SCHEDULE OF LOAD & COMPUTATION: GOING TO MAIN ELECTRICAL

BLDG SUPPLY
2 12 MAIN: 70amps,2p,230v,bolt-on flush mounted
GFCI GFCI
13 CKT.
NO
DESCRIPTION OF LOAD
SERVICE LOAD
VOLTAGE WATTS AB
LOAD AMPERES

BC CA 1Ø
CB SIZE/BOLT-ON

P AT AF
WIRE SIZE
(MM2) THHN
CONDUIT SIZE
(MMØ)
REMARKS

EAB-1
1 12- PINLIGHT 40WATTS 230 480 2.08 2 15 20 15mm EMT
100 AT 2P IN NEMA 1
2 2- EMERGENCY LIGHT & EXIT SIGN 230 1000 4.35 2 15 20 15mm EMT
8 3 REFRIGERATOR 230 1000 4.35 2 20 20 15mm EMT
ENC BOLT-ON TYPE

7 11 4 REFRIGERATOR 230 1000 4.35 2 20 20 20mm EMT L.O. PB


1
15AT 15AT PB
2
EMERGENCY LIGHT &
EXIST SIGN
5 FREEZER 230 1000 4.35 2 20 20 20mm EMT PB
PB
REF 3
20AT 20AT
4 REF
6 FREEZER 230 1000 4.35 2 20 20 20mm EMT
1 14 FAB-1 FREEZER
PB
5 20AT 20AT
PB
6 FREEZER

7 GFCI OUTLET 230 1500 6.52 2 30 40 20mm EMT GFCI OUTLET PB PB


GFCI OUTLET
7 30AT 30AT 8
8 GFCI OUTLET 230 1500 6.52 2 30 40 20mm EMT
PB
PB
GFCI OUTLET 30AT 30AT 10 GFCI OUTLET
9
9 GFCI OUTLET 230 1500 6.52 2 30 40 20mm EMT
FREEZER PB

5
PB
10 GFCI OUTLET 230 1500 6.52 2 30 40 20mm EMT GAS DETECTOR 11 20AT 20AT
12 GAS DETECTOR

PB
EAB-1
PB
13 40AT 40AT
14 FAB-1
11 GAS LEAK DETCTOR 230 1000 4.35 2 20 20 25mm EMT
PB
12 GAS LEAK DETCTOR 230 1000 4.35 2 20 20 25mm EMT SPARE
PB
SPARE

6
15 16

4 11 FAB-01 230 2200 9.56 2 40 40 25mm EMT

25mm EMT
REF 12 EAB-01 230 500 2.17 2 40 40

FREEZER 9 15 SPARE 230 1150 5.00 2 15 20


GROUND
16 SPARE 230 1150 5.00 2 15 20

GFCI Total Connected Load 18480W 80.34A 3 100 100

Demand Factor 0.80 64.27A

Demand VA 14784
GFCI REF Main Circuit Breaker 2P 100AT/BOLT-ON TYPE(100AF) in Nema-1 enclosure

2 Feeder
Note:
2-38mm2 thhn/thwn (83.10/205), 1-14mm2 thhn/thwn str in 50mmØ RSC 1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN
ACCORDANCE W/ THE PROVISIONS OF THE LATEST OF
APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE
1.) Provide conductor copper busbar complying with Local Code requirements & RULES & REGULATIONS OF THE AUTHORITIES

3
CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS
2.) Wire Bending clearance shall comply with the Local Code requirements. & ORDINANCES.

10 2.POWER SERVICE TO THE BUILDING SHALL BE 230 VOLTS,


THREE-PHASE, 3-WIRE + 1 WIRE GRND, 60 HERTZ SYSTEM.

3.WIRING METHOD SHALL BE DONE IN PURE INTERMEDIATE


METTALIC(IMC) CONDUIT ALL THROUGHOUT THE
SYSTEM COMPLETE W/ BOXES & NECESSARY ELECTRICAL
FITTINGS.

4.UNLESS OTHERWISE SPECIFIED IN THE LOAD SCHEDULE,


MINIMUM SIZE OF WIRE & CONDUIT TO BE USED SHALL BE
3.5 SQ. MM TYPE THHN & 20 MM NOMINAL DIAMETER TRADE
SIZE, RESPECTIVELY. WIRE SHALL BE INSULATED FOR 600
VOLTS.

5.ALL MATERIALS & EQUIPMENT TO BE USED SHALL BE NEW &


OF APPROVED TYPE FOR BOTH PURPOSE & LOCATION
INTENDED.

6.ALL MOUNTING HEIGHT SHALL BE SUBJECT TO THE


ARCHITECT'S APPROVAL. OTHERWISE, THE STANDARD
HEIGHT OF 0.30 M FROM THE FFL SHALL BE USED FOR
CONVENIENCE OUTLETS AND 1.40 M FROM THE FFL SHALL
BE USED FOR LIGHTING SWITCHES & THE LIKE.

7.ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER


THE DIRECT SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER.

8.IN CASE OF DISCREPANCIES SHOWN IN THE PLANS, PLEASE


VERIFY ARCHITECT AND THE ELECTRICAL ENGINEER, USING
REQUEST FOR INFORMATION FORMS.

ELECTRICAL LIGHTING LAYOUT ELECTRICAL POWER LAYOUT NOTES:


1. SEE LOAD SCHEDULE AND COMPUTATIONS FOR DETAILS ON EQUIPMENT
RATINGS, LOADINGS, BREAKER AND FEEDER SIZES.

2. LOCATION OF ALL ELECTRICAL PANELS SHALL BE VERIFIED AT SITE AND ARE


SUBJECT TO THE ARCHITECT'S/ENGINEER'S APPROVAL.

3. THE ELECTRICAL CONTRACTOR SHALL BE HELD LIABLE IN OBTAINING THE


ACTUAL SITE CONDITION, MEASUREMENTS, AND CLEARANCES.
COORDINATE WITH OTHER TRADES AT SITE TO AVERT CONFLICT DURING
ACTUAL IMPLEMENTATION.

PL

LP

GFCI

FL

S C A L E:
ELECTRICAL-SYSTEM LAYOUT 1:30MTS

REPUBLIC ACT 9266 PROJECT TITLE OWNER: REVISION DATE SHEET CONTENTS SHEET NO.
ART IV, SECTION 33
DRAWINGS AND SPECIFICATIONS DULY

1
SIGNED AND SEALED AS INSTRUMENT OF ENGR. HENRY D. CINCO AS SHOWN
SERVICE ARE INTELLECTUAL PROPERTY. ENGINEER SUPERVISOR PROFESSIONAL ELECTRICAL ENGINEER
MR. CHOPS SM SOUTHMALL
IT SHALL BE UNLAWFUL FOR ANY PERSON
TO DUPLICATE OR TO MAKE COPIES FOR
PRC REG. NO: PTR NO: PRC REG. NO: 4772 PTR NO: 8122257
-------------------------------------------
OWNER'S REPRESENTATIVE DESIGNED BY : 09459784516 CAD BY : JOHN KARL BENTING
EE
USED IN REPETITION, WETHER EXECUTED
PARTLY OR WHOLE, WITHOUT THE DATE: ISSUED ON: DATE: 11/22/2023 ISSUED ON: JAN 05, 2022 CHECKED BY : DATE : 24 JAN 2024
WRITTEN CONSENT OF THE AUTHOR LOCATION: SM SOUTH MALL LAS PINAS CITY
TIN NO: ISSUED AT: TIN NO: ISSUED AT: PASIG CITY
FILENAME :
------------------ ELECTRICAL