DATA SHEET

CHILLER WITH REFRIGERANT FGAC 2004-8092 D/E G 1/2


R-454B

Fig. 1: Sample versions of the unit series (from left to right: 2 compressors, 4 compressors, 4-8 compressors)

Table of Contents

Order-related documentation ...................................................................................................................................1


Type Code ...............................................................................................................................................................2
Unit description ........................................................................................................................................................3
Options and accessories .........................................................................................................................................4
Operating limits ......................................................................................................................................................11
General Data .........................................................................................................................................................13
Noise levels ...........................................................................................................................................................20
Footprint .................................................................................................................................................................22
Anti-vibration mounts .............................................................................................................................................22
Electrical data ........................................................................................................................................................25
Terminal scheme ...................................................................................................................................................28

Order-related documentation

NOTICE!
For detailed planning, please only use the order-related documentation. Detailed dimensional drawings can be
obtained on request from your responsible FläktGroup sales office. Specifications and technical data are subject
to regular updates. The manufacturer reserves the right to make necessary changes to information without prior
written notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Type Code

CHILLER | FGAC 1015 – 2050 AD 1/2


FG A C 2 004 D G 1 _

Number of compressors
Operating mode

Supply voltage
Capacity stage
Condensing

Unit model
Refrigerant
Unit series

Series
FG FläktGroup Series
Air cooled
A
(outdoor installation)
C Chiller
2 2 Scroll compressors
4 4 Scroll compressors
5 5 Scroll compressors
6 6 Scroll compressors
8 8 Scroll compressors
004- Capacity sizes with 2 compressors (plate, D series):
092 004, 005, 006, 007, 008, 009, 010,
011, 012, 014, 016, 018, 020 ,022

018- Capacity sizes with 4 compressors (plate, D series):


037 018, 021, 024, 026, 029, 033, 037

040- Capacity sizes with 4 compr. (shell and tube, E series):


046 040, 042, 046

051- Capacity sizes with 5 compr. (shell and tube, E series):


058 051, 058

063- Capacity sizes with 6 compr. (shell and tube, E series):


070 063, 067, 070

080- Capacity sizes with 8 compr. (shell and tube, E series):


092 080, 084, 092
D D series units (2 & 4 compressors)
E E series units (4 - 8 compressors)
G Refrigerant R-454B
1 400 V / 3~ / 50 Hz / N / PE
2 400 V / 3~ / 50 Hz / PE
_ Standard
.SL SL unit – super low noise version
.HE HE unit - high efficiency version
.D Standard unit with desuperheater for partial heat recovery
.SD SD unit - super low noise version with desuperheater for partial heat recovery
.HD HD unit - highly efficient version with desuperheater for partial heat recovery
Fig. 2: Explanation of unit type code

Seite 2/28 PR-2020-1032-DE • R5-07/2021 • FläktGroup haftet nicht für Druckfehler und behält sich das Recht vor, Inhalte unangekündigt zu ändern.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Unit description
FläktGroup Chillers with scroll compressors
- Air-cooled for outdoor installation above ground level
- Refrigerant R-454B (GWP 466), safety class A2L according to ISO 817
- ErP 2021 compliant according to (EU) 2016/2281
- 35 unit sizes available
- 3 unit models:
- Standard/.D version
- .SL/.SD - version, sound-optimised with noise reduction up to 8 dB(A)
- .HE/.HD - version, with standard EC fans
- Version with desuperheater for partial heat recovery optional (.D /.SD/ .HD version)
- High energy efficiency at full and part-load mode
- Capacity range approx. 40 kW to 870 kW cooling capacity
- Built-in pump or double pump (redundancy) optionally available, models with standard delivery head or
increased delivery head, as well as on/off pump or speed-controlled pump with increased energy
efficiency.
- Units with built-in pump or pumps are optionally available with built-in buffer tank
- 2-4 refrigerant circuits with 2-3 compressors per circuit
- 2-8 Quiet, low-vibration, fully hermetic scroll compressor
- Electronic expansion valves (EEV) and solenoid valve in the liquid line as standard
- EC fans standard on .HE/.HD units, optional on all other units
- Al/Al micro-channel heat exchanger as condenser, optionally with coating
- Optional with protective grille (Option .I04)
- 1 plate heat exchanger as evaporator (sizes 2004-4037)
- 1 shell and tube heat exchanger as evaporator (sizes 4040-8092)
- Antifreeze heater for the evaporator for unit operation and unit stand-by without glycol at ambient
temperatures above -10 °C; suitable frost protection heating down to -20 °C as special option
- 1 plate heat exchanger as desuperheater (unit types .D/.SD/.HD, sizes 2004-4037)
- 2-4 plate heat exchangers (1 per refrigeration circuit) as desuperheaters (unit types .D/.SD/.HD, sizes
4040-8092), water circuit to be connected in parallel by customer
- Safety valve 10 bar installed; for units with buffer tank 6 bar
- Blow-off lines of the safety valves on the refrigeration circuit side led to the outside or safety valve located
outside
- Water outlet temperature -12 to +20 °C possible depending on size; or -8 to +20 °C for units with partial
heat recovery; restrictions depending on the outside temperature
- Air intake temperature down to min. -20 °C and max. +52 °C possible; depending on selected medium,
water temperature and selected accessories; see application limits diagram
- Wind protected installation required for operation below -10 °C outdoor temperature
- If the temperature falls below the minimum air inlet temperature or exceeds the maximum air inlet
temperature, the unit must be disabled
- Required vibration dampers available as accessories
- Power supply 400V / 3~ / 50 Hz / PE or 400V / 3~ / 50 Hz / N / PE
- Numbered connecting terminals
- Built-in phase sequence protection relay
- Automatic circuit breaker for load and control circuit
- FläktGroup Controls
- Compact display with 8-line display
- Display protection flap with magnetic closure
- Unit release via digital input (standard) or BMS (option)
- Pump relay and, if necessary, 0-10 V output for controlling one or two on-site water pump(s) for units
without built-in pump(s) (optional)
- Group fault signal
- Required flow monitor for on-site installation available as accessory (option .I10)
- Water filters up to 4" for on-site installation available as accessories; from size 4040 on, water filters must
be provided by the customer
- On-site pipe expansion joints must be installed to decouple vibrations, noise transmission and linear
expansion
- All units of the series FGAC 2004-8092 D/E G 1/2 (.SL/ .HE) are Eurovent certified

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 3/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Options and accessories

Mechanics accessories
FGPE modules - Built-in pump module
Consisting of one pump or two parallel pumps with redundancy function. The
water connections are equipped with internal screw threads.
Other components are:
- Steel pipes, water vapour proof insulated
- Pump protection with overcurrent relay
- Pump control with pump supply line and overrun time
- Prevention of pump blockages through regular activation
Pump modules assembled and wired by the manufacturer result in significant
savings in installation costs.
There are 8 different variants of built-in pumps available
- On/Off pump with standard head
- On/off pump with increased delivery head
- Inverter pump with standard head
- Inverter pump with increased delivery head
- On/Off double pumps with standard head
- On/Off double pumps with increased delivery head
- Inverter double pumps with standard head
- Inverter double pumps with increased delivery head
Options - Built-in buffer tank to increase the water volume of the system
.M01/ .M02/ .M03/ This results in considerable savings in installation costs. Other components are:
.M04/ .M05/ .M07/ - Expansion tank (dimensioned for internal buffer tank)
.M08 - Safety valve
- Inlet, air vent and drain valve
- Manometer
.M01 90 L Tank for unit sizes 2004-2006 (.D/.SL/.SD/.HE/.HD)
.M02 140 L Tank for unit sizes 2007-2014 (.D/.SL/.SD/.HE/.HD)
.M03 250 L Tank for unit sizes 2016-2022 (.D/.SL/.SD/.HE/.HD)
.M04 500 L Tank for unit sizes 4018-4026 (.D/.SL/.SD/.HE/.HD)
.M08 600 L Tank for unit sizes 4040-6057 (.D) *)
.M05 700 L Tank for unit sizes 4029-4037 (.D/.SL/.SD/.HE/.HD)
4040-4046, 5058 (.D) *)
.M07 1000 L Tank for unit sizes 6063-8092 (.D)
4040-8092 .SL/.SD/.HE/.HD
Only for units with built-in pumps
*) a 600 or 700 L tank is available dependent on the selected pump module

Installation of accessories
Option .I01 - Spring anti-vibration mounts
Anti-vibration mounts with spring elements for reduction of vibration transfer
(only unit sizes 4018- (enclosed).
8092)
Option .I02 - Rubber anti-vibration isolator
Anti-vibration mounts with rubber elements to minimize vibration transmission
(supplied separately).
FläktGroup recommends the use of rubber anti-vibration isolators. Alternatively,
spring anti-vibration mounts can be used depending on the project specifications.
Option .I04 - Protection grille for air-cooled heat exchanger
Protection grille on external sides of the air-cooled heat exchanger for protecting
fins against damage due to shipping and weather.

Page 4/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Option .I08 - Chilled-water connections with flanges


Depending on the unit type, either mounted flanges or separate flange adaptor kit.
Option .I55 or .I57 - Anti-corrosion coating for microchannel heat exchangers (MCHX)
100% epoxy polymer e-coating process for the entire air-cooled microchannel
heat exchanger as protection against corrosion, UV radiation and for increased
weather resistance to medium aggressive air pollution and use with medium salty
air near the coast
Option .I58 - Display protection
Instead of a display protection flap with magnetic closure, a display protection flap
with lip seal and rotary closure is supplied.
Option .I67/ .I10 - Flow monitor (supplied separately)
with paddle for installation in hydraulic circuit at chilled water outlet.
The on-site installation and wiring of the flow monitor is a prerequisite for warranty
claims!
.I67 Type 1 for unit size 2004-2020
.I10 Type 2 for unit size 4018-8092

Option .I68 to .I72 - Water strainer for installation in the hydraulic circuit at the unit inlet
(supplied separately)
A water strainer must be installed before the direct inlet into the heat exchanger(s)
to protect the heat exchanger(s) from dirt and deposits. The "Y-type" water
strainer has a mesh width of 0.9 mm. The filter insert can be removed without
difficulty and cleaned for maintenance purposes without dismantling the valve
body.

.I68 Filter 1 1/2" for unit size 2004-2006


.I69 Filter 2" for unit size 2007-2009
.I70 Filter 2 1/2" for unit size 2010-2014
.I71 Filter 3" for unit size 2016-2020 and 4018-4021
.I72 Filter 4" for unit size 2022 and 4024-4037

Refrigeration circuit accessories


Option .R13 - High and low pressure gauges
Refrigerant gauge for high and low pressure side for reading off current operating
pressures.
Option .R19 - Safety valve in double model for high and low pressure side
Two safety valves are connected via a changeover valve on the high and low
pressure side each. By using a changeover valve a trouble-free and fast
replacement of safety valves without refrigerant loss is possible for maintenance
and service jobs.
Option .R26 - Shut-off valves for compressor suction and pressure side
Service shut-off valve assembled for fast and easy maintenance

Electrical accessories
Option .E02 - Cabling in colour sequence: L1: brown L2: black L3: grey
The wiring of the load circuit for the unit is carried out in the following colour
sequence:
L1: brown, L2: black, L3: gray
This colour sequence is frequently requested in Great Britain.
Option .E03 - Operation message of compressor
Floating contacts for status indication of each respective compressor.

