Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

6.1 Field copper piping is done as per recommended size.

Field coper piping is tested with recommended pressure and


6.2
vacuumed for 500 micron
6.3 Any damage to coil fins has been repaired
Oil trap is provided every 4 to 5 meter on vertical suction line (where
6.4 the compressor is located above the evaporator) and on vertical
discharge line (where the compressor is located below the Condenser).
Power supply to be turn on to crankcase heater 12 hrs. before
6.5
commissioning
6.6 Check filter drier is installed and its direction
Check expansion valve installation and its position. It has to be as per
6.7
the manufacturer recommendation.
Check whether field piping is connected to the respective circuit as per
6.8
information on the labels.
Check the control wiring and Its size. The size must be minimum of
6.9
1.5 Sq mm- CU
7 Electrical
Power and control wiring are done in accordance with manufacturer’s
7.1
instruction
All cables terminations are tight and free from loose gripping, Proper
7.2
sized cable with gland is provided.
Motor terminals are checked for loose contact and DOL or star delta
7.3 sequence as per the Motor nameplate.
Disconnect switch is located nearby the unit to operate in case of
7.4
emergency.
7.5 Power available to electric heater and Humidifier
Proper control panel is provided that has required logics of operation
7.6 and safety controls as specified.
8 Controls
8.1 Control valves/actuators properly installed and operation checked.
8.2 Dampers/actuators properly installed and operation checked.
8.3 Differential pressure switch is installed and working to be verified..
Verify proper location, installation and calibration of duct static
8.4
pressure sensor
8.5 Motor controller /starter safety controls operation checked
8.6 Temperature control system operational verified.
9 Start Up Test Run
9.1 Motor winding resistance measured.
9.2 Controls cabling loop and terminations are checked
9.3 Safety interlocks are tested
9.4 Proper rotation of the motor is verified
Comments:

Inspected by :
Name:
Signature:

- 24 -

You might also like