THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
MULTIPLIED SPL ISSUED FOR APPROVAL
REVISED AS PER SEC COMMENTS
ISSUED FOR APPROVAL
DESCRIPTION

CUSTOMER: NATIONAL GRID, SA

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

TITLE: 115/33KV SAS POINT LIST (CONSOLIDATED)


DAR

DAR

DAR
BY

PTS NO: 20EN1028


STANDARD:- TES-P-107.02, REV.02
26-May-23

20-Sep-23

05-Oct-23
DATE
NO.

REVISIONS

DRAWN

BY M.W

DATE:- 26-May-23

CHECKED

BY N.A

DATE:- 26-May-23

OPRG. DEPT.
BY

DATE:-

ENG'G. DEPT.
BY:-

DATE:-

APPROVED/CERTF.
INFORMATION
BY:-

DATE:- DATE
DOCUMENT TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.

THIS DRAWING IS NOT SAS POINT LIST


TO BE USED FOR
CONSTRUCTION OF
FOR ORDERING
P NA595 ED-682330 1 OF 96 2
MATERIALS UNTIL
CERTIFIED AND
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
DATED
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FUL
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF
FOR ORDERING
MATERIALS UNTIL
CERTIFIED AND
DATED

ABQAIQ SAUDI ARABIA JOB ORDER NO. 3-1813001.08 DWG. CONT. SHT. EE-6

SEC-E (2004/10)
PROJECT INFORMATION INDEX
PTS No: 20EN1028

Project: CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 115kV ALARMS


CUSTOMER:
NATIONAL GRID, SA 115kV INDICATIONS
Title:
115/33KV SAS POINT LIST 115kV COMMANDS
Based on:
TES-P-107.02 REV.02 DATED: NOV 15, 2018 115kV MEASURANDS
33kV ALARMS
33kV INDICATIONS
33kV COMMANDS
33kV MEASURANDS
GENERAL ALARMS
SAS ALARMS

ED-682330, Rev-2 3 OF 104


TITLE: 115/33KV SAS POINT LIST (CONSOLIDATED)
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

REVISION NO. DATE REVISION DESCRIPTION DESIGNER COMPANY NAME CONTRACTOR NO REMARKS

0 26/5/2023 ISSUED FOR APPROVAL DAR INTERNATIONAL ENGINEERING CONSULTANCY 20EN1028

1 9/20/2023 REVISED AS PER SEC COMMENTS DAR INTERNATIONAL ENGINEERING CONSULTANCY 20EN1028

2 5/10/2023 MULTIPLIED SPL ISSUED FOR APPROVAL DAR INTERNATIONAL ENGINEERING CONSULTANCY 20EN1028

ED-682330, Rev-2 4 OF 104


ED-682330, Rev-2 5 OF 104
GENERAL INFORMATION

SR No. DESCRIPTION DETAIL

01 SCADA CONTROL CENTER ERCC-DAMMAM

02 SPL DESIGNER NAME DAR ENGINEERING

04 132kV GIS-VENDOR NAME HYOSUNG

05 C & R - VENDOR NAME SEP

06 SAS VENDOR NAME SEP

07 POWER TRANSFORMER VENDOR NAME HYOSUNG

08 33kV SWGR-VENDOR NAME EFACEC

ALARM
POINT TYPE
CLASS

1 TRIP ALARMS

2 NON TRIP ALARMS

3 INDICATION & COMMANDS

4 MEASUREMENTS

ED-682330, Rev-2 6 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

115KV ALARMS

ED-682330, Rev-2 PAGE 7 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
E
SPARK 115/33kV SUBSTATION#3 E01 115KV CB ALARMS:
AA1E1Q
005KF1.L
K26A (43, 44) DS/ES IN MAINTENANCE HAND CRANK ALARM/
=E01+LCC X5:47 D0.SP16 BCU_6MD85_SIEMENSNT
K26B (43, 44) INSERTED NORMAL
GGIO4.In
AA1E1Q
d8.stVal
005KF1.L
CB A601 IN MAINTENANCE HAND ALARM/
=E01+LCC X5:21 D0.SP16 K26 (43, BCU_6MD85_SIEMENS
44) NT
CRANK INSERTED NORMAL
GGIO4.In
d7.stVal
ALARM/
=E01+LCC X5:108 K73 (43,44)
BCU_6MD85_SIEMENSNT CB A601 AUTO TRIP ALARM
NORMAL
AA1E1Q
005KF1.L
DS & ES MOTOR RUNNING TIME ALARM/
=E01+LCC X5:45 D0.SP16 K15 (53, BCU_6MD85_SIEMENS
54) NT
EXCEEDED NORMAL
GGIO4.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E01+LCC X5:43 D0.SP16 K97 (31, BCU_6MD85_SIEMENS
32) NT DS/ES CONTROL SUPPLY FAIL
NORMAL
GGIO4.In
AA1E1Q SPARK
d10.stVal K95 (31, 32),
005KF1.L SS#3 E01
K95A (31, 32), ALARM/ ALARM/
=E01+LCC X5:44 D0.SP16 BCU_6MD85_SIEMENSNT DS & ES MOTOR SUPPLY FAIL CB A601 4001
K95B (31, 32), NORMAL NORMAL
GGIO5.In
AA1E1Q K95C (31, 32) URGENT
d6.stVal
005KF1.L ALARM
ALARM/
=E01+LCC X5:20 D0.SP16 K91 (31, BCU_6MD85_SIEMENS
32) NT CB A601 MOTOR SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d8.stVal
005KF1.L
ALARM/
=E01+LCC X5:50 D0.SP16 K12A (51,BCU_6MD85_SIEMENS
52) NT DS/ES LOCK POSITION
NORMAL
GGIO4.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E01+LCC X5:48 D0.SP16 K30 (43, BCU_6MD85_SIEMENS
44) NT DS SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E01+LCC X5:49 D0.SP16 K31 (43, BCU_6MD85_SIEMENS
44) NT ES SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d3.stVal
005KF1.L
CB A601 CTPU (METROCIL) O/V ALARM/
=E01+LCC -- D0.SP16 -- BCU_6MD85_SIEMENSNT
PROTECTION ALARM NORMAL
GGIO9.In
AA1E1Q
d16.stVal
005FN1.
=6D01+CB 74TCS-1 ALARM/
50BF:C14 LD0.SP1 50BF-7VK87 NT CB A601 TRIP CIRCUIT 1 FAULTY
F/TCS.R1 (5,13) NORMAL
6GGIO3.I
AA1E1Q
nd5.stVal
005KF1.L
CB A601 TRIP CIRCUIT 1 DC SUPPLY ALARM/
=E01+LCC X5:33 D0.SP16 K93 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
G00KF1
d9.stVal-
=6D01+CB 15. ALARM/
50BF:D3 74TCS-2 (2,4) 50BF-7VK87 NT CB A601 TRIP CIRCUIT 2 FAULTY
F/TCS.R1 Ind4.stVa NORMAL
AA1E1Q
l
005KF1.L
CB A601 TRIP CIRCUIT 2 DC SUPPLY ALARM/
=E01+LCC X5:35 D0.SP16 K94 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
AA1E1Q
d10.stVal
004KF1.L
ALARM/
=E01+LCC X21:20 D0.SP16 K106 (71,72) COMM_BCU NT CB A601 BCU DC SUPPLY FAIL
NORMAL SPARK
GGIO5.In
AA1E1Q
d12.stVal SS#3 E01
004KF1.L
ALARM/ CB A601 FAULTY /
=E01+LCC X21:21 D0.SP16 K13 (71,72) COMM_BCU NT CB A601 BCU RELAY FAULTY 4002
NORMAL PROT. NORMAL
GGIO5.In
AA1E1Q FLTY
d14.stVal
005KF1.L
ALARM/ ALARM
=E01+LCC -- D0.SP16 -- COMM_BCU NT CB A601 BCU UNDER TEST
NORMAL
GGIO5.In
AA1E1Q
d15.stVal
003FN11
GW1-SRV-1 CB A601 BCU SAS COMMUNICATION ALARM/
=E01+LCC INTERNAL .LD0.SP1 INTERNAL NT
GW2-SEV-2 BOTH CHANNELS FAIL NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
=6D01+CB 74DC (1,3), CBF A601 DC SUPPLY FAIL / DC MCB ALARM/
X6:3 D0.SP16 COMM_BCU NT
F/TCS.R1 F221 (21,22) TRIP NORMAL
GGIO7.In
AA1E1Q
d.stVal
000KF1.L
=6D01+CB 50BF ALARM/
X6:2 D0.SP16 COMM_BCU NT CBF A601 RELAY FAULTY
F/TCS.R1 (B7,B10) NORMAL
GGIO7.In
AA1E1Q
d3.stVal
003FN11
=6D01+CB CBF A601 PROT. SAS ALARM/
INTERNAL .LD0.SP1 INTERNAL 50BF-7VK87 NT
F/TCS.R1 COMMUNICATION FAIL (CH-1 & CH-2) NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:99 D0.SP16 K46 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
AA1E1Q
d1.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:100 D0.SP16 K49 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
d2.stVal
GIS PS01_3 SF6 GAS PRESSURE HIGH ALARM/
=E01+LCC X5:101 K52 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

K55 (31,32) CB A601 PS01_4 SF6 GAS PRESSURE ALARM/


=E01+LCC X5:102 BCU_6MD85_SIEMENS
NT
K55A (31, 32) HIGH STAGE NORMAL

ED-682330, Rev-2 PAGE 8 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
GIS PS01_5 SF6 GAS PRESSURE HIGH ALARM/ E
=E01+LCC X5:103 K60 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_6 SF6 GAS PRESSURE HIGH ALARM/


=E01+LCC X5:104 K63 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_7 SF6 GAS PRESSURE HIGH ALARM/


=E01+LCC X5:105 K66 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_8 SF6 GAS PRESSURE HIGH ALARM/


=E01+LCC X5:106 K69 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
AA1E1Q
005KF1.L
K53 (61, 62), CB A601 SF6 GAS PRESSURE LOW ALARM/ SPARK
=E01+LCC X5:24 D0.SP16 BCU_6MD85_SIEMENS
NT
K56 (61, 62) STAGE-1 NORMAL SS#3 E01
GGIO2.In ALARM /
d4.stVal CB A601 4003
NORMAL
K54 (61,62), CB A601 SF6 GAS PRESSURE LOW ALARM/ SF6 GAS
=E01+LCC X5:31 BCU_6MD85_SIEMENS
NT
K57 (61, 62) STAGE-2 NORMAL ALARM
AA1E1Q
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:83 D0.SP16 K44 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d2.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:84 D0.SP16 K47 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d3.stVal
005KF1.L
GIS PS01_3 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:85 D0.SP16 K50 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d4.stVal
005KF1.L
GIS PS01_4 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:86 D0.SP16 K53 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_5 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:87 D0.SP16 K58 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d6.stVal
005KF1.L
GIS PS01_6 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:88 D0.SP16 K61 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d7.stVal
005KF1.L
GIS PS01_7 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:89 D0.SP16 K64 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d8.stVal
005KF1.L
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:90 D0.SP16 K67 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d9.stVal
005KF1.L
K53 (71,72), ALARM/
=E01+LCC X5:24 D0.SP16 BCU_6MD85_SIEMENS
NT CB A601 CLOSING LOCKOUT ALARM
K56 (71,72) NORMAL
GGIO2.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:91 D0.SP16 K45 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d2.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:92 D0.SP16 K48 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d3.stVal
005KF1.L
GIS PS01_3 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:93 D0.SP16 K51 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d4.stVal
005KF1.L
CB A601 PS01_4 SF6 GAS PRESSURE ALARM/
=E01+LCC X5:94 D0.SP16 K56 (31,32)BCU_6MD85_SIEMENS
NT
LOW STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_5 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:95 D0.SP16 K59 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d6.stVal
005KF1.L
GIS PS01_6 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:96 D0.SP16 K62 (31,32)BCU_6MD85_SIEMENS
NT SPARK
STAGE-2 NORMAL
GGIO7.In
AA1E1Q SS#3 E01 ALARM/
d7.stVal 4004
005KF1.L CB A601 NORMAL
GIS PS01_7 SF6 GAS PRESSURE LOW ALARM/ LOCKOUT
=E01+LCC X5:97 D0.SP16 K65 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d8.stVal
005KF1.L
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E01+LCC X5:98 D0.SP16 K68 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d9.stVal
005KF1.L
CB A601 CLOSING COIL DC SUPPLY ALARM/
=E01+LCC X5:26 D0.SP16 K92 (31,32)BCU_6MD85_SIEMENS
NT
FAIL NORMAL
GGIO4.In
AA1E1Q
d6.stVal
005KF1.L
ALARM/
=E01+LCC X5:19 D0.SP16 K3 (13,14) BCU_6MD85_SIEMENS
NT CB A601 MOTOR RUNTIME EXCEED
NORMAL
GGIO4.In
d5.stVal
CB A601 OPERATING MECHANISIM ALARM/
=E01+LCC X5:18 K4 (83,84)
BCU_6MD85_SIEMENS
NT
FAIL NORMAL
AA1E1Q
005KF1.L
ALARM/
=E01+LCC X5:31 D0.SP16 K54 (21,22)BCU_6MD85_SIEMENS
NT CB A601 TRIP COIL-1 LOCKOUT
NORMAL
GGIO3.In
d11.stVal

ED-682330, Rev-2 PAGE 9 OF 104


SS#3 E01 ALARM/
4004
CB A601 NORMAL
LOCKOUT

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
ALARM/
=E01+LCC X5:38 D0.SP16 K57 (21,22)
BCU_6MD85_SIEMENS
NT CB A601 TRIP COIL-2 LOCKOUT
NORMAL
GGIO3.In
d12.stVal

ED-682330, Rev-2 PAGE 10 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
ALARM/
=E01+LCC X5:59 D0.SP16 K23 (21,22)
BCU_6MD85_SIEMENS
NT CB A601 LCC DC SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E01+LCC X5:58 D0.SP16 K24 (13,14)
BCU_6MD85_SIEMENS
NT CB A601 LCC DC MCB TRIP/OFF
NORMAL
GGIO5.In
d2.stVal
ALARM/
=E01+LCC X5:54 K98 (31,32)
BCU_6MD85_SIEMENS
NT CB A601 INDICATION SUPPLY FAIL
NORMAL
AA1E1Q
005KF1.L K99 (21,22),
ALARM/
=E01+LCC X5:57 BCU_6MD85_SIEMENS
D0.SP16 K108 (21,22), NT CB A601 LCC AC SUPPLY FAIL
NORMAL
AA1E1Q F23 (11,12)
GGIO5.In
d4.stVal
005KF1.L F21 (11,12),
ALARM/
=E01+LCC X5:56 BCU_6MD85_SIEMENS
D0.SP16 F22 (11,12), NT CB A601 LCC AC MCB TRIP
NORMAL SPARK
AA1E1Q F23 (11,12)
GGIO5.In
d5.stVal SS#3 E01
005KF1.L
ALARM/ CB A601 ALARM/
=E01+LCC X5:53 D0.SP16 K14 (13,14)BCU_6MD85_SIEMENS
NT CB A601 LCC ANNUNCIATOR FAULTY 4005
NORMAL NON_URG NORMAL
GGIO5.In
AA1E1Q ENT
d11.stVal
005KF1.L
CB A601 LCC ANNUNCIATOR DC ALARM/ ALARM
=E01+LCC X5:51 D0.SP16 F11 (12, BCU_6MD85_SIEMENS
11) NT
SUPPLY FAIL NORMAL
GGIO5.In
AA1E1Q
d9.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNCH CHECK FAIL (DELTA V)
NORMAL
GGIO1.In
AA1E1Q
d14.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNCH CHECK FAIL (DELTA F)
NORMAL
GGIO1.In
AA1E1Q
d15.stVal
005KF2.L
CB A601 SYNCH CHECK FAIL (DELTA ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
PHI) NORMAL
GGIO1.In
AA1E1Q
d16.stVal
005KF2.L
ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A601 SYNC CHECK BLOCK (VT FF)
AA1E1Q NORMAL
GGIO1.In
005FN11
d13.stVal
=6D01+CB .LD0. TRIP/ SPARK
INTERNAL INTERNAL 50BF/7VK87 T CB A601 CBF 50BF PROTECTION OPTD
F/TCS.R1 CCRBRF NORMAL SS#3 E01
AA1E1Q
1.OpIn.g CB A601 OPERATE/
4006
005FN11
eneral 86BF/A601 (5, CBF NORMAL
=6D01+CB CB A601 86D01+CBF/TCS.R1 LOCKOUT TRIP/ PROT.
50BF:C13 .LD0.SP1 50BF/7VK87 T
F/TCS.R1 AA1E1Q 7) RELAY OPTD NORMAL OPTD
6GGIO1.I
005FN11
nd6.stVal
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:39 K27 (83, BCU_6MD85_SIEMENS
84) NT OFF / ON
6GGIO8.I
AA1E1Q TROLLEY
nd13.stV
005FN11
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:40 S43R (11,BCU_6MD85_SIEMENS
12) NT OFF / ON
6GGIO8.I
AA1E1Q LOCAL
nd14.stV
005FN11 SPARK
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO SS#3 E01
=E01+LCC X5:41 S43R (21,BCU_6MD85_SIEMENS
22) NT OFF / ON OFF / ON 4007
6GGIO8.I
AA1E1Q BCU CB A601
nd15.stV
005FN11 REMOTE
al
.LD0.SP1 CB A601 BAY CONTROL MODE SET TO
=E01+LCC X5:42 S43R (31,BCU_6MD85_SIEMENS
32) OFF / ON
6GGIO8.I
AA1E1Q REMOTE
nd16.stV
005FN11
al
.LD0.SP1 ALARM/
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS
NT CB A601 BAY BLOCK
6GGIO8.I NORMAL
nd13.stV
al
SPARK 115/33kV SUBSTATION#3 E01 115/33KV SPARK CKT-A ALARMS:
AA1E1Q
005FN1.
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM CH-A ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd15.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM CH-B ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd16.stV
005FN1. SPARK
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM F.O ALARM / SS#3 E01
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q TELECOMM. FAIL (BOTH CHANNELS) NORMAL SPARK
nd14.stV 380kV BSP ALARM /
005FN2. 4008
al CKT-A NORMAL
=6D01+L1. System. SPARK 380kV BSP CKT-A FPFM CH-A ALARM / COMM
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL URGENT
O2.Ind31
005FN2. ALARM
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM CH-B ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL
O2.Ind32
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM F.O ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI TELECOMM. FAIL (BOTH CHANNELS) NORMAL
AA1E1Q
O2.Ind23
005FN1.
.stVal
=6D01+L1. SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 RELAY VT FUSE FAIL NORMAL
6GGIO2.I
AA1E1Q
nd5.stVal
000KF1.L
=6D01+L1. 87L/21/67N-2 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R2 (K3,K4) RELAY FAULTY NORMAL
GGIO3.In
d.stVal

ED-682330, Rev-2 PAGE 11 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-AFPSM PROT. ALARM / E
TS2 (1,2) FPSM_7SD522 NT
R2 J9 6GGIO2.I RELAY UNDER TEST NORMAL
AA1E1Q
nd14.stV
000KF1.L
al
=6D01+L1. 74DC2 (1,3), SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
X6:3 D0.SP16 COMM-BCU NT
R2 AA1E1Q F221 (21,22) DC SUPPLY FAIL NORMAL
GGIO3.In
005FN1.
d2.stVal
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL
nd15.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 OptGGIO RELAY VT FUSE FAIL NORMAL
AA1E1Q
1.Ind5.st
000KF1.L
Val
=6D01+L1. 87L/21/67N-1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R1 (M11,M12) RELAY FAULTY NORMAL
GGIO3.In
d5.stVal
=6D01+L1. MICOM SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
TS2 (1,2) FPFM_P546 NT
R1 P546 : E14 RELAY UNDER TEST NORMAL
AA1E1Q
000KF1.L SPARK
=6D01+L1. 74DC1 (11,3), SPARK 380kV BSP CKT-A FPFM PROT. ALARM / SS#3 E01
X6:3 D0.SP16 COMM-BCU NT
R1 AA1E1Q QFR1(21,22) DC SUPPLY FAIL NORMAL SPARK
GGIO3.In FAULTY /
005FN1.
d6.stVal 380kV BSP 4009
NORMAL
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM / CKT-A
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL PROT.
nd15.stV ALARM
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
O2.Ind19
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIST. FUNCTION BLOCKED NORMAL
O2.Ind20
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DEF FUNCTION BLOCKED NORMAL
O2.Ind22
005FN1.
=6D01+L1. .stVal
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
nd11.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I DIST. FUNCTION BLOCKED NORMAL
AA1E1Q
nd12.stV
005FN1.
al
=6D01+L1. SPARK 380kV BSP CKT-A FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 AA1E1Q DEF FUNCTION BLOCKED NORMAL
6GGIO2.I
005FN1.
nd1.stVal
=6D01+L1. 7SD522 : LD0.DPG SPARK 380kV BSP CKT-A FPSM ALARM /
K02 (2, 4) FPSM_7SD522 NT
R2 J7 GIO1.DP
AA1E1Q PROTECTION OUT NORMAL
CSO.stV
005FN2.
=6D01+L1. MICOM System.U al SPARK 380kV BSP CKT-A FPFM ALARM /
K01 (1,10) FPFM_P546 NT
R1 P546 : E12 srGGIO1.
AA1E1Q PROTECTION OUT NORMAL
DPCSO1
005FN1.
=6D01+L1. .stVal
LD0.LDL SPARK 380kV BSP CKT-AFPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
p.Loc.phs
005FN1.
=6D01+L1. .A
LD0.LDL SPARK 380kV BSP CKT-A FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
p.Loc.phs
005FN1.
=6D01+L1. .B
LD0.LDL SPARK 380kV BSP CKT-A FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O DIFF. PROTECTION PH.B OPTD NORMAL
AA1E1Q
p.Loc.phs
005FN1.
.C
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
005FN1.
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd2.stVal
005FN1.
=6D01+L1. SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
6GGIO1.I
005FN1.
nd3.stVal
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
nd12.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
nd13.stV
005FN1.
=6D01+L1. al
LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I DIST. PROTECTION Z3. OPTD NORMAL
nd14.stV
al

