C-170-5381-051 Protrection Relay Coordination Report and Setting Table (88SS14) Rev.0
C-170-5381-051 Protrection Relay Coordination Report and Setting Table (88SS14) Rev.0
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
0 F
For Construcction S.J.LEE D
D.D.LEE K.H.YAN
NG Y.S.YI 0 AUG. 2015
03. 5
Prep
pared Apprroved by
Rev Descriptio
on hecked by
Ch Approved
d by Date
b
by PM
1 OF 14
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
REV
VISION H
HISTORY
Revission Total Number L
List of Updateed/ Modified Sections
Number Purpose of Sheets (if any)
HOLD LIST
L
2 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
TABLE OF CO
ONTENTS
1.0 IN
NTRODUCT
TION
1.1 PURPOS
SE
1.2 SOFTWA
ARE
1.3 REFERE
ENCE
2.0 SY
YSTEM DE
ESCRIPTIO
ON
7.0 AT
ATTACHEM
MENT LIST
ATTACH
HMENT-1 PROTECTION SETT
TING PHIL
LOSOPHY
ATTACH
HMENT-2 PROTECTION RELA
AY SETTIN
NG CALCU
ULATION
ATTACH
HMENT-3 UM FAULT LEVEL
MINIMU L CA
ALCULATIO
ON
ATTACH
HMENT-4 PROTECTION RELA
AY SETTIN
NG TABLE
ATTACH
HMENT-5 URRENT CH
TIME CU HARACTE
ERISTIC CU
URVE
3 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
1.0 INTRODU
UCTION
1.1 PURPOSE
E
The purpose
e of this stud
dy is to ensurre that, in the
e event of an
ny abnormalitty or fault in a
any part of th
he
electrical ne
etwork, the fa
aulty part can
n be isolated
d rapidly and consistentlyy, so that the impact on th
he
rest of the ssystem is min
nimized and a
as much as p
possible the healthy
h part is left intact.
Besides pro
oviding brief details on tthe different relays used in SRIP an
nd outlining ttheir operatio
on
principles th
he key setting
g parameterss for the prottection relayss are also me
entioned in tthis philosoph
hy
document.
This protecctive relay coordination
c study is ap
pplied to 33
3kV,6.6kV, 0
0.415kV systtem for SS1
14
substation fo
or the OMAN
N SRIP Proje
ect.
1.2 SOFTWAR
RE
ETAP Star - Protective Device
D Coord
dination Softw
ware (Version
n 12.0) of Op
peration Tech
hnology, Inc. is
used to devvelop the brie
ef model and to perform th
he Electrical Protection C
Co-ordination Studies.
1.3 REFEREN
NCE
1) Instruction manual and Technical Guide
G of rela
ay manufactu
urer (SIEMEN
NS, ABB)
2000
2) ANSI / IEEE C37.91-2
IEEE Guid
de for Protecctive Relay Applications to
o Power Tran
nsformers.
3) ANSI / IEEE C37.97-1
1979
IEEE Guid
de for Protecctive Relay Applications to
o Power Systtem Buses.
4) IEEE C37
7.96-2000
IEEE Guide
e for AC Mottor Protection
n.
5) IEEE std 242-2001
IEEE Recommended Practice for Protection and coordination of Industrrial and Com
mmercial Pow
wer
Systems.
6) IEEE std 141-1993
IEEE Re
ecommended
d Practice for Electric Pow
wer Distributio
on for Industrial Plants.
7) Simens R
Relay Catalog
gue.
mer vendor data
8) Transform
9) Motor datta vendor datta
10) Single line diagram
11) Electrica
al load list
12) Short Circuit Studiess
13) Load Flo
ow Studies
4 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
The OETC w
will be in a flloating mode
e with the GT
TGs and STG
Gs of both SR
R and SRIP catering to th
he
entire load. The OETC w
will only provvide power in
n case of failu
ure of GTG/S
STG or during start up. It is
also envisaged that botth SR and S
SRIP captive
e generation can feed ea
ach other with partial loa
ad
shutdown if required.
ation conside
The operating configura ered here is w
worst operating condition
n when OETC
C is in floatin
ng
condition, G
GTGs and ST
TGs are operating in parrallel and fee
eding to SR+SRIP load. M
Maximum fau
ult
currents at all switchboa
ards as per the Short Circuit Studiess (refer refere
ence list) forr this case a
are
considered as the basis for this studyy.
The power g
generation and distributio
on throughout the plant is 50Hz.
Following arre the Grounding method
ds provided a
at various volttage levels,
1) 33 kV T
Transformer neutral :
Neutra
al Earthing R
Resistor that e
earth fault cu
urrent is restrricted to 200 A
Amp.
2) 6.6 kV Transformerr neutral
Neutra
al Earthing R
Resistor that e
earth fault cu
urrent is restrricted to 400 A
Amp.
3) 415 V Transformer
T neutral
Solid E
Earthing.
5 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
otherwise re
elays are set to clear faultts as rapidly as possible.
Phase over current prote
ection is also
o used to provvide overload
d protection ffor power fee
eders.
The settingss provided fo
or the O/C and
a E/F relayys shall be checked
c for the system minimum fau
ult
current.
Pannel Relay
P
Panel Name Rating Level Funcction Remark
Description Model
33kV Inccoming 14
4SW201L‐L1 1250A 33kV 7SJ64 50/51/27/25
5
33kV 7SD61 87C By Petrofaac
33kV Inccoming 14
4SW201R‐R1 1250A 33kV 7SJ64 50/51/27/25
5
33kV 7SD61 87C By Petrofaac
33kV Bu
us‐Tie 14
4SW201‐T/S 1250A 33kV 7SJ64 50/51/25/27
7‐L
33kV 7SJ62 27‐R
33kV 7SR23 87A
33kV 7SR23 87B
14TR201A 14
4SW201L‐L2 20MVA 33kV 7SJ64 50/51/51G/5
51N
33kV 7UT61 87T
14TR201B 14
4SW201R‐R2 20MVA 33kV 7SJ64 50/51/51G/5
51N
33kV 7UT61 87T
KM‐170
02A 14
4SW201L‐L3 20MVA 33kV 7SJ64 50/51/50N/5
51N/51G
33kV 7UM62 87M/51G/RTTD
33kV 7UT61 87T/64R
SEL
Exitation Panel 33kV 27M/46/47//49/51LR/66 By Vendor
710‐5
KM‐170
02B 14
4SW201R‐R3 20MVA 33kV 7SJ64 50/51/50N/5
51N/51G
33kV 7UM62 87M/51G/RTTD
33kV 7UT61 87T/64R
SEL
Exitation Panel 33kV 27M/46/47//49/51LR/66 By Vendor
710‐5
KM‐170
02C 14
4SW201L‐L4 20MVA 33kV 7SJ64 50/51/50N/5
51N/51G
33kV 7UM62 87M/51G/RTTD
33kV 7UT61 87T/64R
SEL
Exitation Panel 33kV 27M/46/47//49/51LR/66 By Vendor
710‐5
Spare (TTR) 14
4SW201L_L5 1250A 33kV 7SJ64 50/51/51G/5
51N ‐
33kV 7UT61 87T ‐
Spare (TTR) 14
4SW201R‐R4 1250A 33kV 7SJ64 50/51/51G/5
51N ‐
33kV 7UT61 87T ‐
6.6kV
14
4SW301‐L1 20MVA 6.6kV REB611 64R
ng
Incomin
50/51/50N/5
51N/51G/
6.6kV REF615
60/25/27
6 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
Pannel Relay
P
Panel Name Rating Level Funcction Remark
Description Model
6.6kV
14
4SW301‐R1 20MVA 6.6kV REB611 64R
ng
Incomin
50/51/50N/5
51N/
6.6kV REF615
51G/60/25/2
27
6.6kV Bus‐Tie 14
4SW301‐LR 20MVA 6.6kV REF620 50/51/25/60
0/27‐L
6.6kV REU615 27‐R
14TR301A 14
4SW301‐L2 1.6MVA 6.6kV REF615 50/51/50G/5
51G
14TR302A 14
4SW301‐L3 1.6MVA 6.6kV REF615 50/51/50G/5
51G
14TR303A 14
4SW301‐L4 1.6MVA 6.6kV REF615 50/51/50G/5
51G
27M/46/47//49/51LR/
PM‐170
02A 14
4SW301‐L5 2800kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐170
05B 14
4SW301‐L6 2600kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
KM‐174
42 14
4SW301‐L7 240kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐170
03A 14
4SW301‐L8 1150kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐170
06B 14
4SW301‐L9 315kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐170
07B 14
4SW301‐L10 1065kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐171
11A 14
4SW301‐L11 575kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐171
17A 14
4SW301‐L12 355kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐171
18A 14
4SW301‐L13 500kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐172
20A 14
4SW301‐L14 220kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐172
21A 14
4SW301‐L15 355kW 6.6kV REM615
66/50/51G
Spare (TTR) 14
4SW301‐L16 1.6MVA 6.6kV REF615 50/51/50G/5
51G
27M/46/47//49/51LR/
Spare (M
M) 14
4SW301‐L17 2800kW 6.6kV REM615
66/50/51G/R
RTD
14TR301B 14
4SW301‐R2 1.6MVA 6.6kV REF615 50/51/50G/5
51G
14TR302B 14
4SW301‐R3 1.6MVA 6.6kV REF615 50/51/50G/5
51G
14TR303B 14
4SW301‐R4 1.6MVA 6.6kV REF615 50/51/50G/5
51G
14TR304E :
14TR304
4 14
4SW301‐R5 1.6MVA 6.6kV REF615 50/51/50G/5
51G
1.6MVA
27M/46/47//49/51LR/
PM‐170
02B 14
4SW301‐R6 2800kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐170
05A 14
4SW301‐R7 2600kW 6.6kV REM615
66/50/51G/R
RTD
7 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
Pannel Relay
P
Panel Name Rating Level Funcction Remark
Description Model
27M/46/47//49/51LR/
PM‐170
03B 14
4SW301‐R8 1150kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐170
06A 14
4SW301‐R9 315kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐170
07A 14
4SW301‐R10 1065kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐171
11B 14
4SW301‐R11 575kW 6.6kV REM615
66/50/51G/R
RTD
27M/46/47//49/51LR/
PM‐171
15A 14
4SW301‐R12 160kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐171
16A 14
4SW301‐R13 260kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐172
20B 14
4SW301‐R14 220kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
PM‐172
21B 14
4SW301‐R15 355kW 6.6kV REM615
66/50/51G
27M/46/47//49/51LR/
Spare (M
M) 14
4SW301‐R16 355kW 6.6kV REM615
66/50/51G
Spare (TTR) 14
4SW301‐R17 1.6MVA 6.6kV REF615 50/51/50G/5
51G
415V Incoming 14
4SW401L‐L1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Incoming 14
4SW401R‐R1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Bu
us‐Tie 14
4SW401‐LR 1.6MVA 415V REF615 50/51/25/27
7‐L
415V REU615 27‐R
415V Incoming 14
4SW402L‐L1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Incoming 14
4SW402R‐R1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Bu
us‐Tie 14
4SW402‐LR 1.6MVA 415V REF615 50/51/25/27
7‐L
415V REU615 27‐R
415V Incoming 14
4SW403L‐L1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Incoming 14
4SW403R‐R1 1.6MVA 415V REF615 64R/51G
415V REF615 50/51/50N/5
51N/25/27
415V Bu
us‐Tie 14
4SW403‐LR 1.6MVA 415V REF615 50/51/25/27
7‐L
415V REU615 27‐R
415V 14
4SW404EL‐L1
1 1.6MVA 415V REF615 64R/51G
Emergency
Incomin
ng 415V REF615 50/51/50N/5
51N/25/27
8 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
Pannel Relay
P
Panel Name Rating Level Funcction Remark
Description Model
415V 14
4SW404ER‐R1
1 1.6MVA 415V REF615 64R/51G
Emergency
ng
Incomin 415V REF615 50/51/50N/5
51N/25/27
Refer to atta
achment-2. P
PROTECTION RELAY SE
ETTING CAL
LCULATION
Refer to atta
achment-4. P
PROTECTION RELAY SE
ETTING TABLE
Refer to atta
achment-5. T
TIME CURRE
ENT CHARACTERISTIC CURVE
7.0 ATTACHE
EMENT LIS
ST
attachment--1 PRO
OTECTION RELAY
R SETT
TING PHILO
OSOPHY
attachment--2 PRO
OTECTION RELAY
R SETT
TING CALCU
ULATION
attachment--3 MIN
NIMUM FAUL
LT LEVEL CA
ALCULATION
N
attachment--4 PRO
OTECTION RELAY
R SETT
TING TABLE
E
attachment--5 TIM
ME CURRENT CHARACT
TERISTIC CU
URVE
9 OF 14
4
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
ATTAC
CHMENT-1 PROTEC
CTION SET
TTING PHILOSOPHY
10 OF 14
Location protection type relay no element description REMARK
Main CB Overcurrent 51 Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side / 1.5)
Normally, inst setting can be omited to coordinate with feeder overcurrent relay
time minimum time setting ; almost relays time is fixed at about 0.04s
7SJ64 (if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
time -
Main CB Overcurrent 51 Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side / 1.5)
Normally, inst setting can be omited to coordinate with feeder overcurrent relay
time minimum time setting ; almost relays time is fixed at about 0.04s
7SJ64 (if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
time instantaneous
Main CB Overcurrent 51 Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
above TR inrush current and below TR thermal limit curve.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side/1.5)
above TR inrush current
time minimum time setting ; almost relays time is fixed at about 0.04s
(if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
7SJ64
Main CB Ground overcurrent 51N Pick up phase to ground fault current x 0.4
(In resistor grounding system) (residual) curve type Definite time
TR 1st side 51N setting curve is equal to 51G setting curve
33kV outgoing feeder time adjusted according to relay coordination.
Main
(to captive TR) about 0.2s between this relay and ahead or backup relay.
[Synchro Motor]
50N (inst) Pick up below grouding fault current value/1.5 in resistor grounding system
time minimum time setting as far as possible
Main CB Ground overcurrent 51G Pick up phase to ground fault current x 0.4
(In resistor grounding system) (ZCT) curve type Definite time
51N setting curve is equal to 51G setting curve
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
TR protection Differential 87T Pick up Iop & Irest ratio tap : 30 ~ 40%
(It can be changed according to relay setting type)
time instantaneous
7UT61
TR 2nd in resistor grounding 64R (or 87N) Pick up Iop & Irest ratio tap : 10~ 30%
(It can be changed according to relay setting type)
time instantaneous
Location protection type relay no element description REMARK
Main CB Overcurrent 51 (phase time) Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side / 1.5)
Normally, inst setting can be omited to coordinate with feeder overcurrent relay
time minimum time setting ; almost relays time is fixed at about 0.04s
(if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
In resistor grounding system Ground overcurrent 51N Pick up phase to ground fault current x 0.4
(residual) curve type Definite time
51N setting curve is equal to 51G setting curve
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50N (inst) Pick up below grouding fault current value/1.5 in resistor grounding system
According to actual setting 50N pick up setting can be changed or omitted.
