DATA SHEET

CHILLER
GLAC 2150 – 3722 DA2(.SL/.HE)
WITH SCREW COMPRESSOR

Table of Contents

Type code ................................................................... 1


Unit description ........................................................... 2
Options and accessories ............................................ 3
Operating limits ........................................................... 7
General Specifications ................................................ 9
Noise levels .............................................................. 18
Footprint .................................................................... 19
Anti-vibration isolators .............................................. 20
Electrical data ........................................................... 22
Terminal scheme ...................................................... 24
Order related documentation .................................... 24 Fig. 1: Unit view (example version)

Type code EU

GL A C 2 150 D A 2 .SL
Operating mode

Supply voltage
Capacity stage
Compressors
Condensing

Unit model
Refrigerant
FläktGroup

Number of

Serie

GL FläktGroup Series
Air cooled
A
(outdoor installation)
C Chiller
2 2 Screw compressors
3 3 Screw compressors
Unit sizes with 2 compressors:
150, 170, 190, 192, 220, 260, 265, 270, 272,150, 170, 190,
150-
192, 220, 260, 265, 270, 272,
481
315, 360, 390, 420, 450, 480, 481*, 482, 541, 600*, 602*
Unit sizes with 3 compressors:
570-
570**, 630, 660**, 690*, 720*, 721*, 722*
722
*not for HE units / **only for HE units
D Unit series D
A Refrigerant R134a
2 400 V / 3~ / 50Hz / PE
_ Standard
.HE HE unit - high efficiency model
.SL SL unit - especially quiet model
Fig. 2: Explanation of unit type code
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Unit description

FläktGroup chillers with screw compressors


- Air-cooled for outdoor installation
- ErP 2018-compliant, comfort cooling application range
- High energy efficiency at full and part-load mode
- Refrigerant R-134a (GWP 1430)
- Capacity range approx. 300 kW to 1.7 MW cooling capacity
- 3 unit models
- Standard model (25 unit sizes)
- SL - model, noise-optimized with noise reduction of approx. 12dB(A) (25 unit sizes)
- HE - model as especially quiet model (20 unit sizes)
- Built-in double pump (redundancy) optionally possible, models with standard delivery head or increased
delivery head, as on/off pump
- 2-3 refrigerant circuits
- 2-3 semi-hermetic double-rotor compact screw compressors with a flanged oil separator
- Capacity regulation with internal slider from 40 % - 100 % with internal Vi equalization
- Electronic expansion valve
- W-shaped condenser
- Al/Al micro-channel condenser
- Optional Al/Al micro-channel condenser with epoxy polymer coating
- Optional Cu/Al condenser with polyurethane coating (instead of micro-channel)
- Optional Cu/Al condenser with protective coating of polyester resin (instead of micro-channel)
- Shell-and-tube heat exchanger as evaporator, incl. internal frost protection heater
- Direct-drive axial fans, 6-pole with contact protection against intrusion (IP54 protection)
- Fan speed control with transformer, which provides the fans with different voltages depending on the high
pressure
- EC fans are available as option (option .E81-.E83)
- Water outlet temperature -8 to +18 °C depending on outdoor temperature*)
- Air-inlet temperature from -10 °C to + 46 °C (or 48 °C for HE units) based on 7 °C water outlet
temperature*)
- Extended operating range down to -15 °C*). Air-inlet temperature with EC fans (option .E81-.E83)
- Extended operating range down to -20 °C*) Air-inlet temperature with use of EC fans and winter kit (option
.E81-.E83 and .R23-.R25)
- *) For details see operating limits diagram
- Power supply 400V / 3 / 50 Hz / PE (without N)
- Numbered connecting terminals
- Built-in phase sequence protection relay
- Automatic circuit breaker for load and control current circuit
- Pump relay for control of one on-site chilled water pump (option .E04) or two on-site chilled-water pumps
with redundancy function (option .E34) for units without built-in pumps
- Demand limit contact to reduce electrical power consumption by deactivating compressors or their capacity
steps optional (option .E23)
- FläktGroup Control Step III, black display
-

- Attention: A water filter must be installed on site directly before the evaporator(s) to protect them
from contamination and deposits of any kind. The water filter must have a mesh size of 0.9 mm or
less.
- All units of the GLAC 2150-3690 DA2(.SL) and GLAC 2150-3630DA2.HE series are Eurovent-certified.

Page 2/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Options and accessories

Accessories for controls


Option .E03 - Operation message of compressor
Floating contacts for status indication of each respective compressor.
Option .E04 - Relay for actuating an on-site chilled water pump
Option .E34 - Relay for actuating two parallel on-site chilled water pumps
To increase system availability
The pumps are activated alternately by the controller; if one pump fails, the other
pump is automatically switched on permanently.
The pumps must be fitted with non-return valves on site.
Option .E19/.E20 - Second control connection for remote monitoring and regulation.
Up to 10 units in the same controller family can be connected to an additional
remote control.
Option .E19 for remote controls up to 200 meters away
Option .E20 for remote controls up to 500 meters away
Option .E21 - Sliding setpoint via a 4-20 mA signal provided on-site
Shifting the chilled water setpoint value in a fixed range via a 4-20 mA signal
provided on-site. Changing the setpoint, e.g. during night mode operation, can
realize significant savings potential.
Option .E22 - 2nd setpoint via on-site normally open contact.
External changeover between two setpoint values set for unit by closing a field-
provided dry contact. Raising the setpoint, e.g. during night mode operation, can
realize significant savings potential.
Option .E23 - Demand limit / load limitation
Reduction of electrical power consumption by deactivating compressors or their
capacity stages (demand limit switch) by opening an on-site floating contact. This
function is used if a full electrical power supply is unavailable.
Serial card for - Unit information can be called up via the Internet and LAN
connection to a Unit connection to the building management system (BMS) using a serial
building management card.
system or for
master/slave control The following protocols are used to transmit digital and analog values:
- Readout of error messages
- Retrieval of temperature and pressure values provided by the controller
- Operating status of individual compressors
- Enabling the unit
- Setpoint shift
Option .E14 - Modbus (RS485),
Built-in Modbus interface for connection to the building management system or to
a sequencer.
Option .E15 - LonWorks® ,
Built-in LonWorks interface for connection to the building management system.
Option .E16 - BACnet via IP,
Built-in BACnet via IP interface for connection to the building management
system.
Option .E17 - BACnet via MS/TP RS485,
Built-in BACnet via MS/TP RS485 interface for connection to the building
management system.

Option .E18 - Sequencer without connection to a BMS:

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 3/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Upstream master/slave control. Up to a maximum 5 units of the FläktGroup Step


I, II, III of controller family can be used in a hydraulic circuit and connected to a
sequencer. The sequencer is supplied in a separate switch cabinet with two
temperature sensors that must be installed in a common water inlet and outlet.
Depending on the water inlet temperature, individual capacity stages or units are
switched on or off. Every unit needs a serial card of Modbus type (option .E14) in
order to communicate with the sequencer and its own chilled water pump that
also must be controlled by the chiller/heat pump.
Option .E24 - Sequencer with connection to a BMS via Modbus protocol
Option .E25 - Sequencer with integration to a BMS via LONWORKS® protocol.
Option .E26 - Sequencer with integration to a BMS via IP.
Option .E27 - Sequencer with integration to a BMS via BACnet protocol MS/TP RS485.

