Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

MEP Technical

Academy, Bengaluru

HVAC
NOTES

www.deltatmep.com 0091-888 44 377 24


11/28/2023

REV-0
BATHROOM VENTILATION REV-0

Purpose of Ventilation
All homes need ventilation—the exchange of indoor air
with outdoor air—to reduce indoor moisture, odors, and
other pollutants.

BATHROOM VENTIALTION

1 2

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Purpose of Ventilation Design and Installation of Ventilation system

Exhaust ventilation systems work by Exhaust and air intake


depressurizing the building. positions

• Exhaust fans, or in the


case of a ducted
system; the exhaust
By reducing the inside air grille, should be
pressure below the outdoor air mounted as high as
pressure, they extract indoor possible and be
air from a house while makeup opposite the air intake
air infiltrates through leaks in into the room (which is
the building shell and through typically at the bottom
intentional, passive vents 3 of the door). 4

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

1
11/28/2023

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Design and Installation of Ventilation system


Ventilation Strategies
Make up air

Allowance must be made for replenishment of exhaust air. b) If the room is


The entry door having suitable clearance above the floor, below a roof that is
or to have an air intake grille in the door can achieve this. exposed to the
atmosphere, then a
Exhaust discharge to atmosphere roof-mounted fan
can be used to
a) If the bathroom/toilet has walls that are external, exhaust air directly
then a wall or window-mounted fan to the outside.
can be used to exhaust air directly
to the outside.

5 6

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Ventilation Strategies Ventilation Strategies

• If the room has neither


a). or b)., and is enclosed
within a building, then it
will be necessary to
exhaust the air through
a ducted system to the
outside atmosphere.

7 8

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

2
11/28/2023

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Ventilation Strategies Air flow rate requirements

9 10

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Air flow rate requirements Air flow rate requirements

It is generally acknowledged in the HVAC industry Toilet Ventilation Design (ASHRAE 62.1.2007)
that 25L/s air flow may be adequate for toilet
ventilation and odor control.

However, experience will tell that this air flow rate is


often insufficient to adequately ventilate a bathroom
when a shower is running, particularly in cool or humid
climates. For a bathroom with shower to be free of
condensation (and its inconvenient and harmful
effects) an exhaust rate of between 50 to 100 L/s is
recommended.

11 12

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

3
11/28/2023

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Air flow rate requirements Air flow rate requirements


Disc Valve size

Disc Valve (DIA) CFM


4 Inch 15- 100
6 Inch 30- 180
8 Inch 40- 240

13 14

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

BATHROOM VENTILATION REV-0


BATHROOM VENTILATION REV-0

Air flow rate requirements Air flow rate requirements

15 16

DOC NO: HVAC-CH-16 DOC NO: HVAC-CH-16

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

4
11/28/2023

REV-0
CAR PARKING VENTILATION REV-0

INTRODUCTION

CAR PARKING VENTILATION

1 2

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

INTRODUCTION INTRODUCTION
The car park ventilation system is required to
perform two functions:

a) Provide normal ventilation to prevent the build up


of carbon monoxide during the day-to-day
operation of the car park.

b) Provide smoke clearance in the event of a fire.

3 4

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

1
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

5 6

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

7 8

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

2
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

9 10

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM

11 12

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

3
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

13 14

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

15 16

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

4
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

17 18

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

19 20

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

5
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

21 22

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

23 24

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

6
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

25 26

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

27 28

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

7
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

29 30

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

31 32

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

8
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

33 34

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

35 36

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

9
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

JET VENT AXIAL FANS- IMPULSE FAN JET VENT CENTRIFUGAL FANS- INDUCTION FAN

Ø315MM – 32N – Thrust – 400 sqmt – 20m x 20m Thrust Newtons-50N- 500 sqmt- 25m x 20m
Ø400MM – 50N – Thrust – 500 sqmt – 25m x 20m Thrust Newtons-100N- 1000 sqmt- 50m x 20m

Note: 1.The coverage area varies supplier to supplier


37
2.The Exact position of fan will be decided after CFD38analysis
DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

For Example if the size of Carparking is 20 m x 10 m calculate


Exhaust Air flow, Fresh Air Flow & No of (Axial)

CFM = M3 x ACH / 1.7

Exhaust Air Flow = 50% / 100% --- 3529 CFM / 7059 cfm

Fresh Air Flow = 50% / 100% ---2829 CFM / 5647 cfm

In case of Fire: 4706 CFM (Fire Floor)

