2 CT CORE ADEQUACY FOR BUS SECTION PROTECTION RELAYS SIL-A (50, 51, 51N, 50BF, 74, 86)
Nominal frequency(F): 60 Hz
CT TYPE: T1/2
CT RATIO 1250/1A
RELAY DATA:
MANUFACTURER: FANOX
TYPE: SIL-A
Where
RALF = Rct + Rwire + Rrelay
The effective wire burden will be calculated for a two wire connection of CT and relay according to length, cross-section, copper resistivity and secondary nominal current:
Wire burden:
Length lwire = 5m (Approximate )
2
Cross-section awire = 2.5 mm
2
Resistivity(Cu) pcu = 0.00741 Ohms mm /m
REV.A DWG.NO:65-QC40-J-089 1 OF 2
13.8KV PUMPING STATION PS A1
Pwire = ((k*lwire*pcu)/awire)*(Isn^2)
= 0.030 VA
Rwire = Pwire/I sn^2
= 1.500 ohms
= 6.5+0.03+1.5
RALF = 8.030 ohms
= 8.03 x 10
VALF = 80.3 volt Result-1
= (1.4/1.6)x(20/1^2)x(10)
VSAT = 175.000 volt Result-2
Ual(Required) = If*(Rct+Rwire+Rrelay)
INFERENCE:
Condition-1 is fulfilled i.e. Result-1 (VALF) < Result-2 (VSAT). However Condition-2 is not fullfilled i.e Result-4 (Ual(Available)) < Result-3 (Ual(Required))
REV.A DWG.NO:65-QC40-J-089 2 OF 2