Electrical accessories
Option .E81 or - EC-Fans
.E82 for SL units, Use of EC fans provides the following benefits:
.E83 for HE units - Reduced power consumption in part-load mode
- Continuous speed regulation of fans
- Reduced sound level in part-load mode
- More precise control of the condensing pressure
Operating range down to -15°C air-inlet temperature
Option .E54 or .E72 - Extended operating range for higher outdoor temperatures up to 50 °C (or
for SL units, .E73 for 52 °C for HE units)
HE units Observe operating limit chart!
Attention: Changed technical data due to stronger compressor motors!
Please ask for order-related technical data!
Option .E55 or .E56 - Compensation of reactive current for compressor
for SL units, .E57 for Condensers at the electrical compressor terminals to increase the mean cos phi
HE units
Option .E58 - Heating for switch cabinet
Electric heating of switch cabinet ensures trouble-free operation of all electric
components throughout entire year and prevents build-up of condensation inside
switch cabinets in areas with relatively high air humidity.
Option .E74 - Quick start after power failure (UPS for controller on-site)
Time for restarting of individual compressors and reaching maximum capacity is
reduced to a minimum. The mandatory safety times of compressors are
considered. Inquire with the sales office on the changes in the starting time.
These accessories require an on-site continuous power supply of controller.
Option .E75 - Quick start after power failure (UPS for controller in the unit)
Time for restarting of individual compressors and reaching maximum capacity is
reduced to a minimum. The mandatory safety times of compressors are
considered. Inquire with the sales office on the changes in the starting time. For
the period of voltage failure the controller operates using uninterruptible power
source and can ensure quick start of the unit. For dimensioning the pre-mounted
uninterruptible power source it is required to specify the maximum duration of the
voltage failure when ordering the unit.
Option .E76 - Double power supply with automatic switch over
It is also possible to enable an alterative power supply for the unit, e.g. by using a
second supply line from an emergency power generator. When a standard power
supply fails, the unit automatically switches to an alternative power supply. The
unit switches back to a standard power supply, as soon as the latter is restored.
Option .E77 - Double power supply with motorized remote switch over (supply line from
emergency power generator)

Page 4/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

It is also possible to enable an alterative power supply for the unit, e.g. by using a
second supply line from an emergency power generator. This type is a motorized
switch-over which is actuated using a remote contact of an additional power
supply.
Option .E78 - Switch cabinet lighting
To facilitate unit servicing in bad visibility conditions.

Installation of accessories
Option .I02 or - Rubber isolator
.I26 for SL units Anti-vibration isolators with rubber elements to minimize vibration transmission
.I59 for HE units (supplied separately).
The on-site installation of suitable anti-vibration mounts is a prerequisite for
warranty claims!
Option .I10 - Flow switch
With paddle for installation in the hydraulic circuit at the chilled-water outlet
(supplied separately). The on-site installation and wiring of the flow switch is a
prerequisite for warranty claims!
Option .I08 - Chilled-water connections with flanges
Depending on the unit type either mounted flanges or separate flange adaptor kit.
Only in combination with external water connections when available.
Option .I77 - Water connection of evaporator on the right side
Water connections of the evaporator are located on the right side of unit, facing
(standard pre- the switch cabinet.
selection)
Option .I78 - Water connection of evaporator on the left side
Water connections of the evaporator are located on the left side of unit, facing the
switch cabinet.
Option .I19 for - Extra sound attenuation for compressor section
standard units or Sound-attenuated hood for individual compressors or entire compressor section
I.66 for HE units for reduction of sound power level by -2dB(A).
Depending on the model, unit weight can change.
Option .I05 or - Protection grille for air-cooled heat exchanger
.I65 for SL units Additional protection grille to prevent access to components installed under the
.I61 for HE units air-cooled heat exchangers
Option .I55 or - Anti-corrosion coating for microchannel heat exchangers (MCHX)
.I56 for SL units, 100 % epoxy-polymer coating using e-coating method for the entire air-cooled
I57 for HE units microchannel heat exchanger for protection against corrosion, UV radiation, and
to ensure enhanced weather-proof features in conditions with average air
contamination and application in proximity to sea water with average salt content.
Option .I03 or - Cu/Al heat exchanger with corrosion-resistant coating for the fins (instead
.I23 for SL units, of the microchannel heat exchanger)
I52 for HE units Corrosion-resistant coating for fins of Cu/Al heat exchanger. The use of chemical
cleaning methods and protective-paint coating made of polyester resin ensures
the following characteristics:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
1000 hours
- UV durability
Attention: Change in refrigerant charge volume and unit weight

Option .I18 or - Cu/Al heat exchanger with polyurethane coating (instead of microchannel
.I22 for SL units, heat exchanger)

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 5/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

I51 for HE units Cu/Al heat exchanger with polyurethane paint. The entire heat exchanger
receives protective coating using polyurethane paint, so that the following
qualities are safeguarded:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
4000 hours
- UV durability
Attention: Change in refrigerant charge volume and unit weight

Mechanics accessories
Option .M20 - Frost protection heating for pipework and pump
to protect against freezing in standby mode down to -10 °C outdoor temperature
For installation locations where the outdoor temperature can fall below
-10 °C, the unit must be configured with a water-glycol mixture.
Pumps - Refer to separate pump data information sheet
Refrigeration circuit accessories
Option .R13 - LP and HP Pressure Gauges
Refrigerant gauge for high and low pressure side for reading off current operating
pressures.
Option .R19 - Safety valve in double configuration for high and low-pressure side
Two safety valves are connected via a changeover valve on the high and low-
pressure side each. By using a changeover valve a trouble-free and fast
replacement of safety valves without refrigerant loss is possible for maintenance
and service jobs.
Option .R02 - Shut-off valves for compressor suction side
Service shut-off valve assembled for fast and easy maintenance.
Option .R23 or - Condensing pressure control for the operation at very low air-inlet
.R24 für SL units, temperatures
.R25 for HE units Chilled-water side condenser-pressure control to ensure operation at air-inlet
temperature down to -20 °C and windy operation site.
Refer to the operating limit charts for the exact operating range.
Other accessories
Option .O10 - Glycol operation below 0°C
Option for chiller fitted with screw compressors at chilled-water outlet temperature
below 0°C, operating conditions must be specified in the order.
Option .O24 or .O25 - Increased thermal insulation of evaporator (and possibly pipework and
for units with pumps pump)
Double-layer heat insulation of evaporator (and possibly pump and pipework to
prevent condensate water in environments with especially high relative humidity.
Especially recommended for media temperatures below 0°C.
Option .O27 - Refrigerant leak detection (Alarm)
The compressor section is monitored for leaking medium. A refrigerant leakage is
triggered by an error message from the controller.
Option .O28 - Refrigerant leak detection (compressor switch off)
The compressor section is monitored for leaking medium. In the event of
refrigerant leakage, the compressor is switched off and an error message is
triggered by the controller.
Option .O13 or - Unit stabilization for shipping
.O26 for SL units, Additionally reinforced frame construction to stabilize unit during shipping.
.O14 for HE units

Page 6/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Option .O11 for - Packing of the unit with nylon cover


standard and SL units The unit is shrink-wrapped in nylon foil for transport and storage to protect it from
or .O15 for HE units weather and dirt.

Operating limits
On the water side, the operating limits according to Table 1, and on the air and water side, the limits of the selected
options according to the following chart must be observed.
Table1: Operating limits of water (glycol) circuit

Min Max
Water inlet [°C] -5 26

Water outlet [°C] -8 18 °C or 20 °C with option .E54, .E72 or .E73)

D T at water outlet temp. > 5 °C [K] 4 8

D T at water outlet temp. ≤ 5 °C [K] 3 5

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 7/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

55 55

45 45

35 35

25 25

15 15

5 5

tLuft,Ansaug [°C]
tLuft,Ansaug [°C]

-5 -5

-15 -15

-25 -25
-10 -5 0 5 10 15 20 25 -10 -5 0 5 10 15 20 25
tWasser,Austritt [°C] tWasser,Austritt [°C]
Fig. 3: Standard operating range Fig. 4: Extended operating range for cooling operation in winter

Standard configuration AC fans with autotransformer EC fans with continuously variable actuation
Option .E81 or .E82 for SL units, .E83 for HE units

Operating range down to -10 °C air-intake temperature based on a water-outlet Operating range down to -15 °C air-intake temperature based on a water-outlet
temperature of +5 to +18 °C. temperature of -5 to +18 °C.

