Professional Documents
Culture Documents
190396B - Assignment 02
190396B - Assignment 02
190396B - Assignment 02
LECTURER IN CHARGE:
Prof. M.T.R. Jayasinghe
NAME : M.A. Muhammad
INDEX NO : 190396B
MODULE : CE 4312
Floor Area
• 75% usable floor area
• 25% service area
Take total floor area = 1200 m2
Therefore;
• Usable floor area = 1200 x 0.75 = 900 m2
• Service core area = 1200 x 0.25 = 300 m2
FRONT ELEVATION
3D VIEW OF THE BUILDING
GROUND FLOOR PLAN
LAYOUT OF A TYPICAL FLOOR (2nd-20th floors)
3) DESIGN OF HORIZONTAL AND VERTICAL CIRCULATION
Horizontal Circulation
Vertical Circulation
1. Staircases
2. Lift System
Total usable floor area of the building = 900 m2
Building type = Investment downtown
Area allocation per person = 10m2
900
Hence population per floor = = 90 persons / floor
10
• Within the average interval seconds, this population requires a very high car size. Therefore, zoning
system is recommended.
• The lift system can be designed with having two zones. The first zone has been selected from ground
floor to 10th floor. The second zone has to be from 10th to 20th floor.
For first 10 floors;
For 10 upper floors, the total population = 10 x 90 = 900
The population handled in 5 mins as 12% = 900 x 12% = 108 people
Interval can be 36 seconds with capacity of lifts as 16.
Assume lift speed = 4m/s
The corresponding round trip time with 4m/s lifts = 100 seconds
Floor to floor height = 3.6 m
Hence; No. of lifts = 100/36 = 2.78 lifts
The inside size of the lift (From figure 5.3) = 2100 mm x 1300 mm
The shaft size required = 2550 x 2100 mm
Minimum width of the lobby = 1.5 D
= 1.5 x 1300 = 1950 mm (2.1 m)
The inside size of the lift (From figure 5.3) = 2100 mm x 1300 mm
The shaft size required = 2550 x 2100 mm
Minimum width of the lobby = 1.5 D
= 1.5 x 1300 = 1950 mm (2.1 m)
Lift and Staircase Arrangement
2100
2550
Staircase Plan and Cross Section Views
ARRANGEMENT OF WASHROOMS
DESIGN OF SANITARY APPLIANCES
Male 3 3 2
Female 5 5 -
20th floor
19th floor
18th floor
17th floor
16th floor
15th floor
14th floor
13rd floor
12nd floor
11th floor
10th floor
9th floor
8th floor
7th floor
6th floor
5th floor
4th floor
3rd floor
2nd floor
1st floor
4) DESIGN OF WATER SUPPLY SYSTEM
Assumptions;
o Minimum requirement of water per person =45 l/ employee (with canteen facilities)
o 24-hour uninterrupted water flow
Assume total allowances are 40% (for fire safety system and other allowances.)
140
Therefore, capacity of water sump = 81 x 100 = 113.4 m3
Assume;
• As this is a high-rise building, brake pressure tanks are provided at intermediate floors of the
building.
• This will serve maximum of 5 floors
• Duplicate pump system is provided.
= 20.25 m3
Wash basins 1 8 8
Water closets 1 8 8
urinals 3 2 6
Assume brake pressure tank at the topmost level (20th floor) is 3m above the floor level.
Pipe No. 1
No. of appliances = 18 x 5 = 90
Total loading units = 22 x 5 = 110
Expected discharge flow rate = 1.4 liter/s (Figure 5.1)
Pipe No. 2
• Assume 28mm outer diameter PVC pipes are used.
No. of appliances = 3
Total loading units = 3
Expected discharge flow rate = 0.35 liter/s (figure 5.1) (minimum flow rate)
Pipe No. 3
• Assume 28mm outer diameter PVC pipes are used.
No. of appliances = 10
Total loading units = 14
Expected discharge flow rate = 0.4 liter/s (figure 5.1)
Pipe No. 4
• Assume 28mm outer diameter PVC pipes are used.