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 5/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Option .E05 - Temperature sensor for on-site 2-circuit buffer storage


Temperature sensor for on-site installation in a 2-circuit buffer tank.
The temperature in the buffer tank is used to detect whether the consumers in the
secondary circuit are consuming power. If there is no consumption, the pump(s)
will be deactivated. Can be combined with on/off or inverter pumps.
NTC sensor with 12 m cable length, possibly including required hardware
extension for the control system. Cable can be extended by the customer to a
maximum of 100 m with 1 mm² cable cross section. If the installation is in an
industrial environment (EN 61000-6-2), the length of the connection must be less
than 10 m.
Option .E06 - Soft starter for the compressors
Cannot be combined with reactive current compensators
Option .E21 - Sliding setpoint via a 4-20 mA signal provided on-site
Shifting the cold and hot water setpoint value in a fixed range via a 4-20 mA
(Standard signal provided on-site. Changing the setpoint, e.g. during night operation, can
accessories for size result in significant savings potential.
4018-8092;
replaceable by .E22)
Option .E22 - 2nd setpoint via on-site normally open contact
External switch-over between two setpoint values set for unit by closing an on-site
(cannot be combined floating contact. Raising the setpoint, e.g. during night operation, can realize
with .E21) significant savings potential.
For units with option .E22, the floating setpoint adjustment by means of a 4-20 mA
signal cannot be used.
Option .E23 - Demand limit / load limitation
Reduction of electrical power consumption by deactivating compressors or their
(Standard speed (demand limit switch) by opening an on-site floating contact. This function
accessories for sizes is used if a full electrical power supply is not available
2004-2022 and 4040-
8092)
Option .E13 /.E11 - Antifreeze heating
suitable for equipment operation and equipment stand-by without glycol.
.E13 Antifreeze heating for pump(s) and piping
.E11 Antifreeze heater for pump(s) and piping and tank
The evaporator is equipped as standard with an anti-freeze heater, which is
designed for unit operation and unit stand-by down to -10 °C outside temperature.
Option .E10 - Reinforced antifreeze heating for the evaporator
suitable for unit operation and unit stand-by without glycol for installation sites with
(Special option) lowest ambient temperatures between -10 °C and -20 °C.
Note: FläktGroup recommends that the pump run for frost protection is also
activated depending on the water and air temperature!
Frost protection by pump run: Parameter PMP0046 = 1 (activated)
Based on water and air temperature: Parameter PMP0047 = 1 (activated)
On request - Variable setpoint temperature using outdoor temperature
The setpoint temperature can be controlled in a variable manner depending on
the outdoor temperature. In addition, an external temperature sensor is supplied
for on-site mounting.
On request - Compensation of reactive current for individual compressor motors
Individual PFC capacitors are connected in parallel to each compressor motor in
order to reduce the idle current to a minimum and to improve the cos-phi of the
unit.
Cannot be combined with soft starters (option .E06).

Page 6/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

For standard/.D/.SL/.SD units, select one of the .E46, .E50, .E81 or .E82 options to define the fan types AC or EC
and the operating range. A prerequisite for operation below -10 °C is a wind-protected installation (wind speed < 2
m/s) for each variant described.
Option .E46 - Standard operating range (AC fans)
At chilled water outlet temperature of ≥7 °C the unit can be operated down to
(standard/ .D/ .SL/ outside temperature of -20 °C (or at ≥6 °C to -19 °C).
.SD units)
Further information on the application limits is given in the operating limit
diagrams on the following pages.
Option .E50 - Extended operating range (AC fans)
At chilled water outlet temperature of ≥0 °C, the unit can be operated down to
(standard/ .D/ .SL/ outside temperature of -20 °C.
.SD units of the sizes
2004-2009) Further information on the application limits is given in the operating limit
diagrams on the following pages.
Option .E81 or .E82 - EC fans (extended operating range)
Instead of AC fans, the unit is equipped with EC fans. This results in the following
(only for Standard-/ advantages:
.D-/ .SL-/ .SD-units
EC fans are standard - Reduced power consumption in part-load mode
on .HE/.HD units) - Improved SEER/SCOP values
- continuous speed regulation of fans
- reduced sound level in part-load mode
- More precise control of condensing pressure
- Extended operating limit down to -20°C outdoor temperature at a chilled water
temperature of ≥0°C

Further information on the application limits is given in the operating limit


diagrams on the following pages.

For units without built-in pumps, one of the four following option numbers must be ordered to define the hardware
control of the on-site pump:
Option .E04 - Relay for actuating an on-site chilled water pump
An on/off pump provided on-site is controlled via a floating contact.
Option .E34 - Relay for actuating two parallel on-site chilled-water pumps
Two on-site on/off pumps are controlled via two floating contacts. To increase
system availability, the pumps are alternately activated by the controller; if one
pump fails, the system automatically switches to the other pump permanently.
The pumps must be fitted on-site with non-return valves.
Option .E30 - 0-10 V signal for controlling a customer supplied inverter chilled-water
pump
A speed-controlled inverter pump provided on-site is controlled by a 0-10 V signal.
In addition, there is a floating contact for enabling the pump.
Option .E31 - 0-10 V signal for controlling two parallel inverter chilled-water pumps
provided on-site
Two on-site speed-regulated inverter pumps are controlled by a common 0-10 V
signal. In addition, there are two floating contacts for activating the pumps. To
increase system availability, the pumps are alternately activated by the release
contact of the controller; if one pump fails, the system automatically switches to
the other pump permanently. The pumps must be fitted on-site with non-return
valves.

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 7/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Accessories for controls


Option .E19/E20 - Second remote control connection for remote monitoring and control
Up to 10 units in the same controller family can be connected to an additional
remote control
Option .E19 for remote controls up to 200 meters away
Option .E20 for remote controls up to 500 meters away
Serial card for - Serial interface board for connecting the unit to a building management
connection to a system (BMS)
building management -
system or for The following protocols are used to transmit digital and analog values:
master/slave control – Retrieval of alarm signals
– Retrieval of temperature and pressure values provided by the controller
– Operating status of individual compressors
– Enabling the unit
– Setpoint shift

Option .E14 - Modbus (RS485),


Built-in Modbus interface for connection to the building management system
Option .E15 - LonWorks® ,
Built-in LonWorks interface for connection to the building management system
Option .E16 - BACnet via IP,
Built-in BACnet via IP interface for connection to the building management system

Option .E17 - BACnet via MS/TP RS485,


Built-in BACnet via MS/TP RS485 interface for connection to the building
management system
Option .E28/ .E29 - ISYteq® Multi-Manager
Built-in controller for group control of up to 8 units of the FG series of the same
controller family in a hydraulic network, optimized load adaptation of the
connected units.
There are two types of Multi-Manager available:
.E28 ISYteq® Multi-Manager with digital/analogue inputs/outputs
.E29 ISYteq® Multi-Manager without digital/analogue inputs/outputs
Each unit in the group requires a built-in ISYteq® Multi-Manger. The two types
can be combined as desired.
If digital or analog inputs/outputs are required, such as inputs for 2nd setpoint,
demand limit, 4-20 mA setpoint shift or outputs for a central pump, at least one
unit in the group must be equipped with an ISYteq® Multi-Manager with
digital/analog inputs/outputs (.E28).
For maximum operational safety, it is recommended in this case to equip each
unit with an ISYteq® Multi-Manager with digital/analog inputs/outputs (.E28) and
to apply the corresponding control signals to each unit. This prevents that in case
of failure of the unit to which the digital/analog control signals are connected, the
remaining units can only continue to work with standard values.
Functionality:
- Dynamic Master: Fail-safety by transmission of the group control of the main
master unit to another unit in the group in case of an error, ISYteq Multi-
Manager with digital/analogue inputs/outputs have priority
- Load management: Even load distribution to all units or to as few units as
possible (adjustable)
- StandyBy-Management: An adjustable number of units always remains in stand-
by
- unit prioritization: The units can be activated according to a defined order
- unit start in sequence to avoid voltage peaks

Page 8/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

- Control of the water outlet temperature with auto-adaptive neutral zone


- Control of a central pump for the group or control of individual pumps per unit

Control via digital inputs and outputs (only with option .E28):
- Remote enabling ON/OFF
- Setpoint change via 4-20mA signal (Option .E21 required)
- 2. setpoint via digital input (Option .E22 required)
- Demand limit via digital input (Option .E23 required)
- Demand limit via 4-20mA signal
- Release and 0-10 V signal for central primary circuit pump
- Fault message input for central primary circuit pump
- Status message Multi-Manager
- Collective fault Multi-Manager
- Collective fault unit

BMS functionality
- Control of the unit group via optional BMS interface in the main control unit (to
be ordered separately)
- To read out status messages (compressor status, temperatures, pressures) of
each unit, each unit must be equipped with a BMS interface (to be ordered
separately).

Connection cable between the units (on-site): Bus RS485, CSA 2XAWG21 120
ohm shielded

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 9/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

For units with built-in inverter pumps or on-site inverter pump(s), one of the following three option numbers must
be ordered to define the software type of pump control:
Option .E84 - Setting constant pump speed
on the unit controller for pumps with variable speed. The speed is adjusted once
(only when using during commissioning so that the required water-volume flow passes through the
inverter pumps) evaporator.
Option .E85 - VPS-D control
In order to exploit further potential energy savings, the speed of the on-site or
(only when using built-in inverter pump(s) is reduced down to 50% in part-load mode. As far as
inverter pumps, possible, the Delta T at the evaporator is kept constant on the water side during
cannot be combined part-load mode. VPS-D is intended for systems without system separation, a
with parallel installed single-circuit buffer storage tank and a distributor with overflow to the collector.
units, meaning For the consumer circuits, additional on-site pumps with on-site control are
ISYteq® Multi- required, which are usually designed as pressure-controlled inverter pumps in
Manager) conjunction with 2-way valves at the consumers. Included in delivery are two
separately supplied temperature sensors as well as an extended controller
hardware with the required connection points. The temperature sensors must be
installed on-site at the water inlet to the distributor and in the overflow pipe in
immersion wells with heat-conducting paste. Measurement at the temperature
sensors has a higher-ranking influence on the pump speed and always ensures
an overflow from the distributor to the collector.
It should be noted that
- the hydraulic system is designed so that the primary circuit pump(s) can always
deliver at least 50% of the water volume. If this value is not reached, the unit will
malfunction.
- the overflow line is designed for 50% of the nominal water flow rate
- the flow monitor is calibrated to a value of 35% of the nominal water volume
flow. For this purpose, the maximum pipe cross-section in the area of the flow
monitor must be observed in order to ensure proper functioning.
Observe the separate planning instructions and hydraulic diagrams for VPS-D
systems.
Option .E86 - VPS-E control
In order to exploit further potential energy savings, the speed of the on-site or
(only when using built-in inverter pump(s) is reduced down to 50% in part-load mode. As far as
inverter pumps) possible, the Delta T at the evaporator is kept constant on the water side during
part-load mode. VPS-E is intended for systems with system separation (plate heat
exchangers) and a single-circuit buffer tank on the primary side. For the consumer
circuits on the secondary side of the system separation (plate heat exchanger),
one or more additional on-site pumps with on-site control are required, which are
usually designed as pressure-controlled inverter pumps in conjunction with 2-way
valves at the consumers. Alternatively, the system can be used for single circuit
systems with single-circuit buffer and a single consumer with 3-way valve. A
corresponding software for the function is included in the scope of delivery.
It should be noted that
- the hydraulic system is designed so that the primary circuit pump(s) can always
deliver at least 50% of the water volume. If this value is not reached, the unit will
malfunction.
- the flow monitor is calibrated to a value of 35% of the nominal water volume
flow. For this purpose, the maximum pipe cross-section in the area of the flow
monitor must be observed in order to ensure proper functioning.
Observe the separate planning instructions and hydraulic diagrams for VPS-E
systems.

Page 10/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Other accessories
Option .O01 - Packaging in timber crate and nylon foil
The unit is supplied for shipping in a timber crate and is additionally shrink-
wrapped in nylon foil to protect it from the weather and dirt.
Option .O11 - Packing of the unit with nylon cover
The unit is shrink-wrapped in nylon foil for shipping and storage to protect it from
weather and dirt.
Option .O27 - Refrigerant leak detection (Alarm)
The compressor section is monitored for leaking refrigerant. A detected refrigerant
leakage is signalled by the leakage sensor.
Option .O28 - Refrigerant leak detection (compressor switch off)
The compressor section is monitored for leaking refrigerant.
In the event of a refrigerant leak, the detector triggers an alarm, the unit is
switched off and an alarm is communicated via a separate potential-free contact.
A leakage detection system, which warns the operator of any leakage, extends
the cycle for carrying out leakage checks prescribed by Regulation (EU) No
517/2014 from 12 to 24 months for equipment containing 10.7-107.3 kg of R-
454B. For units with 107.3-1073 kg R-454B the cycle is extended from 6 to 12
months.
Option .O24 - Reinforced thermal insulation for the water-side heat exchanger
To prevent condensation for units that are operated at outside temperatures
below -10 °C.

Operating limits
On the water side, the operating limits according to Table 1 and on the air and water side the limits according to
Figure 2-5 must be observed. The limits given change when glycol is used, depending on the concentration. The
exact operating limits are output in the design program. If operation at ambient temperatures below -10 °C is required,
the unit must be installed sheltered from the wind (speeds < 2 m/s).