ED-682330, Rev-2 PAGE 12 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. LD0.SP1 SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/ E
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
nd14.stV
005FN1.
=6D01+L1. al
LD0.ZCP SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DIST. AIDED OPTD NORMAL
.general(
005FN1.
=6D01+L1. ST)
LD0.ZCV SPARK 380kV BSP CKT-A FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PSOF1.O DIST. SOTF OPTD NORMAL
p.general
=6D01+L1. (ST) SPARK 380kV BSP CKT-A FPSM 50/51-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-R OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPSM 50/51-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-Y OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPSM 50/51-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-B OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPSM 51N-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 AA1E1Q E/F PROTECTION OPTD NORMAL
005FN1.
=6D01+L1. LD0.ECP SPARK 380kV BSP CKT-A FPSM 67N-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DEF. AIDED OPTD NORMAL
.general(
005FN1.
=6D01+L1. ST)
EF4_1.E SPARK 380kV BSP CKT-A FPSM 67N-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 F4TOC1.
AA1E1Q DEF DELAYOPTD NORMAL
Op.gener
005FN2.
=6D01+L1. al(ST)
Protectio SPARK 380kV BSP CKT-A FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
1.Op.phs
005FN2.
=6D01+L1. A
Protectio SPARK 380kV BSP CKT-A FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
1.Op.phs
005FN2.
=6D01+L1. B
Protectio SPARK 380kV BSP CKT-A FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF
AA1E1Q DIFF. PROTECTION PH.B OPTD NORMAL
1.Op.phs
005FN2.
=6D01+L1. C
System. SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.R OPTD NORMAL
O2.Ind1.s
005FN2.
tVal SPARK
=6D01+L1. System. SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/ SS#3 E01
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.Y OPTD NORMAL SPARK
O2.Ind2.s OPERATE /
005FN2. 380kV BSP 4010
tVal NORMAL
=6D01+L1. System. SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/ CKT-A
INTERNAL INTERNAL FPFM_P546 T PROT.
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
O2.Ind3.s OPTD
005FN2.
=6D01+L1. tVal
Protectio SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
S1.Op.ge
005FN2.
=6D01+L1. neral
Protectio SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
S2.Op.ge
005FN2.
=6D01+L1. neral
Protectio SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z3. OPTD NORMAL
S3.Op.ge
005FN2.
=6D01+L1. neral
Protectio SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
S3.Op.ge
005FN2.
=6D01+L1. neral
Protectio SPARK 380kV BSP CKT-A FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPSC
AA1E1Q DIST. AIDED OPTD NORMAL
H1.Op.ge
005FN2.
=6D01+L1. neral
Protectio SPARK 380kV BSP CKT-A 21-1 DIST. TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.SofPS SOTF OPTD NORMAL
OF1.Op1
=6D01+L1. .general SPARK 380kV BSP CKT-A FPFM 50/51-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-R OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPFM 50/51-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-Y OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPFM 50/51-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-B OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPFM TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 50/51N-1 E/F PROTECTION OPTD NORMAL

=6D01+L1. SPARK 380kV BSP CKT-A FPFM 67N-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 AA1E1Q DEF DELAYOPTD NORMAL
005FN2.
=6D01+L1. Protectio SPARK 380kV BSP CKT-A FPFM 67N-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPSC DEF. AIDED OPTD NORMAL
H2.Op.ge
neral

ED-682330, Rev-2 PAGE 13 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN1. COD TRE
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-A 86F-2 TRIP TRIP/ E
86F2 (12,18) FPSM_7SD522 T
R2 K17 6GGIO3.I RELAY OPTD NORMAL
AA1E1Q
nd11.stV
005FN1.
al
=6D01+L1. 7SD522 : SPARK 380kV BSP CKT-A 86BU-2 TRIP/
LD0.SP1 86BU2 (12,18)FPSM_7SD522 T
R2 J1 AA1E1Q LOCKOUT RELAY OPTD NORMAL
6GGIO3.I
005FN2.
nd9.stVal
=6D01+L1. MICOM System. SPARK 380kV BSP CKT-A 86F-1 TRIP TRIP/
86F1 (6,8) FPFM_P546 T
R1 P546 : E2 OptGGIO
AA1E1Q RELAY OPTD NORMAL
1.Ind19.s
005FN2.
=6D01+L1. MICOM System. tVal SPARK 380kV BSP CKT-A 86BU-1 TRIP/
86BU1 (6,8) FPFM_P546 T
R1 P546 : E4 OptGGIO
AA1E1Q LOCKOUT RELAY OPTD NORMAL
1.Ind18.s
005FN1.
=6D01+L1. tVal
LD0.SP1 SPARK 380kV BSP CKT-A FPSM INTER TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO2.I
AA1E1Q TRIP SEND NORMAL
nd13.stV
005FN2.
=6D01+L1. al
System. SPARK 380kV BSP CKT-A FPSM TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 GosGGI
AA1E1Q INTERTRIP RECEIVE NORMAL
O2.Ind18
005FN1.
.stVal
=6D01+L1. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-A 85R-2 INTER TRIP/
85R2 (A1,A3) FPSM_7SD522 T
R2 J3 6GGIO3.I
AA1E1Q TRIP RECEIVE OPTD NORMAL
nd02.stV
005FN2.
=6D01+L1. MICOM System. al SPARK 380kV BSP CKT-A 85R-1 INTER TRIP/
85R1 (1,3) FPFM_P546 T
R1 P546 : E6 OptGGIO
AA1E1Q TRIP RECEIVE OPTD NORMAL
1.Ind10.s
005FN2.
=6D01+L1. tVal
System. SPARK 380kV BSP CKT-A FPFM INTER TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q TRIP SEND NORMAL
O2.Ind24
005FN2.
=6D01+L1. .stVal
System. SPARK 380kV BSP CKT-A FPFM TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI INTERTRIP RECEIVE NORMAL
AA1E1Q
O2.Ind17
000KF1.L
.stVal QFHT (21,22),
=6D01+L1. 7SD522 : CB A601 FPSM PROTECTION PANEL ALARM/
D0.SP16 FPSM_7SD522 NT
R2 P17 QFPS (21,22) AC SUPPLY FAIL NORMAL
GGIO3.In
d4.stVal
=6D01+L1. 7SD522 : 74IO-2 (1,3), CB A601 FPSM PROTECTION PANEL ALARM/
FPSM_7SD522 NT
R2 J4 F222 (21,22) IN/OUT DC SUPPLY FAIL NORMAL
SPARK
=6D01+L1. 7SD522 : 74IND-2 (1,3), CB A601 FPSM PROTECTION PANEL ALARM/ SS#3 E01
FPSM_7SD522 NT SPARK
R2 J6 F223 (21,22) INDICATION DC SUPPLY FAIL NORMAL
380kV BSP ALARM/
4011
CKT-A NORMAL
=6D01+L1. MICOM 74IO1 (3,11), CB A601 FPFM PROTECTION PANEL ALARM/ NON
FPFM_P546 NT
R1 P546 : E8 QFR2 (21,22) IN/OUT DC SUPPLY FAIL NORMAL URGENT
ALARM
74IND1
=6D01+L1. MICOM CB A601 FPFM PROTECTION PANEL ALARM/
(3,11), QFR3 FPFM_P546 NT
R1 P546 : E10 INDICATION DC SUPPLY FAIL NORMAL
AA1E1Q (21,22)
000KF1.L
=6D01+L1. MICOM QFHT (21,22), CB A601 FPFM PROTECTION PANEL AC ALARM/
D0.SP16 FPFM_P546 NT
R1 P546 : C2 QFPS (21,22) SUPPLY FAIL NORMAL
GGIO3.In
AA1E1Q
d8.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 FUSE ALARM/
=E01+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
FAIL ALARM NORMAL
GGIO1.In
AA1E1Q
d7.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 ALARM/
=E01+LCC X18 (5,6) D0.SCS S1 :X18 (5,6)
BCU_6MD85_SIEMENS
NT
ISOLATOR OPEN NORMAL SPARK
WI4.Pos.
AA1E1Q
stVal SS#3 E01
005KF1.L
SPARK 380kV BSP CKT-A VT-601 ALARM/ SPARK FAILED /
=E01+LCC X5:66 D0.SP16 KT6 (6,8) BCU_6MD85_SIEMENS
NT 4012
ISOLATOR INCOMPLETE NORMAL 380kV BSP NORMAL
GGIO2.In
AA1E1Q CKT-A VT
d11.stVal
005KF1.L
SPARK 380kV BSP CKT-A VT-601 MAIN ALARM/ FAIL
=E01+LCC X5:60 D0.SP16 K17(31,32) BCU_6MD85_SIEMENS
NT
MCB TRIP / OFF NORMAL
GGIO2.In
AA1E1Q
d15.stVal
005KF1.L
K102(R,Y,B) SPARK 380kV BSP CKT-A VT-601 ALARM/
=E01+LCC X5:61 D0.SP16 BCU_6MD85_SIEMENS
NT
(13,14) BRANCH MCB TRIP / OFF NORMAL
GGIO2.In
d16.stVal
SPARK 115/33kV SUBSTATION#3 E01 115/33KV TRANSFORMER ALARMS:
AA1E1Q
003KF2.L
T601 MAIN TANK OIL LEVEL LOW ALARM/
=6T1+LCP X3:23, 24 D1.DIOG 71Q1 (3,4) IOM_A2-P849 NT
AA1E1Q ALARM NORMAL
GIO1.Ind
003FN1.
011.stVal
LD0.SP1 T601 MAIN TANK OIL LEVEL HIGH ALARM/
=6T1+LCP X3:25, 26 71Q1 (5,6) IOM_A2-P849 NT
6GGIO3.I ALARM NORMAL
nd15.stV
al T601 MAIN TANK PRESSURE RELIEF ALARM/
=6T1+LCP X3:7, 8 63P1 (11,14) IOM_A2-P849 NT
DEVICE (63P1) ALARM NORMAL

T601 MAIN TANK PRESSURE RELIEF ALARM/


=6T1+LCP X3:9, 10 63P2 (11,14) IOM_A2-P849 NT
DEVICE (63P2) ALARM NORMAL

T601 OLTC PRESSURE RELIEF DEVICE ALARM/


=6T1+LCP X3:11, 12 63P3 (11,14) IOM_A2-P849 NT
(63P3) ALARM NORMAL

ED-682330, Rev-2 PAGE 14 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 OLTC PRESSURE RELIEF DEVICE ALARM/ E
=6T1+LCP X3:13, 14 63P4 (11,14) IOM_A2-P849 NT
(63P4) ALARM NORMAL

T601 PRESSURE RELIEF DEVICE ALARM/


=6T1+LCP X3:15, 16 63P5 (11,14) IOM_A2-P849 NT
(63P5) ALARM (CHAMBER-A) NORMAL

T601 PRESSURE RELIEF DEVICE ALARM/


=6T1+LCP X3:17, 18 63P6 (11,14) IOM_A2-P849 NT
(63P6) ALARM (CHAMBER-B) NORMAL

T601 PRESSURE RELIEF DEVICE ALARM/


=6T1+LCP X3:19, 20 63P7 (11,14) IOM_A2-P849 NT
(63P7) ALARM (CHAMBER-C) NORMAL

ALARM/
=6T1+LCP X5:**, ** -- IOM_A2-P849 NT T601 FIRE PROTECTION FAULTY
NORMAL

Q1, Q2 ALARM/
+6T1+AVC X6:4 COMM-BCU NT T601 AVC RELAY DC MCB FAIL
(21,22) NORMAL

ALARM/
+6T1+AVC X6:2 K90F (4,8) COMM-BCU NT T601 AVC RELAY FAULTY
NORMAL

T601 AVC RELAY FUNCTION ALARM/


+6T1+AVC INTERNAL INTERNAL 90-6RTV NT
MONITORING FAIL NORMAL

T601 AVC RELAY SAS COMM. BOTH ALARM/


+6T1+AVC INTERNAL INTERNAL 90-6RTV NT
AA1E1Q CHANNELS FAIL NORMAL
003FN1.
LD0.SP1 ALARM/
=6T1+LCP X3:31, 32 71Q2 (3,4) IOM_A2-P849 NT T601 OLTC OIL LEVEL LOW ALARM
6GGIO3.I NORMAL
AA1E1Q
nd16.stV
003FN1.
al ALARM/
=6T1+LCP X3:33, 34 LD0.SP1 71Q2 (5,6) IOM_A2-P849 NT T601 OLTC OIL LEVEL HIGH ALARM
NORMAL
6GGIO2.I
nd.stVal SPARK
ALARM/ SS#3 T601
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT T601 SET-1 NEUTRAL CURRENT ALARM
NORMAL TRANSFO
ALARM/
RMER 4013
NORMAL
T601 SET-1 SENSITIVE EARTH FAULT ALARM/ NON
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT
PROTECTION OPTD NORMAL URGENT
ALARM
ALARM/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 NT T601 SET-2 NEUTRAL CURRENT ALARM
NORMAL

T601 SET-2 SENSITIVE EARTH FAULT ALARM/


+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 NT
PROTECTION OPTD NORMAL

ALARM/
=6T1+LCP X3 (53,54) 45M: (19, 20) DGA NT T601 GAS ANALYZER SERVICE ALARM.
NORMAL

ALARM/
=6T1+LCP X3 (55,56) 45M: (22, 24) COMM-BCU NT T601 GAS ANALYZER FAULTY
NORMAL

T601 GAS ANALYZER DC SUPPLY ALARM/


=6T1+LCP X7:37, 38 Q18 (21,22) COMM-BCU NT
FAIL / DC MCB TRIP NORMAL

T601 GAS ANALYZER (F.O) ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
COMMUNICATION FAIL NORMAL

T601 GAS ANALYZER H2 HIGH STAGE- ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
1 ALARM NORMAL

T601 GAS ANALYZER H2 HIGH STAGE- ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
2 ALARM NORMAL

T601 GAS ANALYZER CO HIGH STAGE- ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
1 ALARM NORMAL

T601 GAS ANALYZER CO HIGH STAGE- ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
2 ALARM NORMAL

T601 GAS ANALYZER MOISTURE HIGH ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
ALARM NORMAL

T601 GAS ANALYZER H2O HIGH ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
STAGE-1 ALARM NORMAL

T601 GAS ANALYZER H2O HIGH ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
STAGE-2 ALARM NORMAL

T601 GAS ANALYZER GENERAL HIGH ALARM/


=6T1+LCP INTERNAL INTERNAL DGA NT
STAGE-1 ALARM NORMAL

ED-682330, Rev-2 PAGE 15 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 GAS ANALYZER GENERAL HIGH ALARM/ E
=6T1+LCP INTERNAL INTERNAL DGA NT
STAGE-2 ALARM NORMAL
AA1E1Q
003FN1.
T601 MAIN TRF TANK GAS DETECTOR ALARM/
=6T1+LCP X3:37, 38 LD0.SP1 63D (1,2) IOM_A2-P849 NT
ALARM NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
IO BOX 87T1 ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT T601 SET-1 87T-1 PROT. RELAY FAULTY
(A2:G16) (J11,J12) NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
IO BOX T601 SET-1 87T-1 PROT. DC SUPPLY ALARM/
+6T1+R1 IOM_A2-P849
D0.SP16 QFR1 (21,22), RLA (3,11) NT
(A2:G10) FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d10.stVal
003FN1.
T601 SET-1 87T-1 PROT. RELAY UNDER ALARM /
+6T1+R1 87T1:F4 LD0.SP1 TS1 (13,14) FPFM-P643 NT
TEST NORMAL
6GGIO1.I
AA1E1Q
nd5.stVal
000KF1.L
ALARM/
+6T1+R1 X6:1, 2 D0.SP16 A2 (N11,N12) COMM-BCU NT T601 I/O BOX RELAY FAULTY
NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
T601 I/O BOX DC SUPPLY FAIL / DC ALARM/
+6T1+R1 X6:1, 3 D0.SP16 QFR2 (21,22), RLB
COMM-BCU
(3,11) NT SPARK
MCB TRIP NORMAL
GGIO4.In
AA1E1Q SS#3 T601
d10.stVal
000KF1.L TRANSFO
87T2 (B7, ALARM/ FAULTY/
+6T1+R2 X6:1,2 D0.SP16 COMM-BCU NT T601 SET-2 87T-2 PROT. RELAY FAULTY RMER 4014
B10) NORMAL NORMAL
GGIO4.In
AA1E1Q PROT.
d13.stVal
000KF1.L FLTY
27M2 (1,3), T601 SET-2 87T-2 PROT. RELAY DC ALARM/ ALARM
+6T1+R2 X6:1,3 D0.SP16 COMM-BCU NT
F221 (2,22) SUPPLY FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d14.stVal
000KF1.L
TS87T-2A/ T601 SET-2 87T-2 PROT. RELAY UNDER ALARM /
+6T1+R2 87T2:B12 D0.SP16 FPSM-7UT85 NT
AA1E1Q 2B/2C (17,18)
GGIO5.In
TEST NORMAL
003FN1.
d4.stVal
LD0.SP1 T601 SET-1 87T-1 PROT.RELAY SAS ALARM/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I
AA1E1Q COMM. CH-1 & CH-2 FAIL NORMAL
nd15.stV
003FN1.
al
LD0.SP1 T601 I/O BOX SAS COMM. CH-1 & CH-2 ALARM/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I
AA1E1Q FAIL NORMAL
nd15.stV
003FN1.
al
LD0.SP1 T601 SET-2 87T-2 PROT.RELAY SAS ALARM/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 NT
6GGIO1.I COMM. CH-1 & CH-2 FAIL NORMAL
AA1E1Q
nd16.stV
003KF2.L
al
=6T1+OLT Q8 (Axb1, ALARM/
X7:17,18 D1.DIOG 90-6RTV NT T601 OLTC MOTOR SUPPLY FAIL
C AXc1) NORMAL
GIO1.Ind
AA1E1Q
011.stVal
003KF2.L
=6T1+OLT ALARM/
D1.DIOG F1 (A1, A2) 90-6RTV NT T601 OLTC CONTROL DC SUPPLY FAIL
C AA1E1Q NORMAL
GIO1.Ind
003KF2.L
017.stVal
D1.GEN ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC OUT OF STEP ALARM
GGIO.Al
AA1E1Q NORMAL
m05.stVa
003KF2.L
l
D1.GEN ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC BLOCKED
GGIO.Al
AA1E1Q NORMAL
m01.stVa
003KF2.L
l
D1.ATCC ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC U/V ALARM
1.BlkMin NORMAL
AA1E1Q
Vol.gener
003KF2.L
al ALARM/
+6T1+AVC INTERNAL D1.ATCC INTERNAL 90-6RTV NT T601 AVC O/C ALARM
NORMAL
1.BlkAOv
.stVal
ALARM/
+6T1+AVC INTERNAL INTERNAL 90-6RTV NT T601 AVC O/V ALARM
NORMAL

ALARM/
+6T1+AVC X6:4 Q1 (21,22) COMM-BCU NT T601 AVC CONTROL DC SUPPLY FAIL
AA1E1Q NORMAL
003KF2.L
RTV- D1.GEN QFVT ALARM/
+6T1+AVC 90-6RTV NT T601 AVC VOLTAGE SUPPLY FAIL
90:H10 GGIO.Al (221,222) NORMAL
m06.stVa
l Q19 (AXc1, ALARM/
=6T1+LCP XX:** IOM_A2-P849 NT T601 SPARE COOLING FAN MCB TRIP
AXb1) NORMAL

X7:11, 12, Q5/Q6/Q7 ALARM/


=6T1+LCP IOM_A2-P849 NT T601 MAIN COOLING FAN MCB TRIP
13, 14 (AXc1, AXb1) NORMAL
SPARK
Q2 (AXc1, T601 COOLING FANS STAND BY AC ALARM/ SS#3 T601
=6T1+LCP X7:3, 4 IOM_A2-P849 NT
AXb1) POWER SUPPLY FAIL NORMAL TRANSFO
ALARM/
RMER 4015
NORMAL
Q1 (AXc1, T601 COOLING FANS MAIN AC POWER ALARM/ NON
=6T1+LCP X7:1, 2 IOM_A2-P849 NT
AXb1) SUPPLY FAIL NORMAL URGENT
AA1E1Q ALARM
003KF2.L
=6T1+OLT ALARM/
D1.DIOG KTCIC (4,8) IOM_A2-P849 NT T601 OLTC INCOMPLETE
C NORMAL
GIO1.Ind
023.stVal

ED-682330, Rev-2 PAGE 16 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2


SPARK
115kV ALARMS SS#3 T601
TRANSFO
ALARM/ CONTROL CLOSE
RMER
RECEIVED AT 4015
FULL HMI / ALARM / EVENT TEXT NORMAL SYSTEM OP LOOPTES
HARDWIR IEC TYP
NON
CONTROL CENTRE IEC TY POIN EN
DEVICE URGENT 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME ALARM 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 COOLING FANS CONTROL DC ALARM/ E
=6T1+LCP X7:33, 34 Q16 (11, 12) IOM_A2-P849 NT
SUPPLY FAIL NORMAL

ALARM/
=6T1+LCP X7:9, 10 27A (14, 11) IOM_A2-P849 NT T601 MK PANEL AC SUPPLY FAIL
NORMAL

=6T1+OLT ALARM/
1KMSF (4,8) IOM_A2-P849 NT T601 OLTC PANEL AC SUPPLY FAIL
C NORMAL
AA1E1Q
000KF1.L
QFPS (21,22), ALARM/
+6T1+AVC X6:7 D0.SP16 90-6RTV NT T601 AVC PANEL AC SUPPLY FAIL
QFHT (21,22) NORMAL
GGIO6.In
AA1E1Q
d6.stVal
000KF1.L T601 PROTECTION-1 PANEL
IO BOX QFR4 (21,22), ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT INDICATION DC SUPPLY FAIL / MCB
(A2:G14) RLD (3,11) NORMAL
GGIO4.In
AA1E1Q TRIP
d12.stVal
000KF1.L
IO BOX QFR3 (21,22), T601 PROTECTION-1 PANEL IN/OUT DC ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT
(A2:G12) RLC (3,11) SUPPLY FAIL / MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d12.stVal
000KF1.L
IO BOX QFPS (21,22), T601 PROTECTION-1 PANEL AC MCB ALARM/
+6T1+R1 D0.SP16 IOM_A2-P849 NT
(A2:G8) QFHT (21,22) TRIP NORMAL
GGIO4.In
d12.stVal T601 PROTECTION-2 PANEL
F223 (21,22), ALARM/
+6T1+R2 87T2:B13 FPSM-7UT85 NT INDICATION DC SUPPLY FAIL / MCB
27IND (1,3) NORMAL
TRIP

F222 (21,22), T601 PROTECTION-2 PANEL IN/OUT DC ALARM/


+6T1+R2 87T2:B14 FPSM-7UT85 NT
27M2/IO (1,3) SUPPLY FAIL / MCB TRIP NORMAL
AA1E1Q
000KF1.L
F101 (21,22), T601 PROTECTION-2 PANEL AC MCB ALARM/
+6T1+R2 87T2:A10 D0.SP16 FPSM-7UT85 NT
F102 (21,22) TRIP NORMAL
GGIO4.In
AA1E1Q
d16.stVal
003FN1.
T601 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
003FN1.
T601 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd2.stVal
003FN1.
T601 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.B OPTD NORMAL
6GGIO1.I
AA1E1Q
nd3.stVal
003FN1.
TRIP/
+6T1+R1 87T1:D2 LD0.SP1 86T-1(5,7) FPFM-P643 T T601 86T-1 LOCKOUT RELAYOPTD.
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd6.stVal
Protectio T601 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.R OPTD NORMAL
1.Op.phs
003FN2.
A
Protectio T601 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.Y OPTD NORMAL
1.Op.phs
003FN2.
B
Protectio T601 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.B OPTD NORMAL
1.Op.phs
003FN2.
C
System. TRIP/
+6T1+R2 87T2:D10 86T-2 (22,28) FPSM-7UT85 T T601 86T-2 LOCKOUT RELAYOPTD.
OptGGIO NORMAL
AA1E1Q
1.Ind15.s
003FN1.
tVal T601 SET-1 LV 87REF-1 RESTRICTED TRIP/
+6T1+R1 INTERNAL LD0.REF INTERNAL FPFM-P643 T
EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
AA1E1Q
p.general
003FN1.
T601 SET-1 SBEF STAND BY EARTH TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
FAULT PROTECTION OPTD. NORMAL
6GGIO1.I
AA1E1Q
nd6.stVal
003FN1.
T601 SET-1 HV 50P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd7.stVal
003FN1.
T601 SET-1 HV 50P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd8.stVal
003FN1.
T601 SET-1 HV 50P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
AA1E1Q PH-B OPTD NORMAL
6GGIO1.I
003FN1.
nd9.stVal
LD0.SP1 T601 SET-1 HV 51P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd10.stV
003FN1.
al
LD0.SP1 T601 SET-1 HV 51P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd11.stV
003FN1.
al
LD0.SP1 T601 SET-1 HV 51P O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T601 SET-1 HV 50NP E/F PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I OPTD. NORMAL
nd13.stV
al