REF615 time minimum time setting as far as possible
TR 2nd side
51G Pick up phase to ground fault current x (0.2 ~ 0.3)
(33kV / 6.9kV)
(ZCT) curve type Definite time
Main 51N setting curve is equal to 51G setting curve
14SW301 time adjusted according to relay coordination.
(Incoming)
15SW301 about 0.2s between this relay and ahead or backup relay.
17SW301
undervoltage 27 Pick up 75% of nominal voltage
18SW301 From LINE PT
time 3s
fuse fail (comparation CB 1st and CB 2nd) 60 Pick up 20% of nominal voltage
time instantaneous
Synchro check 25 Live volt nominal voltage x 95%
dead volt nominal voltage x 10%
Δθ (angle) 10°
Δf (freq) rated frequency x 0.1%
volt-diff nominal voltage x 10%
TR protection Differential 87T+C Pick up -
7SD61 - Petrofac SCOPE
time -
7SD61 TR protection Restricted Earth Fault 64R (or 87N) Pick up Iop & Irest ratio tap : 10~ 30%
or (It can be changed according to relay setting type)
REB611
time instantaneous
Location protection type relay no element description REMARK
Main CB Overcurrent 51 (phase time) Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side / 1.5)
Normally, inst setting can be omited to coordinate with feeder overcurrent relay
time minimum time setting ; almost relays time is fixed at about 0.04s
TR 2nd side
(if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
(33kV / 6.9kV)
REF620 undervoltage 27-L Pick up 75% of nominal voltage
From BUS PT
14SW301 Bus tie time 2.5s
15SW301
fuse fail (comparate CB 1st of CB 2nd) 60 Pick up 20% of nominal voltage
17SW301
18SW301 time instantaneous
Synchro check 25 Live volt nominal voltage x 95%
dead volt nominal voltage x 10%
Δθ (angle) 10°
Δf (freq) rated frequency x 0.1%
volt-diff nominal voltage x 10%
undervoltage 27-R Pick up 75% of nominal voltage
REU615 From BUS PT
time 2.5s
Main CB Overcurrent 51 (phase time) Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
above TR inrush current and below TR thermal limit curve.
about 0.2s between this relay and ahead or backup relay.
6.6kV outgoing feeder 50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
(to TR) less than (phase to phase through fault current at TR 1st side/1.5)
above TR inrush current
14SW301 Outgoing REF615
15SW301 time minimum time setting ; almost relays time is fixed at about 0.04s
17SW301 (if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
18SW301
Main CB Ground overcurrent 51G (phase time) Pick up phase to ground fault current x 0.4
(In resistor grounding system) curve type Definite time
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50G (inst) Pick up below grouding fault current value in resistor grounding system
time minimum time setting as far as possible
Location protection type relay no element description REMARK
Main CB Overcurrent 51 (phase time) Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
less than (phase to phase through fault current at TR 1st side / 1.5)
Normally, inst setting can be omited to coordinate with feeder overcurrent relay
time minimum time setting ; almost relays time is fixed at about 0.04s
(if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
TR 2nd side In solid grounding system Ground overcurrent 51G (phase time) Pick up FLC x 0.3 ; concerning unbalanced current
(6.6kV / 0.433kV) curve type very inverse
51N setting curve is equal to 51G setting curve
time adjusted according to relay coordination.
14SW401/402/403/404E
about 0.2s between this relay and ahead or backup relay.
Main
REF 615 51N (phase time) Pick up FLC x 0.3 ; concerning unbalanced current
(Incoming)
15SW401/402/403/404E
curve type very inverse
51N setting curve is equal to 51G setting curve
time adjusted according to relay coordination.
17SW401/402/403/404E
about 0.2s between this relay and ahead or backup relay.
18SW401/402/403/404E 50N (inst) Pick up less than (phase to phase through fault current at TR 1st side / 1.5)
18SW401/402/403/404E about 0.2s between this relay and ahead or backup relay.
50N (inst) Pick up below grouding fault current value/1.5 in solid grounding system
time minimum time setting as far as possible
undervoltage 27 Pick up 75% of nominal voltage
From LINE PT
time about 3s
overvoltage 59 Pick up 115% of nominal voltage
time about 2s
Location protection type relay no element description REMARK
Main CB Overcurrent 51 (phase time) Pick up FLC x 1.25
curve type very inverse
time adjusted according to relay coordination.
about 0.2s between this relay and ahead or backup relay.
50 (inst) Pick up more than (Max three phase through fault current at TR 2nd side x 1.5)
0.433kV
less than (phase to phase through fault current at TR 1st side / 1.5)
(ACB)
time minimum time setting ; almost relays time is fixed at about 0.04s
14SW401/402/403/404E (if 50 relay failure, 51 relay time is below 0.6s in maximum through fault current.)
Bus tie REF 615 undervoltage 27-L Pick up 75% of nominal voltage
15SW401/402/403/404E From BUS PT
time about 3.5s
17SW401/402/403/404E undervoltage 27-R Pick up 75% of nominal voltage
From BUS PT
time about 3.5s
18SW401/402/403/404E
Synchro check 25 Live volt nominal voltage x 95%
dead volt nominal voltage x 10%
Δθ (angle) 10°
Δf (freq) rated frequency x 0.1%
volt-diff nominal voltage x 10%
Location protection type relay no element description REMARK
motor Stall protection 50 Pick up motor LRC x 2 Applied to only VCB
time minimum time setting ; almost relays time is fixed at about 0.04s
In resistor grounding system Ground overcurrent 51G (phase time) Pick up phase to ground fault current x 0.3
time adjusted according to relay coordination.
minimum time setting as far as possible
50G (inst) Pick up below grouding fault current value in resistor grounding system
time minimum time setting as far as possible
motor Thermal 49 Pick up 105~115% of rated current
motor Thermal 49T Pick up SETTING OF RTD
motor undervoltage 27M Pick up about 30% of nominal voltage, concering about motor starting voltage and time.
6.6kV Motor motor time 0.5sec ; For using VCB From feeder PT
REM615
(Induction Motor) Feeder 0.2sec ; For using VCS
motor Current unbalance 46 Pick up 30% of rated current
time about 2 ~ 5s
motor Voltage unbalance 47 Pick up 5% of negative voltage or 90% of nominal voltage
time 2s
motor Stall protection 50LR Pick up motor LRC x 0.5
or motor rated current x 2.5 ~ 3
time enough time to misoperation when motor starting
In resistor grounding system Ground overcurrent 51G (phase time) Pick up phase to ground fault current x 0.3
time adjusted according to relay coordination.
motor
7UM62 minimum time setting as far as possible
Feeder
motor Differential 87M Pick up Iop & Irest ratio tap : 10 ~ 20%
time instantaneous or below 0.1s
motor Thermal 49 Pick up
50N
50Q
50P
motor undervoltage 27M Pick up
time
motor Current unbalance 46 Pick up
time
time
time
Omman Oil Refiineries and Petroleum Protective Relay Coorddination Repport
Inddustries Com
mpany SAOC C and Settinng Table (SS114)
Soohar Refineryy Improvemeent Project C
C-170-5381-0051
Suultanate of Om
man Rev.0
ATTAC
CHMENT-2 PROTEC
CTION RELAY SETT
TING CALC
CULATION
N
Con
ntents Remark
1) 33kkV Incoming
2) 33kkV Outgoing
3) 14T
TR201A/B TR
R 20MVA 2nd
d ; 6.6kV Inco
oming & Tie
4) 14T
TR201A/B TR
R 20MVA 2nd
d ; 6.6kV Outtgoing feeder
5) 14T
TR301A/B, 30
02A/B, 303A
A/B, 304A/BT
TR 1.6MVA 2n
nd ; 0.415kV Incoming & Tie
11 OF 14
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
- 33kV Incoming -
(14SW201)
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
1250 / 1 [A] T3I0 1PHAS I> RELEASE DIFF T3I0 1PHAS : 0.00 ~ 0.50 sec; ∞
Dyn11 ∞ [sec]
IEC : Normal Inverse, Very Inverse, Extremely Inv. Long Inverse
Curve Type :
ANSI : Very Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv.Extremely Inv.Definite Inv.
2. LOAD DATA ( 33 kV )
TR 1st 15000 (KVA) x 1 = 15000 kVA ( 33 kV ) ∴ TR 1st Current = 262.43 (A)
TR 2nd 15000 (KVA) x 1 = 15000 kVA ( 6.9 kV ) ∴ TR 2nd Current = 1255.11 (A)
3-2) I-DIFF>
- Differential current 20 % Setting
1x 0.2 = 0.2 [A] setting. ∴ I-DIFF> = 0.2 [A]
3-3) I-DIF>SWITCH ON
- I-DIFF>: Value underswitch on condition ∴ I-DIF>SWITCH ON = 1 [A]
3-7) I-DIFF>>
∴ I-DIFF>> = ∞ [A]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
3-8) I-DIF>>SWITCH ON
- I-DIFF>>: Value underswitch on condition ∴ I-DIF>>SWITCH ON = ∞ [A]
1. SETTING TABLE
7SJ64 FCT 50/51 50-2 PICKUP 50-2 DELAY 50-1/50-2 PICKUP : 0.10 ~ 35.00 A or ∞
(SIEMENS) ON ∞ [In] ∞ [sec] 50-1/50-2 DELAY : 0.00 ~ 60.00 sec or ∞
2. LOAD DATA ( 33 kV )
14TR201A 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
14TR201B 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
KM-1702A 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702B 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702C 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
∴ TOTAL LOAD 64258 kVA ∴ Full Load Current = 1124.22 (A) ( 33 kV )
3. MOTOR DATA SHEET (KM-1702A~C 6.6kV 7900kW Motor)
kW PF EFF LRC Starting time [s] Hot [s] Cold [s] K(S.F)
7900 1 0.977 4.5 4 7 - 1
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
3-6) 51 PICKUP
- Full Load Current 125 % Setting
- Full Load Current x 1.25 x (1/CT ratio)
1124 x 1.25 x 1 = 1.12 [In] ∴51 PICKUP = 1 [In]
1250
- pick-up current
1 [In] setting. 1 x 1250 = 1250 [A] , 1250 = 111.2 [%]
1 1124
3-8) 51 Drop-out
∴ 51 Drop-out = Instantaneous
5-2) Synchronizing
-Function ON / OFF ∴ Synchronizing = ON
5-13) 25 Synchron
∴ 25 Synchron = YES
5-17) CONNECTIONof V2
∴ CONNECTIONof = A-B
5-20) F SYNCHRON
Frequency threshold ASYN <-->SYN ∴ F SYNCHRON = 0.04 [Hz]
- Nominal Frequency 0.1 % Setting
- Nominal Frequency x 0.001
50 x 0.001 = 0.05 [Hz]
5-21) ∆V-measurement
- Nominal Voltage 10 % Setting
- Nominal Voltage x 0.1
110V x 0.1 = 11 [V] ∴ dV SYNC V2>V1 = 11 [V]
- pick-up voltage
11 [V] setting. 11 = 10 [%] ∴ dV SYNC V2<V1 = 11 [V]
110
5-22) ∆α-measurement
∴ dα SYNC α2> α1= 10 [deg]
∴ dα SYNC α2< α1= 10 [deg]
5-23) T SYNC-DELAY
∴ T SYNC-DELAY = 0 [sec]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
7SJ64 FCT 50/51 50-2 PICKUP 50-2 DELAY 50-1/50-2 PICKUP : 0.10 ~ 35.00 A or ∞
(SIEMENS) ON ∞ [In] ∞ [sec] 50-1/50-2 DELAY : 0.00 ~ 60.00 sec or ∞
2. LOAD DATA ( 33 kV )
14TR201A 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
14TR201B 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
KM-1702A 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702B 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702C 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
∴ TOTAL LOAD 64258 kVA ∴ Full Load Current = 1124.22 (A) ( 33 kV )
3. MOTOR DATA SHEET (KM-1702A~C 6.6kV 7900kW Motor)
kW PF EFF LRC Starting time [s] Hot [s] Cold [s] K(S.F)
7900 1 0.977 4.5 4 7 - 1
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
3-6) 51 PICKUP
- Full Load Current 125 % Setting
- Full Load Current x 1.25 x (1/CT ratio)
1124 x 1.25 x 1 = 1.12 [In] ∴51 PICKUP = 1 [In]
1250
- pick-up current
1 [In] setting. 1 x 1250 = 1250 [A] , 1250 = 111.2 [%]
1 1124
3-8) 51 Drop-out