55 55

45 45

35 35

25 25

15 15

5 5
tLuft,Ansaug [°C]
tLuft,Ansaug [°C]

-5 -5

-15 -15

-25 -25
-10 -5 0 5 10 15 20 25 -10 -5 0 5 10 15 20 25
tWasser,Austritt [°C] tWasser,Austritt [°C]
Fig. 5: Extended operating range for cooling operation in extreme winter Fig. 6: Extended operating range for high outdoor temperatures in summer
conditions
Heavy-duty compressor motor
EC fans with continuously variable actuation (Please ask for order-related changing technical data!)
Option .E81 or .E82 for SL units, .E83 for HE units and additional refrigerant- Option .E54 or .E72 for SL units, .E73 for HE units
circuit-side condenser pressure control Option .R23 (on request)
Operating range up to +50 °C or 52 °C for HE units with a child-water outlet
Operating range down to -20 °C air-intake temperature based on a water-outlet temperature of +2 to +10 °C
temperature of 0 to +18 °C.

Notices for all diagrams


The unit is prepared for the selected operating range during the end-of-line test. Please attach the technical order information to the order.
For operational reasons, water at evaporator outlet temperatures below 5°C must be protected from freezing by adding glycol.
FläktGroup recommends to use at least 30% ethylene glycol.

The unit must be protected from freezing at ambient temperatures less than 5°C.
For this purpose, frost protection heating for the evaporator is provided as standard on units without pumps.
For units with integrated pumps, an antifreeze heater for pipes and pumps is available under option number .M20.
The frost protection heaters are designed for outdoor temperatures down to -10 °C. In installation locations where colder outdoor temperatures may occur, the unit
must be configured with glycol.

Page 8/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

General Specifications
Table 2: General data for standard devices

Unit type GLAC #### DA2 2150 2170 2190 2192 2220 2260 2265 2270 2272
6)
Performance data (catalog) -
Refrigeration capacity 1) Qe [kW] 300 326 383 432 481 533 559 601 658
Power consumption 5) P [kW] 101 117 131 143 169 185 194 204 235
EER - Energy Efficiency Ratio 2.98 2.78 2.93 3.01 2.84 2.88 2.88 2.95 2.80
ESEER 4.26 4.26 4.29 4.32 4.25 4.28 4.28 4.31 4.30
Chilled water flow rate Ve [l/s] 14.33 15.58 18.32 20.66 22.98 25.51 26.72 28.73 31.48
Chilled water pressure
∆pe [kPa] 23.9 28.3 33.6 42.7 32.3 39.8 34.9 40.3 38.5
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.15 4.12 4.17 4.18 4.15 4.14 4.11 4.19 4.17
ηS (ERP 2016/2281) 7) [%] 163 162 164 164 163 162 162 164 164
ERP-compliant 2018         
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 299 325 382 430 479 532 557 599 656
EER - Energy Efficiency Ratio 2.95 2.76 2.90 2.97 2.81 2.85 2.85 2.91 2.77
ESEER 4.13 4.12 4.14 4.13 4.11 4.11 4.13 4.14 4.14
Eurovent Class B C B B C C C B C
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 4 4 5 6 6 7 7 8 8
Total air volume flow [m³/h] 76570 76570 95690 114840 114840 133990 133990 153110 153110
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 10.56 10.56 13.33 13.33 12.50 12.50 15.83 15.83 17.50
Max. water mass flow Ve,max [l/s] 26.67 26.67 31.94 31.94 40.00 40.00 46.94 46.94 50.28
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 1000 1100 1300 1500 1700 1900 2000 2100 2300
Water charge of heat exchanger [l] 91 91 85 85 140 140 124 124 230
Evaporator connection VICTAULIC2) 5“ 5“ 5“ 5“ 6“ 6“ 6“ 6“ 6“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 44 47 55 63 69 76 80 88 94
Oil charge [kg] 30.0 30.0 30.0 30.0 44.0 41.0 38.0 38.0 38.0
Dimensions and weight
A (length) [mm] 2750 2750 4000 4000 4000 5250 5250 5250 5250
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 3160 3170 3720 3810 4610 5060 5060 5130 5520
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 9/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 2: General data for standard units (continued)

Unit type GLAC #### DA2 2315 2360 2390 2420 2450 2480 2481 2482

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 725 803 872 926 982 1021 1059 1146
Power consumption 5) P [kW] 250 267 290 310 337 363 348 389
EER - Energy Efficiency Ratio 2.90 3.00 3.01 2.99 2.92 2.82 3.04 2.95
ESEER 4.29 4.26 4.26 4.29 4.27 4.27 4.28 4.31
Chilled water flow rate Ve [l/s] 34.69 38.39 41.70 44.31 46.98 48.82 50.65 54.81
Chilled water pressure
∆pe [kPa] 46.8 40.9 42.6 48.1 41.8 45.1 48.5 53.3
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.16 4.17 4.17 4.17 4.18 4.15 4.18 4.18
ηS (ERP 2016/2281) 7) [%] 163 164 164 164 164 163 164 164
ERP-compliant 2018        
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 723 800 869 923 979 1018 1055 1142
EER - Energy Efficiency Ratio 2.86 2.97 2.97 2.95 2.88 2.78 3.00 2.90
ESEER 4.11 4.10 4.10 4.11 4.11 4.10 4.11 4.12
Eurovent Class C B B B C C B B
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 9 10 11 12 12 12 14 14
Total air volume flow [m³/h] 172260 191410 210530 229680 229680 229680 267950 267950
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 17.50 19.17 19.17 19.17 25.00 25.00 25.00 25.00
Max. water mass flow Ve,max [l/s] 50.28 54.44 56.11 56.11 63.89 63.89 63.89 68.89
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 2500 2800 3100 3200 3400 3600 3700 4000
Water charge of heat exchanger [l] 230 220 210 210 275 275 275 261
Evaporator connection VICTAULIC2) 6“ 6“ 6“ 6“ 8“ 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 104 117 127 135 140 146 151 164
Oil charge [kg] 49.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
Dimensions and weight
A (length) [mm] 6500 6500 7750 7750 7750 7750 9000 9000
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 6450 6940 7440 7560 7790 7820 8250 8370
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

Page 10/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 2: General data for standard units (continued))

Unit type GLAC #### DA2 2541 2600 2602 3630 3690 3720 3721 3722

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 1176 1239 1303 1401 1481 1547 1654 1710
Power consumption 5) P [kW] 415 426 466 466 514 547 570 594
EER - Energy Efficiency Ratio 2.83 2.91 2.80 3.00 2.88 2.83 2.90 2.88
ESEER 4.27 4.27 4.31 4.27 4.29 4.25 4.28 4.32
Chilled water flow rate Ve [l/s] 56.25 59.26 62.29 67.01 70.81 74.00 79.11 81.79
Chilled water pressure
∆pe [kPa] 42.2 46.9 51.8 45.4 50.7 39.0 44.6 51.2
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.18 4.17 4.17 4.21 4.19 4.18 4.21 4.21
ηS (ERP 2016/2281) 7) [%] 164 164 164 166 165 164 165 166
ERP-compliant 2018        
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 1172 1235 1298 1397 1476 1543 1649 1704
EER - Energy Efficiency Ratio 2.80 2.87 2.76 2.97 2.85 2.80 2.87 2.84
ESEER 4.12 4.11 4.12 4.11 4.11 4.11 4.12 4.14
Eurovent Class C C C w C C C C
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 14 16 16 18 18 18 20 20
Total air volume flow [m³/h] 267950 306250 306250 344520 344520 344520 382790 382790
Compressor Double rotor screw compressor
Number of compressors 2 2 2 3 3 3 3 3
Number of refrigeration circuits 2 2 2 3 3 3 3 3
Minimum part-load speed [%] 20 20 20 13 13 13 13 13
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 31.11 31.11 31.11 41.67 41.67 41.67 41.67 41.67
Max. water mass flow Ve,max [l/s] 100.83 100.83 100.83 102.78 102.78 97.22 97.22 100.00
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 4100 4300 4600 4900 5200 5400 5800 6000
Water charge of heat exchanger [l] 310 310 310 575 575 550 550 500
Evaporator connection VICTAULIC2) 8“ 8“ 8“ 8“ 8“ 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 168 181 186 205 212 221 237 250
Oil charge [kg] 62.0 64.0 64.0 90.0 90.0 90.0 90.0 90.0
Dimensions and weight
A (length) [mm] 9150 10400 10400 11650 11650 11650 12900 12900
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 8660 9200 9310 11880 11940 11950 12490 12570
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 11/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 3: General data for SL units (especially quiet model)

