CHILLER
GLAC 2150 – 3722 DA2(.SL/.HE)
WITH SCREW COMPRESSOR
Table of Contents
Type code EU
GL A C 2 150 D A 2 .SL
Operating mode
Supply voltage
Capacity stage
Compressors
Condensing
Unit model
Refrigerant
FläktGroup
Number of
Serie
GL FläktGroup Series
Air cooled
A
(outdoor installation)
C Chiller
2 2 Screw compressors
3 3 Screw compressors
Unit sizes with 2 compressors:
150, 170, 190, 192, 220, 260, 265, 270, 272,150, 170, 190,
150-
192, 220, 260, 265, 270, 272,
481
315, 360, 390, 420, 450, 480, 481*, 482, 541, 600*, 602*
Unit sizes with 3 compressors:
570-
570**, 630, 660**, 690*, 720*, 721*, 722*
722
*not for HE units / **only for HE units
D Unit series D
A Refrigerant R134a
2 400 V / 3~ / 50Hz / PE
_ Standard
.HE HE unit - high efficiency model
.SL SL unit - especially quiet model
Fig. 2: Explanation of unit type code
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit description
- Attention: A water filter must be installed on site directly before the evaporator(s) to protect them
from contamination and deposits of any kind. The water filter must have a mesh size of 0.9 mm or
less.
- All units of the GLAC 2150-3690 DA2(.SL) and GLAC 2150-3630DA2.HE series are Eurovent-certified.
Page 2/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 3/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Electrical accessories
Option .E81 or - EC-Fans
.E82 for SL units, Use of EC fans provides the following benefits:
.E83 for HE units - Reduced power consumption in part-load mode
- Continuous speed regulation of fans
- Reduced sound level in part-load mode
- More precise control of the condensing pressure
Operating range down to -15°C air-inlet temperature
Option .E54 or .E72 - Extended operating range for higher outdoor temperatures up to 50 °C (or
for SL units, .E73 for 52 °C for HE units)
HE units Observe operating limit chart!
Attention: Changed technical data due to stronger compressor motors!
Please ask for order-related technical data!
Option .E55 or .E56 - Compensation of reactive current for compressor
for SL units, .E57 for Condensers at the electrical compressor terminals to increase the mean cos phi
HE units
Option .E58 - Heating for switch cabinet
Electric heating of switch cabinet ensures trouble-free operation of all electric
components throughout entire year and prevents build-up of condensation inside
switch cabinets in areas with relatively high air humidity.
Option .E74 - Quick start after power failure (UPS for controller on-site)
Time for restarting of individual compressors and reaching maximum capacity is
reduced to a minimum. The mandatory safety times of compressors are
considered. Inquire with the sales office on the changes in the starting time.
These accessories require an on-site continuous power supply of controller.
Option .E75 - Quick start after power failure (UPS for controller in the unit)
Time for restarting of individual compressors and reaching maximum capacity is
reduced to a minimum. The mandatory safety times of compressors are
considered. Inquire with the sales office on the changes in the starting time. For
the period of voltage failure the controller operates using uninterruptible power
source and can ensure quick start of the unit. For dimensioning the pre-mounted
uninterruptible power source it is required to specify the maximum duration of the
voltage failure when ordering the unit.
Option .E76 - Double power supply with automatic switch over
It is also possible to enable an alterative power supply for the unit, e.g. by using a
second supply line from an emergency power generator. When a standard power
supply fails, the unit automatically switches to an alternative power supply. The
unit switches back to a standard power supply, as soon as the latter is restored.
Option .E77 - Double power supply with motorized remote switch over (supply line from
emergency power generator)
Page 4/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
It is also possible to enable an alterative power supply for the unit, e.g. by using a
second supply line from an emergency power generator. This type is a motorized
switch-over which is actuated using a remote contact of an additional power
supply.
Option .E78 - Switch cabinet lighting
To facilitate unit servicing in bad visibility conditions.