∴ 51 Drop-out = Instantaneous
5-2) Synchronizing
-Function ON / OFF ∴ Synchronizing = ON
5-13) 25 Synchron
∴ 25 Synchron = YES
5-17) CONNECTIONof V2
∴ CONNECTIONof = A-B
5-20) F SYNCHRON
Frequency threshold ASYN <-->SYN ∴ F SYNCHRON = 0.04 [Hz]
- Nominal Frequency 0.1 % Setting
- Nominal Frequency x 0.001
50 x 0.001 = 0.05 [Hz]
5-21) ∆V-measurement
- Nominal Voltage 10 % Setting
- Nominal Voltage x 0.1
110V x 0.1 = 11 [V] ∴ dV SYNC V2>V1 = 11 [V]
- pick-up voltage
11 [V] setting. 11 = 10 [%] ∴ dV SYNC V2<V1 = 11 [V]
110
5-22) ∆α-measurement
∴ dα SYNC α2> α1= 10 [deg]
∴ dα SYNC α2< α1= 10 [deg]
5-23) T SYNC-DELAY
∴ T SYNC-DELAY = 0 [sec]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
2. LOAD DATA ( 33 kV )
14TR201A 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
14TR201B 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.9 (A)
KM-1702A 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702B 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
KM-1702C 8085.98 (KVA) x 1 = 8086 kVA ( 33 kV ) ∴ TR 1st Current = 141.5 (A)
∴ TOTAL LOAD 64258 kVA ∴ Full Load Current = 1124.22 (A) ( 33 kV )
1. SETTING TABLE
(SIEMENS) 0.1 [In] 0 [s] td Delay setting : 0, 0.005 ~ 1.0, 1.01 ~ 5, 5.1 ~ 60s
87B 87/50-n
CT Ratio
1250 / 1 [A]
2. BUS DATA
- Voltage : 33 [kV]
- Rated Current : 1250 [A]
- If (Short Circuit Capacity) : 40 [kA]
3. CT DATA
- T (CT Ratio) : 1250 / 1 [A]
- RCT (CT secondary resistance) : 5 [Ω]
- RL (CT lead resistance) : 0.28 [Ω]
( 2.34 [Ω / km] x 0.05 [km] x 2 x 1.2 )
- Vk (Knee point voltage) : 400 [V]
- IMAG (CT magnetising current) : < 70 [mA] at Vk
- Total Number of feeders parallel connected : 5
3) Is (Operating current)
P.O.C = (Is + INLR + ∑IMAG) / T
4) Rs (Stabilising Resistor)
Rs = 169 = 1300 [Ω] Stabilizing Resistor (Selected) : 1300 [Ω]
0.13
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
- pick-up current
0.1 [In] setting. ∴ Is Setting = 0.1 [In]
4-2) Is Setting
∴ td Delay setting = 0 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
(SIEMENS) 0.1 [In] 0 [s] td Delay setting : 0, 0.005 ~ 1.0, 1.01 ~ 5, 5.1 ~ 60s
87B 87/50-n
CT Ratio
1250 / 1 [A]
2. BUS DATA
- Voltage : 33 [kV]
- Rated Current : 1250 [A]
- If (Short Circuit Capacity) : 40 [kA]
3. CT DATA
- T (CT Ratio) : 1250 / 1 [A]
- RCT (CT secondary resistance) : 5 [Ω]
- RL (CT lead resistance) : 0.28 [Ω]
( 2.34 [Ω / km] x 0.05 [km] x 2 x 1.2 )
- Vk (Knee point voltage) : 400 [V]
- IMAG (CT magnetising current) : < 70 [mA] at Vk
- Total Number of feeders parallel connected : 4
3) Is (Operating current)
P.O.C = (Is + INLR + ∑IMAG) / T
4) Rs (Stabilising Resistor)
Rs = 169 = 1300 [Ω] Stabilizing Resistor (Selected) : 1300 [Ω]
0.13
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
- pick-up current
0.1 [In] setting. ∴ Is Setting = 0.1 [In]
4-2) Is Setting
∴ td Delay setting = 0 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
- 33kV Outgoing -
(14SW201)
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
7SJ64 FCT 50/51 50-2 PICKUP 50-2 DELAY 50-1/50-2 PICKUP : 0.10 ~ 35.00 A or ∞
(SIEMENS) ON ∞ [In] ∞ [sec] 50-1/50-2 DELAY : 0.00 ~ 60.00 sec or ∞
51N 50/51 50N-1 PICKUP 50N-1 DELAY 51N PICKUP 51N PICKUP : 0.05 ~ 3.20 A or ∞
VT Ratio (Residual) Overcur. ∞ [In] ∞ [sec] 0.14 [In] 51N TIME DAIL : 0.50 ~ 15.00 or ∞
33kV / 110V 51N TIME DIAL 51N Drop-out 51N ANSI CURVE51N Drop-out : Instantaneous, Disk Emulation
√3 √3 0.25 Instantaneous Definite Time
Sens. Gnd Fault 50Ns-2 PICKUP 50Ns-2 DELAY Sens. Gnd Fault : OFF, ON, Alarm Only
ZCT Ratio OFF ∞ [In] ∞ [sec] 50Ns-1/50Ns-2 PICKUP : 0.10 ~ 35.00 A or ∞
100 / 1 [A] 51G Sens. Gnd 50Ns-1 PICKUP 50Ns-1 DELAY 51Ns PICKUP 50Ns-1/50Ns-2 DELAY : 0.00 ~ 60.00 sec or ∞
(ZCT) Fault 0.8 [In] 0.25 [sec] ∞ [In] 51Ns PICKUP : 0.05 ~ 3.20 A or ∞
Frequency 51Ns TIME DIAL 51Ns Drop-out 51Ns TIME DAIL : 0.50 ~ 15.00 or ∞
50 [Hz] ∞ ∞ 51Ns Drop-out : Instantaneous, Disk Emulation
IEC-INVERSE(Type A), IEC-VERY INVERSE(Type B), IEC-EXTREMELY INV.(Type C), IEC-LONG INVERSE(Type D) : Acc. to IEC 60255-3 or BS 142
Curve Type :
ANSI-INVERSE, ANSI-SHORT INVERSE, ANSI-LONG INVERSE, ANSI-MODERATELY INV., ANSI-VERY INVERSE, ANSI-EXTREMELY INV., DEFINITE INV. : Acc. to A
2. LOAD DATA ( 33 kV )
TR 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 2nd Current = 349.9 (A)
3-6) 51 PICKUP
- Full Load Current 125 % Setting
- Full Load Current x 1.25 x (1/CT ratio)
349.9 x 1.25 x 1 = 0.73 [In] ∴51 PICKUP = 0.73 [In]
600
- pick-up current
0.73 [In] setting. 0.73 x 600 = 438 [A] , 438 = 125.2 [%]
1 349.9
3-8) 51 Drop-out
∴ 51 Drop-out = Instantaneous
1. SETTING TABLE
7UT61 Diff. Prot. Inc.Char.Start Inrush 2Harm. Diff. Protection : On, Off, Block relay
(SIEMENS) On Off On Inc.Char.Start : On, Off, Inrush 2Harm. : On, Off
Restr.n.Harm.
Restr.n.Harm. : Off, 3Harm., 5Harm.
1st CT Ratio 5. Harmonic
600 / 1 [A] I-Diff.> TI-Diff.> I-Diff.>> I-Diff.> : 0.05~2.00 I/InO , I-Diff.>> : 0.5~35.0 I/InO; ∞
2000 / 1 [A] 0 [s] 0.3 0 [I/InO] Slope 1 : 0.10~0.50, Base Point 1 : 0.00~2.00 I/InO
Slope 2 Base Point 2 I-Rest.Startup Slope 2 : 0.25~0.95, Base Point 2 : 0.00~10.00 I/InO
87T I Diff
2nd NCT Ratio 0.5 2.5 [I/InO] Omit. [I/InO] I-Rest.Startup : 0.00~2.00 I/InO
400 / 1 [A] Start-Factor T Start Max. I-ADD On Stab. Start-Factor : 1.0~2.0, T Start Max.:0.0~180.0 s
Omit. Omit. [s] 4 [I/InO] I-Add On Stab.:2.00~15.00 I/InO
TR Winding T Add On-Stab. Crossb.Add On 2Harmonic T Add On-Stab.:2~250 Cy; ∞, 2Harmonic : 10~80%,
2. LOAD DATA ( 33 kV )
TR 1st 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.91 (A)
TR 2nd 20000 (KVA) x 1 = 20000 kVA ( 6.9 kV ) ∴ TR 2nd Current = 1673.48 (A)
3-2) INC.CHAR.START
- Increase of Trip Char. During Start ∴ INC.CHAR.START = Off
3-5) I-DIFF>
- Full Load Current 30 % Setting
- Full Load Current x 0.3 x (1/CT ratio)
349.9 x 0.3 x 1 = 0.17 [In] ∴ I-DIFF> = 0.175 [I/InO]
600
- pick-up current
0.175 [In] setting. 0.175 x 600 = 105 [A] , 105 = 30.01 [%]
1 349.9
3-6) T I-DIFF>
∴ T I-DIFF> = 0 [s]
3-7) I-DIFF>>
- TR Inrush current = TR Rated current x 12 = 4199 [A]
3-9) SLOPE 1
- Slope 1 of Tripping Characteristic ∴ SLOPE 1 = 0.3
3-11) SLOPE 2
- Slope 2 of Tripping Characteristic ∴ SLOPE 2 = 0.5
3-14) START-FACTOR
- Factor for Increasing of Char. At Start ∴ START-FACTOR = Omit.
3-19) 2. HARMONIC
- 2nd Harmonic Content in I-DIFF ∴ 2. HARMONIC = 15 [%]
3-21) n. HARMONIC
- n-th Harmonic Content in I-DIFF ∴ n. HARMONIC = 30 [%]
1. SETTING TABLE
7SJ64 FCT 50/51 50-2 PICKUP 50-2 DELAY 50-1/50-2 PICKUP : 0.10 ~ 35.00 A or ∞
(SIEMENS) ON ∞ [In] ∞ [sec] 50-1/50-2 DELAY : 0.00 ~ 60.00 sec or ∞
50/51N 50/51 50N-1 PICKUP 50N-1 DELAY 51N PICKUP 51N PICKUP : 0.05 ~ 3.20 A or ∞
VT Ratio (Residual) Overcur. ∞ [In] ∞ [sec] 0.14 [In] 51N TIME DAIL : 0.50 ~ 15.00 or ∞
33kV / 110V 51N TIME DIAL 51N Drop-out 51N ANSI CURVE51N Drop-out : Instantaneous, Disk Emulation
√3 √3 0.25 Instantaneous Definite Time
Sens. Gnd Fault 50Ns-2 PICKUP 50Ns-2 DELAY Sens. Gnd Fault : OFF, ON, Alarm Only
ZCT Ratio OFF ∞ [In] ∞ [sec] 50Ns-1/50Ns-2 PICKUP : 0.10 ~ 35.00 A or ∞
100 / 1 [A] 51G Sens. Gnd 50Ns-1 PICKUP 50Ns-1 DELAY 51Ns PICKUP 50Ns-1/50Ns-2 DELAY : 0.00 ~ 60.00 sec or ∞
(ZCT) Fault 0.8 [In] 0.25 [sec] ∞ [In] 51Ns PICKUP : 0.05 ~ 3.20 A or ∞
Frequency 51Ns TIME DIAL 51Ns Drop-out 51Ns TIME DAIL : 0.50 ~ 15.00 or ∞
50 [Hz] ∞ ∞ 51Ns Drop-out : Instantaneous, Disk Emulation
IEC-INVERSE(Type A), IEC-VERY INVERSE(Type B), IEC-EXTREMELY INV.(Type C), IEC-LONG INVERSE(Type D) : Acc. to IEC 60255-3 or BS 142
Curve Type :
ANSI-INVERSE, ANSI-SHORT INVERSE, ANSI-LONG INVERSE, ANSI-MODERATELY INV., ANSI-VERY INVERSE, ANSI-EXTREMELY INV., DEFINITE INV. : Acc. to A
2. LOAD DATA ( 33 kV )
TR 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 2nd Current = 349.9 (A)
3-6) 51 PICKUP
- Full Load Current 125 % Setting
- Full Load Current x 1.25 x (1/CT ratio)
349.9 x 1.25 x 1 = 0.73 [In] ∴51 PICKUP = 0.73 [In]
600
- pick-up current
0.73 [In] setting. 0.73 x 600 = 438 [A] , 438 = 125.2 [%]
1 349.9
3-8) 51 Drop-out
∴ 51 Drop-out = Instantaneous
1. SETTING TABLE
7UT61 Diff. Prot. Inc.Char.Start Inrush 2Harm. Diff. Protection : On, Off, Block relay
(SIEMENS) On On On Inc.Char.Start : On, Off, Inrush 2Harm. : On, Off
Restr.n.Harm.
Restr.n.Harm. : Off, 3Harm., 5Harm.
1st CT Ratio 5. Harmonic
600 / 1 [A] I-Diff.> TI-Diff.> I-Diff.>> I-Diff.> : 0.05~2.00 I/InO , I-Diff.>> : 0.5~35.0 I/InO; ∞
2000 / 1 [A] 0 [s] 0.3 0 [I/InO] Slope 1 : 0.10~0.50, Base Point 1 : 0.00~2.00 I/InO
Slope 2 Base Point 2 I-Rest.Startup Slope 2 : 0.25~0.95, Base Point 2 : 0.00~10.00 I/InO
87T I Diff
2nd NCT Ratio 0.5 2.5 [I/InO] Omit. [I/InO] I-Rest.Startup : 0.00~2.00 I/InO
400 / 1 [A] Start-Factor T Start Max. I-ADD On Stab. Start-Factor : 1.0~2.0, T Start Max.:0.0~180.0 s
Omit. Omit. [s] 4 [I/InO] I-Add On Stab.:2.00~15.00 I/InO
TR Winding T Add On-Stab. Crossb.Add On 2Harmonic T Add On-Stab.:2~250 Cy; ∞, 2Harmonic : 10~80%,
64R On 0.2 [I/InO] 0 [s] I-REF> : 0.05~2.00 I/InS, TI-REF> : 0.00~60.00 sec; ∞
I REF
(87TN) SLOPE
SLOPE : 0.00~0.95
0
IEC : Normal Inverse, Very Inverse, Extremely Inv. Long Inverse
Curve Type :
ANSI : Very Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv.Extremely Inv.Definite Inv.
2. LOAD DATA ( 33 kV )
TR 1st 20000 (KVA) x 1 = 20000 kVA ( 33 kV ) ∴ TR 1st Current = 349.91 (A)
TR 2nd 20000 (KVA) x 1 = 20000 kVA ( 6.9 kV ) ∴ TR 2nd Current = 1673.48 (A)
3-2) INC.CHAR.START
- Increase of Trip Char. During Start ∴ INC.CHAR.START = On
3-5) I-DIFF>
- Full Load Current 30 % Setting
- Full Load Current x 0.3 x (1/CT ratio)
349.9 x 0.3 x 1 = 0.17 [In] ∴ I-DIFF> = 0.175 [I/InO]
600
- pick-up current
0.175 [In] setting. 0.175 x 600 = 105 [A] , 105 = 30.01 [%]
1 349.9
3-6) T I-DIFF>
∴ T I-DIFF> = 0 [s]
3-7) I-DIFF>>
- TR Inrush current = TR Rated current x 12 = 4199 [A]
3-8) T I-DIFF>>
∴ T I-DIFF>> = 0 [s]
3-9) SLOPE 1
- Slope 1 of Tripping Characteristic ∴ SLOPE 1 = 0.3
3-11) SLOPE 2
- Slope 2 of Tripping Characteristic ∴ SLOPE 2 = 0.5
3-14) START-FACTOR
- Factor for Increasing of Char. At Start ∴ START-FACTOR = Omit.
3-19) 2. HARMONIC
- 2nd Harmonic Content in I-DIFF ∴ 2. HARMONIC = 15 [%]
3-21) n. HARMONIC
- n-th Harmonic Content in I-DIFF ∴ n. HARMONIC = 30 [%]
4-2) I-REF>
- ( Error for TR + Error for CT) x margin
1 x ( 0.05 + 0.03 )x 0.05 = 13 [%]
4-4) SLOPE
0.2 = 0.07 ∴ SLOPE = 0
3
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
1. SETTING TABLE
7UM62 O/C I>> O/C I>> T I>> O/C I>> : On, Off, Block relay
(SIEMENS) On 2.83 [In] 0 [s] I>> : 0.05 ~ 20.00 A, T I>> : 0.00~60.00 sec; ∞
87M Phase O/C
Phase Direction LINE ANGLE Phase Direction : Forward or Reverse
400 / 1 [A] IEp IEpT Curve Type IEp : 0.25 ~ 20.00[A] or ∞ (disable) (0.01)
51G 1.6 [In] 0.25 Definite Time IEpT : 0.05 ~ 3.20 or ∞ (disable) [s] (0.01)
Earth O/C
2nd ZCT Ratio (NCT)
50 / 1 [A]
IEC : Normal Inverse, Very Inverse, Extremely Inv. Long Inverse
Curve Type :
ANSI : Very Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv.Extremely Inv.Definite Inv.
