Content

1. Basics
 reasons (regulations, standards)
 function
 components

2. Dimensioning
 regulations
 calculation example

3. Product range
 ground installation
 free standing – full disposal
 free standing - partial disposal

4. Installation
 ventilation, filling device
 sampling pot, remote control,
 suction pipe
Haustechnik

1. BASICS
Haustechnik

Basics

S
y
s
t
1.2

e
Haustechnik

Basics

Waste water containing grease can cause…

…pipe obstruction. …formation of corrosion and …negative effect on treatment


noxious stench. plants.
Haustechnik

Basics

Grease separator plants have to be used if


animal and organic fats and oils have to be
retained.
This applies to commercial and industrial
establishments, where animal and organic fats
occur…
Haustechnik
Basics -
Regulations

Grease separators pursuant to EN 1825


(Germany = DIN EN 1825 - United Kingdom = BS EN 1825

Other national standards


EN 1825 – Part 1 EN 1825 – Part 2
(Example DIN 4040-100)
Manufacturing principles Dimensioning and
Installation, operation
and testing of installing of
and maintenance of
grease separators grease separators
grease separators
Haustechnik
Basics –
operating conditions

EN 1825 – Part 2, chapter 4 recommends the usage of grease


separators in…

• restaurants
• hotels
• canteens
• butcheries
• students‘ refectories
• grill kitchens
• slaughterhouses
• sausages production
• oil mills
• margarine factories
Haustechnik
Basics –
operating conditions

…but what about…

• block of flats ?
• fairs ?
Haustechnik
Basics –
operating conditions

EN 1825 – part 2, chapter 4 points out that grease separators may


have no satisfying effect when used in…

• dairies
• cheese dairies
• fish industry (!)
• „pure“ dish washing
factories
• colour industry

 Wastewater treatment
Haustechnik

Function

Grease separator - functional principle

Grease

Sludge

Precondition: The separator has to be filled with water. Otherwise no separation effect can be guaranteed!
Haustechnik

2. Construction Principles
According to EN 1825,
Part 1
Haustechnik

Components

Functional diagram of grease separator


according to EN 1825, part 1

Grease storage capacity min. 40 l x NS


Grease surface 0.25 m2 x NS

Inlet Outlet

Grease layer

Separation compartment
Inlet Outlet
baffle baffle

Imaginary sludge trap

Capacity = 100 l x NS Capacity of separation compartment is


dependent on hydraulic test.
In the case of meat processing plants Maximum permissible hydrocarbons
Capacity = 200 l x NS in the outlet: „less than 25 mg/l“
Haustechnik

Nominal Size – Determination of main dimensions

Nominal Size Sludge trap Separation Separation Grease storage


volume compartment compartment volume
(volume in litres) (minimum surface (minimum volume in (minimum volume in
area in m2) m3) m3)

NS NS x 100 0,25 x NS 0,24 x NS 0,04 x NS


Haustechnik

Material selection

Stainless Steel Polyethylene Reinforced Concrete

- easy handling - permanently highly


- no fire risk - low heat conduction loadable statically and
- high temperature - high resistance to dynamically
resistance chemical influences - highes shape stability
- hygenic material - disposal-friendly surface towards inside and
- absolute UV resistance - easy after-treatment outside
locally - nearly any installation depths

 Use esclusively for  Use for free-standing  Use esclusively for


free-standing installation and ground installation ground installation
Haustechnik

Material selection

Sealant

„Only sealant made from rubber (elastomeric material) must be


used.“

„Cement mortar must not be used as sealant.“

(EN 1825-1, Chapter 5.2.6)


Haustechnik

Identification

Type Plate

Content:

-EN 1825
-Nominal Size (NS)
-Separator capacity (in litres or m3)
-Sludge trap capacity (in litres or m3)
-Grease storage volume (in litres or m3)
-Maximum height of grease layer (in mm)
-Year of production
Haustechnik

3. Dimensioning according
to EN 1825, part 2
Haustechnik

Dimensioning (EN 1825)

Types of dimensioning according to EN 1825

-per kitchen equipment

-based on meals per day

-based on number of slaughtered animals


Haustechnik

Dimensioning (EN 1825)

Dimensioning based on meals per day:


(example values see „Red book“, page 187 )
Haustechnik

Dimensioning (EN 1825)

Dimensioning based on meals per day:


(example values see „Red book“, page 187 )

Meals per Consumpt/meal F=sporadic load


day factor Waste water qty.