Note: There will be no Fresh Air

39 40

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

10
11/28/2023

CAR PARKING VENTILATION REV-0


CAR PARKING VENTILATION REV-0

JET FAN SYSTEM JET FAN SYSTEM

41 42

DOC NO: HVAC-CH-18 DOC NO: HVAC-CH-18

CAR PARKING VENTILATION REV-0

JET FAN SYSTEM

43

DOC NO: HVAC-CH-18

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

11
11/28/2023

REV-0
KITCHEN VENTILATION SYSTEM REV-0

KITCHEN VENTILATION SYSTEM

1 2
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

3 4
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

1
11/28/2023

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

Buildings with Kitchens


• Hotels
• Restaurants
• Hospitals
• Canteens
• Retails
• Residences
• Jails

5 6
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

System Design for Kitchens Basic Purpose of Kitchen Ventilation


• Air Conditioning • To provide a comfortable environment in the kitchen
• Ventilation
• To ensure the safety of the people working in the
• Fire Safety kitchen and building occupants by:
• Building Pressurization
• Refrigeration  Effective removal of Effluents which may include
gaseous, liquid and solid contaminants produced by
• Air Distribution the cooking process and products of fuel & food
combustion.
• Food Service Equipment's
 Effluents can be life threatening and flammable.
7 8
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

2
11/28/2023

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

Effluent Generation in kitchens Effluent Generation in kitchens


• Heat is a primary ingredients of kitchen effluents. • Primary objective of kitchen ventilation is to capture
and remove the air and effluents that constitute the
• 50% to 90% of the appliance energy input is released plume through an effective exhaust system.
in the form of a rising thermal plume (Convective).
Balance is released into surroundings space through • Heat radiated into space from the appliance must be
radiation. addressed by the space air conditioning system.

• This plume also contain most at of the goods and fuel


generation effluents.

9 10
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

A Commercial Kitchen Typical Kitchen Exhaust System

11 12
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

3
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Wall type exhaust hood


 Wall type exhaust hood
This type is only exhaust hood,
design for wall type application;
 Compensating wall type hood where all air removed comes
from outside the hood ( no make
 Island type exhaust hood up air through the hood).

 Compensating Island type Hood

13 14
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Wall type exhaust hood Wall type exhaust hood

15 16
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

4
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Wall type exhaust hood Compensating wall type exhaust hood


This are the supply and exhaust hood, designed for wall mounted
application; where temperature make-up air is delivered through
grills at the hood front face, internal side or perimeter downward
discharge.

17 18
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Compensating wall type exhaust hood Compensating wall type exhaust hood

19 20
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

5
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Compensating wall type exhaust hood Island type exhaust hood

This type is only


exhaust hood, design
for island type
application; where all
air removed comes
from outside the hood
( no make up air
through the hood).

21 22
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Island type exhaust hood Island type exhaust hood

23 24
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

6
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Island type exhaust hood Compensating island type exhaust hood


This are the supply and exhaust hood, designed for Island
application; where temperature make-up air is delivered through
grills at the hood front face, internal side or perimeter downward
discharge.

25 26
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS TYPES OF HOODS

Compensating island type exhaust hood Compensating island type exhaust hood

27 28
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

7
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

TYPES OF HOODS DESIGN CRITERIA

Compensating island type exhaust hood  An internal ambient temperature of 28°C maximum

 A maximum humidity level of 70%

 Internal noise level should be between:


• NR40 to 50/NC40 to 50 (Kitchens)
• NR35 to 45/NC35 to 45 (Restaurants, bars and cafeterias)

 Dedicated supply make-up air system which should supply


approximately 85% of the extract flow rate

 Humidity is hard to control. The HVAC system should be designed


to provide a good ventilation rate to maximize comfort

29 30
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

DESIGN CRITERIA DESIGN CRITERIA


 Dishwashing machines should be provided with dedicated extract  Duct Sheet Metal Gauge
ventilation to control vapor being discharged into the kitchen • 16 ga galvanized sheet
environment and to avoid potential health hazards caused by • 18 ga galvanized sheet
cluster flies that thrive in steamy conditions.
 Hood Construction 18 ga minimum
 The release of carbon monoxide is to be considered when designing
the system  Black Steel (BS) Duct is used for all kitchen ducts (hoods)