∴ TOTAL LOAD 8086 kVA ∴ Full Load Current = 707.34 (A) ( 6.6 kV )
4-2) I>>
- Full Load Current 20 % Setting
- Full Load Current x 0.2 x (1/CT ratio)
707.3 x 0.2 x 1 = 2.83 [In] ∴ O/C I>> = 2.83 [In]
50
- pick-up current
2.83 [In] setting. 2.83 x 50 = 141.5 [A] , 141.5 = 20 [%]
1 707.3
4-3) T I>>
- Minimum setting ∴ T I>> = 0 [s]
1. SETTING TABLE
REF 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 3000 [ms] Delay time : 60~300000 ms (10)
3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
CT Ratio (PHLPTOC) 1.09 [In] 10 (IEC VI) 0.14 Time multiplier : 0.05~15.00 (0.01)
2000 / 1 [A] 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
(PHHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
NCT Ratio 51N Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
400 / 1 [A] (residual) (EFLPTOC1) 0.08 [In] 15 (IEC DT) 600 [ms] Delay time : 40~200000 ms (10)
50N Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
VCB (residual) (EFHPTOC1) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
2000 [A] Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G Io>-> 0.4 [In] 15 (IEC DT) 600 [ms] Delay time : 60~200000 ms (10)
50 [Hz] 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
(SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
Fuse failure Neg Seq current Lev Neg Seq voltage Lev Neg Seq current Lev : 0.03~0.20 xIn (0.01)
60
(SEQRFUF) 0.03 [In] 0.2 [Un] Neg Seq voltage Lev : 0.03~0.20 xUn (0.01)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 20000 kVA ∴ Full Load Current = 1749.55 (A) ( 6.6 kV )
1. SETTING TABLE
REB 611 64R Operate Value Operate time Operate Value : 1...200 x %In (1)
(HIPDIF)
(ABB) (87) 20 [%In] 20 [ms] Minimum operate time : 20...300000 ms (10)
CT Ratio
2000 / 1 [A]
NCT Ratio
2000 / 1 [A]
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 20000 kVA ∴ Full Load Current = 1749.55 (A) ( 6.6 kV )
4. CALCULATION (64R - Restricted Earth Fault protection) : HIPDIF used for REF
4-1) Operate Value
- Iop & Irest ratio tap 20 % Setting ∴ Operate Value = 20 [%In]
1. SETTING TABLE
REF 620 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-L
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 2500 [ms] Delay time : 60~300000 ms (10)
3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
CT Ratio (PHLPTOC) 1.09 [In] 10 (IEC VI) 0.14 Time multiplier : 0.05~15.00 (0.01)
2000 / 1 [A] 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
(PHHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
VCB Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
Dead L Live B, Dead Bus L Any, Dead L Bus Any,
2000 [A] One Live Dead One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
VT Ratio 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
6.6kV 110V Difference angle Synchrocheck mode Difference angle : 5~90 deg(1)
/
√3 √3 10 [deg] Asynchrocheck Synchrocheck mode : Off, Synchro, Asynchro
Frequency SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
50 [Hz] (SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
Fuse failure Neg Seq current Lev Neg Seq voltage Lev Neg Seq current Lev : 0.03~0.20 xIn (0.01)
60
(SEQRFUF) 0.03 [In] 0.2 [Un] Neg Seq voltage Lev : 0.03~0.20 xUn (0.01)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 20000 kVA ∴ Full Load Current = 1749.55 (A) ( 6.6 kV )
1. SETTING TABLE
REU 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-R
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 2500 [ms] Delay time : 60~300000 ms (10)
VT Ratio
6.6kV 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 20000 kVA ∴ Full Load Current = 1749.55 (A) ( 6.6 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 0.87 [In] 10 (IEC VI) 0.34 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
200 / 1 [A] (PHHPTOC) 14.8 [In] 15 (IEC DT) 40 [ms] Delay time : 40~200000 ms (10)
ZCT Ratio Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
50 / 1 [A] (EFLPTOC) 3.2 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
VCB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
800 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 139.96 (A) ( 6.6 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 0.87 [In] 10 (IEC VI) 0.34 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
200 / 1 [A] (PHHPTOC) 14.8 [In] 15 (IEC DT) 40 [ms] Delay time : 40~200000 ms (10)
ZCT Ratio Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
50 / 1 [A] (EFLPTOC) 3.2 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
VCB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
800 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 139.96 (A) ( 6.6 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 0.87 [In] 10 (IEC VI) 0.34 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
200 / 1 [A] (PHHPTOC) 14.8 [In] 15 (IEC DT) 40 [ms] Delay time : 40~200000 ms (10)
ZCT Ratio Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
50 / 1 [A] (EFLPTOC) 3.2 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
VCB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
800 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 139.96 (A) ( 6.6 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 0.87 [In] 10 (IEC VI) 0.34 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
200 / 1 [A] (PHHPTOC) 14.8 [In] 15 (IEC DT) 40 [ms] Delay time : 40~200000 ms (10)
ZCT Ratio Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
50 / 1 [A] (EFLPTOC) 3.2 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
VCB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
800 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 139.96 (A) ( 6.6 kV )
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 500 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.17 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
500 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.00~1.00 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) 6.64 [In] 15 (IEC DT) 40 [ms] Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.38 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
Input mode Input maximum Input minimum Input mode : 1=Not in use , 2=Resistance, 10=Pt100
10 (Pt100) 20 [mA] 0 [mA] 11=Pt250, 20=Ni100, 21=Ni120, 22=Ni250, 30=Cu10
Value unit Value maximum Value minimum Input maximum / minimum : 0 ~ 2000 / (1)
23 (Degrees celsius)
200 [°C] -10 [°C] Value unit : 1=Dimensionless,5=Ampere
RTD/mA
Val high high limit Val high limit Val low limit ,23=Degrees celsius,30=Ohm
155 [°C] 130 [°C] 0 [°C] Value maximum / minimum : -10000.0 ~ 10000.0 / (1)
RTD
Val low low limit Value deadband Val. high high / high limit : -10000.0 ~ 10000.0 / (1)
-5 [°C] 6000 Val. low low / low limit : -10000.0 ~ 10000.0 / (1)
Winding Winding Alarm Pickup Alarm Delay Time Value deadband : 100 ~ 100000 / (1)
Alarm 130 [°C] 2 [s]
Winding Winding Trip Pickup Trip Delay Time
Trip 155 [°C] 5 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 500 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.16 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
500 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.00~1.00 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) 6.3 [In] 15 (IEC DT) 40 ##### Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.31 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
Input mode Input maximum Input minimum Input mode : 1=Not in use , 2=Resistance, 10=Pt100
10 (Pt100) 20 [mA] 0 [mA] 11=Pt250, 20=Ni100, 21=Ni120, 22=Ni250, 30=Cu10
Value unit Value maximum Value minimum Input maximum / minimum : 0 ~ 2000 / (1)
23 (Degrees celsius)
200 [°C] -10 [°C] Value unit : 1=Dimensionless,5=Ampere
RTD/mA
Val high high limit Val high limit Val low limit ,23=Degrees celsius,30=Ohm
155 [°C] 130 [°C] 0 [°C] Value maximum / minimum : -10000.0 ~ 10000.0 / (1)
RTD
Val low low limit Value deadband Val. high high / high limit : -10000.0 ~ 10000.0 / (1)
-5 [°C] 6000 Val. low low / low limit : -10000.0 ~ 10000.0 / (1)
Winding Winding Alarm Pickup Alarm Delay Time Value deadband : 100 ~ 100000 / (1)
Alarm 130 [°C] 2 [s]
Winding Winding Trip Pickup Trip Delay Time
Trip 155 [°C] 5 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.17 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
200 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.38 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
Input mode Input maximum Input minimum Input mode : 1=Not in use , 2=Resistance, 10=Pt100
10 (Pt100) 20 [mA] 0 [mA] 11=Pt250, 20=Ni100, 21=Ni120, 22=Ni250, 30=Cu10
Value unit Value maximum Value minimum Input maximum / minimum : 0 ~ 2000 / (1)
23 (Degrees celsius)
200 [°C] -10 [°C] Value unit : 1=Dimensionless,5=Ampere
RTD/mA
Val high high limit Val high limit Val low limit ,23=Degrees celsius,30=Ohm
155 [°C] 130 [°C] 0 [°C] Value maximum / minimum : -10000.0 ~ 10000.0 / (1)
RTD
Val low low limit Value deadband Val. high high / high limit : -10000.0 ~ 10000.0 / (1)
-5 [°C] 6000 Val. low low / low limit : -10000.0 ~ 10000.0 / (1)
Winding Winding Alarm Pickup Alarm Delay Time Value deadband : 100 ~ 100000 / (1)
Alarm 130 [°C] 2 [s]
Winding Winding Trip Pickup Trip Delay Time
Trip 155 [°C] 5 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.16 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
200 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.34 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
Input mode Input maximum Input minimum Input mode : 1=Not in use , 2=Resistance, 10=Pt100
10 (Pt100) 20 [mA] 0 [mA] 11=Pt250, 20=Ni100, 21=Ni120, 22=Ni250, 30=Cu10
Value unit Value maximum Value minimum Input maximum / minimum : 0 ~ 2000 / (1)
23 (Degrees celsius)
200 [°C] -10 [°C] Value unit : 1=Dimensionless,5=Ampere
RTD/mA
Val high high limit Val high limit Val low limit ,23=Degrees celsius,30=Ohm
155 [°C] 130 [°C] 0 [°C] Value maximum / minimum : -10000.0 ~ 10000.0 / (1)
RTD
Val low low limit Value deadband Val. high high / high limit : -10000.0 ~ 10000.0 / (1)
-5 [°C] 6000 Val. low low / low limit : -10000.0 ~ 10000.0 / (1)
Winding Winding Alarm Pickup Alarm Delay Time Value deadband : 100 ~ 100000 / (1)
Alarm 130 [°C] 2 [s]
Winding Winding Trip Pickup Trip Delay Time
Trip 155 [°C] 5 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.17 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
100 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.44 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
Input mode Input maximum Input minimum Input mode : 1=Not in use , 2=Resistance, 10=Pt100
10 (Pt100) 20 [mA] 0 [mA] 11=Pt250, 20=Ni100, 21=Ni120, 22=Ni250, 30=Cu10
Value unit Value maximum Value minimum Input maximum / minimum : 0 ~ 2000 / (1)
23 (Degrees celsius)
200 [°C] -10 [°C] Value unit : 1=Dimensionless,5=Ampere
RTD/mA
Val high high limit Val high limit Val low limit ,23=Degrees celsius,30=Ohm
155 [°C] 130 [°C] 0 [°C] Value maximum / minimum : -10000.0 ~ 10000.0 / (1)
RTD
Val low low limit Value deadband Val. high high / high limit : -10000.0 ~ 10000.0 / (1)
-5 [°C] 6000 Val. low low / low limit : -10000.0 ~ 10000.0 / (1)
Winding Winding Alarm Pickup Alarm Delay Time Value deadband : 100 ~ 100000 / (1)
Alarm 130 [°C] 2 [s]
Winding Winding Trip Pickup Trip Delay Time
Trip 155 [°C] 5 [s]
Attachment #02. Relay coordination Calculation(88SS14) Sohar Refinery Improvement Project
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.15 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
100 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 120 [s] 120 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.26 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.14 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
75 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.17 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.2 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
50 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 120 [s] 120 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.64 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.17 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
50 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.38 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.18 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
