Operating Instructions
Liquiphant FTL33
Point level switch for liquids in the food industry
Liquiphant FTL33
Serial number
2. www.endress.com/deviceviewer Endress+Hauser
Operations App
3.
A0023555
2 Endress+Hauser
Liquiphant FTL33 Table of contents
Table of contents
1 Document information . . . . . . . . . 4 10 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1.1 Document function . . . . . . . . . . . . . . . . . . . 4 10.1 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . 37
1.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 10.2 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1.3 Documentation . . . . . . . . . . . . . . . . . . . . . . 5 10.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3 Product description . . . . . . . . . . . . . 8
3.1 Product design . . . . . . . . . . . . . . . . . . . . . . . 8
5 Mounting . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Mounting requirements . . . . . . . . . . . . . . 11
5.2 Mounting the measuring device . . . . . . . 16
5.3 Post-mounting check . . . . . . . . . . . . . . . . 18
6 Electrical connection . . . . . . . . . . 20
6.1 Connecting the device . . . . . . . . . . . . . . . 20
6.2 Post-connection check . . . . . . . . . . . . . . . 29
7 Commissioning . . . . . . . . . . . . . . . . 31
7.1 Function check . . . . . . . . . . . . . . . . . . . . . 31
7.2 LED display . . . . . . . . . . . . . . . . . . . . . . . . 31
7.3 Function of LEDs . . . . . . . . . . . . . . . . . . . . 33
7.4 Function test with test magnet . . . . . . . . 33
8 Diagnostics and
troubleshooting . . . . . . . . . . . . . . . 35
8.1 Diagnostic information via LED
display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9 Maintenance . . . . . . . . . . . . . . . . . . 35
9.1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Endress+Hauser 3
Document information Liquiphant FTL33
1 Document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases of
the life cycle of the device: from product identification, incoming acceptance and storage, to
mounting, connection, operation and commissioning through to troubleshooting,
maintenance and disposal.
1.2 Symbols
1.2.1 Safety instructions
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
A0011189-EN serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
A0011190-EN serious or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
A0011191-EN minor or medium injury.
NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in personal
A0011192-EN injury.
Symbol Meaning
Ground connection
)
A0011200
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
4 Endress+Hauser
Liquiphant FTL33 Document information
Symbol Meaning
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Symbol Meaning
A, B, C, ... Views
Symbol Meaning
Open-ended wrench
A0011222
1.3 Documentation
The document types listed are available in the Download Area of the Endress+Hauser website:
www.endress.com → Download
Technical Information This document contains all the technical data for the device and provides an overview of
TI01148F/00/EN the accessories that can be ordered.
Additional documentation
Endress+Hauser 5
Basic safety instructions Liquiphant FTL33
Residual risks
Due to heat transfer from the process, the temperature of the electronics housing and the
assemblies contained therein may rise to 80 °C (176 °F) during operation.
6 Endress+Hauser
Liquiphant FTL33 Basic safety instructions
Endress+Hauser 7
Product description Liquiphant FTL33
3 Product description
The Liquiphant FTL33 is a point level switch for universal use in all liquids. It is used
preferably in storage tanks, mixing vessels and pipes, where the internal and external hygiene
requirements are particularly stringent.
A B C D
A0022228
Examples
Versions
A B C D
For detailed information on the short tube version and the process connections, see the
Technical Documentation TI01148F/00/EN.
8 Endress+Hauser
Liquiphant FTL33 Incoming acceptance and product identification
‣ Enter the serial number from the nameplates into W@M Device Viewer
(www.endress.com/deviceviewer)
All the information about the measuring device and the scope of the associated
Technical Documentation are displayed.
‣ Enter the serial number from the nameplate into the Endress+Hauser Operations App or
use the Endress+Hauser Operations App to scan the 2-D matrix code (QR Code) provided on
the nameplate
All the information about the measuring device and the scope of the associated
Technical Documentation are displayed.
Endress+Hauser SE+Co. KG
Hauptstraße 1
79689 Maulburg, Germany
Place of manufacture: See nameplate.
Endress+Hauser 9
Incoming acceptance and product identification Liquiphant FTL33
A0020845
10 Endress+Hauser
Liquiphant FTL33 Mounting
5 Mounting
5.1 Mounting requirements
5.1.1 Orientation
Installation is possible in any position in a vessel, pipe or tank.
