Professional Documents
Culture Documents
Quantity of Electricity
Quantity of Electricity
In every electric circuit there are three basic quantities that Electromotive force – This is the force that causes the
are always present. These quantities are:- CURRENT, current to flow through the conductor. It is represented by
ELECTROMOTIVE FORCE and RESISTANCE. the abbreviation e.m.f and is measured in volts, unit symbol
V
Current – This is the movement of electrons through a
conductor. Electric current is represented by the capital Resistance – This is the opposition to the flow of current.
letter I and is measured in amperes, shorten form amp. This limits the flow of current. It is represented by the letter
The unit symbol is the letter A R, and is measured in ohms, unit symbol, the Greek letter
omega (W)
QUANTITY OF ELECTRICITY
the amount of current is represented by the letter I and is Eg. 2 A current of 10 amp flows through a conductor and
measured in amperes. set up a charge of 0.5C, calculate the time taken.
It is said that one coulomb (1C) will pass through a circuit
when a current of one amp (1A) flows for one second (1 t=Q/I
sec). = 0.5
10
Q = I ´ t = coulombs = 0.05 sec.
I=Q/t
= 600 / 15 = 40A
Electric systems involve the uses of circuits, the construction The Source-- The function of the source is to provide
of circuits and classifying the principal parts that are to be energy for the circuit. Eg. Generator, battery.
found in every circuit.
The Load-- The function of the load is to use up the energy
that is provided by the source. Eg. Radio and refrigerator.
AN ELECTRICAL CIRCUIT The Control Device-- The function of the control device is
to open and close (make and break) the path for current to
flow. Eg. Switch , push button
A circuit is an assemblage of conductors and devices
through which current flows or it’s a complete path for The Transmission System-- The function of the
transmission system is to carry energy from the source to
current flow. A basic electrical circuit consists of four main the load. Eg. Conductor, wire (pg 77)
parts namely:
The source; load; Control device and the transmission Control device
system.
Source Load
Transmission system
A German Physicist, GEORGE SIMON OHM carried out an Eg.1 Calculate the current flowing through a conductor of
experiment to determine the relationship between current, 30 ohms (30W) when it is connected to a 120V
voltage and resistance. supply.
He found out that, and make it his law (OHMS LAW) stating
that the current flowing through a conductor is directly I = V/R
proportional to the voltage across it ends but is inversely = 120/30
proportional to its resistance at a constant temperature. = 4A
This relationship can be express in a mathematical formula:
Eg. 2 Calculate the voltage that will cause a current of 10A
I = V/R to flow through a conductor (resistance) of 50 ohms
Where I = current in ampere (A) (50W)
Where V = voltage in volts (V)
Where R = resistance in ohms (W) V=IxR
= 10 x 50
This formula can place in a triangle called the magic = 500V
triangle.
Eg. 3 A current of 20 amp flows through a resistor when it
V is connected to a 600v supply. Calculate the
resistance.
I R
R = V /I
To find any of the three (3) quantities (that is I, V and R) = 600/20
when any two are given you would cover the letter that = 30W
represents the quantity that is to be found and the remaining
two letter will give the formula.
ELECTRIC POWER AND ENERGY
Power (P) is the rate at which work is done, measured in Apparent power (S) is the product of total voltage and total
watt; (W). While energy (W) is the ability to do work, current, measured in volts-ampere, thus the formula:
measured in joules; (J)
The power dissipated by a resistor (or any load) in a d.c.
circuit can be determined by the given formula S = V x I = Volts-ampere; (VA)
P = V x I = watt True power (P) which can also be called real power or the
active power, measured in watts, is always less than the
From the formula P = V x I apparent power (S) is determined by the formula
By substituting I x R for V
we get P = I x R x I P = V x I x p.f.
\ P = I2 R \P = V I cos. q
Substituting V / R for I, We get P = V x V / R = S cos. q
\ P = V2 / R Since the voltage and the current are in phase for a resistor
in an a.c. circuit and the power factor power factor is unity
The total power dissipated by resistors (loads) in series or (1), therefore the power dissipated by a resistor whether in
parallel can be determined by the same formula; an a.c. or d.c. circuit, is determined by the same formula and
Pt = P1 + P2 + P3 … is the same.
4
POWER FACTOR cosine of the phase angle form between the applied voltage
and the current. Therefore
Power factor is defined as the ratio between the actual p.f. = P/S
POWER TRIANGLE
S2 = Q2 + P2 Q
Power triangle
ENERGY
Energy is defined as the ability to do work. Electric energy The watt-second is too small a unit, thus the more
is the product of the useful power and time. Energy is convenient unit is the kilowatt-hour (kWh), and is on the
represented by the capital letter W and its basic unit of basis of kilowatt-hour we pay our electricity bill (light bill).
measurement is the joule (J)
Since energy is the product and time, and time is measured One kilowatt-hour (1kWh) = 1000 Wh
in seconds, therefore energy is measured in watt-second.
One watt-second is equal to one joule.
5
THE KILO-WATT-HOUR METER.
The kilo-watt-hour meter in short (kWh) is put into an One watt sec = one joule
instillation to record the consumption of electric energy. This 1W s = 1J
meter give the reading in kilo-watt-hour (kWh), which is the Because the watt-sec is two small a unit the kWh is used
product of power in (kilo-watt) and the time consumed (in instead.
hours). The basic unit for energy is joules (J), which is the
product of power and time. 1kWh = 3600000J
Power x time
Watt x sec It is on the basis of kilo-watt-hour (kWh) you pay your
W x s = WS = J electricity bill. Your electricity bill is determined by the
energy you consume multiplied by cost per each unit.
(KWh).
6
RESISTORS AND RESISTANCE
Or
And is labeled “ R ”
FACTORS AFFECTING THE RESISTANCE OF
The resistance of a resistor is said to be linear if the current A CONDUCTOR
through the resistor is proportional to the potential difference
(p.d) across its terminals. There are four things that will affect the resistance of a
If the resistance should vary with the magnitude of the conductor. These are:
current or the voltage then the resistance is said to be linear.
Ø The type of material used to make the conductor
Ø The length of the conductor
Ø Cross sectional area (c.s.a) of the conductor
Ø Temperature surrounding the conductor
TYPES OF RESISTORS
Resistors are made in a variety of ways but they all fall into
the categories of either Fixed or Variable resistors. Most
fixed resistors are used in electronic circuits and are made
from carbon moldings or from metal oxide film. Wire wound
resistors maybe wound on what looks like a large washer
made from an insulated material. An arm is mounted
through the center of the washer. By rotating the arm along
the length of wire between the ends; where the arm started
and the point where the arm is, the resistance is varied.