ED-682330, Rev-2 PAGE 17 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN1. COD TRE
LD0.SP1 T601 SET-1 HV 51NP E/F PROTECTION TRIP/ E
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/ SPARK
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL SS#3 T601
nd13.stV TRANSFO OPERATE /
003FN1. 4016
al RMER NORMAL
LD0.SP1 T601 SET-1 LV 51S O/C PROTECTION TRIP/ PROT
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL OPTD
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 50NS E/F PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T601 SET-1 LV 51NS E/F PROTECTION TRIP/
+6T1+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN2.
al
Protectio T601 SET-2 LV 87REF-2 RESTRICTED TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85
n.LzrLvw
AA1E1Q EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 SBEF STAND BY EARTH TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51P O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 50NP E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 HV 51NP E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
System. T601 SET-2 LV 50S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI
AA1E1Q PH-B OPTD NORMAL
O2.Ind2.s
003FN2.
tVal
System. T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI PH-R OPTD NORMAL
O2.Ind3.s
No
tVal T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL siginal in INTERNAL FPSM-7UT85 T
AA1E1Q PH-Y OPTD NORMAL
scheme
003FN2.
Protectio T601 SET-2 LV 51S O/C PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q PH-B OPTD NORMAL
PTOC1.
003FN2.
Op.phsA
Protectio T601 SET-2 LV 50NS E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q OPTD. NORMAL
PTOC1.
003FN2.
Op.phsB
Protectio T601 SET-2 LV 51NS E/F PROTECTION TRIP/
+6T1+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2 OPTD. NORMAL
PTOC1.
Op.phsC

ED-682330, Rev-2 PAGE 18 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
003FN1. E
TRIP/
+6T1+R1 87T1:D4 LD0.SP1 94T-1(1,3) FPFM-P643 T T601 94T-1 TRIP RELAY OPTD
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd8.stVal
System. TRIP/
+6T1+R2 87T2:D14 94T-2 (A2,A4) FPSM-7UT85 T T601 94T-2 TRIP RELAY OPTD
OptGGIO NORMAL
1.Ind16.s
tVal T601 MAIN TANK PRESSURE RELIEF TRIP/
=6T1+LCP X4:7, 8 63P1 (21,24) IOM_A2-P849 T
DEVICE (63P1) OPTD. NORMAL

T601 MAIN TANK PRESSURE RELIEF TRIP/


=6T1+LCP X4:9, 10 63P2 (21,24) IOM_A2-P849 T
DEVICE (63P2) OPTD. NORMAL

T601 OLTC PRESSURE RELIEF DEVICE TRIP/


=6T1+LCP X4:11, 12 63P3 (21,24) IOM_A2-P849 T
(63P3) OPTD. NORMAL

T601 OLTC PRESSURE RELIEF DEVICE TRIP/


=6T1+LCP X4:13, 14 63P4 (21,24) IOM_A2-P849 T
(63P4) OPTD. NORMAL

T601 PRESSURE RELIEF DEVICE TRIP/


=6T1+LCP X4:15, 16 63P5 (21,24) IOM_A2-P849 T
(63P5) OPTD. (CHAMBER-A) NORMAL

T601 PRESSURE RELIEF DEVICE TRIP/


=6T1+LCP X4:17, 18 63P6 (21,24) IOM_A2-P849 T SPARK
(63P6) OPTD. (CHAMBER-B) NORMAL
SS#3 T601
TRANSFO
T601 PRESSURE RELIEF DEVICE TRIP/ OPERATE/
=6T1+LCP X4:19, 20 63P7 (21,24) IOM_A2-P849 T RMER 4017
AA1E1Q (63P7) OPTD. (CHAMBER-C) NORMAL NORMAL
MECH.
003FN2. PROT.
System. T601 MAIN TANK OIL TEMPERATURE TRIP/ OPTD
=6T1+LCP X4:31, 32 26Q-2(41,44) IOM_A2-P849 T
OptGGIO HIGH STAGE-2 OPTD. NORMAL
1.Ind11.s
tVal T601 OLTC PROTECTIVE RELAY TRIP/
=6T1+LCP X4:3, 4 63PR1 (3,4) IOM_A2-P849 T
AA1E1Q STAGE-2 OPTD. NORMAL
003FN2.
System. T601 MAIN TANK BUCHHOLZ SATGE-2 TRIP/
=6T1+LCP X4:1, 2 63B (1, 2) IOM_A2-P849 T
OptGGIO
AA1E1Q OPTD NORMAL
1.Ind2.st
003FN2.
Val
System. T601 HV WINDING TEMPERATURE TRIP/
=6T1+LCP X4:27, 28 49W1 (41,44) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind12.s
003FN2.
tVal
System. T601 LV WINDING TEMPERATURE TRIP/
=6T1+LCP X4:29, 30 49W2 (6,8) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind16.s
003FN2.
tVal
System. TRIP/
=6T1+LCP XX: ** R1 (7,8) IOM_A2-P849 T T601 RAPID PRESSURE OPTD. SPARK
OptGGIO
AA1E1Q NORMAL
1.Ind7.st SS#3 T601
003FN1.
Val TRANSFO
LD0.SP1 FPO:X5 FAULTY/ OPERATE /
=6T1+LCP X5:65, 66 IOM_A2-P849 NT T601 FIRE PROTCTION OPTD RMER 4018
6GGIO3.I (65,66) NORMAL NORMAL
AA1E1Q FIRE
SPARK
nd12.stV
003FN1. PROT
SS#3 T601
al
LD0.SP1 T601 MAIN TANK OIL TEMPERATURE ALARM/ OPTD
TRANSFO ALARM
=6T1+LCP X3:49, 50 26Q (31,34) IOM_A2-P849 NT 4019
6GGIO3.I HIGH STAGE-1 ALARM NORMAL RMER OIL /NORMAL
nd11.stV TEMP ST1
AA1E1Q SPARK
al ALARM
003FN1. SS#3 T601
T601 MAIN TANK BUCHHOLZ STAGE-1 ALARM/ ALARM/
=6T1+LCP X3:1, 2 LD0.SP1 63B (3,4) IOM_A2-P849 NT TRANSFO 4020
ALARM NORMAL NORMAL
6GGIO3.I
AA1E1Q RMER
nd2.stVal
003FN1. BUCH ST1
LD0.SP1 T601 HV WINDING TEMPERATURE ALARM/
=6T1+LCP X3:45, 46 49W1 (31,34) IOM_A2-P849 NT
6GGIO3.I
AA1E1Q HIGH STAGE-1 ALARM NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T601 LV WINDING TEMPERATURE ALARM/
=6T1+LCP X3:47, 48 49W2 (31,34) IOM_A2-P849 NT
6GGIO3.I HIGH STAGE-1 ALARM NORMAL
nd13.stV
al T601 FIBER OPTIC WINDING TEMP. ALARM/
=6T1+LCP CH1 (HV-U) CH1 (HV-U) FOM NT
MONITOR (FOWT) CH1 (HV-U) NORMAL

T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH2 (HV-V) CH2 (HV-V) FOM NT
MONITOR (FOWT) CH2 (HV-V) NORMAL

T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH3 (HV-V) CH3 (HV-V) FOM NT
MONITOR (FOWT) CH3 (HV-V) NORMAL

T601 FIBER OPTIC WINDING TEMP. ALARM/ SPARK


=6T1+LCP CH4 (HV-V) CH4 (HV-V) FOM NT
MONITOR (FOWT) CH4 (HV-V) NORMAL SS#3 T601
TRANSFO OPERATED
4021
RMER / NORMAL
CH5 (HV- T601 FIBER OPTIC WINDING TEMP. ALARM/ WDG
=6T1+LCP CH5 (HV-W) FOM NT
W) MONITOR (FOWT) CH5 (HV-W) NORMAL TEMP ST1

T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH6 (HV-U) CH6 (HV-U) FOM NT
MONITOR (FOWT) CH6 (LV-U) NORMAL

T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH7 (HV-V) CH7 (HV-V) FOM NT
MONITOR (FOWT) CH7 (LV-V) NORMAL

ED-682330, Rev-2 PAGE 19 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED
SPARK
SAS POINT LIST SS#3 T601 REV-2
TRANSFO OPERATED
4021
RMER / NORMAL
115kV ALARMS WDG
TEMP ST1
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
COD TRE
T601 FIBER OPTIC WINDING TEMP. ALARM/ E
=6T1+LCP CH8 (HV-V) CH8 (HV-V) FOM NT
MONITOR (FOWT) CH8 (LV-V) NORMAL

T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH9 (HV-V) CH9 (HV-V) FOM NT
MONITOR (FOWT) CH9 (LV-V) NORMAL

CH10 (HV- T601 FIBER OPTIC WINDING TEMP. ALARM/


=6T1+LCP CH10 (HV-W) FOM NT
W) MONITOR (FOWT) CH10 (LV-W) NORMAL

ALARM/
=E01+LCC -- INTERNAL
BCU_6MD85_SIEMENS
NT T601 VT-602 FUSE FAIL ALARM
NORMAL

ALARM/
=E01+LCC X19 (5,6) S1 :X19 (5,6)
BCU_6MD85_SIEMENS
NT T601 VT-602 ISOLATOR OPEN
NORMAL

ALARM/
=E01+LCC X5:66 KT6A (6,8)
BCU_6MD85_SIEMENS
NT T601 VT-602 ISOLATOR INCOMPLETE
NORMAL

ALARM/
=E01+LCC X5:64 K20 (31,32)
BCU_6MD85_SIEMENS
NT T601 VT-602 MAIN MCB TRIP / OFF SPARK
NORMAL
SS#3 T601 FAILED /
4022
TRANSFO NORMAL
K103 (R,Y,B) ALARM/ RMER VT
=E01+LCC X5:65 BCU_6MD85_SIEMENS
NT T601 VT-602 BRANCH MCB TRIP / OFF
(13,14) NORMAL

ALARM/
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 T601 LV VT FUSE FAIL ALARM
NORMAL
Q411,Q412,Q
413,Q421,Q4 ALARM/
=BH05/IC X7:23 BCPU / REF 620 T601 LV VT MCB TRIP
22,Q423,Q42 NORMAL
4(21,22)
ALARM/
=BH05/IC INTERNAL AA1E1Q INTERNAL BCPU / REF 620 T601 LV VT-304 RACK OUT
003KF2.L NORMAL
D1.GEN
=6T1+OLT GGIO.Al LOCAL/
-- S132A (9,10) 90-6RTV NT T601 OLTC CONTROL MODE IN LOCAL
C m11.stVa REMOTE
SPARK
l/ SS#3 T601
Ind021.st T601 SAS CONTROL MODE AUTHORITY LOCAL/ TRANSFO LOCAL /
+6T1+AVC INTERNAL Val INTERNAL 90-6RTV NT 4023
SET TO SAS/ERCC REMOTE RMER TAP REMOTE
AA1E1Q CHANGER
003KF2.L
LOCAL/ REMOTE
+6T1+AVC RTV-90:I3 D1.DIOG 1KOL (4, 8) 90-6RTV NT T601 AVC CONTROL MODE IN LOCAL
REMOTE
GIO1.Ind
006.stVal
SPARK 115/33kV SUBSTATION#3 E02 115KV CB ALARMS:
AA1E1Q
005KF1.L
K26A (43, 44) DS/ES IN MAINTENANCE HAND CRANK ALARM/
=E02+LCC X5:47 D0.SP16 BCU_6MD85_SIEMENS
NT
K26B (43, 44) INSERTED NORMAL
GGIO4.In
AA1E1Q
d8.stVal
005KF1.L
CB A602 IN MAINTENANCE HAND ALARM/
=E02+LCC X5:21 D0.SP16 K26 (43, BCU_6MD85_SIEMENS
44) NT
CRANK INSERTED NORMAL
GGIO4.In
d7.stVal
ALARM/
=E02+LCC X5:108 K73 (43,44)
BCU_6MD85_SIEMENS
NT CB A602 AUTO TRIP ALARM
NORMAL
AA1E1Q
005KF1.L
DS & ES MOTOR RUNNING TIME ALARM/
=E02+LCC X5:45 D0.SP16 K15 (53, BCU_6MD85_SIEMENS
54) NT
EXCEEDED NORMAL
GGIO4.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E02+LCC X5:43 D0.SP16 K97 (31, BCU_6MD85_SIEMENS
32) NT DS/ES CONTROL SUPPLY FAIL
NORMAL
GGIO4.In
AA1E1Q SPARK
d10.stVal K95 (31, 32),
005KF1.L SS#3 E02
K95A (31, 32), ALARM/ ALARM/
=E02+LCC X5:44 D0.SP16 BCU_6MD85_SIEMENS
NT DS & ES MOTOR SUPPLY FAIL CB A602 4024
K95B (31, 32), NORMAL NORMAL
GGIO5.In
AA1E1Q K95C (31, 32) URGENT
d6.stVal
005KF1.L ALARM
ALARM/
=E02+LCC X5:20 D0.SP16 K91 (31, BCU_6MD85_SIEMENS
32) NT CB A602 MOTOR SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d8.stVal
005KF1.L
ALARM/
=E02+LCC X5:50 D0.SP16 K12A (51,BCU_6MD85_SIEMENS
52) NT DS/ES LOCK POSITION
NORMAL
GGIO4.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E02+LCC X5:48 D0.SP16 K30 (43, BCU_6MD85_SIEMENS
44) NT DS SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E02+LCC X5:49D0.SP16 K31 (43, BCU_6MD85_SIEMENS
44) NT ES SWITCHING INCOMPLETE
NORMAL
GGIO9.In
AA1E1Q
d3.stVal
005KF1.L
CB A602 CTPU (METROCIL) O/V ALARM/
=E02+LCC -- D0.SP16 -- BCU_6MD85_SIEMENS
NT
PROTECTION ALARM NORMAL
GGIO9.In
AA1E1Q
d16.stVal
005FN1.
=6D02+CB 74TCS-1 ALARM/
50BF:C14 LD0.SP1 50BF-7VK87 NT CB A602 TRIP CIRCUIT 1 FAULTY
F/TCS.R1 (5,13) NORMAL
6GGIO3.I
nd5.stVal

ED-682330, Rev-2 PAGE 20 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
CB A602 TRIP CIRCUIT 1 DC SUPPLY ALARM/
=E02+LCC X5:33 D0.SP16 K93 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
G00KF1
d9.stVal-
=6D02+CB 15. ALARM/
50BF:D3 74TCS-2 (2,4) 50BF-7VK87 NT CB A602 TRIP CIRCUIT 2 FAULTY
F/TCS.R1 Ind4.stVa NORMAL
AA1E1Q
l
005KF1.L
CB A602 TRIP CIRCUIT 2 DC SUPPLY ALARM/
=E02+LCC X5:35 D0.SP16 K94 (31,32)BCU_6MD85_SIEMENSNT
FAIL NORMAL
GGIO3.In
AA1E1Q
d10.stVal
004KF1.L
ALARM/
=E02+LCC X21:20 D0.SP16 K106 (71,72) COMM_BCU NT CB A602 BCU DC SUPPLY FAIL
NORMAL SPARK
GGIO5.In
AA1E1Q
d12.stVal SS#3 E02
004KF1.L
ALARM/ CB A602 FAULTY /
=E02+LCC X21:21 D0.SP16 K13 (71,72) COMM_BCU NT CB A602 BCU RELAY FAULTY 4025
NORMAL PROT. NORMAL
GGIO5.In
AA1E1Q FLTY
d14.stVal
005KF1.L
ALARM/ ALARM
=E02+LCC -- D0.SP16 -- COMM_BCU NT CB A602 BCU UNDER TEST
NORMAL
GGIO5.In
AA1E1Q
d15.stVal
003FN11
GW1-SRV-1 CB A602 BCU SAS COMMUNICATION ALARM/
=E02+LCC INTERNAL .LD0.SP1 INTERNAL NT
GW2-SEV-2 BOTH CHANNELS FAIL NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
=6D02+CB 74DC (1,3), CBF A602 DC SUPPLY FAIL / DC MCB ALARM/
X6:3 D0.SP16 COMM_BCU NT
F/TCS.R1 F221 (21,22) TRIP NORMAL
GGIO7.In
AA1E1Q
d.stVal
000KF1.L
=6D02+CB 50BF ALARM/
X6:2 D0.SP16 COMM_BCU NT CBF A602 RELAY FAULTY
F/TCS.R1 (B7,B10) NORMAL
GGIO7.In
AA1E1Q
d3.stVal
003FN11
=6D02+CB CBF A602 PROT. SAS ALARM/
INTERNAL .LD0.SP1 INTERNAL 50BF-7VK87 NT
F/TCS.R1 COMMUNICATION FAIL (CH-1 & CH-2) NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:99 D0.SP16 K46 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
AA1E1Q
d1.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:100 D0.SP16 K49 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
GGIO8.In
d2.stVal
GIS PS01_3 SF6 GAS PRESSURE HIGH ALARM/
=E02+LCC X5:101 K52 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

K55 (31,32) CB A602 PS01_4 SF6 GAS PRESSURE ALARM/


=E02+LCC X5:102 BCU_6MD85_SIEMENS
NT
K55A (31, 32) HIGH STAGE NORMAL

GIS PS01_5 SF6 GAS PRESSURE HIGH ALARM/


=E02+LCC X5:103 K60 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_6 SF6 GAS PRESSURE HIGH ALARM/


=E02+LCC X5:104 K63 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_7 SF6 GAS PRESSURE HIGH ALARM/


=E02+LCC X5:105 K66 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL

GIS PS01_8 SF6 GAS PRESSURE HIGH ALARM/


=E02+LCC X5:106 K69 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE NORMAL
AA1E1Q
005KF1.L
K53 (61, 62), CB A602 SF6 GAS PRESSURE LOW ALARM/ SPARK
=E02+LCC X5:24 D0.SP16 BCU_6MD85_SIEMENS
NT
K56 (61, 62) STAGE-1 NORMAL SS#3 E02
GGIO2.In ALARM /
d4.stVal CB A602 4026
NORMAL
K54 (61,62), CB A602 SF6 GAS PRESSURE LOW ALARM/ SF6 GAS
=E02+LCC X5:31 BCU_6MD85_SIEMENS
NT
K57 (61, 62) STAGE-2 NORMAL ALARM
AA1E1Q
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:83 D0.SP16 K44 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d2.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:84 D0.SP16 K47 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d3.stVal
005KF1.L
GIS PS01_3 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:85 D0.SP16 K50 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d4.stVal
005KF1.L
GIS PS01_4 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:86 D0.SP16 K53 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_5 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:87 D0.SP16 K58 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d6.stVal
005KF1.L
GIS PS01_6 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:88 D0.SP16 K61 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d7.stVal
005KF1.L
GIS PS01_7 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:89 D0.SP16 K64 (31,32)BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
d8.stVal