Unit type GLAC #### DA2.SL 2150 2170 2190 2192 2220 2260 2265 2270 2272

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 289 333 382 419 476 519 556 578 663
Power consumption 5) P [kW] 101 113 126 146 161 175 192 207 223
EER - Energy Efficiency Ratio 2.85 2.95 3.03 2.87 2.95 2.97 2.90 2.79 2.98
ESEER 4.23 4.25 4.28 4.30 4.27 4.28 4.28 4.26 4.26
Chilled water flow rate Ve [l/s] 13.80 15.94 18.25 20.02 22.76 24.80 26.59 27.66 31.72
Chilled water pressure
∆pe [kPa] 22.2 29.6 33.3 40.1 31.7 37.6 34.5 37.4 39.1
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.1 4.13 4.18 4.16 4.17 4.12 4.14 4.14 4.17
ηS (ERP 2016/2281) 7) [%] 161 162 164 163 164 162 162 163 164
ERP-compliant 2018         
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 288 332 380 417 475 517 554 577 661
EER - Energy Efficiency Ratio 2.82 2.92 3.00 2.83 2.92 2.93 2.87 2.76 2.94
ESEER 4.10 4.11 4.13 4.13 4.13 4.12 4.13 4.11 4.11
Eurovent Class C B B C B B C C B
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 4 5 6 6 7 8 8 8 10
Total air volume flow [m³/h] 69160 86440 103720 103720 121000 138280 138280 138280 172870
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 9.00 9.00 7.72 7.72 4.72 4.72 3.77 3.77 3.00
Max. water mass flow Ve,max [l/s] 10.56 10.56 13.33 13.33 12.50 12.50 15.83 15.83 17.50
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 1000 1100 1300 1500 1700 1900 2000 2100 2300
Water charge of heat exchanger [l] 91.0 91.0 85.0 85.0 140 140 124 124 230
Evaporator connection VICTAULIC2) 5“ 5“ 5“ 5“ 6“ 6“ 6“ 6“ 6“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 44 51 58 63 72 79 84 88 101
Oil charge [kg] 30.0 30.0 30.0 30.0 34.0 38.0 38.0 38.0 38.0
Dimensions and weight
A (length) [mm] 2750 4000 4000 4000 5250 5250 5250 5250 6500
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 3420 4160 4230 4230 5200 5560 5580 5620 6610
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

Page 12/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 3: General data for SL units (especially quiet model) (continued)

Unit type GLAC #### DA2.SL 2315 2360 2390 2420 2450 2480 2481 2482

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 717 771 839 893 965 1021 1052 1137
Power consumption 5) P [kW] 247 272 295 315 335 353 341 381
EER - Energy Efficiency Ratio 2.90 2.84 2.85 2.83 2.88 2.89 3.09 2.99
ESEER 4.28 4.26 4.27 4.29 4.27 4.28 4.29 4.29
Chilled water flow rate Ve [l/s] 34.27 36.86 40.11 42.70 46.14 48.85 50.30 54.38
Chilled water pressure
∆pe [kPa] 45.7 37.7 39.4 44.7 40.3 45.2 47.9 52.5
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.16 4.18 4.18 4.16 4.18 4.18 4.2 4.19
ηS (ERP 2016/2281) 7) [%] 163 164 164 164 164 164 165 165
ERP-compliant 2018        
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 714 769 836 890 962 1018 1048 1133
EER - Energy Efficiency Ratio 2.87 2.81 2.82 2.80 2.84 2.85 3.04 2.94
ESEER 4.10 4.11 4.12 4.12 4.12 4.11 4.11 4.11
Eurovent Class C C C C C C B B
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 10 10 11 12 13 14 16 16
Total air volume flow [m³/h] 172870 172870 190150 207430 224710 241990 276590 276590
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 3.00 2.14 1.89 1.89 1.46 1.46 1.46 1.37
Max. water mass flow Ve,max [l/s] 17.50 19.17 19.17 19.17 25.00 25.00 25.00 25.00
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 2500 2800 3100 3200 3400 3600 3700 4000
Water charge of heat exchanger [l] 230 220 210 210 275 275 275 261
Evaporator connection VICTAULIC2) 6“ 6“ 6“ 6“ 8“ 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 109 117 127 135 146 155 159 172
Oil charge [kg] 49.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
Dimensions and weight
A (length) [mm] 6500 6500 7750 7750 9000 9000 10250 10250
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 7080 7550 8090 8200 9000 8870 9360 9470
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 13/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 3: General data for SL units (especially quiet model) (continued)

Unit type GLAC #### DA2.SL 2541 2600 2602 3630 3690 3720 3721 3722

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 1169 1194 1289 1350 1463 1530 1595 1649
Power consumption 5) P [kW] 407 433 459 474 510 540 583 609
EER - Energy Efficiency Ratio 2.87 2.76 2.81 2.85 2.87 2.83 2.74 2.71
ESEER 4.26 4.26 4.30 4.27 4.29 4.25 4.25 4.27
Chilled water flow rate Ve [l/s] 55.91 57.11 61.64 64.56 69.97 73.16 76.27 78.86
Chilled water pressure
∆pe [kPa] 41.7 43.5 50.7 42.1 49.5 38.2 41.5 47.6
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.2 4.15 4.18 4.2 4.19 4.21 4.17 4.16
ηS (ERP 2016/2281) 7) [%] 165 163 164 165 165 165 164 163
ERP-compliant 2018        
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 1166 1190 1285 1346 1458 1526 1590 1644
EER - Energy Efficiency Ratio 2.84 2.73 2.77 2.81 2.83 2.80 2.71 2.67
ESEER 4.11 4.10 4.12 4.11 4.11 4.11 4.11 4.10
Eurovent Class C C C C C C C D
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 16 16 18 18 20 20 20 20
Total air volume flow [m³/h] 276590 276590 311150 311150 345710 345710 345710 345710
Compressor Double rotor screw compressor
Number of compressors 2 2 2 3 3 3 3 3
Number of refrigeration circuits 2 2 2 3 3 3 3 3
Minimum part-load speed [%] 20 20 20 13 13 13 13 13
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 1.03 1.03 1.03 0.78 0.78 0.55 0.55 0.59
Max. water mass flow Ve,max [l/s] 31.11 31.11 31.11 41.67 41.67 41.67 41.67 41.67
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 4100 4300 4600 4900 5200 5400 5800 6000
Water charge of heat exchanger [l] 310 310 310 575 575 550 550 500
Evaporator connection VICTAULIC2) 8“ 8“ 8“ 8“ 8“ 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 177 181 195 205 222 232 242 250
Oil charge [kg] 62.0 64.0 64.0 90.0 90.0 90.0 90.0 90.0
Dimensions and weight
A (length) [mm] 10400 10400 11650 11650 12900 12900 12900 12900
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 9780 9860 10420 12810 13340 13340 13420 13500
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

Page 14/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 4: General data for HE units (especially efficient model))