3
2
A0036961
2 Installation examples
1 Overfill prevention or upper level detection (maximum safety)
2 Dry running protection for pump (minimum safety)
3 Lower level detection (minimum safety)
~30 (1.2)
A A A
A0020734
3 Orientation: vertical from above, vertical from below, horizontal; dimensions in mm (in)
5.1.3 Viscosity
Switching delays may occur in the case of highly viscous liquids. Make sure that the liquid can
easily run off the tuning fork:
Endress+Hauser 11
Mounting Liquiphant FTL33
• If installing in vessels with high-viscosity liquids (A), the tuning fork may not be located in
the installation socket!
• If installing in vessels with low-viscosity liquids (B), the tuning fork may be located in the
installation socket.
• The installation nozzle must be no less than the minimum diameter of 50 mm (2.0 in).
A B
4 Installation options with consideration given to the liquid viscosity, dimensions in mm (in)
A High viscosity (< 10 000 mPa·s)
B Low viscosity (< 2 000 mPa·s)
5.1.4 Buildup
Make sure that the installation socket does not exceed a certain length so that the tuning fork
can project freely into the vessel.
Possibilities for optimization:
• A vertical orientation of the point level switch keeps buildup to a minimum.
• Preferably flush-mounted on vessels or in pipes.
12 Endress+Hauser
Liquiphant FTL33 Mounting
A0022057
5.1.6 Marking
The marking indicates the position of the tuning fork. If installed horizontally in vessels, the
marking is face up.
The marking is either a material specification (e.g. 316L) or a type of thread (e.g. G ½") and is
located:
• On the hexagonal bolt of the process adapter
• On the nameplate
• On the weld-in adapter
Endress+Hauser 13
Mounting Liquiphant FTL33
<-1.4435
316L
G1
<-1.4435
316L
G1
<-1.4435
± 15°
A0022641
316L 316L
G 3/4
G 3/4
< -316L
< -316L
±15°
A0022804
14 Endress+Hauser
Liquiphant FTL33 Mounting
ø >50 (2.0)
316L
G 3/4
ø >10 (0.4)
A0021357
A0021034
Endress+Hauser 15
Mounting Liquiphant FTL33
A0022272
A0022025
1 Flat seal
2 Weld-in adapter
16 Endress+Hauser
Liquiphant FTL33 Mounting
A0022026
A0022028
Thread M24x1.5
64.9 (2.56) for flush mount installation in adapter
8.5 (0.3)
17 (0.7)
A0022037
Endress+Hauser 17
Mounting Liquiphant FTL33
A0022036
NOTICE
‣ Pay attention to the temperature and pressure specifications
for the seals and clips used at the customer site.
A0022035
A0022038
Endress+Hauser 19
Electrical connection Liquiphant FTL33
6 Electrical connection
The device has two operating modes: maximum safety (MAX) and minimum safety (MIN). By
choosing the corresponding operating mode, the user ensures that the device also switches in
a safety-oriented manner even in an alarm condition, e.g. if the power supply line is
disconnected.
• Maximum safety (MAX)
The device keeps the electronic switch closed as long as the liquid level is below the fork.
Sample application: overfill protection
• Minimum safety (MIN)
The device keeps the electronic switch closed as long as the fork is immersed in liquid.
Sample application: Dry running protection for pumps
The electronic switch opens if the limit is reached, if a fault occurs or the power fails
(quiescent current principle).
A0022901
10 M12 plug
20 Endress+Hauser
Liquiphant FTL33 Electrical connection
Maximum safety
2 1
1 2
3 4
0.5A
K 1 2
L– L+
Wire colors for M12 plug:
• 1 = BN (brown)
• 2 = WT (white)
• 3 = BU (blue)
• 4 = BK (black)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
Minimum safety
2 1
1 4
3 4
0.5A
K
1 4
L– L+
Wire colors for M12 plug:
• 1 = BN (brown)
• 2 = WT (white)
• 3 = BU (blue)
• 4 = BK (black)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
Endress+Hauser 21
Electrical connection Liquiphant FTL33
When both outputs are connected, the MIN and MAX outputs assume opposite states (XOR)
when the device is operating fault-free. In the event of an alarm condition or a line break,
both outputs are de-energized.