7
RESISTIVITY
Certain materials permit the reasonable free passage of Where R = resistance in ohms (W)
electric current and are termed conductors. While others r = resistivity in ohm-metre (Wm)
oppose such a free passage and are called insulators. L = length in metre (m)
These abilities are simply taken relative to one another and A = area in meter-square (m2)
made of two wire with resistance of 1W for every 10cm of its sectional area of 1mm2. Calculate its resistance.
length, if the wire is made of 20cm long, then effectively (r = 1.57 x 10-8)
R= rL
A
8
TEMPERATURE CO-EFFICIENT OF RESISTANCE
The resistance of all pure metal is directly proportional to the Eg 1. A copper conductor having resistance of 40W at 400C.
change in temperature. While carbon, electrolytes and Calculate its resistance at 600C ( temperature coefficient of
insulating material resistance is inversely proportional to the resistance of copper is 0.004)
change in temperature. Directly proportional means
resistance increase with the increase in temperature and R2 = R1 [1+ µ ( t2 – t1 )]
decrease with the decrease in temperature. While inversely = 40 [1+ 0.004 (60 – 40]
is vise versa. Therefore all pure metals will have a positive = 40 [1+ 0.004 ( 20 )]
temperature co-efficient, while carbon, electrolytes and = 40 (1+ 0.08)
insulating material will have a negative temperature co- = 40 (1.08 )
efficient. = 43.2W
Certain alloy such as manganin shows no change resistance Eg. 2 A copper conductor having resistance of 40W at
for considerable variation of temperature. This means it’s 600C. Calculate its resistance at 400C (temperature
considered to have a zero (0) coefficient. The ratio of the coefficient of resistance of copper is 0.004)
change of resistance per degree change of temperature to
the resistance at some definite temperature is called R2 = R1 [1+ µ ( t2 – t1 )]
temperature co-efficient of resistance. A standard = 40 [1+ 0.004 (40 – 60)]
temperature of 200c which is roughly the average at = 40 [1+ 0.004 (- 20 )]
atmospheric temperature is considered 100m temperature. = 40 (1+- 0.08)
Resistance of a material is due to the change in temperature = 40 ( 0.98 )
can be determine by the formula. = 36.8W
9
THE SERIES CIRCUIT
A series circuit is one that has all its components (eg. Rt = R1 + R2 +R3
resistor) connected one after the other, in other words end- = 10 + 20 +30
to-end, and has only one path for current flow. Therefore if = 60W
one component is removed or damage or the path is made
open this will affect the entire circuit causing all components If two or more identical resistors are connecting in series,
to stop working. then the resultant resistance can be determined by the given
formula.
Rt = nR,
RESISTORS IN SERIES
Where R = the value of any one resistor and n = the number
of resistors.
When resistors are connected in series to form a circuit,
example the diagram below, the resultant/effective
resistance of such circuit is the sum of the individual
resistors value and can be determined by the formula. Rt =
R1 + R2 + R3 ............
R1 R2 R3
Where Rt = total resistance When a voltage is applied to a series circuit, that voltage
R1 = resistance in resistor one (total voltage Vt) is shared amongst the number of
R2 = resistance in resistor two components (eg. resistor) connected in series. Therefore,
R3 = resistance in resistor three the total voltage is the sum of voltage drop across each
resistor, thus giving the formula:
Note: Any number of resistors can be connected to form a Vt = V1 + V2 + V3........
series circuit.
Where V1 = the total voltage drop across resistor one
Eg. Three resistors of the values 10W, 20W and 30W V2 = the total voltage drop across resistor two
respectively are connected in series. Calculate their V3 = the total voltage drop across resistor three
effective resistance
10
The current flowing in a series circuit is constant (one value) (a) Rt = R1 + R2 (b) It = Vt / Rt
through out the entire circuit. That means the current is the = 10 + 15 = 100/ 25
same through each resistor also the same as the value = 25W = 4A
flowing from the source. Thus the formula
It = I1 = I2 = I3.........
(c) V1= I1 x R1
11
THE PARALLEL CIRCUIT
1 = 1 + 1
A parallel circuit is one that has more than one branch with a Rt R1 R2
load. That means that it has one main path for current flow 1 = 1 + 1 (find the L.C.M)
and several sub-paths. When resistors are connected in Rt 10 15
parallel (or any other load). They are connected across each 3 + 2 = 5
other and each is connected across the source. e.g. the 30 30
circuit diagram below.
To find Rt we invert 1 to become = Rt
Rt 1
also invert the fraction which is 5 / 30 to become 30 / 5
\Rt = 30 / 5 (b) It = Vt / Rt
R1 = 6W = 48 / 6
= 8A
R2
Rt = R / n,
(a) their effective resistance (Rt)
Where R = the value of any one resistor and n = the number
(b) the total current flowing (It)
of resistors.
12
VOLTAGE AND CURRENT IN PARALLEL Or transposing the formula It = I1 + I2 for I2
we get I2 = It I1
CIRCUIT –
Vt = V1 = V2 = V3........ and
It = I1 + I2 + I3....... CURRENT AND VOLTAGE DIVIDER RULE
Eg. Two resistors of 12W and 8W are connected in parallel The current divider rule is for a parallel circuit only, while the
across a 24V supply. Calculate voltage divider rule is used in series circuit only
R1 + R2 = 24 / 4.8 Rt
= 5A
= 12 x 8
12 + 8
= 96/ 20
= 4.8 W
Substituting Vt for V2
\ I2 = Vt / R2
= 24 / 8
= 3A
13
KIRCHHOFF’S LAWS
First Law (current law) states that the sum of current(s) Second Law (voltage law) states that, the sum of voltage
following into a junction of the circuit is equal to the sum of drop around any closed circuit is equal to the voltage applied
I1 I4
I2 I5
I3 I6
I1 + I2 + I3 = I4 + I5 + I6
14
TYPES OF CURRENT
There are two types of current. Direct current can be obtained from a cell or battery or
from a conversation of a a.c. to the d.c. through device
Ø Alternating current (a.c.) known as DIODES.
Ø Direct current (d.c.)
Alternating current flows in one direction and then the
These two current can be define as: other. This happens every half cycle (1800), the
repetitive current is represented by sine waves. The
Direct current – a current that flows only in one curves relating current the time is known as wave
direction. And is represented by the symbol form. Some of the waveforms are as follows.
An E.M.F. (electromotive force) can be induced into a coil When the armature is in parallel with the line of force it will
(conductor) by either rotating the coil/ conductor uniformly not be cut by the magnetic field therefore there will be no
within a magnetic field or the magnetic field across the induced E.M.F. The magnetic field is usually obtained
coil/conductor. An A.C. voltage is usually obtained from a between two magnets.
generator.
The induced E.M.F. will reach its maximum value when the
armature is being cut at 900 by the magnetic field. The
A generator is a device that converts mechanical energy
induced E.M.F. will depend on:
to electrical energy.
(a) the speed of rotation.
When the armature (the rotating coil) is rotated within the (b) the number of turns in the coil or the length of the
magnetic field it will be cut by the magnetic line of force, and conductor.
therefore an E.M.F. will be induced into the coil. (c) the strength of the magnetic field.
15
+ Peak
Peak –to-
Peak Crest
1 2 2 2 3 3 3 t
8 1 4 7 0 3 6
0 0 0 0 0 0 0
30 60 90 120 150
Wavelength - Peak
16
SINGLE PHASE SERIES CIRCUIT
Consider a circuit having a resistor of “R” ohms is exactly the same as that of the voltage, also the two
connected across the terminal of a a.c. source as in the quantities are in phase with each other i.e., they start at
figure below. the same time, reach their maximum at the same time,
and complete a cycle at the same time as depicted in
the figure below.
R
Voltage
Current
Resistor in a.c. circuit
t
If the value of the alternating voltage at any instance is
“ V ” in volts, then the value of the alternating current at
that instant can be determined, by the formula
Voltage and current waveform for a resistive circuit
I =V / R.