Tab. 1: Operating limits water (glycol) circuit

Min Max
Water inlet (cooling) [°C] -7 1) / -9 2) / -5 3) 26

Water outlet (cooling) [°C] -10 1) / -12 2) / -8 3) 20

dT (for water outlet >5 °C) (cooling) [K] 4 8

dT (for water outlet ≤5 °C) (cooling) [K] 3 5

Water-inlet desuperheater
[°C] 30 55
(.D/.SD/.HD units)

Water-outlet desuperheater
[°C] 35 60
(.D/.SD/.HD units)

Glycol concentration [%] 50


1)
Sizes 4004-4037 std/.SL/.HE
2)
Sizes 4040-8092 std/.SL/.HE
3)
.D/.SD/.HD units

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 11/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

60 60

50 50

40 40
Reduced Reduced
30 capacity 30 capacity
operation operation
20 20

10 Option .E50 or .E81 10

0 0

-10 -10
Protected from wind Protected from wind
tAir, suction

tAir, suction
-20 -20

-30 -30
-15 -10 -5 0 5 10 15 20 25 -15 -10 -5 0 5 10 15 20 25
tWater, outlet tWater, outlet

Fig. 2: Operating limits for sizes 2004-4037, types Standard/.SL. Fig. 3: Operating limits for sizes 2004-4037 in HE design.

The operating limits above 40 °C vary depending on the size; note the output in The operating limits above 40 °C vary depending on the size; note the output in
the selection software. The higher limit only applies to sizes 4018, 4021, 4029 the selection software. The higher limit only applies to sizes 4018, 4021, 4029
and 4033. Unit types .D/.SD accordingly, but only down to -8 °C water outlet and 4033. Unit types .HD accordingly, but only down to -8 °C water outlet
temperature. temperature.

60 60

50 50

40 40
Reduced
30 capacity 30 Reduced
operation capacity
20 20 operation

10 Option .E81 or .E82 10

0 0

-10 -10
Protected from wind Protected from wind
tAir, suction

tAir, suction

-20 -20

-30 -30
-15 -10 -5 0 5 10 15 20 25 -15 -10 -5 0 5 10 15 20 25
tWater, outlet tWater, outlet
Fig. 4: Operating limits for sizes 4040-8092, types Standard/.SL. Fig. 5: Operating limits for sizes 4040-8092 in HE design.

Unit types .D/.SD accordingly, but only down to -8 °C water outlet temperature. Unit types .HD accordingly, but only down to -8 °C water outlet temperature.

Notices
For operational reasons, water at evaporator outlet temperatures below 5 °C must be protected from freezing by adding glycol.
FläktGroup recommends the use of at least 30% ethylene glycol.

The unit must be protected from freezing at ambient temperatures lower than 5 °C. Frost protection heating for the water-side heat exchanger is provided as standard
for this purpose. The frost protection heaters are designed for outdoor temperatures down to -10 °C. In installation locations where colder outdoor temperatures may
occur, the unit must be configured with glycol.

Page 12/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

General Data
Tab. 2: General data for units with 2 compressors

Unit type FGAC #### DG1/2 (.SL/.HE) 2004 2005 2006 2007 2008 2009 2010

Capacity data Standard unit


Cooling capacity 1,2,3,5) Qe [kW] 40.4 48.5 54 60.8 68 79.6 93.1
Power consumption 2,5) P [kW] 13.8 16.3 17.3 18 20.9 25.8 28.3
EER 3,5) 2.92 2.97 3.12 3.38 3.26 3.09 3.29
SEER 3,4) 4.61 4.72 4.56 4.65 4.57 4.6 4.53
ηS 3,4) 181 186 179 183 180 181 178
SEER 3,4) (Option .E81) 4.91 4.98 4.77 4.96 4.84 4.82 4.84
ηS 3,4) (Option .E81) 193 196 188 195 190 190 191
Chilled water flow rate Ve [m³/h] 7.0 8.4 9.3 10.5 11.7 13.7 16.1
Pressure drop 2,3) ∆pe [kPa] 44.8 33.3 41.4 45.4 46.2 45.3 36.6
Air volume flow [m³/h] 13500 13500 13500 20376 20376 20376 30564
Capacity data SL unit
Cooling capacity 1,2,3,5) Qe [kW] 39.9 47.7 53.5 60.4 67.4 78.6 92.2
Power consumption 2,5) P [kW] 13.8 16.3 17.3 17.7 20.6 25.8 28.7
EER 3,5) 2.9 2.93 3.09 3.41 3.27 3.05 3.21
SEER 3,4) 4.6 4.71 4.54 4.66 4.57 4.59 4.54
ηS 3,4) 181 185 179 184 180 180 179
SEER 3,4) (Option .E81) 4.86 4.93 4.73 4.93 4.8 4.78 4.9
ηS 3,4) (Option .E81) 191 194 186 194 189 188 193
Chilled water flow rate Ve [m³/h] 6.9 8.2 9.2 10.4 11.6 13.6 15.9
Pressure drop 2,3) ∆pe [kPa] 43.8 32.3 40.6 44.8 45.4 44.2 36
Air volume flow [m³/h] 12636 12636 12636 19224 19224 19224 28404
Capacity data HE unit
Cooling capacity 1,2,3,5) Qe [kW] 41.1 49.2 54.6 61.4 68.8 80.6 94.1
Power consumption 2,5) P [kW] 12.8 14.9 15.8 16.7 19.3 23.6 27.8
EER 3,5) 3.21 3.3 3.46 3.68 3.57 3.42 3.38
SEER 3,4) 4.97 5.07 4.85 5 4.89 4.89 4.85
ηS 3,4) 196 200 191 197 193 193 191
Chilled water flow rate Ve [m³/h] 7.1 8.5 9.4 10.6 11.9 13.9 16.2
Pressure drop 2,3) ∆pe [kPa] 46.3 34.4 42.4 46.4 47.3 46.5 37.5
Air volume flow [m³/h] 17424 17424 17424 26208 26208 26208 39528
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 4 4 4 6 6 6 2
Compressors Scroll compressors
Number of compressors 2 2 2 2 2 2 2
Number of refrigeration circuits 1 1 1 1 1 1 1
Minimum part-load ratio [%] 50 50 50 50 50 50 50
Evaporator (chilled-water side) Plate heat exchanger
Min. water mass flow Ve,min [m³/h] 4.2 5.0 5.7 6.4 7.2 8.4 9.8
Max. water mass flow Ve,max [m³/h] 12.6 14.8 16.8 19.0 21.0 22.0 28.5
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 109 130 145 165 182 216 251
Water charge of heat exchanger [l] 2.4 3.5 3.5 3.8 4.3 5.2 6.8
Evaporator connection Ext. thread 2) 1 ½“ 1 ½“ 1 ½“ 2“ 2“ 2“ 2 ½“
Desuperheater (partial heat recovery) (only unit types .D/.SD/.HD)
Number of plate exchangers 1 1 1 1 1 1 1
Max. water mass flow Vd,max [m³/h] 2.8 3.4 3.7 3.8 4.4 5.4 5.7
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 7.60 7.60 8.00 9.90 10.0 11.1 13.1
Oil charge [kg] 6.00 6.60 5.40 5.40 5.40 5.40 8.00
Connectable cable cross-sections 7)
Rectangular Max [mm] 16x3 16x3 16x3 16x3 16x3 16x3 16x3
Round Max [mm²] 50 50 50 50 50 50 50
Dimensions and weight
A (length) [mm] 1825 1825 1825 2395 2395 2395 2825
B (width) [mm] 1195 1195 1195 1195 1195 1195 1195
H (height) [mm] 1865 1865 1865 1865 1865 1865 1980
Weight 2) [kg] 500 510 550 630 630 640 770
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regionally applicable safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 13/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Tab. 2: General data for units with 2 compressors (continued)

Unit type FGAC #### DG2 (.SL/.HE) 2011 2012 2014 2016 2018 2020 2022

Capacity data Standard unit


Cooling capacity 1,2,3,5) Qe [kW] 103.5 116.2 129.3 151.7 173.9 186.6 208.3
Power consumption 2,5) P [kW] 33.3 38.9 45.1 48.2 56.1 62.2 71.8
EER 3,5) 3.11 2.99 2.87 3.15 3.1 3 2.9
SEER 3,4) 4.29 4.32 4.38 4.48 4.49 4.48 4.46
ηS 3,4) 168 170 172 176 177 176 175
SEER 3,4) (Option .E81) 4.51 4.54 4.56 4.75 4.71 4.67 4.63
ηS 3,4) (Option .E81) 178 179 179 187 185 184 182
Chilled water flow rate Ve [m³/h] 17.9 20.1 22.3 26.2 30.0 32.2 35.9
Pressure drop 2,3) ∆pe [kPa] 45.4 45.5 42.6 47.9 44.1 38.5 48
Air volume flow [m³/h] 30564 30564 30564 46188 46188 46188 46188
Capacity data SL unit
Cooling capacity 1,2,3,5) Qe [kW] 102.5 114.9 127.4 150.1 171.6 183.9 206.1
Power consumption 2,5) P [kW] 33.8 39.8 46.2 49.2 57.6 64.1 74.1
EER 3,5) 3.03 2.89 2.76 3.05 2.98 2.87 2.78
SEER 3,4) 4.27 4.29 4.34 4.48 4.47 4.45 4.4
ηS 3,4) 168 169 171 176 176 175 173
SEER 3,4) (Option .E81) 4.53 4.53 4.55 4.78 4.71 4.67 4.6
ηS 3,4) (Option .E81) 178 178 179 188 185 184 181
Chilled water flow rate Ve [m³/h] 17.7 19.8 22.0 25.9 29.6 31.7 35.5
Pressure drop 2,3) ∆pe [kPa] 44.5 44.4 41.4 46.9 42.9 37.4 47
Air volume flow [m³/h] 28404 28404 28404 42588 42588 42588 42588
Capacity data HE unit
Cooling capacity 1,2,3,5) Qe [kW] 104.4 117.8 131.4 153.6 176.1 189.5 211.4
Power consumption 2,5) P [kW] 32.3 37.2 42.4 46.7 53.7 59 67.3
EER 3,5) 3.23 3.17 3.1 3.29 3.28 3.21 3.14
SEER 3,4) 4.54 4.59 4.62 4.77 4.75 4.73 4.69
ηS 3,4) 179 181 182 188 187 186 185
Chilled water flow rate Ve [m³/h] 18.0 20.3 22.7 26.5 30.4 32.7 36.5
Pressure drop 2,3) ∆pe [kPa] 46.2 46.7 44 49.2 45.2 39.7 49.4
Air volume flow [m³/h] 39528 39528 39528 59544 59544 59544 59544
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 2 2 2 3 3 3 3
Compressors Scroll compressors
Number of compressors 2 2 2 2 2 2 2
Number of refrigeration circuits 1 1 1 1 1 1 1
Minimum part-load ratio [%] 50 50 50 50 50 50 50
Evaporator (chilled-water side) Plate heat exchanger
Min. water mass flow Ve,min [m³/h] 11.0 12.3 13.6 16.1 18.4 19.7 22.1
Max. water mass flow Ve,max [m³/h] 32.0 36.1 40.4 47.0 51.0 51.0 51.0
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 278 314 351 409 468 502 565
Water charge of heat exchanger [l] 6.8 7.6 8.8 9.8 12 14.2 14.2
Evaporator connection Ext. thread 2) 2 ½“ 2 ½“ 2 ½“ 2 ½“ 2 ½“ 2 ½“ 2 ½“
Desuperheater (partial heat recovery) (only unit types .D/.SD/.HD)
Number of plate exchangers 1 1 1 1 1 1 1
Max. water mass flow Vd,max [m³/h] 6.7 8.0 9.6 9.9 11.7 13.0 15.5
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 14.3 15.5 15.8 21.9 22.7 22.8 22.9
Oil charge [kg] 10.6 10.6 10.6 10.6 10.6 10.6 10.6
Connectable cable cross-sections 7)
Rectangular Max [mm] 20x4 20x4 20x4 20x4 20x5 20x5 20x5
Round Max [mm²] 120 120 120 120 120 120 120
Dimensions and weight
A (length) [mm] 2825 2825 2825 3980 3980 3980 3980
B (width) [mm] 1195 1195 1195 1195 1195 1195 1195
H (height) [mm] 1980 1980 1980 1980 1980 1980 1980
Weight 2) [kg] 770 850 920 1130 1170 1180 1220
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

Page 14/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Tab. 3: General data for units with 4 compressors

