Introduction 4
Basic Planning 7
- Positioning Escalators or Moving Walks Within a Building
- Escalators or Moving Walks?
- How Many Escalators or Moving Walks?
- Arrangement of Escalators and Moving Walks
- Proper Inclination
- Optimal Step/Pallet Widths
- Optimal Speed
Detailed Planning 14
- Standards
- Transportation of Disabled Persons, Transportation of Baby Carriages
- Space Requirement
- Safety, Regulation-Compliant
- Operating Modes
- Special Applications
Commercial Sector been installed for space reasons. Even after the
Escalators and moving walks are used to increase elevators had been in operation for some time,
customer density and thus help boost sales in the scheduled sales fgures on the upper foor were
buildings used for commercial purposes. The not achieved due to insufcient customer fow.
following examples taken from everyday practice Once moving walks were installed, sales increased
clearly illustrate how and why: several-fold.
Continuous arrangement
Single unit (one-way trafc)
Proper Inclination
Optimal Speed
Speed not only has a considerable impact on
the potential transportation capacity of escalators
and moving walks, it also infuences the
space requirements. The tables below summarize
the different product confgurations depending
on speed.
Moving walks: Table according to EN 115-1 (other national regulations can be met)
No regulation for radii of curvature
11.000 11.000
6.000 6.000
5.000 5.000
0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85
v [m/s]
Overhead clearance
Protective barrier between balustrades Wedging guard Guards against climbing the balustrades
1 Wedging guards
2 Ceiling defectors
Operating Modes and Energy Efciency passengers, the unit remains ready for operation as
The operating mode of the escalators/ signaled by a direction indicator. The Schindler
moving walks can be adapted to the application. entrance monitoring system detects approaching
There are essentially three operating modes: passengers and sets the escalator/moving walk into
motion whenever required.
- continuous operation
- stop & go operation ECO Premium
- continuous operation with crawling In continuous operation with crawling, the escala-
tor/moving walk continues to crawl at 0.1 m/s in
Schindler escalators and moving walks offer the absence of passengers, using a frequency
optimized energy-saving packages for all three converter. Mechanical wear is considerably lower
operating modes. than in conventional stop & go operation, and in
this operating mode the readiness for operation and
ECO the direction of travel are indicated by the slowly
Continuous operation is the optimal mode for moving steps.
the commercial sector in which customers are to
be transported efciently to the upper foors of ECO Premium Plus
the store. As the top of the range, the ECO Premium Plus
package offers the highest energy-saving potential.
ECO Plus It combines the energy-saving functions of the ECO
Stop & go operation is recommended for the Plus and the ECO Premium packages and features
intermittent arrival of passengers or for sporadic stop & go operation together with stand-by speed
use outside peak times. Typical applications include operation. For top energy efciency, high-efciency
movie theaters and airports. When there are no drives and motors must be specifed.
0.1 0.1
8
22 h
Escalator Operation
With Shopping or Baggage Carts
For safety reasons, the transportation of shopping
and baggage carts on escalators is not allowed.
If they must be transported, moving walks must be
installed.
Additional stops for emergency situations at the exit, with a distance between 2.0
m and 3.0 m before the comb intersection line, must be provided.
Schindler escalators and moving walks are ideally The following table provides an overview of the
designed for use in all the relevant application product types and their main application segments.
segments. The modular structure of Schindler
escalators and moving walks means that the
components required can be adapted to each
application while retaining the same outer design.
Optimal planning and preparation of on-site The key points involved in this process are
transportation and the moving of the escalator/ summarized below.
moving walk into the building are essential for
ensuring the best possible installation sequence Moving the Escalator or
and thereby minimizing building costs. Escalators/ Moving Walk Into the Building
moving walks are entirely preassembled at the A suitable area for unloading the escalator/moving
factory. This is why planning on-site transportation walk from the truck has to be provided in front of
of the escalators/moving walks, which can be up to the building. The access routes to the building and
17 m long and weigh up to 100 kN, is such a key the installation site must be level and accessible
step in the planning process. with roller dollies.
Planning is based on the technical specifcations Essentially, there are two possibilities for moving the
in our dimension sheets or on the layout drawing escalator/moving walk into the building:
specifc to the project.
- Through ground-foor openings in
As a matter of principle, we recommend the building using special forklift trucks
that you coordinate the date and time - Through appropriate side openings in the building
as well as how the escalator/moving walk or roof using an on-site or mobile crane
will be moved into the building and the
access route with our experts PLENTY OF
TIME IN ADVANCE.
Transportation to the Installation Site The required entrance width depends on the width
The clearance over the entire access route must not of the escalator/moving walk. Given the length of
be less than the minimum dimension stipulated in the escalator/moving walk, make sure all curves and
the dimension sheet/layout drawing. (Don’t forget bends can be negotiated easily. We recommend
suspended pipes or lines.) that you plot out the entire transportation route on
a CAD plan or paper model.
