THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
MULTIPLIED SPL ISSUED FOR APPROVAL
REVISED AS PER SEC COMMENTS
ISSUED FOR APPROVAL
DESCRIPTION
DAR
DAR
BY
20-Sep-23
05-Oct-23
DATE
NO.
REVISIONS
DRAWN
BY M.W
DATE:- 26-May-23
CHECKED
BY N.A
DATE:- 26-May-23
OPRG. DEPT.
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
APPROVED/CERTF.
INFORMATION
BY:-
DATE:- DATE
DOCUMENT TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
ABQAIQ SAUDI ARABIA JOB ORDER NO. 3-1813001.08 DWG. CONT. SHT. EE-6
SEC-E (2004/10)
PROJECT INFORMATION INDEX
PTS No: 20EN1028
REVISION NO. DATE REVISION DESCRIPTION DESIGNER COMPANY NAME CONTRACTOR NO REMARKS
1 9/20/2023 REVISED AS PER SEC COMMENTS DAR INTERNATIONAL ENGINEERING CONSULTANCY 20EN1028
2 5/10/2023 MULTIPLIED SPL ISSUED FOR APPROVAL DAR INTERNATIONAL ENGINEERING CONSULTANCY 20EN1028
ALARM
POINT TYPE
CLASS
1 TRIP ALARMS
4 MEASUREMENTS
115KV ALARMS
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
E
SPARK 115/33kV SUBSTATION#3 E01 115KV CB ALARMS:
AA1E1Q
005KF1.L
K26A (43, 44) DS/ES IN MAINTENANCE HAND CRANK ALARM/
=E01+LCC X5:47 D0.SP16 BCU_6MD85_SIEMENSNT
K26B (43, 44) INSERTED NORMAL
GGIO4.In
AA1E1Q
d8.stVal
005KF1.L
CB A601 IN MAINTENANCE HAND ALARM/
=E01+LCC X5:21 D0.SP16 K26 (43, BCU_6MD85_SIEMENS
44) NT
CRANK INSERTED NORMAL
GGIO4.In
d7.stVal
ALARM/
=E01+LCC X5:108 K73 (43,44)
BCU_6MD85_SIEMENSNT CB A601 AUTO TRIP ALARM
NORMAL
AA1E1Q
005KF1.L
DS & ES MOTOR RUNNING TIME ALARM/
=E01+LCC X5:45 D0.SP16 K15 (53, BCU_6MD85_SIEMENS
54) NT
EXCEEDED NORMAL
GGIO4.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E01+LCC X5:43 D0.SP16 K97 (31, BCU_6MD85_SIEMENS
32) NT DS/ES CONTROL SUPPLY FAIL
NORMAL
GGIO4.In
AA1E1Q SPARK
d10.stVal K95 (31, 32),
005KF1.L SS#3 E01
K95A (31, 32), ALARM/ ALARM/
=E01+LCC X5:44 D0.SP16 BCU_6MD85_SIEMENSNT DS & ES MOTOR SUPPLY FAIL CB A601 4001
K95B (31, 32), NORMAL NORMAL
GGIO5.In
AA1E1Q K95C (31, 32) URGENT
d6.stVal
005KF1.L ALARM
ALARM/
=E01+LCC X5:20 D0.SP16 K91 (31, BCU_6MD85_SIEMENS
32) NT CB A601 MOTOR SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d8.stVal
005KF1.L
ALARM/
=E01+LCC X5:50 D0.SP16 K12A (51,BCU_6MD85_SIEMENS
52) NT DS/ES LOCK POSITION
NORMAL
GGIO4.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E01+LCC X5:48 D0.SP16 K30 (43, BCU_6MD85_SIEMENS
44) NT DS SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E01+LCC X5:49 D0.SP16 K31 (43, BCU_6MD85_SIEMENS
44) NT ES SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d3.stVal
005KF1.L
CB A601 CTPU (METROCIL) O/V ALARM/
=E01+LCC -- D0.SP16 -- BCU_6MD85_SIEMENSNT
PROTECTION ALARM NORMAL
GGIO9.In
AA1E1Q
d16.stVal
005FN1.
=6D01+CB 74TCS-1 ALARM/
50BF:C14 LD0.SP1 50BF-7VK87 NT CB A601 TRIP CIRCUIT 1 FAULTY
F/TCS.R1 (5,13) NORMAL
6GGIO3.I
AA1E1Q
nd5.stVal
005KF1.L
CB A601 TRIP CIRCUIT 1 DC SUPPLY ALARM/
=E01+LCC X5:33 D0.SP16 K93 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
G00KF1
d9.stVal-
=6D01+CB 15. ALARM/
50BF:D3 74TCS-2 (2,4) 50BF-7VK87 NT CB A601 TRIP CIRCUIT 2 FAULTY
F/TCS.R1 Ind4.stVa NORMAL
AA1E1Q
l
005KF1.L
CB A601 TRIP CIRCUIT 2 DC SUPPLY ALARM/
=E01+LCC X5:35 D0.SP16 K94 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
AA1E1Q
d10.stVal
004KF1.L
ALARM/
=E01+LCC X21:20 D0.SP16 K106 (71,72) COMM_BCU NT CB A601 BCU DC SUPPLY FAIL
NORMAL SPARK
GGIO5.In
AA1E1Q
d12.stVal SS#3 E01
004KF1.L
ALARM/ CB A601 FAULTY /
=E01+LCC X21:21 D0.SP16 K13 (71,72) COMM_BCU NT CB A601 BCU RELAY FAULTY 4002
NORMAL PROT. NORMAL
GGIO5.In
AA1E1Q FLTY
d14.stVal
005KF1.L
ALARM/ ALARM
=E01+LCC -- D0.SP16 -- COMM_BCU NT CB A601 BCU UNDER TEST
NORMAL
GGIO5.In
AA1E1Q
d15.stVal
003FN11
GW1-SRV-1 CB A601 BCU SAS COMMUNICATION ALARM/
=E01+LCC INTERNAL .LD0.SP1 INTERNAL NT
GW2-SEV-2 BOTH CHANNELS FAIL NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
=6D01+CB 74DC (1,3), CBF A601 DC SUPPLY FAIL / DC MCB ALARM/
X6:3 D0.SP16 COMM_BCU NT
F/TCS.R1 F221 (21,22) TRIP NORMAL
GGIO7.In
AA1E1Q
d.stVal
000KF1.L
=6D01+CB 50BF ALARM/
X6:2 D0.SP16 COMM_BCU NT CBF A601 RELAY FAULTY
F/TCS.R1 (B7,B10) NORMAL
GGIO7.In
AA1E1Q
d3.stVal
003FN11
=6D01+CB CBF A601 PROT. SAS ALARM/
INTERNAL .LD0.SP1 INTERNAL 50BF-7VK87 NT
F/TCS.R1 COMMUNICATION FAIL (CH-1 & CH-2) NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:99 D0.SP16 K46 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
AA1E1Q
d1.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:100 D0.SP16 K49 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
d2.stVal
GIS PS01_3 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:101 K52 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
GIS PS01_5 SF6 GAS PRESSURE HIGH ALARM/ E
=E01+LCC X5:103 K60 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
ALARM/
=E01+LCC X5:38 D0.SP16 K57 (21,22)
BCU_6MD85_SIEMENS
NT CB A601 TRIP COIL-2 LOCKOUT
NORMAL
GGIO3.In
d12.stVal
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
ALARM/
=E01+LCC X5:59 D0.SP16 K23 (21,22)
BCU_6MD85_SIEMENS
NT CB A601 LCC DC SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E01+LCC X5:58 D0.SP16 K24 (13,14)
BCU_6MD85_SIEMENS
NT CB A601 LCC DC MCB TRIP/OFF
NORMAL
GGIO5.In
d2.stVal
ALARM/
=E01+LCC X5:54 K98 (31,32)
BCU_6MD85_SIEMENS
NT CB A601 INDICATION SUPPLY FAIL
NORMAL
AA1E1Q
005KF1.L K99 (21,22),
ALARM/
=E01+LCC X5:57 BCU_6MD85_SIEMENS
D0.SP16 K108 (21,22), NT CB A601 LCC AC SUPPLY FAIL
NORMAL
AA1E1Q F23 (11,12)
GGIO5.In
d4.stVal
005KF1.L F21 (11,12),
ALARM/
=E01+LCC X5:56 BCU_6MD85_SIEMENS
D0.SP16 F22 (11,12), NT CB A601 LCC AC MCB TRIP
NORMAL SPARK
AA1E1Q F23 (11,12)
GGIO5.In
d5.stVal SS#3 E01
005KF1.L
ALARM/ CB A601 ALARM/
=E01+LCC X5:53 D0.SP16 K14 (13,14)BCU_6MD85_SIEMENS
NT CB A601 LCC ANNUNCIATOR FAULTY 4005
NORMAL NON_URG NORMAL
GGIO5.In
AA1E1Q ENT
d11.stVal
005KF1.L
CB A601 LCC ANNUNCIATOR DC ALARM/ ALARM
=E01+LCC X5:51 D0.SP16 F11 (12, BCU_6MD85_SIEMENS
11) NT
SUPPLY FAIL NORMAL
GGIO5.In
AA1E1Q
d9.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNCH CHECK FAIL (DELTA V)
NORMAL
GGIO1.In
AA1E1Q
d14.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNCH CHECK FAIL (DELTA F)
NORMAL
GGIO1.In
AA1E1Q
d15.stVal
005KF2.L
CB A601 SYNCH CHECK FAIL (DELTA ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
PHI) NORMAL
GGIO1.In
AA1E1Q
d16.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNC CHECK BLOCK (VT FF)
AA1E1Q NORMAL
GGIO1.In
005FN11
d13.stVal
=6D01+CB .LD0. TRIP/ SPARK
INTERNAL INTERNAL 50BF/7VK87 T CB A601 CBF 50BF PROTECTION OPTD
F/TCS.R1 CCRBRF NORMAL SS#3 E01
AA1E1Q
1.OpIn.g CB A601 OPERATE/
4006
005FN11
eneral 86BF/A601 (5, CBF NORMAL
=6D01+CB CB A601 86D01+CBF/TCS.R1 LOCKOUT TRIP/ PROT.
50BF:C13 .LD0.SP1 50BF/7VK87 T
F/TCS.R1 AA1E1Q 7) RELAY OPTD NORMAL OPTD
6GGIO1.I
005FN11
nd6.stVal
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:39 K27 (83, BCU_6MD85_SIEMENS
84) NT OFF / ON
6GGIO8.I
AA1E1Q TROLLEY
nd13.stV
005FN11
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:40 S43R (11,BCU_6MD85_SIEMENS
12) NT OFF / ON
6GGIO8.I
AA1E1Q LOCAL
nd14.stV
005FN11 SPARK
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO SS#3 E01
=E01+LCC X5:41 S43R (21,BCU_6MD85_SIEMENS
22) NT OFF / ON OFF / ON 4007
6GGIO8.I
AA1E1Q BCU CB A601
nd15.stV
005FN11 REMOTE
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:42 S43R (31,BCU_6MD85_SIEMENS
32) OFF / ON
6GGIO8.I
AA1E1Q REMOTE
nd16.stV
005FN11
al
.LD0.SP1 ALARM/
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS
NT CB A601 BAY BLOCK
6GGIO8.I NORMAL
nd13.stV
al
SPARK 115/33kV SUBSTATION#3 E01 115/33KV SPARK CKT-A ALARMS:
AA1E1Q
005FN1.
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM CH-A ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd15.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM CH-B ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd16.stV
005FN1. SPARK
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM F.O ALARM / SS#3 E01
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q TELECOMM. FAIL (BOTH CHANNELS) NORMAL SPARK
nd14.stV 380kV BSP ALARM /
005FN2. 4008
al CKT-A NORMAL
=6D01+L1. System. SPARK 380kV BSP CKT-A FPFM CH-A ALARM / COMM
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL URGENT
O2.Ind31
005FN2. ALARM
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM CH-B ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL
O2.Ind32
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM F.O ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI TELECOMM. FAIL (BOTH CHANNELS) NORMAL
AA1E1Q
O2.Ind23
005FN1.
.stVal
=6D01+L1. SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 RELAY VT FUSE FAIL NORMAL
6GGIO2.I
AA1E1Q
nd5.stVal
000KF1.L
=6D01+L1. 87L/21/67N-2 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R2 (K3,K4) RELAY FAULTY NORMAL
GGIO3.In
d.stVal
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-AFPSM PROT. ALARM / E
TS2 (1,2) FPSM_7SD522 NT
R2 J9 6GGIO2.I RELAY UNDER TEST NORMAL
AA1E1Q
nd14.stV
000KF1.L
al
=6D01+L1. 74DC2 (1,3), SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
X6:3 D0.SP16 COMM-BCU NT
R2 AA1E1Q F221 (21,22) DC SUPPLY FAIL NORMAL
GGIO3.In
005FN1.
d2.stVal
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL
nd15.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 OptGGIO RELAY VT FUSE FAIL NORMAL
AA1E1Q
1.Ind5.st
000KF1.L
Val
=6D01+L1. 87L/21/67N-1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R1 (M11,M12) RELAY FAULTY NORMAL
GGIO3.In
d5.stVal
=6D01+L1. MICOM SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
TS2 (1,2) FPFM_P546 NT
R1 P546 : E14 RELAY UNDER TEST NORMAL
AA1E1Q
000KF1.L SPARK
=6D01+L1. 74DC1 (11,3), SPARK 380kV BSP CKT-A FPFM PROT. ALARM / SS#3 E01
X6:3 D0.SP16 COMM-BCU NT
R1 AA1E1Q QFR1(21,22) DC SUPPLY FAIL NORMAL SPARK
GGIO3.In FAULTY /
005FN1.
d6.stVal 380kV BSP 4009
NORMAL
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM / CKT-A
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL PROT.
nd15.stV ALARM
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
O2.Ind19
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIST. FUNCTION BLOCKED NORMAL
O2.Ind20
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DEF FUNCTION BLOCKED NORMAL
O2.Ind22
005FN1.
=6D01+L1. .stVal
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
nd11.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I DIST. FUNCTION BLOCKED NORMAL
AA1E1Q
nd12.stV
005FN1.
al
=6D01+L1. SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 AA1E1Q DEF FUNCTION BLOCKED NORMAL
6GGIO2.I
005FN1.
nd1.stVal
=6D01+L1. 7SD522 : LD0.DPG SPARK 380kV BSP CKT-A FPSM ALARM /
K02 (2, 4) FPSM_7SD522 NT
R2 J7 GIO1.DP
AA1E1Q PROTECTION OUT NORMAL
CSO.stV
005FN2.
=6D01+L1. MICOM System.U al SPARK 380kV BSP CKT-A FPFM ALARM /
K01 (1,10) FPFM_P546 NT
R1 P546 : E12 srGGIO1.
AA1E1Q PROTECTION OUT NORMAL
DPCSO1
005FN1.
=6D01+L1. .stVal
LD0.LDL SPARK 380kV BSP CKT-AFPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
p.Loc.phs
005FN1.
=6D01+L1. .A
LD0.LDL SPARK 380kV BSP CKT-A FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
p.Loc.phs
005FN1.
=6D01+L1. .B
LD0.LDL SPARK 380kV BSP CKT-A FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O DIFF. PROTECTION PH.B OPTD NORMAL
AA1E1Q
p.Loc.phs
005FN1.
.C
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
005FN1.
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd2.stVal
005FN1.
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
6GGIO1.I
005FN1.
nd3.stVal
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
nd12.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
nd13.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I DIST. PROTECTION Z3. OPTD NORMAL
nd14.stV
al
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/ E
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
nd14.stV
005FN1.
=6D01+L1. al
LD0.ZCP SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DIST. AIDED OPTD NORMAL
.general(
005FN1.
=6D01+L1. ST)
LD0.ZCV SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PSOF1.O DIST. SOTF OPTD NORMAL
p.general
=6D01+L1. (ST) SPARK 380kV BSP CKT-A FPSM 50/51-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-R OPTD NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-A 86F-2 TRIP TRIP/ E
86F2 (12,18) FPSM_7SD522 T
R2 K17 6GGIO3.I RELAY OPTD NORMAL
AA1E1Q
nd11.stV
005FN1.
al
=6D01+L1. 7SD522 : SPARK 380kV BSP CKT-A 86BU-2 TRIP/
LD0.SP1 86BU2 (12,18)FPSM_7SD522 T
R2 J1 AA1E1Q LOCKOUT RELAY OPTD NORMAL
6GGIO3.I
005FN2.
nd9.stVal
=6D01+L1. MICOM System. SPARK 380kV BSP CKT-A 86F-1 TRIP TRIP/
86F1 (6,8) FPFM_P546 T
R1 P546 : E2 OptGGIO
AA1E1Q RELAY OPTD NORMAL
1.Ind19.s
005FN2.
=6D01+L1. MICOM System. tVal SPARK 380kV BSP CKT-A 86BU-1 TRIP/
86BU1 (6,8) FPFM_P546 T
R1 P546 : E4 OptGGIO
AA1E1Q LOCKOUT RELAY OPTD NORMAL
1.Ind18.s
005FN1.
=6D01+L1. tVal
LD0.SP1 SPARK 380kV BSP CKT-A FPSM INTER TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO2.I
AA1E1Q TRIP SEND NORMAL
nd13.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPSM TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 GosGGI
AA1E1Q INTERTRIP RECEIVE NORMAL
O2.Ind18
005FN1.
.stVal
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-A 85R-2 INTER TRIP/
85R2 (A1,A3) FPSM_7SD522 T
R2 J3 6GGIO3.I
AA1E1Q TRIP RECEIVE OPTD NORMAL
nd02.stV
005FN2.
=6D01+L1. MICOM System. al SPARK 380kV BSP CKT-A 85R-1 INTER TRIP/
85R1 (1,3) FPFM_P546 T
R1 P546 : E6 OptGGIO
AA1E1Q TRIP RECEIVE OPTD NORMAL
1.Ind10.s
005FN2.
=6D01+L1. tVal
System. SPARK 380kV BSP CKT-A FPFM INTER TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q TRIP SEND NORMAL
O2.Ind24
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI INTERTRIP RECEIVE NORMAL
AA1E1Q
O2.Ind17
000KF1.L
.stVal QFHT (21,22),
=6D01+L1. 7SD522 : CB A601 FPSM PROTECTION PANEL ALARM/
D0.SP16 FPSM_7SD522 NT
R2 P17 QFPS (21,22) AC SUPPLY FAIL NORMAL
GGIO3.In
d4.stVal
=6D01+L1. 7SD522 : 74IO-2 (1,3), CB A601 FPSM PROTECTION PANEL ALARM/
FPSM_7SD522 NT
R2 J4 F222 (21,22) IN/OUT DC SUPPLY FAIL NORMAL
SPARK
=6D01+L1. 7SD522 : 74IND-2 (1,3), CB A601 FPSM PROTECTION PANEL ALARM/ SS#3 E01
FPSM_7SD522 NT SPARK
R2 J6 F223 (21,22) INDICATION DC SUPPLY FAIL NORMAL
380kV BSP ALARM/
4011
CKT-A NORMAL
=6D01+L1. MICOM 74IO1 (3,11), CB A601 FPFM PROTECTION PANEL ALARM/ NON
FPFM_P546 NT
R1 P546 : E8 QFR2 (21,22) IN/OUT DC SUPPLY FAIL NORMAL URGENT
ALARM
74IND1
=6D01+L1. MICOM CB A601 FPFM PROTECTION PANEL ALARM/
(3,11), QFR3 FPFM_P546 NT
R1 P546 : E10 INDICATION DC SUPPLY FAIL NORMAL
AA1E1Q (21,22)
000KF1.L
=6D01+L1. MICOM QFHT (21,22), CB A601 FPFM PROTECTION PANEL AC ALARM/
D0.SP16 FPFM_P546 NT
R1 P546 : C2 QFPS (21,22) SUPPLY FAIL NORMAL
GGIO3.In
AA1E1Q
d8.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 FUSE ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
FAIL ALARM NORMAL
GGIO1.In
AA1E1Q
d7.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 ALARM/
=E01+LCC X18 (5,6) D0.SCS S1 :X18 (5,6)
BCU_6MD85_SIEMENS
NT
ISOLATOR OPEN NORMAL SPARK
WI4.Pos.