Unit type GLAC #### DA2.HE 2150 2170 2190 2192 2220 2260 2265 2270 2272

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 302 350 395 462 513 551 591 629 684
Power consumption 5) P [kW] 95.4 109 125 144 160 175 184 196 218
EER - Energy Efficiency Ratio 3.17 3.22 3.16 3.21 3.21 3.15 3.20 3.21 3.14
ESEER 4.38 4.39 4.40 4.37 4.40 4.39 4.40 4.39 4.41
Chilled water flow rate Ve [l/s] 14.46 16.72 18.89 22.08 24.54 26.37 28.25 30.07 32.70
Chilled water pressure
∆pe [kPa] 24.4 32.6 35.7 29.8 36.8 34.0 39.0 44.2 41.6
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.3 4.29 4.29 4.3 4.31 4.25 4.26 4.28 4.3
ηS (ERP 2016/2281) 7) [%] 169 169 168 169 169 167 167 168 169
ERP-compliant 2018         
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 302 349 394 460 512 550 589 627 682
EER - Energy Efficiency Ratio 3.14 3.18 3.12 3.17 3.17 3.12 3.16 3.16 3.10
ESEER 4.23 4.23 4.23 4.23 4.24 4.25 4.24 4.21 4.24
Eurovent Class A A A A A A A A A
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 5 6 6 7 8 8 9 10 10
Total air volume flow [m³/h] 95690 114840 114840 133990 153110 153110 172260 191410 191410
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 9.00 9.00 7.72 4.72 4.72 3.77 3.77 3.77 3.00
Max. water mass flow Ve,max [l/s] 10.56 10.56 13.33 12.50 12.50 15.83 15.83 15.83 17.50
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 1100 1200 1400 1600 1800 1900 2100 2200 2400
Water charge of heat exchanger [l] 91 91 85 140 140 124 124 124 230
Evaporator connection VICTAULIC2) 5“ 5“ 5“ 6“ 6“ 6“ 6“ 6“ 6“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 48 54 58 68 79 81 87 92 100
Oil charge [kg] 24.5 30.0 30.0 37.0 44.0 38.0 38.0 38.0 38.0
Dimensions and weight
A (length) [mm] 4000 4000 4000 5250 5250 5250 6500 6500 6500
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 3660 3720 3760 4660 5040 5090 5830 5690 6110
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 15/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 4: General data for HE units (especially efficient model) (continued)

Unit type GLAC #### DA2.HE 2315 2360 2390 2420 2450 2480 2482 2541

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 766 838 905 956 1031 1098 1177 1236
Power consumption 5) P [kW] 242 260 280 299 320 339 375 391
EER - Energy Efficiency Ratio 3.17 3.22 3.24 3.19 3.22 3.23 3.14 3.16
ESEER 4.39 4.39 4.40 4.42 4.40 4.43 4.40 4.41
Chilled water flow rate Ve [l/s] 36.64 40.06 43.26 45.72 49.29 52.53 56.31 59.13
Chilled water pressure
∆pe [kPa] 37.2 44.5 45.8 51.2 46.0 50.1 42.3 46.7
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.33 4.3 4.32 4.31 4.31 4.33 4.33 4.34
ηS (ERP 2016/2281) 7) [%] 170 169 170 169 169 170 170 171
ERP-compliant 2018        
Application Comfort Comfort Comfort Comfort Comfort Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 764 835 902 952 1028 1094 1173 1232
EER - Energy Efficiency Ratio 3.13 3.18 3.19 3.14 3.18 3.19 3.10 3.12
ESEER 4.23 4.21 4.22 4.22 4.22 4.24 4.24 4.24
Eurovent Class A A A A A A A A
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 11 12 13 14 15 16 16 18
Total air volume flow [m³/h] 210530 229680 248830 267950 287100 306250 306250 344520
Compressor Double rotor screw compressor
Number of compressors 2 2 2 2 2 2 2 2
Number of refrigeration circuits 2 2 2 2 2 2 2 2
Minimum part-load speed [%] 20 20 20 20 20 20 20 20
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 2.14 2.14 1.89 1.89 1.46 1.40 1.03 1.03
Max. water mass flow Ve,max [l/s] 19.17 19.17 19.17 19.17 25.00 25.00 31.11 31.11
Max. working pressure pmax [bar] 10 10 10 10 10 10 10 10
Min. chilled water system content [l] 2700 2900 3200 3300 3600 3800 4100 4300
Water charge of heat exchanger [l] 220 220 210 210 275 269 310 310
Evaporator connection VICTAULIC2) 6“ 6“ 6“ 6“ 8“ 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 113 123 133 141 151 161 173 182
Oil charge [kg] 49.0 60.0 60.0 60.0 60.0 60.0 60.0 62.0
Dimensions and weight
A (length) [mm] 7750 7750 9000 9000 10400 10400 10400 11650
B (width) [mm] 2260 2260 2260 2260 2260 2260 2260 2260
H (height) [mm] 2500 2500 2500 2500 2500 2500 2500 2500
Weight 4.5) [kg] 6970 7440 7890 8000 8700 8780 9040 10120
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

Page 16/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 4: General data for HE units (especially efficient model) (continued)

Unit type GLAC #### DA2.HE 3570 3630 3660

Performance data (catalog) - 6)


Refrigeration capacity 1) Qe [kW] 1342 1460 1521
Power consumption 5) P [kW] 414 459 485
EER - Energy Efficiency Ratio 3.24 3.18 3.14
ESEER 4.35 4.37 4.39
Chilled water flow rate Ve [l/s] 64.17 69.81 72.73
Chilled water pressure
∆pe [kPa] 41.6 34.7 37.7
drop
ERP conformity
SEER (ERP 2016/2281)7) 4.33 4.34 4.36
ηS (ERP 2016/2281) 7) [%] 170 171 172
ERP-compliant 2018   
Application Comfort Comfort Comfort
Performance values according to EN14511-3:2011
Refrigeration capacity 1) Qe [kW] 1338 1456 1517
EER - Energy Efficiency Ratio 3.20 3.15 3.10
ESEER 4.20 4.24 4.24
Eurovent Class A A A
Controls Step III with black display
Fans Axial Fans
Fan Quantity n 19 20 20
Total air volume flow [m³/h] 363640 382790 382790
Compressor Double rotor screw compressor
Number of compressors 3 3 3
Number of refrigeration circuits 3 3 3
Minimum part-load speed [%] 13 13 13
Evaporator (cold-water side)
Min. water mass flow Ve,min [l/s] 0.78 0.55 0.55
Max. water mass flow Ve,max [l/s] 41.67 41.67 50.00
Max. working pressure pmax [bar] 10 10 10
Min. chilled water system content [l] 4700 5100 5300
Water charge of heat exchanger [l] 575 550 500
Evaporator connection VICTAULIC2) 8“ 8“ 8“
Refrigeration circuit charge
Refrigerant R134a 3,4) [kg] 197 226 224
Oil charge [kg] 90.0 90.0 90.0
Dimensions and weight
A (length) [mm] 12900 12900 12900
B (width) [mm] 2260 2260 2260
H (height) [mm] 2500 2500 2500
Weight 4.5) [kg] 12160 12330 12640
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7°C; ambient temperature 35°C; values partially rounded off
2) Victaulic coupling supplied separately, with transition to welding end (units without pumps)
3) For exact refrigerant charge volume, refer to the unit identification plate.
4) Applies to units with micro-channel heat exchanger as condenser
5) based on the entire unit (without pumps)
6) Data apply to input parameters as described under 1) and without glycol; conversion required when using glycol
7) Applies to units in standard configuration without pumps

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 17/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Noise levels
Tab.5: Noise levels

Total sound level Octave band [Hz]

Sound power level [dB]

Sound
Sound power
Unit type GLAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)

