System Design

T2 3/4 in.

T1 3/4 in.

N
3/4 in.
T2

1 in.

DH
20 ft. MAX

CYLINDER

Figure 3-5. Piping Parameters, Total-Flooding Coverage, IND-50/IND-45

Table 3-4. Total-Flooding Piping Parameters (IND-50/IND-45)


Maximum Limits

T1 to T2 to
Cylinder to T1
Item T2 Nozzle

Pipe Equiv. Pipe Equiv. Pipe Equiv.


Qty Qty Qty
Size Length Size Length Size Length

Pipe 1 in. 60 ft. 60 ft. 3/4 in. 15 ft. 15 ft. 3/4 in. 7 ft. 7 ft.

90° Ell 1 in. 7 14 ft. 3/4 in. 1 2 ft. 3/4 in. 2 ft. 4 ft.

Tee 1 in. 1 5 ft. 3/4 in. 1 4 ft. 3/4 in. 0 -


Total Maximum 79 ft. Total Maximum 21 ft. Total Maximum 11 ft.

January 2007 3-10 P/N 220423