Connection for function monitoring using XOR operation Yellow LED (ye) LED red (rd)
2 1 Max output
1 2
3 4
0.5A
K1 K2 Sensor covered
Min output
L– L+ 1 4
Max output
1 2
1 4
1 2
Fault
1 4
Symbols Description
LED lit
LED not lit
Fault or warning
K1/K2 External load
22 Endress+Hauser
Liquiphant FTL33 Electrical connection
A0022900
11 Valve plug
3-wire DC-PNP
3 2
1 2
+
3 K
–
3 2
0.5A
L– L+
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
3-wire DC-PNP
2 3
1 2
3 +
K
– 2 3
0.5A
L– L+
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
A0022902
3-wire DC-PNP
3 3 2
2
1
+
K
0.5A 3 2
L– L+
Wire colors:
1 = BK (black)
2 = GR (gray)
3 = BN (brown)
Ground = GNYE (green-yellow)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
3-wire DC-PNP
3
2 3
2 1
+
0.5A K 2 3
L+ L–
24 Endress+Hauser
Liquiphant FTL33 Electrical connection
3-wire DC-PNP
Wire colors:
1 = BK (black)
2 = GR (gray)
3 = BN (brown)
Ground = GNYE (green-yellow)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
Endress+Hauser 25
Electrical connection Liquiphant FTL33
P/S
2.7
2.5
2.3
2.1
1.9
1.7
1.5
1.3 P1
1.1
0.9
0.7 P2
0.5 U
20 24 27 43 48 53 60 110 121 207 230 253
A0023486
P1: AC mode
Relay operating voltage: Relay rated power
• 24 V: 1.3 to 6 VA
• 110 V: 1.5 to 27.5 VA
• 230 V: 2.5 to 57.5 VA
26 Endress+Hauser
Liquiphant FTL33 Electrical connection
P2: DC mode
Relay operating voltage: Relay rated power
• 24 V: 0.7 to 6 W
• 48 V: 0.9 to 12 W
• 60 V: 1.5 to 15 W
Relays with a lower rated power can be operated by means of an RC module connected in
parallel (optional).
A0022900
14 Valve plug
2-wire AC/DC
1 3
1 A0045072
3
>20 V
K 1 3
A0045074
0.5A
L1/L+ N/L–
A0021219
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
Endress+Hauser 27
Electrical connection Liquiphant FTL33
2-wire AC/DC
1 2
1 2 A0045070
>20 V
K 1 2
0.5A A0045069
L1/L+ N/L–
A0021220
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
A0022902
28 Endress+Hauser
Liquiphant FTL33 Electrical connection
2-wire AC/DC
3 1 3
A0045072
2 1
>20 V
K 1 3
0.5A A0045074
L1/L+ N/L–
A0022161
Wire colors:
1 = BK (black)
2 = GR (gray)
3 = BN (brown)
Ground = GNYE (green-yellow)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
2-wire AC/DC
3 1 2
A0045070
2 1
>20 V
K 1 2
0.5A A0045069
N/L– L1/L+
A0022225
Wire colors:
1 = BK (black)
2 = GR (gray)
3 = BN (brown)
Ground = GNYE (green-yellow)
Symbols Description
Yellow LED (ye) lit
Yellow LED (ye) not lit
K External load
Endress+Hauser 29
Electrical connection Liquiphant FTL33
30 Endress+Hauser
Liquiphant FTL33 Commissioning
7 Commissioning
7.1 Function check
Go through the following checklists before commissioning:
• "Post-installation check" checklist
• "Post-connection check" checklist
The function of the tuning fork can be tested by immersing the tuning fork in a vessel
containing water.
A B
2 1 2 3 1
3 1 4 3
2 3
2 1
A0016856
Function Description
M12 plug
Indicates the sensor state: tuning fork is covered by liquid
Yellow LED (ye) Valve plug / cable
Lit Indicates the switching state:
• MAX operating mode (overfill protection): sensor is not covered by liquid
• MIN operating mode (dry running protection): the sensor is covered by liquid
Endress+Hauser 31
Commissioning Liquiphant FTL33
Function Description
LED red (rd) Warning/maintenance required: error can be rectified, e.g. incorrect wiring; protective function if
Flashing test magnet is held against the sensor for longer than 30 s
On the metal housing cover (IP69), there is no external signaling via LEDs.
gn
ye 1
ye 2
(1.08)
27.5
³40
(1.57)
A0020871
32 Endress+Hauser
Liquiphant FTL33 Commissioning
Operating modes
Connection
Maximum safety (MAX) Minimum safety (MIN) Warning Fault
1 ye gn
1 4
2 3
rd
2 ye1
ye2 gn
3 ye gn
3
2 1
rd
4 ye gn
rd
A0021223
A0021225 A0021226 A0021227 A0021228 A0022920 A0021229
Endress+Hauser 33
Commissioning Liquiphant FTL33
If the test magnet is held against the marking for longer than 30 s, the red LED will flash: the
device returns automatically to the current switch status.