50 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 540 [s] 540 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.49 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.15 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
50 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.27 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REM 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27M
(ABB) (PSPTUV) 0.3 [Un] 15 (IEC DT) 200 [ms] Delay time : 60~300000 ms (10)
Start Value Curve Type Delay Time Start Value : 0.01~0.50 x In (0.01)
CT Ratio I2>M 0.19 [In] 15 (IEC DT) 3000 [ms] Delay time : 100~120000 ms (10)
46
30 / 1 [A] (MNSPTOC) Operation Cooling time : 5~7200 s (1)
ZCT Ratio Env temperature mode Env temperature set Env temp. mode : FLC Only, Use RTD, Set Amb Temp
Alarm thermal value Restart thermal value Alarm thermal value : 50.0~100.0 % (0.1)
VT Ratio Time constant normal Time constant start Time constant normal : 80~4000 s (1)
6.6kV 110V 180 [s] 180 [s] Time constant start : 80~4000 s (1)
/
√3 √3 Start Value Delay Time Start value : 0.010~1.20 x Un (0.001)
47 (NSPTOV)
0.9 [Un] 2000 [ms] Delay time : 40~120000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
50
(EFLPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
Io> Start Value Curve Type Delay Time Start Value : 0.010~5.000 x In (0.005)
51G
(EFLPTOC) 2.4 [In] 15 (IEC DT) 400 [ms] Delay time : 40~200000 ms (10)
Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50G
(EFHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
Ist> Operation Start Value Delay Time Start value : 0.10~10.00 x In (0.01)
51LR
(JAMPTOC) On 1.56 [In] 2000 [ms] Delay time : 100~120000 ms (10), Operation : On, Off
Motor start-up time Lock rotor time Motor start-up time : 1~80.0 s (1)
Str over delay time Operation mode Str over delay time : 0~60000 ms (1)
Is2t n< - [ms] - Operation mode : Iit, IIt CB, IIt & stall, IIt & stall CB
66
(STTPMSU1) Counter Red rate Cumulative time Lim Counter Red rate : 2.0~250.0 s/h (0.1)
Emg start Red rate Restart inhibit time Emg start Red rate : 0.00~100.0 % (0.01)
- [In]
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
5-4) Operation
∴ Operation = On
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51N
(EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 0 Time multiplier : 0.05~15.00 (0.01)
ACB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50N
2500 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27
VT Ratio (PSPTUV) 0.75 [Un] 15 (IEC DT) 3000 [ms] Delay time : 60~300000 ms (10)
415V 110V Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
/ Dead L Live B, Dead Bus L Any, Dead L Bus Any,
√3 √3 Live L, Dead B One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
Frequency 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
(SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51G
(ABB) (EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 64R dIoLo> Operate Value Operate time Restraint mode Operate Value : 5~50 x %In (1)
2500 / 1 [A] (87N) (LREFPNDF) 20 [%In] 40 [ms] 1 (None) Minimum operate time : 40~300000 ms (1)
NCT Ratio
2500 / 1 [A]
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-L
(PSPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
ACB Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
Dead L Live B, Dead Bus L Any, Dead L Bus Any,
2500 [A] One Live Dead One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
VT Ratio 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
415V 110V Difference angle Synchrocheck mode Difference angle : 5~90 deg(1)
/
√3 √3 10 [deg] Asynchrocheck Synchrocheck mode : Off, Synchro, Asynchro
Frequency SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
50 [Hz] (SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REU 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-R
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51N
(EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 0 Time multiplier : 0.05~15.00 (0.01)
ACB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50N
2500 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27
VT Ratio (PSPTUV) 0.75 [Un] 15 (IEC DT) 3000 [ms] Delay time : 60~300000 ms (10)
415V 110V Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
/ Dead L Live B, Dead Bus L Any, Dead L Bus Any,
√3 √3 Live L, Dead B One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
Frequency 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
(SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
1. SETTING TABLE
REF 615 Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51G
(ABB) (EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 64R dIoLo> Operate Value Operate time Restraint mode Operate Value : 5~50 x %In (1)
2500 / 1 [A] (87N) (LREFPNDF) 20 [%In] 40 [ms] 1 (None) Minimum operate time : 40~300000 ms (1)
NCT Ratio
2500 / 1 [A]
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-L
(PSPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
ACB Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
Dead L Live B, Dead Bus L Any, Dead L Bus Any,
2500 [A] One Live Dead One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
VT Ratio 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
415V 110V Difference angle Synchrocheck mode Difference angle : 5~90 deg(1)
/
√3 √3 10 [deg] Asynchrocheck Synchrocheck mode : Off, Synchro, Asynchro
Frequency SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
50 [Hz] (SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REU 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-R
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51N
(EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 0 Time multiplier : 0.05~15.00 (0.01)
ACB Io>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50N
2500 [A] (EFHPTOC) Omit. Omit. Omit. Delay time : 40~200000 ms (10)
3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27
VT Ratio (PSPTUV) 0.75 [Un] 15 (IEC DT) 3000 [ms] Delay time : 60~300000 ms (10)
415V 110V Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
/ Dead L Live B, Dead Bus L Any, Dead L Bus Any,
√3 √3 Live L, Dead B One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
Frequency 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
(SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
1. SETTING TABLE
REF 615 Io> Start Value Curve Type Time Multiplier Start Value : 0.010~5.000 x In (0.005)
51G
(ABB) (EFLPTOC) 0.36 [In] 10 (IEC VI) 0.27 Time multiplier : 0.05~15.00 (0.01)
CT Ratio 64R dIoLo> Operate Value Operate time Restraint mode Operate Value : 5~50 x %In (1)
2500 / 1 [A] (87N) (LREFPNDF) 20 [%In] 40 [ms] 1 (None) Minimum operate time : 40~300000 ms (1)
NCT Ratio
2500 / 1 [A]
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REF 615 3I> Start Value Curve Type Time Multiplier Start Value : 0.05~5.00 x In (0.01)
51
(ABB) (PHLPTOC) 1.11 [In] 10 (IEC VI) 0.19 Time multiplier : 0.05~15.00 (0.01)
3I>> Start Value Curve Type Delay Time Start Value : 0.10~40.00 x In (0.01)
50
CT Ratio (PHHPTOC) Omit Omit Omit Delay time : 40~200000 ms (10)
2500 / 1 [A] 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-L
(PSPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
ACB Live dead mode Live dead mode : Off, Both Dead, Live L Dead B,
Dead L Live B, Dead Bus L Any, Dead L Bus Any,
2500 [A] One Live Dead One Live Dead, Not Both Live
Difference voltage Difference frequency Difference voltage : 0.01~0.50 xUn (0.01)
VT Ratio 0.1 [Un] 0.001 [Fn] Difference frequency : 0.001~0.100 xFn (0.001)
415V 110V Difference angle Synchrocheck mode Difference angle : 5~90 deg(1)
/
√3 √3 10 [deg] Asynchrocheck Synchrocheck mode : Off, Synchro, Asynchro
Frequency SYNC Continuous 0.1 [Un] Dead line value : 0.1~0.8 xUn (0.1)
25
50 [Hz] (SECRSYN) Live line value Close pulse Live line value : 0.2~1.0 xUn (0.1)
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
1. SETTING TABLE
REU 615 3U< Start Value Curve Type Delay Time Start Value : 0.05~1.20 x Un (0.01)
27-R
(ABB) (PHPTUV) 0.75 [Un] 15 (IEC DT) 3500 [ms] Delay time : 60~300000 ms (10)
VT Ratio
415V 110V
/
√3 √3
1 : ANSI Ext. Inv. 2 : ANSI Very. Inv. 3 : ANSI Norm. Inv. 4 : ANSI Mod Inv. 5 : ANSI Def. Time 6 : L.T.E. Inv. 7 : L.T.V. Inv. 8 : L.T. Inv 9 : IEC Norm. Inv.
Curve Type :
10 : IEC Very Inv. 11 : IEC Inv. 12 : IEC Ext. Inv. 13 : IEC S.T. Inv. 14 : IEC L.T. Inv. 15 : IEC Def. Time 17 : Programmable 18 : RI type 19 : RD Type
Voltage Type : 5:ANSI Def.Time 15:IEC Def.Time 17:Inv.CurveA 18:Inv.CurveB 19:Inv.CurveC 20:Programmable 21:Inv.CurveA 22:Inv.CurveB 23:Programmable
∴ TOTAL LOAD 1600 kVA ∴ Full Load Current = 2225.93 (A) ( 0.415 kV )
ATTAC
CHMENT-3 MINIMUM FAULT LEVEL CA
ALCULATION
12 OF 14
Attachment-3 Minimum Fault Level Diagram (88SS14)
PROCESS SUBSTATION 14
Cable43 Cable45
CB199
CB202 CB204
14SW201-T/S CT ±
1250/1 R
Open
14SW201L-L4 CT ±
14SW201L-L3 CT ±
14SW201L-L2 CT ± CB261 14SW201R-R2 CT ±
14SW201R-R3 CT ±
14SW201L-L4 ZCT ± 14SW201L-L4 14SW201L-L3 ZCT ± 14SW201L-L3 14SW201L-L2 ZCT ± 14SW201L-L2 Open 14SW201R-R2 ZCT ± 14SW201R-R2 14SW201R-R3 ZCT ± 14SW201R-R3
100/1 100/1 100/1 100/1 100/1
Z1
Cable4 Cable16 Cable102 Cable110 Cable13
3-1/C 500 3-1/C 500 3-1/C 500 3-1/C 500 3-1/C 500
80 m R 80 m R 80 m 80 m 80 m R
14SW201 BUS(R)2
14TR202C-N 14TR202A-N 33 kV 14TR202B-N
14TR202C 14TR202A 14TR201A 14TR201A NCT 1250 A 14TR201B 14TR201B NCT 14TR202B
20 MVA 20 MVA 20 MVA 400/1 20 MVA 400/1 20 MVA
± ±
33/6.9 kV ±
33/6.9 kV ±
33/6.9 kV 33/6.9 kV 33/6.9 kV ±
RY-KM-1702A CB92
CB64 CB65
KM-1702C KM-1702A Open KM-1702B
±
7900 kW 7900 kW 14SW301-LR CT OCR
7900 kW
2000/1
14SW301 BUS(L) 6.6 kV 2000 A 19.63 14SW301-LR 14SW301 BUS(R) 6.6 kV 2000 A
CB120 CB117 CB76 CB69 CB114 CB108 CB75 CB91 CB104 CB130 CB131
Open Open Open Open Open Open Open Open Open Open Open
14SW301-L15 CT ±
14SW301-L14 CT ±
14SW301-L13 CT ±
14SW301-L12 CT ±
14SW301-L11 CT ±
14SW301-L10 CT ±
14SW301-L9 CT ±
14SW301-L8 CT ±
14SW301-L7 CT ±
14SW301-L6 CT ±
14SW301-L5 CT ±
14SW301-L4 CT ±
14SW301-L3 CT ±
14SW301-L2 CT ±
14SW301-R2 CT ±
14SW301-R3 CT ±
14SW301-R4 CT ±
14SW301-R5 CT ±
14SW301-R6 CT ±
14SW301-R7 CT ±
14SW301-R8 CT ±
14SW301-R9 CT ±
14SW301-R10 CT ±
14SW301-R11 CT ±
14SW301-R12 CT ±
14SW301-R13 CT ±
14SW301-R14 CT ±
14SW301-R15 CT ±
75/1 R 50/1 R 100/1 R 75/1 R 100/1 R 200/1 R 50/1 R 200/1 R 50/1 R 500/1 R 500/1 R 200/1 OCR 200/1 OCR 200/1 OCR 200/1 OCR 200/1 OCR 200/1 OCR 200/1 OCR 500/1 R 500/1 R 200/1 R 50/1 R 200/1 R 100/1 R 30/1 R 50/1 R 50/1 R 75/1 R
14SW301-L15 ZCT ±
14SW301-L14 ZCT
14SW301-L15 ±
14SW301-L13 ZCT
14SW301-L14 ±
14SW301-L12 ZCT
14SW301-L13 ±
14SW301-L11 ZCT
14SW301-L12 ±
14SW301-L10 ZCT
14SW301-L11 ±
14SW301-L9 ZCT
14SW301-L10 ±
14SW301-L8 ZCT
14SW301-L9 ±
14SW301-L7 ZCT
14SW301-L8 ±
14SW301-L6 ZCT
14SW301-L7 ±
14SW301-L5 ZCT
14SW301-L6 ± 14SW301-L5 14SW301-L4 ZCT ± 14SW301-L4 14SW301-L3 ZCT ± 14SW301-L3 14SW301-L2 ZCT ± 14SW301-L2 14SW301-R2 ZCT ± 14SW301-R2 14SW301-R3 ZCT ± 14SW301-R3 14SW301-R4 ZCT ± 14SW301-R4 14SW301-R5 ZCT ± 14SW301-R5 14SW301-R6 ZCT ±
14SW301-R7 ZCT
14SW301-R6 ±
14SW301-R8 ZCT
14SW301-R7 ±
14SW301-R9 ZCT
14SW301-R8 ±
14SW301-R10 ZCT
14SW301-R9 ±
14SW301-R11 ZCT
14SW301-R10 ±
14SW301-R12 ZCT
14SW301-R11 ±
14SW301-R13 ZCT
14SW301-R12 ±
14SW301-R14 ZCT
14SW301-R13 ±
14SW301-R15 ZCT
14SW301-R14 ± 14SW301-R15
50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1 50/1
Cable156 Cable151 Cable150 Cable149 Cable139 Cable137 Cable135 Cable131 Cable126 Cable112 Cable90 Cable70 Cable65 Cable84 Cable82 Cable69 Cable76 Cable80 Cable180 Cable181 Cable184 Cable185 Cable186 Cable187 Cable188 Cable189 Cable192 Cable193
1-3/C 25 1-3/C 25 1-3/C 25 1-3/C 25 1-3/C 25 1-3/C 70 1-3/C 25 1-3/C 70 1-3/C 25 2-3/C 120 2-3/C 120 1-3/C 150 1-3/C 150 1-3/C 150 1-3/C 150 1-3/C 150 1-3/C 150 1-3/C 150 2-3/C 120 2-3/C 120 1-3/C 70 1-3/C 25 1-3/C 70 1-3/C 25 1-3/C 25 1-3/C 25 1-3/C 25 1-3/C 25
291 m 231 m 291 m 291 m 431 m 431 m 351 m 431 m 291 m 431 m 431 m 80 m 80 m 80 m 80 m 80 m 80 m 80 m 431 m 431 m 431 m 351 m 431 m 431 m 231 m 291 m 231 m 231 m
6 %Z 6 %Z
PM-1721A PM-1720A PM-1718A PM-1717A PM-1711A PM-1707B PM-1706B PM-1703A KM-1742 PM-1705B PM-1702A PM-1702B PM-1705A PM-1703B PM-1706A PM-1707A PM-1711B PM-1715A PM-1716A
575 kW PM-1720B PM-1721B
355 kW 220 kW 500 kW 355 kW 1065 kW 315 kW 1150 kW 240 kW 2600 kW 2800 kW 2800 kW 2600 kW 1150 kW 315 kW 1065 kW 575 kW 160 kW 260 kW 220 kW 355 kW