Consider the effect of an alternating current flowing in purely inductive circuit (or the current through the
through an inductor having an inductance of “ L ” Henry inductor) will lag the voltage by 900.
and a negligible resistance, as in the figure below.
V I
L
Direction of rotation
Inductor in a.c. circuit
VL
17
RESISTANCE AND INDUCTANCE IN SERIES
Consider a resistor of pure resistance and an inductor The combination of both components will give an
(with negligible resistance) of pure inductance opposition to alternating current called, IMPEDANCE
connected in series to an alternating current source as (Z), and this can be determined by the given formula:
in the figure below.
Z2 = R2 + X2
L
The opposition that the inductor offers to the rate of Eg. An inductor of 0.5H and a resistor of 50W are
change to alternating current is called inductive connected in series, then to a 240V-50HZ supply.
reactance ( XL ) measured in ohms and is determined Calculate the impedance of the circuit.
by the given formula:
XL = 2pƒL
XL = 2pƒL = wL = W
= 2 x 3.142 x 50 x 0.5
= 157.1W
Where p = 3.142
ƒ = Frequency in hertz (HZ)
Z2 = R2 + X2
L = inductance, in Henry (H)
= ( 50 )2 + ( 157.1 )2
w = Angular velocity
= 2500 + 24680.41
= 27180.41
\Z = Ö27180.41
=164.865W
18
ALTERNATING CURRENT IN A CAPACITIVE CAPACITANCE & RESISTOR IN SERIES
CIRCUIT
Consider a resistor (purely resistance) and a capacitor
Consider the effect of an alternating current flowing (purely capacitive and negligible resistance) connective
through a capacitance of “F” farad and negligible to an alternating current source as in the figure below.
resistance, as in the figure below
C
C
R
Capacitor in a.c. circuit The opposition that the capacitor offers to the rate of
change of current is CAPACITIVE REACTANCE ( XC ),
Assuming the circuit to be purely capacitive, the applied and is measured in ohms. Capacitance can be
voltage will reach its maximum value a quarter of a determined by the given formula:
cycle (900) after the current. This means the current in
XC = 1
purely capacitive circuit (or the current through the
2 pƒC x 10-6
capacitor) will lead the voltage by 900.
If 10-6 is brought to the top, it becomes 106
\ XC = 106
I V 2 pƒC
The total opposition of the combined circuit is called
impedance. (Z) measured in ohms and can be
determined by the given formula:
19
RLC SERIES CIRCUIT
Consider a resistor, inductor, and a capacitor connected in If the resultant reactance is more inductive, then the current
series then connected to an A.C. supply as in the figure will lag behind the voltage by an angle between zero and
below. 900. If the resultant reactance is more capacitive, the
current will lead the voltage by an angle between zero and
L R C 900.
Z2 = R2 + X2
Z2 = R2 + ( XL - XC ) 2
Or R2 + ( XC - XL) 2
Cos-1 R / Z
Where R / Z = the power factor = Cos. q
20
Eg. A 50W resistor, a 300µ F capacitor and an inductor of
0.5H are connected in series, then to a 240V-50HZ
supply. Calculate
a. the impedance of the circuit
b. the total current flowing in the circuit
c. the phase angle
d. the voltage across each component
XL = 2pƒL
= 2 x 3.142 x 50 x 0.5
= 157.1W
XC = 106
2 pƒC
= 106
c. q = Cos-1 R / Z
2 x 3.142 x 50 x 300
= Cos-1 50 / 149.132
= 106 / 94260
= Cos-1 0.335
= 16.6W
= 70.4270
\The current lags behind the voltage by 70.4270
X = XL – XC (since XL is greater than XC )
= 157.1 - 16.6
d. VR = IR
= 140.5 = 1.61 x 50
= 80.5V
Z2 = R2 + X2
= ( 50 )2 + ( 140.5 )2
VL = I XL
= 2500 + 19740.25
= 1.61 x 157.1
= 22240.25
= 252.93V
\Z = Ö22240.25
VC = I XC
=149.132W
= 1.61 x 10.6
= 17.07V
b. I=V/Z
= 240 / 149.132
= 1.61A [Note: In many cases, the voltage drop across the inductor
will be higher than the supply voltage.]
21
CAPACITOR AND POWER FACTOR ( P.F.)
p.f. = R / Z Power factor can either be lagging or leading, but most (if
not all) are of the lagging type. To correct a low, lagging
Since Z = Vt / I and R = VR/ I
power factor, reactive power is added to the circuit by
p.f. = VR ÷ Vt connecting a capacitor in parallel with the load or across the
I I
supply. The capacitor takes a leading current; this
\p.f. = VR / Vt
compensates for and reduces the idle component of the
machine current. The power is therefore increased and the
total current reduced.
22
RESONANCE IN A SERIES CIRCUIT
formulas: 2pƒC
= 106 / 2 x 3.142 x 50 x 300
XL = XC = 106 / 94260
= 10.6W
2pƒC = 106
2pƒL Which is the same as XL, \ XL = 10.6W
From this formula, \ L = XL / 2pƒ
= 10.6 / 2 x 3.142 x 50
L = 106 / 4p2ƒ2C
= 0.034H
Since XL = XC, therefore VL = VC To find the voltage drop, you must find the total current, and
Z=R the total current is determined by the formula:
23
RESONANCE FREQUENCY MAGNIFICATION OF VOLTAGE
Resonance frequency is the frequency when resonance The ratio between the applied voltage and the voltage
occurs. Thus the formula: across the inductor (or capacitor) at resonance is called
ƒr = 106 / 2pÖLC MAGNIFICATION OF VOLTAGE (Q factor). This is a
quantity without unit.
So for the frequency for the example on page 38 is
Q factor = Vc / Vt or VL / Vt
ƒr = 106 / 2pÖLC
= 106 / 2 x 3.142 x Ö0.034 x 300 I XL / I R = 2pƒLI / I R.
OR
Q-factor = XC / R
= 10.6 / 10
= 1.06
24
CONDUCTORS, INSULATORS AND CABLES
each strand having a diameter (not cross-sectional-area) of
0.036mm
Some of the more frequent conductors used are An insulator is a material that offers a very high resistance
Ø Silver to the flow of electric current. Insulators for everyday use
Ø Copper and should posses the following properties:
Ø Aluminum Some of the more frequent insulator used are
Ø Gold 1. Rubber
Ø Platinum 2. Plastic
Ø Broze 3. Air
Ø Brass 4. Glass
5. Fibre glass
gold is considered to be the best conductor , but because it
6. Porcelein
is expense, copper is used more frequently; especially in
7.ceramic
domestic and commercial buildings. Also, copper is more
flexible than the other two; therefore copper is the most
widely used conductor.
25
Ø Chemical Properties: it should be able to carrying capacity as the operating conditions of the cable
withstand the corrosive effect of chemical. change.