Installation of accessories
Option .I02 or - Rubber isolator
.I26 for SL units Anti-vibration isolators with rubber elements to minimize vibration transmission
.I59 for HE units (supplied separately).
The on-site installation of suitable anti-vibration mounts is a prerequisite for
warranty claims!
Option .I10 - Flow switch
With paddle for installation in the hydraulic circuit at the chilled-water outlet
(supplied separately). The on-site installation and wiring of the flow switch is a
prerequisite for warranty claims!
Option .I08 - Chilled-water connections with flanges
Depending on the unit type either mounted flanges or separate flange adaptor kit.
Only in combination with external water connections when available.
Option .I77 - Water connection of evaporator on the right side
Water connections of the evaporator are located on the right side of unit, facing
(standard pre- the switch cabinet.
selection)
Option .I78 - Water connection of evaporator on the left side
Water connections of the evaporator are located on the left side of unit, facing the
switch cabinet.
Option .I19 for - Extra sound attenuation for compressor section
standard units or Sound-attenuated hood for individual compressors or entire compressor section
I.66 for HE units for reduction of sound power level by -2dB(A).
Depending on the model, unit weight can change.
Option .I05 or - Protection grille for air-cooled heat exchanger
.I65 for SL units Additional protection grille to prevent access to components installed under the
.I61 for HE units air-cooled heat exchangers
Option .I55 or - Anti-corrosion coating for microchannel heat exchangers (MCHX)
.I56 for SL units, 100 % epoxy-polymer coating using e-coating method for the entire air-cooled
I57 for HE units microchannel heat exchanger for protection against corrosion, UV radiation, and
to ensure enhanced weather-proof features in conditions with average air
contamination and application in proximity to sea water with average salt content.
Option .I03 or - Cu/Al heat exchanger with corrosion-resistant coating for the fins (instead
.I23 for SL units, of the microchannel heat exchanger)
I52 for HE units Corrosion-resistant coating for fins of Cu/Al heat exchanger. The use of chemical
cleaning methods and protective-paint coating made of polyester resin ensures
the following characteristics:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
1000 hours
- UV durability
Attention: Change in refrigerant charge volume and unit weight
Option .I18 or - Cu/Al heat exchanger with polyurethane coating (instead of microchannel
.I22 for SL units, heat exchanger)
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 5/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
I51 for HE units Cu/Al heat exchanger with polyurethane paint. The entire heat exchanger
receives protective coating using polyurethane paint, so that the following
qualities are safeguarded:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
4000 hours
- UV durability
Attention: Change in refrigerant charge volume and unit weight
Mechanics accessories
Option .M20 - Frost protection heating for pipework and pump
to protect against freezing in standby mode down to -10 °C outdoor temperature
For installation locations where the outdoor temperature can fall below
-10 °C, the unit must be configured with a water-glycol mixture.
Pumps - Refer to separate pump data information sheet
Refrigeration circuit accessories
Option .R13 - LP and HP Pressure Gauges
Refrigerant gauge for high and low pressure side for reading off current operating
pressures.
Option .R19 - Safety valve in double configuration for high and low-pressure side
Two safety valves are connected via a changeover valve on the high and low-
pressure side each. By using a changeover valve a trouble-free and fast
replacement of safety valves without refrigerant loss is possible for maintenance
and service jobs.
Option .R02 - Shut-off valves for compressor suction side
Service shut-off valve assembled for fast and easy maintenance.
Option .R23 or - Condensing pressure control for the operation at very low air-inlet
.R24 für SL units, temperatures
.R25 for HE units Chilled-water side condenser-pressure control to ensure operation at air-inlet
temperature down to -20 °C and windy operation site.
Refer to the operating limit charts for the exact operating range.
Other accessories
Option .O10 - Glycol operation below 0°C
Option for chiller fitted with screw compressors at chilled-water outlet temperature
below 0°C, operating conditions must be specified in the order.
Option .O24 or .O25 - Increased thermal insulation of evaporator (and possibly pipework and
for units with pumps pump)
Double-layer heat insulation of evaporator (and possibly pump and pipework to
prevent condensate water in environments with especially high relative humidity.