AA1E1Q
stVal SS#3 E01
005KF1.L
SPARK 380kV BSP CKT-A VT-601 ALARM/ SPARK FAILED /
=E01+LCC X5:66 D0.SP16 KT6 (6,8) BCU_6MD85_SIEMENS
NT 4012
ISOLATOR INCOMPLETE NORMAL 380kV BSP NORMAL
GGIO2.In
AA1E1Q CKT-A VT
d11.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 MAIN ALARM/ FAIL
=E01+LCC X5:60 D0.SP16 K17(31,32) BCU_6MD85_SIEMENS
NT
MCB TRIP / OFF NORMAL
GGIO2.In
AA1E1Q
d15.stVal
005KF1.L
K102(R,Y,B) SPARK 380kV BSP CKT-A VT-601 ALARM/
=E01+LCC X5:61 D0.SP16 BCU_6MD85_SIEMENS
NT
(13,14) BRANCH MCB TRIP / OFF NORMAL
GGIO2.In
d16.stVal
SPARK 115/33kV SUBSTATION#3 E01 115/33KV TRANSFORMER ALARMS:
AA1E1Q
003KF2.L
T601 MAIN TANK OIL LEVEL LOW ALARM/
=6T1+LCP X3:23, 24 D1.DIOG 71Q1 (3,4) IOM_A2-P849 NT
AA1E1Q ALARM NORMAL
GIO1.Ind
003FN1.
011.stVal
LD0.SP1 T601 MAIN TANK OIL LEVEL HIGH ALARM/
=6T1+LCP X3:25, 26 71Q1 (5,6) IOM_A2-P849 NT
6GGIO3.I ALARM NORMAL
nd15.stV
al T601 MAIN TANK PRESSURE RELIEF ALARM/
=6T1+LCP X3:7, 8 63P1 (11,14) IOM_A2-P849 NT
DEVICE (63P1) ALARM NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 OLTC PRESSURE RELIEF DEVICE ALARM/ E
=6T1+LCP X3:13, 14 63P4 (11,14) IOM_A2-P849 NT
(63P4) ALARM NORMAL
ALARM/
=6T1+LCP X5:**, ** -- IOM_A2-P849 NT T601 FIRE PROTECTION FAULTY
NORMAL
Q1, Q2 ALARM/
+6T1+AVC X6:4 COMM-BCU NT T601 AVC RELAY DC MCB FAIL
(21,22) NORMAL
ALARM/
+6T1+AVC X6:2 K90F (4,8) COMM-BCU NT T601 AVC RELAY FAULTY
NORMAL
ALARM/
=6T1+LCP X3 (53,54) 45M: (19, 20) DGA NT T601 GAS ANALYZER SERVICE ALARM.
NORMAL
ALARM/
=6T1+LCP X3 (55,56) 45M: (22, 24) COMM-BCU NT T601 GAS ANALYZER FAULTY
NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 GAS ANALYZER GENERAL HIGH ALARM/ E
=6T1+LCP INTERNAL INTERNAL DGA NT
STAGE-2 ALARM NORMAL
AA1E1Q
003FN1.
T601 MAIN TRF TANK GAS DETECTOR ALARM/
=6T1+LCP X3:37, 38 LD0.SP1 63D (1,2) IOM_A2-P849 NT
ALARM NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
IO BOX 87T1 ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT T601 SET-1 87T-1 PROT. RELAY FAULTY
(A2:G16) (J11,J12) NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
IO BOX T601 SET-1 87T-1 PROT. DC SUPPLY ALARM/
+6T1+R1 IOM_A2-P849
D0.SP16 QFR1 (21,22), RLA (3,11) NT
(A2:G10) FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d10.stVal
003FN1.
T601 SET-1 87T-1 PROT. RELAY UNDER ALARM /
+6T1+R1 87T1:F4 LD0.SP1 TS1 (13,14) FPFM-P643 NT
TEST NORMAL
6GGIO1.I
AA1E1Q
nd5.stVal
000KF1.L
ALARM/
+6T1+R1 X6:1, 2 D0.SP16 A2 (N11,N12) COMM-BCU NT T601 I/O BOX RELAY FAULTY
NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
T601 I/O BOX DC SUPPLY FAIL / DC ALARM/
+6T1+R1 X6:1, 3 D0.SP16 QFR2 (21,22), RLB
COMM-BCU
(3,11) NT SPARK
MCB TRIP NORMAL
GGIO4.In
AA1E1Q SS#3 T601
d10.stVal
000KF1.L TRANSFO
87T2 (B7, ALARM/ FAULTY/
+6T1+R2 X6:1,2 D0.SP16 COMM-BCU NT T601 SET-2 87T-2 PROT. RELAY FAULTY RMER 4014
B10) NORMAL NORMAL
GGIO4.In
AA1E1Q PROT.
d13.stVal
000KF1.L FLTY
27M2 (1,3), T601 SET-2 87T-2 PROT. RELAY DC ALARM/ ALARM
+6T1+R2 X6:1,3 D0.SP16 COMM-BCU NT
F221 (2,22) SUPPLY FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d14.stVal
000KF1.L
TS87T-2A/ T601 SET-2 87T-2 PROT. RELAY UNDER ALARM /
+6T1+R2 87T2:B12 D0.SP16 FPSM-7UT85 NT
AA1E1Q 2B/2C (17,18)
GGIO5.In
TEST NORMAL
003FN1.
d4.stVal
LD0.SP1 T601 SET-1 87T-1 PROT.RELAY SAS ALARM/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I
AA1E1Q COMM. CH-1 & CH-2 FAIL NORMAL
nd15.stV
003FN1.
al
LD0.SP1 T601 I/O BOX SAS COMM. CH-1 & CH-2 ALARM/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I
AA1E1Q FAIL NORMAL
nd15.stV
003FN1.
al
LD0.SP1 T601 SET-2 87T-2 PROT.RELAY SAS ALARM/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 NT
6GGIO1.I COMM. CH-1 & CH-2 FAIL NORMAL
AA1E1Q
nd16.stV
003KF2.L
al
=6T1+OLT Q8 (Axb1, ALARM/
X7:17,18 D1.DIOG 90-6RTV NT T601 OLTC MOTOR SUPPLY FAIL
C AXc1) NORMAL
GIO1.Ind
AA1E1Q
011.stVal
003KF2.L
=6T1+OLT ALARM/
D1.DIOG F1 (A1, A2) 90-6RTV NT T601 OLTC CONTROL DC SUPPLY FAIL
C AA1E1Q NORMAL
GIO1.Ind
003KF2.L
017.stVal
D1.GEN ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC OUT OF STEP ALARM
GGIO.Al
AA1E1Q NORMAL
m05.stVa
003KF2.L
l
D1.GEN ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC BLOCKED
GGIO.Al
AA1E1Q NORMAL
m01.stVa
003KF2.L
l
D1.ATCC ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC U/V ALARM
1.BlkMin NORMAL
AA1E1Q
Vol.gener
003KF2.L
al ALARM/
+6T1+AVC INTERNAL D1.ATCC INTERNAL 90-6RTV NT T601 AVC O/C ALARM
NORMAL
1.BlkAOv
.stVal
ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC O/V ALARM
NORMAL
ALARM/
+6T1+AVC X6:4 Q1 (21,22) COMM-BCU NT T601 AVC CONTROL DC SUPPLY FAIL
AA1E1Q NORMAL
003KF2.L
RTV- D1.GEN QFVT ALARM/
+6T1+AVC 90-6RTV NT T601 AVC VOLTAGE SUPPLY FAIL
90:H10 GGIO.Al (221,222) NORMAL
m06.stVa
l Q19 (AXc1, ALARM/
=6T1+LCP XX:** IOM_A2-P849 NT T601 SPARE COOLING FAN MCB TRIP
AXb1) NORMAL
ALARM/
=6T1+LCP X7:9, 10 27A (14, 11) IOM_A2-P849 NT T601 MK PANEL AC SUPPLY FAIL
NORMAL
=6T1+OLT ALARM/
1KMSF (4,8) IOM_A2-P849 NT T601 OLTC PANEL AC SUPPLY FAIL
C NORMAL
AA1E1Q
000KF1.L
QFPS (21,22), ALARM/
+6T1+AVC X6:7 D0.SP16 90-6RTV NT T601 AVC PANEL AC SUPPLY FAIL
QFHT (21,22) NORMAL
GGIO6.In
AA1E1Q
d6.stVal
000KF1.L T601 PROTECTION-1 PANEL
IO BOX QFR4 (21,22), ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT INDICATION DC SUPPLY FAIL / MCB
(A2:G14) RLD (3,11) NORMAL
GGIO4.In
AA1E1Q TRIP
d12.stVal
000KF1.L
IO BOX QFR3 (21,22), T601 PROTECTION-1 PANEL IN/OUT DC ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT
(A2:G12) RLC (3,11) SUPPLY FAIL / MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d12.stVal
000KF1.L
IO BOX QFPS (21,22), T601 PROTECTION-1 PANEL AC MCB ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT
(A2:G8) QFHT (21,22) TRIP NORMAL
GGIO4.In
d12.stVal T601 PROTECTION-2 PANEL
F223 (21,22), ALARM/
+6T1+R2 87T2:B13 FPSM-7UT85 NT INDICATION DC SUPPLY FAIL / MCB
27IND (1,3) NORMAL
TRIP
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN1. COD TRE
LD0.SP1 T601 SET-1 HV 51NP E/F PROTECTION TRIP/ E
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/ SPARK
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL SS#3 T601
nd13.stV TRANSFO OPERATE /
003FN1. 4016
al RMER NORMAL
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/ PROT
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL OPTD
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50NS E/F PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51NS E/F PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN2.
al
Protectio T601 SET-2 LV 87REF-2 RESTRICTED TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85
n.LzrLvw
AA1E1Q EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 SBEF STAND BY EARTH TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50NP E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51NP E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
System. T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI
AA1E1Q PH-B OPTD NORMAL
O2.Ind2.s
003FN2.
tVal
System. T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI PH-R OPTD NORMAL
O2.Ind3.s
No
tVal T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL siginal in INTERNAL FPSM-7UT85 T
AA1E1Q PH-Y OPTD NORMAL
scheme
003FN2.
Protectio T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q PH-B OPTD NORMAL
PTOC1.
003FN2.
Op.phsA
Protectio T601 SET-2 LV 50NS E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q OPTD. NORMAL
PTOC1.
003FN2.
Op.phsB
Protectio T601 SET-2 LV 51NS E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2 OPTD. NORMAL
PTOC1.
Op.phsC
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
003FN1. E
TRIP/
+6T1+R1 87T1:D4 LD0.SP1 94T-1(1,3) FPFM-P643 T T601 94T-1 TRIP RELAY OPTD
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd8.stVal
System. TRIP/
+6T1+R2 87T2:D14 94T-2 (A2,A4) FPSM-7UT85 T T601 94T-2 TRIP RELAY OPTD
OptGGIO NORMAL
1.Ind16.s
tVal T601 MAIN TANK PRESSURE RELIEF TRIP/
=6T1+LCP X4:7, 8 63P1 (21,24) IOM_A2-P849 T
DEVICE (63P1) OPTD. NORMAL
ALARM/
=E01+LCC -- INTERNAL
BCU_6MD85_SIEMENS
NT T601 VT-602 FUSE FAIL ALARM
NORMAL
ALARM/
=E01+LCC X19 (5,6) S1 :X19 (5,6)
BCU_6MD85_SIEMENS
NT T601 VT-602 ISOLATOR OPEN
NORMAL
ALARM/
=E01+LCC X5:66 KT6A (6,8)
BCU_6MD85_SIEMENS
NT T601 VT-602 ISOLATOR INCOMPLETE
NORMAL
ALARM/
=E01+LCC X5:64 K20 (31,32)
BCU_6MD85_SIEMENS
NT T601 VT-602 MAIN MCB TRIP / OFF SPARK
NORMAL
SS#3 T601 FAILED /
4022
TRANSFO NORMAL
K103 (R,Y,B) ALARM/ RMER VT
=E01+LCC X5:65 BCU_6MD85_SIEMENS
NT T601 VT-602 BRANCH MCB TRIP / OFF
(13,14) NORMAL
ALARM/
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 T601 LV VT FUSE FAIL ALARM
NORMAL
Q411,Q412,Q
413,Q421,Q4 ALARM/
=BH05/IC X7:23 BCPU / REF 620 T601 LV VT MCB TRIP
22,Q423,Q42 NORMAL
4(21,22)
ALARM/
=BH05/IC INTERNAL AA1E1Q INTERNAL BCPU / REF 620 T601 LV VT-304 RACK OUT
003KF2.L NORMAL
D1.GEN
=6T1+OLT GGIO.Al LOCAL/
-- S132A (9,10) 90-6RTV NT T601 OLTC CONTROL MODE IN LOCAL
C m11.stVa REMOTE
SPARK
l/ SS#3 T601
Ind021.st T601 SAS CONTROL MODE AUTHORITY LOCAL/ TRANSFO LOCAL /
+6T1+AVC INTERNAL Val INTERNAL 90-6RTV NT 4023
SET TO SAS/ERCC REMOTE RMER TAP REMOTE
AA1E1Q CHANGER
003KF2.L
LOCAL/ REMOTE
+6T1+AVC RTV-90:I3 D1.DIOG 1KOL (4, 8) 90-6RTV NT T601 AVC CONTROL MODE IN LOCAL
REMOTE
GIO1.Ind
006.stVal
SPARK 115/33kV SUBSTATION#3 E02 115KV CB ALARMS:
AA1E1Q
005KF1.L
K26A (43, 44) DS/ES IN MAINTENANCE HAND CRANK ALARM/
=E02+LCC X5:47 D0.SP16 BCU_6MD85_SIEMENS
NT
K26B (43, 44) INSERTED NORMAL
GGIO4.In
AA1E1Q
d8.stVal
005KF1.L
CB A602 IN MAINTENANCE HAND ALARM/
=E02+LCC X5:21 D0.SP16 K26 (43, BCU_6MD85_SIEMENS
44) NT
CRANK INSERTED NORMAL
GGIO4.In
d7.stVal
ALARM/
=E02+LCC X5:108 K73 (43,44)
BCU_6MD85_SIEMENS
NT CB A602 AUTO TRIP ALARM
NORMAL
AA1E1Q
005KF1.L
DS & ES MOTOR RUNNING TIME ALARM/
=E02+LCC X5:45 D0.SP16 K15 (53, BCU_6MD85_SIEMENS
54) NT
EXCEEDED NORMAL
GGIO4.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E02+LCC X5:43 D0.SP16 K97 (31, BCU_6MD85_SIEMENS
32) NT DS/ES CONTROL SUPPLY FAIL
NORMAL
GGIO4.In
AA1E1Q SPARK
d10.stVal K95 (31, 32),
005KF1.L SS#3 E02
K95A (31, 32), ALARM/ ALARM/
=E02+LCC X5:44 D0.SP16 BCU_6MD85_SIEMENS
NT DS & ES MOTOR SUPPLY FAIL CB A602 4024
K95B (31, 32), NORMAL NORMAL
GGIO5.In
AA1E1Q K95C (31, 32) URGENT
d6.stVal
005KF1.L ALARM
ALARM/
=E02+LCC X5:20 D0.SP16 K91 (31, BCU_6MD85_SIEMENS
32) NT CB A602 MOTOR SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d8.stVal
005KF1.L
ALARM/
=E02+LCC X5:50 D0.SP16 K12A (51,BCU_6MD85_SIEMENS
52) NT DS/ES LOCK POSITION
NORMAL
GGIO4.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E02+LCC X5:48 D0.SP16 K30 (43, BCU_6MD85_SIEMENS
44) NT DS SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E02+LCC X5:49D0.SP16 K31 (43, BCU_6MD85_SIEMENS
44) NT ES SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d3.stVal
005KF1.L
CB A602 CTPU (METROCIL) O/V ALARM/
=E02+LCC -- D0.SP16 -- BCU_6MD85_SIEMENS
NT
PROTECTION ALARM NORMAL
GGIO9.In
AA1E1Q
d16.stVal
005FN1.