200 x 100 l x 5 = 100,000 l

100,000 litres = 3.0864 l/s (max. waste water inflow


QS=
9 oper.hrs.x 3.600 sec. to separator)

NS = QS x fd x ft x fr
Haustechnik

Dimensioning (EN 1825)

fd = density of ft = temperature of fr = cleaning agents


waste water water

fd = 1 (for density until 0,94 g/cm3) ft = 1 (temperature until 60° C) fr = 1 (no agents)
fd = 1,5 (for density over 0,94 g/cm3) ft = 1,3 (temperature over 60° C) fr = 1,3 (agents)
fr = 1,5 (hospitals)

 In „normal“ kitchens  Depends normally on  Could be even higher in


(restaurants, hotels etc.) always character of dish washer. hopitals, has to checked
assume density 0,94. together with planning
offices.

NS = QS x fd x ft x fr
NS = 3.0864 x 1 x 1.3 x 1.3 = NS 5.22  NS 7
Haustechnik

Dimensioning (EN 1825)

Dimensioning based on number of slaughtered animals:


(example values see „Red book, page 190)
Haustechnik

Dimensioning (EN 1825)

Dimensioning based on number of slaughtered animals:


(example values see „Red book, page 190)

Sausage Unit-specific water F=sporadic load


quantity per kg
production sausage production
factor Waste water qty.

200 x 15 l x 35 = 105,000 l

105000 litres = 3.645 l/s (max. waste water inflow


QS=
8 oper.hrs.x3.600 sec. to separator)
Haustechnik

Dimensioning (EN 1825)

fd = density of ft = temperature of fr = cleaning agents


waste water water

fd = 1 (for density until 0,94 g/cm3) ft = 1 (temperature until 60° C) fr = 1 (no agents)
fd = 1,5 (for density over 0,94 g/cm3) ft = 1,3 (temperature over 60° C) fr = 1,3 (agents)
fr = 1,5 (hospitals)

 In „normal“ kitchens  Depends normally on  Could be even higher in


(restaurants, hotels etc.) always character of dish washer. hopitals, has to checked
assume density 0,94. together with planning
offices.

NS = QS x fd x ft x fr
Double-sized
NS = 3.645 x 1 x 1.0 x 1.3 = NS 4.74  NS 7 sludge trap!
Haustechnik

Dimensioning (EN 1825)

Dimensioning per kitchen equipment (example see Red book, page


183)
Haustechnik

Dimensioning (EN 1825)

Dimensioning per kitchen equipment (see Red book, page 183)


Equipment Number qi l/s (n x qi) Simultaneity Grey water
factor Zi (n) Qs
Boiler outlet 25 mm 10 1 10 l/s 0.20 2

Boiler outlet 50 mm 15 2 30 l/s 0.20 6

Tilting boiler outlet 70 mm 4 1 4 l/s 0.21 0.84

Tilting boiler 100 mm 5 3 15 l/s 0.20 3

Wash basin without odour seal, 50 mm 8 1.5 12 l/s 0.20 2.4

Dishwasher 6 2 12 l/s 0.30 3.6

Tilting frying pan 4 1 4 l/s 0.21 0.84

High-pressure cleaner 2 2 4 l/s 0.31 1.24

Vegetable wash units 3 2 6 l/s 0.25 1.5

Outlet valve DN 20 8 1 8 l/s 0.20 1.6

Outlet valve DN 25 6 1.7 10.2 l/s 0.20 2.04

Sum Qs 25.06 l/s


Haustechnik

Dimensioning (EN 1825)