Especially recommended for media temperatures below 0°C.
Option .O27 - Refrigerant leak detection (Alarm)
The compressor section is monitored for leaking medium. A refrigerant leakage is
triggered by an error message from the controller.
Option .O28 - Refrigerant leak detection (compressor switch off)
The compressor section is monitored for leaking medium. In the event of
refrigerant leakage, the compressor is switched off and an error message is
triggered by the controller.
Option .O13 or - Unit stabilization for shipping
.O26 for SL units, Additionally reinforced frame construction to stabilize unit during shipping.
.O14 for HE units
Page 6/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Operating limits
On the water side, the operating limits according to Table 1, and on the air and water side, the limits of the selected
options according to the following chart must be observed.
Table1: Operating limits of water (glycol) circuit
Min Max
Water inlet [°C] -5 26
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 7/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
55 55
45 45
35 35
25 25
15 15
5 5
tLuft,Ansaug [°C]
tLuft,Ansaug [°C]
-5 -5
-15 -15
-25 -25
-10 -5 0 5 10 15 20 25 -10 -5 0 5 10 15 20 25
tWasser,Austritt [°C] tWasser,Austritt [°C]
Fig. 3: Standard operating range Fig. 4: Extended operating range for cooling operation in winter
Standard configuration AC fans with autotransformer EC fans with continuously variable actuation
Option .E81 or .E82 for SL units, .E83 for HE units
Operating range down to -10 °C air-intake temperature based on a water-outlet Operating range down to -15 °C air-intake temperature based on a water-outlet
temperature of +5 to +18 °C. temperature of -5 to +18 °C.
55 55
45 45
35 35
25 25
15 15
5 5
tLuft,Ansaug [°C]
tLuft,Ansaug [°C]
-5 -5
-15 -15
-25 -25
-10 -5 0 5 10 15 20 25 -10 -5 0 5 10 15 20 25
tWasser,Austritt [°C] tWasser,Austritt [°C]
Fig. 5: Extended operating range for cooling operation in extreme winter Fig. 6: Extended operating range for high outdoor temperatures in summer
conditions
Heavy-duty compressor motor
EC fans with continuously variable actuation (Please ask for order-related changing technical data!)
Option .E81 or .E82 for SL units, .E83 for HE units and additional refrigerant- Option .E54 or .E72 for SL units, .E73 for HE units
circuit-side condenser pressure control Option .R23 (on request)
Operating range up to +50 °C or 52 °C for HE units with a child-water outlet
Operating range down to -20 °C air-intake temperature based on a water-outlet temperature of +2 to +10 °C
temperature of 0 to +18 °C.
The unit must be protected from freezing at ambient temperatures less than 5°C.
For this purpose, frost protection heating for the evaporator is provided as standard on units without pumps.
For units with integrated pumps, an antifreeze heater for pipes and pumps is available under option number .M20.
The frost protection heaters are designed for outdoor temperatures down to -10 °C. In installation locations where colder outdoor temperatures may occur, the unit
must be configured with glycol.