Unit type FGAC #### DG2 (.SL/.HE) 4018 4021 4024 4026 4029 4033 4037

Capacity data Standard unit


Cooling capacity 1,2,3,5) Qe [kW] 168.1 197.2 225.8 250.4 279.7 312.8 345.4
Power consumption 2,5) P [kW] 50.2 59 69.7 78.2 82.8 94.8 107.9
EER 3,5) 3.35 3.34 3.24 3.2 3.38 3.3 3.2
SEER 3,4) 4.73 4.76 4.78 4.79 4.71 4.73 4.62
ηS 3,4) 186 188 188 189 185 186 182
SEER 3,4) (Option .E81) 5.01 5.03 4.99 5 4.98 4.99 4.83
ηS 3,4) (Option .E81) 197 198 196 197 196 197 190
Chilled water flow rate Ve [m³/h] 29.0 34.0 38.9 43.2 48.2 53.9 59.5
Pressure drop 2,3) ∆pe [kPa] 42.7 44.3 46.7 46.6 42.8 39.8 48.5
Air volume flow [m³/h] 68004 68004 68004 68004 102024 102024 102024
Capacity data SL unit
Cooling capacity 1,2,3,5) Qe [kW] 167.1 195.7 223.7 247.5 277.9 310.2 342.6
Power consumption 2,5) P [kW] 50.6 60.6 71.9 81.4 83.5 97.2 111.2
EER 3,5) 3.3 3.23 3.11 3.04 3.33 3.19 3.08
SEER 3,4) 4.77 4.78 4.77 4.75 4.8 4.79 4.64
ηS 3,4) 188 188 188 187 189 188 183
SEER 3,4) (Option .E81) 5.01 5 4.94 4.92 5.04 5.01 4.82
ηS 3,4) (Option .E81) 197 197 195 194 199 197 190
Chilled water flow rate Ve [m³/h] 28.8 33.8 38.6 42.7 47.9 53.5 59.1
Pressure drop 2,3) ∆pe [kPa] 42.2 43.6 45.8 45.5 42.2 39.2 47.8
Air volume flow [m³/h] 57312 57312 57312 57312 85968 85968 85968
Capacity data HE unit
Cooling capacity 1,2,3,5) Qe [kW] 168.1 197.2 225.8 250.4 279.7 312.8 345.4
Power consumption 2,5) P [kW] 49 57.8 68.4 77 80.8 92.8 106.3
EER 3,5) 3.43 3.41 3.3 3.25 3.46 3.37 3.25
SEER 3,4) 5.01 5.03 4.99 5 4.98 4.99 4.83
ηS 3,4) 197 198 196 197 196 197 190
Chilled water flow rate Ve [m³/h] 29.0 34.0 38.9 43.2 48.2 53.9 59.5
Pressure drop 2,3) ∆pe [kPa] 42.7 44.3 46.7 46.6 42.8 39.8 48.5
Air volume flow [m³/h] 68004 68004 68004 68004 102024 102024 102024
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 4 4 4 4 6 6 6
Compressors Scroll compressors
Number of compressors 4 4 4 4 4 4 4
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load ratio [%] 25 25 25 25 25 25 25
Evaporator (chilled-water side) Plate heat exchanger
Min. water mass flow Ve,min [m³/h] 18.9 22.1 25.3 28.0 31.3 35.3 39.2
Max. water mass flow Ve,max [m³/h] 51.2 59.8 62.0 62.0 84.3 94.8 102.0
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 440 520 590 660 730 820 920
Water charge of heat exchanger [l] 9 10 12 15 20 24 24
Evaporator connection VICTAULIC 2) 3“ 3“ 3“ 3“ 3“ 4“ 4“
Desuperheater (partial heat recovery) (only unit types .D/.SD/.HD)
Number of plate exchangers 1 1 1 1 1 1 1
Max. water mass flow Vd,max [m³/h] 9.7 11.3 13.6 15.5 16.7 18.5 20.4
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 30.1 31.9 37.5 37.6 47.5 51.8 51.9
Oil charge [kg] 14.4 19.4 24.4 24.4 24.4 24.4 24.4
Connectable cable cross-sections 7)
Min 70 70 95 95 150 185 185
Round [mm²]
Max 95 95 150 150 240 240 240
Dimensions and weight
A (length) [mm] 3160 3160 3160 3160 4335 4335 4335
B (width) [mm] 2250 2250 2250 2250 2250 2250 2250
H (height) [mm] 2290 2290 2290 2290 2290 2290 2290
Weight 2) [kg] 1620 1640 1850 1880 2230 2260 2470
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 15/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Tab. 4: General data for units with 4-6 compressors, standard units

Unit type FGAC #### EG2 4040 4042 4046 5051 6057 5058 6063

Capacity data Standard unit


Cooling capacity 1,2,3,5) Qe [kW] 378.6 398.5 436.5 487.5 538.3 546.2 597.3
Power consumption 2,5) P [kW] 117.6 124.1 139 154.3 169.8 170.7 186.1
EER 3,5) 3.22 3.21 3.14 3.16 3.17 3.2 3.21
SEER 3,4) 4.67 4.68 4.65 4.7 4.7 4.76 4.75
ηS 3,4) 184 184 183 185 185 187 187
SEER 3,4) (Option .E81) 4.88 4.89 4.8 4.91 4.92 4.93 4.97
ηS 3,4) (Option .E81) 192 192 189 193 194 194 196
Chilled water flow rate Ve [m³/h] 65.3 68.7 75.2 84.0 92.8 94.1 102.9
Pressure drop 2,3) ∆pe [kPa] 61.8 48.6 58.3 55.1 67.1 42.5 50.9
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 6 6 6 7 8 8 9
Total air volume flow [m³/h] 128376 122724 122724 143172 163620 163620 184068
Compressors Scroll compressors
Number of compressors 4 4 4 5 6 5 6
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load ratio [%] 25 25 25 20 17 20 17
Evaporator (chilled-water side) Shell & Tube heat exchanger
Min. water mass flow Ve,min [m³/h] 38.1 40.7 44.4 49.2 53.9 56.5 61.2
Max. water mass flow Ve,max [m³/h] 99.3 96.2 107.7 118.2 127.1 137.8 145.3
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 950 1000 1090 1460 1610 1640 1790
Water charge of heat exchanger [l] 79 67 67 83 83 128 128
Evaporator connection VICTAULIC 2) 4“ 4“ 4“ 5“ 5“ 5“ 5“
Desuperheaters (partial heat recovery) (only unit types .D)
Number of plate exchangers, to be
2 2 2 2 2 2 2
piped parallel on site
Max. water mass flow Vd,max [m³/h] 21.6 22.7 26.1 28.1 29.9 32.2 34.1
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 46.6 51.5 51.7 59.6 64.4 72.0 74.8
Oil charge [kg] 21.2 21.2 21.2 26.5 31.8 26.5 31.8
Connectable cable cross-sections 7)
Min 2x30x5 2x30x5 2x30x5 2x30x5
Rectangular [mm]
Max 2x40x5 2x40x5 2x40x5 2x50x5 2x50x5 2x50x5 2x50x5
Max 185 185 185 2x150 2x150 2x150 2x150
Round [mm²]
Max 240 240 240 2x300 2x300 2x300 2x300
Dimensions and weight
A (length) [mm] 3905 3905 3905 5080 5080 5080 6255
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2560 2560 2560 2560 2560 2560 2560
Weight 2) [kg] 2590 2620 2660 3190 3420 3500 3940
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

Page 16/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Tab. 4: General data for units with 4-6 compressors, standard units (continued)

Unit type FGAC #### EG2 6067 6070 8076 8080 8084 8089 8092

Capacity data Standard unit


Cooling capacity 1,2,3,5) Qe [kW] 635.7 655.8 719.8 758.8 797.4 834.8 866.3
Power consumption 2,5) P [kW] 200.5 203 220.8 234.9 247.6 262.5 276.8
EER 3,5) 3.17 3.23 3.26 3.23 3.22 3.18 3.13
SEER 3,4) 4.73 4.77 4.75 4.74 4.75 4.75 4.74
ηS 3,4) 186 188 187 187 187 187 187
SEER 3,4) (Option .E81) 4.88 5.02 4.96 4.93 4.94 4.92 4.89
ηS 3,4) (Option .E81) 192 198 195 194 195 194 193
Chilled water flow rate Ve [m³/h] 109.5 113.0 124.0 130.8 137.4 143.9 149.3
Pressure drop 2,3) ∆pe [kPa] 49.2 52.4 56.9 63.3 47.2 51.7 55.7
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 9 10 12 12 12 12 12
Total air volume flow [m³/h] 184068 204516 251640 256788 245448 245448 245448
Compressors Scroll compressors
Number of compressors 6 6 8 8 8 8 8
Number of refrigeration circuits 3 2 4 4 4 4 4
Minimum part-load ratio [%] 17 17 13 13 13 13 13
Evaporator (chilled-water side) Shell & Tube heat exchanger
Min. water mass flow Ve,min [m³/h] 64.9 68.3 71.5 76.1 81.6 85.4 88.9
Max. water mass flow Ve,max [m³/h] 155.4 161.5 186.2 186.2 204.0 204.0 217.3
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 1910 1970 2160 2280 2400 2500 2600
Water charge of heat exchanger [l] 116 116 169 169 157 157 157
Evaporator connection VICTAULIC 2) 5“ 5“ 6“ 6“ 6“ 6“ 6“
Desuperheaters (partial heat recovery) (only unit types .D)
Number of plate exchangers, to be
3 2 4 4 4 4 4
piped parallel on site
Max. water mass flow Vd,max [m³/h] 37.6 38.1 40.3 43.2 45.4 49.0 52.1
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 75.1 85.6 88.5 95.1 104 106 106
Oil charge [kg] 31.8 31.8 42.4 42.4 42.4 42.4 42.4
Connectable cable cross-sections 7)
Min 2x30x5 2x30x5 2x40x5 2x40x5 2x40x5 2x40x5 2x40x5
Rectangular [mm]
Max 2x50x5 2x50x5 2x63x5 2x63x5 2x63x5 2x63x5 2x63x5
Min 2x150 2x150 2x185 2x185 2x185 2x185 2x185
Round [mm²]
Max 2x300 2x300 2x300 2x300 2x300 2x300 2x300
Dimensions and weight
A (length) [mm] 6255 6255 7430 7430 7430 7430 7430
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2560 2560 2560 2560 2560 2560 2560
Weight 2) [kg] 3980 4100 4970 5010 5080 5120 5150
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 17/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Table 5: General data for units with 4-6 compressors, .SL and .HE units

Unit type FGAC #### EG2.SL/HE 4040 4042 4046 5051 6057 5058 6063

Capacity data SL unit


Cooling capacity 1,2,3,5) Qe [kW] 379.2 398.7 437 487.3 538.1 545.9 596.7
Power consumption 2,5) P [kW] 113.9 120.1 134.5 150.4 167.1 167.5 184.2
EER 3,5) 3.33 3.32 3.25 3.24 3.22 3.26 3.24
SEER 3,4) 4.73 4.76 4.72 4.76 4.7 4.81 4.8
ηS 3,4) 186 187 186 188 185 190 189
SEER 3,4) (Option .E82) 5.03 5.05 4.92 5.07 5.03 5.13 5.11
ηS 3,4) (Option .E82) 198 199 194 200 198 202 201
Chilled water flow rate Ve [m³/h] 65.4 68.7 75.3 84.0 92.7 94.1 102.8
Pressure drop 2,3) ∆pe [kPa] 62 48.6 58.4 55 67.1 42.5 50.8
Capacity data HE unit
Cooling capacity 1,2,3,5) Qe [kW] 379.6 399.5 439.2 489.7 540.2 548.1 599.1
Power consumption 2,5) P [kW] 111.6 117.2 129.9 145.3 161.7 161.7 177.8
EER 3,5) 3.4 3.41 3.38 3.37 3.34 3.39 3.37
SEER 3,4) 5.03 5.06 4.91 5.07 5.05 5.13 5.13
ηS 3,4) 198 199 194 200 199 202 202
Chilled water flow rate Ve [m³/h] 65.4 68.9 75.7 84.4 93.1 94.5 103.2
Pressure drop 2,3) ∆pe [kPa] 62.1 48.8 59 55.6 67.6 42.8 51.2
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 8 8 8 9 10 10 11
Total air volume flow [m³/h] 171180 163620 163620 184068 204516 204516 225000
Compressors Scroll compressors
Number of compressors 4 4 4 5 6 5 6
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load ratio [%] 25 25 25 20 17 20 17
Evaporator (chilled-water side) Shell & Tube heat exchanger
Min. water mass flow Ve,min [m³/h] 38.1 40.7 44.4 49.2 53.9 56.5 61.2
Max. water mass flow Ve,max [m³/h] 99.3 96.2 107.7 118.2 127.1 137.8 145.3
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 950 1000 1090 1460 1610 1640 1790
Water charge of heat exchanger [l] 79 67 67 83 83 128 128
Evaporator connection VICTAULIC 2) 4“ 4“ 4“ 5“ 5“ 5“ 5“
Desuperheater (partial heat recovery) (only unit types .SD/.HD)
Number of plate exchangers, to be
2 2 2 2 2 2 2
piped parallel on site
Max. water mass flow Vd,max [m³/h] 21.6 22.7 26.1 28.1 29.9 32.2 34.1
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 56.1 59.9 62.7 76.5 77.9 80.8 88.8
Oil charge [kg] 21.2 21.2 21.2 26.5 31.8 26.5 31.8
Connectable cable cross-sections 7)
2x30x5 2x30x5 2x30x5 2x30x5
Rectangular Max [mm]
2x40x5 2x40x5 2x40x5 2x50x5 2x50x5 2x50x5 2x50x5
185 185 185 2x150 2x150 2x150 2x150
Round Max [mm²]
240 240 240 2x300 2x300 2x300 2x300
Dimensions and weight
A (length) [mm] 5080 5080 5080 6255 6255 6255 7430
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2560 2560 2560 2560 2560 2560 2560
Weight 2) [kg] 2930 2960 3000 3600 3830 3900 4290
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