ED-682330, Rev-2 PAGE 21 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
005KF1.L E
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:90 D0.SP16 K67 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-1 NORMAL
GGIO6.In
AA1E1Q
d9.stVal
005KF1.L
K53 (71,72), ALARM/
=E02+LCC X5:24 D0.SP16 BCU_6MD85_SIEMENS
NT CB A602 CLOSING LOCKOUT ALARM
K56 (71,72) NORMAL
GGIO2.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_1 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:91 D0.SP16 K45 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d2.stVal
005KF1.L
GIS PS01_2 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:92 D0.SP16 K48 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d3.stVal
005KF1.L
GIS PS01_3 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:93 D0.SP16 K51 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d4.stVal
005KF1.L
CB A602 PS01_4 SF6 GAS PRESSURE ALARM/
=E02+LCC X5:94 D0.SP16 K56 (31,32)
BCU_6MD85_SIEMENS
NT
LOW STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d5.stVal
005KF1.L
GIS PS01_5 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:95 D0.SP16 K59 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d6.stVal
005KF1.L
GIS PS01_6 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:96 D0.SP16 K62 (31,32)
BCU_6MD85_SIEMENS
NT SPARK
STAGE-2 NORMAL
GGIO7.In
AA1E1Q SS#3 E02 ALARM/
d7.stVal 4027
005KF1.L CB A602 NORMAL
GIS PS01_7 SF6 GAS PRESSURE LOW ALARM/ LOCKOUT
=E02+LCC X5:97 D0.SP16 K65 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d8.stVal
005KF1.L
GIS PS01_8 SF6 GAS PRESSURE LOW ALARM/
=E02+LCC X5:98 D0.SP16 K68 (31,32)
BCU_6MD85_SIEMENS
NT
STAGE-2 NORMAL
GGIO7.In
AA1E1Q
d9.stVal
005KF1.L
CB A602 CLOSING COIL DC SUPPLY ALARM/
=E02+LCC X5:26 D0.SP16 K92 (31,32)
BCU_6MD85_SIEMENS
NT
FAIL NORMAL
GGIO4.In
AA1E1Q
d6.stVal
005KF1.L
ALARM/
=E02+LCC X5:19 D0.SP16 K3 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 MOTOR RUNTIME EXCEED
NORMAL
GGIO4.In
d5.stVal
CB A602 OPERATING MECHANISIM ALARM/
=E02+LCC X5:18 K4 (83,84)
BCU_6MD85_SIEMENS
NT
FAIL NORMAL
AA1E1Q
005KF1.L
ALARM/
=E02+LCC X5:31 D0.SP16 K54 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 TRIP COIL-1 LOCKOUT
NORMAL
GGIO3.In
AA1E1Q
d11.stVal
005KF1.L
ALARM/
=E02+LCC X5:38 D0.SP16 K57 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 TRIP COIL-2 LOCKOUT
NORMAL
GGIO3.In
AA1E1Q
d12.stVal
005KF1.L
ALARM/
=E02+LCC X5:59 D0.SP16 K23 (21,22)
BCU_6MD85_SIEMENS
NT CB A602 LCC DC SUPPLY FAIL
NORMAL
GGIO5.In
AA1E1Q
d.stVal
005KF1.L
ALARM/
=E02+LCC X5:58 D0.SP16 K24 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 LCC DC MCB TRIP/OFF
NORMAL
GGIO5.In
d2.stVal
ALARM/
=E02+LCC X5:54 K98 (31,32)
BCU_6MD85_SIEMENS
NT CB A602 INDICATION SUPPLY FAIL
NORMAL
AA1E1Q
005KF1.L K99 (21,22),
ALARM/
=E02+LCC X5:57 BCU_6MD85_SIEMENS
D0.SP16 K108 (21,22), NT CB A602 LCC AC SUPPLY FAIL
NORMAL
AA1E1Q F23 (11,12)
GGIO5.In
d4.stVal
005KF1.L F21 (11,12),
ALARM/
=E02+LCC X5:56 BCU_6MD85_SIEMENS
D0.SP16 F22 (11,12), NT CB A602 LCC AC MCB TRIP
NORMAL SPARK
AA1E1Q F23 (11,12)
GGIO5.In
d5.stVal SS#3 E02
005KF1.L
ALARM/ CB A602 ALARM/
=E02+LCC X5:53 D0.SP16 K14 (13,14)
BCU_6MD85_SIEMENS
NT CB A602 LCC ANNUNCIATOR FAULTY 4028
NORMAL NON_URG NORMAL
GGIO5.In
AA1E1Q ENT
d11.stVal
005KF1.L
CB A602 LCC ANNUNCIATOR DC ALARM/ ALARM
=E02+LCC X5:51 D0.SP16 F11 (12, BCU_6MD85_SIEMENS
11) NT
SUPPLY FAIL NORMAL
GGIO5.In
AA1E1Q
d9.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNCH CHECK FAIL (DELTA V)
NORMAL
GGIO1.In
AA1E1Q
d14.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNCH CHECK FAIL (DELTA F)
NORMAL
GGIO1.In
AA1E1Q
d15.stVal
005KF2.L
CB A602 SYNCH CHECK FAIL (DELTA ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
PHI) NORMAL
GGIO1.In
AA1E1Q
d16.stVal
005KF2.L
ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT CB A602 SYNC CHECK BLOCK (VT FF)
AA1E1Q NORMAL
GGIO1.In
005FN11
d13.stVal
=6D02+CB .LD0. TRIP/ SPARK
INTERNAL INTERNAL 50BF/7VK87 T CB A602 CBF 50BF PROTECTION OPTD
F/TCS.R1 CCRBRF NORMAL SS#3 E02
1.OpIn.g CB A602 OPERATE/
4029
eneral CBF NORMAL
PROT.
OPTD
ED-682330, Rev-2 PAGE 22 OF 104
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI OP TRO
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT ADDR E rks
BER DESCRIPTION SPARK E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX LITRA INDEX ID
SS#3 E02 ESS ARM TYPE ST CEN
TIFIER
AA1E1Q CB A602 OPERATE/ COD TRE
4029
005FN11 CBF NORMAL E
=6D02+CB 86BF/A602 (5, CB A602 86D02+CBF/TCS.R1 LOCKOUT TRIP/ PROT.
50BF:C13 .LD0.SP1 50BF/7VK87 T
F/TCS.R1 AA1E1Q 7) RELAY OPTD NORMAL OPTD
6GGIO1.I
005FN11
nd6.stVal
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:39 K27 (83, BCU_6MD85_SIEMENS
84) NT OFF / ON
6GGIO8.I
AA1E1Q TROLLEY
nd13.stV
005FN11
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:40 S43R (11,BCU_6MD85_SIEMENS
12) NT OFF / ON
6GGIO8.I
AA1E1Q LOCAL
nd14.stV
005FN11 SPARK
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO SS#3 E02
=E02+LCC X5:41 S43R (21,BCU_6MD85_SIEMENS
22) NT OFF / ON OFF / ON 4030
6GGIO8.I
AA1E1Q BCU CB A602
nd15.stV
005FN11 REMOTE
al
.LD0.SP1 CB A602 BAY CONTROL MODE SET TO
=E02+LCC X5:42 S43R (31,BCU_6MD85_SIEMENS
32) OFF / ON
6GGIO8.I
AA1E1Q REMOTE
nd16.stV
005FN11
al
.LD0.SP1 ALARM/
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS
NT CB A602 BAY BLOCK
6GGIO8.I NORMAL
nd13.stV
al
SPARK 115/33kV SUBSTATION#3 E02 115/33KV SPARK CKT-B ALARMS:
AA1E1Q
005FN1.
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM CH-A ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd15.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM CH-B ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q F.O TELECOMM. FAIL NORMAL
nd16.stV
005FN1. SPARK
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM F.O ALARM / SS#3 E02
INTERNAL INTERNAL FPSM_7SD522 NT SPARK
R2 6GGIO1.I
AA1E1Q TELECOMM. FAIL (BOTH CHANNELS) NORMAL
nd14.stV 380kV BSP ALARM /
005FN2. 4031
al CKT-B NORMAL
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM CH-A ALARM / COMM
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL URGENT
O2.Ind31
005FN2. ALARM
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM CH-B ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q F.O TELECOMM. FAIL NORMAL
O2.Ind32
005FN2.
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM F.O ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI TELECOMM. FAIL (BOTH CHANNELS) NORMAL
AA1E1Q
O2.Ind23
005FN1.
.stVal
=6D02+L2. SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 RELAY VT FUSE FAIL NORMAL
6GGIO2.I
AA1E1Q
nd5.stVal
000KF1.L
=6D02+L2. 87L/21/67N-2 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R2 AA1E1Q (K3,K4) RELAY FAULTY NORMAL
GGIO3.In
005FN1.
d.stVal
=6D02+L2. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-BFPSM PROT. ALARM /
TS2 (1,2) FPSM_7SD522 NT
R2 J9 6GGIO2.I RELAY UNDER TEST NORMAL
AA1E1Q
nd14.stV
000KF1.L
al
=6D02+L2. 74DC2 (1,3), SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
X6:3 D0.SP16 COMM-BCU NT
R2 AA1E1Q F221 (21,22) DC SUPPLY FAIL NORMAL
GGIO3.In
005FN1.
d2.stVal
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL
nd15.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D02+L2. al
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 OptGGIO RELAY VT FUSE FAIL NORMAL
AA1E1Q
1.Ind5.st
000KF1.L
Val
=6D02+L2. 87L/21/67N-1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
X6:2 D0.SP16 COMM-BCU NT
R1 (M11,M12) RELAY FAULTY NORMAL
GGIO3.In
d5.stVal
=6D02+L2. MICOM SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
TS2 (1,2) FPFM_P546 NT
R1 P546 : E14 RELAY UNDER TEST NORMAL
AA1E1Q
000KF1.L SPARK
=6D02+L2. 74DC1 (11,3), SPARK 380kV BSP CKT-B FPFM PROT. ALARM / SS#3 E02
X6:3 D0.SP16 COMM-BCU NT
R1 AA1E1Q QFR1(21,22) DC SUPPLY FAIL NORMAL SPARK
GGIO3.In FAULTY /
005FN1.
d6.stVal 380kV BSP 4032
NORMAL
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM / CKT-B
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-A FAIL NORMAL PROT.
nd15.stV ALARM
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 6GGIO2.I
AA1E1Q RELAY SAS COMM. CH-B FAIL NORMAL
nd16.stV
005FN2.
=6D02+L2. al
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
O2.Ind19
005FN2.
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM /
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI DIST. FUNCTION BLOCKED NORMAL
O2.Ind20
.stVal

ED-682330, Rev-2 PAGE 23 OF 104


SPARK
SS#3 E02
SPARK
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 FAULTY / DOC. NO: ED
380kV BSP 4032
NORMAL
CKT-B
SAS POINT LIST PROT. REV-2
ALARM

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN2. COD TRE
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM PROT. ALARM / E
INTERNAL INTERNAL FPFM_P546 NT
R1 GosGGI
AA1E1Q DEF FUNCTION BLOCKED NORMAL
O2.Ind22
005FN1.
=6D02+L2. .stVal
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I
AA1E1Q DIFF FUNCTION BLOCKED NORMAL
nd11.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL INTERNAL FPSM_7SD522 NT
R2 6GGIO1.I DIST. FUNCTION BLOCKED NORMAL
AA1E1Q
nd12.stV
005FN1.
al
=6D02+L2. SPARK 380kV BSP CKT-B FPSM PROT. ALARM /
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 NT
R2 AA1E1Q DEF FUNCTION BLOCKED NORMAL
6GGIO2.I
005FN1.
nd1.stVal
=6D02+L2. 7SD522 : LD0.DPG SPARK 380kV BSP CKT-B FPSM ALARM /
K02 (2, 4) FPSM_7SD522 NT
R2 J7 GIO1.DP
AA1E1Q PROTECTION OUT NORMAL
CSO.stV
005FN2.
al
=6D02+L2. MICOM System.U SPARK 380kV BSP CKT-B FPFM ALARM /
K01 (1,10) FPFM_P546 NT
R1 P546 : E12 srGGIO1.
AA1E1Q PROTECTION OUT NORMAL
DPCSO1
005FN1.
=6D02+L2. .stVal
LD0.LDL SPARK 380kV BSP CKT-BFPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
p.Loc.phs
005FN1.
=6D02+L2. .A
LD0.LDL SPARK 380kV BSP CKT-B FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
p.Loc.phs
005FN1.
=6D02+L2. .B
LD0.LDL SPARK 380kV BSP CKT-B FPSM 87-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PDIF1.O DIFF. PROTECTION PH.B OPTD NORMAL
AA1E1Q
p.Loc.phs
005FN1.
.C
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
005FN1.
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 DIST. PROTECTION PH.Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd2.stVal
005FN1.
=6D02+L2. SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL LD0.SP1 INTERNAL FPSM_7SD522 T
R2 AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
6GGIO1.I
005FN1.
nd3.stVal
=6D02+L2. LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
nd12.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
nd13.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z3. OPTD NORMAL
nd14.stV
005FN1.
=6D02+L2. al
LD0.SP1 SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO3.I
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
nd14.stV
005FN1.
=6D02+L2. al
LD0.ZCP SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DIST. AIDED OPTD NORMAL
.general(
005FN1.
=6D02+L2. ST)
LD0.ZCV SPARK 380kV BSP CKT-B FPSM 21-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 PSOF1.O DIST. SOTF OPTD NORMAL
p.general
=6D02+L2. (ST) SPARK 380kV BSP CKT-B FPSM 50/51-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-R OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPSM 50/51-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-Y OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPSM 50/51-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 O/C PROTECTION PH-B OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPSM 51N-2 TRIP/


INTERNAL INTERNAL FPSM_7SD522 T
R2 AA1E1Q E/F PROTECTION OPTD NORMAL
005FN1.
=6D02+L2. LD0.ECP SPARK 380kV BSP CKT-B FPSM 67N-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 SCH1.Op
AA1E1Q DEF. AIDED OPTD NORMAL
.general(
005FN1.
=6D02+L2. ST)
EF4_1.E SPARK 380kV BSP CKT-B FPSM 67N-2 TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 F4TOC1.
AA1E1Q DEF DELAYOPTD NORMAL
Op.gener
005FN2.
=6D02+L2. al(ST)
Protectio SPARK 380kV BSP CKT-B FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF
AA1E1Q DIFF. PROTECTION PH.R OPTD NORMAL
1.Op.phs
005FN2.
=6D02+L2. A
Protectio SPARK 380kV BSP CKT-B FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF
AA1E1Q DIFF. PROTECTION PH.Y OPTD NORMAL
1.Op.phs
005FN2.
=6D02+L2. B
Protectio SPARK 380kV BSP CKT-B FPFM 87-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DifPDIF DIFF. PROTECTION PH.B OPTD NORMAL
1.Op.phs
C

ED-682330, Rev-2 PAGE 24 OF 104


SPARK
SS#3 E02
SPARK
OPERATE /
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
005FN2. COD TRE
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ E
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.R OPTD NORMAL
O2.Ind1.s
005FN2.
tVal SPARK
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ SS#3 E02
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.Y OPTD NORMAL SPARK
O2.Ind2.s OPERATE /
005FN2. 380kV BSP 4033
tVal NORMAL
=6D02+L2. System. SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/ CKT-B
INTERNAL INTERNAL FPFM_P546 T PROT.
R1 GosGGI
AA1E1Q DIST. PROTECTION PH.B OPTD NORMAL
O2.Ind3.s OPTD
005FN2.
=6D02+L2. tVal
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z1. OPTD NORMAL
S1.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z2. OPTD NORMAL
S2.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z3. OPTD NORMAL
S3.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPDI
AA1E1Q DIST. PROTECTION Z4. OPTD NORMAL
S3.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B FPFM 21-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPSC
AA1E1Q DIST. AIDED OPTD NORMAL
H1.Op.ge
005FN2.
=6D02+L2. neral
Protectio SPARK 380kV BSP CKT-B 21-1 DIST. TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.SofPS SOTF OPTD NORMAL
OF1.Op1
=6D02+L2. .general SPARK 380kV BSP CKT-B FPFM 50/51-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-R OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPFM 50/51-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-Y OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPFM 50/51-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 O/C PROTECTION PH-B OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPFM TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 50/51N-1 E/F PROTECTION OPTD NORMAL

=6D02+L2. SPARK 380kV BSP CKT-B FPFM 67N-1 TRIP/


INTERNAL INTERNAL FPFM_P546 T
R1 AA1E1Q DEF DELAYOPTD NORMAL
005FN2.
=6D02+L2. Protectio SPARK 380kV BSP CKT-B FPFM 67N-1 TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 n.DisPSC
AA1E1Q DEF. AIDED OPTD NORMAL
H2.Op.ge
005FN1.
neral
=6D02+L2. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-B 86F-2 TRIP TRIP/
86F2 (12,18) FPSM_7SD522 T
R2 K17 6GGIO3.I RELAY OPTD NORMAL
AA1E1Q
nd11.stV
005FN1.
al
=6D02+L2. 7SD522 : SPARK 380kV BSP CKT-B 86BU-2 TRIP/
LD0.SP1 86BU2 (12,18)FPSM_7SD522 T
R2 J1 AA1E1Q LOCKOUT RELAY OPTD NORMAL
6GGIO3.I
005FN2.
nd9.stVal
=6D02+L2. MICOM System. SPARK 380kV BSP CKT-B 86F-1 TRIP TRIP/
86F1 (6,8) FPFM_P546 T
R1 P546 : E2 OptGGIO
AA1E1Q RELAY OPTD NORMAL
1.Ind19.s
005FN2.
=6D02+L2. MICOM System. tVal SPARK 380kV BSP CKT-B 86BU-1 TRIP/
86BU1 (6,8) FPFM_P546 T
R1 P546 : E4 OptGGIO
AA1E1Q LOCKOUT RELAY OPTD NORMAL
1.Ind18.s
005FN1.
=6D02+L2. tVal
LD0.SP1 SPARK 380kV BSP CKT-B FPSM INTER TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 6GGIO2.I
AA1E1Q TRIP SEND NORMAL
nd13.stV
005FN2.
=6D02+L2. al
System. SPARK 380kV BSP CKT-B FPSM TRIP/
INTERNAL INTERNAL FPSM_7SD522 T
R2 GosGGI
AA1E1Q INTERTRIP RECEIVE NORMAL
O2.Ind18
005FN1.
.stVal
=6D02+L2. 7SD522 : LD0.SP1 SPARK 380kV BSP CKT-B 85R-2 INTER TRIP/
85R2 (A1,A3) FPSM_7SD522 T
R2 J3 6GGIO3.I
AA1E1Q TRIP RECEIVE OPTD NORMAL
nd02.stV
005FN2.
=6D02+L2. MICOM System. al SPARK 380kV BSP CKT-B 85R-1 INTER TRIP/
85R1 (1,3) FPFM_P546 T
R1 P546 : E6 OptGGIO
AA1E1Q TRIP RECEIVE OPTD NORMAL
1.Ind10.s
005FN2.
=6D02+L2. tVal
System. SPARK 380kV BSP CKT-B FPFM INTER TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI
AA1E1Q TRIP SEND NORMAL
O2.Ind24
005FN2.
=6D02+L2. .stVal
System. SPARK 380kV BSP CKT-B FPFM TRIP/
INTERNAL INTERNAL FPFM_P546 T
R1 GosGGI INTERTRIP RECEIVE NORMAL
AA1E1Q
O2.Ind17
000KF1.L
.stVal QFHT (21,22),
=6D02+L2. 7SD522 : CB A602 FPSM PROTECTION PANEL ALARM/
D0.SP16 FPSM_7SD522 NT
R2 P17 QFPS (21,22) AC SUPPLY FAIL NORMAL
GGIO3.In
d4.stVal
=6D02+L2. 7SD522 : 74IO-2 (1,3), CB A602 FPSM PROTECTION PANEL ALARM/
FPSM_7SD522 NT
R2 J4 F222 (21,22) IN/OUT DC SUPPLY FAIL NORMAL
SPARK
SS#3 E02
SPARK
380kV BSP ALARM/
ED-682330, Rev-2 4034 PAGE 25 OF 104
CKT-B NORMAL
NON
URGENT
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
SPARK COD TRE
=6D02+L2. 7SD522 : 74IND-2 (1,3), CB A602 FPSM PROTECTION PANEL ALARM/ SS#3 E02 E
FPSM_7SD522 NT SPARK
R2 J6 F223 (21,22) INDICATION DC SUPPLY FAIL NORMAL
380kV BSP ALARM/
4034
CKT-B NORMAL
=6D02+L2. MICOM 74IO1 (3,11), CB A602 FPFM PROTECTION PANEL ALARM/ NON
FPFM_P546 NT
R1 P546 : E8 QFR2 (21,22) IN/OUT DC SUPPLY FAIL NORMAL URGENT
ALARM
74IND1
=6D02+L2. MICOM CB A602 FPFM PROTECTION PANEL ALARM/
(3,11), QFR3 FPFM_P546 NT
R1 P546 : E10 INDICATION DC SUPPLY FAIL NORMAL
AA1E1Q (21,22)
000KF1.L
=6D02+L2. MICOM QFHT (21,22), CB A602 FPFM PROTECTION PANEL AC ALARM/
D0.SP16 FPFM_P546 NT
R1 P546 : C2 QFPS (21,22) SUPPLY FAIL NORMAL
GGIO3.In
AA1E1Q
d8.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 FUSE ALARM/
=E02+LCC INTERNAL D0.SP16 INTERNAL BCU_6MD85_SIEMENS
NT
FAIL ALARM NORMAL
GGIO1.In
AA1E1Q
d7.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 ALARM/
=E02+LCC X18 (5,6) D0.SCS S1 :X18 (5,6)
BCU_6MD85_SIEMENS
NT
ISOLATOR OPEN NORMAL SPARK
WI4.Pos.
AA1E1Q
stVal SS#3 E02
005KF1.L
SPARK 380kV BSP CKT-B VT-601 ALARM/ SPARK FAILED /
=E02+LCC X5:66 D0.SP16 KT6 (6,8) BCU_6MD85_SIEMENS
NT 4035
ISOLATOR INCOMPLETE NORMAL 380kV BSP NORMAL
GGIO2.In
AA1E1Q CKT-B VT
d11.stVal
005KF1.L
SPARK 380kV BSP CKT-B VT-601 MAIN ALARM/ FAIL
=E02+LCC X5:60 D0.SP16 K17(31,32) BCU_6MD85_SIEMENS
NT
MCB TRIP / OFF NORMAL
GGIO2.In
AA1E1Q
d15.stVal
005KF1.L
K102(R,Y,B) SPARK 380kV BSP CKT-B VT-601 ALARM/
=E02+LCC X5:61 D0.SP16 BCU_6MD85_SIEMENS
NT
(13,14) BRANCH MCB TRIP / OFF NORMAL
GGIO2.In
d16.stVal
SPARK 115/33kV SUBSTATION#3 E02 115/33KV TRANSFORMER ALARMS:
AA1E1Q
003KF2.L
T602 MAIN TANK OIL LEVEL LOW ALARM/
=6T2+LCP X3:23, 24 D1.DIOG 71Q1 (3,4) IOM_A2-P849 NT
AA1E1Q ALARM NORMAL
GIO1.Ind
003FN1.
011.stVal
LD0.SP1 T602 MAIN TANK OIL LEVEL HIGH ALARM/
=6T2+LCP X3:25, 26 71Q1 (5,6) IOM_A2-P849 NT
6GGIO3.I ALARM NORMAL
nd15.stV
al T602 MAIN TANK PRESSURE RELIEF ALARM/
=6T2+LCP X3:7, 8 63P1 (11,14) IOM_A2-P849 NT
DEVICE (63P1) ALARM NORMAL

T602 MAIN TANK PRESSURE RELIEF ALARM/


=6T2+LCP X3:9, 10 63P2 (11,14) IOM_A2-P849 NT
DEVICE (63P2) ALARM NORMAL

T602 OLTC PRESSURE RELIEF DEVICE ALARM/


=6T2+LCP X3:11, 12 63P3 (11,14) IOM_A2-P849 NT
(63P3) ALARM NORMAL

T602 OLTC PRESSURE RELIEF DEVICE ALARM/


=6T2+LCP X3:13, 14 63P4 (11,14) IOM_A2-P849 NT
(63P4) ALARM NORMAL

T602 PRESSURE RELIEF DEVICE ALARM/


=6T2+LCP X3:15, 16 63P5 (11,14) IOM_A2-P849 NT
(63P5) ALARM (CHAMBER-A) NORMAL

T602 PRESSURE RELIEF DEVICE ALARM/


=6T2+LCP X3:17, 18 63P6 (11,14) IOM_A2-P849 NT
(63P6) ALARM (CHAMBER-B) NORMAL

T602 PRESSURE RELIEF DEVICE ALARM/


=6T2+LCP X3:19, 20 63P7 (11,14) IOM_A2-P849 NT
(63P7) ALARM (CHAMBER-C) NORMAL

ALARM/
=6T2+LCP X5:**, ** -- IOM_A2-P849 NT T602 FIRE PROTECTION FAULTY
NORMAL

Q1, Q2 ALARM/
+6T2+AVC X6:4 COMM-BCU NT T602 AVC RELAY DC MCB FAIL
(21,22) NORMAL

ALARM/
+6T2+AVC X6:2 K90F (4,8) COMM-BCU NT T602 AVC RELAY FAULTY
NORMAL

T602 AVC RELAY FUNCTION ALARM/


+6T2+AVC INTERNAL INTERNAL 90-6RTV NT
MONITORING FAIL NORMAL

T602 AVC RELAY SAS COMM. BOTH ALARM/


+6T2+AVC INTERNAL INTERNAL 90-6RTV NT
AA1E1Q CHANNELS FAIL NORMAL
003FN1.
LD0.SP1 ALARM/
=6T2+LCP X3:31, 32 71Q2 (3,4) IOM_A2-P849 NT T602 OLTC OIL LEVEL LOW ALARM
6GGIO3.I NORMAL
AA1E1Q
nd16.stV
003FN1.
al ALARM/
=6T2+LCP X3:33, 34 LD0.SP1 71Q2 (5,6) IOM_A2-P849 NT T602 OLTC OIL LEVEL HIGH ALARM
NORMAL
6GGIO2.I
nd.stVal SPARK
ALARM/ SS#3 T602
+6T2+R1 INTERNAL INTERNAL FPFM-P643 NT T602 SET-1 NEUTRAL CURRENT ALARM
NORMAL TRANSFO
ALARM/
RMER 4036
NORMAL
NON
URGENT
ED-682330, Rev-2
ALARM PAGE 26 OF 104
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI TRO
PANEL SOURCE ADDRE T/ TEXT SPARK
SCADA TEXT ADDR E OP rks
BER DESCRIPTION E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX SS#3 T602
LITRA INDEX ID
ESS ARM TYPE ST CEN
TIFIER TRANSFO
ALARM/ COD TRE
RMER 4036
NORMAL E
T602 SET-1 SENSITIVE EARTH FAULT ALARM/ NON
+6T2+R1 INTERNAL INTERNAL FPFM-P643 NT
PROTECTION OPTD NORMAL URGENT
ALARM
ALARM/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 NT T602 SET-2 NEUTRAL CURRENT ALARM
NORMAL