Page 8/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
General Specifications
Table 2: General data for standard devices
Unit type GLAC #### DA2 2150 2170 2190 2192 2220 2260 2265 2270 2272
6)
Performance data (catalog) -
Refrigeration capacity 1) Qe [kW] 300 326 383 432 481 533 559 601 658
Power consumption 5) P [kW] 101 117 131 143 169 185 194 204 235
EER - Energy Efficiency Ratio 2.98 2.78 2.93 3.01 2.84 2.88 2.88 2.95 2.80
ESEER 4.26 4.26 4.29 4.32 4.25 4.28 4.28 4.31 4.30
Chilled water flow rate Ve [l/s] 14.33 15.58 18.32 20.66 22.98 25.51 26.72 28.73 31.48
Chilled water pressure
∆pe [kPa] 23.9 28.3 33.6 42.7 32.3 39.8 34.9 40.3 38.5
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.15 4.12 4.17 4.18 4.15 4.14 4.11 4.19 4.17
ηS (ERP 2016/2281) 7) [%] 163 162 164 164 163 162 162 164 164
ERP-compliant 2018
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 299 325 382 430 479 532 557 599 656
EER - Energy Efficiency Ratio 2.95 2.76 2.90 2.97 2.81 2.85 2.85 2.91 2.77
ESEER 4.13 4.12 4.14 4.13 4.11 4.11 4.13 4.14 4.14
Eurovent Class B C B B C C C B C
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 4 4 5 6 6 7 7 8 8
Total air volume flow [m³/h] 76570 76570 95690 114840 114840 133990 133990 153110 153110
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 10.56 10.56 13.33 13.33 12.50 12.50 15.83 15.83 17.50
Max. water mass flow Ve,max [l/s] 26.67 26.67 31.94 31.94 40.00 40.00 46.94 46.94 50.28
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 1000 1100 1300 1500 1700 1900 2000 2100 2300
Water charge of heat exchanger [l] 91 91 85 85 140 140 124 124 230
Evaporator connection VICTAULIC2) 5“ 5“ 5“ 5“ 6“ 6“ 6“ 6“ 6“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 44 47 55 63 69 76 80 88 94
Oil charge [kg] 30.0 30.0 30.0 30.0 44.0 41.0 38.0 38.0 38.0
Dimensions and weight
A (length) [mm] 2750 2750 4000 4000 4000 5250 5250 5250 5250
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 3160 3170 3720 3810 4610 5060 5060 5130 5520
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 9/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2 2315 2360 2390 2420 2450 2480 2481 2482
Page 10/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2 2541 2600 2602 3630 3690 3720 3721 3722
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 11/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2.SL 2150 2170 2190 2192 2220 2260 2265 2270 2272
Page 12/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2.SL 2315 2360 2390 2420 2450 2480 2481 2482
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 13/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2.SL 2541 2600 2602 3630 3690 3720 3721 3722
Page 14/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2.HE 2150 2170 2190 2192 2220 2260 2265 2270 2272
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 15/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC #### DA2.HE 2315 2360 2390 2420 2450 2480 2482 2541
Page 16/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 17/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Noise levels
Tab.5: Noise levels
Sound
Sound power
Unit type GLAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)
Standard units
2150 DA2 99 67 90 97 98 97 95 89 82 72
2170 DA2 99 67 90 97 98 97 95 89 82 72
2190 DA2 99 67 90 97 98 97 95 89 82 72
2192 DA2 100 68 91 98 99 98 96 90 83 73
2220 DA2 100 68 91 98 99 98 96 90 83 73
2260 DA2 100 68 91 98 99 98 96 90 83 73