The type of delivery has to be stipulated at the time
of the release for production. After that date the The entire transportation route must be level
escalators/moving walks can no longer be designed and free of obstacles, and be able to withstand
in several parts. particular foor loads. If not, the appropriate load
distribution has to be provided. Our experts can
advise you.
Once the detailed planning is completed, you will Site Preparation Inspection
receive from us a project planning sheet or a layout Before your escalator/moving walk is delivered,
drawing based on your indications and containing our installation team examines on site the supports
all the relevant information such as escalator/ and the installation dimensions. Acceptance of the
moving walk geometry, support loads, and key preparations to be made by the customer, i.e., elec-
electrical data. You can also draw up this plan trical connections, transportation routes, etc.,
yourself using SchindlerDraw at www.schindler.com. is also carried out with the site management.
Moving the Escalator/Moving Walk Into the If no suspension points are provided by the customer,
Building installation scaffolds are used. This installation
Moving the escalator/moving walk into the building method takes longer and involves more materials.
up to the supports is a critical process that requires
meticulous preparations (see Services Provided If the roof or ceiling opening is sufciently large,
by the Customer, Site Preparations). a crane can be used to set the escalator/moving
walk down onto its end supports from above.
Once the escalator/moving walk has been
unloaded by crane or forklift truck, the escalator/ Because a certain amount of time will probably
moving walk is placed on roller dollies and towed elapse between the placing of the escalator/
by forklift truck. To minimize the on-site transpor- moving walk and its commissioning, the unit
tation logistics, it is extremely important to keep should be adequately protected against dirt and
the transportation route as short and as straight as damage due to building work.
possible.
Checklist
c Rise
Services to Be Provided by
the Customer
c Masonry, scaffolding, and cutting work
walk supports
c Protective railings for the upper foor opening,
if necessary
c Power supply to the escalator or moving walk
main switch
c Phone line for remote monitoring
Disclaimer
The specifcations, options, and colors mentioned in this brochure are indicative only and are subject to change without notice.
They are not intended to, and do not, constitute an offer on the part of the Schindler Group.
min. 3984
50 kN
449
min. 300
1000
(900)
886 ) Z
(79
6
Power supply
1050
±5
947
(Hmax.)
200
50 kN
min. 2300
449 400
2376
H=
R2 FFL
(900)
1000
30
Z
O
+20
Ø 120
0
1050
1150
+10
h
E -0
A
D
B
C
l D
30
L= ±5 175 +100
135
(900)
1000
(900)
1000
Z
886 )
(79
6
Power supply
1050
±5
947
200
(Hmax.)
50 kN
min. 2300
449 400
2776
H=
R2 FFL
30
(900)
1000
Z
+20
Ø 120
1150 0
1050
2675
Step width (mm) 600 800 1000
A: Step width 600 800 1000
+20
4850 0 B: Width between handrails 758 958 1158
C: Handrail center distance 838 1038 1238
Water drain for D: Width of escalator 1140 1340 1540
outdoor installation
E: Width of pit 1200 1400 1600
L max.1): Limiting span length 19300 17600 16200
Hmax.: Maximum rise 12000 9300 8000
C A. : Distance between outer 918 1118 1318
faces of handrails
Transportation dimensions +10
175 - 0
30
h-770
+10
h
E -0
A
D
B
C
l D
30
+10
L= 5 175 0
135
min. 3285
50 kN
449
min. 300
(900)
1000
Z
86 6)
(7
6
7
Power supply
1050
±5
96
7
50 kN
(Hmax.)
min. 2300
229
449 2325
H=
400
35
FFL
(900)
1000
R2
O
Z
+20
Ø 120
1050
1150 0
+10
h
E -0
A
D
B
C
l D
30
+10
L= ±5 175 0
135
min. 50 kN
01
12 R1 2) With a double drive,
(900)
1000
FFL
Z the truss must be
Power supply
extended by 417 mm.
88
(79
±5
1263
ø 100
6
6)
94
(Hmax.)
of 900 mm, h is reduced
7
449 1) 2) by 70 mm.
R3 2582
H=
400
R2 4) Delivery in min. 2 parts.
(900)
1000
FFL
200
Z
30
0
ø 120
m ±5
m=0.5774(x-2639)-1523
2579
+20
4850 -0 Step width (mm) 600 800 1000
x= ±5 A: Step width 600 800 1000
B: Width between handrails 758 958 1158
Water drain for
outdoor installation C: Handrail center distance 838 1038 1238
D: Width of escalator 1140 1340 1540
E: Width of pit 1200 1400 1600
Lmax.1): Limiting span length 19000 17300 15900
Hmax.: Maximum rise 13000 13000 13000
C A. : Distance between outer 918 1118 1318
faces of handrails
Transportation dimensions +10
175 - 0
30
h-770
+10
h
E -0
A
D
B
C
l D
30
Detail Z
Step width Rise Weight Support loads Transp. dimensions
Gaps at joints to be A H R1 R2 R3 Balustrade height 1000
filled with joint filler mm mm kN kN kN kN h3) l
(by customer)
9000 111 53 44 104 4) 4)
114
+5
±5 10000 119 56 47
135 -0
L= 175 +10
4) 4)
-0
11000 126 59 49 123 4) 4)
support
surface 15000 169 78 63 162 5) 5)
front face
900 (1000)
Carrying force min. 50 kN 510 the truss must be
min. 300
(1030)
930
Ø 100 extended by 417 mm.