Page 18/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Table 5: General data for units with 4-6 compressors, .SL and .HE units (continued)

Unit type FGAC #### EG2.SL/HE 6067 6070 8076 8080 8084 8089 8092

Capacity data SL unit


Cooling capacity 1,2,3,5) Qe [kW] 635.9 654.7 719.8 760 798.1 836.5 868.1
Power consumption 2,5) P [kW] 193.9 201.4 213.6 227.5 240.4 254.3 267.9
EER 3,5) 3.28 3.25 3.37 3.34 3.32 3.29 3.24
SEER 3,4) 4.85 4.81 4.81 4.81 4.82 4.83 4.85
ηS 3,4) 191 189 189 189 190 190 191
SEER 3,4) (Option .E82) 5.1 5.12 5.16 5.13 5.14 5.14 5.12
ηS 3,4) (Option .E82) 201 202 203 202 203 203 202
Chilled water flow rate Ve [m³/h] 109.6 112.8 124.0 131.0 137.5 144.1 149.6
Pressure drop 2,3) ∆pe [kPa] 49.2 52.2 56.9 63.5 47.3 51.9 55.9
Capacity data HE unit
Cooling capacity 1,2,3,5) Qe [kW] 638.4 658 720.5 761.5 800.4 839 871.6
Power consumption 2,5) P [kW] 187.8 194.1 210.7 222.7 234 246 258.6
EER 3,5) 3.4 3.39 3.42 3.42 3.42 3.41 3.37
SEER 3,4) 5.11 5.14 5.15 5.13 5.14 5.14 5.12
ηS 3,4) 201 203 203 202 203 203 202
Chilled water flow rate Ve [m³/h] 110.0 113.4 124.2 131.2 137.9 144.6 150.2
Pressure drop 2,3) ∆pe [kPa] 49.6 52.7 57 63.7 47.6 52.2 56.4
Controls FläktGroup controller with TA software and compact display
Fans Axial fans
Number of fans n 12 12 16 16 16 16 16
Total air volume flow [m³/h] 245448 245448 335484 342360 327240 327240 327240
Compressors Scroll compressors
Number of compressors 6 6 8 8 8 8 8
Number of refrigeration circuits 3 2 4 4 4 4 4
Minimum part-load ratio [%] 17 17 13 13 13 13 13
Evaporator (chilled-water side) Shell & Tube heat exchanger
Min. water mass flow Ve,min [m³/h] 64.9 68.3 71.5 76.1 81.6 85.4 88.9
Max. water mass flow Ve,max [m³/h] 155.4 161.5 186.2 186.2 204.0 204.0 217.3
Max. operating pressure pmax [bar] 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9) 10 8) / 6 9)
Min. chilled water system content [l] 1910 1970 2160 2280 2400 2500 2600
Water charge of heat exchanger [l] 116 116 169 169 157 157 157
Evaporator connection VICTAULIC 2) 5“ 5“ 6“ 6“ 6“ 6“ 6“
Desuperheater (partial heat recovery) (only unit types .SD/.HD)
Number of plate exchangers, to be
3 2 4 4 4 4 4
piped parallel on site
Max. water mass flow Vd,max [m³/h] 37.6 38.1 40.3 43.2 45.4 49.0 52.1
Max. operating pressure pmax [bar] 10 10 10 10 10 10 10
Refrigeration circuit charge
Refrigerant R-454B 6) (GWP 466) [kg] 94.1 98.8 107 129 129 129 129
Oil charge [kg] 31.8 31.8 42.4 42.4 42.4 42.4 42.4
Connectable cable cross-sections 7)
2x30x5 2x30x5 2x40x5 2x40x5 2x40x5 2x40x5 2x40x5
Rectangular Max [mm]
2x50x5 2x50x5 2x63x5 2x63x5 2x63x5 2x63x5 2x63x5
2x150 2x150 2x185 2x185 2x185 2x185 2x185
Round Max [mm²]
2x300 2x300 2x300 2x300 2x300 2x300 2x300
Dimensions and weight
A (length) [mm] 7430 7430 9780 9780 9780 9780 9780
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2560 2560 2560 2560 2560 2560 2560
Weight 2) [kg] 4430 4450 5660 5720 5770 5810 5850
1) Chilled water temperature (inlet/outlet) 12/7 °C; outside air temperature 35 °C; without glycol Values partly rounded off
2) Applies to units in standard configuration without pumps, without buffer storage
3) Value certified in Eurovent
4) Data according to ErP Directive (EU) 2016/2281 for comfort coolers and DIN EN 14825:2019-07, average climate, fan coil (12/7), variable flow, variable temperature
5) Performance data according to EN14511-3:2019-07
6) Take the exact amount of refrigerant from the unit's type plate
7) Observe the regional safety regulations and structural conditions for dimensioning the supply line
8) without buffer tank
9) with buffer tank

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 19/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Noise levels
Tab. 6: Noise level

Total sound level Octave band [Hz]

Sound power level [dB]

Sound
Sound power
Unit type FGAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)

Standard units
2004DG1(.D) 81 49 82 82 79 78 77 73 67 52
2005DG1(.D) 82 50 83 83 80 79 78 74 68 53
2006DG1(.D) 81 49 82 82 79 78 77 73 67 52
2007DG1(.D) 83 51 84 84 81 80 79 75 69 54
2008DG1(.D) 84 52 85 85 82 81 80 76 70 55
2009DG1(.D) 84 52 85 85 82 81 80 76 70 55
2010DG2(.D) 84 52 86 84 85 84 78 73 67 61
2011DG2(.D) 84 52 86 84 85 84 78 73 67 61
2012DG2(.D) 84 52 86 84 85 84 78 73 67 61
2014DG2(.D) 85 53 87 85 86 85 79 74 68 62
2016DG2(.D) 86 54 87 88 86 85 81 76 69 64
2018DG2(.D) 87 55 88 89 87 86 82 77 70 65
2020DG2(.D) 87 55 88 89 87 86 82 77 70 65
2022DG2(.D) 88 56 89 90 88 87 83 78 71 66
4018DG2(.D) 86 54 80 80 81 82 83 78 72 68
4021DG2(.D) 86 54 80 80 81 82 83 78 72 68
4024DG2(.D) 87 55 81 81 82 83 84 79 73 69
4026DG2(.D) 87 55 81 81 82 83 84 79 73 69
4029DG2(.D) 88 56 82 82 83 84 85 80 74 70
4033DG2(.D) 90 58 84 84 85 86 87 82 76 72
4037DG2(.D) 91 59 85 85 86 87 88 83 77 73
4040EG2(.D) 94 62 97 96 93 91 90 85 79 74
4042EG2(.D) 94 62 97 96 93 91 90 85 79 74
4046EG2(.D) 94 62 97 96 93 91 90 85 79 74
5051EG2(.D) 94 62 97 96 93 91 90 85 79 74
6057EG2(.D) 95 63 98 97 94 92 91 86 80 74
5058EG2(.D) 95 63 98 97 94 92 91 86 80 74
6063EG2(.D) 95 62 98 97 94 92 91 86 80 74
6067EG2(.D) 95 62 98 97 94 92 91 86 80 74
6070EG2(.D) 96 63 98 97 95 93 92 87 81 75
8076EG2(.D) 96 63 98 97 95 93 92 87 81 75
8080EG2(.D) 96 63 98 97 95 93 92 87 81 75
8084EG2(.D) 97 64 99 98 96 94 93 88 82 76
8089EG2(.D) 97 64 99 98 96 94 93 88 82 76
8092EG2(.D) 97 64 99 98 96 94 93 88 82 76
SL units (super low noise version)
2004DG1.SL/SD 77 45 78 78 75 74 73 69 63 48
2005DG1.SL/SD 78 46 79 79 76 75 74 70 64 49
2006DG1.SL/SD 77 45 78 78 75 74 73 69 63 48
2007DG1.SL/SD 79 47 80 80 77 76 75 71 65 50
2008DG1.SL/SD 80 48 81 81 78 77 76 72 66 51
2009DG1.SL/SD 80 48 81 81 78 77 76 72 66 51
2010DG2.SL/SD 80 48 82 80 81 80 74 69 63 57
2011DG2.SL/SD 80 48 82 80 81 80 74 69 63 57
2012DG2.SL/SD 80 48 82 80 81 80 74 69 63 57
2014DG2.SL/SD 82 50 84 82 83 82 76 71 65 59
2016DG2.SL/SD 82 50 85 87 83 81 76 72 66 62
2018DG2.SL/SD 83 51 86 88 84 82 77 73 67 63
2020DG2.SL/SD 83 51 86 88 84 82 77 73 67 63
2022DG2.SL/SD 84 52 87 89 85 83 78 74 68 64
4018DG2.SL/SD 81 49 80 80 77 77 78 72 67 63
4021DG2.SL/SD 82 50 81 81 78 78 79 73 68 64
4024DG2.SL/SD 83 51 82 82 79 79 80 74 69 65
4026DG2.SL/SD 83 51 82 82 79 79 80 74 69 65
4029DG2.SL/SD 84 52 83 83 80 80 81 75 70 66
4033DG2.SL/SD 86 54 85 85 82 82 83 77 72 68
4037DG2.SL/SD 87 55 86 86 83 83 84 78 73 69
4040EG2.SL/SD 86 54 88 87 86 84 81 76 69 63
4042EG2.SL/SD 86 54 88 87 86 84 81 76 69 63
4046EG2.SL/SD 87 55 89 88 87 85 82 77 70 64

Page 20/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Total sound level Octave band [Hz]

Sound power level [dB]

Sound
Sound power
Unit type FGAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)