T602 SET-2 SENSITIVE EARTH FAULT ALARM/


+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 NT
PROTECTION OPTD NORMAL

ALARM/
=6T2+LCP X3 (53,54) 45M: (19, 20) DGA NT T602 GAS ANALYZER SERVICE ALARM.
NORMAL

ALARM/
=6T2+LCP X3 (55,56) 45M: (22, 24) COMM-BCU NT T602 GAS ANALYZER FAULTY
NORMAL

T602 GAS ANALYZER DC SUPPLY ALARM/


=6T2+LCP X7:37, 38 Q18 (21,22) COMM-BCU NT
FAIL / DC MCB TRIP NORMAL

T602 GAS ANALYZER (F.O) ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
COMMUNICATION FAIL NORMAL

T602 GAS ANALYZER H2 HIGH STAGE- ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
1 ALARM NORMAL

T602 GAS ANALYZER H2 HIGH STAGE- ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
2 ALARM NORMAL

T602 GAS ANALYZER CO HIGH STAGE- ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
1 ALARM NORMAL

T602 GAS ANALYZER CO HIGH STAGE- ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
2 ALARM NORMAL

T602 GAS ANALYZER MOISTURE HIGH ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
ALARM NORMAL

T602 GAS ANALYZER H2O HIGH ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
STAGE-1 ALARM NORMAL

T602 GAS ANALYZER H2O HIGH ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
STAGE-2 ALARM NORMAL

T602 GAS ANALYZER GENERAL HIGH ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
STAGE-1 ALARM NORMAL

T602 GAS ANALYZER GENERAL HIGH ALARM/


=6T2+LCP INTERNAL INTERNAL DGA NT
STAGE-2 ALARM NORMAL
AA1E1Q
003FN1.
T602 MAIN TRF TANK GAS DETECTOR ALARM/
=6T2+LCP X3:37, 38 LD0.SP1 63D (1,2) IOM_A2-P849 NT
ALARM NORMAL
6GGIO2.I
AA1E1Q
nd2.stVal
000KF1.L
IO BOX 87T1 ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT T602 SET-1 87T-1 PROT. RELAY FAULTY
(A2:G16) (J11,J12) NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
IO BOX T602 SET-1 87T-1 PROT. DC SUPPLY ALARM/
+6T2+R1 IOM_A2-P849
D0.SP16 QFR1 (21,22), RLA (3,11) NT
(A2:G10) FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d10.stVal
003FN1.
T602 SET-1 87T-1 PROT. RELAY UNDER ALARM /
+6T2+R1 87T1:F4 LD0.SP1 TS1 (13,14) FPFM-P643 NT
TEST NORMAL
6GGIO1.I
AA1E1Q
nd5.stVal
000KF1.L
ALARM/
+6T2+R1 X6:1, 2 D0.SP16 A2 (N11,N12) COMM-BCU NT T602 I/O BOX RELAY FAULTY
NORMAL
GGIO4.In
AA1E1Q
d9.stVal
000KF1.L
T602 I/O BOX DC SUPPLY FAIL / DC ALARM/
+6T2+R1 X6:1, 3 D0.SP16 QFR2 (21,22), RLB
COMM-BCU
(3,11) NT SPARK
MCB TRIP NORMAL
GGIO4.In
AA1E1Q SS#3 T602
d10.stVal
000KF1.L TRANSFO
87T2 (B7, ALARM/ FAULTY/
+6T2+R2 X6:1,2 D0.SP16 COMM-BCU NT T602 SET-2 87T-2 PROT. RELAY FAULTY RMER 4037
B10) NORMAL NORMAL
GGIO4.In
AA1E1Q PROT.
d13.stVal
000KF1.L FLTY
27M2 (1,3), T602 SET-2 87T-2 PROT. RELAY DC ALARM/ ALARM
+6T2+R2 X6:1,3 D0.SP16 COMM-BCU NT
F221 (2,22) SUPPLY FAIL / DC MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d14.stVal
000KF1.L
TS87T-2A/ T602 SET-2 87T-2 PROT. RELAY UNDER ALARM /
+6T2+R2 87T2:B12 D0.SP16 FPSM-7UT85 NT
AA1E1Q 2B/2C (17,18)
GGIO5.In
TEST NORMAL
003FN1.
d4.stVal
LD0.SP1 T602 SET-1 87T-1 PROT.RELAY SAS ALARM/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I
AA1E1Q COMM. CH-1 & CH-2 FAIL NORMAL
nd15.stV
003FN1.
al
LD0.SP1 T602 I/O BOX SAS COMM. CH-1 & CH-2 ALARM/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 NT
6GGIO1.I FAIL NORMAL
nd15.stV
al

ED-682330, Rev-2 PAGE 27 OF 104


SPARK
SS#3 T602
TRANSFO
FAULTY/
RMER 4037
NORMAL
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
PROT. DOC. NO: ED
FLTY
ALARM
SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN1. COD TRE
LD0.SP1 T602 SET-2 87T-2 PROT.RELAY SAS ALARM/ E
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 NT
6GGIO1.I COMM. CH-1 & CH-2 FAIL NORMAL
AA1E1Q
nd16.stV
003KF2.L
al
=6T2+OLT Q8 (Axb1, ALARM/
X7:17,18 D1.DIOG 90-6RTV NT T602 OLTC MOTOR SUPPLY FAIL
C AXc1) NORMAL
GIO1.Ind
AA1E1Q
011.stVal
003KF2.L
=6T2+OLT ALARM/
D1.DIOG F1 (A1, A2) 90-6RTV NT T602 OLTC CONTROL DC SUPPLY FAIL
C AA1E1Q NORMAL
GIO1.Ind
003KF2.L
017.stVal
D1.GEN ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC OUT OF STEP ALARM
GGIO.Al
AA1E1Q NORMAL
m05.stVa
003KF2.L
l
D1.GEN ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC BLOCKED
GGIO.Al
AA1E1Q NORMAL
m01.stVa
003KF2.L
l
D1.ATCC ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC U/V ALARM
1.BlkMin NORMAL
AA1E1Q
Vol.gener
003KF2.L
al ALARM/
+6T2+AVC INTERNAL D1.ATCC INTERNAL 90-6RTV NT T602 AVC O/C ALARM
NORMAL
1.BlkAOv
.stVal
ALARM/
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT T602 AVC O/V ALARM
NORMAL

ALARM/
+6T2+AVC X6:4 Q1 (21,22) COMM-BCU NT T602 AVC CONTROL DC SUPPLY FAIL
AA1E1Q NORMAL
003KF2.L
RTV- D1.GEN QFVT ALARM/
+6T2+AVC 90-6RTV NT T602 AVC VOLTAGE SUPPLY FAIL
90:H10 GGIO.Al (221,222) NORMAL
m06.stVa
l Q19 (AXc1, ALARM/
=6T2+LCP XX:** IOM_A2-P849 NT T602 SPARE COOLING FAN MCB TRIP
AXb1) NORMAL

X7:11, 12, Q5/Q6/Q7 ALARM/


=6T2+LCP IOM_A2-P849 NT T602 MAIN COOLING FAN MCB TRIP
13, 14 (AXc1, AXb1) NORMAL
SPARK
Q2 (AXc1, T602 COOLING FANS STAND BY AC ALARM/ SS#3 T602
=6T2+LCP X7:3, 4 IOM_A2-P849 NT
AXb1) POWER SUPPLY FAIL NORMAL TRANSFO
ALARM/
RMER 4038
NORMAL
Q1 (AXc1, T602 COOLING FANS MAIN AC POWER ALARM/ NON
=6T2+LCP X7:1, 2 IOM_A2-P849 NT
AXb1) SUPPLY FAIL NORMAL URGENT
AA1E1Q ALARM
003KF2.L
=6T2+OLT ALARM/
D1.DIOG KTCIC (4,8) IOM_A2-P849 NT T602 OLTC INCOMPLETE
C NORMAL
GIO1.Ind
023.stVal
T602 COOLING FANS CONTROL DC ALARM/
=6T2+LCP X7:33, 34 Q16 (11, 12) IOM_A2-P849 NT
SUPPLY FAIL NORMAL

ALARM/
=6T2+LCP X7:9, 10 27A (14, 11) IOM_A2-P849 NT T602 MK PANEL AC SUPPLY FAIL
NORMAL

=6T2+OLT ALARM/
1KMSF (4,8) IOM_A2-P849 NT T602 OLTC PANEL AC SUPPLY FAIL
C NORMAL
AA1E1Q
000KF1.L
QFPS (21,22), ALARM/
+6T2+AVC X6:7 D0.SP16 90-6RTV NT T602 AVC PANEL AC SUPPLY FAIL
QFHT (21,22) NORMAL
GGIO6.In
AA1E1Q
d6.stVal
000KF1.L T602 PROTECTION-1 PANEL
IO BOX QFR4 (21,22), ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT INDICATION DC SUPPLY FAIL / MCB
(A2:G14) RLD (3,11) NORMAL
GGIO4.In
AA1E1Q TRIP
d12.stVal
000KF1.L
IO BOX QFR3 (21,22), T602 PROTECTION-1 PANEL IN/OUT DC ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT
(A2:G12) RLC (3,11) SUPPLY FAIL / MCB TRIP NORMAL
GGIO4.In
AA1E1Q
d12.stVal
000KF1.L
IO BOX QFPS (21,22), T602 PROTECTION-1 PANEL AC MCB ALARM/
+6T2+R1 D0.SP16 IOM_A2-P849 NT
(A2:G8) QFHT (21,22) TRIP NORMAL
GGIO4.In
d12.stVal T602 PROTECTION-2 PANEL
F223 (21,22), ALARM/
+6T2+R2 87T2:B13 FPSM-7UT85 NT INDICATION DC SUPPLY FAIL / MCB
27IND (1,3) NORMAL
TRIP

F222 (21,22), T602 PROTECTION-2 PANEL IN/OUT DC ALARM/


+6T2+R2 87T2:B14 FPSM-7UT85 NT
27M2/IO (1,3) SUPPLY FAIL / MCB TRIP NORMAL
AA1E1Q
000KF1.L
F101 (21,22), T602 PROTECTION-2 PANEL AC MCB ALARM/
+6T2+R2 87T2:A10 D0.SP16 FPSM-7UT85 NT
F102 (21,22) TRIP NORMAL
GGIO4.In
AA1E1Q
d16.stVal
003FN1.
T602 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd1.stVal
003FN1.
T602 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.Y OPTD NORMAL
6GGIO1.I
nd2.stVal

ED-682330, Rev-2 PAGE 28 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q COD TRE
003FN1. E
T602 SET-1 87T-1 DIFF. PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH.B OPTD NORMAL
6GGIO1.I
AA1E1Q
nd3.stVal
003FN1.
TRIP/
+6T2+R1 87T1:D2 LD0.SP1 86T-1(5,7) FPFM-P643 T T602 86T-1 LOCKOUT RELAYOPTD.
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd6.stVal
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.R OPTD NORMAL
1.Op.phs
003FN2.
A
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.Y OPTD NORMAL
1.Op.phs
003FN2.
B
Protectio T602 SET-2 87T-2 DIFF. PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.DifPDIF
AA1E1Q PH.B OPTD NORMAL
1.Op.phs
003FN2.
C
System. TRIP/
+6T2+R2 87T2:D10 86T-2 (22,28) FPSM-7UT85 T T602 86T-2 LOCKOUT RELAYOPTD.
OptGGIO NORMAL
AA1E1Q
1.Ind15.s
003FN1.
tVal T602 SET-1 LV 87REF-1 RESTRICTED TRIP/
+6T2+R1 INTERNAL LD0.REF INTERNAL FPFM-P643 T
EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
AA1E1Q
p.general
003FN1.
T602 SET-1 SBEF STAND BY EARTH TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
FAULT PROTECTION OPTD. NORMAL
6GGIO1.I
AA1E1Q
nd6.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-R OPTD NORMAL
6GGIO1.I
AA1E1Q
nd7.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
PH-Y OPTD NORMAL
6GGIO1.I
AA1E1Q
nd8.stVal
003FN1.
T602 SET-1 HV 50P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL LD0.SP1 INTERNAL FPFM-P643 T
AA1E1Q PH-B OPTD NORMAL
6GGIO1.I
003FN1.
nd9.stVal
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd10.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd11.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51P O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 50NP E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 HV 51NP E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-R OPTD NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/ SPARK
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-Y OPTD NORMAL SS#3 T602
nd13.stV TRANSFO OPERATE /
003FN1. 4039
al RMER NORMAL
LD0.SP1 T602 SET-1 LV 51S O/C PROTECTION TRIP/ PROT
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q PH-B OPTD NORMAL OPTD
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 50NS E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN1.
al
LD0.SP1 T602 SET-1 LV 51NS E/F PROTECTION TRIP/
+6T2+R1 INTERNAL INTERNAL FPFM-P643 T
6GGIO1.I
AA1E1Q OPTD. NORMAL
nd13.stV
003FN2.
al
Protectio T602 SET-2 LV 87REF-2 RESTRICTED TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85
n.LzrLvw
AA1E1Q EARTH FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 SBEF STAND BY EARTH TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q FAULT PROTECTION OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw PH-R OPTD NORMAL
PDIF2.O
p.general

ED-682330, Rev-2 PAGE 29 OF 104


TRANSFO OPERATE /
4039
RMER NORMAL
PROT
OPTD

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN2. COD TRE
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/ E
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51P O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-B OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 50NP E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 HV 51NP E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q OPTD. NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-R OPTD NORMAL
PDIF2.O
003FN2.
p.general
Protectio T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.LzrLvw
AA1E1Q PH-Y OPTD NORMAL
PDIF2.O
003FN2.
p.general
System. T602 SET-2 LV 50S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI
AA1E1Q PH-B OPTD NORMAL
O2.Ind2.s
003FN2.
tVal
System. T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
GosGGI PH-R OPTD NORMAL
O2.Ind3.s
No
tVal T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL siginal in INTERNAL FPSM-7UT85 T
AA1E1Q PH-Y OPTD NORMAL
scheme
003FN2.
Protectio T602 SET-2 LV 51S O/C PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q PH-B OPTD NORMAL
PTOC1.
003FN2.
Op.phsA
Protectio T602 SET-2 LV 50NS E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2
AA1E1Q OPTD. NORMAL
PTOC1.
003FN2.
Op.phsB
Protectio T602 SET-2 LV 51NS E/F PROTECTION TRIP/
+6T2+R2 INTERNAL INTERNAL FPSM-7UT85 T
n.OcpEl2 OPTD. NORMAL
AA1E1Q
PTOC1.
003FN1.
Op.phsC TRIP/
+6T2+R1 87T1:D4 LD0.SP1 94T-1(1,3) FPFM-P643 T T602 94T-1 TRIP RELAY OPTD
AA1E1Q NORMAL
6GGIO2.I
003FN2.
nd8.stVal
System. TRIP/
+6T2+R2 87T2:D14 94T-2 (A2,A4) FPSM-7UT85 T T602 94T-2 TRIP RELAY OPTD
OptGGIO NORMAL
1.Ind16.s
tVal T602 MAIN TANK PRESSURE RELIEF TRIP/
=6T2+LCP X4:7, 8 63P1 (21,24) IOM_A2-P849 T
DEVICE (63P1) OPTD. NORMAL

T602 MAIN TANK PRESSURE RELIEF TRIP/


=6T2+LCP X4:9, 10 63P2 (21,24) IOM_A2-P849 T
DEVICE (63P2) OPTD. NORMAL

T602 OLTC PRESSURE RELIEF DEVICE TRIP/


=6T2+LCP X4:11, 12 63P3 (21,24) IOM_A2-P849 T
(63P3) OPTD. NORMAL

T602 OLTC PRESSURE RELIEF DEVICE TRIP/


=6T2+LCP X4:13, 14 63P4 (21,24) IOM_A2-P849 T
(63P4) OPTD. NORMAL

T602 PRESSURE RELIEF DEVICE TRIP/


=6T2+LCP X4:15, 16 63P5 (21,24) IOM_A2-P849 T
(63P5) OPTD. (CHAMBER-A) NORMAL

T602 PRESSURE RELIEF DEVICE TRIP/


=6T2+LCP X4:17, 18 63P6 (21,24) IOM_A2-P849 T SPARK
(63P6) OPTD. (CHAMBER-B) NORMAL
SS#3 T602
TRANSFO
T602 PRESSURE RELIEF DEVICE TRIP/ OPERATE/
=6T2+LCP X4:19, 20 63P7 (21,24) IOM_A2-P849 T RMER 4040
AA1E1Q (63P7) OPTD. (CHAMBER-C) NORMAL NORMAL
MECH.
003FN2. PROT.
System. T602 MAIN TANK OIL TEMPERATURE TRIP/ OPTD
=6T2+LCP X4:31, 32 26Q-2(41,44) IOM_A2-P849 T
OptGGIO HIGH STAGE-2 OPTD. NORMAL
1.Ind11.s
tVal T602 OLTC PROTECTIVE RELAY TRIP/
=6T2+LCP X4:3, 4 63PR1 (3,4) IOM_A2-P849 T
AA1E1Q STAGE-2 OPTD. NORMAL
003FN2.
System. T602 MAIN TANK BUCHHOLZ SATGE-2 TRIP/
=6T2+LCP X4:1, 2 63B (1, 2) IOM_A2-P849 T
OptGGIO OPTD NORMAL
1.Ind2.st
Val

ED-682330, Rev-2 PAGE 30 OF 104


SPARK
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SS#3 T602 DOC. NO: ED
TRANSFO
OPERATE/
RMER 4040
SAS POINT LIST NORMAL REV-2
MECH.
PROT.
115kV ALARMS OPTD

CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT E NAM DEVI OP TRO rks
BER ADDR
TB. NO SS/IDEN NT DESCRIPTION
INDEX LITRA INDEX ID E/AL CE TE L LDC
ESS ARM TYPE ST CEN
TIFIER
AA1E1Q
003FN2. COD TRE
System. T602 HV WINDING TEMPERATURE TRIP/ E
=6T2+LCP X4:27, 28 49W1 (41,44) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind12.s
003FN2.
tVal
System. T602 LV WINDING TEMPERATURE TRIP/
=6T2+LCP X4:29, 30 49W2 (6,8) IOM_A2-P849 T
OptGGIO
AA1E1Q HIGH STAGE-2 OPTD. NORMAL
1.Ind16.s
003FN2.
tVal
System. TRIP/
=6T2+LCP XX: ** R1 (7,8) IOM_A2-P849 T T602 RAPID PRESSURE OPTD. SPARK
OptGGIO
AA1E1Q NORMAL
1.Ind7.st SS#3 T602
003FN1.
Val TRANSFO
LD0.SP1 FPO:X5 FAULTY/ OPERATE /
=6T2+LCP X5:65, 66 IOM_A2-P849 NT T602 FIRE PROTCTION OPTD RMER 4041
6GGIO3.I (65,66) NORMAL NORMAL
AA1E1Q FIRE
SPARK
nd12.stV
003FN1. PROT
SS#3 T602
al
LD0.SP1 T602 MAIN TANK OIL TEMPERATURE ALARM/ OPTD
TRANSFO ALARM
=6T2+LCP X3:49, 50 26Q (31,34) IOM_A2-P849 NT 4042
6GGIO3.I HIGH STAGE-1 ALARM NORMAL RMER OIL /NORMAL
nd11.stV TEMP ST1
AA1E1Q SPARK
al ALARM
003FN1. SS#3 T602
T602 MAIN TANK BUCHHOLZ STAGE-1 ALARM/ ALARM/
=6T2+LCP X3:1, 2 LD0.SP1 63B (3,4) IOM_A2-P849 NT TRANSFO 4043
ALARM NORMAL NORMAL
6GGIO3.I
AA1E1Q RMER
nd2.stVal
003FN1. BUCH ST1
LD0.SP1 T602 HV WINDING TEMPERATURE ALARM/
=6T2+LCP X3:45, 46 49W1 (31,34) IOM_A2-P849 NT
6GGIO3.I
AA1E1Q HIGH STAGE-1 ALARM NORMAL
nd12.stV
003FN1.
al
LD0.SP1 T602 LV WINDING TEMPERATURE ALARM/
=6T2+LCP X3:47, 48 49W2 (31,34) IOM_A2-P849 NT
6GGIO3.I HIGH STAGE-1 ALARM NORMAL
nd13.stV
al T602 FIBER OPTIC WINDING TEMP. ALARM/
=6T2+LCP CH1 (HV-U) CH1 (HV-U) FOM NT
MONITOR (FOWT) CH1 (HV-U) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH2 (HV-V) CH2 (HV-V) FOM NT
MONITOR (FOWT) CH2 (HV-V) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH3 (HV-V) CH3 (HV-V) FOM NT
MONITOR (FOWT) CH3 (HV-V) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/ SPARK


=6T2+LCP CH4 (HV-V) CH4 (HV-V) FOM NT
MONITOR (FOWT) CH4 (HV-V) NORMAL SS#3 T602
TRANSFO OPERATED
4044
RMER / NORMAL
CH5 (HV- T602 FIBER OPTIC WINDING TEMP. ALARM/ WDG
=6T2+LCP CH5 (HV-W) FOM NT
W) MONITOR (FOWT) CH5 (HV-W) NORMAL TEMP ST1

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH6 (HV-U) CH6 (HV-U) FOM NT
MONITOR (FOWT) CH6 (LV-U) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH7 (HV-V) CH7 (HV-V) FOM NT
MONITOR (FOWT) CH7 (LV-V) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH8 (HV-V) CH8 (HV-V) FOM NT
MONITOR (FOWT) CH8 (LV-V) NORMAL

T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH9 (HV-V) CH9 (HV-V) FOM NT
MONITOR (FOWT) CH9 (LV-V) NORMAL

CH10 (HV- T602 FIBER OPTIC WINDING TEMP. ALARM/


=6T2+LCP CH10 (HV-W) FOM NT
W) MONITOR (FOWT) CH10 (LV-W) NORMAL

ALARM/
=E02+LCC -- INTERNAL
BCU_6MD85_SIEMENS
NT T602 VT-602 FUSE FAIL ALARM
NORMAL

ALARM/
=E02+LCC X19 (5,6) S1 :X19 (5,6)
BCU_6MD85_SIEMENS
NT T602 VT-602 ISOLATOR OPEN
NORMAL

ALARM/
=E02+LCC X5:66 KT6A (6,8)
BCU_6MD85_SIEMENS
NT T602 VT-602 ISOLATOR INCOMPLETE
NORMAL

ALARM/
=E02+LCC X5:64 K20 (31,32)
BCU_6MD85_SIEMENS
NT T602 VT-602 MAIN MCB TRIP / OFF SPARK
NORMAL
SS#3 T602 FAILED /
4045
TRANSFO NORMAL
K103 (R,Y,B) ALARM/ RMER VT
=E02+LCC X5:65 BCU_6MD85_SIEMENS
NT T602 VT-602 BRANCH MCB TRIP / OFF
(13,14) NORMAL