 Exhaust/Makeup Air 1500-2200 FPM velocity  Stainless Steel (SS) duct is used for laundry exhaust duct.
• 430 - Cheap & catch rust easily
• 304 - This type is used for hoods
 Duct to be terminated 40 inch above the roof
• 316 & 317 - Special and pure stainless steel for operation
theaters in hospitals. (317 SS is with low carbon)
 Cleanout to be provided at the base of the riser and every 20 feet

31 32
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

8
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

DESIGN CRITERIA

33 34
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION DESIGN REV-0

DESIGN CRITERIA DESIGN CRITERIA


Selection of Grease Filters
Grease filters should be provided in hoods to prevent of grease
accumulation inside the duct work, fan blades, walls & tops.

Grease accumulation inside the duct work and fan blades will
reduce the design efficiency of exhaust fan and will not work
properly.

Grease filter should be installed at an angle between 45 to 60


degree from the horizontal axis to prevent grease from dripping
back to the surface of cooking equipment.

35 36
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

9
11/28/2023

KITCHEN VENTILATION DESIGN REV-0


KITCHEN VENTILATION SYSTEM REV-0

DESIGN CRITERIA

440 cfm

37 38
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

39 40
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

10
11/28/2023

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

41 42
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

KITCHEN VENTILATION SYSTEM REV-0


KITCHEN VENTILATION SYSTEM REV-0

43 44
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

11
11/28/2023

REV-0
SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System

SMOKE MANAGEMENT SYSTEM

1 2
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


The objective of malls, atria, and other large area smoke control • Smoke from a fire in an enclosed area, rises in a plume to the ceiling.
systems is to prevent the area from filling with smoke as a result of
fire in the area or an adjoining area. • As it rises, air is entrained into it which in turn increases the volume of
the smoke.
Purging is used as the means to dilute and remove smoke.
• As the smoke reaches the ceiling, a layer is formed, which is referred to
In large areas the smoke produced is buoyant and rises in a plume as the smoke layer.
until it strikes the ceiling or stratifies because of temperature
inversion. • Control of this layer is the main task of a smoke ventilation system.

The smoke layer then tends to descend as the plume continues to


supply smoke.

Also, sprinklers can reduce the heat release rate and the smoke
entering the plume.

3 4
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

1
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


• Smoke can fill a room in just a few minutes. Thick smoke can obscure By using smoke ventilation and smoke barriers, drop down smoke curtains
exits signs and doorways, making escape hazardous and slow. for example, the smoke layer is contained above a pre-calculated height
(normally 3m minimum) and is either extracted naturally or by mechanical
• The typical speed of smoke travel is between 1 and 2 m/s. This can be means by ventilators installed in the ceiling.
faster than the escape speed of an occupant.

• When the smoke reaches a dead end, it will dip down and be drawn back
towards the fire, possibly confusing occupants and causing them to move
towards the fire.

5 6
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System

Without smoke ventilation. The red arrows depict the predicted With smoke ventilation.
movement of smoke, whilst the white arrows show the direction
of fresh air movement without smoke ventilation.

7 8
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

2
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System

9 10
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


a) Life Safety
FUNDAMENTALS OF DESIGN The system is to be designed to maintain tenable conditions on
escape routes and in other areas throughout the period they
are likely to being use by occupants of the building.
The fist question to be answered before attempting any smoke
extraction design is b) Fire fighting access / property protection
The system is to be designed to increase visibility for, and
"What is the purpose of this system?". reduce heat exposure to, trained Fire fighters thus allowing
earlier and less hazardous attack on the Fire. Such systems will
There are three basic possibilities. help to reduce property damage by increasing fire brigade
effectiveness.
a) Life Safety
b) Fire fighting access / property protection c) Smoke purging
c) Smoke purging The system is to be designed to enable smoke to be cleared
from a building after the fire has been brought under control.