2265 DA2 100 68 91 98 99 98 96 90 83 73
2270 DA2 100 68 91 98 99 98 96 90 83 73
2272 DA2 102 70 93 100 101 100 98 92 85 75
2315 DA2 102 69 93 100 101 100 98 92 85 75
2360 DA2 102 69 93 100 101 100 98 92 85 75
2390 DA2 103 70 94 101 102 101 99 93 86 76
2420 DA2 103 70 94 101 102 101 99 93 86 76
2450 DA2 104 71 95 102 103 102 100 94 87 77
2480 DA2 104 71 95 102 103 102 100 94 87 77
2481 DA2 104 71 95 102 103 102 100 94 87 77
2482 DA2 104 71 95 102 103 102 100 94 87 77
2541 DA2 105 72 96 103 104 103 101 95 88 78
2600 DA2 106 73 97 104 105 104 102 96 89 78
2602 DA2 106 73 97 104 105 104 102 96 89 78
3630 DA2 106 73 97 104 105 104 102 96 89 78
3690 DA2 106 73 97 104 105 104 102 96 89 78
3720 DA2 106 73 97 104 105 104 102 96 89 78
3721 DA2 106 73 97 104 105 104 102 96 89 78
3722 DA2 106 73 97 104 105 104 102 96 89 78
SL units (super-quiet model)
2150 DA2 .SL 87 55 79 77 80 84 85 76 64 57
2170 DA2 .SL 87 55 79 77 80 84 85 76 64 57
2190 DA2 .SL 88 56 80 78 81 85 86 77 65 58
2192 DA2 .SL 88 56 80 78 81 85 86 77 65 58
2220 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2260 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2265 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2270 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2272 DA2 .SL 90 57 82 81 85 87 88 76 66 58
2315 DA2 .SL 91 58 84 83 86 88 89 77 67 59
2360 DA2 .SL 91 58 84 83 86 88 89 77 67 59
2390 DA2 .SL 92 59 85 84 87 89 90 78 68 60
2420 DA2 .SL 92 59 85 84 87 89 90 78 68 60
2450 DA2 .SL 93 60 86 85 88 90 91 79 69 61
2480 DA2 .SL 93 60 86 85 88 90 91 79 69 61
2481 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2482 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2541 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2600 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2602 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3630 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3690 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3720 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3721 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3722 DA2 .SL 95 62 88 87 90 93 93 80 70 62
Page 18/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Sound
Sound power
Unit type GLAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)
Footprint
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 19/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Anti-vibration isolators
Table 7: Required anti-vibration mounts depending on unit model
Unit type GLAC… FläktGroup sales number (complete as accessory) FläktGroup individual part designation
Standard units
2150 DA2 GLZAC2150DA.I02 6 x FZ-400-51
2170 DA2 GLZAC2170DA.I02 6 x FZ-400-51
2190 DA2 GLZAC2190DA.I02 8 x FZ-400-51
2192 DA2 GLZAC2192DA.I02 8 x FZ-400-51
2220 DA2 GLZAC2220DA.I02 8 x FZ-400-51
2260 DA2 GLZAC2260DA.I02 8 x FZ-400-57
2265 DA2 GLZAC2265DA.I02 8 x FZ-400-57
2270 DA2 GLZAC2270DA.I02 8 x FZ-400-57
2272 DA2 GLZAC2272DA.I02 8 x FZ-400-57
2315 DA2 GLZAC2315DA.I02 10 x FZ-400-57
2360 DA2 GLZAC2360DA.I02 10 x FZ-400-57
2390 DA2 GLZAC2390DA.I02 12 x FZ-400-57
2420 DA2 GLZAC2420DA.I02 12 x FZ-400-57
2450 DA2 GLZAC2450DA.I02 12 x FZ-400-57
2480 DA2 GLZAC2480DA.I02 12 x FZ-400-57
2481 DA2 GLZAC2481DA.I02 14 x FZ-400-57
2482 DA2 GLZAC2482DA.I02 14 x FZ-400-57
2541 DA2 GLZAC2541DA.I02 14 x FZ-400-57
2600 DA2 GLZAC2600DA.I02 16 x FZ-400-57
2602 DA2 GLZAC2602DA.I02 16 x FZ-400-57
3630 DA2 GLZAC3630DA.I02 18 x FZ-400-57