ALARM/
=BH05/IC INTERNAL INTERNAL BCPU / REF 620 T602 LV VT FUSE FAIL ALARM
NORMAL
Q411,Q412,Q
413,Q421,Q4 ALARM/
=BH05/IC X7:23 BCPU / REF 620 T602 LV VT MCB TRIP
22,Q423,Q42 NORMAL
4(21,22)
ALARM/
=BH05/IC INTERNAL AA1E1Q INTERNAL BCPU / REF 620 T602 LV VT-304 RACK OUT
003KF2.L NORMAL
D1.GEN
=6T2+OLT GGIO.Al LOCAL/
-- S132A (9,10) 90-6RTV NT T602 OLTC CONTROL MODE IN LOCAL
C m11.stVa REMOTE SPARK
l/ SS#3 T602
Ind021.st TRANSFO LOCAL /
Val 4046
ED-682330, Rev-2 RMER TAP REMOTE PAGE 31 OF 104

CHANGER
REMOTE
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED

SAS POINT LIST REV-2

115kV ALARMS
CONTROL CLOSE
FULL RECEIVED AT
HMI / ALARM / EVENT TEXT IEC SYSTEM OP LOOPTES
HARDWIR IEC TYP CONTROL CENTRE TY POIN EN
DEVICE 101/1 DATA T
SOURCE ED 61850 E P T LO CON Rema
NAME/NUM IED NAME 04 NAM DEVI OP TRO
PANEL SOURCE ADDRE T/ TEXT SCADA TEXT ADDR E rks
BER DESCRIPTION E/AL CE TE L LDC
TB. NO SS/IDEN NT INDEX LITRA INDEX ID
ESS ARM TYPE ST CEN
TIFIER SPARK
SS#3 T602 COD TRE
T602 SAS CONTROL MODE AUTHORITY LOCAL/ TRANSFO LOCAL / E
+6T2+AVC INTERNAL INTERNAL 90-6RTV NT 4046
SET TO SAS/ERCC REMOTE RMER TAP REMOTE
AA1E1Q CHANGER
003KF2.L
LOCAL/ REMOTE
+6T2+AVC RTV-90:I3 D1.DIOG 1KOL (4, 8) 90-6RTV NT T602 AVC CONTROL MODE IN LOCAL
REMOTE
GIO1.Ind
006.stVal
SPARE ADDRESS:

SPARE ADDRESS (FROM) 4047

SPARE ADDRESS (TO) 4056

ED-682330, Rev-2 PAGE 32 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

115KV INDICATIONS

ED-682330, Rev-2 PAGE 33 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED-682330

SAS POINT LIST REV-2

115kV INDICATION

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
DEVICE IEC 101/104 TYPE
SOURCE PANEL SOURCE ADDRESS/IDENTIFI IED NAME POINT LOOP REMARKS
NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO ER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE

SPARK 115/33kV SUBSTATION#3 E01 115kV (CB-A601) INDICATIONS

X10:45,46 -S1 (55,56)


=E01+LCC BCU_6MD85_SIEMENS CIRCUIT BREAKER A601 STATUS CLOSE / OPEN A601 BREAKER CLOSE / OPEN 4127
X10:5,6 -S1 (15,16)

X13:37,38 -S1 (69,70)


=E01+LCC BCU_6MD85_SIEMENS DISCONNECTOR SWITCH D601 STATUS CLOSE / OPEN D601 ISOLATOR CLOSE / OPEN 4128
X13:11,12 -S1 (29,30)

X15:49,50 -S1 (69,70)


=E01+LCC BCU_6MD85_SIEMENS DISCONNECTOR SWITCH D602 STATUS CLOSE / OPEN D602 ISOLATOR CLOSE / OPEN 4129
X15:17,18 -S1 (29,30)

X11:41,42 -S1 (67,68)


=E01+LCC BCU_6MD85_SIEMENS EARTH SWITCH K601 STATUS CLOSE / OPEN K601 EARTH SWITCH CLOSE / OPEN 4130
X11:13,14 -S1 (21,22)

X14:35,36 -S1 (67,68)


=E01+LCC BCU_6MD85_SIEMENS EARTH SWITCH K602 STATUS CLOSE / OPEN K602 EARTH SWITCH CLOSE / OPEN 4131
X14:9,10 -S1 (21,22)

X16:35,36 -S1 (67,68)


=E01+LCC BCU_6MD85_SIEMENS EARTH SWITCH K603 STATUS CLOSE / OPEN K603 EARTH SWITCH CLOSE / OPEN 4132
X16:9,10 -S1 (21,22)

X17:41,42 -S1 (67,68)


=E01+LCC BCU_6MD85_SIEMENS EARTH SWITCH K604 STATUS CLOSE / OPEN K604 EARTH SWITCH CLOSE / OPEN 4133
X17:13,14 -S1 (21,22)

X18:5,6 -S1 (5,6)


=E01+LCC BCU_6MD85_SIEMENS VT-601 ISOLATOR STATUS CLOSE / OPEN VT601 ISOLATOR CLOSE / OPEN 4134
X18:7,8 -S1 (7,8)

X19:5,6 -S1 (5,6)


=E01+LCC BCU_6MD85_SIEMENS VT-602 ISOLATOR STATUS CLOSE / OPEN VT602 ISOLATOR CLOSE / OPEN 4135
X19:7X8 -S1 (7,8)

84AM (6, 61)


+6T1+AVC RTV-90:H4,H5 90_6RTV GT-1 AVC STATUS AUTO / MANUAL T601 AVC AUTO / MANUAL 4136
84AM (4, 40)

SPARK 115/33kV SUBSTATION#3 E02 115kV (CB-A602) INDICATIONS

X10:45,46 -S1 (55,56)


=E02+LCC BCU_6MD85_SIEMENS CIRCUIT BREAKER A602 STATUS CLOSE / OPEN A602 BREAKER CLOSE / OPEN 4137
X10:5,6 -S1 (15,16)

X13:37,38 -S1 (69,70)


=E02+LCC BCU_6MD85_SIEMENS DISCONNECTOR SWITCH D602 STATUS CLOSE / OPEN D602 ISOLATOR CLOSE / OPEN 4138
X13:11,12 -S1 (29,30)

X15:49,50 -S1 (69,70)


=E02+LCC BCU_6MD85_SIEMENS DISCONNECTOR SWITCH D602 STATUS CLOSE / OPEN D602 ISOLATOR CLOSE / OPEN 4139
X15:17,18 -S1 (29,30)

X11:41,42 -S1 (67,68)


=E02+LCC BCU_6MD85_SIEMENS EARTH SWITCH K605 STATUS CLOSE / OPEN K601 EARTH SWITCH CLOSE / OPEN 4140
X11:13,14 -S1 (21,22)

X14:35,36 -S1 (67,68)


=E02+LCC BCU_6MD85_SIEMENS EARTH SWITCH K606 STATUS CLOSE / OPEN K602 EARTH SWITCH CLOSE / OPEN 4141
X14:9,10 -S1 (21,22)

X16:35,36 -S1 (67,68)


=E02+LCC BCU_6MD85_SIEMENS EARTH SWITCH K607 STATUS CLOSE / OPEN K603 EARTH SWITCH CLOSE / OPEN 4142
X16:9,10 -S1 (21,22)

X17:41,42 -S1 (67,68)


=E02+LCC BCU_6MD85_SIEMENS EARTH SWITCH K608 STATUS CLOSE / OPEN K604 EARTH SWITCH CLOSE / OPEN 4143
X17:13,14 -S1 (21,22)

X18:5,6 -S1 (5,6)


=E02+LCC BCU_6MD85_SIEMENS VT-602 ISOLATOR STATUS CLOSE / OPEN VT602 ISOLATOR CLOSE / OPEN 4144
X18:7,8 -S1 (7,8)

X19:5,6 -S1 (5,6)


=E02+LCC BCU_6MD85_SIEMENS VT-602 ISOLATOR STATUS CLOSE / OPEN VT602 ISOLATOR CLOSE / OPEN 4145
X19:7X8 -S1 (7,8)

84AM (6, 61)


+6T2+AVC RTV-90:H4,H5 90_6RTV GT-2 AVC STATUS AUTO / MANUAL T602 AVC AUTO / MANUAL 4146
84AM (4, 40)

STATION/PCC AUTHORITY

SAS/ERCC INTERNAL INTERNAL STATION/PCC AUTHORITY SAS/PCC STATION/PCC AUTHORITY SAS/PCC 4147

SPARE ADDRESS:

SPARE ADDRESS (FROM) 4148

SPARE ADDRESS (TO) 4152

ED-682330, Rev-2 PAGE 34 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

115KV COMMAND

ED-682330, Rev-2 PAGE 35 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED-682330

SAS POINT LIST REV-2

115kV COMMANDS

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
SOURCE DEVICE IEC 101/104 TYPE OPEN
SOURCE ADDRESS / IED NAME REMARKS
PANEL NAME/NUMBER ADDRESS ID POINT NAME/ALARM DEVICE LOOP TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX LDC
CODE TYPE CENTRE

SPARK 115/33kV SUBSTATION#3 E01 115kV (CB-A601) COMMANDS

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS CIRCUIT BREAKER A601 COMMAND EXECUTED CLOSE/OPEN A601 BREAKER CLOSE/OPEN 1001

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D601 COMMAND EXECUTED CLOSE/OPEN D601 ISOLATOR CLOSE/OPEN 1002

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D602 COMMAND EXECUTED CLOSE/OPEN D602 ISOLATOR CLOSE/OPEN 1003

K601 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K601 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH

K602 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K602 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH

K603 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K603 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH

K604 EARTH
=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K604 COMMAND CLOSE/OPEN CLOSE/OPEN UPTO HMI
SWITCH

+6T1+AVC INTERNAL INTERNAL 90_6RTV GT-1 TAP COMMAND EXECUTED RAISE / LOWER GT-1 TAP RAISE / LOWER 1004

+6T1+AVC INTERNAL INTERNAL 90_6RTV GT-1 AVC COMMAND EXECUTED AUTO / MANUAL GT-1 AVC AUTO / MANUAL 1005

SPARK 115/33kV SUBSTATION#3 E02 115kV (CB-A602) COMMANDS

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS CIRCUIT BREAKER A602 COMMAND EXECUTED CLOSE/OPEN A602 BREAKER CLOSE/OPEN 1006

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D603 COMMAND EXECUTED CLOSE/OPEN D603 ISOLATOR CLOSE/OPEN 1007

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS ISOLATOR D604 COMMAND EXECUTED CLOSE/OPEN D604 ISOLATOR CLOSE/OPEN 1008

K601 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K605 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH

K602 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K606 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH

K603 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K607 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH

K604 EARTH
=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS EARTHING SWITCH K608 COMMAND CLOSE/OPEN CLOSE / OPEN UPTO HMI
SWITCH

+6T2+AVC INTERNAL INTERNAL 90_6RTV GT-2 TAP COMMAND EXECUTED RAISE / LOWER GT-2 TAP RAISE / LOWER 1009

+6T2+AVC INTERNAL INTERNAL 90_6RTV GT-2 AVC COMMAND EXECUTED AUTO / MANUAL GT-2 AVC AUTO / MANUAL 1010

SAPRE ADDRESS:

SPARE ADDRESS (FROM) 1011

SPARE ADDRESS (TO) 1012

ED-682330, Rev-2 PAGE 36 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

115KV MEASUREMENTS

ED-682330, Rev-2 PAGE 37 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED-682330

SAS POINT LIST REV-2

115kVMEASUREMENTS
LOCAL RANGE SCADA RANGE CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE
SOURCE IEC 101/104 CONTROL SYSTEM
SOURCE ADDRESS/IDENTIFIE NAME/NUMBE IED NAME CT RATIO VT RATIO UNIT OPEN LOOP TEST REMARKS
PANEL ADDRESS DATA/DEVICE TYPE
TB R R MIN MAX MIN MAX CONTROL CENTRE LDC

SPARK 115/33kV SUBSTATION#3 E01 115kV (CB-A601) MEASUREMENT

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MW 2001 -382.4 382.4 -32767 32767

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MVAR 2002 -382.4 382.4 -32767 32767

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS - 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 KV 2003 0 138 -32767 32767

=E01+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A - A 2004 0 1920 0 32767

=6T1+AVC INTERNAL INTERNAL 90_6RTV TAP 2005 1.0 27.0 0 32767

SPARK 115/33kV SUBSTATION#3 E02 115kV (CB-A602) MEASUREMENT

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MW 2006 -382.4 382.4 -32767 32767

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 MVAR 2007 -382.4 382.4 -32767 32767

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS - 115Kv/Ѵ3 / 115/ Ѵ3 V - 115 KV 2008 0 138 -32767 32767

=E02+LCC INTERNAL INTERNAL BCU_6MD85_SIEMENS 1600-1200-1000-800/1A - A 2009 0 1920 0 32767

=6T2+AVC INTERNAL INTERNAL 90_6RTV TAP 2010 1.0 27.0 0 32767

SPARE ADDRESS:

SAPRE ADDRESS (FROM) 2011

SAPRE ADDRESS (TO) 2012

ED-682330, Rev-2 PAGE 38 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

33KV ALARMS

ED-682330, Rev-2 PAGE 39 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 - 33KV CB GROUPED ALARMS

=BH03/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B413 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH03/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B413 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH03/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B413 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH03/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B413 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH03/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B413 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH03/OG X7.1:18 Q204 (21,22) COMM-BCU CB B413 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH03/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B413 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH04/CAP X7:18 74TC1 (1,3) BCPU / REF 620 CB B414 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH04/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B414 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH04/CAP X7:19 74TC2 (1,3) BCPU / REF 620 CB B414 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH04/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B414 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH04/CAP X7.1:11 IRF:X100 (3,4) COMM-BCU CB B414 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH04/CAP X7.1:18 Q204 (21,22) COMM-BCU CB B414 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH04/CAP X7:17 X902:X903 (19,20) BCPU / REF 620 CB B414 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH05/IC X7:18 74TC1 (1,3) BCPU / REF 620 CB A402 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH05/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A402 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH05/IC X7:19 74TC2 (1,3) BCPU / REF 620 CB A402 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH05/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A402 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH05/IC X7.1:11 IRF:X100 (3,4) COMM-BCU CB A402 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH05/IC X7.1:18 Q204 (21,22) COMM-BCU CB A402 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH05/IC X7:17 X902:X903 (19,20) BCPU / REF 620 CB A402 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

ED-682330, Rev-2 PAGE 40 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH06/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B415 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH06/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B415 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH06/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B415 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH06/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B415 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH06/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B415 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH06/OG X7.1:18 Q204 (21,22) COMM-BCU CB B415 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH06/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B415 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH07/AUX X7:18 74TC1 (1,3) BCPU / REF 620 CB B416 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH07/AUX X7.1:17 Q201 (21,22) BCPU / REF 620 CB B416 TRIP CIRCUIT-1 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH07/AUX X7:19 74TC2 (1,3) BCPU / REF 620 CB B416 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH07/AUX X7.1:17 Q202 (21,22) BCPU / REF 620 CB B416 TRIP CIRCUIT-2 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH07/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU CB B416 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH07/AUX X7.1:18 Q204 (21,22) COMM-BCU CB B416 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH07/AUX X7:17 X902:X903 (19,20) BCPU / REF 620 CB B416 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH08/BS X7.1:11 IRF:X100 (3,4) COMM-BCU CB A401 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH08/BS X7.1:18 Q204 (21,22) COMM-BCU CB A401 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH08/BS X7:17 X902:X903 (19,20) BCPU / REF 620 CB A401 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL
SPARK SS#3 33kV CB PROT. FAULTY/
NT FLTY ALARM NORMAL 4057

=BH08/BS X7:18 74TC1 (1,3) BCPU / REF 620 CB A401 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH08/BS X7.1:17 Q201 (21,22) BCPU / REF 620 CB A401 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 41 OF 104


DOC. NO: ED-682330

REV-2

NT HMI/ALARM/EVENTS TEXT RECEIVED


SPARK AT CB
SS#3 33kV CONTROL
PROT. CENTER
FAULTY/
4057 CONTROL SYSTEM DATA CLOSE LOOP TEST
FLTY ALARM NORMAL
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH08/BS X7:19 74TC2 (1,3) BCPU / REF 620 CB A401 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH08/BS X7.1:17 Q201 (21,22) BCPU / REF 620 CB A401 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH10/AUX X7:18 74TC1 (1,3) BCPU / REF 620 CB B421 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH10/AUX X7.1:17 Q201 (21,22) BCPU / REF 620 CB B421 TRIP CIRCUIT-1 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH10/AUX X7:19 74TC2 (1,3) BCPU / REF 620 CB B421 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH10/AUX X7.1:17 Q202 (21,22) BCPU / REF 620 CB B421 TRIP CIRCUIT-2 DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH10/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU CB B421 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH10/AUX X7.1:18 Q204 (21,22) COMM-BCU CB B421 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH10/AUX X7:17 X902:X903 (19,20) BCPU / REF 620 CB B421 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH11/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B422 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH11/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B422 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH11/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B422 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH11/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B422 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH11/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B422 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH11/OG X7.1:18 Q204 (21,22) COMM-BCU CB B422 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH11/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B422 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH12/IC X7:18 74TC1 (1,3) BCPU / REF 620 CB A403 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH12/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A403 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH12/IC X7:19 74TC2 (1,3) BCPU / REF 620 CB A403 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH12/IC X7.1:17 Q201 (21,22) BCPU / REF 620 CB A403 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH12/IC X7.1:11 IRF:X100 (3,4) COMM-BCU CB A403 BCPU PROT. RELAY FAULTY ALARM / NORMAL

ED-682330, Rev-2 PAGE 42 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH12/IC X7.1:18 Q204 (21,22) COMM-BCU CB A403 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH12/IC X7:17 X902:X903 (19,20) BCPU / REF 620 CB A403 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH13/CAP X7:18 74TC1 (1,3) BCPU / REF 620 CB B423 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH13/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B423 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH13/CAP X7:19 74TC2 (1,3) BCPU / REF 620 CB B423 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH13/CAP X7.1:17 Q201 (21,22) BCPU / REF 620 CB B423 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH13/CAP X7.1:11 IRF:X100 (3,4) COMM-BCU CB B423 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH13/CAP X7.1:18 Q204 (21,22) COMM-BCU CB B423 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH13/CAP X7:17 X902:X903 (19,20) BCPU / REF 620 CB B423 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH14/OG X7:18 74TC1 (1,3) BCPU / REF 620 CB B424 TRIP CIRCUIT-1 FAULTY ALARM / NORMAL

=BH14/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B424 TRIP CIRCUIT-1 DC SUPPLY FAIL ALARM / NORMAL

=BH14/OG X7:19 74TC2 (1,3) BCPU / REF 620 CB B424 TRIP CIRCUIT-2 FAULTY ALARM / NORMAL

=BH14/OG X7.1:17 Q201 (21,22) BCPU / REF 620 CB B424 TRIP CIRCUIT-2 DC SUPPLY FAIL ALARM / NORMAL

=BH14/OG X7.1:11 IRF:X100 (3,4) COMM-BCU CB B424 BCPU PROT. RELAY FAULTY ALARM / NORMAL

=BH14/OG X7.1:18 Q204 (21,22) COMM-BCU CB B424 BCPU PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM / NORMAL

=BH14/OG X7:17 X902:X903 (19,20) BCPU / REF 620 CB B424 BCPU PROT. RELAY UNDER TEST ALARM / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 BCPU PROT. RELAY SAS COMM. FAIL ALARM / NORMAL

=BH03/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B413 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH03/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B413 SPRING NOT CHARGED ALARM / NORMAL

=BH04/CAP X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B414 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH04/CAP X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B414 SPRING NOT CHARGED ALARM / NORMAL

ED-682330, Rev-2 PAGE 43 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH05/IC X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A402 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH05/IC X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A402 SPRING NOT CHARGED ALARM / NORMAL

=BH06/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B415 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH06/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B415 SPRING NOT CHARGED ALARM / NORMAL

=BH07/AUX X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B416 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH07/AUX X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B416 SPRING NOT CHARGED ALARM / NORMAL

=BH08/BS X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A401 MOTOR SUPPLY FAIL ALARM / NORMAL
SPARK SS#3 33kV 33KV CB ALARM/
NT LOCKOUT NORMAL 4058

=BH08/BS X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A401 SPRING NOT CHARGED ALARM / NORMAL

=BH10/AUX X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B421 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH10/AUX X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B421 SPRING NOT CHARGED ALARM / NORMAL

=BH11/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B422 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH11/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B422 SPRING NOT CHARGED ALARM / NORMAL

=BH12/IC X7.1:14 74DC1 (15,16) BCPU / REF 620 CB A403 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH12/IC X7:1 KSC1 (11 , 14) BCPU / REF 620 CB A403 SPRING NOT CHARGED ALARM / NORMAL

=BH13/CAP X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B423 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH13/CAP X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B423 SPRING NOT CHARGED ALARM / NORMAL

=BH14/OG X7.1:14 74DC1 (15,16) BCPU / REF 620 CB B424 MOTOR SUPPLY FAIL ALARM / NORMAL

=BH14/OG X7:1 KSC1 (11 , 14) BCPU / REF 620 CB B424 SPRING NOT CHARGED ALARM / NORMAL

Q205 (21,22),
=BH03/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B413 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH03/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B413 AC MCBs TRIP ALARM / NORMAL

=BH03/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B413 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH03/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B413 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH04/CAP X7.1:18 Q204 (21,22) BCPU / REF 620 CB B414 DC MCBs TRIP ALARM / NORMAL

ED-682330, Rev-2 PAGE 44 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

Q207 (11,12),
=BH04/CAP X7:14 Q208 (11,12) BCPU / REF 620 CB B414 AC MCBs TRIP ALARM / NORMAL

=BH04/CAP X7.1:18 Q203 (21,22) BCPU / REF 620 CB B414 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH04/CAP X7:14 Q207 (11,12), BCPU / REF 620 CB B414 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH05/IC X7.1:18 Q204 (21,22) BCPU / REF 620 CB A402 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH05/IC X7:14 Q208 (11,12) BCPU / REF 620 CB A402 AC MCBs TRIP ALARM / NORMAL

=BH05/IC X7.1:18 Q203 (21,22) BCPU / REF 620 CB A402 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH05/IC X7:14 Q207 (11,12), BCPU / REF 620 CB A402 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH06/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B415 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH06/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B415 AC MCBs TRIP ALARM / NORMAL

=BH06/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B415 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH06/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B415 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH07/AUX X7.1:18 Q204 (21,22) BCPU / REF 620 CB B416 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH07/AUX X7:14 Q208 (11,12) BCPU / REF 620 CB B416 AC MCBs TRIP ALARM / NORMAL

=BH07/AUX X7.1:18 Q203 (21,22) BCPU / REF 620 CB B416 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH07/AUX X7:14 Q207 (11,12), BCPU / REF 620 CB B416 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH08/BS X7.1:18 Q204 (21,22) BCPU / REF 620 CB A401 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH08/BS X7:14 Q208 (11,12) BCPU / REF 620 CB A401AC MCBs TRIP ALARM / NORMAL

Q401/Q421/Q422/Q411/ SPARK SS#3 33KV NON ALARM/


=BH08/BS X7:20 Q431 (21,22) BCPU / REF 620 NT CB A401 VT MCB TRIP ALARM / NORMAL URGENT ALARM NORMAL 4059

=BH08/BS X7.1:18 Q203 (21,22) BCPU / REF 620 CB A401 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH08/BS X7:14 Q207 (11,12), BCPU / REF 620 CB A401INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH10/AUX X7.1:18 Q204 (21,22) BCPU / REF 620 CB B421 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH10/AUX X7:14 Q208 (11,12) BCPU / REF 620 CB B421 AC MCBs TRIP ALARM / NORMAL