Dimensioning per kitchen equipment:

NS = QS x fd x ft x fr
NS = 25.06 x 1.0 x 1.0 x 1.3 = NS 37.59  NS 40
Haustechnik

Dimensioning (EN 1825)

Dimensioning according to EN 1825 vs. dimensioning according to DIN 4040

Grease layer
Grease layer

Separation compartment
Sludge
trap Separation compartment

Imaginary sludge trap

Grease separator Grease separator


according to DIN 4040 according to EN 1825
(old German standard)
Haustechnik

Dimensioning (EN 1825)

…which means:

Dimensioning according to EN 1825 = Choose separator according to EN 1825

Dimensioning according to DIN 4040 = Choose separator according to DIN 4040

…but:

Dimensioning according to EN 1825 = Never choose separator according to DIN 4040!

Dimensioning accordint to DIN 4040 = Never choose separator according to EN 1825!


Haustechnik

3. PRODUCT RANGE
Haustechnik

Product range

Two possibilities

Free standing
Ground installation installation
Haustechnik

GROUND INSTALLATION
Haustechnik

Product range

Ground installation - properties

• Separator is installed outside a building in the ground


• Load class A,B or D possible
• NS 1 – 10 (made from polyethylene)
• NS 1- 40 (made from reinforced concrete)
Haustechnik

Product range

Ground installation – example

Kitchen facilities
Haustechnik

Product range

Ground installation – product series ECO FPI

• separator made from polyethylene


• cover made from concrete
• available in NS 1 – 10
• load class B or D
Haustechnik

Product range

ECO-FPI NG 4

Haustechnik

Product range

ECO-FPI NG 4
Haustechnik

Product range

ECO-FPI NG 4
Haustechnik

Product range

ECO-FPI NG 4
Haustechnik

Product range

ECO-FPI NG 4 with sampling shaft


Haustechnik

Product range

ECO-FPI NG 4 with direct suction


pipe R
Haustechnik

Product range

Ground installation – product series LIPUMAX/LIPUSED

• separator made from reinforced concrete


• cover made from concrete
• available in NS 1 – 25 (LIPUMAX)
• available in NS 20 – 40 (LIPUSED)
• selectively available with inner coating (polyethylene)
Haustechnik

Product range

FREE STANDING
INSTALLATION
- FULL DISPOSAL
Haustechnik

Product range

Free standing installation - properties

• separator is installed inside a building, it stands free


inside a cellar room (or something similar)
• made from polyethylene or stainless steel
• in round or oval shape
• available in NS 1 – 10 (oval shape)
• available in NS 1 – 20 (round shape)
Haustechnik

Product range

Free standing installation - example

Kitchen facilities
Haustechnik

Product range

Free standing installation – product series


Material stainless steel Material polyethylene

dn 1 LIPUREX-O/-OD ECO-JET-O/-OD
N a eg Basic version:
no at
e is s standard design
re no LIPUREX-R/-RD ECO-JET-R/-RD
u v is Extension stage 1:
ci ne
e sa tx with direct disposal
B e ECO-JET-G/-GD
Extension stage 2:
P with direct disposal, high-pressure
cleaning and manual control
r 3/
2 Extension stage 3:
LIPURAT-OS/-OA HYDROJET-OS/-OA
o se
ga with direct disposal, high-pressure
g ts LIPURAT-RS/-RA HYDROJET-RS/-RA cleaning and automatic control
r no
is
a ne LIPURAT-OSE/-OAE HYDROJET-OSE/-OAE
tx
m E
m Legend:
s
t -O : oval shape -S : plus high-pressure cleaning and
-R : round shape manual control
r -G : separated chambers -A : plus high-pressure cleaning and
u -D : plus direct suction pipe automatic control
k -E : plus disposal pump
Haustechnik