3690 DA2 GLZAC3690DA.I02 18 x FZ-400-57
3720 DA2 GLZAC3720DA.I02 18 x FZ-400-57
3721 DA2 GLZAC3721DA.I02 20 x FZ-400-57
3722 DA2 GLZAC3722DA.I02 20 x FZ-400-57
SL units (especially quiet model)
2150 DA2 .SL GLZAC2150DA.I26 6 x FZ-400-51
2170 DA2 .SL GLZAC2170DA.I26 8 x FZ-400-51
2190 DA2 .SL GLZAC2190DA.I26 8 x FZ-400-51
2192 DA2 .SL GLZAC2192DA.I26 8 x FZ-400-51
2220 DA2 .SL GLZAC2220DA.I26 8 x FZ-400-51
2260 DA2 .SL GLZAC2260DA.I26 8 x FZ-400-57
2265 DA2 .SL GLZAC2265DA.I26 8 x FZ-400-57
2270 DA2 .SL GLZAC2270DA.I26 8 x FZ-400-57
2272 DA2 .SL GLZAC2272DA.I26 10 x FZ-400-57
2315 DA2 .SL GLZAC2315DA.I26 10 x FZ-400-57
2360 DA2 .SL GLZAC2360DA.I26 10 x FZ-400-57
2390 DA2 .SL GLZAC2390DA.I26 12 x FZ-400-57
2420 DA2 .SL GLZAC2420DA.I26 12 x FZ-400-57
2450 DA2 .SL GLZAC2450DA.I26 14 x FZ-400-57
2480 DA2 .SL GLZAC2480DA.I26 14 x FZ-400-57
2481 DA2 .SL GLZAC2481DA.I26 16 x FZ-400-57
2482 DA2 .SL GLZAC2482DA.I26 16 x FZ-400-57
2541 DA2 .SL GLZAC2541DA.I26 16 x FZ-400-57
2600 DA2 .SL GLZAC2600DA.I26 16 x FZ-400-57
2602 DA2 .SL GLZAC2602DA.I26 18 x FZ-400-57
3630 DA2 .SL GLZAC3630DA.I26 18 x FZ-400-57
3690 DA2 .SL GLZAC3690DA.I26 20 x FZ-400-57
3720 DA2 .SL GLZAC3720DA.I26 20 x FZ-400-57
3721 DA2 .SL GLZAC3721DA.I26 20 x FZ-400-57
3722 DA2 .SL GLZAC3722DA.I26 20 x FZ-400-57
Page 20/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Unit type GLAC… FläktGroup sales number (complete as accessory) FläktGroup individual part designation
NOTICE!
If the units are operated without the appropriate anti-vibration mounts, the warranty is void!
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 21/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Electrical data
Table 8: Electrical data
starter
L.R.A.
F.L.A.
F.L.A.
Power
F.L.A
F.L.I.
F.L.I.
F.L.I.
[kW]
[kW]
[kW]
With
GLAC…
S.A.
S.A.
Soft
n
[A]
[A]
[A]
[A]
supply
Standard units
2150 DA2 400/3/50 2 2x62.7 2x102.3 2x303 8.0 16 133 220 381 N/A
2170 DA2 400/3/50 2 2x71.1 2x116.2 2x350 8.0 16 150 248 440 N/A
2190 DA2 400/3/50 2 1x71.1+1x80.9 1x116.2+1x129.8 1x350+1x423 10.0 20 162 265 516 N/A
2192 DA2 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2220 DA2 400/3/50 2 2x99.9 2x163.4 2x300 12.0 24 212 350 427 N/A
2260 DA2 400/3/50 2 1x99.9+1x127.8 1x163.4+1x209 1x300+1x404 14.0 28 242 399 535 N/A
2265 DA2 400/3/50 2 1x112.3+1x127.8 1x184.7+1x209 1x360+1x404 14.0 28 254 420 552 N/A
2270 DA2 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2272 DA2 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2315 DA2 400/3/50 2 1x127.8+1x161.7 1x209+1x258 1x404+1x465 18.0 36 308 501 631 N/A
2360 DA2 400/3/50 2 2x161.7 2x258 2x465 20.0 40 343 554 674 N/A
2390 DA2 400/3/50 2 1x161.7+1x188.1 1x258+1x306 1x465+1x586 22.0 44 372 606 799 N/A
2420 DA2 400/3/50 2 2x188.1 2x306 2x586 24.0 48 400 658 830 N/A
2450 DA2 400/3/50 2 1x188.1+1x213 1x306+1x345 1x586+1x650 24.0 48 425 697 894 N/A
2480 DA2 400/3/50 2 2x213 2x345 2x650 24.0 48 450 736 917 N/A
2481 DA2 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2482 DA2 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2541 DA2 400/3/50 2 1x213+1x260 1x345+1x423 1x650+1x917 28.0 56 501 821 1191 N/A
2600 DA2 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
2602 DA2 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
3630 DA2 400/3/50 3 3x188.1 3x306 3x586 36.0 72 600 986 1051 N/A
3690 DA2 400/3/50 3 1x188.1+2x213 1x306+2x345 1x586+2x650 36.0 72 650 1064 1138 N/A
