Drive Selection Chart R0
Drive Selection Chart R0
DETAILS VALUE
Design Temperature 45
Design Altitude 1000
Assumed
Motor
Voltage Voltage Motor DRIVE Drive Rated Drive current Panel Heat Loss
S.No PANEL NAME Panel Type Rating Overload Requiremet Drive Model No
Range (V) Current QTY. current (A) @45Deg C Dimension Approx. (Watts)
(kW)
FLC (A)
110% overload for 1min. Once
1 CWP#3 (Cooling water pump 380-500Vac 415 315 529.0 1 FC302N250 588 588
in every 10mins.
ACW pump#1(Aux. cooling 110% overload for 1min. Once
2 Lineup Panel 380-500Vac 415 110 190.0 2 FC302N90K 212 212 6400 (W) x 2275 (H) x 600 (D) 17025
water) in every 10mins.
110% overload for 1min. Once
3 CT Fan#1,2,3 (Cooling Tower) 380-500Vac 415 90 147.0 3 FC302P75K 177 177
in every 10mins.
CEP 1,2 (Condensate 110% overload for 1min. Once
4 Standalone Panel 380-500Vac 415 75 130.0 2 FC302P55K 147 147 800 (W) x 2275 (H) x 600 (D) 1453
extraction pump ) in every 10mins.
Rev.: 0
# Classified as Business Page 1