Product range

Basic version

Standard design

Advantages
low purchase price

easy bringing in and assembly

no wear and tear parts

LIPUREX®-O
Haustechnik

Product range

Extension stage 1 Direct disposal

With direct disposal

Advantages
Higher comfort thanks to suction appliance

No odour nuisance during disposal process

Trouble-free handling

No wear and tear parts


LIPUREX®-OD
Haustechnik

Product range

Extension stage 2
With direct disposal, high-pressure
inner cleaning and manual control Option Suction pipe
High pressure cleaning

Disposal pump

Advantages
Hydro-mechanic inner cleaning
by means of high-pressure pump

Suction or pumping, crushing and


cleaning in one working process

Even following disposal, opening is


not required

LIPURAT®-OS
Haustechnik

Product range

Extension stage 3
With direct disposal, high-
pressure inner cleaning and Option Suction pipe
High pressure cleaning
automatic control

Advantages Remote control Switch box


Fully automatic programme
control

Easy operation possible


via remote control

Optimum system for a


problem-free disposal

LIPURAT®-OA
Haustechnik

Product range

FREE STANDING
INSTALLATION
- PARTIAL DISPOSAL
Haustechnik

Product range

Function of separator with partial disposal

Inlet
90 % of total volume is Outlet
...not removed

No grease deposits


...thanks to short stay in
...separator

Disposal without
...interrupting operation
...and without suction
...vehicle Grease

Sediments
Haustechnik

Product range

Partial disposal

Stainless steel

Lipatomat
Haustechnik

Product range

Installation of separator with partial disposal

1 Grease separator LIPATOR NG 4


Connection to sewer 2 Sampling device
3 Lifting plant
4 Grease collecting container
5 Sediments collecting container
6 Ventilation
7 Ventilation
Haustechnik

4. INSTALLATION
Haustechnik

INSTALLATION

Ventilation:
1. Inlet and outlet have to be adequately
aerated!

2. Ventilation to be taken above the roof

3. All connecting cables exceeding 5 m


have to be separately aerated

4. If the length of the inlet pipe exceeds


10 m and there is no separate venti-
lated connecting cable available, a
ventilation pipe has to be provided to
the inlet pipe directly in front of the
separator plant!
Haustechnik

INSTALLATION

Prevention of
grease deposit:
1. A thermal insulation may be ne-
cessary in the case of inlet pipes
led through cool cellar rooms!

2. A heating may be necessary in


the case of inlet pipes led through
building parts exposed to frost,
as e.g. underground garages!

3. The temperature of the heating


should be adjustable via a
thermostat.

4. In the case of heated rooms and


frostfree laid cables, no additional
measures are required!
Haustechnik
Installation as per
DIN V 4040 part 2

Inlet:
1. Transition into horizontal pipes
has to be performed by two
45 º bends!

2. The intermediate section must be


at least 250 mm long!

3. Then, a calm region has to be


provided, the length of which
should be at least 10 times the
nominal width of the inlet pipe!

4. Inlet pipes must have a minimum


slope of 2 % (1:50)!
Haustechnik

INSTALLATION

wrong

KPMG Munich
Haustechnik

INSTALLATION

right

AGFA Munich
Haustechnik

INSTALLATION

Emptying:
1. Unless stipulated otherwise, grease
separator and sludge trap should be
emptied, cleaned and re-filled with fresh
water at least once a month, preferably,
however, fortnightly!
Haustechnik

INSTALLATION

Emptying:
Haustechnik

INSTALLATION

Sampling:
1. Behind the separator, a sampling
possibility has to be provided to
check the waste water values!
Haustechnik

INSTALLATION

Lifting plant:
1. Grease separator plant, the static
water level of which lies beyond
the backflow level, have to be
drained via a following lifting plant!

2. A twin lifting plant has to be


installed in the case of industrial
and commercial areas!
Haustechnik

INSTALLATION

Backflow loop:
1. The pipe bottom of the backflow
loop has to be led above the
backflow level!

You might also like