Each insulator is picked for a particular application. For Eg. A twin-core 10mm2 P.V.C. cable will carry a maximum
example, porcelain and fireclay are relatively good insulator, current of 40A at an ambient temperature of 250C, but if the
but could not be used for covering conductors forming a ambient temperature is increased to 650C, then the
cable because they are not flexible. P.V.C. is also a good maximum current attained will now be:
insulator, but cannot used in conditions where the Þ (current rating) x (rating factor
temperature exceeds 450C eg. Insulation for electric fires. = 40 x 0.44
= 17.60A
For low voltage wires, a single coating is used, but for high
voltage wires, several layer of insulations are used. To be The rating factor is also dependent on the type of excess
effective, the insulation must be able to withstand the current protection. If cables are bunched together, their
conditions of the environment in which it is used. current capacity will decrease.
26
SELECTING THE CORRECT SIZED CABLE FOR A Vd/A/m £ M.P.V.D. x 103
PARTICULAR JOB. ILOAD x L
When selecting a cable for a particular job, the first things to £ 6 x 1000
take into consideration are: 30 x 175
Ø The cable must be able to carry the load current £ 1.14
safely
Ø The cable must be sized such that the voltage Check the JS21 for the size that has a Vd/A/m that is equal
drop in it does not exceed 2.5% of the supply to 1.14 or the nearest one that is lesser than 1.14, then look
voltage. for the cable size that corresponds with it. Also check under
the correct phase column (i.e. three phase or single phase),
and check that the cable can carry that current or a current
The maximum permissible voltage drop that is bigger.
(M.P.V.D.) = 2.5 x supply voltage
100
Eg. A cable is to be run 175m and carry a load current of
30A at a 240V supply, single phase. Determine the correct
size cable.
27
When choosing a cable after you calculate its size, you Ø The current rating of the sub-circuit cables should be
determine greater than the current rating of the respective sub-
q if its armoured or non-armoured circuit breakers.
q the type of insulation
q the number of core (eg. s/core; twin & earth etc)
q type of conductor (eg. Copper or aluminum)
28
WIRING A HOUSE
When wiring a house, to determine the size main circuit Since they are 110V lamps, then they can be evenly
breaker, the size service main cable and the size panel box, distributed to the two bus-bars. Thus the total current is
you start your calculations from the final sub-circuits up to divided in two (7.81 / 2) = 3.905A
the main breaker and subsequently, the main cable. leaving 15. Using four (4) to three circuit breakers
and three (3) to one. This gives six circuits (six
Eg. A three-bed room house with the following: s/pole circuit breakers). To calculate the current
Ø 18 -- convenient outlets (110V each) for the outlets, you use the formula for diversity
Ø 2 -- a/c units rated at 24000 BTU / 220V at a (100% 0f the largest breaker) + (40% of the sum
First you must remember that in accordance to the JS21, distributed to the two bus-bars. Thus the total current is
= 0.91A = 37.6A
\The total lighting current = 13 x 0.91 =11.83A Therefore the total current for the two units is
current)
= 0.66 x 11.83 v The current rating for the water heater is
29
v The current rating for the 13A fused special outlet The number of single pole circuit breakers is (lights = 2
is calculated at 100% and is protected by a 20A and outlets = 6) = 8 S/pole circuit breakers.
D/Pole breaker = 13A
Total number of S/Pole breaker slots = 18. Thus a 24-
The total current is the sum of the individual currents, = way panel can be used.
3.905 + 30 + 75.2 + 10.7 + 13 = 132.805A
The service main cable would be a 50 mm2
The main circuit breaker would be a 150A double Three 50 mm2 cables, single phase, enclosed in
pole circuit breaker. conduit will carry 150 Amps safely.
PROTECTION OF AN INSTALLATION
(PROTECTIVE DEVICE)
The main factors against which an installation must be A circuit breaker (either thermal or electromagnetic) is a
protected are as followed: device that is used to make (close) and break (open), a
circuit both manually and automatically (under normal and
Ø Earth leakage and danger of electric shock abnormal conditions). If a condition such as an overload and
Ø Excess current short circuit occur, the breaker will automatically open circuit
Ø Moisture and corrosion (this means the circuit breaker will chip). When a breaker
chips the lever is in the center. To reset the breaker it must
There are three basic reasons for fitting protective devices in be turned “OFF” and then “ON”.
an installation
Ø To protect the circuit against excess current
Ø To protect the circuit against earth leakage
Ø To allow the consumer and/or the maintenance
electrician to isolate the installation from the
supply Graphic symbol single double triple
pole pole pole
Protective devices fall into three categories:
Ø Thermal
Ø Electromagnetic
Ø Fuse
30
The breakers installed must be of the correct current rating Fusing Factor –this is a number without unit that when
and must be of sufficient breaking capacity for short circuit multiplied by the current rating of the fuse will give the fusing
faults. The breaker shall be so adjusted so that it will open current.
the circuit when a current flow equal to 1.25 times the rating \ Fusing Current = Fusing Factor x Current Rating
of the smallest cable/conductor it is used to protect. This The advantages of a rewirable fuse are:
requirement does not apply to motor circuits. The breaker Ø It is cheap
must be firmly secured in the panel and all the strands of the Ø Its element is easy to be replaced
conductor must be well secured in the breaker terminal. The
breakers must be identified on the panel directory as to the Some disadvantages are:
circuits they control and protect. Ø Fuse element deteriorate in use
Ø Any size of fuse wire can be fitted, thus defeating
the purpose of the fuse
Ø Lacking in discrimination. It is possible that a 15A
CARTRIDGE FUSE
Graphic symbol
31
Supply authority These two are not linked.
Pothead L1 L2 N
KWh meter
Distribution box
1 2
3 4
5 6
Sub-circuits
7 8
1 2
3 4
5 6
7 8
32
OVERLOAD AND SHORT CIRCUIT Short circuit is a condition where there is an unintentional
connection/contact between
respective protective device or the supply. Example, if a Ø Two or more live conductors
33
ELECTRICAL TEST (THE PURPOSE OF TESTING AN INSTALLATION)
It is very important to carryout the relevant tests on an Earth Continuity – this is to done to
instillation (circuit) to detect faults before connecting it
to power supply to avoid dangerous situations from Ø Ensure that the earth continuity conductor is
arising. continuous connected to those parts of the
installation to which it is supposed to be, also
The main tests carried out on an installation are that all metals and earthing terminals are
Ø Verification of Polarity properly earthed and connected together.
Ø Earth continuity resistance test Ø Measure the resistance of the earth continuity
Ø Insulation Resistance tests conductor
Ø Test for ring circuit continuity Ø Ensure that the earth continuity conductor is
capable of carrying heavy leakage current
The test should be carried out on new installations, Ø Ensure that the earth electrode is effectively
additions to existing installation and periodically on connected to the general mass of earth.
existing ones.
Instrument used; the ohmmeter.
Verification of Polarity Test – this is done to ensure Procedure: check between every metal box.
that the phase conductor(s) is/are taken through the
respective protective devices and the respective control The maximum allowable resistance of the earth
devices then to the load. The neutral conductor should continuity conductor must not exceed one ohm.
never be broken by a fuse, circuit breaker or a switch.
The following must be noted:
The instrument used is an ohmmeter and the reading
should be zero ohm once the polarity is correct. Ø Gas and water pipes must not be used as
earth continuity conductors, but they may be
In order to carry out the polarity test on an installation, bonded to the earth continuity conductor.
the following should be noted: Ø Where separate earth continuity conductors
Ø Loads must be out are used, the minimum allowable size is
Ø All switches off; neutral in; protective devices 1mm2
out Ø It is essential that all joints in an earth
Ø Supply off continuity conductor are electrically and
mechanically sound, should also be protected
Test for continuity of live and neutral conductors in their against corrosion.
appropriate position with the ohmmeter.