=6D02+CB 74TCS-1 ALARM/
50BF:C14 LD0.SP1 50BF-7VK87 NT CB A602 TRIP CIRCUIT 1 FAULTY
F/TCS.R1 (5,13) NORMAL
6GGIO3.I
nd5.stVal
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
CB A602 TRIP CIRCUIT 1 DC SUPPLY ALARM/
=E02+LCC X5:33 D0.SP16 K93 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
G00KF1
d9.stVal-
=6D02+CB 15. ALARM/
50BF:D3 74TCS-2 (2,4) 50BF-7VK87 NT CB A602 TRIP CIRCUIT 2 FAULTY
F/TCS.R1 Ind4.stVa NORMAL
AA1E1Q
l
005KF1.L
CB A602 TRIP CIRCUIT 2 DC SUPPLY ALARM/
=E02+LCC X5:35 D0.SP16 K94 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
AA1E1Q
d10.stVal
004KF1.L
ALARM/
=E02+LCC X21:20 D0.SP16 K106 (71,72) COMM_BCU NT CB A602 BCU DC SUPPLY FAIL
NORMAL SPARK
GGIO5.In
AA1E1Q
d12.stVal SS#3 E02
004KF1.L
ALARM/ CB A602 FAULTY /
=E02+LCC X21:21 D0.SP16 K13 (71,72) COMM_BCU NT CB A602 BCU RELAY FAULTY 4025
NORMAL PROT. NORMAL
GGIO5.In
AA1E1Q FLTY
d14.stVal
005KF1.L
ALARM/ ALARM
=E02+LCC -- D0.SP16 -- COMM_BCU NT CB A602 BCU UNDER TEST
NORMAL
GGIO5.In
AA1E1Q
d15.stVal
003FN11
GW1-SRV-1 CB A602 BCU SAS COMMUNICATION ALARM/
=E02+LCC INTERNAL .LD0.SP1 INTERNAL NT
GW2-SEV-2 BOTH CHANNELS FAIL NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
=6D02+CB 74DC (1,3), CBF A602 DC SUPPLY FAIL / DC MCB ALARM/
X6:3 D0.SP16 COMM_BCU NT
F/TCS.R1 F221 (21,22) TRIP NORMAL
GGIO7.In
AA1E1Q
d.stVal
000KF1.L
=6D02+CB 50BF ALARM/
X6:2 D0.SP16 COMM_BCU NT CBF A602 RELAY FAULTY
F/TCS.R1 (B7,B10) NORMAL
GGIO7.In
AA1E1Q
d3.stVal
003FN11
=6D02+CB CBF A602 PROT. SAS ALARM/
INTERNAL .LD0.SP1 INTERNAL 50BF-7VK87 NT
F/TCS.R1 COMMUNICATION FAIL (CH-1 & CH-2) NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:99 D0.SP16 K46 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
AA1E1Q
d1.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:100 D0.SP16 K49 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
d2.stVal
GIS PS01_3 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:101 K52 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:90 D0.SP16 K67 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d9.stVal
005KF1.L
K53 (71,72), ALARM/
=E02+LCC X5:24 D0.SP16 BCU_6MD85_SIEMENS
NT CB A602 CLOSING LOCKOUT ALARM
K56 (71,72) NORMAL
GGIO2.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:91 D0.SP16 K45 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d2.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:92 D0.SP16 K48 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d3.stVal
005KF1.L
GIS PS01_3 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:93 D0.SP16 K51 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d4.stVal
005KF1.L
CB A602 PS01_4 SF6 GAS PRESSURE ALARM/
=E02+LCC X5:94 D0.SP16 K56 (31,32)
BCU_6MD85_SIEMENS
NT
LOW STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_5 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:95 D0.SP16 K59 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d6.stVal
005KF1.L
GIS PS01_6 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:96 D0.SP16 K62 (31,32)
BCU_6MD85_SIEMENS
NT SPARK
STAGE-2 NORMAL
GGIO7.In
AA1E1Q SS#3 E02 ALARM/
d7.stVal 4027
005KF1.L CB A602 NORMAL
GIS PS01_7 SF6 GAS PRESSURE LOW ALARM/ LOCKOUT
=E02+LCC X5:97 D0.SP16 K65 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d8.stVal
005KF1.L
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:98 D0.SP16 K68 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d9.stVal
005KF1.L
CB A602 CLOSING COIL DC SUPPLY ALARM/
=E02+LCC X5:26 D0.SP16 K92 (31,32)
BCU_6MD85_SIEMENS
NT
FAIL NORMAL
GGIO4.In
AA1E1Q
d6.stVal
005KF1.L
ALARM/
=E02+LCC X5:19 D0.SP16 K3 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 MOTOR RUNTIME EXCEED
NORMAL
GGIO4.In
d5.stVal
CB A602 OPERATING MECHANISIM ALARM/
=E02+LCC X5:18 K4 (83,84)
BCU_6MD85_SIEMENS
NT
FAIL NORMAL
AA1E1Q
005KF1.L
ALARM/
=E02+LCC X5:31 D0.SP16 K54 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 TRIP COIL-1 LOCKOUT
NORMAL
GGIO3.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E02+LCC X5:38 D0.SP16 K57 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 TRIP COIL-2 LOCKOUT
NORMAL
GGIO3.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E02+LCC X5:59 D0.SP16 K23 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 LCC DC SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E02+LCC X5:58 D0.SP16 K24 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 LCC DC MCB TRIP/OFF
NORMAL
GGIO5.In
d2.stVal
ALARM/
=E02+LCC X5:54 K98 (31,32)
BCU_6MD85_SIEMENS
NT CB A602 INDICATION SUPPLY FAIL
NORMAL
AA1E1Q
005KF1.L K99 (21,22),
ALARM/
=E02+LCC X5:57 BCU_6MD85_SIEMENS
D0.SP16 K108 (21,22), NT CB A602 LCC AC SUPPLY FAIL
NORMAL
AA1E1Q F23 (11,12)
GGIO5.In
d4.stVal
005KF1.L F21 (11,12),
ALARM/
=E02+LCC X5:56 BCU_6MD85_SIEMENS
D0.SP16 F22 (11,12), NT CB A602 LCC AC MCB TRIP
NORMAL SPARK
AA1E1Q F23 (11,12)
GGIO5.In
d5.stVal SS#3 E02
005KF1.L
ALARM/ CB A602 ALARM/
=E02+LCC X5:53 D0.SP16 K14 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 LCC ANNUNCIATOR FAULTY 4028
NORMAL NON_URG NORMAL
GGIO5.In
AA1E1Q ENT
d11.stVal
005KF1.L
CB A602 LCC ANNUNCIATOR DC ALARM/ ALARM
=E02+LCC X5:51 D0.SP16 F11 (12, BCU_6MD85_SIEMENS
11) NT
SUPPLY FAIL NORMAL
GGIO5.In
AA1E1Q
d9.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNCH CHECK FAIL (DELTA V)
NORMAL
GGIO1.In
AA1E1Q
d14.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNCH CHECK FAIL (DELTA F)
NORMAL
GGIO1.In
AA1E1Q
d15.stVal
005KF2.L
CB A602 SYNCH CHECK FAIL (DELTA ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
PHI) NORMAL
GGIO1.In
AA1E1Q
d16.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNC CHECK BLOCK (VT FF)
AA1E1Q NORMAL
GGIO1.In
005FN11
d13.stVal
=6D02+CB .LD0. TRIP/ SPARK
INTERNAL INTERNAL 50BF/7VK87 T CB A602 CBF 50BF PROTECTION OPTD
F/TCS.R1 CCRBRF NORMAL SS#3 E02
1.OpIn.g CB A602 OPERATE/
4029
eneral CBF NORMAL
PROT.
OPTD
ED-682330, Rev-2 PAGE 22 OF 104
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI OP TRO
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT ADDR E rks
BER DESCRIPTION SPARK E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX LITRA INDEX ID
SS#3 E02 ESS ARM TYPE ST CEN
TIFIER
AA1E1Q CB A602 OPERATE/ COD TRE
4029
005FN11 CBF NORMAL E
=6D02+CB 86BF/A602 (5, CB A602 86D02+CBF/TCS.R1 LOCKOUT TRIP/ PROT.
50BF:C13 .LD0.SP1 50BF/7VK87 T
F/TCS.R1 AA1E1Q 7) RELAY OPTD NORMAL OPTD
6GGIO1.I
005FN11
nd6.stVal
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:39 K27 (83, BCU_6MD85_SIEMENS
84) NT OFF / ON
6GGIO8.I
AA1E1Q TROLLEY
nd13.stV
005FN11
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:40 S43R (11,BCU_6MD85_SIEMENS
12) NT OFF / ON
6GGIO8.I
AA1E1Q LOCAL
nd14.stV
005FN11 SPARK
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO SS#3 E02
=E02+LCC X5:41 S43R (21,BCU_6MD85_SIEMENS
22) NT OFF / ON OFF / ON 4030
6GGIO8.I
AA1E1Q BCU CB A602
nd15.stV
005FN11 REMOTE
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:42 S43R (31,BCU_6MD85_SIEMENS
32) OFF / ON
6GGIO8.I
AA1E1Q REMOTE
nd16.stV
005FN11
al
.LD0.SP1 ALARM/
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS
NT CB A602 BAY BLOCK
6GGIO8.I NORMAL
nd13.stV
al
SPARK 115/33kV SUBSTATION#3 E02 115/33KV SPARK CKT-B ALARMS:
AA1E1Q
005FN1.
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM CH-A ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd15.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM CH-B ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd16.stV
005FN1. SPARK
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM F.O ALARM / SS#3 E02
INTERNAL INTERNAL FPSM_7SD522 NT SPARK
R2 6GGIO1.I
AA1E1Q TELECOMM. FAIL (BOTH CHANNELS) NORMAL
nd14.stV 380kV BSP ALARM /
005FN2. 4031
al CKT-B NORMAL
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM CH-A ALARM / COMM
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL URGENT
O2.Ind31
005FN2. ALARM
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM CH-B ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL
O2.Ind32
005FN2.
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM F.O ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI TELECOMM. FAIL (BOTH CHANNELS) NORMAL
AA1E1Q
O2.Ind23
005FN1.
.stVal
=6D02+L2. SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 RELAY VT FUSE FAIL NORMAL
6GGIO2.I
AA1E1Q
nd5.stVal
000KF1.L
=6D02+L2. 87L/21/67N-2 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R2 AA1E1Q (K3,K4) RELAY FAULTY NORMAL
GGIO3.In
005FN1.
d.stVal
=6D02+L2. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-BFPSM PROT. ALARM /
TS2 (1,2) FPSM_7SD522 NT
R2 J9 6GGIO2.I RELAY UNDER TEST NORMAL
AA1E1Q
nd14.stV
000KF1.L
al
=6D02+L2. 74DC2 (1,3), SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
X6:3 D0.SP16 COMM-BCU NT
R2 AA1E1Q F221 (21,22) DC SUPPLY FAIL NORMAL
GGIO3.In
005FN1.
d2.stVal
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL
nd15.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D02+L2. al
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 OptGGIO RELAY VT FUSE FAIL NORMAL
AA1E1Q
1.Ind5.st
000KF1.L
Val
=6D02+L2. 87L/21/67N-1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R1 (M11,M12) RELAY FAULTY NORMAL
GGIO3.In
d5.stVal
=6D02+L2. MICOM SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
TS2 (1,2) FPFM_P546 NT
R1 P546 : E14 RELAY UNDER TEST NORMAL
AA1E1Q
000KF1.L SPARK
=6D02+L2. 74DC1 (11,3), SPARK 380kV BSP CKT-B FPFM PROT. ALARM / SS#3 E02
X6:3 D0.SP16 COMM-BCU NT
R1 AA1E1Q QFR1(21,22) DC SUPPLY FAIL NORMAL SPARK
GGIO3.In FAULTY /
005FN1.
d6.stVal 380kV BSP 4032
NORMAL
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM / CKT-B
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL PROT.
nd15.stV ALARM
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D02+L2. al
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
O2.Ind19
005FN2.
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI DIST. FUNCTION BLOCKED NORMAL
O2.Ind20
.stVal
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN2. COD TRE
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM / E
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DEF FUNCTION BLOCKED NORMAL
O2.Ind22
005FN1.
=6D02+L2. .stVal
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
nd11.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I DIST. FUNCTION BLOCKED NORMAL
AA1E1Q
nd12.stV
005FN1.
al
=6D02+L2. SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 AA1E1Q DEF FUNCTION BLOCKED NORMAL
6GGIO2.I
005FN1.
nd1.stVal
=6D02+L2. 7SD522 : LD0.DPG SPARK 380kV BSP CKT-B FPSM ALARM /
K02 (2, 4) FPSM_7SD522 NT
R2 J7 GIO1.DP
AA1E1Q PROTECTION OUT NORMAL
CSO.stV
005FN2.
al
=6D02+L2. MICOM System.U SPARK 380kV BSP CKT-B FPFM ALARM /
K01 (1,10) FPFM_P546 NT
R1 P546 : E12 srGGIO1.
AA1E1Q PROTECTION OUT NORMAL
DPCSO1
005FN1.
=6D02+L2. .stVal
LD0.LDL SPARK 380kV BSP CKT-BFPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
p.Loc.phs
005FN1.
=6D02+L2. .A
LD0.LDL SPARK 380kV BSP CKT-B FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
p.Loc.phs
005FN1.
=6D02+L2. .B
LD0.LDL SPARK 380kV BSP CKT-B FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O DIFF. PROTECTION PH.B OPTD NORMAL
AA1E1Q
p.Loc.phs
005FN1.
.C
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
005FN1.
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd2.stVal
005FN1.
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
6GGIO1.I
005FN1.
nd3.stVal
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
nd12.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
nd13.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z3. OPTD NORMAL
nd14.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
nd14.stV
005FN1.
=6D02+L2. al
LD0.ZCP SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DIST. AIDED OPTD NORMAL
.general(
005FN1.
=6D02+L2. ST)
LD0.ZCV SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PSOF1.O DIST. SOTF OPTD NORMAL
p.general
=6D02+L2. (ST) SPARK 380kV BSP CKT-B FPSM 50/51-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-R OPTD NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN2. COD TRE
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ E
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.R OPTD NORMAL
O2.Ind1.s
005FN2.
tVal SPARK
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ SS#3 E02
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.Y OPTD NORMAL SPARK
O2.Ind2.s OPERATE /
005FN2. 380kV BSP 4033
tVal NORMAL
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ CKT-B
INTERNAL INTERNAL FPFM_P546 T PROT.
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
O2.Ind3.s OPTD
005FN2.
=6D02+L2. tVal
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
S1.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
S2.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z3. OPTD NORMAL
S3.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
S3.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPSC
AA1E1Q DIST. AIDED OPTD NORMAL
H1.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B 21-1 DIST. TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.SofPS SOTF OPTD NORMAL
OF1.Op1
=6D02+L2. .general SPARK 380kV BSP CKT-B FPFM 50/51-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-R OPTD NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
SPARK COD TRE
=6D02+L2. 7SD522 : 74IND-2 (1,3), CB A602 FPSM PROTECTION PANEL ALARM/ SS#3 E02 E
FPSM_7SD522 NT SPARK
R2 J6 F223 (21,22) INDICATION DC SUPPLY FAIL NORMAL
380kV BSP ALARM/
4034
CKT-B NORMAL
=6D02+L2. MICOM 74IO1 (3,11), CB A602 FPFM PROTECTION PANEL ALARM/ NON
FPFM_P546 NT
R1 P546 : E8 QFR2 (21,22) IN/OUT DC SUPPLY FAIL NORMAL URGENT
ALARM
74IND1
=6D02+L2. MICOM CB A602 FPFM PROTECTION PANEL ALARM/
(3,11), QFR3 FPFM_P546 NT
R1 P546 : E10 INDICATION DC SUPPLY FAIL NORMAL
AA1E1Q (21,22)
000KF1.L
=6D02+L2. MICOM QFHT (21,22), CB A602 FPFM PROTECTION PANEL AC ALARM/
D0.SP16 FPFM_P546 NT
R1 P546 : C2 QFPS (21,22) SUPPLY FAIL NORMAL
GGIO3.In
AA1E1Q
d8.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 FUSE ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
FAIL ALARM NORMAL
GGIO1.In
AA1E1Q
d7.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 ALARM/
=E02+LCC X18 (5,6) D0.SCS S1 :X18 (5,6)
BCU_6MD85_SIEMENS
NT
ISOLATOR OPEN NORMAL SPARK
WI4.Pos.
AA1E1Q
stVal SS#3 E02
005KF1.L
SPARK 380kV BSP CKT-B VT-601 ALARM/ SPARK FAILED /
=E02+LCC X5:66 D0.SP16 KT6 (6,8) BCU_6MD85_SIEMENS
NT 4035
ISOLATOR INCOMPLETE NORMAL 380kV BSP NORMAL
GGIO2.In
AA1E1Q CKT-B VT
d11.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 MAIN ALARM/ FAIL
=E02+LCC X5:60 D0.SP16 K17(31,32) BCU_6MD85_SIEMENS
NT
MCB TRIP / OFF NORMAL
GGIO2.In
AA1E1Q
d15.stVal
005KF1.L
K102(R,Y,B) SPARK 380kV BSP CKT-B VT-601 ALARM/
=E02+LCC X5:61 D0.SP16 BCU_6MD85_SIEMENS
NT
(13,14) BRANCH MCB TRIP / OFF NORMAL
GGIO2.In
d16.stVal
SPARK 115/33kV SUBSTATION#3 E02 115/33KV TRANSFORMER ALARMS:
AA1E1Q
003KF2.L
T602 MAIN TANK OIL LEVEL LOW ALARM/
=6T2+LCP X3:23, 24 D1.DIOG 71Q1 (3,4) IOM_A2-P849 NT
AA1E1Q ALARM NORMAL
GIO1.Ind
003FN1.
011.stVal
LD0.SP1 T602 MAIN TANK OIL LEVEL HIGH ALARM/
=6T2+LCP X3:25, 26 71Q1 (5,6) IOM_A2-P849 NT
6GGIO3.I ALARM NORMAL
nd15.stV
al T602 MAIN TANK PRESSURE RELIEF ALARM/
=6T2+LCP X3:7, 8 63P1 (11,14) IOM_A2-P849 NT
DEVICE (63P1) ALARM NORMAL
ALARM/
=6T2+LCP X5:**, ** -- IOM_A2-P849 NT T602 FIRE PROTECTION FAULTY
NORMAL
Q1, Q2 ALARM/
+6T2+AVC X6:4 COMM-BCU NT T602 AVC RELAY DC MCB FAIL
(21,22) NORMAL
ALARM/
+6T2+AVC X6:2 K90F (4,8) COMM-BCU NT T602 AVC RELAY FAULTY
NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI TRO
PANEL SOURCE ADDRE T/ TEXT SPARK
SCADA TEXT ADDR E OP rks
BER DESCRIPTION E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX SS#3 T602
LITRA INDEX ID
ESS ARM TYPE ST CEN
TIFIER TRANSFO
ALARM/ COD TRE
RMER 4036
NORMAL E
T602 SET-1 SENSITIVE EARTH FAULT ALARM/ NON
+6T2+R1 INTERNAL INTERNAL FPFM-P643 NT
PROTECTION OPTD NORMAL URGENT
ALARM
ALARM/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 NT T602 SET-2 NEUTRAL CURRENT ALARM
NORMAL
ALARM/
=6T2+LCP X3 (53,54) 45M: (19, 20) DGA NT T602 GAS ANALYZER SERVICE ALARM.
NORMAL
ALARM/
=6T2+LCP X3 (55,56) 45M: (22, 24) COMM-BCU NT T602 GAS ANALYZER FAULTY
NORMAL
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN1. COD TRE
LD0.SP1 T602 SET-2 87T-2 PROT.RELAY SAS ALARM/ E
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 NT
6GGIO1.I COMM. CH-1 & CH-2 FAIL NORMAL
AA1E1Q
nd16.stV
003KF2.L
al
=6T2+OLT Q8 (Axb1, ALARM/
X7:17,18 D1.DIOG 90-6RTV NT T602 OLTC MOTOR SUPPLY FAIL
C AXc1) NORMAL
GIO1.Ind
AA1E1Q
011.stVal
003KF2.L
=6T2+OLT ALARM/
D1.DIOG F1 (A1, A2) 90-6RTV NT T602 OLTC CONTROL DC SUPPLY FAIL
C AA1E1Q NORMAL
GIO1.Ind
003KF2.L
017.stVal
D1.GEN ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC OUT OF STEP ALARM
GGIO.Al
AA1E1Q NORMAL
m05.stVa
003KF2.L
l
D1.GEN ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC BLOCKED
GGIO.Al
AA1E1Q NORMAL
m01.stVa
003KF2.L
l
D1.ATCC ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC U/V ALARM
1.BlkMin NORMAL
AA1E1Q
Vol.gener
003KF2.L
al ALARM/
+6T2+AVC INTERNAL D1.ATCC INTERNAL 90-6RTV NT T602 AVC O/C ALARM
NORMAL
1.BlkAOv
.stVal
ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC O/V ALARM
NORMAL
ALARM/
+6T2+AVC X6:4 Q1 (21,22) COMM-BCU NT T602 AVC CONTROL DC SUPPLY FAIL
AA1E1Q NORMAL
003KF2.L
RTV- D1.GEN QFVT ALARM/
+6T2+AVC 90-6RTV NT T602 AVC VOLTAGE SUPPLY FAIL
90:H10 GGIO.Al (221,222) NORMAL
m06.stVa
l Q19 (AXc1, ALARM/
=6T2+LCP XX:** IOM_A2-P849 NT T602 SPARE COOLING FAN MCB TRIP
AXb1) NORMAL
ALARM/
=6T2+LCP X7:9, 10 27A (14, 11) IOM_A2-P849 NT T602 MK PANEL AC SUPPLY FAIL
NORMAL
=6T2+OLT ALARM/
1KMSF (4,8) IOM_A2-P849 NT T602 OLTC PANEL AC SUPPLY FAIL
C NORMAL
AA1E1Q
000KF1.L
QFPS (21,22), ALARM/
+6T2+AVC X6:7 D0.SP16 90-6RTV NT T602 AVC PANEL AC SUPPLY FAIL
QFHT (21,22) NORMAL
GGIO6.In
AA1E1Q
d6.stVal
000KF1.L T602 PROTECTION-1 PANEL
IO BOX QFR4 (21,22), ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT INDICATION DC SUPPLY FAIL / MCB
(A2:G14) RLD (3,11) NORMAL
GGIO4.In
AA1E1Q TRIP
d12.stVal
000KF1.L
IO BOX QFR3 (21,22), T602 PROTECTION-1 PANEL IN/OUT DC ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT
(A2:G12) RLC (3,11) SUPPLY FAIL / MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d12.stVal
000KF1.L
IO BOX QFPS (21,22), T602 PROTECTION-1 PANEL AC MCB ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT
(A2:G8) QFHT (21,22) TRIP NORMAL
GGIO4.In
d12.stVal T602 PROTECTION-2 PANEL
F223 (21,22), ALARM/
+6T2+R2 87T2:B13 FPSM-7UT85 NT INDICATION DC SUPPLY FAIL / MCB
27IND (1,3) NORMAL
TRIP
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
003FN1. E
T602 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.B OPTD NORMAL
6GGIO1.I
AA1E1Q
nd3.stVal
003FN1.