11 12
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

3
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System

To Determine the Flow rate of Extraction Absolute Temperature of Smoke

V = Ms Ts Ts = To + dT
To Ps
Where
V = Required Air Volumetric flow rate CMS
Ts= Absolute Smoke Temperature in K
Ps = Smoke Density = 1.2 Kg/m3
To = Ambient Temperature in K
Ts= Absolute Smoke Temperature in K

To = Ambient Temperature in K

13 14
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


Calculating smoke temperature
Determine the Heat release:
The temperature rise of the smoke layer can be calculated
from:
Q= q x A
dT = Q/MCp
Where
where
q= Heat Release Kw/sqmt
Q = heat flow rate (kW)
A= fire Area in sqmt
dT = temperature rise of the smoke layer
above ambient (k)

Cp = specific heat capacity of the gases (1.01 kJ/kgK)

M = mass flow rate of smoky gases (kg/s)


15 16
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

4
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


Design Consideration
Heat release =
• 93 kw/M2 for furniture Design of Fire
• 100 kw/M2 for stored furniture in boxes .
Fire Area in Sqmt
• 320 kw/M2 for cellulosic
(Carton for packaging, paper and packaging)
• 260 kw/M2 for vehicles(car park), PETROL, dyes Fire area according to fire group as follows:-
• 390 kw/M2 for Wooden trash and sawdust
1-GROUP 1 ( 3X3M) = 9 M2
• 310 kw/M2 for electrical products
• 620 kw/M2 for cardboard boxes 2-GROUP 2 ( 4.5 X 4.5 M) = 20.25 M2
• 540 kw/M2 for miscellaneous goods and coated
• 210 kw/M2 for cardboard rolls 3-GROUP 3 ( 6.0 X 6.0 M) = 36.00 M2

4-GROUP 4 ( 9.0 X 9.0M) = 81.00 M2

17 18
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System GROUP 3


Smoke Extract System
Design Consideration - Spinning and weaving factories and
laundries and cleaning chemicals shops Having established the clear layer height in the mall,
Design of Fire - Kitchens and leather tanning factories
the mass flow rate of smoke can then be calculated.
- Grain mills and factories not bad products
and foam rubber factories and products
GROUP 1 and textile factories and carpet M = 0.19 P Y 3/2
Restaurants, bars, cafés and public facilities - Timber factories, carpentry workshops
- Slaughterhouses and power plants and dairy and factories soap and wax products, sugar
plants mills and factories fleeces Where
- Cement products factories and cement industry - Alazall studios and television

GROUP 2 GROUP 4 M = mass flow rate of smoke entering the


- Bakery and biscuit factories Include the following materials factories or
- Facilities chemical industry have few serious establishments deal
- Large garages and auto repair shops 1 - celluloid? smoke layer within the shop (kg/s)
- Auto accessories factories 2 - paints and adhesive materials and
- Factories Food and Alagxih saved bitumen
- Machinery plants, including light industry 3 - fireworks and floor coverings and foam P = the perimeter of the fire (m)
rubber
4 - Oil Industries and hangars
Y = the height from the base of the fire to the smoke layer
(m)
19 20
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

5
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System Smoke Extract System


Assumption

Smoke Plume Height ( Y ) - Atrium

Assume height (meter) of Smoke as below :

4m -1 floor
8m -2 floor
12m -3 floor
24m -6 floor

21 22
DOC NO: HVAC-CH-20 DOC NO: HVAC-CH-20

SMOKE MANAGEMENT SYSTEM REV-0

Smoke Extract System

Assumption

Smoke Plume Height ( Y )

The minimum height of


the smoke layer base
must be 2.5 m from the
mall floor to ensure
safety, and preferably
at least 3 m in a single-
storey mall.

23
DOC NO: HVAC-CH-20

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

6
11/28/2023

REV-0 REV-0

SMOKE MANAGEMENT SYSTEM

1 2
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMANT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Introduction Objective
A smoke Management system can be Designing a smoke management system requires agreement on the
classified into two systems: system objectives. The following is a partial list of potential system
objectives:
• Stairwell Pressurization System:
Keeping smoke out of escape routes using • Provide safety for the occupants
Pressure differentials or velocity
• Extend egress time
• Provide safe egress route
• Smoke Extract System: • Provide safe zones (tenable environment)
Removal of hot smoke from fire room
• Assist firefighters
• Limit property damage
• Limit spread of smoke away from fire area
• Clear smoke away for visibility
• Provide elevator usage during fires as an egress route for the
handicapped

3 4
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

1
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Definition Definition
SMOKE CONTROL - ANY method for controlling smoke movement SMOKE MANAGEMENT SYSTEM - The use of FANS or VENTS to keep
or dilution. buoyant smoke above the escape route
in the same space (BS5588 Parts 7 & 10).
CONTAINMENT - The use of physical barriers (BS5588 - Parts 1 to 3).
BUOYANCY - The tendency of warmer air or smoke to rise when
DISPOSAL - The continuous dilution of smoke to
located in cooler surrounding air. Caused by the warm
a safe concentration.
air being less dense than the cooler resulting in
CLEARANCE - Removal of smoke from a building after pressure differences.
the fire has been supressed.