34
Insulation Resistance Test -- this is done to Ring Circuit Test – On completion of a ring circuit
determine whether the insulation of the conductors installation, a test similar to that carried out to check the
used or the insulation of the joints made is such that no verification of polarity must be carried out to ensure the
significant leakage of current occurs whenever the continuity of all lines, neutrals and earth continuity
circuit is energized. conductors throughout the ring circuit. This test is
carried out at the point of connection in the installation
The instrument used is the meg-ohmmeter. The distribution board prior to the completion to the ring
acceptable reading between circuit conductors.
Ø Live and earth should not be less than one
megohm A ring circuit is one where there is an alternate path
Ø Phases should not be less than two for current flow to the load.
megohms
35
Standard procedures for upgrading of installation from 110V single-phase to 220/110V, 3-wire single-phase.
Procedures to be followed:
# ACTIONS
PROCEDURE DONE BY
1 Electrician
The Electrician advises JPS of intention to upgrade supply and obtain permission in writing from
JPS to proceed.
2 Electrician
When the new phase (L2) is drawn in it is tied to the neutral at the pothead and connected to the
right side of the meter socket and the installation is left at 100V with the 110V meter still working
3 Electrician
The main breaker is changed to a double pole breaker. At this stage line-two (L2) is not connected
to the main breaker but left taped inside the panel and is coloured RED to facilitate easy
identification connection.
4 Electrician
Electrician makes formal request to the Chief Electrical Inspector (G.E.I.) for inspection.
5 G.E.I.
If found satisfactory, the G.E.I. then sends a certificate to JPS
6 JPS
After the contract is signed for a 220V supply, JPS removes the link between neutral and the new
phase (L2) at the pothead, connect the 220V triplex service line, install and seal new 220V/110V
meter.
7 Electrician
After JPS has completed their installation the following must be done by the electrician:
(i) The jumper (bridge) in the panel is to be removed first
(ii) The new phase (L2) must then be connected to the main double pole
circuit breaker thus finalizing the upgrading to 220V
36
EXISTING 110V CONNECTION (Electrician makes this connection)
(JPS personnel will remove it)
L 110V N L N
Bridge
37
TRANSFORMERS
A transformer is a static electro-magnetic device that is transmission by overhead line system and then
capable of transforming the value of alternating current stepped-down to values which can be used in factories,
and voltage at a constant frequency. It is constructed homes and other commercial buildings.
connected together. the secondary coil will give out a version that is either
greater or lesser than the input voltage/current,
Yoke (also the bottom part) depending on the ratio between the number of turns on
s
conductors. To alleviate this, much higher voltages current flows through it, it creates an electromagnetic
than that produced by the generators are needed. That field within that coil. This magnetic field links the two
is why the transformers used in electrical power coils, and thus induces an e.m.f. in the secondary coil.
stations to increase the voltages to transmission level This induced e.m.f. depends on the ratio between the
are called step-up transformers. The voltage number of turns on the primary and the secondary
produced by a power station is usually stepped-up for coils, and the input voltage.
38
RELATIONSHIP BETWEEN THE NUMBER OF TURNS, CURRENT AND VOLTAGE
Eg. A transformer with 2000 turns on the primary and transformer is a step-up or step-down transformer.
800 on the secondary is connected to a 400V When the transformer is given in ratio terms, it indicates
supply and is supplying a load. Calculate: the voltage and terns ratio. The inverse of this is the
current ratio.
(i) the primary and secondary volts-per-turn
(j) the secondary voltage
Example, a 4 : 1 or 2 : 1 transformer is a step-down
(i) VP = VS = 400 / 2000 = 0. 2V transformer because the primary comes first, while a 2 :
NP NS 3 or 4 : 5 transformer is a step-up transformer.
(ii) VP = NP
VS NS
Eg. A 4 : 1 transformer with 300 turns on the primary is
400 = 2000
connected to a 200V supply and is supplying a
VS 800
load using 2A. Calculate:
By cross-multiplying, we get
(i) the secondary voltage
2000 VS = 800 x 400 (ii) the secondary turns
VS = 320000 / 2000 (iii) the primary current
= 160V
39
(i) VP = 4/1 (ii) NP = 4 / 1 (iii) IS = 1 / 4
VS NS IP
\ VS = 200 / 4 \ NS = 300 / 4 \ IP = 2 / 4
= 50V = 75 = 0 . 5A
TRANSFORMER EFFICIENCY
l = PO x 100 = %
40
Primary copper loss Þ IP2 x RP AUTOTRANSFORMER
= ( 50 )2 x 0.42
= 1050W An autotransformer is a transformer that has its primary
and secondary windings being on the same, and the
IS = 500000 / 400 magnetic flux from the primary cuts the turns of the
= 1250A secondary and induces an e.m.f. into them. This type
Secondary copper loss Þ IS x RS 2
of transformer uses the principle of self-inductance.
= ( 1250 ) 2 x 0.0019
= 2968.75W
Total losses = (total copper loss ) + (iron loss) A Current transformer (CT) is used when the load
= 4.01875 + 2.9 current exceeds 200A. The reason is that, kWh meter
= 6.91875kW sockets are manufactured with a maximum current
rating of 180A (200A). Thus the current transformer is
Note: change the apparent power to true power used. Current transformers are also called instrument
Pi = S x p.f. transformers, because they are used to accommodate
= 500 x 0.8 measuring instruments. Current transformers have no
= 400kW primary windings. A conductor is placed inside the
hole, in the center, which works as the primary winding
of the transformer. This conductor (a current-carrying
l= 1 - losses x 100
conductor) produces a magnetic field, which is
Pi
transferred to the secondary winding of the current
transformer. The high current is reduced by the
= 1 - 6.91875
transformer so that it can be measured.
400
= ( 1 - 0.0172969 ) x 100 Current transformers usually have a ratio of something :
= ( 0.9827031 ) x 100 5, example 300 : 5. This means that the full-scale
= 98.27% deflection (f.s.d.) of the CT is 5A, but the actual current
of the consumer (load) is 300A. So, if the actual
current is 300A and the f.s.d. on the CT is 5A, then
each stroke = 300 / 5 = 60A. Say the reading on the
CT is 4, then the actual current used by the consumer
(load) at that instant is 4 x 60 = 240A.
41
For a three-phase configuration, they are usually
connected in STAR. CT’s are usually connected on low 24kV
CT Meter Device
TRANSFORMER REGULATION
ends of the CT should be shorted out. secondary voltage at no load and the secondary at full
load, when divided by the secondary no load voltage is
called voltage regulation per unit.
Therefore
Voltage Reg. = No load voltage – Full load voltage
No load voltage
VOLTAGE TRANSFORMER
42
SOLENOIDS
A solenoid is a coil of wire with the wire wound in the If a solenoid is energized with direct current, the polarity
same direction, so that when the coil is carrying a of its magnetic poles remains fixed. If the solenoid is
current, all the turns are assisting one another in energized with alternating current, its polarity reverses
producing a magnetic field. The magnetic field may be with each reversal of the direction of the current.
intensified by inserting a soft iron inside the coil.