5051EG2.SL/SD 87 54 89 88 87 85 82 77 70 64
6057EG2.SL/SD 87 54 89 88 87 85 82 77 70 64
5058EG2.SL/SD 88 55 90 89 88 86 83 78 71 65
6063EG2.SL/SD 88 55 90 89 88 86 83 78 71 65
6067EG2.SL/SD 88 55 90 89 88 86 83 78 71 65
6070EG2.SL/SD 89 56 91 90 89 87 84 79 72 66
8076EG2.SL/SD 90 57 92 91 90 88 85 80 73 67
8080EG2.SL/SD 90 57 92 91 90 88 85 80 73 67
8084EG2.SL/SD 90 57 92 91 90 88 85 80 73 67
8089EG2.SL/SD 90 57 92 91 90 88 85 80 73 67
8092EG2.SL/SD 90 57 92 91 90 88 85 80 73 67
HE units (highly efficient version)
2004DG1.HE/HD 85 53 86 86 82 81 81 78 70 58
2005DG1.HE/HD 85 53 86 86 82 81 81 78 70 58
2006DG1.HE/HD 85 53 86 86 82 81 81 78 70 58
2007DG1.HE/HD 86 54 91 85 84 83 82 79 72 63
2008DG1.HE/HD 87 55 92 86 85 84 83 80 73 64
2009DG1.HE/HD 87 55 92 86 85 84 83 80 73 64
2010DG2.HE/HD 89 57 90 90 86 85 85 82 74 62
2011DG2.HE/HD 89 57 90 90 86 85 85 82 74 62
2012DG2.HE/HD 89 57 90 90 86 85 85 82 74 62
2014DG2.HE/HD 90 58 91 91 87 86 86 83 75 63
2016DG2.HE/HD 91 59 91 93 89 88 87 83 76 68
2018DG2.HE/HD 91 59 91 93 89 88 87 83 76 68
2020DG2.HE/HD 91 59 91 93 89 88 87 83 76 68
2022DG2.HE/HD 92 60 92 94 90 89 88 84 77 69
4018DG2.HE/HD 86 54 80 80 81 82 83 78 72 68
4021DG2.HE/HD 86 54 80 80 81 82 83 78 72 68
4024DG2.HE/HD 87 55 81 81 82 83 84 79 73 69
4026DG2.HE/HD 87 55 81 81 82 83 84 79 73 69
4029DG2.HE/HD 88 56 82 82 83 84 85 80 74 70
4033DG2.HE/HD 90 58 84 84 85 86 87 82 76 72
4037DG2.HE/HD 91 59 85 85 86 87 88 83 77 73
4040EG2.HE/HD 95 63 98 97 94 92 91 86 80 74
4042EG2.HE/HD 95 63 98 97 94 92 91 86 80 74
4046EG2.HE/HD 95 63 98 97 94 92 91 86 80 74
5051EG2.HE/HD 95 62 98 97 94 92 91 86 80 74
6057EG2.HE/HD 96 63 98 97 95 93 92 87 81 75
5058EG2.HE/HD 96 63 98 97 95 93 92 87 81 75
6063EG2.HE/HD 96 63 98 97 95 93 92 87 81 75
6067EG2.HE/HD 97 64 99 98 96 94 93 88 82 76
6070EG2.HE/HD 97 64 99 98 96 94 93 88 82 76
8076EG2.HE/HD 97 64 99 98 96 94 93 88 82 76
8080EG2.HE/HD 97 64 99 98 96 94 93 88 82 76
8084EG2.HE/HD 98 65 99 99 97 95 94 89 83 76
8089EG2.HE/HD 98 65 99 99 97 95 94 89 83 76
8092EG2.HE/HD 98 65 99 99 97 95 94 89 83 76
Data on operating conditions
Data applies only to water inlet and outlet temperatures of 12 °C/ 7 C° and outside-air temperatures of 35 °C.
1) Specification of sound power (EUROVENT certified value)
The manufacturer determines the sound power value for Eurovent-certified units in accordance with ISO 9614 standard.
This certification expressly refers to sound power in dB(A), which thus constitutes obligatory data in this case.
2) Specification of sound pressure level
The sound pressure level is determined according to enveloping surface method with a reflecting plane (Q = 2). The distance of
10 m refers to the external dimensions of the unit. For sound pressure level the following corrections can be used:
Sound pressure level at 5 m: +5 dB as compared to sound pressure level at 10 meters distance
Sound pressure level at 15 m: -3 dB as compared to sound pressure level at 10 meters distance
Sound pressure level at 20 m: -6 dB as compared to sound pressure level at 10 meters distance
Only an externally engaged acoustics engineer should carry out specific sound level calculations to be valid for your installation site.

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 21/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Footprint
R4 CLEARANCE FOR AIR SUPPLY!
Unit must be able to freely discharge air upwards. Air short-circuiting must be
impossible! The necessary clearances near and over the unit may exceed the
depicted maintenance clearance by many times.

Tab. 7: Clearances

Unit sizes R1 R2 R3 R4

2004-2022 [mm] 1000 1000 1000 1000


Fig. 6: Required clearances (example
representation) 4018-4037 [mm] 2300 1500 1500 1500
4040-8092 [mm] 2000 1500 1500 1500

Anti-vibration mounts
Tab. 8: Required anti-vibration mounts according to the unit model

Spring anti-vibration mounts (Option .I01) Rubber anti-vibration isolators (option .I02)

FläktGroup individual part designation FläktGroup individual part designation


Unit type FGAC…
Units with pump(s) Units with
Units without Units with pump(s) Units without Units with
and with buffer pump(s) and
pump(s) and without buffer pump(s) pump(s) and with
tank without buffer
tank buffer tank
tank
Standard units
2004DG1(.D) N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2005DG1(.D) N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2006DG1(.D) N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2007DG1(.D) N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2008DG1(.D) N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2009DG1(.D) N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2010DG2(.D) N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2011DG2(.D) N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2012DG2(.D) N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2014DG2(.D) N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2016DG2(.D) N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2018DG2(.D) N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2020DG2(.D) N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2022DG2(.D) N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4018DG2(.D) 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4021DG2(.D) 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4024DG2(.D) 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4026DG2(.D) 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4029DG2(.D) 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4033DG2(.D) 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4037DG2(.D) 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4040EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4042EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4046EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
5051EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
6057EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
5058EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
6063EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
6067EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
6070EG2(.D) 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000

Page 22/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Spring anti-vibration mounts (Option .I01) Rubber anti-vibration isolators (option .I02)

FläktGroup individual part designation FläktGroup individual part designation


Unit type FGAC…
Units with pump(s) Units with
Units without Units with pump(s) Units without Units with
and with buffer pump(s) and
pump(s) and without buffer pump(s) pump(s) and with
tank without buffer
tank buffer tank
tank
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
8076EG2(.D) 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-57 10xFZ-400-57
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
8080EG2(.D) 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-57 10xFZ-400-57
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
8084EG2(.D) 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-57 10xFZ-400-57
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
8089EG2(.D) 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-57 10xFZ-400-57
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
8092EG2(.D) 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-57 10xFZ-400-57
5xSR21-1000
2xSR21-1000 2xSR21-1000
SL units (super low noise version)
2004DG1.SL/SD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2005DG1.SL/SD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2006DG1.SL/SD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2007DG1.SL/SD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2008DG1.SL/SD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2009DG1.SL/SD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2010DG2.SL/SD N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2011DG2.SL/SD N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2012DG2.SL/SD N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2014DG2.SL/SD N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2016DG2.SL/SD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2018DG2.SL/SD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2020DG2.SL/SD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2022DG2.SL/SD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4018DG2.SL/SD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4021DG2.SL/SD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4024DG2.SL/SD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4026DG2.SL/SD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4029DG2.SL/SD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4033DG2.SL/SD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4037DG2.SL/SD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4040EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4042EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4046EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
5051EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
6057EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
5058EG2.SL/SD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6063EG2.SL/SD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6067EG2.SL/SD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6070EG2.SL/SD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8076EG2.SL/SD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8080EG2.SL/SD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 23/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Spring anti-vibration mounts (Option .I01) Rubber anti-vibration isolators (option .I02)

FläktGroup individual part designation FläktGroup individual part designation


Unit type FGAC…
Units with pump(s) Units with
Units without Units with pump(s) Units without Units with
and with buffer pump(s) and
pump(s) and without buffer pump(s) pump(s) and with
tank without buffer
tank buffer tank
tank
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8084EG2.SL/SD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8089EG2.SL/SD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8092EG2.SL/SD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
HE units (highly efficient version)
2004DG1.HE/HD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2005DG1.HE/HD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2006DG1.HE/HD N/A N/A N/A 4xFZ-100-57 4xFZ-200-51 4xFZ-200-51
2007DG1.HE/HD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2008DG1.HE/HD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2009DG1.HE/HD N/A N/A N/A 4xFZ-200-51 4xFZ-200-51 4xFZ-200-51
2010DG2.HE/HD N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2011DG2.HE/HD N/A N/A N/A 4xFZ-200-51 4xFZ-200-57 4xFZ-200-57
2012DG2.HE/HD N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2014DG2.HE/HD N/A N/A N/A 4xFZ-200-57 4xFZ-200-57 4xFZ-200-57
2016DG2.HE/HD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2018DG2.HE/HD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2020DG2.HE/HD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
2022DG2.HE/HD N/A N/A N/A 6xFZ-200-51 6xFZ-200-57 6xFZ-200-57
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4018DG2.HE/HD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4021DG2.HE/HD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4024DG2.HE/HD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H + 4xSR21-550H +
4026DG2.HE/HD 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4029DG2.HE/HD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4033DG2.HE/HD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
4xSR21-550H + 4xSR21-550H +
4037DG2.HE/HD 6xSR21-800 6xFZ-400-51 6xFZ-400-51 6xFZ-400-51
2xSR21-800 2xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4040EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4042EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 6xSR21-550H + 4xSR21-550H +
4046EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-51
2xSR21-800 2xSR21-800 4xSR21-800
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
5051EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
6057EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
6xSR21-550H + 3xSR21-550H + 5xSR21-800 +
5058EG2.HE/HD 8xFZ-400-51 8xFZ-400-51 8xFZ-400-57
2xSR21-800 5xSR21-800 3xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6063EG2.HE/HD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6067EG2.HE/HD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-550H + 5xSR21-550H +
5xSR21-800 +
6070EG2.HE/HD 3xSR21-800 + 3xSR21-800 + 10xFZ-400-51 10xFZ-400-51 10xFZ-400-51
5xSR21-1000
2xSR21-1000 2xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8076EG2.HE/HD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8080EG2.HE/HD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8084EG2.HE/HD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8089EG2.HE/HD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000
5xSR21-800 + 5xSR21-800 + 5xSR21-800 +
8092EG2.HE/HD 10xFZ-400-51 10xFZ-400-57 10xFZ-600-51
5xSR21-1000 5xSR21-1000 5xSR21-1000

NOTICE!
If the units are operated without the appropriate anti-vibration mounts, the warranty is void!

Page 24/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Electrical data
Tab. 9: Electrical data

Unit type Compressors Fan 3) Total 1) 2) 3)

starter
L.R.A.
F.L.A.

F.L.A.
F.L.A
F.L.I.

F.L.I.

F.L.I.
[kW]

[kW]

[kW]

With
FGAC…

S.A.

S.A.

Soft
Power supply n

[A]

[A]

[A]