TRIP/
+6T2+R1 87T1:D2 LD0.SP1 86T-1(5,7) FPFM-P643 T T602 86T-1 LOCKOUT RELAYOPTD.
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd6.stVal
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.R OPTD NORMAL
1.Op.phs
003FN2.
A
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.Y OPTD NORMAL
1.Op.phs
003FN2.
B
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.B OPTD NORMAL
1.Op.phs
003FN2.
C
System. TRIP/
+6T2+R2 87T2:D10 86T-2 (22,28) FPSM-7UT85 T T602 86T-2 LOCKOUT RELAYOPTD.
OptGGIO NORMAL
AA1E1Q
1.Ind15.s
003FN1.
tVal T602 SET-1 LV 87REF-1 RESTRICTED TRIP/
+6T2+R1 INTERNAL LD0.REF INTERNAL FPFM-P643 T
EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
AA1E1Q
p.general
003FN1.
T602 SET-1 SBEF STAND BY EARTH TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
FAULT PROTECTION OPTD. NORMAL
6GGIO1.I
AA1E1Q
nd6.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd7.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd8.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
AA1E1Q PH-B OPTD NORMAL
6GGIO1.I
003FN1.
nd9.stVal
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd10.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd11.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 50NP E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51NP E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/ SPARK
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL SS#3 T602
nd13.stV TRANSFO OPERATE /
003FN1. 4039
al RMER NORMAL
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/ PROT
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL OPTD
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50NS E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51NS E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN2.
al
Protectio T602 SET-2 LV 87REF-2 RESTRICTED TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85
n.LzrLvw
AA1E1Q EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 SBEF STAND BY EARTH TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw PH-R OPTD NORMAL
PDIF2.O
p.general
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN2. COD TRE
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/ E
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50NP E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51NP E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
System. T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI
AA1E1Q PH-B OPTD NORMAL
O2.Ind2.s
003FN2.
tVal
System. T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI PH-R OPTD NORMAL
O2.Ind3.s
No
tVal T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL siginal in INTERNAL FPSM-7UT85 T
AA1E1Q PH-Y OPTD NORMAL
scheme
003FN2.
Protectio T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q PH-B OPTD NORMAL
PTOC1.
003FN2.
Op.phsA
Protectio T602 SET-2 LV 50NS E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q OPTD. NORMAL
PTOC1.
003FN2.
Op.phsB
Protectio T602 SET-2 LV 51NS E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2 OPTD. NORMAL
AA1E1Q
PTOC1.
003FN1.
Op.phsC TRIP/
+6T2+R1 87T1:D4 LD0.SP1 94T-1(1,3) FPFM-P643 T T602 94T-1 TRIP RELAY OPTD
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd8.stVal
System. TRIP/
+6T2+R2 87T2:D14 94T-2 (A2,A4) FPSM-7UT85 T T602 94T-2 TRIP RELAY OPTD
OptGGIO NORMAL
1.Ind16.s
tVal T602 MAIN TANK PRESSURE RELIEF TRIP/
=6T2+LCP X4:7, 8 63P1 (21,24) IOM_A2-P849 T
DEVICE (63P1) OPTD. NORMAL
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN2. COD TRE
System. T602 HV WINDING TEMPERATURE TRIP/ E
=6T2+LCP X4:27, 28 49W1 (41,44) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind12.s
003FN2.
tVal
System. T602 LV WINDING TEMPERATURE TRIP/
=6T2+LCP X4:29, 30 49W2 (6,8) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind16.s
003FN2.
tVal
System. TRIP/
=6T2+LCP XX: ** R1 (7,8) IOM_A2-P849 T T602 RAPID PRESSURE OPTD. SPARK
OptGGIO
AA1E1Q NORMAL
1.Ind7.st SS#3 T602
003FN1.
Val TRANSFO
LD0.SP1 FPO:X5 FAULTY/ OPERATE /
=6T2+LCP X5:65, 66 IOM_A2-P849 NT T602 FIRE PROTCTION OPTD RMER 4041
6GGIO3.I (65,66) NORMAL NORMAL
AA1E1Q FIRE
SPARK
nd12.stV
003FN1. PROT
SS#3 T602
al
LD0.SP1 T602 MAIN TANK OIL TEMPERATURE ALARM/ OPTD
TRANSFO ALARM
=6T2+LCP X3:49, 50 26Q (31,34) IOM_A2-P849 NT 4042
6GGIO3.I HIGH STAGE-1 ALARM NORMAL RMER OIL /NORMAL
nd11.stV TEMP ST1
AA1E1Q SPARK
al ALARM
003FN1. SS#3 T602
T602 MAIN TANK BUCHHOLZ STAGE-1 ALARM/ ALARM/
=6T2+LCP X3:1, 2 LD0.SP1 63B (3,4) IOM_A2-P849 NT TRANSFO 4043
ALARM NORMAL NORMAL
6GGIO3.I
AA1E1Q RMER
nd2.stVal
003FN1. BUCH ST1
LD0.SP1 T602 HV WINDING TEMPERATURE ALARM/
=6T2+LCP X3:45, 46 49W1 (31,34) IOM_A2-P849 NT
6GGIO3.I
AA1E1Q HIGH STAGE-1 ALARM NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T602 LV WINDING TEMPERATURE ALARM/
=6T2+LCP X3:47, 48 49W2 (31,34) IOM_A2-P849 NT
6GGIO3.I HIGH STAGE-1 ALARM NORMAL
nd13.stV
al T602 FIBER OPTIC WINDING TEMP. ALARM/
=6T2+LCP CH1 (HV-U) CH1 (HV-U) FOM NT
MONITOR (FOWT) CH1 (HV-U) NORMAL
ALARM/
=E02+LCC -- INTERNAL
BCU_6MD85_SIEMENS
NT T602 VT-602 FUSE FAIL ALARM
NORMAL
ALARM/
=E02+LCC X19 (5,6) S1 :X19 (5,6)
BCU_6MD85_SIEMENS
NT T602 VT-602 ISOLATOR OPEN
NORMAL
ALARM/
=E02+LCC X5:66 KT6A (6,8)
BCU_6MD85_SIEMENS
NT T602 VT-602 ISOLATOR INCOMPLETE
NORMAL
ALARM/
=E02+LCC X5:64 K20 (31,32)
BCU_6MD85_SIEMENS
NT T602 VT-602 MAIN MCB TRIP / OFF SPARK
NORMAL
SS#3 T602 FAILED /
4045
TRANSFO NORMAL
K103 (R,Y,B) ALARM/ RMER VT
=E02+LCC X5:65 BCU_6MD85_SIEMENS
NT T602 VT-602 BRANCH MCB TRIP / OFF
(13,14) NORMAL
ALARM/
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 T602 LV VT FUSE FAIL ALARM
NORMAL
Q411,Q412,Q
413,Q421,Q4 ALARM/
=BH05/IC X7:23 BCPU / REF 620 T602 LV VT MCB TRIP
22,Q423,Q42 NORMAL
4(21,22)
ALARM/
=BH05/IC INTERNAL AA1E1Q INTERNAL BCPU / REF 620 T602 LV VT-304 RACK OUT
003KF2.L NORMAL
D1.GEN
=6T2+OLT GGIO.Al LOCAL/
-- S132A (9,10) 90-6RTV NT T602 OLTC CONTROL MODE IN LOCAL
C m11.stVa REMOTE SPARK
l/ SS#3 T602
Ind021.st TRANSFO LOCAL /
Val 4046
ED-682330, Rev-2 RMER TAP REMOTE PAGE 31 OF 104
CHANGER
REMOTE
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED
115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI OP TRO
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT ADDR E rks
BER DESCRIPTION E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX LITRA INDEX ID
ESS ARM TYPE ST CEN
TIFIER SPARK
SS#3 T602 COD TRE
T602 SAS CONTROL MODE AUTHORITY LOCAL/ TRANSFO LOCAL / E
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT 4046
SET TO SAS/ERCC REMOTE RMER TAP REMOTE
AA1E1Q CHANGER
003KF2.L
LOCAL/ REMOTE
+6T2+AVC RTV-90:I3 D1.DIOG 1KOL (4, 8) 90-6RTV NT T602 AVC CONTROL MODE IN LOCAL
REMOTE
GIO1.Ind
006.stVal
SPARE ADDRESS:
115KV INDICATIONS
115kV INDICATION
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
DEVICE IEC 101/104 TYPE
SOURCE PANEL SOURCE ADDRESS/IDENTIFI IED NAME POINT LOOP REMARKS
NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO ER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
STATION/PCC AUTHORITY
SAS/ERCC INTERNAL INTERNAL STATION/PCC AUTHORITY SAS/PCC STATION/PCC AUTHORITY SAS/PCC 4147
SPARE ADDRESS:
115KV COMMAND
115kV COMMANDS
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
SOURCE DEVICE IEC 101/104 TYPE OPEN
SOURCE ADDRESS / IED NAME REMARKS
PANEL NAME/NUMBER ADDRESS ID POINT NAME/ALARM DEVICE LOOP TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX LDC
CODE TYPE CENTRE
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS CIRCUIT BREAKER A601 COMMAND EXECUTED CLOSE/OPEN A601 BREAKER CLOSE/OPEN 1001
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D601 COMMAND EXECUTED CLOSE/OPEN D601 ISOLATOR CLOSE/OPEN 1002
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D602 COMMAND EXECUTED CLOSE/OPEN D602 ISOLATOR CLOSE/OPEN 1003
K601 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K601 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH
K602 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K602 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH
K603 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K603 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH
K604 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K604 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH
+6T1+AVC INTERNAL INTERNAL 90_6RTV GT-1 TAP COMMAND EXECUTED RAISE / LOWER GT-1 TAP RAISE / LOWER 1004
+6T1+AVC INTERNAL INTERNAL 90_6RTV GT-1 AVC COMMAND EXECUTED AUTO / MANUAL GT-1 AVC AUTO / MANUAL 1005
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS CIRCUIT BREAKER A602 COMMAND EXECUTED CLOSE/OPEN A602 BREAKER CLOSE/OPEN 1006
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D603 COMMAND EXECUTED CLOSE/OPEN D603 ISOLATOR CLOSE/OPEN 1007
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D604 COMMAND EXECUTED CLOSE/OPEN D604 ISOLATOR CLOSE/OPEN 1008
K601 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K605 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH
K602 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K606 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH
K603 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K607 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH
K604 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K608 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH
+6T2+AVC INTERNAL INTERNAL 90_6RTV GT-2 TAP COMMAND EXECUTED RAISE / LOWER GT-2 TAP RAISE / LOWER 1009
+6T2+AVC INTERNAL INTERNAL 90_6RTV GT-2 AVC COMMAND EXECUTED AUTO / MANUAL GT-2 AVC AUTO / MANUAL 1010
SAPRE ADDRESS:
115KV MEASUREMENTS
115kVMEASUREMENTS
LOCAL RANGE SCADA RANGE CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE
SOURCE IEC 101/104 CONTROL SYSTEM
SOURCE ADDRESS/IDENTIFIE NAME/NUMBE IED NAME CT RATIO VT RATIO UNIT OPEN LOOP TEST REMARKS
PANEL ADDRESS DATA/DEVICE TYPE
TB R R MIN MAX MIN MAX CONTROL CENTRE LDC
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MW 2001 -382.4 382.4 -32767 32767
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MVAR 2002 -382.4 382.4 -32767 32767
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS - 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 KV 2003 0 138 -32767 32767
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MW 2006 -382.4 382.4 -32767 32767
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MVAR 2007 -382.4 382.4 -32767 32767
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS - 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 KV 2008 0 138 -32767 32767
SPARE ADDRESS:
33KV ALARMS
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH03/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B413 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH03/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B413 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH03/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B413 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH03/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B413 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH03/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B413 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH03/OG X7.1:18 Q204 (21,22) COMM-BCU CB B413 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH03/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B413 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH04/CAP X7:18 74TC1 (1,3) BCPU / REF 620 CB B414 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH04/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B414 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH04/CAP X7:19 74TC2 (1,3) BCPU / REF 620 CB B414 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH04/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B414 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH04/CAP X7.1:11 IRF:X100 (3,4) COMM-BCU CB B414 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH04/CAP X7.1:18 Q204 (21,22) COMM-BCU CB B414 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH04/CAP X7:17 X902:X903 (19,20) BCPU / REF 620 CB B414 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH05/IC X7:18 74TC1 (1,3) BCPU / REF 620 CB A402 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH05/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A402 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH05/IC X7:19 74TC2 (1,3) BCPU / REF 620 CB A402 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH05/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A402 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH05/IC X7.1:11 IRF:X100 (3,4) COMM-BCU CB A402 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH05/IC X7.1:18 Q204 (21,22) COMM-BCU CB A402 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH05/IC X7:17 X902:X903 (19,20) BCPU / REF 620 CB A402 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH06/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B415 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH06/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B415 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH06/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B415 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH06/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B415 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH06/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B415 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH06/OG X7.1:18 Q204 (21,22) COMM-BCU CB B415 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH06/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B415 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH07/AUX X7:18 74TC1 (1,3) BCPU / REF 620 CB B416 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH07/AUX X7.1:17 Q201 (21,22) BCPU / REF 620 CB B416 TRIP CIRCUIT-1 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH07/AUX X7:19 74TC2 (1,3) BCPU / REF 620 CB B416 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH07/AUX X7.1:17 Q202 (21,22) BCPU / REF 620 CB B416 TRIP CIRCUIT-2 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH07/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU CB B416 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH07/AUX X7.1:18 Q204 (21,22) COMM-BCU CB B416 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH07/AUX X7:17 X902:X903 (19,20) BCPU / REF 620 CB B416 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH08/BS X7.1:11 IRF:X100 (3,4) COMM-BCU CB A401 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH08/BS X7.1:18 Q204 (21,22) COMM-BCU CB A401 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH08/BS X7:17 X902:X903 (19,20) BCPU / REF 620 CB A401 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
SPARK SS#3 33kV CB PROT. FAULTY/
NT FLTY ALARM NORMAL 4057
=BH08/BS X7:18 74TC1 (1,3) BCPU / REF 620 CB A401 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH08/BS X7.1:17 Q201 (21,22) BCPU / REF 620 CB A401 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
REV-2
=BH08/BS X7:19 74TC2 (1,3) BCPU / REF 620 CB A401 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH08/BS X7.1:17 Q201 (21,22) BCPU / REF 620 CB A401 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH10/AUX X7:18 74TC1 (1,3) BCPU / REF 620 CB B421 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH10/AUX X7.1:17 Q201 (21,22) BCPU / REF 620 CB B421 TRIP CIRCUIT-1 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH10/AUX X7:19 74TC2 (1,3) BCPU / REF 620 CB B421 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH10/AUX X7.1:17 Q202 (21,22) BCPU / REF 620 CB B421 TRIP CIRCUIT-2 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH10/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU CB B421 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH10/AUX X7.1:18 Q204 (21,22) COMM-BCU CB B421 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH10/AUX X7:17 X902:X903 (19,20) BCPU / REF 620 CB B421 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH11/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B422 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH11/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B422 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH11/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B422 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH11/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B422 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH11/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B422 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH11/OG X7.1:18 Q204 (21,22) COMM-BCU CB B422 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH11/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B422 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH12/IC X7:18 74TC1 (1,3) BCPU / REF 620 CB A403 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH12/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A403 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH12/IC X7:19 74TC2 (1,3) BCPU / REF 620 CB A403 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH12/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A403 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH12/IC X7.1:11 IRF:X100 (3,4) COMM-BCU CB A403 BCPU PROT. RELAY FAULTY ALARM / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH12/IC X7.1:18 Q204 (21,22) COMM-BCU CB A403 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH12/IC X7:17 X902:X903 (19,20) BCPU / REF 620 CB A403 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH13/CAP X7:18 74TC1 (1,3) BCPU / REF 620 CB B423 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH13/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B423 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH13/CAP X7:19 74TC2 (1,3) BCPU / REF 620 CB B423 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH13/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B423 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH13/CAP X7.1:11 IRF:X100 (3,4) COMM-BCU CB B423 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH13/CAP X7.1:18 Q204 (21,22) COMM-BCU CB B423 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH13/CAP X7:17 X902:X903 (19,20) BCPU / REF 620 CB B423 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH14/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B424 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL
=BH14/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B424 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL
=BH14/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B424 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL
=BH14/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B424 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL
=BH14/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B424 BCPU PROT. RELAY FAULTY ALARM / NORMAL
=BH14/OG X7.1:18 Q204 (21,22) COMM-BCU CB B424 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL
=BH14/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B424 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
=BH03/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B413 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH03/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B413 SPRING NOT CHARGED ALARM / NORMAL
=BH04/CAP X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B414 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH04/CAP X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B414 SPRING NOT CHARGED ALARM / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH05/IC X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A402 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH05/IC X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A402 SPRING NOT CHARGED ALARM / NORMAL
=BH06/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B415 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH06/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B415 SPRING NOT CHARGED ALARM / NORMAL
=BH07/AUX X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B416 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH07/AUX X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B416 SPRING NOT CHARGED ALARM / NORMAL
=BH08/BS X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A401 MOTOR SUPPLY FAIL ALARM / NORMAL
SPARK SS#3 33kV 33KV CB ALARM/
NT LOCKOUT NORMAL 4058
=BH08/BS X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A401 SPRING NOT CHARGED ALARM / NORMAL
=BH10/AUX X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B421 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH10/AUX X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B421 SPRING NOT CHARGED ALARM / NORMAL
=BH11/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B422 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH11/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B422 SPRING NOT CHARGED ALARM / NORMAL
=BH12/IC X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A403 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH12/IC X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A403 SPRING NOT CHARGED ALARM / NORMAL
=BH13/CAP X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B423 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH13/CAP X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B423 SPRING NOT CHARGED ALARM / NORMAL