No. of appliances = 5
Total loading units = 5
Expected discharge flow rate = 0.35 liter/s (figure 5.1) (minimum flow rate)
Since the head will keep increasing for other floors, this pipe arrangement will be okay for other floors
as well. The calculation can be done for the remaining floors as mentioned above.
Horizontal pipes:
From table 8.4(b);
Total discharge units for pipe 3 = 14 x 8 + 0.3 x 2 = 112.6
Pipe 03 diameter =76 mm
Total discharge units for pipe 4 = 3 x 5 = 15
Pipe 04 diameter =63 mm
Total discharge units for pipe 2 = 3 x 3 = 9
Pipe 02 diameter =50 mm
Ventilation pipe
Provide 75mm diameter ventilation pipes to prevent the loss of trap seal.
User Per floor For whole Total All waste Total Blackwater Total Greywater
number building (l/ day) (l/ day) (l/ day)
Daytime 81 1620 81000 48600 32400
employees
Overnight 9 180 36000 9000 27000
employees
Customers/ 14 280 2800 1400 1400
Visitors
119800 59000 60800
Therefore,
(Assume peak flow rate is 4 times the average hourly flow)
• Blackwater flow = (59000 x 4)/(1000 x 24 x 3600) = 2.731 x 10-3 m3/s
• Grey water flow = (60800 x 4)/(1000 x 24 x 3600) = 2.815 x 10-3 m3/s
• Continue the soil pipe (125mm diameter) for the below ground water for black water discharge
pipes.
• Continue the vertical waste pipes (100mm diameter) for the below ground water for grey water
discharge pipes.
Chezy’s formula
V = C√(mi)
m = hydraulic mean radius
C – Chezy’s constant (assume as 55)
i = slope
Here if we use the same equation, we use to calculate the minimum volume of a septic tank for a
residential building, for the 20-story building we get a minimum volume as:
Minimum volume of septic tank for a residential building = 2000+180p
P = no. of people
Therefore, minimum volume of septic tank = 2000+180 x (90 x 20) = 326000l = 405.2m3
This is not practically feasible to be constructed at the same sight (below ground water system
with sufficient access)
Therefore, considering this is in the Colombo area, we can connect the sewer line to the main
sewer system in the Colombo area.
Below ground water disposal system with 100m length from the building.
Here the building sewer line will be connected to the main sewer line which is at 100m length from
the building. IT is not necessary to design septic tanks, soakage pits etc. in this case. The only
designs that will be needed will be of manholes and inspection chambers.
7) AIR CONDITIONING SYSTEM
Since this is an office building, to provide as many offices as possible with individual AC units,
consider smaller capacity split type AC units.
Since the total electricity demand is quite high, the building will need a sub-station, this substation
is fed by high voltage cables. The substation will consist of a transformer and the switches
Fire controlling capacity will be achieved as passive control and active control
Passive control
Use of reinforced concrete as wall material to have good fire resistance
Design fire resistance – One hour
Active control
1. Placement of fire extinguishers – Provide fire extinguishers at appropriate locations for each floor
3. Sprinkler system
• Use wet system sprinklers on the building
• Fire hazard class – Extra light hazard
Spacing of sprinklers
S – design spacing of sprinklers on range pipes
D – distance between adjacent rows of sprinklers
S, D < 4.6 (for extra light hazard)
S x D ≤ 21m2 (for extra light hazard)
Therefore, consider S = 4m, D = 5m
Since this is office building there may not be many equipment that generate high vibrations. However,
there may be heavy equipment. These should be located at the ground floor.
Lift motor will be situated on the 11th floor and the roof level
Service runs
Here we provide a dedicated shaft to facilitate the service runs. Also, a false ceiling will be used as
an efficient way to hide the service runs. These are hung from a bracket and fixed to the underside
of the floor slab, supporting a series of interlocking metal sections that forma grid. When the grid
has been fitted, installations can be made for lighting, speakers and other equipment which needs to
be connected to the ceiling.
The service runs going through walls will be sealed to minimize the chance of fire spreading. Service
ducts will be provided to conceal services and to facilitate inspection, repair and alterations of the
services. It also reduces the noise and protects the services from danger.