3720 DA2 400/3/50 3 3x213 3x345 3x650 36.0 72 675 1103 1160 N/A
3721 DA2 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3722 DA2 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
SL units (especially quiet model)
2150 DA2 .SL 400/3/50 2 2x62.7 2x102.3 2x303 8.0 16 133 220 381 N/A
2170 DA2 .SL 400/3/50 2 1x62.7+1x80.9 1x102.3+1x129.8 1x303+1x423 10.0 20 154 251 505 N/A
2190 DA2 .SL 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2192 DA2 .SL 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2220 DA2 .SL 400/3/50 2 1x80.9+1x112.3 1x129.8+1x184.7 1x229+1x360 14.0 28 207 341 468 N/A
2260 DA2 .SL 400/3/50 2 2x112.3 2x184.7 2x360 16.0 32 241 400 512 N/A
2265 DA2 .SL 400/3/50 2 1x112.3+1x127.8 1x184.7+1x209 1x360+1x404 16.0 32 256 424 556 N/A
2270 DA2 .SL 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2272 DA2 .SL 400/3/50 2 2x127.8 2x209 2x404 20.0 40 276 456 573 N/A
2315 DA2 .SL 400/3/50 2 1x127.8+1x161.7 1x209+1x258 1x404+1x465 20.0 40 310 505 634 N/A
2360 DA2 .SL 400/3/50 2 2x161.7 2x258 2x465 20.0 40 343 554 674 N/A
2390 DA2 .SL 400/3/50 2 1x161.7+1x188.1 1x258+1x306 1x465+1x586 22.0 44 372 606 799 N/A
2420 DA2 .SL 400/3/50 2 2x188.1 2x306 2x586 24.0 48 400 658 830 N/A
2450 DA2 .SL 400/3/50 2 1x188.1+1x213 1x306+1x345 1x586+1x650 26.0 52 427 700 898 N/A
2480 DA2 .SL 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2481 DA2 .SL 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2482 DA2 .SL 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2541 DA2 .SL 400/3/50 2 1x213+1x260 1x345+1x423 1x650+1x917 32.0 64 505 829 1199 N/A
2600 DA2 .SL 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
2602 DA2 .SL 400/3/50 2 2x260 2x423 2x917 36.0 72 556 914 1250 N/A
3630 DA2 .SL 400/3/50 3 3x188.1 3x306 3x586 36.0 72 600 986 1051 N/A
3690 DA2 .SL 400/3/50 3 1x188.1+2x213 1x306+2x345 1x586+2x650 40.0 80 654 1072 1145 N/A
3720 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3721 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3722 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
Page 22/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
starter
L.R.A.
F.L.A.
F.L.A.
Power
F.L.A
F.L.I.
F.L.I.
F.L.I.
[kW]
[kW]
[kW]
With
GLAC…
S.A.
S.A.
Soft
n
[A]
[A]
[A]
[A]
supply
All values refer to units without built-in pumps. For units with built-in pumps, the pump data must be added.
n Number of compressors
F.L.I. El. FULL LOAD INPUT
F.L.A. Operating current
L.R.A. Starting current of each compressor
S.A. Starting current of entire unit
1) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.
2) Please observe the regionally applicable standards for cable cross-sections and backup fuses. Voltage tolerance: max. 10%,
voltage imbalance
between phases: max. 3%.
3) Values are based on the total number of fans operating at maximum speed.
PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 23/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)
Terminal scheme
E F A B C D AA AA FC1 FC1 FC2 FC2 FC3 FC3 FP1 FP1 FP2 FP2
5J1
NOTICE!
For detailed planning please only use the order-related documentation. Detailed dimensional drawings can be
obtained on request from your responsible FläktGroup sales office. Specifications and technical data are subject to
regular updates. The manufacturer reserves the right to make necessary changes to information without prior
written notice.
Page 24/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..