=BH14/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B424 MOTOR SUPPLY FAIL ALARM / NORMAL
=BH14/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B424 SPRING NOT CHARGED ALARM / NORMAL
Q205 (21,22),
=BH03/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B413 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH03/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B413 AC MCBs TRIP ALARM / NORMAL
=BH03/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B413 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH03/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B413 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH04/CAP X7.1:18 Q204 (21,22) BCPU / REF 620 CB B414 DC MCBs TRIP ALARM / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
Q207 (11,12),
=BH04/CAP X7:14 Q208 (11,12) BCPU / REF 620 CB B414 AC MCBs TRIP ALARM / NORMAL
=BH04/CAP X7.1:18 Q203 (21,22) BCPU / REF 620 CB B414 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH04/CAP X7:14 Q207 (11,12), BCPU / REF 620 CB B414 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH05/IC X7.1:18 Q204 (21,22) BCPU / REF 620 CB A402 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH05/IC X7:14 Q208 (11,12) BCPU / REF 620 CB A402 AC MCBs TRIP ALARM / NORMAL
=BH05/IC X7.1:18 Q203 (21,22) BCPU / REF 620 CB A402 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH05/IC X7:14 Q207 (11,12), BCPU / REF 620 CB A402 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH06/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B415 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH06/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B415 AC MCBs TRIP ALARM / NORMAL
=BH06/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B415 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH06/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B415 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH07/AUX X7.1:18 Q204 (21,22) BCPU / REF 620 CB B416 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH07/AUX X7:14 Q208 (11,12) BCPU / REF 620 CB B416 AC MCBs TRIP ALARM / NORMAL
=BH07/AUX X7.1:18 Q203 (21,22) BCPU / REF 620 CB B416 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH07/AUX X7:14 Q207 (11,12), BCPU / REF 620 CB B416 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH08/BS X7.1:18 Q204 (21,22) BCPU / REF 620 CB A401 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH08/BS X7:14 Q208 (11,12) BCPU / REF 620 CB A401AC MCBs TRIP ALARM / NORMAL
=BH08/BS X7.1:18 Q203 (21,22) BCPU / REF 620 CB A401 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH08/BS X7:14 Q207 (11,12), BCPU / REF 620 CB A401INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH10/AUX X7.1:18 Q204 (21,22) BCPU / REF 620 CB B421 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH10/AUX X7:14 Q208 (11,12) BCPU / REF 620 CB B421 AC MCBs TRIP ALARM / NORMAL
=BH10/AUX X7.1:18 Q203 (21,22) BCPU / REF 620 CB B421 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH10/AUX X7:14 Q207 (11,12), BCPU / REF 620 CB B421 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH11/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B422 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH11/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B422 AC MCBs TRIP ALARM / NORMAL
=BH11/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B422 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH11/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B422 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH12/IC X7.1:18 Q204 (21,22) BCPU / REF 620 CB A403 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH12/IC X7:14 Q208 (11,12) BCPU / REF 620 CB A403 AC MCBs TRIP ALARM / NORMAL
=BH12/IC X7.1:18 Q203 (21,22) BCPU / REF 620 CB A403 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH12/IC X7:14 Q207 (11,12), BCPU / REF 620 CB A403 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH13/CAP X7.1:18 Q204 (21,22) BCPU / REF 620 CB B423 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH13/CAP X7:14 Q208 (11,12) BCPU / REF 620 CB B423 AC MCBs TRIP ALARM / NORMAL
=BH13/CAP X7.1:18 Q203 (21,22) BCPU / REF 620 CB B423 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH13/CAP X7:14 Q207 (11,12), BCPU / REF 620 CB B423 INDICATION DC SUPPLY FAIL ALARM / NORMAL
Q205 (21,22),
=BH14/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B424 DC MCBs TRIP ALARM / NORMAL
Q207 (11,12),
=BH14/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B424 AC MCBs TRIP ALARM / NORMAL
=BH14/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B424 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL
=BH14/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B424 INDICATION DC SUPPLY FAIL ALARM / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-R TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-Y TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-B TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50N INST E/F PROT OPTD TRIP / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
SPARK SS#3 33KV PROT. OPERATE/
OPTD NORMAL 4060
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51 DELAY O/C PROT OPTD PH-Y TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51 DELAY O/C PROT OPTD PH-B TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51N DELAY E/F PROT OPTD TRIP / NORMAL
=BH08/BS X7.1:12 86BS (17,19) COMM-BCU CB A401 86 LOCKOUT RELAY OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 CBF PROTECTION OPTD TRIP / NORMAL
=BH03/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B413 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 CBF PROTECTION OPTD TRIP / NORMAL
=BH04/CAP X7.1:13 86CBF (17,19) BCPU / REF 620 CB B414 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 CBF PROTECTION OPTD TRIP / NORMAL
=BH05/IC X7.1:13 86CBF (17,19) BCPU / REF 620 CB A402 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 SET-1 LV CBF PROTECTION OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 SET-2 LV CBF PROTECTION OPTD TRIP / NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 LV 86CBF LOCKOUT RELAY OPTD TRIP / NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 CBF PROTECTION OPTD TRIP / NORMAL
=BH06/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B415 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 CBF PROTECTION OPTD TRIP / NORMAL
=BH07/AUX X7.1:13 86CBF (17,19) BCPU / REF 620 CB B416 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 BCPU CBF PROTECTION OPTD TRIP / NORMAL
SPARK SS#3 33KV CBF PROT. OPERATE/
T OPTD NORMAL 4061
=BH08/BS X7.1:13 86CBF (17,19) BCPU / REF 620 CB A401 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 CBF PROTECTION OPTD TRIP / NORMAL
=BH10/AUX X7.1:13 86CBF (17,19) BCPU / REF 620 CB B421 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 CBF PROTECTION OPTD TRIP / NORMAL
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH11/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B422 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 CBF PROTECTION OPTD TRIP / NORMAL
=BH12/IC X7.1:13 86CBF (17,19) BCPU / REF 620 CB A403 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 SET-1 LV CBF PROTECTION OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 SET-2 LV CBF PROTECTION OPTD TRIP / NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 LV 86CBF LOCKOUT RELAY OPTD TRIP / NORMAL
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 CBF PROTECTION OPTD TRIP / NORMAL
=BH13/CAP X7.1:13 86CBF (17,19) BCPU / REF 620 CB B423 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 CBF PROTECTION OPTD TRIP / NORMAL
=BH14/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B424 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH03/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B413 VT MCB TRIP ALARM/ NORMAL
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B414 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH03/OG X7:20 Q401 (21,22) BCPU / REF 620 CB B414 VT MCB TRIP ALARM/ NORMAL
=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK OUT ALARM/ NORMAL
=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 VT-314 RACK IN ALARM/ NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH05/IC X7:20 Q412 (21,22) BCPU / REF 620 CB A402 VT MCB TRIP ALARM/ NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK OUT ALARM/ NORMAL
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK IN ALARM/ NORMAL
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH06/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B415 VT MCB TRIP ALARM/ NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 VT FUSE FAIL ALARM ALARM/ NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH07/AUX X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B416 VT MCB TRIP ALARM/ NORMAL
SPARK SS#3 FAILED/
NT 33kV VT NORMAL 4062
=BH010/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH010/AUX X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B421 VT MCB TRIP ALARM/ NORMAL
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH11/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B422 VT MCB TRIP ALARM/ NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH12/IC X7:20 Q412 (21,22) BCPU / REF 620 CB A403 VT MCB TRIP ALARM/ NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT-304 RACK OUT ALARM/ NORMAL
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT-304 RACK IN ALARM/ NORMAL
=BH13/CAP X7:20 Q401 (21,22) BCPU / REF 620 CB B423 VT MCB TRIP ALARM/ NORMAL
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB A423 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 VT-304 RACK OUT ALARM/ NORMAL
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 VT-314 RACK IN ALARM/ NORMAL
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 VT FUSE FAIL ALARM ALARM/ NORMAL
=BH14/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B424 VT MCB TRIP ALARM/ NORMAL
=BH03/OG X7:8 S103 (21,22) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH03/OG X7:10 S103 (23,24) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO LOCAL
=BH03/OG X7:10 S103 (18,17) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B413 REMOTE OFF/ON 4063
=BH03/OG X7:111 S103 (20,19) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO REMOTE
=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH05/IC X7:8 S103 (21,22) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH05/IC X7:10 S103 (23,24) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO LOCAL
SPARK SS#3
ED-682330, Rev-2 NT OFF/ON CB A402 REMOTE OFF/ON 4064 PAGE 51 OF 104
DOC. NO: ED-682330
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH05/IC X7:10 S103 (18,17) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A402 REMOTE OFF/ON 4064
=BH05/IC X7:111 S103 (20,19) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO REMOTE
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH04/CAP X7:8 S103 (21,22) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH04/CAP X7:10 S103 (23,24) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO LOCAL
=BH04/CAP X7:10 S103 (18,17) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B414 REMOTE OFF/ON 4065
=BH04/CAP X7:111 S103 (20,19) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO REMOTE
=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH06/OG X7:8 S103 (21,22) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH06/OG X7:10 S103 (23,24) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO LOCAL
=BH06/OG X7:10 S103 (18,17) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B415 REMOTE OFF/ON 4066
=BH06/OG X7:111 S103 (20,19) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO REMOTE
=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH07/AUX X7:8 S103 (21,22) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH07/AUX X7:10 S103 (23,24) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO LOCAL
=BH07/AUX X7:10 S103 (18,17) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B416 REMOTE OFF/ON 4067
=BH07/AUX X7:111 S103 (20,19) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO REMOTE
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH08/BS X7:8 S103 (21,22) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH08/BS X7:10 S103 (23,24) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO LOCAL
=BH08/BS X7:10 S103 (18,17) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A401 REMOTE OFF/ON 4068
=BH08/BS X7:111 S103 (20,19) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO REMOTE
=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH10/AUX X7:8 S103 (21,22) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH10/AUX X7:10 S103 (23,24) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO LOCAL
=BH10/AUX X7:10 S103 (18,17) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B421 REMOTE OFF/ON 4069
=BH10/AUX X7:111 S103 (20,19) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO REMOTE
REV-2
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH11/OG X7:8 S103 (21,22) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH11/OG X7:10 S103 (23,24) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO LOCAL
=BH11/OG X7:10 S103 (18,17) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B422 REMOTE OFF/ON 4070
=BH11/OG X7:111 S103 (20,19) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO REMOTE
=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH12/IC X7:8 S103 (21,22) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH12/IC X7:10 S103 (23,24) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO LOCAL
=BH12/IC X7:10 S103 (18,17) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A403 REMOTE OFF/ON 4071
=BH12/IC X7:111 S103 (20,19) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO REMOTE
=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH13/CAP X7:8 S103 (21,22) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH13/CAP X7:10 S103 (23,24) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO LOCAL
=BH13/CAP X7:10 S103 (18,17) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B423 REMOTE OFF/ON 4072
=BH13/CAP X7:111 S103 (20,19) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO REMOTE
=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH14/OG X7:8 S103 (21,22) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO TROLLEY /OFF
=BH14/OG X7:10 S103 (23,24) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO LOCAL
=BH14/OG X7:10 S103 (18,17) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B424 REMOTE OFF/ON 4073
=BH14/OG X7:111 S103 (20,19) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO REMOTE
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER SPARK SS#3 ADDRESS
NT OFF/ON CB B424 REMOTE OFF/ON 4073 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC
=BH07/AUX X7.1:35,41 KTA (3,7) BCPU / REF 620 AUX. TR-1 OIL LEVEL LOW ALARM ALARM/NORMAL
=BH07/AUX X7.1:36,42 KTT (3,7) BCPU / REF 620 AUX. TR-1 OIL LEVEL HIGH ALARM ALARM/NORMAL
=BH07/AUX X7.1:31,37 KBA (3,7) BCPU / REF 620 AUX. TR-1 BUCHHOLZ STAGE-1 ALARM ALARM/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 RMU-1 EARTH LEAKAGE OPTD ALARM/NORMAL
=BH07/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU AUX. TR-1 BCPU RELAY FAULTY ALARM/NORMAL
=BH07/AUX X7.1:18 Q204 (21,22) COMM-BCU AUX. TR-1 BCPU RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 BCPU RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH07/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-1 PROT RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 PROT RELAY SAS COMM. FAIL ALARM/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50N INST. E/F PROTECTION OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH07/AUX X7:21 KBT (3,7) BCPU / REF 620 AUX. TR-1 BUCHHOLZ STAGE-2 OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50N INST. E/F PROTECTION OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL
86M (42,48),
=BH07/AUX X7:13 X904 (13,14) BCPU / REF 620 AUX. TR-1 86T LOCKOUT RELAY OPTD TRIP/NORMAL
=BH10/AUX X7.1:35,41 KTA (3,7) BCPU / REF 620 AUX. TR-2 OIL LEVEL LOW ALARM ALARM/NORMAL
=BH10/AUX X7.1:36,42 KTT (3,7) BCPU / REF 620 AUX. TR-2 OIL LEVEL HIGH ALARM ALARM/NORMAL
=BH10/AUX X7.1:31,37 KBA (3,7) BCPU / REF 620 AUX. TR-2 BUCHHOLZ STAGE-1 ALARM ALARM/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 RMU-2 EARTH LEAKAGE OPTD ALARM/NORMAL
=BH10/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU AUX. TR-2 BCPU RELAY FAULTY ALARM/NORMAL
=BH10/AUX X7.1:18 Q204 (21,22) COMM-BCU AUX. TR-2 BCPU RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 BCPU RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH10/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-2 PROT RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
REV-2
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 PROT RELAY SAS COMM. FAIL ALARM/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50N INST. E/F PROTECTION OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL
=BH10/AUX X7:21 KBT (3,7) BCPU / REF 620 AUX. TR-2 BUCHHOLZ STAGE-2 OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50N INST. E/F PROTECTION OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL
86M (42,48),
=BH10/AUX X7:13 X904 (13,14) BCPU / REF 620 AUX. TR-2 86T LOCKOUT RELAY OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 87V-1 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-1 URGENT NORMAL 4080
ALARM
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 87V-2 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
=BH04+R1 X6:3 GP1:X11 (3,2) COMM-BCU CAP. BANK-1 SET-1 87C-1 PROT. RELAY FAULTY ALARM/NORMAL
74R1 (1,3),
=BH04+R1 X6:4 Q1 (21,22) COMM-BCU CAP. BANK-1 SET-1 87C-1 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL
=BH04+R1 X32:15 TS1A (3,4) GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY UNDER TEST ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL
=BH04+R1 X32:7 TS3 (17,18) GP1-REC670 CAP BANK-1 SET-1 87C-1 PROT RELAY VT MCB TRIP ALARM/NORMAL
SPARK SS#3 FAULTY/
NT CAPACITOR BANK-1 PROT. NORMAL 4081
FLTY.
=BH04+R1 X6:6 GP2:A (11,12) COMM-BCU CAP. BANK-1 SET-2 87C-2 PROT. RELAY FAULTY ALARM/NORMAL
74R2 (1,3),
=BH04+R1 X6:7 Q3 (21,22) COMM-BCU CAP. BANK-1 SET-2 87C-2 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL
=BH04+R1 SEL487V_B:47 TS2 (13,14) GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY UNDER TEST ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL
=BH04+R1 SEL487V_B:37 TS4 (25,26) GP-2 SEL487V CAP BANK-1 SET-2 87C-2 PROT RELAY VT MCB TRIP ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50N-1 INST E/F PROT OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51N-1 DELAY E/F PROT OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 87V-1 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL
86C1 (14,16),
=BH04+R1 X31:13 TS3 (11,12) GP1-REC670 CAP BANK-1 SET-1 86C-1 LOCKOUT RELAY OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T CAPACITOR BANK-1 PROT. NORMAL 4082
OPTD
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-R OPTD TRIP/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT SPARK SS#3 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER T CAPACITOR BANK-1 PROT. OPERATE/
NORMAL
ADDRESS
4082 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA
OPTDLITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50N-2 INST E/F PROT OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51N-2 DELAY E/F PROT OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 87V-2 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL
86C2 (6,8)
=BH04+R1 SEL487V_A:28 TS4 (5,6) GP-2 SEL487V CAP BANK-1 SET-2 86C-2 LOCKOUT RELAY OPTD TRIP/NORMAL
=BH04+R1 GP1_X32:5 C1 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL AC MCB TRIP ALARM/NORMAL
74IND1 (1,3),
=BH04+R1 GP1_X32:3 Q5 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL INDICATION SUPPLY FAIL ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
74IO1 (1,3),
=BH04+R1 GP1_X32:1 Q2 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL SET-1 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-1 NON NORMAL 4083
URGENT ALARM
74IO2 (1,3),
=BH04+R1 GP2_A:32 Q4 (21,22) GP-2 SEL487V CAP. BANK-1 PROTECTION PANEL SET-2 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL
QDC2(21,22),
=BH04+ACCS X6:6 RLB (3,11) COMM-BCU ACCS INDICATION DC SUPPLY FAIL ALARM/NORMAL
=BH04+R1 INTERNAL INTERNAL C264 CAP. BANK-1 CONTROLER (ACCS) OPEN COMMAND ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 87V-1 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-2 URGENT NORMAL 4084
ALARM
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 87V-2 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
=BH13+R1 X6:3 GP2:X11 (3,2) COMM-BCU CAP. BANK-2 SET-1 87C-1 PROT. RELAY FAULTY ALARM/NORMAL
74R1 (1,3),
=BH13+R1 X6:4 Q1 (21,22) COMM-BCU CAP. BANK-2 SET-1 87C-1 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH13+R1 X32:15 TS1A (3,4) GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY UNDER TEST ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL
=BH13+R1 X32:7 TS3 (17,18) GP2-REC670 CAP BANK-2 SET-1 87C-1 PROT RELAY VT MCB TRIP ALARM/NORMAL
SPARK SS#3 FAULTY/
NT CAPACITOR BANK-2 PROT. NORMAL 4085
FLTY.