The soft iron that is inserted within the coil is usually
The direction of the magnetic field produced by a moveable i.e. when the coil is energized; it pulls the soft
current in a solenoid can be determined by applying the iron (armature) inward. As soon as the coil is de-
grip rule (the right hand rule). The solenoid has energized, a spring action returns the armature to its
magnetic poles and magnetic field that have the same original position.
properties as those of a permanent magnet.
A SOLENOID
43
LIGHT AND POWER CIRCUITS AND CALCULATION
The entry of the end into an accessory is called There is a wide variety of conductor termination.
termination. In the case of stranded conductors, the Typical methods of securing conductors in accessories
strands should be twisted together before terminating. are pillar-terminals, nut and washer and screw-head.
Care must be taken not to damage the conductor.
44
FILAMENT LAMPS
AN INCANDESCENT LAMP
45
DISCHARGE LAMPS
SODIUM-VAPOUR LAMP
This lamp gives an orange light and is used mainly for The lamp will start immediately whether it is hot or cold.
street and road lighting, and on airfields. The lamp is Care must be taken in disposing of used sodium lamps,
because metallic sodium may burn if it comes into
the most efficient producer of light, but because of its
contact with moisture or water.
single-colour characteristic, it gives an inferior colour
quality (everything looks yellow or gray to black). The
lamp consists of a long glass tube, which contains a The average life of all sodium lamps is 6000 hours.
46
LOW PRESSURE MERCURY VAPOUR Ø The capacitor – this is fitted across the
supply to improve the power factor of the
LAMP
circuit by neutralizing the inductive effect of
the choke.
This lamp is known as the fluorescent lamp. It
consists of a glass tube filled with mercury vapour at
Electrodes
low pressure. The electrodes are located at the ends of
Starter
the tube. When the lamp is switched “ ON “, an arc-
discharge excites a barely-visible radiation, the greater
part of which consists of ultra-violet radiation. The
interior wall of the tube is coated with a fluorescent
powder which transforms the ultra-violet radiation to
tube
visible radiation or light. The type of light, that is the Ballast
colour range, is determined by the composition of the
fluorescent powder. When the temperature of the gas Power factor
correctional
or vapour rises, the resistance of the discharge lamp
Supply capacitor (optional)
decreases and will thus tend to draw an ever-increasing
current from the supply. The current is limited to a A FLUORESCENT LAMP CIRCUIT
predetermined value by the insertion in the circuit, in
series with the lamp, a choke (ballast).
There are two types of fluorescent lamps: There are two methods of starting fluorescent lamps:
The hot cathode is the more common type. In this type, The practical application of the lamp includes the
the electrodes are heated and the voltage of operation lighting of:
starting voltage on starting (caused by the incandescent lamp. Some of these are:
and also limits the current in the lamp when Ø It is better for the human eye (better for
Ø The starter –used only for starting. After Ø It gives more illumination for the same
47
HIGH- PRESSURE MERCURY-VAPOUR LAMP
48
LIGHTING SUB CIRCUIT
Electrical apparatus are connected by cables to the The other terminal is connected to the live terminal of
electricity supply and to the associated protective the lamp holder by connecting wire and the neutral
device (usually fuse circuit breaker). This is an terminal of the lamp holder is connected to the neutral
arrangement called a circuit. A circuit that supplies terminal of the supply.
apparatus directly is known as a sub- circuit. When
connected to a distribution board, this is called a final
sub- circuit. The simplest sub circuit arrangement for
lighting circuit is a one-way, comprising one lamp Graphic symbol
49
THE TWO-WAY SWITCH INTERMEDIATE SWITCH
A two-way switch (single-pole double throw) is one An intermediate switch is one that allows independent
that provides two independent switching positions. It switching from three or more positions. It has four
has three terminals, one is called the common and the terminals and is usually used between two two-way
other two are called travellers terminals. When used switches. There are three (3) types of intermediate
in pairs, they allow two independent control positions. switches. When using the most common type, the two
Either of the two can turn “ON” and/or “OFF” the lights top terminals are connected to the two traveller’s
independently. They have no “ ON “ or “ OFF “ terminals of one two-way switch and the two bottom
position. terminals are connected to the two traveller’s terminals
of the other two-way switch. Any number of
intermediate switches can be connected between the
two two-way switches, each giving a complete
Graphic symbol independent control.
When two-way switches are connected in a circuit, the
live conductor is connected to the common terminal of The intermediate switching arrangement is used when
any one of the two-way switches (because two-way lamp(s) is/are to be controlled from three or more
switches are single-pole switches). The common switching positions, such as long corridors or areas
terminal of the other two-way switch is connected to the where there are a number of entry points.
live terminal of the lamp holder. The neutral wire is
connected directly to the neutral terminal of the lamp
holder. The two remaining terminals on one two-way
switch are connected to the two remaining terminals on
the other two-way switch by wires called travellers.
The most
common type
50
DOUBLE-POLE SWITCH variable resistor, where it either increases or decreases
the resistance for the path of current flow to the lamp.
A double pole switch is one that controls two lines. It In varying the resistance, the voltage across the lamp is
makes and breaks both poles simultaneously. It has varied, thus varying the light output of the lamp.
four terminals. The two lines are connected to the two Dimmer switches come in both sliding and turning
top types. Some are basic two-terminal while others may
have terminals for other connections. The switch is
connected into the circuit similarly to the connection of
a single pole switch.
THE PHOTOCELL
Outer case
Window
Neutral (white)
DIMMER SWITCH
A photocell
51
LIGHTING FIXTURES AND ACCESSORIES
Handy box –as its name implies, this is a box that can
be used for several purposes. For example, it can be
used to accommodate switches, convenient outlets
(plugs), as draw through boxes etc. A draw through
box is a box where cables are drawn through, also
connections can be made in this box.
52
POWER CIRCUIT WIRING A 240V PLUG
Regulation to be studied
53
CABLE COLOUR CODING
54
INSTALLING A METER BASE
Ø Meter base must be installed at a location to meet height of all the breakers should be hand reachable
the requirements of the Government Electrical without the assistance of stools, chairs etc.
55
ELECTRIC MOTORS AND GENERATORS
D.C. motor
The armature of a d.c. motor with windings in place
A d.c. motor is one that can be used for such
mechanical works that require control such as printing
The speed of a d.c. motor is dependent on four factors:
machines, elevators, etc.
Ø The strength of the magnetic field. This is an
Its main parts are:
inverse relationship. Speed is inversely
proportional to the strength of the magnetic
Ø The armature ( the rotating coil )
field.
Ø Field poles (coil)
Ø The number of poles in the main field
Ø End plates and brushes
Ø The number of armature conductors
Ø The voltage across the armature
56
TYPES OF D.C. MOTORS SHUNT WOUND MOTOR
57
COMPOUND MOTOR resistance must be placed in the low-resistance
armature circuit (which is generally less than one ohm
In the compound motor there are two field coils. One is {1W}) to limit the armature current until the speed (and
in series with the armature and the other is across the back e.m.f.) builds up.
them, as in the figure below.
STARTER
Shunt field
Vt = E + ( Ia x Ra ) + VB
REVERSING D.C. MOTORS.