Standard units
2150 DA2 99 67 90 97 98 97 95 89 82 72
2170 DA2 99 67 90 97 98 97 95 89 82 72
2190 DA2 99 67 90 97 98 97 95 89 82 72
2192 DA2 100 68 91 98 99 98 96 90 83 73
2220 DA2 100 68 91 98 99 98 96 90 83 73
2260 DA2 100 68 91 98 99 98 96 90 83 73
2265 DA2 100 68 91 98 99 98 96 90 83 73
2270 DA2 100 68 91 98 99 98 96 90 83 73
2272 DA2 102 70 93 100 101 100 98 92 85 75
2315 DA2 102 69 93 100 101 100 98 92 85 75
2360 DA2 102 69 93 100 101 100 98 92 85 75
2390 DA2 103 70 94 101 102 101 99 93 86 76
2420 DA2 103 70 94 101 102 101 99 93 86 76
2450 DA2 104 71 95 102 103 102 100 94 87 77
2480 DA2 104 71 95 102 103 102 100 94 87 77
2481 DA2 104 71 95 102 103 102 100 94 87 77
2482 DA2 104 71 95 102 103 102 100 94 87 77
2541 DA2 105 72 96 103 104 103 101 95 88 78
2600 DA2 106 73 97 104 105 104 102 96 89 78
2602 DA2 106 73 97 104 105 104 102 96 89 78
3630 DA2 106 73 97 104 105 104 102 96 89 78
3690 DA2 106 73 97 104 105 104 102 96 89 78
3720 DA2 106 73 97 104 105 104 102 96 89 78
3721 DA2 106 73 97 104 105 104 102 96 89 78
3722 DA2 106 73 97 104 105 104 102 96 89 78
SL units (super-quiet model)
2150 DA2 .SL 87 55 79 77 80 84 85 76 64 57
2170 DA2 .SL 87 55 79 77 80 84 85 76 64 57
2190 DA2 .SL 88 56 80 78 81 85 86 77 65 58
2192 DA2 .SL 88 56 80 78 81 85 86 77 65 58
2220 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2260 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2265 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2270 DA2 .SL 89 57 81 79 82 86 87 78 66 59
2272 DA2 .SL 90 57 82 81 85 87 88 76 66 58
2315 DA2 .SL 91 58 84 83 86 88 89 77 67 59
2360 DA2 .SL 91 58 84 83 86 88 89 77 67 59
2390 DA2 .SL 92 59 85 84 87 89 90 78 68 60
2420 DA2 .SL 92 59 85 84 87 89 90 78 68 60
2450 DA2 .SL 93 60 86 85 88 90 91 79 69 61
2480 DA2 .SL 93 60 86 85 88 90 91 79 69 61
2481 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2482 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2541 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2600 DA2 .SL 94 61 86 85 89 92 92 79 69 61
2602 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3630 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3690 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3720 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3721 DA2 .SL 94 61 86 85 89 92 92 79 69 61
3722 DA2 .SL 95 62 88 87 90 93 93 80 70 62

Continued and footnotes on next page

Page 18/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 5: Noise levels (continued)

Total sound level Octave band [Hz]

Sound power level [dB]

Sound
Sound power
Unit type GLAC pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)

HE units (especially efficient model)


2150 DA2 .HE 98 66 89 96 97 96 94 88 81 71
2170 DA2 .HE 98 66 89 96 97 96 94 88 81 71
2190 DA2 .HE 99 67 90 97 98 97 95 89 82 72
2192 DA2 .HE 99 67 90 97 98 97 95 89 82 72
2220 DA2 .HE 100 68 91 98 99 98 96 90 83 73
2260 DA2 .HE 100 68 91 98 99 98 96 90 83 73
2265 DA2 .HE 101 68 92 99 100 99 97 91 84 74
2270 DA2 .HE 101 68 92 99 100 99 97 91 84 74
2272 DA2 .HE 101 68 92 99 100 99 97 91 84 74
2315 DA2 .HE 101 68 92 99 100 99 97 91 84 74
2360 DA2 .HE 102 69 93 100 101 100 98 92 85 75
2390 DA2 .HE 102 69 93 100 101 100 98 92 85 75
2420 DA2 .HE 103 70 94 101 102 101 99 93 86 76
2450 DA2 .HE 103 70 94 101 102 101 99 93 86 76
2480 DA2 .HE 103 70 94 101 102 101 99 93 86 76
2482 DA2 .HE 103 70 94 101 102 101 99 93 86 76
2541 DA2 .HE 104 71 95 102 103 102 100 94 87 77
3570 DA2 .HE 104 71 95 102 103 102 100 94 87 77
3630 DA2 .HE 104 71 95 102 103 102 100 94 87 77
3660 DA2 .HE 104 71 95 102 103 102 100 94 87 77
Data on operating conditions
Data applies only to water inlet and outlet temperature of 12 °C/ 7 C° and ambient air temperatures of 35 °C. All specifications apply to units without pumps.
1) Specification of sound power (EUROVENT certified value)
Manufacturer determines the sound power value for Eurovent-certified units in accordance with ISO 9614 standard.
This certification expressly refers to sound power in dB(A), which thus constitutes obligatory data in this case.
2) Specification of sound pressure level
The sound pressure level is determined according to enveloping surface method with a reflecting plane (Q = 2) The distance of
10 m refers to the external dimensions of the unit. For sound pressure level the following corrections can be used:
Sound pressure level at 5 m: +5 dB as compared to sound pressure level at 10 meters distance.
Sound pressure level at 15 m: -3 dB as compared to sound pressure level at 10 meters distance.
Sound pressure level at 20 m: -6 dB as compared to sound pressure level at 10 meters distance.
Only an externally engaged acoustics engineer should carry out specific sound level calculations to be valid for your installation site.

Footprint

CLEARANCE FOR AIR SUPPLY!


Unit must be able to freely discharge air upwards. Air short-circuiting must be
impossible! The necessary clearances near and over the unit may exceed the
depicted maintenance clearance by many times.
Tab.6: Clearances

All unit sizes R1 R2 R3 R4

Required clearances [mm] 1500 2300 1500 1500

Fig. 7: Required clearances (example)

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 19/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Anti-vibration isolators
Table 7: Required anti-vibration mounts depending on unit model

Unit type GLAC… FläktGroup sales number (complete as accessory) FläktGroup individual part designation