=BH10/AUX X7.1:18 Q203 (21,22) BCPU / REF 620 CB B421 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 45 OF 104


SPARK SS#3 33KV NON ALARM/
NT URGENT ALARM NORMAL 4059

DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH10/AUX X7:14 Q207 (11,12), BCPU / REF 620 CB B421 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH11/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B422 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH11/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B422 AC MCBs TRIP ALARM / NORMAL

=BH11/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B422 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH11/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B422 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH12/IC X7.1:18 Q204 (21,22) BCPU / REF 620 CB A403 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH12/IC X7:14 Q208 (11,12) BCPU / REF 620 CB A403 AC MCBs TRIP ALARM / NORMAL

=BH12/IC X7.1:18 Q203 (21,22) BCPU / REF 620 CB A403 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH12/IC X7:14 Q207 (11,12), BCPU / REF 620 CB A403 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH13/CAP X7.1:18 Q204 (21,22) BCPU / REF 620 CB B423 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH13/CAP X7:14 Q208 (11,12) BCPU / REF 620 CB B423 AC MCBs TRIP ALARM / NORMAL

=BH13/CAP X7.1:18 Q203 (21,22) BCPU / REF 620 CB B423 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH13/CAP X7:14 Q207 (11,12), BCPU / REF 620 CB B423 INDICATION DC SUPPLY FAIL ALARM / NORMAL

Q205 (21,22),
=BH14/OG X7.1:18 Q204 (21,22) BCPU / REF 620 CB B424 DC MCBs TRIP ALARM / NORMAL

Q207 (11,12),
=BH14/OG X7:14 Q208 (11,12) BCPU / REF 620 CB B424 AC MCBs TRIP ALARM / NORMAL

=BH14/OG X7.1:18 Q203 (21,22) BCPU / REF 620 CB B424 CLOSING/CONTROL DC SUPPLY FAIL ALARM / NORMAL

=BH14/OG X7:14 Q207 (11,12), BCPU / REF 620 CB B424 INDICATION DC SUPPLY FAIL ALARM / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

ED-682330, Rev-2 PAGE 46 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 I/C 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-R TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-Y TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50 INST O/C PROT OPTD PH-B TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 50N INST E/F PROT OPTD TRIP / NORMAL

SPARK SS#3 33KV PROT. OPERATE/


=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51 DELAY O/C PROT OPTD PH-R TRIP / NORMAL OPTD NORMAL 4060

ED-682330, Rev-2 PAGE 47 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC
SPARK SS#3 33KV PROT. OPERATE/
OPTD NORMAL 4060

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51 DELAY O/C PROT OPTD PH-Y TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51 DELAY O/C PROT OPTD PH-B TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 51N DELAY E/F PROT OPTD TRIP / NORMAL

=BH08/BS X7.1:12 86BS (17,19) COMM-BCU CB A401 86 LOCKOUT RELAY OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 I/C 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50 INST O/C PROTECTION PH-B OPTD TRIP / NORMAL

ED-682330, Rev-2 PAGE 48 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-R OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-Y OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51 DELAY O/C PROTECTION PH-B OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 50N INST. E/F PROTECTION OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 O/G 51N DELAY E/F PROTECTION OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 CBF PROTECTION OPTD TRIP / NORMAL

=BH03/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B413 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 CBF PROTECTION OPTD TRIP / NORMAL

=BH04/CAP X7.1:13 86CBF (17,19) BCPU / REF 620 CB B414 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 CBF PROTECTION OPTD TRIP / NORMAL

=BH05/IC X7.1:13 86CBF (17,19) BCPU / REF 620 CB A402 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 SET-1 LV CBF PROTECTION OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 SET-2 LV CBF PROTECTION OPTD TRIP / NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 GT-1 LV 86CBF LOCKOUT RELAY OPTD TRIP / NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 CBF PROTECTION OPTD TRIP / NORMAL

=BH06/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B415 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 CBF PROTECTION OPTD TRIP / NORMAL

=BH07/AUX X7.1:13 86CBF (17,19) BCPU / REF 620 CB B416 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 BCPU CBF PROTECTION OPTD TRIP / NORMAL
SPARK SS#3 33KV CBF PROT. OPERATE/
T OPTD NORMAL 4061

=BH08/BS X7.1:13 86CBF (17,19) BCPU / REF 620 CB A401 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 CBF PROTECTION OPTD TRIP / NORMAL

=BH10/AUX X7.1:13 86CBF (17,19) BCPU / REF 620 CB B421 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 CBF PROTECTION OPTD TRIP / NORMAL

ED-682330, Rev-2 PAGE 49 OF 104


DOC. NO: ED-682330

SPARK SS#3 33KV CBF PROT. OPERATE/


T OPTD NORMAL 4061
REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH11/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B422 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 CBF PROTECTION OPTD TRIP / NORMAL

=BH12/IC X7.1:13 86CBF (17,19) BCPU / REF 620 CB A403 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 SET-1 LV CBF PROTECTION OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 SET-2 LV CBF PROTECTION OPTD TRIP / NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 GT-2 LV 86CBF LOCKOUT RELAY OPTD TRIP / NORMAL

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 CBF PROTECTION OPTD TRIP / NORMAL

=BH13/CAP X7.1:13 86CBF (17,19) BCPU / REF 620 CB B423 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 CBF PROTECTION OPTD TRIP / NORMAL

=BH14/OG X7.1:13 86CBF (17,19) BCPU / REF 620 CB B424 86CBF LOCK OUT RELAY OPTD TRIP / NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH03/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B413 VT MCB TRIP ALARM/ NORMAL

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B414 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH03/OG X7:20 Q401 (21,22) BCPU / REF 620 CB B414 VT MCB TRIP ALARM/ NORMAL

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK OUT ALARM/ NORMAL

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 VT-314 RACK IN ALARM/ NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH05/IC X7:20 Q412 (21,22) BCPU / REF 620 CB A402 VT MCB TRIP ALARM/ NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK OUT ALARM/ NORMAL

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 VT-304 RACK IN ALARM/ NORMAL

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH06/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B415 VT MCB TRIP ALARM/ NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 VT FUSE FAIL ALARM ALARM/ NORMAL

SPARK SS#3 FAILED/


ED-682330, Rev-2 NT 33kV VT NORMAL 4062 PAGE 50 OF 104
DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH07/AUX X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B416 VT MCB TRIP ALARM/ NORMAL
SPARK SS#3 FAILED/
NT 33kV VT NORMAL 4062

=BH010/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH010/AUX X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B421 VT MCB TRIP ALARM/ NORMAL

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH11/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B422 VT MCB TRIP ALARM/ NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH12/IC X7:20 Q412 (21,22) BCPU / REF 620 CB A403 VT MCB TRIP ALARM/ NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT-304 RACK OUT ALARM/ NORMAL

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 VT-304 RACK IN ALARM/ NORMAL

=BH13/CAP X7:20 Q401 (21,22) BCPU / REF 620 CB B423 VT MCB TRIP ALARM/ NORMAL

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB A423 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 VT-304 RACK OUT ALARM/ NORMAL

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 VT-314 RACK IN ALARM/ NORMAL

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 VT FUSE FAIL ALARM ALARM/ NORMAL

=BH14/OG X7:20 Q401 (21,22), Q402 (21,22) BCPU / REF 620 CB B424 VT MCB TRIP ALARM/ NORMAL

=BH03/OG X7:8 S103 (21,22) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH03/OG X7:10 S103 (23,24) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO LOCAL

=BH03/OG X7:10 S103 (18,17) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B413 REMOTE OFF/ON 4063

=BH03/OG X7:111 S103 (20,19) BCPU / REF 620 CB B413 BAY CONTROL MODE SET TO REMOTE

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH03/OG INTERNAL INTERNAL BCPU / REF 620 CB B413 BAY BLOCK

=BH05/IC X7:8 S103 (21,22) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH05/IC X7:10 S103 (23,24) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO LOCAL

SPARK SS#3
ED-682330, Rev-2 NT OFF/ON CB A402 REMOTE OFF/ON 4064 PAGE 51 OF 104
DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH05/IC X7:10 S103 (18,17) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A402 REMOTE OFF/ON 4064

=BH05/IC X7:111 S103 (20,19) BCPU / REF 620 CB A402 BAY CONTROL MODE SET TO REMOTE

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH05/IC INTERNAL INTERNAL BCPU / REF 620 CB A402 BAY BLOCK

=BH04/CAP X7:8 S103 (21,22) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH04/CAP X7:10 S103 (23,24) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO LOCAL

=BH04/CAP X7:10 S103 (18,17) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B414 REMOTE OFF/ON 4065

=BH04/CAP X7:111 S103 (20,19) BCPU / REF 620 CB B414 BAY CONTROL MODE SET TO REMOTE

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH04/CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 BAY BLOCK

ED-682330, Rev-2 PAGE 52 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH06/OG X7:8 S103 (21,22) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH06/OG X7:10 S103 (23,24) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO LOCAL

=BH06/OG X7:10 S103 (18,17) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B415 REMOTE OFF/ON 4066

=BH06/OG X7:111 S103 (20,19) BCPU / REF 620 CB B415 BAY CONTROL MODE SET TO REMOTE

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH06/OG INTERNAL INTERNAL BCPU / REF 620 CB B415 BAY BLOCK

=BH07/AUX X7:8 S103 (21,22) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH07/AUX X7:10 S103 (23,24) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO LOCAL

=BH07/AUX X7:10 S103 (18,17) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B416 REMOTE OFF/ON 4067

=BH07/AUX X7:111 S103 (20,19) BCPU / REF 620 CB B416 BAY CONTROL MODE SET TO REMOTE

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 CB B416 BAY BLOCK

=BH08/BS X7:8 S103 (21,22) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH08/BS X7:10 S103 (23,24) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO LOCAL

=BH08/BS X7:10 S103 (18,17) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A401 REMOTE OFF/ON 4068

=BH08/BS X7:111 S103 (20,19) BCPU / REF 620 CB A401 BAY CONTROL MODE SET TO REMOTE

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 BAY BLOCK

=BH08/BS INTERNAL INTERNAL BCPU / REF 620 CB A401 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH10/AUX X7:8 S103 (21,22) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH10/AUX X7:10 S103 (23,24) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO LOCAL

=BH10/AUX X7:10 S103 (18,17) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B421 REMOTE OFF/ON 4069

=BH10/AUX X7:111 S103 (20,19) BCPU / REF 620 CB B421 BAY CONTROL MODE SET TO REMOTE

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 BAY BLOCK

ED-682330, Rev-2 PAGE 53 OF 104


DOC. NO: ED-682330

REV-2

NT HMI/ALARM/EVENTS TEXT OFF/ON RECEIVED


SPARK AT CONTROL CENTER
SS#3
OFF/ON 4069 CONTROL SYSTEM DATA CLOSE LOOP TEST
CB B421 REMOTE
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 CB B421 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH11/OG X7:8 S103 (21,22) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH11/OG X7:10 S103 (23,24) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO LOCAL

=BH11/OG X7:10 S103 (18,17) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B422 REMOTE OFF/ON 4070

=BH11/OG X7:111 S103 (20,19) BCPU / REF 620 CB B422 BAY CONTROL MODE SET TO REMOTE

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH11/OG INTERNAL INTERNAL BCPU / REF 620 CB B422 BAY BLOCK

=BH12/IC X7:8 S103 (21,22) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH12/IC X7:10 S103 (23,24) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO LOCAL

=BH12/IC X7:10 S103 (18,17) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB A403 REMOTE OFF/ON 4071

=BH12/IC X7:111 S103 (20,19) BCPU / REF 620 CB A403 BAY CONTROL MODE SET TO REMOTE

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH12/IC INTERNAL INTERNAL BCPU / REF 620 CB A403 BAY BLOCK

=BH13/CAP X7:8 S103 (21,22) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH13/CAP X7:10 S103 (23,24) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO LOCAL

=BH13/CAP X7:10 S103 (18,17) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B423 REMOTE OFF/ON 4072

=BH13/CAP X7:111 S103 (20,19) BCPU / REF 620 CB B423 BAY CONTROL MODE SET TO REMOTE

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH13/CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 BAY BLOCK

=BH14/OG X7:8 S103 (21,22) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO TROLLEY /OFF

=BH14/OG X7:10 S103 (23,24) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO LOCAL

=BH14/OG X7:10 S103 (18,17) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO BCPU
SPARK SS#3
NT OFF/ON CB B424 REMOTE OFF/ON 4073

=BH14/OG X7:111 S103 (20,19) BCPU / REF 620 CB B424 BAY CONTROL MODE SET TO REMOTE

ED-682330, Rev-2 PAGE 54 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER SPARK SS#3 ADDRESS
NT OFF/ON CB B424 REMOTE OFF/ON 4073 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 HMI CONTROL MODE AUTHORITY SET TO SAS/RCC

=BH14/OG INTERNAL INTERNAL BCPU / REF 620 CB B424 BAY BLOCK

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 SST-1 ALARMS

=BH07/AUX X7.1:35,41 KTA (3,7) BCPU / REF 620 AUX. TR-1 OIL LEVEL LOW ALARM ALARM/NORMAL

=BH07/AUX X7.1:36,42 KTT (3,7) BCPU / REF 620 AUX. TR-1 OIL LEVEL HIGH ALARM ALARM/NORMAL

SPARK SS#3 ALARM/


=BH07/AUX X7.1:33,39 KLA (3,7) BCPU / REF 620 NT AUX. TR-1 OIL TEMPERATURE HIGH STAGE-1 ALARM ALARM/NORMAL 33KV AUX. TR.-1 URGENT NORMAL 4074
ALARM

=BH07/AUX X7.1:31,37 KBA (3,7) BCPU / REF 620 AUX. TR-1 BUCHHOLZ STAGE-1 ALARM ALARM/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 RMU-1 EARTH LEAKAGE OPTD ALARM/NORMAL

=BH07/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU AUX. TR-1 BCPU RELAY FAULTY ALARM/NORMAL

=BH07/AUX X7.1:18 Q204 (21,22) COMM-BCU AUX. TR-1 BCPU RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 BCPU RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

SPARK SS#3 FAULTY/


=BH07/AUX X7:17 X902:X903:X904 (19,20) BCPU / REF 620 NT AUX. TR-1 BCPU RELAY UNDER TEST ALARM/NORMAL AUX. TR.-1 PROT. FLTY NORMAL 4075
ALARM

=BH07/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-1 PROT. FAULTY ALARM/NORMAL

=BH07/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-1 PROT RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 PROT RELAY SAS COMM. FAIL ALARM/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 50N INST. E/F PROTECTION OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-1 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL

ED-682330, Rev-2 PAGE 55 OF 104


SPARK SS#3 OPERATE/
T AUX. TR.-1 PROT. OPTD NORMAL 4076
DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH07/AUX X7:21 KBT (3,7) BCPU / REF 620 AUX. TR-1 BUCHHOLZ STAGE-2 OPTD TRIP/NORMAL

SPARK SS#3 OPERATE/


=BH07/AUX X7:21 KLT (3,7) BCPU / REF 620 T AUX. TR-1 OIL TEMPERATURE HIGH STAGE-2 OPTD TRIP/NORMAL AUX. TR.-1 PROT. OPTD NORMAL 4076

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 50N INST. E/F PROTECTION OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH07/AUX INTERNAL INTERNAL RMU-BCPU RMU-1 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL

86M (42,48),
=BH07/AUX X7:13 X904 (13,14) BCPU / REF 620 AUX. TR-1 86T LOCKOUT RELAY OPTD TRIP/NORMAL

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 SST-2 ALARMS

=BH10/AUX X7.1:35,41 KTA (3,7) BCPU / REF 620 AUX. TR-2 OIL LEVEL LOW ALARM ALARM/NORMAL

=BH10/AUX X7.1:36,42 KTT (3,7) BCPU / REF 620 AUX. TR-2 OIL LEVEL HIGH ALARM ALARM/NORMAL

SPARK SS#3 ALARM/


=BH10/AUX X7.1:33,39 KLA (3,7) BCPU / REF 620 NT AUX. TR-2 OIL TEMPERATURE HIGH STAGE-1 ALARM ALARM/NORMAL 33KV AUX. TR.-2 URGENT NORMAL 4077
ALARM

=BH10/AUX X7.1:31,37 KBA (3,7) BCPU / REF 620 AUX. TR-2 BUCHHOLZ STAGE-1 ALARM ALARM/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 RMU-2 EARTH LEAKAGE OPTD ALARM/NORMAL

=BH10/AUX X7.1:11 IRF:X100 (3,4) COMM-BCU AUX. TR-2 BCPU RELAY FAULTY ALARM/NORMAL

=BH10/AUX X7.1:18 Q204 (21,22) COMM-BCU AUX. TR-2 BCPU RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 BCPU RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

SPARK SS#3 FAULTY/


=BH10/AUX X7:17 X902:X903:X904 (19,20) BCPU / REF 620 NT AUX. TR-2 BCPU RELAY UNDER TEST ALARM/NORMAL AUX. TR.-2 PROT. FLTY NORMAL 4078
ALARM

=BH10/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-2 PROT. FAULTY ALARM/NORMAL

=BH10/AUX-RMU INTERNAL INTERNAL COMM-BCU RMU-2 PROT RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

ED-682330, Rev-2 PAGE 56 OF 104


DOC. NO: ED-682330

REV-2

SPARK SS#3 FAULTY/


NT AUX. TR.-2 PROT. FLTY NORMAL 4078
ALARM
HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 PROT RELAY SAS COMM. FAIL ALARM/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 50N INST. E/F PROTECTION OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL BCPU / REF 620 AUX. TR-2 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL

=BH10/AUX X7:21 KBT (3,7) BCPU / REF 620 AUX. TR-2 BUCHHOLZ STAGE-2 OPTD TRIP/NORMAL

SPARK SS#3 OPERATE/


=BH10/AUX X7:21 KLT (3,7) BCPU / REF 620 T AUX. TR-2 OIL TEMPERATURE HIGH STAGE-2 OPTD TRIP/NORMAL AUX. TR.-2 PROT. OPTD NORMAL 4079

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50 INST O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 50N INST. E/F PROTECTION OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51 DELAY O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH10/AUX INTERNAL INTERNAL RMU-BCPU RMU-2 51N DELAY E/F PROTECTION OPTD TRIP/NORMAL

86M (42,48),
=BH10/AUX X7:13 X904 (13,14) BCPU / REF 620 AUX. TR-2 86T LOCKOUT RELAY OPTD TRIP/NORMAL

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 - CAPACITOR BANK-1 ALARMS

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

ED-682330, Rev-2 PAGE 57 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

SPARK SS#3 ALARM/


NT CAPACITOR BANK-1 URGENT NORMAL 4080
ALARM

ED-682330, Rev-2 PAGE 58 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 87V-1 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-1 URGENT NORMAL 4080
ALARM
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 87V-2 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL

=BH04+R1 X6:3 GP1:X11 (3,2) COMM-BCU CAP. BANK-1 SET-1 87C-1 PROT. RELAY FAULTY ALARM/NORMAL

74R1 (1,3),
=BH04+R1 X6:4 Q1 (21,22) COMM-BCU CAP. BANK-1 SET-1 87C-1 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL

=BH04+R1 X32:15 TS1A (3,4) GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY UNDER TEST ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP. BANK-1 SET-1 87C-1 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL

=BH04+R1 X32:7 TS3 (17,18) GP1-REC670 CAP BANK-1 SET-1 87C-1 PROT RELAY VT MCB TRIP ALARM/NORMAL
SPARK SS#3 FAULTY/
NT CAPACITOR BANK-1 PROT. NORMAL 4081
FLTY.
=BH04+R1 X6:6 GP2:A (11,12) COMM-BCU CAP. BANK-1 SET-2 87C-2 PROT. RELAY FAULTY ALARM/NORMAL

74R2 (1,3),
=BH04+R1 X6:7 Q3 (21,22) COMM-BCU CAP. BANK-1 SET-2 87C-2 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL

=BH04+R1 SEL487V_B:47 TS2 (13,14) GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY UNDER TEST ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-1 SET-2 87C-2 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL

=BH04+R1 SEL487V_B:37 TS4 (25,26) GP-2 SEL487V CAP BANK-1 SET-2 87C-2 PROT RELAY VT MCB TRIP ALARM/NORMAL

ED-682330, Rev-2 PAGE 59 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50-1 INST O/C PROT PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 50N-1 INST E/F PROT OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51-1 DELAY O/C PROT PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 51N-1 DELAY E/F PROT OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 27-1 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 59-1 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 87V-1 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP1-REC670 CAP BANK-1 SET-1 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL

86C1 (14,16),
=BH04+R1 X31:13 TS3 (11,12) GP1-REC670 CAP BANK-1 SET-1 86C-1 LOCKOUT RELAY OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T CAPACITOR BANK-1 PROT. NORMAL 4082
OPTD
=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-R OPTD TRIP/NORMAL

ED-682330, Rev-2 PAGE 60 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT SPARK SS#3 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER T CAPACITOR BANK-1 PROT. OPERATE/
NORMAL
ADDRESS
4082 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA
OPTDLITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50-2 INST O/C PROT PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 50N-2 INST E/F PROT OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51-2 DELAY O/C PROT PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 51N-2 DELAY E/F PROT OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 27-2 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 59-2 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 87V-2 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH04+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-1 SET-2 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL

86C2 (6,8)
=BH04+R1 SEL487V_A:28 TS4 (5,6) GP-2 SEL487V CAP BANK-1 SET-2 86C-2 LOCKOUT RELAY OPTD TRIP/NORMAL

=BH04+R1 GP1_X32:5 C1 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL AC MCB TRIP ALARM/NORMAL

74IND1 (1,3),
=BH04+R1 GP1_X32:3 Q5 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL INDICATION SUPPLY FAIL ALARM/NORMAL

SPARK SS#3 ALARM/


ED-682330, Rev-2 NT CAPACITOR BANK-1 NON NORMAL 4083 PAGE 61 OF 104
URGENT ALARM
DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

74IO1 (1,3),
=BH04+R1 GP1_X32:1 Q2 (21,22) GP1-REC670 CAP. BANK-1 PROTECTION PANEL SET-1 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-1 NON NORMAL 4083
URGENT ALARM
74IO2 (1,3),
=BH04+R1 GP2_A:32 Q4 (21,22) GP-2 SEL487V CAP. BANK-1 PROTECTION PANEL SET-2 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL

QDC2(21,22),
=BH04+ACCS X6:6 RLB (3,11) COMM-BCU ACCS INDICATION DC SUPPLY FAIL ALARM/NORMAL

=BH04+R1 INTERNAL INTERNAL C264 CAP. BANK-1 CONTROLER (ACCS) OPEN COMMAND ALARM/NORMAL

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 - CAPACITOR BANK-2 ALARMS

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 87V-1 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL
SPARK SS#3 ALARM/
NT CAPACITOR BANK-2 URGENT NORMAL 4084
ALARM
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-R ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-Y ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-1 PH-B ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 87V-2 VOLTAGE DIFF. STAGE-1 ALARM ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -1 ALARM ALARM/NORMAL

=BH13+R1 X6:3 GP2:X11 (3,2) COMM-BCU CAP. BANK-2 SET-1 87C-1 PROT. RELAY FAULTY ALARM/NORMAL

74R1 (1,3),
=BH13+R1 X6:4 Q1 (21,22) COMM-BCU CAP. BANK-2 SET-1 87C-1 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL

ED-682330, Rev-2 PAGE 62 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH13+R1 X32:15 TS1A (3,4) GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY UNDER TEST ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

SPARK SS#3 FAULTY/


NT CAPACITOR BANK-2 PROT. NORMAL 4085
FLTY.

