Professional Documents
Culture Documents
Anjali Shah. Instrumentationlab Report1
Anjali Shah. Instrumentationlab Report1
Anjali Shah. Instrumentationlab Report1
Dhulikhel, Kavre
2
Experiment-I
Title: Calibration of a Multimeter
Apparatus:
S. No. Equipment Range Type Quantity
1 Multimeter 0-220V Digital 1
3 DC voltage supply 0-15V 1
4 Resistor 1kΩ 2
5 Bread-board 1
6 Wires Few
Theory:
A digital multimeter is used to measure voltage, current, resistance and as well as check the
continuity of the circuit. The display shows the measured value. A multimeter is calibrated to
a known zero value prior to readings for accurate measurements.
Circuit diagram:
|𝐴𝑚− 𝐴𝑡 |
𝑟𝑠𝑒(%) = ∗ 100% (1)
𝐴𝑡
3
Observation Table:
4
FIGURE 2: Am vs At for Ammeter reading in amperes
Conclusion:
Hence, the calibration of the multimeter was done by taking both voltmeter and ammeter
readings. The percentage relative square error(rse) was also calculated by using the formula.
The status was concluded to be true if rse was less than or equal to 0, otherwise false. The
calibration curve was shown in graph for Am vs At for both readings.
5
Experiment-II
Title: Use of Megger for Insulation testing of a transformer
Apparatus
S. No. Equipment Range Type Quantity
1 Megger 230V, 1-phase 1
2 Connecting wires 3/22, 15A Few
3 Transformer
Theory:
Megger is used for insulation testing. The insulation should be high in MΩ for good equipment
and will lie in Ω range for damaged equipment.
Circuit diagram:
(a) (b)
Figure 1 (a). Transformer (b) Transformer insulation testing using megger
Procedure:
1. Remove completely external supply to transformer.
2. Connect leads to megger and set the megger voltage to 1000V.
3. Measure the insulation resistance
6
Observation Table:
Table 1. Phase-ground insulation resistance check
S. No. Connection Resistance (MΩ)
1 1.1-Ground 21
2 1.2-Ground 22
3 1.3-Ground 22
4 2-Ground 49
5 2.2-Ground 48
6 3.1-Ground 260
7 3.2-Ground 436
Conclusion:
Hence, megger testing was done between phase to phase and phase to ground of the transformer
to check the resistance between them or if there is an insulation breakdown. The results
observed were positive as they were in the range of 20-2000 Megaohms.