Standard units
2150 DA2 GLZAC2150DA.I02 6 x FZ-400-51
2170 DA2 GLZAC2170DA.I02 6 x FZ-400-51
2190 DA2 GLZAC2190DA.I02 8 x FZ-400-51
2192 DA2 GLZAC2192DA.I02 8 x FZ-400-51
2220 DA2 GLZAC2220DA.I02 8 x FZ-400-51
2260 DA2 GLZAC2260DA.I02 8 x FZ-400-57
2265 DA2 GLZAC2265DA.I02 8 x FZ-400-57
2270 DA2 GLZAC2270DA.I02 8 x FZ-400-57
2272 DA2 GLZAC2272DA.I02 8 x FZ-400-57
2315 DA2 GLZAC2315DA.I02 10 x FZ-400-57
2360 DA2 GLZAC2360DA.I02 10 x FZ-400-57
2390 DA2 GLZAC2390DA.I02 12 x FZ-400-57
2420 DA2 GLZAC2420DA.I02 12 x FZ-400-57
2450 DA2 GLZAC2450DA.I02 12 x FZ-400-57
2480 DA2 GLZAC2480DA.I02 12 x FZ-400-57
2481 DA2 GLZAC2481DA.I02 14 x FZ-400-57
2482 DA2 GLZAC2482DA.I02 14 x FZ-400-57
2541 DA2 GLZAC2541DA.I02 14 x FZ-400-57
2600 DA2 GLZAC2600DA.I02 16 x FZ-400-57
2602 DA2 GLZAC2602DA.I02 16 x FZ-400-57
3630 DA2 GLZAC3630DA.I02 18 x FZ-400-57
3690 DA2 GLZAC3690DA.I02 18 x FZ-400-57
3720 DA2 GLZAC3720DA.I02 18 x FZ-400-57
3721 DA2 GLZAC3721DA.I02 20 x FZ-400-57
3722 DA2 GLZAC3722DA.I02 20 x FZ-400-57
SL units (especially quiet model)
2150 DA2 .SL GLZAC2150DA.I26 6 x FZ-400-51
2170 DA2 .SL GLZAC2170DA.I26 8 x FZ-400-51
2190 DA2 .SL GLZAC2190DA.I26 8 x FZ-400-51
2192 DA2 .SL GLZAC2192DA.I26 8 x FZ-400-51
2220 DA2 .SL GLZAC2220DA.I26 8 x FZ-400-51
2260 DA2 .SL GLZAC2260DA.I26 8 x FZ-400-57
2265 DA2 .SL GLZAC2265DA.I26 8 x FZ-400-57
2270 DA2 .SL GLZAC2270DA.I26 8 x FZ-400-57
2272 DA2 .SL GLZAC2272DA.I26 10 x FZ-400-57
2315 DA2 .SL GLZAC2315DA.I26 10 x FZ-400-57
2360 DA2 .SL GLZAC2360DA.I26 10 x FZ-400-57
2390 DA2 .SL GLZAC2390DA.I26 12 x FZ-400-57
2420 DA2 .SL GLZAC2420DA.I26 12 x FZ-400-57
2450 DA2 .SL GLZAC2450DA.I26 14 x FZ-400-57
2480 DA2 .SL GLZAC2480DA.I26 14 x FZ-400-57
2481 DA2 .SL GLZAC2481DA.I26 16 x FZ-400-57
2482 DA2 .SL GLZAC2482DA.I26 16 x FZ-400-57
2541 DA2 .SL GLZAC2541DA.I26 16 x FZ-400-57
2600 DA2 .SL GLZAC2600DA.I26 16 x FZ-400-57
2602 DA2 .SL GLZAC2602DA.I26 18 x FZ-400-57
3630 DA2 .SL GLZAC3630DA.I26 18 x FZ-400-57
3690 DA2 .SL GLZAC3690DA.I26 20 x FZ-400-57
3720 DA2 .SL GLZAC3720DA.I26 20 x FZ-400-57
3721 DA2 .SL GLZAC3721DA.I26 20 x FZ-400-57
3722 DA2 .SL GLZAC3722DA.I26 20 x FZ-400-57

Continued on the next page

Page 20/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 7: Required anti-vibration mounts depending on unit model (continued)

Unit type GLAC… FläktGroup sales number (complete as accessory) FläktGroup individual part designation

HE units (especially efficient model)


2150 DA2 .HE GLZAC2150DA.I59 8 x FZ-400-57
2170 DA2 .HE GLZAC2170DA.I59 8 x FZ-400-57
2190 DA2 .HE GLZAC2190DA.I59 8 x FZ-400-57
2192 DA2 .HE GLZAC2192DA.I59 8 x FZ-400-57
2220 DA2 .HE GLZAC2220DA.I59 8 x FZ-400-57
2260 DA2 .HE GLZAC2260DA.I59 8 x FZ-400-57
2265 DA2 .HE GLZAC2265DA.I59 10 x FZ-400-57
2270 DA2 .HE GLZAC2270DA.I59 10 x FZ-400-57
2272 DA2 .HE GLZAC2272DA.I59 10 x FZ-400-57
2315 DA2 .HE GLZAC2315DA.I59 12 x FZ-400-57
2360 DA2 .HE GLZAC2360DA.I59 12 x FZ-400-57
2390 DA2 .HE GLZAC2390DA.I59 14 x FZ-400-57
2420 DA2 .HE GLZAC2420DA.I59 14 x FZ-400-57
2450 DA2 .HE GLZAC2450DA.I59 16 x FZ-400-57
2480 DA2 .HE GLZAC2480DA.I59 16 x FZ-400-57
2482 DA2 .HE GLZAC2482DA.I59 16 x FZ-400-57
2541 DA2 .HE GLZAC2541DA.I59 18 x FZ-400-57
3570 DA2 .HE GLZAC3570DA.I59 20 x FZ-400-57
3630 DA2 .HE GLZAC3630DA.I59 20 x FZ-400-57
3660 DA2 .HE GLZAC3660DA.I59 20 x FZ-400-57

NOTICE!
If the units are operated without the appropriate anti-vibration mounts, the warranty is void!

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 21/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Electrical data
Table 8: Electrical data

Unit Type Compressor Fans3) Total 1) 2) 3)

starter
L.R.A.
F.L.A.

F.L.A.
Power

F.L.A
F.L.I.

F.L.I.

F.L.I.
[kW]

[kW]

[kW]

With
GLAC…

S.A.

S.A.

Soft
n

[A]

[A]

[A]

[A]
supply

Standard units
2150 DA2 400/3/50 2 2x62.7 2x102.3 2x303 8.0 16 133 220 381 N/A
2170 DA2 400/3/50 2 2x71.1 2x116.2 2x350 8.0 16 150 248 440 N/A
2190 DA2 400/3/50 2 1x71.1+1x80.9 1x116.2+1x129.8 1x350+1x423 10.0 20 162 265 516 N/A
2192 DA2 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2220 DA2 400/3/50 2 2x99.9 2x163.4 2x300 12.0 24 212 350 427 N/A
2260 DA2 400/3/50 2 1x99.9+1x127.8 1x163.4+1x209 1x300+1x404 14.0 28 242 399 535 N/A
2265 DA2 400/3/50 2 1x112.3+1x127.8 1x184.7+1x209 1x360+1x404 14.0 28 254 420 552 N/A
2270 DA2 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2272 DA2 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2315 DA2 400/3/50 2 1x127.8+1x161.7 1x209+1x258 1x404+1x465 18.0 36 308 501 631 N/A
2360 DA2 400/3/50 2 2x161.7 2x258 2x465 20.0 40 343 554 674 N/A
2390 DA2 400/3/50 2 1x161.7+1x188.1 1x258+1x306 1x465+1x586 22.0 44 372 606 799 N/A
2420 DA2 400/3/50 2 2x188.1 2x306 2x586 24.0 48 400 658 830 N/A
2450 DA2 400/3/50 2 1x188.1+1x213 1x306+1x345 1x586+1x650 24.0 48 425 697 894 N/A
2480 DA2 400/3/50 2 2x213 2x345 2x650 24.0 48 450 736 917 N/A
2481 DA2 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2482 DA2 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2541 DA2 400/3/50 2 1x213+1x260 1x345+1x423 1x650+1x917 28.0 56 501 821 1191 N/A
2600 DA2 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
2602 DA2 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
3630 DA2 400/3/50 3 3x188.1 3x306 3x586 36.0 72 600 986 1051 N/A
3690 DA2 400/3/50 3 1x188.1+2x213 1x306+2x345 1x586+2x650 36.0 72 650 1064 1138 N/A
3720 DA2 400/3/50 3 3x213 3x345 3x650 36.0 72 675 1103 1160 N/A
3721 DA2 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3722 DA2 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
SL units (especially quiet model)
2150 DA2 .SL 400/3/50 2 2x62.7 2x102.3 2x303 8.0 16 133 220 381 N/A
2170 DA2 .SL 400/3/50 2 1x62.7+1x80.9 1x102.3+1x129.8 1x303+1x423 10.0 20 154 251 505 N/A
2190 DA2 .SL 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2192 DA2 .SL 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2220 DA2 .SL 400/3/50 2 1x80.9+1x112.3 1x129.8+1x184.7 1x229+1x360 14.0 28 207 341 468 N/A
2260 DA2 .SL 400/3/50 2 2x112.3 2x184.7 2x360 16.0 32 241 400 512 N/A
2265 DA2 .SL 400/3/50 2 1x112.3+1x127.8 1x184.7+1x209 1x360+1x404 16.0 32 256 424 556 N/A
2270 DA2 .SL 400/3/50 2 2x127.8 2x209 2x404 16.0 32 272 448 566 N/A
2272 DA2 .SL 400/3/50 2 2x127.8 2x209 2x404 20.0 40 276 456 573 N/A
2315 DA2 .SL 400/3/50 2 1x127.8+1x161.7 1x209+1x258 1x404+1x465 20.0 40 310 505 634 N/A
2360 DA2 .SL 400/3/50 2 2x161.7 2x258 2x465 20.0 40 343 554 674 N/A
2390 DA2 .SL 400/3/50 2 1x161.7+1x188.1 1x258+1x306 1x465+1x586 22.0 44 372 606 799 N/A
2420 DA2 .SL 400/3/50 2 2x188.1 2x306 2x586 24.0 48 400 658 830 N/A
2450 DA2 .SL 400/3/50 2 1x188.1+1x213 1x306+1x345 1x586+1x650 26.0 52 427 700 898 N/A
2480 DA2 .SL 400/3/50 2 2x213 2x345 2x650 28.0 56 454 743 924 N/A
2481 DA2 .SL 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2482 DA2 .SL 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2541 DA2 .SL 400/3/50 2 1x213+1x260 1x345+1x423 1x650+1x917 32.0 64 505 829 1199 N/A
2600 DA2 .SL 400/3/50 2 2x260 2x423 2x917 32.0 64 552 907 1243 N/A
2602 DA2 .SL 400/3/50 2 2x260 2x423 2x917 36.0 72 556 914 1250 N/A
3630 DA2 .SL 400/3/50 3 3x188.1 3x306 3x586 36.0 72 600 986 1051 N/A
3690 DA2 .SL 400/3/50 3 1x188.1+2x213 1x306+2x345 1x586+2x650 40.0 80 654 1072 1145 N/A
3720 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3721 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A
3722 DA2 .SL 400/3/50 3 3x213 3x345 3x650 40.0 80 679 1111 1168 N/A