[A]
Standard units
2004DG1(.D) 400/3+N/50 2 2x9.1 2x15.6 2x98 1.2 4 19.4 36 118 79
2005DG1(.D) 400/3+N/50 2 2x10.5 2x18.1 2x142 1.2 4 22.2 41 165 108
2006DG1(.D) 400/3+N/50 2 2x11.5 2x18.1 2x123 1.2 4 24.2 41 146 96
2007DG1(.D) 400/3+N/50 2 2x12.9 2x20.4 2x138 1.8 6 27.6 47 165 110
2008DG1(.D) 400/3+N/50 2 2x14.4 2x22.9 2x145 1.8 6 30.6 52 175 116
2009DG1(.D) 400/3+N/50 2 2x16.7 2x26.9 2x172 1.8 6 35.2 60 206 137
2010DG2(.D) 400/3/50 2 1x16.7+1x22.4 1x26.9+1x35.6 1x172+1x211 4 8 43.1 71 246 162
2011DG2(.D) 400/3/50 2 2x22.4 2x35.6 2x211 4 8 48.8 79 255 171
2012DG2(.D) 400/3/50 2 1x22.4+1x30.5 1x35.6+1x48 1x211+1x210 4 8 56.9 92 255 170
2014DG2(.D) 400/3/50 2 2x30.5 2x48 2x210 4 8 65 104 266 182
2016DG2(.D) 400/3/50 2 1x30.5+1x38 1x48+1x61 1x210+1x326 6 12 74.5 121 386 256
2018DG2(.D) 400/3/50 2 2x38 2x61 2x326 6 12 82 134 399 269
2020DG2(.D) 400/3/50 2 2x42.8 2x70.2 2x326 6 12 91.6 152 408 278
2022DG2(.D) 400/3/50 2 2x46.4 2x75.6 2x295 6 12 98.8 163 383 265
4018DG2(.D) 400/3/50 4 4x17.1 4x29.3 4x197 7.6 16 76 133 301 223
4021DG2(.D) 400/3/50 4 2x17.1+2x23.7 2x29.3+2x38.7 2x197+2x215 7.6 16 89.2 152 328 243
4024DG2(.D) 400/3/50 4 4x23.7 4x38.7 4x215 7.6 16 102.4 170 347 262
4026DG2(.D) 400/3/50 4 2x23.7+2x28.4 2x38.7+2x46.3 2x215+2x260 7.6 16 111.8 186 399 296
4029DG2(.D) 400/3/50 4 4x28.4 4x46.3 4x260 11.4 24 125 209 422 319
4033DG2(.D) 400/3/50 4 2x28.4+2x36.2 2x46.3+2x59.6 2x260+2x320 11.4 24 140.6 235 496 369
4037DG2(.D) 400/3/50 4 4x36.2 4x59.6 4x320 11.4 24 156.2 262 522 395
4040EG2(.D) 400/3/50 4 3x34.5+1x42 3x55.1+1x68.4 3x326+1x298 11.4 24 156.9 257 515 393
4042EG2(.D) 400/3/50 4 2x34.5+2x42 2x55.1+2x68.4 2x326+2x298 11.4 24 164.4 270 528 400
4046EG2(.D) 400/3/50 4 4x42 4x68.4 4x298 11.4 24 179.4 297 527 408
5051EG2(.D) 400/3/50 5 3x34.5+2x42 3x55.1+2x68.4 3x326+2x298 13.3 28 200.8 329 587 464
6057EG2(.D) 400/3/50 6 6x34.5 6x55.1 6x326 15.2 32 222.2 362 633 504
5058EG2(.D) 400/3/50 5 5x42 5x68.4 5x298 15.2 32 225.2 373 603 485
6063EG2(.D) 400/3/50 6 3x34.5+3x42 3x55.1+3x68.4 3x326+3x298 17.1 36 246.6 406 663 538
6067EG2(.D) 400/3/50 6 1x34.5+5x42 1x55.1+5x68.4 1x326+5x298 17.1 36 261.6 432 690 547
6070EG2(.D) 400/3/50 6 6x42 6x68.4 6x298 19 40 271 449 679 561
8076EG2(.D) 400/3/50 8 8x34.5 8x55.1 8x326 22.8 48 298.8 488 759 630
8080EG2(.D) 400/3/50 8 6x34.5+2x42 6x55.1+2x68.4 6x326+2x298 22.8 48 313.8 514 772 680
8084EG2(.D) 400/3/50 8 4x34.5+4x42 4x55.1+4x68.4 4x326+4x298 22.8 48 328.8 541 798 683
8089EG2(.D) 400/3/50 8 2x34.5+6x42 2x55.1+6x68.4 2x326+6x298 22.8 48 343.8 567 825 686
8092EG2(.D) 400/3/50 8 8x42 8x68.4 8x298 22.8 48 358.8 594 824 706
Standard units + EC fan (option .E81)
2004DG1(.D)+.E81 400/3+N/50 2 2x9.1 2x15.6 2x98 1.38 8 19.6 40 122 83
2005DG1(.D)+.E81 400/3+N/50 2 2x10.5 2x18.1 2x142 1.38 8 22.4 45 169 112
2006DG1(.D)+.E81 400/3+N/50 2 2x11.5 2x18.1 2x123 1.38 8 24.4 45 150 100
2007DG1(.D)+.E81 400/3+N/50 2 2x12.9 2x20.4 2x138 2.07 12 27.9 54 172 116
2008DG1(.D)+.E81 400/3+N/50 2 2x14.4 2x22.9 2x145 2.07 12 30.9 59 181 122
2009DG1(.D)+.E81 400/3+N/50 2 2x16.7 2x26.9 2x172 2.07 12 35.5 67 212 143
2010DG2(.D)+.E81 400/3/50 2 1x16.7+1x22.4 1x26.9+1x35.6 1x172+1x211 3.4 6 42.5 68 243 160
2011DG2(.D)+.E81 400/3/50 2 2x22.4 2x35.6 2x211 3.4 6 48.2 77 252 169
2012DG2(.D)+.E81 400/3/50 2 1x22.4+1x30.5 1x35.6+1x48 1x211+1x210 3.4 6 56.3 89 252 168
2014DG2(.D)+.E81 400/3/50 2 2x30.5 2x48 2x210 3.4 6 64.4 101 263 180
2016DG2(.D)+.E81 400/3/50 2 1x30.5+1x38 1x48+1x61 1x210+1x326 5.1 9 73.6 117 382 253
2018DG2(.D)+.E81 400/3/50 2 2x38 2x61 2x326 5.1 9 81.1 130 395 266
2020DG2(.D)+.E81 400/3/50 2 2x42.8 2x70.2 2x326 5.1 9 90.7 149 404 275
2022DG2(.D)+.E81 400/3/50 2 2x46.4 2x75.6 2x295 5.1 9 97.9 159 379 262
4018DG2(.D)+.E81 400/3/50 4 4x17.1 4x29.3 4x197 6.8 12 75.0 128 296 219
4021DG2(.D)+.E81 400/3/50 4 2x17.1+2x23.7 2x29.3+2x38.7 2x197+2x215 6.8 12 88.4 147 323 239
4024DG2(.D)+.E81 400/3/50 4 4x23.7 4x38.7 4x215 6.8 12 101.6 166 342 258
4026DG2(.D)+.E81 400/3/50 4 2x23.7+2x28.4 2x38.7+2x46.3 2x215+2x260 6.8 12 111.0 181 395 292
4029DG2(.D)+.E81 400/3/50 4 4x28.4 4x46.3 4x260 10.2 18 123.8 201 415 313
4033DG2(.D)+.E81 400/3/50 4 2x28.4+2x36.2 2x46.3+2x59.6 2x260+2x320 10.2 18 139.4 228 488 363
4037DG2(.D)+.E81 400/3/50 4 4x36.2 4x59.6 4x320 10.2 18 155.0 255 515 389
4040EG2(.D)+.E81 400/3/50 4 3x34.5+1x42 3x55.1+1x68.4 3x326+1x298 10.2 18 155.7 250 508 393
4042EG2(.D)+.E81 400/3/50 4 2x34.5+2x42 2x55.1+2x68.4 2x326+2x298 10.2 18 163.2 263 521 400
4046EG2(.D)+.E81 400/3/50 4 4x42 4x68.4 4x298 10.2 18 178.2 290 519 402

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 25/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Unit Type Compressors Fan 3) Total 1) 2) 3)

starter
L.R.A.
F.L.A.

F.L.A.
F.L.A
F.L.I.

F.L.I.

F.L.I.
[kW]

[kW]

[kW]

With
S.A.

S.A.
FGAC…

Soft
Power supply n

[A]

[A]

[A]

[A]
5051EG2(.D)+.E81 400/3/50 5 3x34.5+2x42 3x55.1+2x68.4 3x326+2x298 11.9 21 199.4 321 579 464
6057EG2(.D)+.E81 400/3/50 6 6x34.5 6x55.1 6x326 13.6 24 220.6 352 623 496
5058EG2(.D)+.E81 400/3/50 5 5x42 5x68.4 5x298 13.6 24 223.6 364 593 477
6063EG2(.D)+.E81 400/3/50 6 3x34.5+3x42 3x55.1+3x68.4 3x326+3x298 15.3 27 244.8 395 652 538
6067EG2(.D)+.E81 400/3/50 6 1x34.5+5x42 1x55.1+5x68.4 1x326+5x298 15.3 27 259.8 421 679 547
6070EG2(.D)+.E81 400/3/50 6 6x42 6x68.4 6x298 17 30 269 437 667 551
8076EG2(.D)+.E81 400/3/50 8 8x34.5 8x55.1 8x326 20.4 36 296.4 473 744 618
8080EG2(.D)+.E81 400/3/50 8 6x34.5+2x42 6x55.1+2x68.4 6x326+2x298 20.4 36 311.4 500 757 680
8084EG2(.D)+.E81 400/3/50 8 4x34.5+4x42 4x55.1+4x68.4 4x326+4x298 20.4 36 326.4 526 784 683
8089EG2(.D)+.E81 400/3/50 8 2x34.5+6x42 2x55.1+6x68.4 2x326+6x298 20.4 36 341.4 553 811 686
8092EG2(.D)+.E81 400/3/50 8 8x42 8x68.4 8x298 20.4 36 326.4 580 809 694
SL units (super low noise version)
2004DG1.SL/SD 400/3+N/50 2 2x9.1 2x15.6 2x98 1.2 4 19.4 36 118 79
2005DG1.SL/SD 400/3+N/50 2 2x10.5 2x18.1 2x142 1.2 4 22.2 41 165 108
2006DG1.SL/SD 400/3+N/50 2 2x11.5 2x18.1 2x123 1.2 4 24.2 41 146 96
2007DG1.SL/SD 400/3+N/50 2 2x12.9 2x20.4 2x138 1.8 6 27.6 47 165 110
2008DG1.SL/SD 400/3+N/50 2 2x14.4 2x22.9 2x145 1.8 6 30.6 52 175 116
2009DG1.SL/SD 400/3+N/50 2 2x16.7 2x26.9 2x172 1.8 6 35.2 60 206 137
2010DG2.SL/SD 400/3/50 2 1x16.7+1x22.4 1x26.9+1x35.6 1x172+1x211 4 8 43.1 71 246 162
2011DG2.SL/SD 400/3/50 2 2x22.4 2x35.6 2x211 4 8 48.8 79 255 171
2012DG2.SL/SD 400/3/50 2 1x22.4+1x30.5 1x35.6+1x48 1x211+1x210 4 8 56.9 92 255 170
2014DG2.SL/SD 400/3/50 2 2x30.5 2x48 2x210 4 8 65 104 266 182
2016DG2.SL/SD 400/3/50 2 1x30.5+1x38 1x48+1x61 1x210+1x326 6 12 74.5 121 386 256
2018DG2.SL/SD 400/3/50 2 2x38 2x61 2x326 6 12 82 134 399 269
2020DG2.SL/SD 400/3/50 2 2x42.8 2x70.2 2x326 6 12 91.6 152 408 278
2022DG2.SL/SD 400/3/50 2 2x46.4 2x75.6 2x295 6 12 98.8 163 383 265
4018DG2.SL/SD 400/3/50 4 4x17.1 4x29.3 4x197 7.6 16 76 133 301 223
4021DG2.SL/SD 400/3/50 4 2x17.1+2x23.7 2x29.3+2x38.7 2x197+2x215 7.6 16 89.2 152 328 243
4024DG2.SL/SD 400/3/50 4 4x23.7 4x38.7 4x215 7.6 16 102.4 170 347 262
4026DG2.SL/SD 400/3/50 4 2x23.7+2x28.4 2x38.7+2x46.3 2x215+2x260 7.6 16 111.8 186 399 296
4029DG2.SL/SD 400/3/50 4 4x28.4 4x46.3 4x260 11.4 24 125 209 422 319
4033DG2.SL/SD 400/3/50 4 2x28.4+2x36.2 2x46.3+2x59.6 2x260+2x320 11.4 24 140.6 235 496 369
4037DG2.SL/SD 400/3/50 4 4x36.2 4x59.6 4x320 11.4 24 156.2 262 522 395
4040EG2.SL/SD 400/3/50 4 3x34.5+1x42 3x55.1+1x68.4 3x326+1x298 7.2 12 155.1 251 509 393
4042EG2.SL/SD 400/3/50 4 2x34.5+2x42 2x55.1+2x68.4 2x326+2x298 7.2 12 162.6 265 522 400
4046EG2.SL/SD 400/3/50 4 4x42 4x68.4 4x298 7.2 12 177.6 291 521 396
5051EG2.SL/SD 400/3/50 5 3x34.5+2x42 3x55.1+2x68.4 3x326+2x298 8.4 14 198.3 322 580 464
6057EG2.SL/SD 400/3/50 6 6x34.5 6x55.1 6x326 9.6 16 219 353 624 488
5058EG2.SL/SD 400/3/50 5 5x42 5x68.4 5x298 9.6 16 222 364 594 469
6063EG2.SL/SD 400/3/50 6 3x34.5+3x42 3x55.1+3x68.4 3x326+3x298 10.8 18 242.7 395 652 538
6067EG2.SL/SD 400/3/50 6 1x34.5+5x42 1x55.1+5x68.4 1x326+5x298 10.8 18 258.9 424 681 547
6070EG2.SL/SD 400/3/50 6 6x42 6x68.4 6x298 12 20 266.4 437 666 541
8076EG2.SL/SD 400/3/50 8 8x34.5 8x55.1 8x326 14.4 24 295.2 476 747 606
8080EG2.SL/SD 400/3/50 8 6x34.5+2x42 6x55.1+2x68.4 6x326+2x298 14.4 24 310.2 503 760 680
8084EG2.SL/SD 400/3/50 8 4x34.5+4x42 4x55.1+4x68.4 4x326+4x298 14.4 24 325.2 529 787 683
8089EG2.SL/SD 400/3/50 8 2x34.5+6x42 2x55.1+6x68.4 2x326+6x298 14.4 24 340.2 556 813 686
8092EG2.SL/SD 400/3/50 8 8x42 8x68.4 8x298 14.4 24 355.2 582 812 682
SL units (super low noise version) + EC fan (option .E82)
2004DG1.SL/SD+.E81 400/3+N/50 2 2x9.1 2x15.6 2x98 1.38 8 19.6 40 122 83
2005DG1.SL/SD+.E81 400/3+N/50 2 2x10.5 2x18.1 2x142 1.38 8 22.4 45 169 112
2006DG1.SL/SD+.E81 400/3+N/50 2 2x11.5 2x18.1 2x123 1.38 8 24.4 45 150 100
2007DG1.SL/SD+.E81 400/3+N/50 2 2x12.9 2x20.4 2x138 2.07 12 27.9 54 172 116
2008DG1.SL/SD+.E81 400/3+N/50 2 2x14.4 2x22.9 2x145 2.07 12 30.9 59 181 122
2009DG1.SL/SD+.E81 400/3+N/50 2 2x16.7 2x26.9 2x172 2.07 12 35.5 67 212 143
2010DG2.SL/SD+.E81 400/3/50 2 1x16.7+1x22.4 1x26.9+1x35.6 1x172+1x211 3.4 6 42.5 68 243 160
2011DG2.SL/SD+.E81 400/3/50 2 2x22.4 2x35.6 2x211 3.4 6 48.2 77 252 169
2012DG2.SL/SD+.E81 400/3/50 2 1x22.4+1x30.5 1x35.6+1x48 1x211+1x210 3.4 6 56.3 89 252 168
2014DG2.SL/SD+.E81 400/3/50 2 2x30.5 2x48 2x210 3.4 6 64.4 101 263 180
2016DG2.SL/SD+.E81 400/3/50 2 1x30.5+1x38 1x48+1x61 1x210+1x326 5.1 9 73.6 117 382 253
2018DG2.SL/SD+.E81 400/3/50 2 2x38 2x61 2x326 5.1 9 81.1 130 395 266
2020DG2.SL/SD+.E81 400/3/50 2 2x42.8 2x70.2 2x326 5.1 9 90.7 149 404 275
2022DG2.SL/SD+.E81 400/3/50 2 2x46.4 2x75.6 2x295 5.1 9 97.9 159 379 262
4018DG2.SL/SD+.E81 400/3/50 4 4x17.1 4x29.3 4x197 6.8 12 88.4 147 296 219
4021DG2.SL/SD+.E81 400/3/50 4 2x17.1+2x23.7 2x29.3+2x38.7 2x197+2x215 6.8 12 88.4 147 323 239

Page 26/28 PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Unit Type Compressors Fan 3) Total 1) 2) 3)

starter
L.R.A.
F.L.A.