Cable200 Cable202
9-1/C 500 9-1/C 500
35 m 35 m
14SW401L-L1 CT ±
14SW401R-R1 CT ±
14SW401L-L1 14SW401R-R1
CB111
CB113 CB109
0.415 kV Open
2500 A 14SW401-LR CT ±
2500/1 OCR
14SW401 Bus(L) 14SW401 Bus(R)
31.41 14SW401-LR 0.415 kV
2.78 34.2 2500 A
kA
6 %Z 6 %Z
Cable204 Cable205
9-1/C 500 9-1/C 500
35 m 35 m
14SW402L-L1 CT ±
14SW402R-R1 CT ±
14SW402L-L1 14SW402R-R1
CB72
CB70 CB74
14SW402-LR CT Open
±
14TR303A 14TR303A NCT 14TR303B 14TR303B NCT 14TR304 14TR304 NCT 14TR304E 14TR304E NCT
1.6 MVA 2500/1 1.6 MVA 2500/1 1.6 MVA 2500/1 1.6 MVA 2500/1
6.6/0.433 kV ±
6.6/0.433 kV ±
6.6/0.433 kV ±
6.6/0.433 kV ±
6 %Z 6 %Z 6 %Z 6 %Z
Cable6 Cable14
Cable206 Cable207
9-1/C 500 9-1/C 500 9-1/C 500 9-1/C 500
35 m 35 m 35 m 35 m
14SW403L-L1 CT ±
14SW403R-R1 CT ±
14SW404EL-L1 CT ±
14SW404ER-R1 CT ±
CB79
CB77 CB89 CB135 CB143
ML14SW403 SL14SW403 SR14SW403 SRH14SW403 ML14SW404E SL14SW404E SLH14SW404E MR14SW404E SR14SW404E SRH14SW404E
367 kW 123 kVA MR14SW403 37 kW 75.8 kVA 78 kW
138 kW 358 kVA 4.1 kVA 351 kVA 51.7 kVA 332 kVA
ATTAC
CHMENT-4 PROTEC
CTION RELAY SETT
TING TABL
LE
Con
ntents Remark
1) 33kkV Incoming
2) 33kkV Outgoing
3) 14T
TR201A/B TR
R 20MVA 2nd
d ; 6.6kV Inco
oming & Tie
4) 14T
TR201A/B TR
R 20MVA 2nd
d ; 6.6kV Outtgoing feeder
5) 14T
TR301A/B, 30
02A/B, 303A
A/B, 304A/BT
TR 1.6MVA 2n
nd ; 0.415kV Incoming & Tie
6) 0.415kV LV Mottor
7) 0.415kV LV Fee
eder
13 OF 14
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
- 33kV Incoming -
(14SW201)
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
CT Primary 1250 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
CT Primary 1250 [ A ]
Ratio Secondary 1 [A]
VT Primary 33 [ kV ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
FCT 27 ON / OFF ON
SYNC function 25
V< [V] 1 ~ 60 11
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
Direct CO YES or NO NO
CT Primary 1250 [ A ]
Ratio Secondary 1 [A]
VT Primary 33 [ kV ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
FCT 27 ON / OFF ON
SYNC function 25
V< [V] 1 ~ 60 11
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
Direct CO YES or NO NO
VT Primary 33 [ kV ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
FCT 27 ON / OFF ON
CT Primary 1250 [ kV ]
Ratio Secondary 1 [V]
[ Protection Setting ]
87/50-n 87B
CT Primary 1250 [ kV ]
Ratio Secondary 1 [V]
[ Protection Setting ]
87/50-n 87B
- 33kV Outgoing -
(14SW201)
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
CT Primary 600 [ A ]
Ratio Secondary 1 [A]
VT Primary 33 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 100 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
[ Protection Setting ]
I Diff 87T
[ Protection Setting ]
[ Protection Setting ]
I Diff 87T
I REF 64R
SLOPE 0.00~0.95 0
Attachment #04. Protection Relay Setting Table (88SS14) Sohar Refinery Improvement Project
[ Protection Setting ]
CT Primary 2000 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
NCT Primary 400 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC1 51N
EFHPTOC1 50N
DEFLPDEF 51G
PHPTUV 27
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, Live L, Dead B
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
SEQRFUF 60
CT Primary 2000 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ kV ]
Ratio Secondary 110 [ V ]
NCT Primary 2000 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
HIPDIF 64R
CT Primary 2000 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
PHPTUV 27-L
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, One Live Dead
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
SEQRFUF 60
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHPTUV 27-R
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50 1 ~ 19
EFLPTOC 51G
EFHPTOC 50G
CT Primary 500 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.17
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.32
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
RTD/mA RTD
CT Primary 500 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.16
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.15
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
RTD/mA RTD
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 200 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.17
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.47
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
RTD/mA RTD
CT Primary 200 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 160 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.16
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.21
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
RTD/mA RTD
CT Primary 100 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 125 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.17
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.45
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
RTD/mA RTD
CT Primary 100 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 125 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.15
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 2.73
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.14
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 2.52
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 50 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 80 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.2
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.61
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 50 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 50 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.17
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 2.98
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 50 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 50 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.18
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.45
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 50 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 50 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.15
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 2.73
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 30 [ A ]
Ratio Secondary 1 [A]
VT Primary 6.6 [ kV ]
Ratio Secondary 110 [ V ]
ZCT Primary 50 [ A ]
Ratio Secondary 1 [A]
P.F 50 [ A ]
[ Protection Setting ]
PHHPTOC 50
EFLPTOC 51G
EFHPTOC 50G
JAMPTOC 51LR
PSPTUV 27M
MNSPTOC 46M
Start Value [Un] 0.01~0.50 x In 0.19
(in steps of 0.01)
Curve Type 1 ~ 19 15
MPTTR 49M
Env temperature mode FLC Only, Use RTD, Set Amb Temp FLC Only
STTPMSU1 66
Start detection A [In] 1.0~10.0 x In -
(in steps of 0.1)
Motor start-up A [In] 1.0~10.0 x In 3.31
(in steps of 0.1)
Motor start-up time [s] 1~80.0 -
(in steps of 1)
Lock rotor time [s] 2~120 -
(in steps of 1)
Str over delay time [ms] 0~60000 -
(in steps of 1)
Operation mode Iit, IIt CB, IIt & stall, IIt & stall CB -
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC 51N
EFHPTOC 50N
PSPTUV 27
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, Live L, Dead B
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
NCT Primary 2500 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
EFLPTOC 51G
LREFPNDF 64R
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
PSPTUV 27-L
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, One Live Dead
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHPTUV 27-R
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
EFLPTOC 51N
EFHPTOC 50N
PSPTUV 27
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, Live L, Dead B
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
NCT Primary 2500 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
EFLPTOC 51G
LREFPNDF 64R
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
PSPTUV 27-L
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, One Live Dead
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHPTUV 27-R
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
EFLPTOC 51
PHHPTOC 50
EFLPTOC 51N
EFHPTOC 50N
PSPTUV 27
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, Live L, Dead B
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
NCT Primary 2500 [ A ]
Ratio Secondary 1 [A]
[ Protection Setting ]
EFLPTOC 51G
LREFPNDF 64R
CT Primary 2500 [ A ]
Ratio Secondary 1 [A]
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHLPTOC 51
PHHPTOC 50
PSPTUV 27-L
SECRSYN 25
Live dead mode Off, Both Dead, Live L Dead B, One Live Dead
Dead L Live B, Dead Bus L Any,
Dead L Bus Any, One Live Dead,
Not Both Live
Difference voltage [Un] 0.01~0.50 xUn 0.1
(in steps of 0.01)
Difference frequency [Fn] 0.001~0.100 xFn 0.001
(in steps of 0.001)
Difference angle [deg] 5~90 10
(in steps of 1)
Synchrocheck mode Off, Synchro, Asynchro Asynchrocheck
VT Primary 415 [ V ]
Ratio Secondary 110 [ V ]
[ Protection Setting ]
PHPTUV 27-R
- 0.415kV Motor -
(14SW401,14SW402,14SW403,14SW404E)
Attachment #04. LV Motor setting table (88SS14)
415V Motor Switchgear - 14SW401 "BUS L" E-1722A-M01 E-1722B-M03 E-1735A-M01 E-1735B-M03 E-1737A-M01 E-1737B-M03 E-1742A-M01
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9
Release
415V Motor Switchgear - 14SW401 "BUS R" E-1730A-M01 E-1730B-M03 E-1730C-M05 E-1730D-M07 E-1730E-M09 E-1730F-M11 E-1730G-M13
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
415V Motor Switchgear - 14SW401 "BUS R" E-1730H-M15 E-1735A-M02 E-1735B-M04 E-1737A-M02 E-1737B-M04 E-1744A-M01 E-1744B-M03
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
415V Motor Switchgear - 14SW402 "BUS L" PM-1724B PM-1725B PM-1726B PM-1727B PM-1728A PM-1729A PM-1730B
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
415V Motor Switchgear - 14SW403 "BUS L" E-1720A-M01 E-1720B-M03 E-1720C-M05 E-1720D-M07 E-1720E-M09 E-1720F-M11 E-1720G-M13
Motor rating [kW] 18.5 18.5 18.5 18.5 18.5 18.5 18.5
Motor power factor [%] 80.5 80.5 80.5 80.5 80.5 80.5 80.5
Motor efficient [%] 91.7 91.7 91.7 91.7 91.7 91.7 91.7
Full load current [A] 34.87 34.87 34.87 34.87 34.87 34.87 34.87
Basic
Starting time 2 2 2 2 2 2 2
Data
Locked rotor current [%] 650 650 650 650 650 650 650
MCCB AF [A] 100 100 100 100 100 100 100
MCCB AT [A] 50 50 50 50 50 50 50
CKT Type 401-3 401-3 401-3 401-3 401-3 401-3 401-3
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
415V Motor Switchgear - 14SW403 "BUS L" E-1720H-M15 E-1720I-M17 E-1720J-M19 E-1720K-M21 E-1720L-M23 E-1720M-M25 E-1720N-M27
Motor rating [kW] 18.5 18.5 18.5 18.5 18.5 18.5 18.5
Motor power factor [%] 80.5 80.5 80.5 80.5 80.5 80.5 80.5
Motor efficient [%] 91.7 91.7 91.7 91.7 91.7 91.7 91.7
Full load current [A] 34.87 34.87 34.87 34.87 34.87 34.87 34.87
Basic
Starting time 2 2 2 2 2 2 2
Data
Locked rotor current [%] 650 650 650 650 650 650 650
MCCB AF [A] 100 100 100 100 100 100 100
MCCB AT [A] 50 50 50 50 50 50 50
CKT Type 401-3 401-3 401-3 401-3 401-3 401-3 401-3
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9
Release
Magnetic
D sine Magnetic Setting 9 9 9 9 9 9 9
Release
- 0.415kV Feeder -
(14SW401,14SW402,14SW403,14SW404E)
Attachment #04. LV Feeder setting table (88SS14)
415V Feeder Switchgear - 14SW401 "BUS L" E-1750A-M03 E-1757A-M01 P-1702A-E-02 P-1705A-E-02 P-1711A-E-02 170WO401 170WO404/405
Current Setting, Ir (Ir=xIn) 40% 40% 40% 40% 40% 70% 70%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - 100% Ir 100% Ir
Overload
(Neutral) Time delay, TN - - - - - same as overload same as overload
Micro
(MTX 2.0)
processor Protection Mode - - - - - ON ON
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - 20%In 20%In
Earth fault
Time delay, tg - - - - - 100ms 100ms
(MTX 2.0)
Protection Mode - - - - - ON ON
415V Feeder Switchgear - 14SW401 "BUS R" E-1742A-M02 E-1750A-M02 P-1702B-E-02 P-1703B-E-02 P-1705B-E-02 P-1711B-E-02 170WO402/403
Current Setting, Ir (Ir=xIn) 45% 40% 40% 40% 40% 40% 70%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - 100% Ir
Overload
(Neutral) Time delay, TN - - - - - - same as overload
Micro
(MTX 2.0)
processor Protection Mode - - - - - - ON
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - 20%In
Earth fault
Time delay, tg - - - - - - 100ms
(MTX 2.0)
Protection Mode - - - - - - ON
Attachment #04. LV Feeder setting table (88SS14)
Current Setting, Ir (Ir=xIn) 40% 40% 40% 40% 40% 40% 40%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