=BH13+R1 X6:6 GP2:A (11,12) COMM-BCU CAP. BANK-2 SET-2 87C-2 PROT. RELAY FAULTY ALARM/NORMAL
74R2 (1,3),
=BH13+R1 X6:7 Q3 (21,22) COMM-BCU CAP. BANK-2 SET-2 87C-2 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL
=BH13+R1 SEL487V_B:47 TS2 (13,14) GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY UNDER TEST ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL
=BH13+R1 SEL487V_B:37 TS4 (25,26) GP-2 SEL487V CAP BANK-2 SET-2 87C-2 PROT RELAY VT MCB TRIP ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50N-1 INST E/F PROT OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51N-1 DELAY E/F PROT OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 87V-1 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL
86C1 (14,16),
=BH13+R1 X31:13 TS3 (11,12) GP2-REC670 CAP BANK-2 SET-1 86C-1 LOCKOUT RELAY OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T CAPACITOR BANK-2 PROT. NORMAL 4086
OPTD
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50N-2 INST E/F PROT OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51N-2 DELAY E/F PROT OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 87V-2 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL
86C2 (6,8)
=BH13+R1 SEL487V_A:28 TS4 (5,6) GP-2 SEL487V CAP BANK-2 SET-2 86C-2 LOCKOUT RELAY OPTD TRIP/NORMAL
=BH13+R1 GP2_X32:5 C1 (21,22) GP2-REC670 CAP. BANK-2 PROTECTION PANEL AC MCB TRIP ALARM/NORMAL
74IND1 (1,3),
=BH13+R1 GP2_X32:3 Q5 (21,22) GP2-REC670 CAP. BANK-2 PROTECTION PANEL INDICATION SUPPLY FAIL ALARM/NORMAL
74IO2 (1,3),
=BH13+R1 GP2_A:32 Q4 (21,22) GP-2 SEL487V CAP. BANK-2 PROTECTION PANEL SET-2 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL
=BH13+R1 INTERNAL INTERNAL C264 CAP. BANK-2 CONTROLER (ACCS) OPEN COMMAND ALARM/NORMAL
QDC1 (21,22),
3ACCS X6:5 RLA (3,11) COMM-BCU ACCS RELAY DC SUPPLY FAIL/MCB TRIP ALARM/NORMAL
Q01 (21,22),
3ACCS X6:8 Q02 (21,22) COMM-BCU ACCS CHANGE OVER DC MCB TRIP ALARM/NORMAL
3ACCS ACCS_N22 TS/1,2,3,4,5 (9,10) C264 ACCS RELAY UNDER TEST ALARM/NORMAL
3ACCS INTERNAL INTERNAL C264 ACCS RELAY RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH04+ACCS ACCS_P10 KM1(A1, A11) C264 ACCS SET IN LOCAL POSITION ALARM/NORMAL
SPARK SS#3
NT ACCS REMOTE OFF / ON 4089
=BH04+ACCS INTERNAL INTERNAL C264 ACCS BAY CONTROL AUTHORITY TO SAS/CRCC ALARM/NORMAL
=BH09 X7.1,11 87B1 (F11, F12), COMM-BCU BUS BAR-1 87B PROT. RELAY FAULTY ALARM/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH09 X1:33, 34 Q202 (21,22) COMM-BCU BUS BAR-1 87B PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
=BH09 X7:13 X911 (27,28) MICOM-P142 BUS BAR-1 87B PROT. RELAY UNDER TEST ALARM/NORMAL
SPARK SS#3 FAULTY/
NT 33KV BB PROT. FLTY ALARM NORMAL 4090
=BH09 X7.1,13 95B1 (26,28) COMM-BCU BUS BAR-1 95B CT SUPERVISION ALARM ALARM/NORMAL
=BH09 X7.1,12 95B1 (25,27) COMM-BCU BUS BAR-1 95B CT SUPERVISION FAULTY ALARM/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-R OPTD TRIP/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-Y OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T 33KV BB PROT. OPTD NORMAL 4091
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-B OPTD TRIP/NORMAL
=BH09 X7.1:19 86B (12,18) COMM-BCU BUS BAR-1 86B-A LOCKOUT RELAY OPTD TRIP/NORMAL
=BH08.1 X7:7 F800 (417,418) -IO1_REC670 BUS BAR-1 VT FUSE FAIL ALARM TRIP/NORMAL
=BH09 X7.1,11 87B1 (F11, F12), COMM-BCU BUS BAR-2 87B PROT. RELAY FAULTY ALARM/NORMAL
=BH09 X1:33, 34 Q202 (21,22) COMM-BCU BUS BAR-2 87B PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL
=BH09 X7:13 X911 (27,28) MICOM-P142 BUS BAR-2 87B PROT. RELAY UNDER TEST ALARM/NORMAL
SPARK SS#3 FAULTY/
NT 33KV BB PROT. FLTY ALARM NORMAL 4093
=BH09 X7.1,13 95B1 (26,28) COMM-BCU BUS BAR-2 95B CT SUPERVISION ALARM ALARM/NORMAL
=BH09 X7.1,12 95B1 (25,27) COMM-BCU BUS BAR-2 95B CT SUPERVISION FAULTY ALARM/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-R OPTD TRIP/NORMAL
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-Y OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T 33KV BB PROT. OPTD NORMAL 4094
=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-B OPTD TRIP/NORMAL
REV-2
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER SPARK SS#3 OPERATE/ ADDRESS
T 33KV BB PROT. OPTD NORMAL 4094 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
=BH09 X7.1:19 86B (12,18) COMM-BCU BUS BAR-2 86B-A LOCKOUT RELAY OPTD TRIP/NORMAL
=BH08.1 X7:7 F800 (417,418) -IO1_REC670 BUS BAR-2 VT FUSE FAIL ALARM TRIP/NORMAL
SPARE ADDRESS:
33KV INDICATIONS
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
BH03/OG INDICATIONS
S711 (3, 4)
BH03-O/G X7:2,3 BCPU / REF 620 CB B413 BREAKER RACK IN / OUT B413 BREAKER RACK IN / OUT 4154
S701 (3, 4)
BH04/CAP INDICATIONS
S711 (3, 4)
BH04-CAP X7:2,3 BCPU / REF 620 CB B414 BREAKER RACK IN / OUT B414 BREAKER RACK IN / OUT 4157
S701 (3, 4)
BH05/IC INDICATIONS
S711 (3, 4)
BH05-I/C X7:2,3 BCPU / REF 620 CB A402 BREAKER RACK IN / OUT A402 BREAKER RACK IN / OUT 4160
S701 (3, 4)
BH06/OG INDICATIONS
S711 (3, 4)
BH06-O/G X7:2,3 BCPU / REF 620 CB B415 BREAKER RACK IN / OUT B415 BREAKER RACK IN / OUT 4163
S701 (3, 4)
BH07/AUX INDICATIONS
S711 (3, 4)
BH07-SST X7:2,3 BCPU / REF 620 CB B416 BREAKER RACK IN / OUT B416 BREAKER RACK IN / OUT 4166
S701 (3, 4)
S711 (3, 4)
BH08-BS X7:2,3 BCPU / REF 620 CB A401 BREAKER RACK IN / OUT A401 BREAKER RACK IN / OUT 4169
S701 (3, 4)
BH10/AUX INDICATIONS
S711 (3, 4)
BH10-SST X7:2,3 BCPU / REF 620 CB B421 BREAKER RACK IN / OUT B421 BREAKER RACK IN / OUT 4173
S701 (3, 4)
BH11/OG INDICATIONS
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
S711 (3, 4)
BH11-O/G X7:2,3 BCPU / REF 620 CB B422 BREAKER RACK IN / OUT B422 BREAKER RACK IN / OUT 4176
S701 (3, 4)
BH12/IC INDICATIONS
S711 (3, 4)
BH12-I/C X7:2,3 BCPU / REF 620 CB A403 BREAKER RACK IN / OUT A403 BREAKER RACK IN / OUT 4179
S701 (3, 4)
BH13/CAP INDICATIONS
S711 (3, 4)
BH13-CAP X7:2,3 BCPU / REF 620 CB B423 BREAKER RACK IN / OUT B423 BREAKER RACK IN / OUT 4182
S701 (3, 4)
BH14/OG INDICATIONS
S711 (3, 4)
BH14-O/G X7:2,3 BCPU / REF 620 CB B424 BREAKER RACK IN / OUT B424 BREAKER RACK IN / OUT 4185
S701 (3, 4)
UF INDICATIONS
+3UFLS 81-1_D2 KM1 (1, 10) 81-1_P142 33KV UNDER FREQUENCY RELAY 81-1 STAGE-1/2/3/4 IN /OUT U/F RLY-1 STAGE-1/2/3/4 IN /OUT 4187
UV INDICATIONS
+3UVLS-1 27-1_D8 KM1 (1, 10) 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-1 IN/OUT U/V RLY-1 STAGE-1 IN/OUT 4188
+3UVLS-1 27-1_D10 KM2 (1, 10) 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-2 IN/OUT U/V RLY-1 STAGE-2 IN/OUT 4189
+3UVLS-1 27-1_D12 KM3 (1, 10) 27-1A_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-3 IN/OUT U/V RLY-1 STAGE-3 IN/OUT 4190
+3UVLS-2 27-2_D8 KM1 (1, 10) 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-1 IN/OUT U/V RLY-2 STAGE-1 IN/OUT 4191
+3UVLS-2 27-2_D10 KM2 (1, 10) 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-2 IN/OUT U/V RLY-2 STAGE-2 IN/OUT 4192
+3UVLS-2 27-2_D12 KM3 (1, 10) 27-2A_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-3 IN/OUT U/V RLY-2 STAGE-3 IN/OUT 4193
ACCS INDICATIONS
SPARE ADDRESS:
33KV COMMANDS
33kV COMMANDS
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
BH03/OG COMMANDS
BH03-O/G INTERNAL INTERNAL BCPU / REF 620 CB B413 COMMAND SELECTED CLOSE / OPEN CB B413 CLOSE / OPEN 1013 0
BH03-O/G INTERNAL INTERNAL BCPU / REF 620 CB B413 COMMAND EXECUTED CLOSE / OPEN CB B413 CLOSE / OPEN 1014 0
BH04/CAP COMMANDS
BH04-CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 COMMAND SELECTED CLOSE / OPEN CB B414 CLOSE / OPEN 1015 0
BH04-CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 COMMAND EXECUTED CLOSE / OPEN CB B414 CLOSE / OPEN 1016 0
BH05/IC COMMANDS
BH05-I/C INTERNAL INTERNAL BCPU / REF 620 CB A402 COMMAND SELECTED CLOSE / OPEN CB A402 CLOSE / OPEN 1017 0
BH05-I/C INTERNAL INTERNAL BCPU / REF 620 CB A402 COMMAND EXECUTED CLOSE / OPEN CB A402 CLOSE / OPEN 1018 0
BH06/OG COMMANDS
BH06-O/G INTERNAL INTERNAL BCPU / REF 620 CB B415 COMMAND SELECTED CLOSE / OPEN CB B415 CLOSE / OPEN 1019 0
BH06-O/G INTERNAL INTERNAL BCPU / REF 620 CB B415 COMMAND EXECUTED CLOSE / OPEN CB B415 CLOSE / OPEN 1020 0
BH07/AUX COMMANDS
BH07-SST INTERNAL INTERNAL BCPU / REF 620 CB B416 COMMAND SELECTED CLOSE / OPEN CB B416 CLOSE / OPEN 1021 0
BH07-SST INTERNAL INTERNAL BCPU / REF 620 CB B416 COMMAND EXECUTED CLOSE / OPEN CB B416 CLOSE / OPEN 1022 0
BH08-BS INTERNAL INTERNAL BCPU / REF 620 CB A401 COMMAND SELECTED CLOSE / OPEN CB A401 CLOSE / OPEN 1023 0
BH08-BS INTERNAL INTERNAL BCPU / REF 620 CB A401 COMMAND EXECUTED CLOSE / OPEN CB A401 CLOSE / OPEN 1024 0
BH10/AUX COMMANDS
BH10-SST INTERNAL INTERNAL BCPU / REF 620 CB B421 COMMAND SELECTED CLOSE / OPEN CB B421 CLOSE / OPEN 1025 0
BH10-SST INTERNAL INTERNAL BCPU / REF 620 CB B421 COMMAND EXECUTED CLOSE / OPEN CB B421 CLOSE / OPEN 1026 0
BH11/OG COMMANDS
BH11-O/G INTERNAL INTERNAL BCPU / REF 620 CB B422 COMMAND SELECTED CLOSE / OPEN CB B422 CLOSE / OPEN 1027 0
BH11-O/G INTERNAL INTERNAL BCPU / REF 620 CB B422 COMMAND EXECUTED CLOSE / OPEN CB B422 CLOSE / OPEN 1028 0
BH12/IC COMMANDS
BH12-I/C INTERNAL INTERNAL BCPU / REF 620 CB A403 COMMAND SELECTED CLOSE / OPEN CB A403 CLOSE / OPEN 1029 0
BH12-I/C INTERNAL INTERNAL BCPU / REF 620 CB A403 COMMAND EXECUTED CLOSE / OPEN CB A403 CLOSE / OPEN 1030 0
BH13/CAP COMMANDS
BH13-CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 COMMAND SELECTED CLOSE / OPEN CB B423 CLOSE / OPEN 1031 0
BH13-CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 COMMAND EXECUTED CLOSE / OPEN CB B423 CLOSE / OPEN 1032 0
BH14/OG COMMANDS
BH14-O/G INTERNAL INTERNAL BCPU / REF 620 CB B424 COMMAND SELECTED CLOSE / OPEN CB B424 CLOSE / OPEN 1033 0
BH14-O/G INTERNAL INTERNAL BCPU / REF 620 CB B424 COMMAND EXECUTED CLOSE / OPEN CB B424 CLOSE / OPEN 1034 0
UF COMMANDS
33kV COMMANDS
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
33KV UNDER FREQUENCY RELAY 81-1 STAGE-1/2 COMMAND
+3UFLS INTERNAL INTERNAL 81-1_P142 IN /OUT U/F RLY 81-1 STAGE-1/2 IN /OUT 1035
EXECUTED
UV COMMANDS
+3UVLS-1 INTERNAL INTERNAL 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-1 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-1 IN/OUT 1039
+3UVLS-1 INTERNAL INTERNAL 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-2 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-2 IN/OUT 1040
+3UVLS-1 INTERNAL INTERNAL 27-1A_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-3 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-3 IN/OUT 1041
+3UVLS-2 INTERNAL INTERNAL 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-1 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-1 IN/OUT 1042
+3UVLS-2 INTERNAL INTERNAL 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-2 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-2 IN/OUT 1043
+3UVLS-2 INTERNAL INTERNAL 27-2A_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-3 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-3 IN/OUT 1044
ACCS COMMANDS
=3ACCS INTERNAL INTERNAL C264 33KV ACCS COMMAND EXECUTED AUTO/MANUAL ACCS AUTO/MANUAL 1045
SPARE ADDRESS:
33KV MEASUREMENTS
33kV MEASUREMENTS
BH03/OG MEASUREMENTS
BH04/CAP MEASUREMENTS
BH05-I/C MEASUREMENTS
BH06/OG MEASUREMENTS
BH07/AUX MEASUREMENTS
BH07-SST INTERNAL CONFIGURATION 1250-800-400-200/1A 33KV / √3 : 120 - 120/ √3 V MW 2026 -13.71 13.71 -32767 +32767
BH10/AUX MEASUREMENTS
BH10-SST INTERNAL CONFIGURATION 1250-800-400-200/1A 33KV / √3 : 120 - 120/ √3 V MW 2032 -13.71 13.71 -32767 +32767
BH11/OG MEASUREMENTS
33kV MEASUREMENTS
BH12-I/C MEASUREMENTS
BH13/CAP MEASUREMENTS
BH14/OG MEASUREMENTS
SPARE ADDRESS:
GENERAL ALARMS
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
=MAIN ACDB XLOR-1:2 LOR-1 (6,8) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER F86 LOCK OUT RELAY OPTD ALARM/NORMAL
=MAIN ACDB XVR1:2 R3 (03,04) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER U/V PROTECTION OPTD ALARM/NORMAL
=MAIN ACDB XRLA-1:3,4 RL3 (5, 6) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER 50/51N PROTECTION OPTD ALARM/NORMAL
=MAIN ACDB 1AX:5,6 R8 (53,54) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER MCCB TRIP ALARM/NORMAL
=MAIN ACDB 1AX:3,4 R5A (21,22) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER MCCB OFF ALARM/NORMAL
=MAIN ACDB XLOR-2:2 LOR-2 (6,8) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER F86 LOCK OUT RELAY OPTD ALARM/NORMAL
=MAIN ACDB XVR2:2 R4 (03,04) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER U/V PROTECTION OPTD ALARM/NORMAL
=MAIN ACDB XRLA-2:3,4 RL3 (5, 6) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER 50/51N PROTECTION OPTD ALARM/NORMAL
=MAIN ACDB 2AX:5,6 R9 (53,54) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER MCCB TRIP ALARM/NORMAL
=MAIN ACDB 2AX:3,4 R6A (21,22) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER MCCB OFF ALARM/NORMAL
=MAIN ACDB 3AX:5,6 R10 (03,04) BCU1_6MD85 NT MAIN ACDB BUS TIE MCCB TRIP ALARM/NORMAL
=MAIN ACDB 3AX:3,4 R7A (21,22) BCU1_6MD85 NT MAIN ACDB BUS TIE MCCB OFF ALARM/NORMAL
HVAC-PP1 X5:2 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 MCCB/MCB OFF ALARM / NORMAL
HVAC-PP1 X5:3 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 MCCB/MCB TRIP ALARM / NORMAL
HVAC-PP1 X5:4 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 IN MANUAL MODE ALARM / NORMAL
HVAC-PP2 X5:5 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 MCCB/MCB OFF ALARM / NORMAL
HVAC-PP2 X5:6 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 MCCB/MCB TRIP ALARM / NORMAL
HVAC-PP2 X5:7,9 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 IN MANUAL MODE ALARM / NORMAL
HVAC-CP1 X5:10 CR77-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM TEMP. HIGH ALARM ALARM / NORMAL
HVAC-CP1 X5:11 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM TEMP. HIGH ALARM ALARM / NORMAL
HVAC-CP1 X5:12,13 CRXX-1(170,171) BCU1_6MD85 NT RECORD ROOM TEMP. HIGH ALARM ALARM / NORMAL
HVAC-CP1 X5:14 CRXX-1(170,171) BCU1_6MD85 NT COMMUNICATION ROOM TEMP. HIGH ALARM ALARM / NORMAL
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
HVAC-CP2 X5:15 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWGR ROOM TEMP. HIGH ALARM ALARM / NORMAL
HVAC-CP2 X5:16,18 CRXX-1(170,171) BCU1_6MD85 NT BATTERY ROOM TEMP. HIGH ALARM ALARM / NORMAL
HVAC-CP2 X5:17 CRXX-1(170,171) BCU1_6MD85 NT SECURITY ROOM TEMP. HIGH ALARM ALARM / NORMAL
+3UFLS X6:1,2 81-1 (F11,F12) BCU1_6MD85 NT SEC-A UNDER FREQUENCY RELAY 81-1 FAULTY ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-1_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 BLOCK ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-1_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 VT MCB TRIP ALARM/NORMAL
QA1(21,22)
+3UFLS X6:3 BCU1_6MD85 NT SEC-A UNDER FREQUENCY RELAY 81-1 DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA(11,3)
+3UFLS X6:8 81-2 (F11,F12) BCU1_6MD85 NT SEC-B UNDER FREQUENCY RELAY 81-2 FAULTY ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 BLOCK ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 VT MCB TRIP ALARM/NORMAL
QB1(21,22)
+3UFLS X6:9 BCU1_6MD85 NT SEC-B UNDER FREQUENCY RELAY 81-2 DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLC(11,3)
+3UFLS 81-1:B2 TS1(15,16) 81-2_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 UNDER TEST ALARM/NORMAL
+3UFLS 81-2:D14 TS2(15,16) 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 UNDER TEST ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 NT UFLS-1A SAS COMMUNICATION FAIL CH-1& CH-2 ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 NT UFLS-1B SAS COMMUNICATION FAIL CH-1& CH-2 ALARM/NORMAL
=SAS+CAP.1 X8:8 BCU1 (B10, B7) BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX FAULTY ALARM/NORMAL
Q1.3 (21,22)
=SAS+CAP.1 X8:4 BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX DC SUPPLY FAIL ALARM/NORMAL
74DC (14,6)
Q1.1 (21,22)
=SAS+CAP.1 X8:3 BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX DC MCB TRIP ALARM/NORMAL
Q1.2 (21,22)
=SAS+CAP.1 INTERNAL INTERNAL BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX SAS COMM.FAIL CH-1 & CH-2 ALARM/NORMAL
27-2 (F11,F12)
+3UVLS-2 X6:1,2 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-2/27-2A FAULTY ALARM/NORMAL
27-2A (F11,F12)
+3UVLS-1 INTERNAL INTERNAL 27-1_P142 NT UNDER VOLTAGE RELAY 27-1/27-1A BLOCK ALARM/NORMAL
+3UVLS-2 INTERNAL INTERNAL 27-2_REC670 NT UNDER VOLTAGE RELAY 27-2-27-2A BLOCK ALARM/NORMAL
=E01+LCC F33 (2/11,2/12) F33 (2/11,2/12) 27-1 (P142) NT UNDER VOLTAGE RELAY 27-1/27-1A VT SUPPLY FAIL ALARM/NORMAL
=E02+LCC F33 (2/11,2/12) F33 (2/11,2/12) 27-2 (P142) NT UNDER VOLTAGE RELAY 27-2-27-2A VT SUPPLY FAIL ALARM/NORMAL
+3UVLS-1 27-1:B4 TS-1(15,16) 27-1_P142 NT UNDER VOLTAGE RELAY 27-1/27-1A UNDER TEST ALARM/NORMAL
TS-1(30,29), TS-
+3UVLS-2 27-1:B4 27-2_P142 NT UNDER VOLTAGE RELAY 27-2/27-2A UNDER TEST ALARM/NORMAL
4(29,30)
Q1A(21,22)
+3UVLS-1 X6:3 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-1/27-1A DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA (11, 3)
Q1A(21,22)
+3UVLS-2 X6:3 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-2/27-2A DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA (11, 3)
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
+3UVLS-1 INTERNAL INTERNAL 27-1_P142 NT UVLS-1 27-1 SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL
+3UVLS-1 INTERNAL INTERNAL 27-1A_P142 NT UVLS-1 27-1A SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL
+3UVLS-2 INTERNAL INTERNAL 27-2_P142 NT UVLS-2 27-2 SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL
+3UVLS-2 INTERNAL INTERNAL 27-2A_P142 NT UVLS-2 27-2A SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL
=MAIN ACDB XRLA-1:1,2 RL2 (3,4) BCU1_6MD85 NT MAIN ACDB BUS-A 50/51N RELAY FAULTY ALARM/NORMAL
=MAIN ACDB XRLA-2:1,2 RL2 (3,4) BCU1_6MD85 NT MAIN ACDB BUS-B 50/51N RELAY FAULTY ALARM/NORMAL
=MAIN ACDB XTCS-1:1,2 TCS-1(7,9) BCU1_6MD85 NT MAIN ACDB BUS INCOMER-1 TC FAULTY ALARM/NORMAL
=MAIN ACDB XTCS-2:1,2 TCS-2(7,9) BCU1_6MD85 NT MAIN ACDB BUS INCOMER-2 TC FAULTY ALARM/NORMAL
=MAIN ACDB XTCS-3:1,2 TCS-3(7,9) BCU1_6MD85 NT MAIN ACDB BUS -TIE TC FAULTY ALARM/NORMAL
HVAC-CP1 X5:18 CRXX-1(170,171) BCU1_6MD85 NT HVAC-1 BCU1_6MD85 FAULT PACU (1A/1B) ALARM/NORMAL
HVAC-CP2 X5:19 CRXX-1(170,171) BCU1_6MD85 NT HVAC-2 BCU1_6MD85 FAULT PACU (2A/2B) ALARM/NORMAL
HVAC-CP1 X5:20 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS/CONTROL ROOM PACU-1A & 1B FAULTY ALARM / NORMAL
HVAC-CP1 X5:21 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS BUILDING VENTILATION FAULTY ALARM / NORMAL
HVAC-CP1 X5:22 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS BUILDING AIR CONDITION SYSTEM FAULTY ALARM / NORMAL
HVAC-CP1 X5:23 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM VENTILATION FAULTY ALARM / NORMAL
HVAC-CP1 X5:24 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM AIR CONDITION SYSTEM FAULTY ALARM / NORMAL
HVAC-CP1 X5:25 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM HIGH HUMIDITY-1 ALARM ALARM / NORMAL
HVAC-CP1 X5:26 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM HIGH HUMIDITY-2 ALARM ALARM / NORMAL
HVAC-CP1 X5:27 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM HIGH HUMIDITY ALARM ALARM / NORMAL
HVAC-CP2 X5:28 CRXX-1(170,171) BCU1_6MD85 NT TELECOM ROOM HIGH HYDROGEN ALARM ALARM / NORMAL
HVAC-CP2 X5:29 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWITCH GEAR BUILDING VENTILATION FAULTY ALARM / NORMAL
HVAC-CP2 X5:30 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWITCH GEAR BUILDING AIR CONDITION SYSTEM FAULTY ALARM / NORMAL SPARK SS # 3
ALARM/
NON URGENT 4107
NORMAL
ALARM
HVAC-CP2 X5:31 CRXX-1(170,171) BCU1_6MD85 NT 33kV SWITCHGEAR ROOM HIGH HUMIDITY ALARM ALARM / NORMAL
QFHT (21,22)
=6D01+CBF/TCS.R1 50BF:D8 BCU1_6MD85 NT CBF/TCS PROTECTION PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)
QFHT (21,22)
=6D02+CBF/TCS.R1 50BF:D8 BCU1_6MD85 NT CBF/TCS PROTECTION PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)
QFHT (21,22)
+3UVLS-1 27-1:B2 BCU1_6MD85 NT UNDER VOLTAGE PANEL-1 AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)
+3UVLS-2 27-1:B2 C1(11,12) BCU1_6MD85 NT UNDER VOLTAGE PANEL-2 AC SUPPLY FAIL ALARM/NORMAL
QFPS(21,22)
+3UFLS 81-1(D12) BCU1_6MD85 NT UNDER FREQUENCY PANEL AC SUPPLY FAIL ALARM/NORMAL
QFHT(21,22)
QFHT (21,22)
=SAS+CAP.1 X8:7 QFPS (21,22) BCU1_6MD85 NT SAS CAP.1 PANEL AC SUPPLY FAIL ALARM/NORMAL
KAC (14, 6)
QFHT (21,22)
AMI X6:5 BCU1_6MD85 NT AMI PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)
QFHT (21,22)
=3RM1 X6:3 BCU1_6MD85 NT REVENUE METER PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)
FRM-1_L2-M368 (T9,
FACP X6:3 BCU1_6MD85 NT 115kV GIS ROOM FIRE SYSTEM OPTD ALARM / NORMAL
T10)
FRM-1_L1-M353 (T9,
