit from this list, click
the ‘Invite User’ button. This displays the “Invite User” screen,
which prompts the administrator to enter an e-mail address
for the new user. After entering the e-mail address, clicking
the ‘Search’ button to the right of the field begins a search
for the user within the database. If the user does not exist in
the database, a prompt appears asking to add the new user
(Figure 42 on page 24).
1 2
5
4 6 7 8
Figure 41: Units Overview Screen Figure 42: Prompt to Create a New User
Site Dashboard
The “Site Dashboard” (Figure 55) displays the critical building/ Once the details have been added for the site, two new items,
site information, including building status information, HVAC “View Details” and “Setup Meters”, appear in the Building
summary information, building information, weather forecast, Status section (Figure 57). Clicking ‘View Details’ directs the
comfort index, resources, and equipment metrics. user the “Energy Star Information” screen, which allows the
user to update property information, add meters, and set
Building Status energy targets. Clicking the ‘Setup Meters’ button takes the
The Building Status portion of the Site Dashboard displays basic user directly to the ‘Meters & Consumption’ tab of the “Energy
utility usage information as well as overall building Energy Star Star Information” screen. Until usage data is uploaded, the
Score. The information in this portion of the dashboard can corresponding fields will read, “Not Available”.
only be generated by clicking the ‘Subscribe To Energy Star’
button, and entering general building and utility information
(Figure 56). It is important to note that this does not create a
portfolio in Energy Star’s Portfolio Manager, it simply allows
Intelligent Equipment to calculate scores to display within the
User Interface. Once all information is entered on all three tabs,
clicking the ‘Save’ button returns the user to the Site Dashboard.
Clicking the ‘Cancel’ button cancels any changes.
Setup Meters
The “Meters & Consumption” tab of the “Energy Star Figure 58: Meters and Consumption Tab
Information” screen (Figure 58) allows the user to add their
utility meter information.
The user must first add the desired meter by clicking the
corresponding ‘Add’ button, then give the meter a name
(Figure 59).
Once all desired meters are added and given names, clicking
the ‘Submit’ button provides each of the meters with an ‘Upload
Data’ button (Figure 60). All data must be uploaded using the
template provided by clicking the ‘Download Template’ button
(Figure 61). The template is in Comma-Separated Values (.csv)
format, and can be edited using a number of readily available
spreadsheet software programs.
Once all data is entered into the template, the file should be
saved. Following this, clicking the ‘Upload Data’ opens a dialog
box, allowing the user to navigate to and select the desired file.
Once the file is selected, the upload begins immediately, and a
confirmation message appears when complete (Figure 62).
After all desired meter data is uploaded, clicking the ‘Building’
link near the top of the screen returns the user to the “Site
Dashboard”. An Energy Star score should now be calculated,
and all meters with uploaded data should display usage
comparison to the previous month or year (Figure 63). If enough
data is available, the comparison will be year-over-year.
The user can also choose to display a “Target Energy Star”
score by choosing this option on the “Targets” tab of the
“Energy Star Information” screen. Click the ‘View Details’
button, then select the ‘Targets’ tab. The user then clicks the
‘Edit’ button, which makes the “Target Metric” field editable. Figure 59: Adding a Meter
The user can choose from three different reports; Target
Energy Star Score, Target Percentage better than Baseline,
and Target Percentage better than Median (Figure 64).
The Target Percentage better than Baseline option makes
a comparison between current and baseline performance.
The Target Percentage better than Median option makes a
comparison between the current building’s performance and
that of similar size and usage characteristics.
Once the “Target Metric” is decided, the user must then enter
a “Target Value” for the metric. Clicking the ‘Save’ button sets Figure 60: Upload Data Button
the target. After this, clicking the ‘Building’ link near the top of
the screen returns the user to the “Site Dashboard”, where the
“Target Score” should now be visible (Figure 65).
HVAC Summary
The “HVAC Summary” portion of the Site Dashboard (Figure Figure 66: HVAC Summary
66) serves as a quick reference to current unit/system status
information, including unit status, suggested maintenance
status, and live power.
The option to display further details is available for the unit
status, maintenance, and live power displays in the section.
By clicking the ‘View Details’ button under the “Unit Status”
item, a pop-up will appear displaying information including unit
name, alarm status, unit status, current occupancy, control
temperature, and subscription status (Figure 67). By default, Figure 67: Unit Status Information
the information for all units is displayed.
By clicking the ‘View Details’ button under the “Maintenance”
item, the user can access the Maintenance Details for the site
(Figure 68).
Any recommended maintenance is listed for each unit, a history
of maintenance logs for the site is presented. To search for logs
during a specific time frame, the user only needs to enter a start
and end date, after which, the UI will automatically refresh to
display only log items occurring between those dates. By clicking
the ‘Add Servicing Entity’ button, the user can add reference
information for the site service provider (Figure 69). The user
can also send an e-mail message from the “Maintenance
Details” screen using the ‘Send Message’ button.
By clicking on the ‘View Details’ button under the “Live Power
Usage” item, a pop-up will appear displaying unit name, unit
status, and current power usage for all units (Figure 70).
By default, the HVAC Summary section displays data for all
units associated with the site. However, the data can be filtered
to a specific unit by choosing it from the unit list selector in
the upper, right corner of the HVAC Summary section (Figure
71). If this is done, all data displayed in the “Unit Status”,
“Maintenance”, and “Live Power” usage items is restricted
to the selected unit. Additionally, all information displayed by
clicking the ‘View Details’ button under each item is also filtered
to the specific unit.
Figure 69: Adding a Service Entity Figure 70: Live Power Details
Sustainability Index
The “Sustainability Index” header of the Site Dashboard
displays current CO2 Emissions for the site, and a comparison
to the previous month or year (Figure 76). The data will
automatically display year-over-year comparison once
enough meter data has been entered for the Site. Clicking the
‘Sustainability Index’ header once expands the data for display,
while clicking it a second time collapses it.
Resources
The “Resources” header of the Site Dashboard displays a list
of links to resources on Green Buildings.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your
local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.