415V Feeder Switchgear - 14SW402 "BUS R" K-1702B-E-02 K-1702B-E-03 KM-1741B ME-1710 170WO408/409 14MPP401 170MOP402
Current Setting, Ir (Ir=xIn) 40% 40% 50% 40% 70% 60% 40%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - 100% Ir 100% Ir 100% Ir 100% Ir
Overload
(Neutral) Time delay, TN - - - same as overload same as overload same as overload same as overload
Micro
(MTX 2.0)
processor Protection Mode - - - ON ON ON ON
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - 20%In 20%In 20%In 20%In
Earth fault
Time delay, tg - - - 100ms 100ms 100ms 100ms
(MTX 2.0)
Protection Mode - - - ON ON ON ON
Attachment #04. LV Feeder setting table (88SS14)
415V Feeder Switchgear - 14SW402 "BUS L" KM-1741A 170WO406/407 170WO414/415 170MOP401 170MOP403
Rating [kW] 45 [kVA] 45 [kVA] 19.2 [kVA] 2.5 [kVA] 235.8 [kVA] 11.8 [kVA]
power factor [%] 90 90 90 90 90 90
efficient [%] 100 100 100 100 100 100
Basic
Full load current [A] 69.57 69.57 29.68 3.87 364.5 17.78
Data
MCCB AF [A] 250 250 250 250 400 250
MCCB AT [A] 100 100 40 40 400 63
CKT Type 401-7 401-7 401-5 401-6 401-7 401-7
Thermal - Overload - - - - - -
Magnetic TM
Release Short Circuit - - - - - -
88MRS00- 88OS16-
415V Feeder Switchgear - 14SW403 "BUS R" E-1721-M01 170WO412/413 170WO418 14MLP401
00MPP400R HPP400
rating [kW] 4 45 [kVA] 45 [kVA] 195 [kVA] 235.8 [kVA] 23.5 [kVA]
power factor [%] 90 90 90 90 90 90
efficient [%] 100 100 100 100 100 100
Basic
Full load current [A] 6.19 69.57 69.57 301.43 392.32 36.33
Data
MCCB AF [A] 250 250 250 400 400 250
MCCB AT [A] 63 100 100 400 400 63
CKT Type 401-5 401-7 401-7 401-7 401-7 401-7
Thermal - Overload - - - - - -
Magnetic TM
Release Short Circuit - - - - - -
415V Feeder Switchgear - 14SW404E "BUS L" E-1720A-M02 E-1720C-M06 E-1720E-M10 E-1720G-M14 E-1720I-M18 E-1720K-M22 E-1720M-M26
Current Setting, Ir (Ir=xIn) 50% 50% 50% 50% 50% 50% 50%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
415V Feeder Switchgear - 14SW404E "BUS R" 14MLP402E E-1720B-M04 E-1720D-M08 E-1720F-M12 E-1720H-M16 E-1720J-M20 E-1720L-M24
Current Setting, Ir (Ir=xIn) 45% 50% 50% 50% 50% 50% 50%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
415V Feeder Switchgear - 14SW404E "BUS L" E-1720O-M30 E-1721-M02 E-1722A-M02 E-1726A-M01 E-1726A-M03 E-1726B-M04 E-1726C-M06
Current Setting, Ir (Ir=xIn) 50% 40% 40% 40% 40% 50% 50%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
Short Circuit
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
415V Feeder Switchgear - 14SW404E "BUS R" E-1720N-M28 E-1720P-M32 E-1722B-M04 E-1726A-M02 E-1726B-M05 E-1726C-M07 E-1726D-M09
Current Setting, Ir (Ir=xIn) 50% 50% 40% 40% 50% 50% 50%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
Attachment #04. LV Feeder setting table (88SS14)
415V Feeder Switchgear - 14SW404E "BUS L" E-1726D-M08 E-1726E-M10 E-1730A-M02 E-1730B-M04 E-1730C-M06 E-1730D-M08 E-1744A-M02
Rating [kW] 30 30 30 30 30 30 30
power factor [%] 90 90 90 90 90 90 90
efficient [%] 100 100 100 100 100 100 100
Basic
Full load current [A] 46.38 46.38 46.38 46.38 46.38 46.38 46.38
Data
MCCB AF [A] 250 250 250 250 250 250 250
MCCB AT [A] 100 100 100 100 100 100 100
CKT Type 401-5 401-5 401-5 401-5 401-5 401-5 401-5
Thermal - Overload - - - - - - -
Magnetic TM
Release Short Circuit - - - - - - -
Current Setting, Ir (Ir=xIn) 50% 50% 50% 50% 50% 50% 50%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
Short Circuit
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
415V Feeder Switchgear - 14SW404E "BUS R" E-1726E-M11 E-1730E-M10 E-1730F-M12 E-1730G-M14 E-1730H-M16 E-1744B-M04 17AP02-2
Current Setting, Ir (Ir=xIn) 50% 50% 50% 50% 50% 50% 40%
Overload
Protection Time delay, Tr(Inverse) 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir 3s at 6Ir
(MTX 2.0 & Protection Mode ON ON ON ON ON ON ON
MTX 1.0)
Thermal Memory Enable Enable Enable Enable Enable Enable Enable
Current Setting, IN (IN=xIr) - - - - - - -
Overload
(Neutral) Time delay, TN - - - - - - -
Micro
(MTX 2.0)
processor Protection Mode - - - - - - -
release
Short Circuit Current Setting, Is(Is=xIr) 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir 5.5 Ir
(MTX 2.0 & Time delay, ts Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous Instantaneous
MTX 1.0)
Protection Mode ON ON ON ON ON ON ON
Current Setting, Ig(Ig=xIn) - - - - - - -
Earth fault
Time delay, tg - - - - - - -
(MTX 2.0)
Protection Mode - - - - - - -
Attachment #04. LV Feeder setting table (88SS14)
88MRS00- 88OS16-
415V Feeder Switchgear - 14SW404E "BUS R" 17AP04-2 14BC501-2
00MPP401E LP402E
rating [kW] 12.9 [kVA] 19.2 [kVA] 29.6 [kVA] 11.8 [kVA]
power factor [%] 90 90 90 90
efficient [%] 100 100 100 100
Basic
Full load current [A] 19.95 29.68 45.76 18.25
Data
MCCB AF [A] 250 250 250 250
MCCB AT [A] 63 40 160 63
CKT Type 401-5 401-5 401-5 401-5
Thermal - Overload - - - -
Magnetic TM
Release Short Circuit - - - -
ATTAC
CHMENT-5 TIME CU
URRENT C
CHARACTERISTIC C
CURVE
Con
ntents Remark
2) 6.9//0.433kV Tra
ansformer (14
4TR – 301/30
02/303/304) OCR
4) 0.415kV Motor
14 OF 14
Attachment #05. Time Current Characteristic Curve (88SS14) Sohar Refinery Improvement Project
02SW201A
33 kV
500 500
02SW201B
300 300 33 kV
14SW201L-L1 - P
OC1
Siemens CB107 CB106
7SJ64
100 100
CT Ratio 1250:1
IEC - Very Inverse
Pickup = 1 (0.1 - 4 Sec - 1A)
50 50 Cable43 Cable45
Time Dial = 0.14
3x = 0.945 s, 5x = 0.472 s, 8x = 0.27 s
30 30
14SW201R-R1 - P
OC1 ± ±
1250/1 R 14SW201-T/S
5 5 14SW201 BUS(L) 14SW201 BUS(R)
Seconds
Seconds
14SW201R-R2 - P 33 kV 33 kV
3
OC1 3
14SW201L-L2 - P
OC1
Siemens CB2 CB4
7SJ64
1 14TR201A CT Ratio 600:1
1
.1 .1
14TR201A
Inrush 14TR201A 14TR201B
400/1 400/1
.05 .05 ± ±
14SW201L-L1 - 3P
.03 .03
14SW201R-R1 - 3P
14SW201-T/S - 3P
14SW201L-L2 - 3P
14SW201R-R2 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 100 14SW201 BUS(R) (Nom. kV=33, Plot Ref. kV=33) ETAP Star 12.0.0C
CB199
500 14SW201-T/S - P 500
OC1 CB202 CB204
300 Siemens 300
±
50 50 CB2 CB4
14SW201R-R2 - P
OC1
30 30
14SW201L-L2 - P ± ±
Seconds
OC1 3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
3 14SW301-R1 - P Inst = 10.25 (0.1 - 35 Sec - 1A) 3
OC1
1 ABB 1
REF 615. 14TR201A
CT Ratio 2000:1 Cable101 Cable107
.5 IEC - Very Inverse .5
Pickup = 1.09 (0.05 - 5 xCT Sec)
.3 Time Dial = 0.14 .3
3x = 0.945 s, 5x = 0.473 s, 8x = 0.27 s ± ±
OCR
.03 .03
2000/1
14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
14SW301-L1 - 3P 14SW201R-R2 - 3P
14SW201L-L2 - 3P 6.6 kV 6.6 kV
14SW301-R1 - 3P
14SW301-LR - 3P 14SW201-T/S - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 14SW201 BUS(R) (Nom. kV=33, Plot Ref. kV=33) ETAP Star 12.0.0C
CB199
500 500
CB202 CB204
14SW201-T/S - P
300 300
OC1 1250/1
±
R 14SW201-T/S
Siemens
7SJ64 14SW201 BUS(L) 14SW201 BUS(R)
RY-KM-1702A - OL CT Ratio 1250:1
33 kV 33 kV
100 Schweitzer IEC - Very Inverse 100
710 (R304) Pickup = 1 (0.1 - 4 Sec - 1A)
CT Ratio 800:1 Time Dial = 0.14
50 Run Curve (Curve, Hot) 3x = 0.945 s, 5x = 0.472 s, 8x = 0.27 s 50
Pickup = 1.15 (1.01 - 1.5 xFLA)
30 Curve Number = 1 30 CB328
Inst = 9 (0.1 - 20 xFLA) 14SW201L-L3 - P
Time Delay = 0.01 s OC1
Siemens ±
600/1 R
7SJ64
10 10
KM-1702A-Hot CT Ratio 600:1 ± 14SW201L-L3
100/1
IEC - Extremely Inverse
Pickup = 0.73 (0.1 - 4 Sec - 1A)
5 5 Cable16
Time Dial = 0.4
Seconds
Seconds
3x = 4 s, 5x = 1.33 s, 8x = 0.508 s
3 Inst = 9.4 (0.1 - 35 Sec - 1A) 3
14TR202A 14TR202A-N
1 14TR202A 1 ±
400/1
.5 .5
Cable17
.3 ∆ 0.344 s .3
Bus86
14TR202A 6.6 kV
Inrush
.1 .1
±
800/1 R
RY-KM-1702A
.05 .05
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 14SW201 BUS(R) (Nom. kV=33, Plot Ref. kV=33) ETAP Star 12.0.0C
6.9/0.433kV Transformer
(14TR - 301/302/303/304)
Amps X 10 (Plot Ref. kV=6.6)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
14SW301-LR - P
500 500
OC1
ABB
300 300
REF 615.
CT Ratio 2000:1 CB92
IEC - Very Inverse CB64 CB65
Pickup = 1.09 (0.05 - 5 xCT Sec)
Open
100
Time Dial = 0.14 100 ±
Seconds
OC1 3x = 2.3 s, 5x = 1.15 s, 8x = 0.656 s
3 Inst = 14.8 (0.1 - 40 xCT Sec) 3 Cable84 Cable82
14SW401-LR - P
OC1 Time Delay = 0.04 s
ABB
REF 615.
CT Ratio 2500:1 14TR301A 14TR301A 14TR301B
1 1
1.6 MVA 2500/1 1.6 MVA 2500/1
IEC - Very Inverse 6.6/0.433 kV ±
6.6/0.433 kV ±
14TR301A
Inrush ± ±
14SW401L-L1 14SW401R-R1
CB111
.05 .05
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
14SW301-LR - P
500 OC1 500
CB92
ABB CB64 CB65
300 REF 615. 300
Open
CT Ratio 2000:1 ±
50 50 CB69
14SW301-L3 - P CB75
30
OC1 30
14SW301-R3 - P
OC1 200/1
±
OCR
±
200/1 OCR
ABB
± 14SW301-L3 14SW301-R3
REF 615. 50/1 ±
10 10 50/1
14SW402L-L1 - P CT Ratio 200:1
OC1 IEC - Very Inverse Cable65 Cable69
Pickup = 0.87 (0.05 - 5 xCT Sec)
5 14SW402R-R1 - P 5
Seconds
Seconds
Time Dial = 0.34
OC1 3x = 2.3 s, 5x = 1.15 s, 8x = 0.656 s
3 Inst = 14.8 (0.1 - 40 xCT Sec) 3
14SW402-LR - P 14TR302A 14TR302B
OC1 Time Delay = 0.04 s 1.6 MVA 2500/1 1.6 MVA 2500/1
6.6/0.433 kV ±
6.6/0.433 kV ±
ABB 6 %Z 6 %Z
REF 615.
1 CT Ratio 2500:1 14TR302A 1
IEC - Very Inverse
Pickup = 1.11 (0.05 - 5 xCT Sec) Cable204 Cable205
.5 Time Dial = 0.19 .5
3x = 1.28 s, 5x = 0.641 s, 8x = 0.366 s ±
±
14SW402L-L1 14SW402R-R1
CB72
14TR302A CB70 CB74
Inrush Open
.1 .1 ±
2500/1 OCR
14SW402 Bus(L) 14SW402 Bus(R)
0.415 kV 14SW402-LR 0.415 kV
.05 .05
14SW402-LR - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 Bus35 (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C
Seconds
OC1 Time Dial = 0.34
3 3x = 2.3 s, 5x = 1.15 s, 8x = 0.656 s 3
14SW403-LR - P 14TR303A 14TR303B
OC1 Inst = 14.8 (0.1 - 40 xCT Sec)
1.6 MVA 2500/1 1.6 MVA 2500/1
Time Delay = 0.04 s 6.6/0.433 kV 6.6/0.433 kV
ABB ± ±
REF 615. 6 %Z 6 %Z
14TR303A
1 CT Ratio 2500:1 1
IEC - Very Inverse
Pickup = 1.11 (0.05 - 5 xCT Sec) Cable206 Cable207
.5 Time Dial = 0.19 .5
3x = 1.28 s, 5x = 0.641 s, 8x = 0.366 s
± ±
14SW403L-L1 14SW403R-R1
14TR303A CB77 CB89
Inrush CB79
.1 .1
Open
±
2500/1 OCR
.05 .05
14SW403 Bus(L) 14SW403-LR
14SW301-L4 - 3P 14SW403 Bus(R)
.03 .03
0.415 kV 0.415 kV
14SW403L-L1 - 3P 14SW301-R4 - 3P
14SW403R-R1 - 3P 14SW301-LR - 3P
14SW403-LR - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
14SW301-LR - P CB92
CB64 CB65
300
OC1 300
ABB Open
REF 615. ±
OCR
CT Ratio 2000:1 2000/1
14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
IEC - Very Inverse
100 Pickup = 1.09 (0.05 - 5 xCT Sec) 100 6.6 kV 6.6 kV
Time Dial = 0.14
3x = 0.945 s, 5x = 0.473 s, 8x = 0.27 s
50 50
CB104
30 30
14SW301-R5 - P
OC1 ±
Seconds
3x = 2.3 s, 5x = 1.15 s, 8x = 0.656 s
3 Inst = 14.8 (0.1 - 40 xCT Sec) 3
14SW404ER-R1 - P Time Delay = 0.04 s 14TR304 14TR304E
1.6 MVA 2500/1 1.6 MVA 2500/1
OC1 6.6/0.433 kV ±
6.6/0.433 kV ±
14SW404EL-L1 - P 6 %Z 6 %Z
14TR304
1 OC1 1
ABB Cable6 Cable14
REF 615.
.5 CT Ratio 2500:1 .5
IEC - Very Inverse
± ±
.05 .05
14SW404 E(L) 14SW404E (R)
.03 .03
0.415 kV 0.415 kV
14SW404EL-L1 - 3P 14SW301-LR - 3P
14SW301-R5 - 3P
14SW404ER-R1 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
6.6kV Motor
Amps X 100 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
14SW301-L1 - P
500 OC1 500
14SW301-R1 - P
300 OC1 300
14TR201A 14TR201B
14SW301-LR - P 20 MVA 400/1 20 MVA 400/1
± ±
OC1 33/6.9 kV 33/6.9 kV
ABB 8 %Z 8 %Z
100 REF 615. 100
CT Ratio 2000:1
IEC - Very Inverse Cable101 Cable107
50 Pickup = 1.09 (0.05 - 5 xCT Sec) 50
Time Dial = 0.14
30 3x = 0.945 s, 5x = 0.473 s, 8x = 0.27 s 30
± ±
Seconds
±
Time Constant = 180 OCR
k Factor = 1.1 2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
14SW301-L5 - OL 6.6 kV 6.6 kV
CB117 CB130
1 1
14SW301-R6 - P - 50 14TR201A Open
OC1
.5 ABB .5 ±
500/1
±
500/1 R
R
REM 615.
CT Ratio 500:1 ± 14SW301-L5 ± 14SW301-R6
.3 .3 50/1
Inst = 6.64 (0.1 - 40 xCT Sec) 50/1
Time Delay = 0.04 s Cable180
Cable90
14SW301-L5 - P - 50
14TR201A
OC1
.1 Inrush .1
.05 .05
14SW301-L1 - P
500 OC1 500
14SW301-R1 - P
300 300
OC1
14TR201A 14TR201B
14SW301-LR - P 20 MVA 400/1 20 MVA 400/1
± ±
CT Ratio 2000:1
IEC - Very Inverse Cable101 Cable107
50 Pickup = 1.09 (0.05 - 5 xCT Sec) 50
Seconds
±
CB120 CB131
1 1
14SW301-R7 - P 14TR201A
Open
OC1
.5 ABB .5 ± ±
.05 .05
14SW301-L1 - 3P
.03 .03
14SW301-R1 - 3P
14SW301-LR - 3P
PM-1705A-100% 14SW301-L6 - 3P
14SW301-R7 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1705B PM-1705A
Amps X 100 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 2600 kW 2600 kW
ETAP Star 12.0.0C
8 %Z 8 %Z
14SW301-LR - P
100 100
OC1
ABB
Cable101 Cable107
REF 615.