F.L.A.
F.L.A
F.L.I.

F.L.I.

F.L.I.
[kW]

[kW]

[kW]

With
S.A.

S.A.
FGAC…

Soft
Power supply n

[A]

[A]

[A]

[A]
4024DG2.SL/SD+.E81 400/3/50 4 4x23.7 4x38.7 4x215 6.8 12 101.6 166 342 258
4026DG2.SL/SD+.E81 400/3/50 4 2x23.7+2x28.4 2x38.7+2x46.3 2x215+2x260 6.8 12 111.0 181 395 292
4029DG2.SL/SD+.E81 400/3/50 4 4x28.4 4x46.3 4x260 10.2 18 123.8 201 415 313
4033DG2.SL/SD+.E81 400/3/50 4 2x28.4+2x36.2 2x46.3+2x59.6 2x260+2x320 10.2 18 139.4 228 488 363
4037DG2.SL/SD+.E81 400/3/50 4 4x36.2 4x59.6 4x320 10.2 18 155.0 255 515 389
4040EG2.SL/SD+.E82 400/3/50 4 3x34.5+1x42 3x55.1+1x68.4 3x326+1x298 10.2 18 159.1 255 513 393
4042EG2.SL/SD+.E82 400/3/50 4 2x34.5+2x42 2x55.1+2x68.4 2x326+2x298 10.2 18 166.6 269 526 400
4046EG2.SL/SD+.E82 400/3/50 4 4x42 4x68.4 4x298 10.2 18 181.6 295 525 402
5051EG2.SL/SD+.E82 400/3/50 5 3x34.5+2x42 3x55.1+2x68.4 3x326+2x298 11.9 21 202.8 326 584 464
6057EG2.SL/SD+.E82 400/3/50 6 6x34.5 6x55.1 6x326 13.6 24 224 358 629 496
5058EG2.SL/SD+.E82 400/3/50 5 5x42 5x68.4 5x298 13.6 24 223.6 364 593 477
6063EG2.SL/SD+.E82 400/3/50 6 3x34.5+3x42 3x55.1+3x68.4 3x326+3x298 15.3 27 248.2 400 658 538
6067EG2.SL/SD+.E82 400/3/50 6 1x34.5+5x42 1x55.1+5x68.4 1x326+5x298 15.3 27 264.9 430 687 547
6070EG2.SL/SD+.E82 400/3/50 6 6x42 6x68.4 6x298 17 30 272.4 443 672 551
8076EG2.SL/SD+.E82 400/3/50 8 8x34.5 8x55.1 8x326 20.4 36 303.2 484 755 618
8080EG2.SL/SD+.E82 400/3/50 8 6x34.5+2x42 6x55.1+2x68.4 6x326+2x298 20.4 36 318.2 511 768 680
8084EG2.SL/SD+.E82 400/3/50 8 4x34.5+4x42 4x55.1+4x68.4 4x326+4x298 20.4 36 333.2 537 795 683
8089EG2.SL/SD+.E82 400/3/50 8 2x34.5+6x42 2x55.1+6x68.4 2x326+6x298 20.4 36 348.2 564 821 686
8092EG2.SL/SD+.E82 400/3/50 8 8x42 8x68.4 8x298 20.4 36 363.2 590 820 694
HE units (highly efficient version)
2004DG1.HE/HD 400/3+N/50 2 2x9.1 2x15.6 2x98 1.38 8 19.6 40 122 83
2005DG1.HE/HD 400/3+N/50 2 2x10.5 2x18.1 2x142 1.38 8 22.4 45 169 112
2006DG1.HE/HD 400/3+N/50 2 2x11.5 2x18.1 2x123 1.38 8 24.4 45 150 100
2007DG1.HE/HD 400/3+N/50 2 2x12.9 2x20.4 2x138 2.07 12 27.9 54 172 116
2008DG1.HE/HD 400/3+N/50 2 2x14.4 2x22.9 2x145 2.07 12 30.9 59 181 122
2009DG1.HE/HD 400/3+N/50 2 2x16.7 2x26.9 2x172 2.07 12 35.5 67 212 143
2010DG2.HE/HD 400/3/50 2 1x16.7+1x22.4 1x26.9+1x35.6 1x172+1x211 3.4 6 42.5 68 243 160
2011DG2.HE/HD 400/3/50 2 2x22.4 2x35.6 2x211 3.4 6 48.2 77 252 169
2012DG2.HE/HD 400/3/50 2 1x22.4+1x30.5 1x35.6+1x48 1x211+1x210 3.4 6 56.3 89 252 168
2014DG2.HE/HD 400/3/50 2 2x30.5 2x48 2x210 3.4 6 64.4 101 263 180
2016DG2.HE/HD 400/3/50 2 1x30.5+1x38 1x48+1x61 1x210+1x326 5.1 9 73.6 117 382 253
2018DG2.HE/HD 400/3/50 2 2x38 2x61 2x326 5.1 9 81.1 130 395 266
2020DG2.HE/HD 400/3/50 2 2x42.8 2x70.2 2x326 5.1 9 90.7 149 404 275
2022DG2.HE/HD 400/3/50 2 2x46.4 2x75.6 2x295 5.1 9 97.9 159 379 262
4018DG2.HE/HD 400/3/50 4 4x17.1 4x29.3 4x197 6.8 12 75.0 128 296 219
4021DG2.HE/HD 400/3/50 4 2x17.1+2x23.7 2x29.3+2x38.7 2x197+2x215 6.8 12 88.4 147 323 239
4024DG2.HE/HD 400/3/50 4 4x23.7 4x38.7 4x215 6.8 12 101.6 166 342 258
4026DG2.HE/HD 400/3/50 4 2x23.7+2x28.4 2x38.7+2x46.3 2x215+2x260 6.8 12 111.0 181 395 292
4029DG2.HE/HD 400/3/50 4 4x28.4 4x46.3 4x260 10.2 18 123.8 201 415 313
4033DG2.HE/HD 400/3/50 4 2x28.4+2x36.2 2x46.3+2x59.6 2x260+2x320 10.2 18 139.4 228 488 363
4037DG2.HE/HD 400/3/50 4 4x36.2 4x59.6 4x320 10.2 18 155.0 255 515 389
4040EG2.HE/HD 400/3/50 4 3x34.5+1x42 3x55.1+1x68.4 3x326+1x298 10.2 18 159.1 255 513 393
4042EG2.HE/HD 400/3/50 4 2x34.5+2x42 2x55.1+2x68.4 2x326+2x298 10.2 18 166.6 269 526 400
4046EG2.HE/HD 400/3/50 4 4x42 4x68.4 4x298 10.2 18 181.6 295 525 402
5051EG2.HE/HD 400/3/50 5 3x34.5+2x42 3x55.1+2x68.4 3x326+2x298 11.9 21 202.8 326 584 464
6057EG2.HE/HD 400/3/50 6 6x34.5 6x55.1 6x326 13.6 24 224.0 358 629 496
5058EG2.HE/HD 400/3/50 5 5x42 5x68.4 5x298 13.6 24 227.0 369 599 477
6063EG2.HE/HD 400/3/50 6 3x34.5+3x42 3x55.1+3x68.4 3x326+3x298 15.3 27 248.2 400 658 538
6067EG2.HE/HD 400/3/50 6 1x34.5+5x42 1x55.1+5x68.4 1x326+5x298 15.3 27 264.9 430 687 547
6070EG2.HE/HD 400/3/50 6 6x42 6x68.4 6x298 17 30 272.4 443 672 551
8076EG2.HE/HD 400/3/50 8 8x34.5 8x55.1 8x326 20.4 36 303.2 484 755 618
8080EG2.HE/HD 400/3/50 8 6x34.5+2x42 6x55.1+2x68.4 6x326+2x298 20.4 36 318.2 511 768 680
8084EG2.HE/HD 400/3/50 8 4x34.5+4x42 4x55.1+4x68.4 4x326+4x298 20.4 36 333.2 537 795 683
8089EG2.HE/HD 400/3/50 8 2x34.5+6x42 2x55.1+6x68.4 2x326+6x298 20.4 36 348.2 564 821 686
8092EG2.HE/HD 400/3/50 8 8x42 8x68.4 8x298 20.4 36 363.2 590 820 694

All values refer to units without built-in pumps. For units with built-in pumps, the pump data must be added.

n Number of compressors F.L.I. Maximum power consumption F.L.A. Maximum power consumption
L.R.A. Starting current per compressor S.A. Starting current of entire unit

1) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.
2) Please observe the regionally applicable standards for cable cross-sections and backup fuses. Voltage tolerance: max. 10%,
voltage imbalance between phases: max. 3%.
3) Values are based on the total number of fans operating at maximum speed.

PR-2020-1032-GB • R5-07/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 27/28
Chiller with refrigerant R-454B
FGAC 2004-8092 D/E G 1/2

Terminal scheme
Setpoint shift Activation
Demand limit*
4-20 mA signal Temperature sensor 2- 2nd setpoint*
(option .E23)
Put on Put on (option .E21) 4) circuit buffer tank (option .E22)
shielding shielding (option .E05)

Y + -
G

021 022 GND 051 052 R S R M


GND + -
Serial card RS485/Modbus, LonWorks FGAC 2004-8092 DG/EG 1/2 (.D/.SL/.SD/ .HE/ .HD)
or BACnet as option, .E14 - .E17

E F A B 019 020 AA AA 096 097 FCx FCx 063 064 GND 067 068 031 032 033 034 FP1 FP1 FP2 FP2

J1 0V 0V

Contact Flow On-site General fault Refrigerant Operating Fault Fault Relay for Relay for 2nd
On-site inverter pumps
Remote monitor* water signal # max. leakage alarm message message message on-site on-site chilled-
0-10 V signal
On/Off deficiency 2A (Opt. .O28) Compressor on site on site chilled- water
1) 5)
(option .E30/.E31) 2)
* protection* ~ / 50 Hz # pump 1* 3) pump 2* 3) water pump
(Opt. .E03) Put on (Opt. (Opt. .E34) Pump #
2) 2)
shielding #
E.04/ (Opt. (Opt. .E34)
Cabling on-site provided by others E.34) E.04/E.34)
# on-site potential necessary (max. 230 V / 50 Hz / 2 A)
* potential may not be supplied on-site (potential supplied by controller)
1) Remove jumper J1 if remote contact is used. For connecting, for example, a timer or outdoor temperature switch (with hysteresis) to
enable the unit. Switching over the water temperature (e.g., in the buffer tank) is not permitted (caution: not covered by the warranty,
possible damage to the unit!)
2) With two parallel inverter pumps (redundancy) provided by the customer, use the 0-10 V signal equally as control signal for both pumps.
Additionally, apply the enable signals of the corresponding terminals to the pumps. The pumps are switched over via the enable signals.
If available, connect the fault signals of the customer's pumps. Remove the jumper in each case.
3) Note: If the setpoint shift is not required or not connected, parameter
4) REG 0047 must be set to 0, otherwise an error is displayed.
5) One signal per compressor

Fig. 7: Terminal scheme