PRESSURISATION - Blowing clean air into the escape route to hold back
smoke from fire (BS5588 Part 4).

DE-PRESSURISATION - Extracting hot smoke from the FIRE ROOM


to hold back smoke from the escape route
(BS5588 Part 4 Rewrite).

5 6
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION

7 8
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

2
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION
Objective

• The objective of stairwell pressurization


is to provide an acceptable environment
within a stairwell, in the event of a fire,
to furnish an egress route for occupants
and a staging area for firefighters.

• On the fire floor, a pressure difference


must be maintained across the closed
stair tower door to ensure that smoke
infiltration is limited.

• Also, adequate purging must be provided


to limit smoke density caused by
temporary door openings on the fire
floor.

9 10
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

11 12
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

3
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

13 14
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

15 16
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

4
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION STAIRWELL PRESSURIZATION

17 18
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION STAIRWELL PRESSURIZATION

19 20
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

5
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Application: Fire protection STAIRWELL PRESSURIZATION


Safety position:
CLOSED Fire protection Smoke extraction

Motorised fire dampers effectively Mechanical smoke extraction ensures


prevent fire and smoke from spreading. a clear view and delays the
flash-over.

21 22
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

Application: Smoke extraction


STAIRWELL PRESSURIZATION
Safety position: Safety position:
OPEN CLOSED CLOSED DOORS
Design Pressure
Building Height Fire Pressure Wind/Stack Effect Design Pressure
(m) (Pa) (Pa) (Pa)

5 8.5 8.0 25

25 8.5 10.5 25

50 8.5 13.0 50

100 8.5 19.5 50

150 8.5 29.5 50

Maximum pressure differential - 60 pa


BS 5588 part 4
23 24
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

6
11/28/2023

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION STAIRWELL PRESSURIZATION


CLOSED DOORS CLOSED DOORS
Pressure Control Typical leakage areas around doors
Type of Door Size Crack Leakage
Q = 0.827 AP 1/n + Losses Length (m) Area (m 2 )

Q = Volume of air required (m3 /sec) Single Leaf in Frame Opening 2 m x 800 mm 5.6 0.01
into Pressurised Space
A = Leakage area from the space (m /sec)
Single Leaf in Frame Opening 2 m x 800 mm 5.6 0.02
P = Pressure differential (Pa) Outwards

N = Leakage factor = (2 doors for etc) (1.6 for windows) Double Leaf with or without 2 m x 1.6 m 9.2 0.03
Central Rebate

Lift Door 2 m High x 8.0 0.06


Q = 0.827 A P 1/2 x 1.50 2 m Wide

25 26
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

SMOKE MANAGEMENT SYSTEM REV-0


SMOKE MANAGEMENT SYSTEM REV-0

STAIRWELL PRESSURIZATION STAIRWELL PRESSURIZATION


CLOSED DOORS OPEN DOORS
Establishing leakage areas Velocity Control Q = A x VE
1. Single Doors A = Net Free Area V = Velocity of Controlling Air (m /sec)
A = Area of Open Door (m )
2. Doors in Parallel AE = A1 + A2 + A3 + A4 Q = Volume of Air Required (m/sec)
- /2
1

3. Doors in Series AE =
[ 1 + 1 + 1 + 1
(A1 )
2
(A2 )
2
(A3 )
2
(A4 )
2] V = 0.75 m/sec (Means of Escape - BS 5588 Part 4)
= 2.00 m/sec (Fire fighting - BS 5588 Part 5)

27 28
DOC NO: HVAC-CH-19 DOC NO: HVAC-CH-19

www.deltaTmep.com dT-Ventilation Notes 0091- 888 44 377 24

7
IGBC AP Webinars
LEED GA Internships
Exam Prep. Workshops

Plumbing
Course

TechTalks
Fire Fighting Placement
Course Assistance
a n d mu ch mo re ...

30th Cross, K.V.Layout, Jayanagar-4th Block, East. Bengaluru-560011, INDIA


www.deltaTmep.com | +91 888 443 7724 | info@deltaTmep.com

You might also like