FACP X6:4 BCU1_6MD85 NT 33KV SWITCH GEAR FIRE SYSTEM OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M354 (T9,
FACP X6:5 BCU1_6MD85 NT CONTROL ROOM FIRE SYSTEM OPTD ALARM / NORMAL
T10)
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
FRM-1_L1-M355 (T9,
FACP X6:6 BCU1_6MD85 NT SECURITY EQUIPMENT ROOM FIRE SYSTEM OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M77 (T9,
FACP X6:7 BCU1_6MD85 NT CLEAN AGENT MANUAL RELEASE OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M104 (T9,
FACP X6:10 BCU1_6MD85 NT FIRE SYSTEM COMPRESSOR OPTD ALARM / NORMAL
T10)
FRM-1_L1-MXXX (T9,
FACP X6:11 BCU1_6MD85 NT AUXILIARY TRANSFORMER-1 FIRE SYSTEM OPTD ALARM / NORMAL
T10)
FRM-1_L1-MXXX (T9,
FACP X6:12 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 FIRE SYSTEM OPTD ALARM / NORMAL
T10)
FRM-1_L1-M84 (T9,
FACP X6:13 BCU1_6MD85 NT FIRE SYSTEM DIESEL PUMP OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M85 (T9,
FACP X6:14 BCU1_6MD85 NT FIRE SYSTEM ELECTRIC PUMP OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M82 (T9,
FACP X6:15 BCU1_6MD85 NT FIRE PUMP HOUSE FIRE SYSTEM OPERATED ALARM / NORMAL
T10)
FRM-1_L2-M365 (T9,
FACP X6:3 BCU1_6MD85 NT 115KV GIS ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M353 (T9,
FACP X6:4 BCU1_6MD85 NT CONTROL ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M354 (T9,
FACP X6:5 BCU1_6MD85 NT 33KV SWGR ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M355 (T9,
FACP X6:6 BCU1_6MD85 NT MANUAL CALL POINT OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M77 (T9,
FACP X6:7 BCU1_6MD85 NT SECURITY ROOM/ GUARD HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M77 (T9,
FACP X6:8 BCU1_6MD85 NT CAPACITOR BANK-1 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10) SPARK SS # 3 SSGA
SMOKE DETECTOR OPERATE/NORMAL 4109
FRM-1_L1-M102 (T9, OPTD
FACP X6:9 BCU1_6MD85 NT CAPACITOR BANK-2 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M104 (T9,
FACP X6:10 BCU1_6MD85 NT AUXILIARY TRANSFORMER-1 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-MXXX (T9,
FACP X6:11 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-MXXX (T9,
FACP X6:12 BCU1_6MD85 NT FIRE PUMP HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M84 (T9,
FACP X6:13 BCU1_6MD85 NT GUARD HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M85 (T9,
FACP X6:14 BCU1_6MD85 NT TELECOM SHELTER SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)
FRM-1_L1-M80 (T9,
FACP X6:16 BCU1_6MD85 NT 115kV GIS ROOM FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L1-MXX (T9,
FACP X6:17 BCU1_6MD85 NT CONTROL BUILDING FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L1-M79 (T9,
FACP X6:18 BCU1_6MD85 NT 33kV SWGR BUILDING FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L2-M362 (T9,
FACP X6:19 BCU1_6MD85 NT SECURITY HOUSE FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L1-M78 (T9,
FACP X6:20 BCU1_6MD85 NT CAPACITOR BANK-1 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L2-M364 (T9,
FACP X6:21 BCU1_6MD85 NT CAPACITOR BANK-2 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA
SSGA FIRE LITRA
SYSTEM
FAULTY/
TEXT INDEX 4110 NAME/ALARM LDC
NORMAL TYPE CENTRE
CODE
FRM-1_L2-M365 (T9,
FACP X6:23 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L2-M365 (T9,
FACP X6:24 BCU1_6MD85 NT LOW FUEL IN DIESEL TANK ALARM / NORMAL
T10)
FRM-1_L2-M365 (T9,
FACP X6:25 BCU1_6MD85 NT CLEAN AGENT SYSTEM IN MANUAL MODE ALARM / NORMAL
T10)
FRM-1_L2-M365 (T9,
FACP X6:26 BCU1_6MD85 NT CLEAN AGENT FIRE SYSTEM FAULTY ALARM / NORMAL
T10)
FRM-1_L1-M83 (T9,
FACP X6:27 BCU1_6MD85 NT FIRE SYSTEM COMPRESSOR FAULTY ALARM / NORMAL
T10)
FRM-1_L2-M365 (T9,
FACP X6:28 BCU1_6MD85 NT FIRE FIGHTING SYSTEM IN MANUAL MODE ALARM / NORMAL
T10)
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
+3UVLS-1 27-1:D2 94UV-11(1,3) 27-1_P142 NT UNDER VOLTAGE 27-1 STAGE-1 OPTD ALARM/NORMAL
+3UVLS-1 27-1:D4 94UV-21(1,3) 27-1_P142 NT UNDER VOLTAGE 27-1 STAGE-2 OPTD ALARM/NORMAL
+3UVLS-1 27-1:D6 94UV-31(1,3) 27-1A_P142 NT UNDER VOLTAGE 27-1 STAGE-3 OPTD ALARM/NORMAL
+3UVLS-2 27-2:D2 94UV-11(1,3) 27-2_P142 NT UNDER VOLTAGE 27-2 STAGE-1 OPTD ALARM/NORMAL
+3UVLS-2 27-2:D4 94UV-21(1,3) 27-2_P142 NT UNDER VOLTAGE 27-2 STAGE-2 OPTD ALARM/NORMAL
+3UVLS-2 27-2:D6 94UV-31(1,3) 27-2A_P142 NT UNDER VOLTAGE 27-2 STAGE-3 OPTD ALARM/NORMAL
SPARK SS # 3 UV LOAD
OPERATE / NORMAL 4111
SHED OPTD.
+3UVLS-1 X6:4 94-11 (14,16) 27-1_P142 NT UNDER VOLTAGE STAGE-1 TRIP RELAYS (94UV-11) OPTD ALARM/NORMAL
+3UVLS-1 X6:5 94-21 (14,16) 27-1_P142 NT UNDER VOLTAGE STAGE-2 TRIP RELAYS (94UV-21) OPTD ALARM/NORMAL
+3UVLS-1 X6:6 94-31 (14,16) 27-1A_P142 NT UNDER VOLTAGE STAGE-3 TRIP RELAYS (94UV-31) OPTD ALARM/NORMAL
+3UVLS-2 X6:4 94UV-11(1,3) 27-2_P142 NT UNDER VOLTAGE STAGE-1 TRIP RELAYS (94UV-11) OPTD ALARM/NORMAL
+3UVLS-2 X6:5 94UV-21(1,3) 27-2_P142 NT UNDER VOLTAGE STAGE-2 TRIP RELAYS (94UV-21) OPTD ALARM/NORMAL
+3UVLS-2 X6:6 94UV-31(1,3) 27-2A_P142 NT UNDER VOLTAGE STAGE-3 TRIP RELAYS (94UV-31) OPTD ALARM/NORMAL
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-1 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-2 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-3 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-4 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-1 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-2 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-3 OPTD ALARM/NORMAL
+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-4 OPTD ALARM/NORMAL
SPARK SS # 3 UF LOAD
OPERATE / NORMAL 4112
SHED OPTD.
+3UFLS X6:4 '94UF-11(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-1 TRIP RELAY (94UF-1A) OPTD ALARM/NORMAL
+3UFLS X6:5 94UF-21(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-2 TRIP RELAY (94UF-2A) OPTD ALARM/NORMAL
+3UFLS X6:6 '94UF-31(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-3 TRIP RELAY (94UF-3A) OPTD ALARM/NORMAL
+3UFLS X6:7 '94UF-41(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-4 TRIP RELAY (94UF-4A) OPTD ALARM/NORMAL
+3UFLS X6:10 '94UF-12(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-1 TRIP RELAY (94UF-1B) OPTD ALARM/NORMAL
+3UFLS X6:11 94UF-22(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-2 TRIP RELAY (94UF-2B) OPTD ALARM/NORMAL
+3UFLS X6:12 '94UF-32(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-3 TRIP RELAY (94UF-3B) OPTD ALARM/NORMAL
+3UFLS X6:13 '94UF-42(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-4 TRIP RELAY (94UF-4B) OPTD ALARM/NORMAL
Q1.1~Q1.33 (11,12),
=SUB DCDB-1 X1A:1,2 Q2.1~Q2.30 (11,12), BCU1_6MD85 NT SUB DCP-1 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)
Q1.1~Q1.24 (11,12),
=SUB DCDB-2 X1A:1,2 Q2.1~Q2.24 (11,12), BCU1_6MD85 NT SUB DCP-2 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)
Q1.1~Q1.39 (11,12),
=SUB DCDB-3 X1A:1,2 Q2.1~Q2.39 (11,12), BCU1_6MD85 NT SUB DCP-3 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)
Q1.1~Q1.63 (11,12),
=SUB DCDB-4 X1A:1,2 Q2.1~Q2.60 (11,12), BCU1_6MD85 NT SUB DCP-4 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)
Q1.1~Q1.9 (11,12),
=SUB DCDB-5 X1A:1,2 Q2.1~Q2.9 (11,12), BCU1_6MD85 NT SUB DCP-5 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)
Q1~Q6 (11,12),
=SUB DCDB-1C X1A:1,2 BCU1_6MD85 NT SUB DCP-1C (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
A001 (95,96)
SPARK SS # 3
Q1~Q6 (11,12), ALARM/NORMAL 4114
=SUB DCDB-2C X1A:1,2 BCU1_6MD85 NT SUB DCP-2C (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL DC SUPPLY FAIL
A001 (95,96)
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER SPARK SS # 3
ALARM/NORMAL ADDRESS
4114 ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA
DC SUPPLY FAIL TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
Q1.1~Q1.8
=MAIN DCDB X1A:1,2 BCU1_6MD85 NT MAIN DCDB BUS-A (CONTROL ROOM) MCCB OFF ALARM/NORMAL
(11, 12)
Q2.1~Q2.7
=MAIN DCDB X1B:1,2 BCU1_6MD85 NT MAIN DCDB BUS-B (CONTROL ROOM) MCCB OFF ALARM/NORMAL
(11, 12)
RLB(11,3)
+UVLS-1 27-1:D14 27-1_P142 NT UNDER VOLTAGE PANEL RELAY 27-1/27-1A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLB(11,3)
+UVLS-2 27-2:D14 27-2_P142 NT UNDER VOLTAGE PANEL RELAY 27-2/27-2A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLC(11,3)
+UVLS-1 27-1:D16 27-1_P142 NT UNDER VOLTAGE PANEL RELAY 27-1/27-1A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QA3(21,22)
RLC(11,3)
+UVLS-2 27-2:D16 27-2_P142 NT UNDER VOLTAGE PANEL RELAY 27-2/27-2A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QA3(21,22)
RLB(11,3)
+UFLS 81-1:DI4 81-1_P142 NT UNDER FREQUENCY PANEL RELAY 81-A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLD(11,3)
+UFLS 81-2:DI2 81-2_P142 NT UNDER FREQUENCY PANEL RELAY 81-B IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QB2(21,22)
RLE(11,3)
+UFLS 81-1:DI6 81-2_P142 NT UNDER FREQUENCY PANEL RELAY 81-A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QC1(21,22)
AVC.1 X6:4 Q16 (21,22) BCU1_6MD85 NT GT-1 AVC PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL
AVC.2 X6:4 Q16 (21,22) BCU1_6MD85 NT GT-2 AVC PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL
QDC1(21,22)
ACCS X6:5 BCU1_6MD85 NT ACCS PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL
RLA(11,3)
125V DC CHARGER-1 X30:1,3 BA300 (X30:1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1/2 EARTH FAULT ALARM/NORMAL
125V DC CHARGER-2 X30:4,5 BA300 (X30:4,5) BCU1_6MD85 NT 125V BATTERY CHARGER-1/2 URGENT ALARM ALARM/NORMAL
125V DC CHARGER-1 X5:16,18 J6(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 MAINS MCCB TRIP ALARM/NORMAL
125V DC CHARGER-1 X5:22,24 J8(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 BATTERY MCCB TRIP ALARM/NORMAL
125V DC CHARGER-1 X5:19,21 J7(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 DC MCCB TRIP ALARM/NORMAL
125V DC CHARGER-1 X5:1,3 J1(1,2) BCU1_6MD85 NT 125V BATTERY CHARGER-1 FAILURE ALARM/NORMAL
125V DC CHARGER-1 X5:13,15 J5(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 AC SUPPLY FAIL ALARM/NORMAL
125V DC CHARGER-1 X5:10,12 J4(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 TEMPERATURE HIGHALARM ALARM/NORMAL
125V DC CHARGER-1 X5:7,9 J3(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 UNDER VOLTAGE ALARM ALARM/NORMAL
SPARK SS # 3 125V
BATTERIES CHARGER ALARM / NORMAL 4115
FAIL
125V DC CHARGER-1 X5:4,6 J2(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 UNDER/OVER VOLTAGE ALARM ALARM/NORMAL
125V DC CHARGER-1 X5:1,3 J1(1,3) BCU1_6MD85 NT 125V BATTERY FAILURE ALARM ALARM/NORMAL
125V DC CHARGER-1 X5:16,18 J6(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 MAINS MCCB TRIP ALARM/NORMAL
125V DC CHARGER-2 X5:19,21 J7(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 DC MCCB TRIP ALARM/NORMAL
125V DC CHARGER-2 X5:22,24 J8(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 FAILURE ALARM/NORMAL
125V DC CHARGER-2 X5:13,15 J5(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 AC SUPPLY FAIL ALARM/NORMAL
125V DC CHARGER-2 X5:7,9 J3(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 TEMPERATURE HIGHALARM ALARM/NORMAL
125V DC CHARGER-2 X5:4,6 J2(1,5) BCU1_6MD85 NT 125V BATTERY CHARGER-2 UNDER VOLTAGE ALARM ALARM/NORMAL
125V DC CHARGER-2 X5:10,12 J4(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 UNDER/OVER VOLTAGE ALARM ALARM/NORMAL
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
QFRM1 (21,22)
QFRM2 (21,22)
QFRM3 (21,22)
=3RM1 X6:1,2 BCU1_6MD85 NT REVENUE METER PANEL DC MCB TRIP ALARM/NORMAL
QFRM4 (21,22)
QFRM5 (21,22)
QFRM6 (21,22)
QFVRM1 (21,22)
QFVRM3 (21,22)
=3RM1 X6:4 BCU1_6MD85 NT RM VT MCB TRIP ALARM/NORMAL
QFVRM5 (21,22)
QFVRM6 (21,22)
=3RM1 X5:3,4 RM1 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-1 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
=3RM1 X5:12,13 RM2 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-2 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
=3RM1 X5:21,22 RM3 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-3 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-3 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
=3RM1 X5:30,31 RM4 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-4 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-4 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
=3RM1 X5:39,40 RM5 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-5 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-5 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
=3RM1 X5:48,49 RM6 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-6 FAULTY ALARM/NORMAL
=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-6 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL SPARK SS # 3
AMR/AMI NON URGENT ALARM / NORMAL 4116
ALARM
AMI X5:8 RM1 (50, 51) BCU1_6MD85 NT AMI PANEL RM1 METER FAULTY ALARM/NORMAL
AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL RM1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
AMI X5:9 RM2 (50, 51) BCU1_6MD85 NT AMI PANEL RM2 METER FAULTY ALARM/NORMAL
AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL RM2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
AMI X5:10 PQM1 (4C, 4NC) BCU1_6MD85 NT AMI PANEL PQM-1 METER FAULTY ALARM/NORMAL
AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL PQM-1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
AMI X5:11 PQM2 (4C, 4NC) BCU1_6MD85 NT AMI PANEL PQM-2 METER FAULTY ALARM/NORMAL
AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL PQM-2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL
ES (C01,NC1)
AMI X6:12 BCU1_6MD85 NT AMI ETHERNET SWITCH FAIL ALARM/NORMAL
ES (C02,NC2)
QFDC1 (21,22)
AMI X6:2 BCU1_6MD85 NT AMI PANEL DC MCB TRIP ALARM/NORMAL
QFDC2 (21,22)
QFRM1 (21,22)
QFRM2 (21,22)
QFPQM1 (21,22)
AMI X6:3 BCU1_6MD85 NT AMI PANEL DC SUPPLY FAIL ALARM/NORMAL
QFPQM2 (21,22)
QES (21,22)
QFVTF (21,22)
DVM CABINET ,-- K01: (11,14) BCU1_6MD85 NT FOX615 DVM RACK MAJOR ALARM ALARM / NORMAL
SPARK SS # 3 ALARM/
MPLS-TP X101:1,3 K01: (21,24) BCU1_6MD85 NT MPLS MAJOR ALARM ALARM / NORMAL 4117
COMM URGENT NORMAL
MPLS-TP X101:1,6 K01: (31,34) BCU1_6MD85 NT MPLS MINOR ALARM ALARM / NORMAL
SPARK SS # 3 ALARM/
DVM CABINET ,-- K02: (11,14) BCU1_6MD85 NT FOX615 DVM RACK MINOR ALARM ALARM / NORMAL 4118
COMM NON-URGENT NORMAL
REV-2
HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
SAPRE ADDRESS:
SAS ALARMS
SAS ALARMS
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 APPLICATION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 LAN-A STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 LAN-B STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CENTRAL DB/STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CPU TEMPERATURE ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CLIENT SERVER PROTOCOL ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 SNMP ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 APPLICATION LICENSE ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 HARD DISK CAPACITY ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-1 DC POWER SUPPLY ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-2 DC POWER SUPPLY ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 1 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 2CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 3 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 4 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 104 PORT NO 1 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 104 PORT NO 2 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 APPLICATION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 LAN-A STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 LAN-B STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CENTRAL DB/STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CPU TEMPERATURE ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CLIENT SERVER PROTOCOL ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 SNMP ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 APPLICATION LICENSE ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -1 HARD DISK CAPACITY ALARM / NORMAL
SAS ALARMS
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-3 DC POWER SUPPLY ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-4 DC POWER SUPPLY ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 1 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 2CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 3 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 4 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 104 PORT NO 1 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 104 PORT NO 2 CONNECTION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 APPLICATION STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 LAN-A STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 LAN-B STATUS ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CPU TEMP ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 APPLICATION STATUS SYNCHRONISATION ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CLIENT SERVER PROTOCOL ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 SNMP ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 HARD CAPACITY ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CENTRAL DB/STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 APPLICATION STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 LAN-A STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 LAN-B STATUS ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CPU TEMP ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 APPLICATION STATUS SYNCHRONISATION ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CLIENT SERVER PROTOCOL ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 SNMP ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 HARD CAPACITY ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CENTRAL DB/STATUS ALARM / NORMAL
SAS ALARMS
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS LAN-A STATUS ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS LAN-B STATUS ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS HARD DISK STATUS (HDD/SSD) ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS HARD DISK CAPACITY ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS CPU TEMP ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS POWER SUPPLY DC-2 ALARM / NORMAL
=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87T1(SET-1) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87T2(SET-2) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87T1(SET-1) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87T2(SET-2) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 (CP1) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 (CP2) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 (CP1) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 (CP2) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 27A PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-1 F1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-2 27A PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 F1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
SAS ALARMS
=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 DC-1 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 DC-2 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 DC-1 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 DC-2 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 DC-1 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 DC-2 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 POWER SUPPLY DC ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 DC-1 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 DC-2 MCB ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS ALARM ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS DC-1 MCB ALARM / NORMAL
SPARK SS # 3
STATION
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS DC-2 MCB ALARM / NORMAL Alarm/Normal 4122
URGENT
ALARM
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 STATUS ALARM / NORMAL
SAS ALARMS
=SAS+SP 1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 DC-1 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 DC-2 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 STATUS ALARM / NORMAL