Where Vt = applied voltage
direction of the current flow through either the armature Ia = armature current
When a d.c. motor armature is run up to speed, a back and is taking an armature current of 40A. If the
e.m.f. is induced in the armature conductors which motor has an armature resistance of 0.1W and a
opposes the applied e.m.f. and so limits the current brush voltage drop of 2V, calculate the back e.m.f.
58
From the formula OVER-CURRENT PROTECTION
Vt = E + ( Ia x Ra ) + VB , \ E = Vt - ( Ia x Ra ) - VB
= 500 - ( 40 x 0.1) – 2 The purpose of this protection is to gaurd the motor
= 500 – 4 – 2 against excess current. The line current to the motor
= 494V flows through a coil (the current coil) which attracts a
soft-iron armature when the motor is being overloaded.
This soft-iron armature carries a contact which shorts
NO VOLTAGE PROCTECTION out the no-volt coil, thus releasing the starter handle to
the “OFF” position. The no-volt coil has many turns of
the purpose of this protection is to ensure that the fine wire. The current coil has a few turns of heavy
handle is replaced to the “OFF” position when the wire, and is usually set to operete at 150% of full-load
supply is cut off. The no-volt coil, which is usually current.
connected in series with the field, forms an
electromagnet which holds the spring-loaded starter
handle in the “run” position. When the suply is cut off
the no-volt coil is de-magnetized and the coil alsoallows
the motor to stop from a distance by connecting a stop
button which, when pressed, shorts out the no-volt coil.
59
D.C. GENERATOR
60
SEPARATELY EXITED GENERATOR. For a generator, the terminal voltage is calculated by
the given formula:
When the field coils of a generator are connected to an
Vt = E - ( Ia x Ra ) - VB
outside source of electricity, the generator is known as .
+ to load -
Eg. A d.c. generator delivering 500V at 80A from an
A SEPARATELY EXCITED SHUNT GENERATOR armature having a resistance of 0.1W. Assuming
a negligible brush voltage drop, calculate the
(i) As a generator E = Vt + ( Ia x Ra )
= 240 + (80 x 0.1)
= 240 + 8
= 248V
(ii) As a motor E = Vt - ( Ia x Ra )
= 240 – (60 x 0.1)
= 240 – 6
= 234V
61
A.C. MOTORS
core with semi-closed slots. The coils are wound into usually located on top of the main winding and is used
the slots. The stator is comprised of a laminated steel for staring only. The main windings are of heavy
core with semi-closed slots, a heavy cast-iron or steel insulated copper wire and are usually located at the
frame into which the core is pressed, and two windings bottom of the slots. The two windings are connected in
(coils) of insulated copper wire wound into the slots. parallel to the supply. The two windings are connected
in parallel to the supply.
62
The centrifugal switch is located inside the motor and DUAL-VOLTAGE SPLIT-PHASE MOTORS
its function is to disconnect the auxiliary windings from
the supply after the motor reaches a predetermined Most split-phase motors are made for single voltage
speed (75% of full speed). operation. However, some split-phase motors, usually
motors made for specific application, are made so that
The usual type consists of two main parts, namely a
they can be connected for either of two voltages,
stationary part and a rotating part. When the motor is
usually 115V and 230V. Such a motor usually has a
at standstill (not running) the centrifugal switch is
main winding of two sections and a starting winding of
closed. When the motor starts running and it reaches
one section. A sufficient number of leads are brought
approximately 75% of full speed, the centrifugal switch
out of the motor to permit a changeover from one
opens, thus automatically disconnecting the starting
voltage to another and for reversing. If the motor is to
windings from the circuit.
operate on 115V, the two sections of the running
The end plates are fastened to the stator frame by
winding are connected in parallel. If the operation of
means of screws or bolts and serve mainly to keep the
230V is desired, then the two sections are connected in
rotor in position. The bore of the endplates in which
series. In either case, the starting winding usually
the rotor shaft rests, is fitted with either ball or sleeve
operates on the lower voltage only and is connected
bearings.
across one of the running winding. This means that the
starting winding is intended for only one voltage. In a
PRINCIPLE OF OPERATION
dual-voltage motor, the two running windings are of the
same size wire and are wound with the same number
When a voltage is applied to the stator windings an
of turns in the same slots, one on top the other. The
electromagnetic field is created in the coil. This
wires are brought out of each section, and are marked
magnetic field then cuts the armature (rotor) coil thus
T1 & T2 for coil one, and T3 & T4 for coil two.
inducing an e.m.f. into it. This induced e.m.f. then
The starting winding is usually wound last, and its leads
create another electromagnetic field which creates an
are marked T5 & T6
opposing current that will cause the armature to rotate
due to the process of repulsion.
CAPACITOR MOTORS
REVERSING A SPLIT PHASE MOTOR
A capacitor motor has two stator windings: An auxiliary
To reverse a split phase motor, one should reverse the winding connected in series with a capacitor and a
direction of the current through either the auxiliary main winding. Capacitor motors are available in three
windings or the main windings. To do this, one would types designated as: (1) Capacitor Start (2) single-
reverse the leads of either the main winding or the value capacitor and (3) two-value capacitor.
auxiliary winding. Although the split-phase motor is low In the capacitor start motors, the auxiliary winding is
in cost, it has the disadvantages of high starting current used only for starting and is cut out at approximately
and relatively low starting torque, and is somewhat 75% of the synchronous (full) speed while the other
noisier when heavily loaded than the single-value of two, both the auxiliary and the main windings are
two-value capacitor motors. employed when running as well as starting.
63
The two-value capacitor motor uses two capacitors, exhibit the pulsating hum characteristic of most single-
while the other two types employ only one. phase motors when loaded.
64
SHADED POLE MOTORS
The shaded-pole motor is a single-phase a.c. motor All shaded-pole motors have rotors of the squirrel-cage
varying in size from approximately 1/100 to 1/20 h.p. It type. On many of these motors only one of the end
is used for applications requiring very low starting plates can be removed, the other is cast as part of the
65
THREE PHASE INDUCTION MOTOR
In the induction motor, electrical energy is supplied to Three phase (3f) motors vary from fractional
the stationary windings and is transferred inductively to horsepower to several thousand horsepower. These
the rotating winding (the rotor). The rotor is separated motors have a high constant speed characteristic and
from the stator by a small air gap. No electrical are made in designs giving a variety of torque
connection is made between the two sets of circuits. characteristics. Some are designed to draw normal
The two principal kinds of induction motors are: current while others draw high starting current. When a
three-phase motor is starting, it draws up to six times
Ø The squirrel cage motor, and
the running current. In a three-phase motor, there are
Ø The wound rotor
three different stator windings which are 1200 apart.
Eg.
Coil 1
1200 1200
insulated coils of wire, and they are not permanently coil two, the ending of coil two is connected to the
short-circuited. The ends of the rotor windings are beginning of coil three and the ending of coil three is
66
The source (L1, L2 & L3) is connected to the junctions rotating flux (synchronous speed) is ‘ N ’ revolution per
that are formed between the three coils. second (r.p.s). Thus giving the formula
L1 L1 N=f/P
if it lost one line before starting it will not start, it will Where P, means number of poles instead of number of
Therefore N = 120 f / P
= 120 x 50 / 4
= 1500 r.p.m.
THE RELATIONSHIP BETWEEN SPEED, This formula gives the answer in revolution per minute.