The test magnet is not included in the scope of delivery. It can optionally be ordered as
an accessory. See the "Accessories" -> "Additional accessories" section
N TEST
A0020960
34 Endress+Hauser
Liquiphant FTL33 Diagnostics and troubleshooting
Green LED
No power supply Check connector, cable and power supply
Not lit
Yellow LED
Not lit • Check cable
Internal sensor failure or sensor
• Reduce maximum load current to below 250 mA
Yellow LED corroded
• Replace device
Both lit
Unexpected behavior Incorrect connector assignment or Pay attention to the polarity of the power supply!
of yellow LED incorrect cable wiring
Correct connection:
Valve plug: L+ to PIN1, L- to PIN 3
Cable: L+ BK (black), L- BN (brown)
Result (for MIN operating mode)
• Tuning fork covered: yellow LED lit.
• Tuning fork not covered: yellow LED not lit.
Result (for MAX operating mode)
• Tuning fork covered: yellow LED not lit.
• Tuning fork not covered: yellow LED lit.
9 Maintenance
No special maintenance work is required.
Endress+Hauser 35
Maintenance Liquiphant FTL33
9.1 Cleaning
The sensor must be cleaned if necessary. It can also be cleaned while installed (e.g. CIP
Cleaning in Place / SIP Sterilization in Place). Care must be taken to ensure that no damage
occurs to the sensor in the process.
36 Endress+Hauser
Liquiphant FTL33 Repair
10 Repair
Repair is not envisaged for the point level switch.
10.2 Return
The requirements for safe device return can vary depending on the device type and national
legislation.
1. Refer to the website for more information:
http://www.endress.com/support/return-material
2. Return the device if repairs or a factory calibration are required, or if the wrong device
was ordered or delivered.
10.3 Disposal
11 Accessories
For detailed information on accessories, see the Technical Documentation TI01148F.
Weld-in adapter
TI00426F/00/EN
For detailed information on the weld-in adapters, see
and the supplementary documentation → 5.
Seals, O-rings
Endress+Hauser 37
Accessories Liquiphant FTL33
Wire colors:
• 1 = BN (brown)
• 2 = WT (white)
• 3 = BU (blue)
• 4 = BK (black)
Socket wrench for mounting Hexagon bolt, AF32, order number: 52010156
38 Endress+Hauser
Liquiphant FTL33 Technical data
12 Technical data
For additional information on the technical data, see the Technical Documentation
TI01148F/00/EN.
12.2 Environment
Ambient temperature range –40 to +70 °C (–40 to +158 °F), see derating → 40
Endress+Hauser 39
Technical data Liquiphant FTL33
Electromagnetic compatibility Electromagnetic compatibility in accordance with all relevant requirements of the
EN 61326 series and NAMUR recommendation EMC (NE21). For details, refer to
the EC Declaration of Conformity.
Available in the Download Area of the Endress+Hauser website:
www.endress.com.
12.2.1 Derating
Ta
[°F] [°C] 1
+158 +70 2
Ta
+122 +50
Tp
+32 0
–40 –40
[°C]
–40 0 +50 +100
+80 TP
[°F]
–40 +32 +122 +212
+176
A0022002
40 Endress+Hauser
Liquiphant FTL33 Technical data
Ta
[°F] [°C] 1
+158 +70 2
Ta
+122 +50
Tp +32 0
–40 –40
[°C]
–20 0 +50 +100 +150
+90 TP
[°F]
–4 +32 +122 +212 +302
+194
A0020869
12.3 Process
NOTICE
‣ Note the pressure and temperature derating depending on the process connection selected.
Process temperature range –40 to +100 °C (–40 to +212 °F)
Lateral loading capacity Lateral loading capacity of the tuning fork: max. 200 N
Endress+Hauser 41