=SAS+SP 2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 DC-1 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 DC-2 MCB ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 STATUS ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 ANTENNA ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 GPS SYNC ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NTP SYNC ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NETWORK LAN-A ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NETWORK LAN-B ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 STATUS ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 DC-1 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 DC-2 MCB ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 STATUS ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 ANTENNA ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 GPS SYNC ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NTP SYNC ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NETWORK LAN-A ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NETWORK LAN-B ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 STATUS ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 DC-1 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 DC-2 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 1 TEMPERATURE HIGH ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 2 TEMPERATURE HIGH ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 3 TEMPERATURE HIGH ALARM / NORMAL
SAS ALARMS
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 TEMPERATURE HIGH ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 TEMPERATURE HIGH ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 STATUS ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 DC-1 MCB ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 DC-2 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 DC-1 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 DC-2 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 DC-1 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 DC-2 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 DC-1 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 DC-2 MCB ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 STATUS ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 STATUS ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 STATUS ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 STATUS ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 DC-1 MCB ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 DC-2 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 DC-1 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 DC-2 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 DC-1 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 DC-2 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 DC-1 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 DC-2 MCB ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 STATUS ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 STATUS ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 STATUS ALARM / NORMAL
=SAS+SP1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 SETTING CHANGES ALARM / NORMAL
=SAS+SP2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 SETTING CHANGES ALARM / NORMAL
SAS+SLA1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ESWA11 SETTING CHANGES ALARM / NORMAL
SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ESWA01 SETTING CHANGES ALARM / NORMAL
SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ESWA02 SETTING CHANGES ALARM / NORMAL
SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ESWA03 SETTING CHANGES ALARM / NORMAL
SAS+SLB1 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ESWB11 SETTING CHANGES ALARM / NORMAL
SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ESWB11 SETTING CHANGES ALARM / NORMAL
SAS ALARMS
SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ESWB02 SETTING CHANGES ALARM / NORMAL
SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ESWB03 SETTING CHANGES ALARM / NORMAL
SAS+SLA1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ESWA11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ESWA01 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ESWA02 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ESWA03 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLB1 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1ESWB11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1ESWB11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1ESWB02 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1ESWB03 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 POWER SUPPLY DC-1 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 POWER SUPPLY DC-2 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 ETHERNET SWITCH-ESWA11 PORT01 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 ETHERNET SWITCH-ESWA11 PORT02 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS CONSOLE DESK A3-PRINTER ETHERNET SWITCH-ESWA11 PORT03 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 SRV-1 ETHERNET SWITCH-ESWA11 PORT05 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 SRV-2 ETHERNET SWITCH-ESWA11 PORT06 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 GW-1 ETHERNET SWITCH-ESWA11 PORT07 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 GW-2 ETHERNET SWITCH-ESWA11 PORT08 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 GPS-1 ETHERNET SWITCH-ESWA11 PORT09 ALARM / NORMAL
SAS ALARMS
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 GPS-2 ETHERNET SWITCH-ESWA11 PORT10 ALARM / NORMAL
=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP3 EWS ETHERNET SWITCH-ESWA11 PORT11 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT01 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT02 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT03 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT01 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT02 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT03 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT01 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT02 ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT03 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT01 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT02 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT03 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS CONSOLE DESK A4-PRINTER ETHERNET SWITCH-ESWB11 PORT03 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 SRV-1 ETHERNET SWITCH-ESWB11 PORT05 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 SRV-2 ETHERNET SWITCH-ESWB11 PORT06 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 GW-1 ETHERNET SWITCH-ESWB11 PORT07 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 GW-2 ETHERNET SWITCH-ESWB11 PORT08 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 GPS-1 ETHERNET SWITCH-ESWB11 PORT09 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 GPS-2 ETHERNET SWITCH-ESWB11 PORT10 ALARM / NORMAL
=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP3 EWS ETHERNET SWITCH-ESWB11 PORT11 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT01 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT02 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT03 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT01 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT02 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT03 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT01 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT02 ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT03 ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-2/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 AC SUPPLY ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
SAS ALARMS
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 KVM-1 TRAY DC SUPPLY ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 AC SUPPLY ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 KVM 2 TRAY DC SUPPLY ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 AC SUPPLY ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 AC SUPPLY ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 AC SUPPLY ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 AC SUPPLY ALARM / NORMAL
=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL
=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL
=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 COMMON BCU STATUS ALARM / NORMAL
=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 COMMON BCU CONTROL SUPPLY ALARM / NORMAL
+FOPPA.1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP FOPPA.1 AC MCB TRIP ALARM / NORMAL
+FOPPB.1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP FOPPB.1 AC MCB TRIP ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PRINTER A3 AC MCB TRIP ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PRINTER A4 AC MCB TRIP ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 REMOTE SCREEN DC SUPPLY ALARM / NORMAL
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP LARGE SCREEN DC SUPPLY ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 REMOTE SCREEN DC SUPPLY ALARM / NORMAL
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 SPLITTER-1/2 FAIL ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 REMOTE SCREEN DC FAIL ALARM / NORMAL
=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 SPLITTER-1/2 FAIL ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 STATUS ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 NETWORK ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 ONLINE ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 OUT OF PAPER ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 TONER ALARM / NORMAL
SAS ALARMS
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 DOOR ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 SUPPLY ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 STATUS ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 NETWORK ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 ONLINE ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 OUT OF PAPER ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 TONER ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 DOOR ALARM / NORMAL
=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 SUPPLY ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME# LOG-IN ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME# CHANGE USER# AUTHORITY ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME#CREATE NEW USER IS# ALARM / NORMAL
=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME#DELETE USER IS# ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME# LOG-IN ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME# CHANGE USER# AUTHORITY ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME#CREATE NEW USER IS# ALARM / NORMAL
=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME#DELETE USER IS# ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP CB A601 (BCU CH-A) ESWA01 PORT-05 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP CB A602 (BCU CH-A) ESWA01 PORT 06 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 87L1(FPFM CH-A) ESWA01 PORT 07 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 87L2(FPSM CH-A) ESWA01 PORT 08 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 (50CBFTCS CH-A) ESWA01 PORT 09 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 87L1(FPFM CH-A) ESWA01 PORT10 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 87L2(FPSM CH-A) ESWA01 PORT11 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 (50CBFTCS CH-A) ESWA01 PORT12 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 87T1(SET-1 CH-A) ESWA01 PORT 13 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 (IO BOX CH-A) ESWA01 PORT14 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 87T2(SET-2 CH-A) ESWA01 PORT 15 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 87T1(SET-1 CH-A) ESWA01 PORT 16 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 (IO BOX CH-A) ESWA01 PORT 17 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 87T2(SET-2 CH-A) ESWA01 PORT 18 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 (AVC CH-A) ESWA01 PORT 19 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 (AVC CH-A) ESWA01 PORT 20 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B413 (BCPU CH-A) ESWA02 PORT 05 FAIL ALARM / NORMAL
SAS ALARMS
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B414 (BCPU CH-A) ESWA02 PORT 06 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A402 (BCPU CH-A) ESWA02 PORT 07 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B415 (BCPU CH-A) ESWA02 PORT 08FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B416 (BCPU CH-A) ESWA02 PORT 09 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A401 (BCPU CH-A) ESWA02 PORT 10FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B421 (BCPU CH-A) ESWA02 PORT 11 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B422 (BCPU CH-A) ESWA02 PORT 12FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A403 (BCPU CH-A) ESWA02 PORT 13 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B423 (BCPU CH-A) ESWA02 PORT 14 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B424 (BCPU CH-A) ESWA02 PORT 15 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-1 (CP1 CH-A) ESWA02 PORT 16 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-1 (CP2 CH-A) ESWA02 PORT 17 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-2 (CP1 CH-A) ESWA02 PORT 18 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA02 NON-TRIP CAP.PANEL-2 (CP2 CH-A) ESWA02 PORT 19 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA02 NON-TRIP UNDER VOLTAGE-1 (27A CH-A) ESWA02 PORT 20 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-1 (F1 CH-A) ESWA03 PORT 05 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-2 (27A CH-A) ESWA03 PORT 06 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-2 (F1 CH-A) ESWA03 PORT 07 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER FREQUENCY (81A-1 CH-A) ESWA03 PORT 08 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER FREQUENCY (81A-2 CH-A) ESWA03 PORT 09 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP ACCS (CH-A) ESWA03 PORT 10 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP COMMON BCU 1 (CH-A) ESWA03 PORT 11 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A601 DGA1 (CH-A) ESWA03 PORT 12 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A602 DGA2 (CH-A) ESWA03 PORT 13 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A601_HSPOT1 (CH-A) ESWA03 PORT 14 FAIL ALARM / NORMAL
=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A602 HSPOT2 (CH-A) ESWA03 PORT 15 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP CB A601 (BCU CH-B) ESWB01 PORT-05 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP CB A602 (BCU CH-B) ESWB01 PORT 06 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 87L1(FPFM CH-B) ESWB01 PORT 07 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 87L2(FPSM CH-B) ESWB01 PORT 08 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 (50CBFTCS CH-B) ESWB01 PORT 09 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 87L1(FPFM CH-B) ESWB01 PORT10 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 87L2(FPSM CH-B) ESWB01 PORT11 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 (50CBFTCS CH-B) ESWB01 PORT12 FAIL ALARM / NORMAL
SAS ALARMS
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 87T1(SET-1 CH-B) ESWB01 PORT 13 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 (IO BOX CH-B) ESWB01 PORT14 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 87T2(SET-2 CH-B) ESWB01 PORT 15 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 87T1(SET-1 CH-B) ESWB01 PORT 16 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 (IO BOX CH-B) ESWB01 PORT 17 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 87T2(SET-2 CH-B) ESWB01 PORT 18 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 (AVC CH-B) ESWB01 PORT 19 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 (AVC CH-B) ESWB01 PORT 20 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B413 (BCPU CH-B) ESWB02 PORT 05 FAIL ALARM / NORMAL SPARK SS # 3
STATION NON
Alarm/Normal 4123
URGENT
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B414 (BCPU CH-B) ESWB02 PORT 06 FAIL ALARM / NORMAL ALARM
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A402 (BCPU CH-B) ESWB02 PORT 07 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B415 (BCPU CH-B) ESWB02 PORT 08FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B416 (BCPU CH-B) ESWB02 PORT 09 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A401 (BCPU CH-B) ESWB02 PORT 10FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B421 (BCPU CH-B) ESWB02 PORT 11 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B422 (BCPU CH-B) ESWB02 PORT 12FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A403 (BCPU CH-B) ESWB02 PORT 13 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B423 (BCPU CH-B) ESWB02 PORT 14 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B424 (BCPU CH-B) ESWB02 PORT 15 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-1 (CP1 CH-B) ESWB02 PORT 16 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-1 (CP2 CH-B) ESWB02 PORT 17 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-2 (CP1 CH-B) ESWB02 PORT 18 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP CAP.PANEL-2 (CP2 CH-B) ESWB02 PORT 19 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-1 (27A CH-B) ESWB02 PORT 20 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-1 (F1 CH-B) ESWB03 PORT 05 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-2 (27A CH-B) ESWB03 PORT 06 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-2 (F1 CH-B) ESWB03 PORT 07 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER FREQUENCY (81A-1 CH-B) ESWB03 PORT 08 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER FREQUENCY (81A-2 CH-B) ESWB03 PORT 09 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP ACCS (CH-B) ESWB03 PORT 10 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP COMMON BCU 1 (CH-B) ESWB03 PORT 11 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A601 DGA1 (CH-B) ESWB03 PORT 12 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A602 DGA2 (CH-B) ESWB03 PORT 13 FAIL ALARM / NORMAL
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A601_HSPOT1 (CH-B) ESWB03 PORT 14 FAIL ALARM / NORMAL
SAS ALARMS
=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A602 HSPOT2 (CH-B) ESWB03 PORT 15 FAIL ALARM / NORMAL
=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU SAS COMM.CH-A FAIL ALARM / NORMAL
=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87L1(SET-1) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87L2(SET-2) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87L1(SET-1) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87L2(SET-2) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 RELAY (CP1) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 RELAY (CP2) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 RELAY (CP1) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 RELAY (CP2) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY SAS COMM.CH-A FAIL ALARM / NORMAL
=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
SAS ALARMS
=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL
=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 SAS COMM.CH-A FAIL ALARM / NORMAL
=SAS+CAP2 INTERNAL COMMON BCU-2/6MD85 COMBCU2_6MD85 NON-TRIP COMMON BCU 2 SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 SAS COMM.CH-A FAIL ALARM / NORMAL
=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 SAS COMM.CH-A FAIL ALARM / NORMAL
=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 SAS COMM.CH-A FAIL ALARM / NORMAL
=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU SAS COMM.CH-B FAIL ALARM / NORMAL
=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87L1(SET-1) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87L2(SET-2) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87L1(SET-1) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87L2(SET-2) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 RELAY (CP1) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 RELAY (CP2) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 RELAY (CP1) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 RELAY (CP2) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
SAS ALARMS
=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY SAS COMM.CH-B FAIL ALARM / NORMAL
=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL
=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 SAS COMM.CH-B FAIL ALARM / NORMAL
=SAS+CAP2 INTERNAL COMMON BCU-2/6MD85 COMBCU2_6MD85 NON-TRIP COMMON BCU 2 SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 SAS COMM.CH-B FAIL ALARM / NORMAL
=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 SAS COMM.CH-B FAIL ALARM / NORMAL
=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 SAS COMM.CH-B FAIL ALARM / NORMAL