NUMBER OF POLES AND FREQUENCY. The actual speed of the motor is called the rotor
speed. This is the speed at which the rotor conductors
The speed of a three-phase motor is affected by two are being cut by the rotating flux. The speed that is lost
main factors: within the motor is called the slip speed. The ratio
Ø The frequency of the supply and between the slip speed and the synchronous speed is
Ø The number of pair of poles. called per-unit-slip. Thus the percentage slip is the
per-unit-slip multiplied by 100.
The speed is directly proportional to the supply
frequency but is inversely proportional to the number of Let the actual speed (rotor speed) be “ Nr”; the per unit
pairs of poles (or just number of poles). slip be “ S “ and the synchronous speed be “ N ”. The
slip speed can be determined by the given formula:
For a three-phase motor with ‘ P ’ pairs of poles
supplied at a frequency of “ f “ hertz, the speed of the Slip speed = N - Nr
67
\Per-unit-slip (S) = ( N – Nr ) a. N = 120 f / P b. S = ( N - Nr ) x 100
N = 120 x 50 / 4 N
= 1500 r.p.m. = ( 1500 – 1200 ) x 100
And percentage slip = ( N – Nr ) x 100
N 1500
N = 20%
Now 4% as percentage slip is 4 / 100 giving 0.04 as per The frequency of the rotor e.m.f. and the current can be
unit slip. determine by the given formula:
Therefore the slip speed (the speed that is lost inside to 600 rpm.
Eg. 2 A 4-pole squirrel cage motor has an actual speed =1440 rpm
68
SYNCHRONOUS MOTORS
69
THREE-PHASE MOTOR CONTROL
3 f circuit breaker 3 f motor Relay coil
70
to 250% of full-load current depending on the code
letter of the motor.
OVERLOAD PROTECTION In a manual starter, an overload trips a mechanical
latch, causing the starter contacts to open and
The effect of an overload is a rise in temperature in the disconnect the motor from the line. In the magnetic
motor windings. The larger the overload, the more starters, an overload opens a set of contacts within the
quickly the temperature will increase to a point overload relay itself. These contacts are wired in series
damaging to the insulation and lubrication of the motor. with the starter coil in the control circuit of the magnetic
An adverse relationship, therefore, exists between starter. Breaking the coil circuit causes the starter
current and time; the higher the current, the shorter the contacts to open, thus disconnecting the motor from the
time before motor damage or burnout can occur. All line.
overloads shorten motor life by deteriorating the
insulation. There are two classifications of overload relays –
magnetic and thermal. Magnetic relays react only to
The ideal overload protection for a motor is an element excess current and are not affected by temperature.
with current-sensing properties, which could act to Thermal relays can further be divided into two types –
open the motor circuit when the full-load current is melting alloys and bimetallic.
exceeded. The operation of the protective device
should be such that the motor is allowed to carry
harmless overloads, but is quickly removed from the
line when an overload has persisted too long.
71
THREE PHASE CALCULATIONS
IL
VPH R
4-WIRE Y SYSTEM
1200 1200
.
VPH 1200 VPH This system is used when three separate loads have to
Y B be supplied. Example, houses will obtain supply from a
IL IL one phase to neutral. Another building might obtain
supply from another phase to neutral, etc. Most times
the loads are not balanced; hence the current may
- VY VL
differ in each line.
300 If the loads are balanced then the currents are equal.
Thus, the result is that the current in the neutral line is
300
1200 VR zero. However, this is not so when the loads are not
balanced.
VY
VR VB
Cos. 300 = 0.866 which is equal to 0.5Ö3
(VPH) (VPH)
Thus Cos. 300 can be substituted by 0.5Ö3; giving VY (VPH)
72
- IB IL
= Ö3 IPH
73
The power in both star and delta is determined by the THREE PHASE TRANSFORMER
same formula:
CONFIGURATIONS
P = Ö3 VL IL p.f
When three single-phase transformers are connected
= 1.732 x 440 x 25 x 0.85
to form a three-phase bank, they can be connected in
= 16194.2W
one of the following FOUR configurations: -
74
If the transformers are rated at 24kV, their primary can
be connected in delta, thus each transformer is
connected across two phases (line voltage), but their
secondary can be connected in either DELTA or STAR.
L1 L2 N L3 L1 L2 L3
STAR-DELTA (EDISON DELTA) STAR-DELTA (STRAIGHT DELTA)
L1 L2 N L3 L1 L2 N L3
STAR-STAR DELTA-STAR
75
THE RESPONSIBILITIES OF A LICENSED ELECTRICIAN
1. Ascertain the size (current and voltage ü The G.E.I. is a body of people, not an
rating) and type load (if the load is individual. They enforce the light and power
single phase or three phase) that will act
be required. ü C.E.I. means Chief Electrical Inspector. (a
2. Find out whether or not the supply is person)
available. (You can do this by looking ü A contract form is the form used to carry out
on the J.P.S. light pole to see the type any job that is to be submitted for
of supply wires or contact the supply inspection.
authority for information) ü For every commercial and industrial
3. Do a design of the installation. installation, a plan MUST be submitted, also
4. Submit a completed notice form to the all three phase installation. For houses, its
Government Electrical Inspectorate only if the main cable exceeds 70A.
(G.E.I.) ü For a plan, the plan must be
5. Submit the design to the G.E.I. for o Floor plan, showing location of
approval. switches; plugs; panel box; lamps etc.
(4 & 5 can be done together, or 5 can be done o Sectional view showing earth rod
before 4.) (length and size earth cable)
6. Commence work on the installation o One line diagram showing if it’s
after approval of design. from pothead-to-meter-to-panel-to-
7. Request intermediate inspection, if sub circuits or if it’s from pothead-
necessary. to-panel-to-sub circuits.
8. Carry out the necessary test on the
completed installation
(One of the first tests is visual.)
9. Make a formal request for an
inspection of the completed installation.
(One of the first tests is visual.)
10. Collect the inspection report and hand
it over to the client.
76
STANDBY GENERATORS’ INSTALLATION
Whenever installing a standby generator it will be oil to flow from the surface to the bottom of the
necessary to ensure that the generator’s exhaust gravel bed.
is directed away from buildings or openings of
buildings (windows, doors, grilled areas etc). EARTHING OF GENERATORS
This is to ensure that the gas emitted from the
exhaust is not directed into the building or that The casing of large standby generators should
the heat from the exhaust is not allowed to be effectively connected to the general mass of
decrease the strength of the building or cause a earth by means of an earth electrode. The size of
fire. the earthing lead should obey the table at the
bottom of page 155 of the JS 21, and at least two
DECREASING THE OPERATIONAL NOISE OF (2) earthing-locations should employ.
GENERATORS
The fuel tanks of generators must be installed in It is advisable that generators be started off-load,
an area, so prepared to ensure that in the case of however, if it becomes necessary for it to be
a spill the oil will be contained in a sump. The started on-load it is advisable that the starting
sump should contain a one-foot deep gravel bed load does not exceed approximately forty percent
(of at least one inch gravel) that will allow for the (40%) of the rated load of the generator. This will
77
allow for the prime mover to run up to speed from the supply authority (J.P.S.); three (3) from
within a time that will not significantly affect the the standby generator and three (3) from the
connected load. load.
78
LIGHTING PROTECTION SYSTEM
79