FFL Z 3) Support loads for two
intermediate supports
(1050)
min. 2300
on request.
±5
Drive station
916 4) Dimensions for balustrade
430 height of 1,000 mm.
539
5) Free spaces, overhead
Y
H=
Z FFL
100,110,120 X,Y clearance, safety
clearance; celling
+20
(1050)
1150 0
deflectors, wedging
H2 -10
H1 -10
R23)
100=4500 0 110=4200 0
R33) R43) R13)
120=3900
+20
0 All dimensions in mm.
L u±5 min. 6600 L m±5 ( L o min. 6800)
Observe national
L= +10 regulations!
-5
Subject to change.
100: L=(H+18.5)x5.6713+2719 2) 110: L=Hx5.1446+2719 2) 12 0: L=(H-18.5)x4.7046+2719 2) INT = intermediate
support(s)
Inclination Rise Length Transp. dimensions Pallet width A = 800 Pallet width A = 1000 Pallet width A = 1100
in one part Weight (kN) Supp. loads (kN) Weight (kN) Supp. loads (kN) Weight (kN) Supp. loads (kN) The stated loads are
H L h4) l G Gu Go R1 R2 R3 G Gu Go R1 R2 R3 G Gu Go R1 R2 R3 characteristic values
3000 19838 2460 20420 86 39 47 40 34 92 92 42 50 44 39 108 95 44 52 46 42 116 according to EN 1990.
10° 4000 25509 2470 26180 104 48 56 46 41 119 111 51 60 53 47 139 115 53 62 57 50 149
5000 31180 2470 31940 130 61 69 56 50 148 143 67 76 70 61 168 150 70 80 77 67 178
3000 16746 2460 17380 77 34 43 36 30 78 82 37 45 40 35 91 85 39 46 42 38 98
12° 4000 21450 2470 22190 93 42 51 42 36 100 99 45 54 47 41 117 102 47 56 50 44 126
5000 26155 2470 27000 106 49 57 47 41 122 116 54 62 56 48 143 121 57 65 61 52 154
30
Transportation dimensions
hmax. = 2470 mm
E +10
0
Schindler
A
D
C
B
h4)
G
30
Detail Z
185 +100
+10 +10
L= -5 175 0 l (max. = 17000 mm)
otherwise delivery in several parts
Gaps at joints
to be filled with
joint filler Detail X Detail Y
(by customer) one intermediate supports two or more intermediate supports
400
Entire support
surface smooth
385
and level
450
min. 2300
1412
F C 1412 loads T2, D2, M1, M3 etc. are
equally distributed among
A
1000
B the supports on the left and
D D
1150 +20
right side.
1150 +20
1) 1)
=
drive stations must be
A
C
C
E
E
travel direction
mounted always on the same
=
end.
Section F-F Detail A All dimensions in mm.
Entire support surface Tension station
D smooth and level End support - movable
150
All loads in KN.
C
FFL 360 +10 L +30
Observe national regulations!
B
185 +10
Subject to change.
(100)
A
Detail B
Drive station
600 +10
min.250 min.250 50
E +10
300
(100)
Truss joint A
Lateral
Support distance
Skirt panel cladding valid for horizontal installation
5 FFL
Upper edge (by customer) Width A (mm) 1000 1200 1400
of pallet
40
Rough t min 5900 5900 5900
concrete
max 11500 11000 10500
min.550
(35) d min 5900 5900 5900
max 11500 11000 10500
E +10
m1...m17 min 5751 5501 5251
max 11500 11000 10500
Speed
v = 0.5–0.65 m/s
Nominal rise according
to EN 115 with
A = 1000 mm
Size S: max. 13 m
All dimensions in
mm. Observe national
regulations!
Subject to changes.
Detail Z
Detail X
(1 intermediate support)
X1 = X2 = X3 =
Speed
v = 0.5 – 0.65 m/s
Nominal rise according to
1104
EN 115 with A = 1000 mm
max. 16 m
min. 300
Observe national
m2 = 0,577. (x1 + x2 - L1) - 1540
regulations.
400 Subject to changes.
- 10
X,Y
m2 =
30°
- 10
Please contact Schindler for support loads, motor rating, transport dimensions and weight !
Please contact Schindler for dimensions relating to truss extensions, double drives, frequency
converters and lighting installations.
Please request detail information Z, X and Y for expansion joints, seismic specifcations and wind
loads respectively from Schindler.
Please contact the supplying factory for availability and delivery date.
For outdoor installation, Please contact Schindler. For speed V=0.75m/s please contact Schindler.
WIF 90029EN-01/2016