Continued and footnotes on next page

Page 22/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Table 8: Electrical data (continued)

Unit Type Compressor Fans3) Total 1) 2) 3)

starter
L.R.A.
F.L.A.

F.L.A.
Power

F.L.A
F.L.I.

F.L.I.

F.L.I.
[kW]

[kW]

[kW]

With
GLAC…

S.A.

S.A.

Soft
n

[A]

[A]

[A]

[A]
supply

HE units (especially efficient model)


2150 DA2 .HE 400/3/50 2 1x49.6+1x72.3 1x82.5+1x118 1x269+1x350 10.0 20 132 220 426 N/A
2170 DA2 .HE 400/3/50 2 2x71.1 2x116.2 2x350 12.0 24 154 255 447 N/A
2190 DA2 .HE 400/3/50 2 2x80.9 2x129.8 2x423 12.0 24 174 282 527 N/A
2192 DA2 .HE 400/3/50 2 1x80.9+1x99.9 1x129.8+1x163.4 1x229+1x300 14.0 28 195 320 408 N/A
2220 DA2 .HE 400/3/50 2 2x99.9 2x163.4 2x300 16.0 32 216 357 435 N/A
2260 DA2 .HE 400/3/50 2 2x112.3 2x184.7 2x360 16.0 32 241 400 512 N/A
2265 DA2 .HE 400/3/50 2 1x112.3+1x127.8 1x184.7+1x209 1x360+1x404 18.0 36 258 428 560 N/A
2270 DA2 .HE 400/3/50 2 2x127.8 2x209 2x404 20.0 40 248 410 469 N/A
2272 DA2 .HE 400/3/50 2 2x127.8 2x209 2x404 20.0 40 276 456 573 N/A
2315 DA2 .HE 400/3/50 2 1x127.8+1x161.7 1x209+1x258 1x404+1x465 22.0 44 312 509 638 N/A
2360 DA2 .HE 400/3/50 2 2x161.7 2x258 2x465 24.0 48 347 562 682 N/A
2390 DA2 .HE 400/3/50 2 1x161.7+1x188.1 1x258+1x306 1x465+1x586 26.0 52 376 613 806 N/A
2420 DA2 .HE 400/3/50 2 2x188.1 2x306 2x586 28.0 56 404 665 837 N/A
2450 DA2 .HE 400/3/50 2 1x188.1+1x213 1x306+1x345 1x586+1x650 30.0 60 431 708 905 N/A
2480 DA2 .HE 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2482 DA2 .HE 400/3/50 2 2x213 2x345 2x650 32.0 64 458 751 932 N/A
2541 DA2 .HE 400/3/50 2 1x213+1x260 1x345+1x423 1x650+1x917 36.0 72 509 836 1206 N/A
3570 DA2 .HE 400/3/50 3 2x161.7+1x188.1 2x258+1x306 2x465+1x586 38.0 76 550 894 1000 N/A
3630 DA2 .HE 400/3/50 3 3x188.1 3x306 3x586 40.0 80 604 994 1058 N/A
3660 DA2 .HE 400/3/50 3 2x188.1+1x213 2x306+1x345 2x586+1x650 40.0 80 629 1033 1122 N/A

All values refer to units without built-in pumps. For units with built-in pumps, the pump data must be added.
n Number of compressors
F.L.I. El. FULL LOAD INPUT
F.L.A. Operating current
L.R.A. Starting current of each compressor
S.A. Starting current of entire unit

1) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.
2) Please observe the regionally applicable standards for cable cross-sections and backup fuses. Voltage tolerance: max. 10%,
voltage imbalance
between phases: max. 3%.
3) Values are based on the total number of fans operating at maximum speed.

PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 23/24
Air-cooled chiller
GLAC 2150 – 3722 DA2(.SL/.HE)

Terminal scheme

Setpoint shift Demand limit* Activation


4-20 mA signal (option .E23) 2nd setpoint*
Put on (option .E21) (option .E22)
shielding
Put on
shielding
Y + -
G

SA1 SA2 GND R S SC1 SC1


GND + -
Serial card RS485/Modbus, LonWorks GLAC 2150-3722 DA2 (.SL/.HE)
or BACnet as option, .E14 - .E17

E F A B C D AA AA FC1 FC1 FC2 FC2 FC3 FC3 FP1 FP1 FP2 FP2

5J1

Operation message compressor 1-3


Contact Flow Operation Common # Relay for 2nd
Relay for
(option .E03)
Remote On/Off* 1) switch* message of the fault signal # on-site chilled-wateron-site chilled-
on-site chilled- max. 2 A~/50 Hz for GLAC 2150 – 2602 DA2 2) water
not applicable FC3 pump # 2)
water pump* 2) (Option E.04/E.34) pump #
Cabling on-site provided by others (option .E34)
# on-site potential necessary max. 230 V / 50 Hz / 2 A)
* potential may not be supplied by others (supplied by controller)
1) Remove jumper J1 if remote contact is used. For connecting e.g. a timer or outdoor temperature switch (with hysteresis) to enable the
device. Switching dependent on the water temperature (e.g. in the buffer storage tank) is not permitted (caution: not covered by the
warranty, possible damage to the unit!)
2) Only for units without built-in pumps: Use connection C-D for feedback signal of the on-site chilled-water pump(s) (on-site load contactor or
pump electronics; closed contact when operating the pump(s)). Connections C-D without bridge. The on-site chilled-water pump(s) must
be enabled via the unit controller (contacts FP1 or FP1/ FP2 for two parallel on-site chilled-water pumps with redundancy function).
For units with built-in pump(s), connection C-D is bridged.

Fig. 8: Terminal scheme

Order related documentation

NOTICE!
For detailed planning please only use the order-related documentation. Detailed dimensional drawings can be
obtained on request from your responsible FläktGroup sales office. Specifications and technical data are subject to
regular updates. The manufacturer reserves the right to make necessary changes to information without prior
written notice.

Page 24/24 PR-2018-1112-GB • R1-06/2019 • FläktGroup is not liable for printing errors and reserves the right to change content without notice..