50 50
CT Ratio 2000:1
IEC - Very Inverse
30 30
Pickup = 1.09 (0.05 - 5 xCT Sec) ± ±
Seconds
±
Fuse7
Fuse38
1 1
14TR201A
Open
.5 .5 ± ±
200/1 R 200/1 R
.3 .3
± 14SW301-L8 ± 14SW301-R8
50/1 50/1
Cable131 Cable184
14TR201A
Inrush
.1 .1
.05 .05
PM-1703A-100%
.03 .03
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L8 - 3P
14SW301-R8 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1703A
1150 kW PM-1703B
1150 kW
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C
Seconds
REM 615. ±
OCR
CT Ratio 200:1 2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
Thermal Overload Curve
Pickup = 0.59 (0.05 - 4 xCT Sec) 6.6 kV 6.6 kV
Time Constant = 180
k Factor = 1.1
14SW301-L10 - OL Fuse11 Fuse40
1 1
Open
14TR201A
.5 .5 ± ±
200/1 R 200/1 R
.3 .3 ± 14SW301-L10 ± 14SW301-R10
50/1 50/1
Cable137 Cable186
14TR201A
.1
Inrush .1
.05 .05
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1707B PM-1707A
Amps X 100 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 1065 kW 1065 kW
ETAP Star 12.0.0C
Seconds
±
OCR
Pickup = 0.63 (0.05 - 4 xCT Sec) 2000/1
3 Time Constant = 180 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
k Factor = 1.1 6.6 kV 6.6 kV
14SW301-L11 - OL
Fuse13 Fuse41
1 1
Open
14TR201A
± ±
.5 .5 100/1 100/1
R R
± 14SW301-L11 ± 14SW301-R11
.3 .3 50/1 50/1
Cable139 Cable187
14TR201A
Inrush
.1 .1
.05 .05
.03
PM-1711A-100% .03
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L11 - 3P
14SW301-R11 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1711A PM-1711B
575 kW 575 kW
Amps X 100 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C
OC1 8 %Z 8 %Z
100 100
14SW301-LR - P
OC1
Cable101 Cable107
50
ABB 50
REF 615.
CT Ratio 2000:1
30 30
IEC - Very Inverse ± ±
Open
5 5
Seconds
Seconds
±
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
14SW301-L13 - OL 6.6 kV 6.6 kV
ABB
REM 615.
CT Ratio 100:1 Fuse20
1 Thermal Overload Curve 14TR201A
1
Pickup = 0.56 (0.05 - 4 xCT Sec) Open
Time Constant = 120
.5 k Factor = 1.1 .5 ±
100/1 R
.3 .3 ± 14SW301-L13
50/1
Cable150
14TR201A
Inrush
.1 .1
.05 .05
.03 .03
PM-1718A-100% 14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L13 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1718A
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 500 kW
ETAP Star 12.0.0C
Bussmann 14SW301-L1 - P
300 7.2WFNHA OC1 300
Other 7.2 kV 14TR201A 14TR201B
80A
14SW301-R1 - P 20 MVA 400/1 20 MVA 400/1
± ±
OC1 33/6.9 kV 33/6.9 kV
8 %Z 8 %Z
14SW301-LR - P
100 100
OC1
ABB
Cable101 Cable107
50
REF 615. 50
CT Ratio 2000:1
IEC - Very Inverse
30 30
Pickup = 1.09 (0.05 - 5 xCT Sec)
PM-1717A-Hot 2000/1
±
2000/1
±
10 10 CB92
CB64 CB65
Open
5 5
Seconds
Seconds
±
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
14SW301-R15 - OL 6.6 kV 6.6 kV
ABB
REM 615. Fuse47
CT Ratio 75:1 Fuse22 Fuse19
1 1
Thermal Overload Curve 14TR201A
Open
Pickup = 0.51 (0.05 - 4 xCT Sec)
.5 Time Constant = 180 .5 ± ± ±
.05 .05
14SW301-R1 - P 8 %Z 8 %Z
100 OC1 100
14SW301-LR - P
Cable101 Cable107
50 OC1 50
ABB
30
REF 615. 30
CT Ratio 2000:1 ± ±
Open
5 5
Seconds
Seconds
±
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
6.6 kV 6.6 kV
14SW301-R9 - OL
ABB
REM 615. Fuse9 Fuse39
1 1
CT Ratio 50:1 14TR201A
Open
Thermal Overload Curve
.5 Pickup = 0.72 (0.05 - 4 xCT Sec) .5 ± ±
.05 .05
PM-1706A-100%
.03 .03
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L9 - 3P
14SW301-R9 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1706B PM-1706A
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 315 kW 315 kW
ETAP Star 12.0.0C
Bussmann
300 7.2WFNHA 300
14SW301-LR - P
OC1 Cable101 Cable107
50 50
ABB
REF 615.
30 PM-1716A-Hot CT Ratio 2000:1
30
± ±
5 5
Open
Seconds
Seconds
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
6.6 kV 6.6 kV
1 1
Fuse43
14TR201A Open
14SW301-R13 - OL
.5 ABB .5
±
.05 .05
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-R13 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1716A
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C
260 kW
500 500
Fuse5
Bussmann
300 300
7.2WFNHA
Other 7.2 kV 14TR201A 14TR201B
400/1 400/1
50A 14SW301-L1 - P 20 MVA
±
20 MVA
±
Open
5 5
Seconds
Seconds
±
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
14SW301-L7 - OL 6.6 kV 6.6 kV
ABB
REM 615.
CT Ratio 50:1 Fuse5
1 Thermal Overload Curve 1
Pickup = 0.65 (0.05 - 4 xCT Sec) 14TR201A
Time Constant = 540
.5 k Factor = 1.1 .5 ±
50/1 R
.3 .3 ± 14SW301-L7
50/1
14TR201A Cable126
Inrush
.1 .1
.05 .05
KM-1742-100%
.03 .03
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L7 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
KM-1742
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 240 kW
ETAP Star 12.0.0C
500 500
Fuse21
300 Bussmann 300
7.2WFNHA 14SW301-L1 - P 14TR201A 14TR201B
Other 7.2 kV OC1 20 MVA 400/1 20 MVA 400/1
± ±
Open
5 5
Seconds
Seconds
±
OCR
2000/1
3 3 14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
6.6 kV 6.6 kV
Fuse21 Fuse46
1 1
14TR201A Open
.5 .5
14SW301-R14 - OL ± ±
50/1 R 50/1 R
ABB
.3 REM 615. .3 ± 14SW301-L14 ± 14SW301-R14
50/1 50/1
CT Ratio 50:1
Thermal Overload Curve
14TR201A Cable151 Cable192
Pickup = 0.56 (0.05 - 4 xCT Sec)
Time Constant = 180 Inrush
.1 .1
k Factor = 1.1
14SW301-L14 - OL
.05 .05
.03 .03
PM-1720A-100%
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-L14 - 3P
14SW301-R14 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1720A PM-1720B
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) 220 kW 220 kW
ETAP Star 12.0.0C
500 500
Fuse42 14SW301-L1 - P
300 Bussmann OC1 300
7.2WFNHA 14SW301-R1 - P 14TR201A 14TR201B
Other 7.2 kV 20 MVA 400/1 20 MVA 400/1
OC1 ± ±
50A 33/6.9 kV 33/6.9 kV
14SW301-LR - P 8 %Z 8 %Z
100 OC1 100
ABB
REF 615. Cable101 Cable107
50 50
CT Ratio 2000:1
IEC - Very Inverse
30 Pickup = 1.09 (0.05 - 5 xCT Sec) 30
PM-1715A-Hot Time Dial = 0.14
± ±
10 10
CB92
CB64 CB65
5 5 Open
Seconds
Seconds
OCR
3 3
2000/1
14SW301 BUS(L) 14SW301-LR 14SW301 BUS(R)
6.6 kV 6.6 kV
1 1 Fuse42
14TR201A Open
.5 14SW301-R12 - OL .5
±
ABB 30/1 R
.3 REM 615. .3
± 14SW301-R12
CT Ratio 30:1 50/1
Thermal Overload Curve
Pickup = 0.69 (0.05 - 4 xCT Sec) 14TR201A Cable188
Time Constant = 180 Inrush
.1 .1
k Factor = 1.1
.05 .05
.03 .03
PM-1715A-100%
14SW301-L1 - 3P
14SW301-R1 - 3P
14SW301-LR - 3P
14SW301-R12 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
PM-1715A
Amps X 10 14SW301 BUS(R) (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C 160 kW
0.415kV Motor
Amps X 10 Bus140 (Nom. kV=0.415, Plot Ref. kV=0.415)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
14SW401L-L1 - P
300
OC1 300 14TR301A 14TR301B
14SW401R-R1 - P 1.6 MVA 2500/1 1.6 MVA 2500/1
6.6/0.433 kV ±
6.6/0.433 kV ±
OC1 6 %Z 6 %Z
14SW401-LR - P
100 OC1 100
ABB Cable200 Cable202
REF 615.
50 CT Ratio 2500:1 50
IEC - Very Inverse
30 Pickup = 1.11 (0.05 - 5 xCT Sec) 30
± ±
OCR
Stall Time = 5
5 5 14SW401 Bus(L) 14SW401-LR 14SW401 Bus(R)
Seconds
Seconds
0.415 kV 0.415 kV
3 3
1 14TR301A 1 1/1
±
MR
14SW401-M
CB376
.5 .5
.3 .3
14TR301A
Inrush PM-1708A
.1 PM-1708A-100% .1 37 kW
.05 .05
.03 .03
14SW401L-L1 - 3P
14SW401R-R1 - 3P 14SW401-M - 3P
14SW401-LR - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 Bus140 (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 12.0.0C
500 500
OC1
14TR302A 14TR302B
14SW402R-R1 - P 1.6 MVA 2500/1 1.6 MVA 2500/1
OC1 6.6/0.433 kV ±
6.6/0.433 kV ±
OCR
Time Dial = 0.19
14SW402L-L1 14SW402R-R1
3x = 1.28 s, 5x = 0.641 s, 8x = 0.366 s CB72
10 10 CB70 CB74
Open
±
2500/1 OCR
5 5 14SW402 Bus(L) 14SW402 Bus(R)
Seconds
Seconds
0.415 kV 14SW402-LR 0.415 kV
3 3
1 14TR302A 1
±
1/1 MR
.5 .5 14SW402-M
CB381
.3 .3
14TR302A
Inrush
.1 .1
PM-1710A
55 kW
.05 .05
.03
PM-1710A-100% .03
14SW402L-L1 - 3P
14SW402R-R1 - 3P 14SW402-M - 3P
14SW402-LR - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 Bus142 (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 12.0.0C
500 500
OC1 6 %Z 6 %Z
ABB
50 50
REF 615.
CT Ratio 2500:1 Cable206 Cable207
30 IEC - Very Inverse 30
Pickup = 1.11 (0.05 - 5 xCT Sec)
± ±
Time Dial = 0.19 2500/1 OCR 2500/1 OCR
3x = 1.28 s, 5x = 0.641 s, 8x = 0.366 s
14SW403L-L1 14SW403R-R1
10 10
14SW403-M - OL CB77 CB89
CB79
L&T
5 MCOMP. 5 Open
Seconds
Seconds
CT Ratio 1:1 ±
14TR303A
1 1
.5 .5 ±
1/1 MR
.3 .3 14SW403-M
CB397
14TR303A
Inrush
.1 PM-1719B-100% .1
PM-1719B
.05 .05
110 kW
.03 .03
14SW403L-L1 - 3P
14SW403R-R1 - 3P
14SW403-M - 3P
14SW403-LR - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 100 Bus152 (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 12.0.0C
500 500
300 300
14SW404ER-R1 - P
OC1
14SW404EL-L1 - P
OC1 14TR304 14TR304E
100 100
ABB 1.6 MVA 2500/1 1.6 MVA 2500/1
REF 615. 6.6/0.433 kV ±
6.6/0.433 kV ±
CT Ratio 2500:1 6 %Z 6 %Z
50 50
IEC - Very Inverse
Pickup = 1.11 (0.05 - 5 xCT Sec) Cable6
30 Time Dial = 0.19 30 Cable14
3x = 1.28 s, 5x = 0.641 s, 8x = 0.366 s
14SW404E-M - OL
L&T ± ±
Seconds
Open
3 3
1 14TR304 1
.5 .5 ±
1/1 MR
.3 .3 14SW404E-M
CB398
14TR304
Inrush
.1 .1
PM-1376B-100%
PM-1376B
.05 .05
45 kW
.03 .03
14SW404EL-L1 - 3P
14SW404E-M - 3P
14SW404ER-R1 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 14SW404 E(L) (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 12.0.0C
02SW201A
33 kV
500 500
02SW201B
300 300 33 kV
CB107 CB106
100 100
14SW201R-R2 - G 14SW201L-L2 - G
OC1 OC1
50 Siemens Siemens 50 Cable43 Cable45
7SJ64 7SJ64
30 CT Ratio 100:1 CT Ratio 600:1 30
Definite Time Definite Time
Pickup = 0.6 (0.05 - 4 Sec - 1A) Pickup = 0.1 (0.05 - 4 Sec - 1A) ±
R
±
1250/1 R 14SW201-T/S
5 5 14SW201 BUS(L) 14SW201 BUS(R)
Seconds
Seconds
33 kV 33 kV
3 3
CB2 CB4
1 1
± ±
600/1 R 600/1 R
.5 .5
± 14SW201L-L2 ± 14SW201R-R2
100/1 100/1
.3 .3
Cable102 Cable110
.1 .1
14TR201A 14TR201B
400/1 400/1
.05 .05 ± ±
.03 .03
14SW201L-L2 - G - LG
14SW201R-R2 - G - LG
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps 14SW201 BUS(L) (Nom. kV=33, Plot Ref. kV=33) ETAP Star 12.0.0C
500 500
300 300
14TR201A 14TR201B
400/1 400/1
± ±
14SW301-L1 - G
OC1
100 ABB 100
REF 615.
CT Ratio 2000:1 Cable101 Cable107
50 IEC - Definite Time 50
Pickup = 0.08 (0.01 - 5 xCT Sec)
30 Time Dial = 0.6 30 ± ±
Seconds
OCR
Time Dial = 0.6 14SW301 BUS(L) 2000/1
3 3x = 0.6 s, 5x = 0.6 s, 8x = 0.6 s 3 14SW301-LR 14SW301 BUS(R)
6.6 kV 6.6 kV
CB117 CB108
1 1
±
±
.5 .5
500/1 R 200/1 OCR
± 14SW301-L5 ± 14SW301-R2
50/1 50/1
.3 .3
Amps X 10 14SW301 BUS(L) (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 12.0.0C
500 500
300 300
100 100
50 50
30 30
14SW402L-L1 - G
OC1
14SW402R-R1 - G
OC1
10 10
ABB
REF 615.
CT Ratio 2500:1
5 5
Seconds
Seconds
IEC - Very Inverse
Pickup = 0.26 (0.01 - 5 xCT Sec)
3 3
Time Dial = 0.27 14TR302A 14TR302B
3x = 1.82 s, 5x = 0.911 s, 8x = 0.521 s 1.6 MVA 2500/1 1.6 MVA 2500/1
6.6/0.433 kV ±
6.6/0.433 kV ±
6 %Z 6 %Z
1 1
Cable204 Cable205
.5 .5
±
±
14SW402L-L1 14SW402R-R1
CB72
CB70 CB74
.1 .1
Open
±
2500/1 OCR
14SW402 Bus(L) 14SW402 Bus(R)
0.415 kV 14SW402-LR 0.415 kV
.05 .05
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 100 14SW402 Bus(L) (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 12.0.0C