ED-682330, Rev-2 PAGE 63 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP. BANK-2 SET-1 87C-1 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL

=BH13+R1 X32:7 TS3 (17,18) GP2-REC670 CAP BANK-2 SET-1 87C-1 PROT RELAY VT MCB TRIP ALARM/NORMAL
SPARK SS#3 FAULTY/
NT CAPACITOR BANK-2 PROT. NORMAL 4085
FLTY.
=BH13+R1 X6:6 GP2:A (11,12) COMM-BCU CAP. BANK-2 SET-2 87C-2 PROT. RELAY FAULTY ALARM/NORMAL

74R2 (1,3),
=BH13+R1 X6:7 Q3 (21,22) COMM-BCU CAP. BANK-2 SET-2 87C-2 PROT. RELAY DC SUPPLY FAIL/DC MCB TRIP ALARM/NORMAL

=BH13+R1 SEL487V_B:47 TS2 (13,14) GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY UNDER TEST ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP. BANK-2 SET-2 87C-2 PROT. RELAY VT FUSE FAILURE ALARM/NORMAL

=BH13+R1 SEL487V_B:37 TS4 (25,26) GP-2 SEL487V CAP BANK-2 SET-2 87C-2 PROT RELAY VT MCB TRIP ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50-1 INST O/C PROT PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 50N-1 INST E/F PROT OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51-1 DELAY O/C PROT PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 51N-1 DELAY E/F PROT OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 27-1 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 59-1 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 87V-1 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL

ED-682330, Rev-2 PAGE 64 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 46-1 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 67-1 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP2-REC670 CAP BANK-2 SET-1 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL

86C1 (14,16),
=BH13+R1 X31:13 TS3 (11,12) GP2-REC670 CAP BANK-2 SET-1 86C-1 LOCKOUT RELAY OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T CAPACITOR BANK-2 PROT. NORMAL 4086
OPTD
=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50-2 INST O/C PROT PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 50N-2 INST E/F PROT OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51-2 DELAY O/C PROT PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 51N-2 DELAY E/F PROT OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 27-2 U/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 59-2 O/V PROTECTION STAGE-2 PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 87V-2 VOLTAGE DIFF. STAGE-2 OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 46-2 NEUTRAL CURRENT UNBALANCE STAGE -2 OPTD TRIP/NORMAL

ED-682330, Rev-2 PAGE 65 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 UNDER CURRENT PROTECTION STAGE-2 OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-R OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-Y OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 67-2 DIRECTIONAL O/C PROTECTION PH-B OPTD TRIP/NORMAL

=BH13+R1 INTERNAL INTERNAL GP-2 SEL487V CAP BANK-2 SET-2 DIRECTIONAL NEGATIVE SEQUENCE PROTECTION OPTD TRIP/NORMAL

86C2 (6,8)
=BH13+R1 SEL487V_A:28 TS4 (5,6) GP-2 SEL487V CAP BANK-2 SET-2 86C-2 LOCKOUT RELAY OPTD TRIP/NORMAL

=BH13+R1 GP2_X32:5 C1 (21,22) GP2-REC670 CAP. BANK-2 PROTECTION PANEL AC MCB TRIP ALARM/NORMAL

74IND1 (1,3),
=BH13+R1 GP2_X32:3 Q5 (21,22) GP2-REC670 CAP. BANK-2 PROTECTION PANEL INDICATION SUPPLY FAIL ALARM/NORMAL

74IO1 (1,3), SPARK SS#3 ALARM/


=BH13+R1 GP2_X32:1 Q2 (21,22) GP2-REC670 NT CAP. BANK-2 PROTECTION PANEL SET-1 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL CAPACITOR BANK-2 NON NORMAL 4087
URGENT ALARM

74IO2 (1,3),
=BH13+R1 GP2_A:32 Q4 (21,22) GP-2 SEL487V CAP. BANK-2 PROTECTION PANEL SET-2 IN/OUT DC SUPPLY FAILURE/MCB TRIP ALARM/NORMAL

=BH13+R1 INTERNAL INTERNAL C264 CAP. BANK-2 CONTROLER (ACCS) OPEN COMMAND ALARM/NORMAL

QDC1 (21,22),
3ACCS X6:5 RLA (3,11) COMM-BCU ACCS RELAY DC SUPPLY FAIL/MCB TRIP ALARM/NORMAL

Q01 (21,22),
3ACCS X6:8 Q02 (21,22) COMM-BCU ACCS CHANGE OVER DC MCB TRIP ALARM/NORMAL

3ACCS ACCS_N22 TS/1,2,3,4,5 (9,10) C264 ACCS RELAY UNDER TEST ALARM/NORMAL

3ACCS X6:2 H20 (H19,H21) COMM-BCU ACCS RELAY FAULTY ALARM/NORMAL


SPARK SS#3 FAULTY/
NT ACCS FLTY ALARM NORMAL 4088

3ACCS INTERNAL INTERNAL C264 ACCS RELAY VT SUPPLY FAILURE ALARM/NORMAL

3ACCS INTERNAL INTERNAL C264 ACCS RELAY BLOCK ALARM/NORMAL

3ACCS INTERNAL INTERNAL C264 ACCS RELAY RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

3ACCS INTERNAL INTERNAL C264 ACCS EQUIPMENT OUT OF SERVICE ALARM/NORMAL

=BH04+ACCS ACCS_P10 KM1(A1, A11) C264 ACCS SET IN LOCAL POSITION ALARM/NORMAL
SPARK SS#3
NT ACCS REMOTE OFF / ON 4089

=BH04+ACCS INTERNAL INTERNAL C264 ACCS BAY CONTROL AUTHORITY TO SAS/CRCC ALARM/NORMAL

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 -33KV BUSBAR-1 PROTECTION ALARMS

=BH09 X7.1,11 87B1 (F11, F12), COMM-BCU BUS BAR-1 87B PROT. RELAY FAULTY ALARM/NORMAL

ED-682330, Rev-2 PAGE 66 OF 104

SPARK SS#3 FAULTY/


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER ADDRESS POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH09 X1:33, 34 Q202 (21,22) COMM-BCU BUS BAR-1 87B PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

=BH09 X7:13 X911 (27,28) MICOM-P142 BUS BAR-1 87B PROT. RELAY UNDER TEST ALARM/NORMAL
SPARK SS#3 FAULTY/
NT 33KV BB PROT. FLTY ALARM NORMAL 4090

=BH09 X7.1,13 95B1 (26,28) COMM-BCU BUS BAR-1 95B CT SUPERVISION ALARM ALARM/NORMAL

=BH09 X7.1,12 95B1 (25,27) COMM-BCU BUS BAR-1 95B CT SUPERVISION FAULTY ALARM/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-R OPTD TRIP/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-Y OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T 33KV BB PROT. OPTD NORMAL 4091

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-1 87B DIFFERENTIAL PROT PH-B OPTD TRIP/NORMAL

=BH09 X7.1:19 86B (12,18) COMM-BCU BUS BAR-1 86B-A LOCKOUT RELAY OPTD TRIP/NORMAL

=BH08.1 X7:7 F800 (417,418) -IO1_REC670 BUS BAR-1 VT FUSE FAIL ALARM TRIP/NORMAL

Q411 (11, 12)


Q412 (11, 12) SPARK SS#3 FAILED/
Q413 (11, 12) NT 33KV BB-1 VT FAIL NORMAL 4092
Q414 (11, 12)
=BH08.1 X7:4 Q421 (11, 12) -IO1_REC670 BUS BAR-1 VT BRANCH MCB’S TRIP TRIP/NORMAL
Q422 (11, 12)
Q423 (11, 12)
Q424 (11, 12)
Q425 (11, 12)

CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 -33KV BUSBAR-2 PROTECTION ALARMS

=BH09 X7.1,11 87B1 (F11, F12), COMM-BCU BUS BAR-2 87B PROT. RELAY FAULTY ALARM/NORMAL

=BH09 X1:33, 34 Q202 (21,22) COMM-BCU BUS BAR-2 87B PROT. RELAY DC SUPPLY FAIL / DC MCB TRIP ALARM/NORMAL

=BH09 X7:13 X911 (27,28) MICOM-P142 BUS BAR-2 87B PROT. RELAY UNDER TEST ALARM/NORMAL
SPARK SS#3 FAULTY/
NT 33KV BB PROT. FLTY ALARM NORMAL 4093

=BH09 X7.1,13 95B1 (26,28) COMM-BCU BUS BAR-2 95B CT SUPERVISION ALARM ALARM/NORMAL

=BH09 X7.1,12 95B1 (25,27) COMM-BCU BUS BAR-2 95B CT SUPERVISION FAULTY ALARM/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B PROT. RELAY SAS COMM. BOTH CHANNELS FAIL ALARM/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-R OPTD TRIP/NORMAL

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-Y OPTD TRIP/NORMAL
SPARK SS#3 OPERATE/
T 33KV BB PROT. OPTD NORMAL 4094

=BH09 INTERNAL INTERNAL MICOM-P142 BUS BAR-2 87B DIFFERENTIAL PROT PH-B OPTD TRIP/NORMAL

ED-682330, Rev-2 PAGE 67 OF 104


DOC. NO: ED-682330

REV-2

HMI/ALARM/EVENTS TEXT RECEIVED AT CONTROL CENTER CONTROL SYSTEM DATA CLOSE LOOP TEST
HARDWIRE FULL IEC 61850 DEVICE IED TYPE IEC TYPE OPEN
SOURCE PANEL SOURCE ADDRESS/ NAME/NUMBER NAME T/NT 101/104 ID LOOP TEST REMARKS
TB.# IDENTIFIER SPARK SS#3 OPERATE/ ADDRESS
T 33KV BB PROT. OPTD NORMAL 4094 POINT NAME/ DEVICE TYPE CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX ALARM CODE CENTRE LDC

=BH09 X7.1:19 86B (12,18) COMM-BCU BUS BAR-2 86B-A LOCKOUT RELAY OPTD TRIP/NORMAL

=BH08.1 X7:7 F800 (417,418) -IO1_REC670 BUS BAR-2 VT FUSE FAIL ALARM TRIP/NORMAL

Q411 (11, 12)


Q412 (11, 12) SPARK SS#3 FAILED/
Q413 (11, 12) NT 33KV BB-2 VT FAIL NORMAL 4095
Q414 (11, 12)
=BH09.1 X7:4 Q421 (11, 12) -IO1_REC670 BUS BAR-2 VT BRANCH MCB’S TRIP TRIP/NORMAL
Q422 (11, 12)
Q423 (11, 12)
Q424 (11, 12)
Q425 (11, 12)

SPARE ADDRESS:

SPARE ADDRESS (FROM) 4096

SPARE ADDRESS (TO) 4104

ED-682330, Rev-2 PAGE 68 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

33KV INDICATIONS

ED-682330, Rev-2 PAGE 69 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE

BH03/OG INDICATIONS

Q101 (I1:17, I1:8)


BH03-O/G X7:6, 7 BCPU / REF 620 CB B413 BREAKER STATUS CLOSE / OPEN B413 BREAKER CLOSE / OPEN 4153
Q101 (I1:9, I1:10)

S711 (3, 4)
BH03-O/G X7:2,3 BCPU / REF 620 CB B413 BREAKER RACK IN / OUT B413 BREAKER RACK IN / OUT 4154
S701 (3, 4)

S601 (11, 12)


BH03-O/G X7:4,5 BCPU / REF 620 EARTH SWITCH K413 STATUS CLOSE/OPEN K404 EARTH SWITCH CLOSE / OPEN 4155
S601 (9, 10)

BH04/CAP INDICATIONS

Q101 (I1:17, I1:8)


BH04-CAP X7:6, 7 BCPU / REF 620 CB B414 BREAKER STATUS CLOSE / OPEN B414 BREAKER CLOSE / OPEN 4156
Q101 (I1:9, I1:10)

S711 (3, 4)
BH04-CAP X7:2,3 BCPU / REF 620 CB B414 BREAKER RACK IN / OUT B414 BREAKER RACK IN / OUT 4157
S701 (3, 4)

S601 (11, 12)


BH04-CAP X7:4,5 BCPU / REF 620 EARTH SWITCH K414 STATUS CLOSE/OPEN K413 EARTH SWITCH CLOSE / OPEN 4158
S601 (9, 10)

BH05/IC INDICATIONS

Q101 (I2:11, I2:12)


BH05-I/C X7:6, 7 BCPU / REF 620 CB A402 BREAKER STATUS CLOSE / OPEN A402 BREAKER CLOSE / OPEN 4159
Q101 (I2:7, I2:8)

S711 (3, 4)
BH05-I/C X7:2,3 BCPU / REF 620 CB A402 BREAKER RACK IN / OUT A402 BREAKER RACK IN / OUT 4160
S701 (3, 4)

S601 (11, 12)


BH05-I/C X7:4,5 BCPU / REF 620 EARTH SWITCH K404 STATUS CLOSE/OPEN K414 EARTH SWITCH CLOSE / OPEN 4161
S601 (9, 10)

BH06/OG INDICATIONS

Q101 (I1:17, I1:8)


BH06-O/G X7:6, 7 BCPU / REF 620 CB B415 BREAKER STATUS CLOSE / OPEN B415 BREAKER CLOSE / OPEN 4162
Q101 (I1:9, I1:10)

S711 (3, 4)
BH06-O/G X7:2,3 BCPU / REF 620 CB B415 BREAKER RACK IN / OUT B415 BREAKER RACK IN / OUT 4163
S701 (3, 4)

S601 (11, 12)


BH06-O/G X7:4,5 BCPU / REF 620 EARTH SWITCH K415 STATUS CLOSE/OPEN K415 EARTH SWITCH CLOSE / OPEN 4164
S601 (9, 10)

BH07/AUX INDICATIONS

Q101 (I1:17, I1:8)


BH07-SST X7:6, 7 BCPU / REF 620 CB B416 BREAKER STATUS CLOSE / OPEN B416 BREAKER CLOSE / OPEN 4165
Q101 (I1:9, I1:10)

S711 (3, 4)
BH07-SST X7:2,3 BCPU / REF 620 CB B416 BREAKER RACK IN / OUT B416 BREAKER RACK IN / OUT 4166
S701 (3, 4)

S601 (11, 12)


BH07-SST X7:4,5 BCPU / REF 620 EARTH SWITCH K416 STATUS CLOSE/OPEN K416 EARTH SWITCH CLOSE / OPEN 4167
S601 (9, 10)

33kV BUSBAR INDICATIONS

Q101 (I1:17, I1:8)


BH08-BS X7:6, 7 BCPU / REF 620 CB A401 BREAKER STATUS CLOSE / OPEN A401 BREAKER CLOSE / OPEN 4168
Q101 (I1:9, I1:10)

S711 (3, 4)
BH08-BS X7:2,3 BCPU / REF 620 CB A401 BREAKER RACK IN / OUT A401 BREAKER RACK IN / OUT 4169
S701 (3, 4)

S601 (11, 12)


BH8.1 X7:4,5 BCPU / REF 620 EARTH SWITCH K401 STATUS CLOSE/OPEN K401 EARTH SWITCH CLOSE / OPEN 4170
S601 (9, 10)

S601 (11, 12)


BH9.1 X7:4,5 BCPU / REF 620 EARTH SWITCH K402 STATUS CLOSE/OPEN K402 EARTH SWITCH CLOSE / OPEN 4171
S601 (9, 10)

BH10/AUX INDICATIONS

Q101 (I1:17, I1:8)


BH10-SST X7:6, 7 BCPU / REF 620 CB B421 BREAKER STATUS CLOSE / OPEN B421 BREAKER CLOSE / OPEN 4172
Q101 (I1:9, I1:10)

S711 (3, 4)
BH10-SST X7:2,3 BCPU / REF 620 CB B421 BREAKER RACK IN / OUT B421 BREAKER RACK IN / OUT 4173
S701 (3, 4)

S601 (11, 12)


BH10-SST X7:4,5 BCPU / REF 620 EARTH SWITCH K421 STATUS CLOSE/OPEN K421 EARTH SWITCH CLOSE / OPEN 4174
S601 (9, 10)

BH11/OG INDICATIONS

Q101 (I1:17, I1:8)


BH11-O/G X7:6, 7 BCPU / REF 620 CB B422 BREAKER STATUS CLOSE / OPEN B422 BREAKER CLOSE / OPEN 4175
Q101 (I1:9, I1:10)

ED-682330, Rev-2 PAGE 70 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
S711 (3, 4)
BH11-O/G X7:2,3 BCPU / REF 620 CB B422 BREAKER RACK IN / OUT B422 BREAKER RACK IN / OUT 4176
S701 (3, 4)

S601 (11, 12)


BH11-O/G X7:4,5 BCPU / REF 620 EARTH SWITCH K422 STATUS CLOSE/OPEN K422 EARTH SWITCH CLOSE / OPEN 4177
S601 (9, 10)

BH12/IC INDICATIONS

Q101 (I2:11, I2:12)


BH12-I/C X7:6, 7 BCPU / REF 620 CB A403 BREAKER STATUS CLOSE / OPEN A403 BREAKER CLOSE / OPEN 4178
Q101 (I2:7, I2:8)

S711 (3, 4)
BH12-I/C X7:2,3 BCPU / REF 620 CB A403 BREAKER RACK IN / OUT A403 BREAKER RACK IN / OUT 4179
S701 (3, 4)

S601 (11, 12)


BH12-I/C X7:4,5 BCPU / REF 620 EARTH SWITCH K404 STATUS CLOSE/OPEN K404 EARTH SWITCH CLOSE / OPEN 4180
S601 (9, 10)

BH13/CAP INDICATIONS

Q101 (I1:17, I1:8)


BH13-CAP X7:6, 7 BCPU / REF 620 CB B423 BREAKER STATUS CLOSE / OPEN B423 BREAKER CLOSE / OPEN 4181
Q101 (I1:9, I1:10)

S711 (3, 4)
BH13-CAP X7:2,3 BCPU / REF 620 CB B423 BREAKER RACK IN / OUT B423 BREAKER RACK IN / OUT 4182
S701 (3, 4)

S601 (11, 12)


BH13-CAP X7:4,5 BCPU / REF 620 EARTH SWITCH K423 STATUS CLOSE/OPEN K423 EARTH SWITCH CLOSE / OPEN 4183
S601 (9, 10)

BH14/OG INDICATIONS

Q101 (I1:17, I1:8)


BH14-O/G X7:6, 7 BCPU / REF 620 CB B424 BREAKER STATUS CLOSE / OPEN B424 BREAKER CLOSE / OPEN 4184
Q101 (I1:9, I1:10)

S711 (3, 4)
BH14-O/G X7:2,3 BCPU / REF 620 CB B424 BREAKER RACK IN / OUT B424 BREAKER RACK IN / OUT 4185
S701 (3, 4)

S601 (11, 12)


BH14-O/G X7:4,5 BCPU / REF 620 EARTH SWITCH K424 STATUS CLOSE/OPEN K424 EARTH SWITCH CLOSE / OPEN 4186
S601 (9, 10)

UF INDICATIONS

+3UFLS 81-1_D2 KM1 (1, 10) 81-1_P142 33KV UNDER FREQUENCY RELAY 81-1 STAGE-1/2/3/4 IN /OUT U/F RLY-1 STAGE-1/2/3/4 IN /OUT 4187

UV INDICATIONS

+3UVLS-1 27-1_D8 KM1 (1, 10) 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-1 IN/OUT U/V RLY-1 STAGE-1 IN/OUT 4188

+3UVLS-1 27-1_D10 KM2 (1, 10) 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-2 IN/OUT U/V RLY-1 STAGE-2 IN/OUT 4189

+3UVLS-1 27-1_D12 KM3 (1, 10) 27-1A_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-3 IN/OUT U/V RLY-1 STAGE-3 IN/OUT 4190

+3UVLS-2 27-2_D8 KM1 (1, 10) 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-1 IN/OUT U/V RLY-2 STAGE-1 IN/OUT 4191

+3UVLS-2 27-2_D10 KM2 (1, 10) 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-2 IN/OUT U/V RLY-2 STAGE-2 IN/OUT 4192

+3UVLS-2 27-2_D12 KM3 (1, 10) 27-2A_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-3 IN/OUT U/V RLY-2 STAGE-3 IN/OUT 4193

ACCS INDICATIONS

KM1 (A1, A11)


+3ACCS C264 33KV ACCS AUTO/MANUAL ACCS AUTO/MANUAL 4194
KM1 (A2, A21)

SPARE ADDRESS:

SPARE ADDRESS (FROM) 4195

SPARE ADDRESS (TO) 4204

ED-682330, Rev-2 PAGE 71 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

33KV COMMANDS

ED-682330, Rev-2 PAGE 72 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED-682330

SAS POINT LIST REV-2

33kV COMMANDS

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE

BH03/OG COMMANDS

BH03-O/G INTERNAL INTERNAL BCPU / REF 620 CB B413 COMMAND SELECTED CLOSE / OPEN CB B413 CLOSE / OPEN 1013 0

BH03-O/G INTERNAL INTERNAL BCPU / REF 620 CB B413 COMMAND EXECUTED CLOSE / OPEN CB B413 CLOSE / OPEN 1014 0

BH04/CAP COMMANDS

BH04-CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 COMMAND SELECTED CLOSE / OPEN CB B414 CLOSE / OPEN 1015 0

BH04-CAP INTERNAL INTERNAL BCPU / REF 620 CB B414 COMMAND EXECUTED CLOSE / OPEN CB B414 CLOSE / OPEN 1016 0

BH05/IC COMMANDS

BH05-I/C INTERNAL INTERNAL BCPU / REF 620 CB A402 COMMAND SELECTED CLOSE / OPEN CB A402 CLOSE / OPEN 1017 0

BH05-I/C INTERNAL INTERNAL BCPU / REF 620 CB A402 COMMAND EXECUTED CLOSE / OPEN CB A402 CLOSE / OPEN 1018 0

BH06/OG COMMANDS

BH06-O/G INTERNAL INTERNAL BCPU / REF 620 CB B415 COMMAND SELECTED CLOSE / OPEN CB B415 CLOSE / OPEN 1019 0

BH06-O/G INTERNAL INTERNAL BCPU / REF 620 CB B415 COMMAND EXECUTED CLOSE / OPEN CB B415 CLOSE / OPEN 1020 0

BH07/AUX COMMANDS

BH07-SST INTERNAL INTERNAL BCPU / REF 620 CB B416 COMMAND SELECTED CLOSE / OPEN CB B416 CLOSE / OPEN 1021 0

BH07-SST INTERNAL INTERNAL BCPU / REF 620 CB B416 COMMAND EXECUTED CLOSE / OPEN CB B416 CLOSE / OPEN 1022 0

33kV BUSBAR-A COMMANDS

BH08-BS INTERNAL INTERNAL BCPU / REF 620 CB A401 COMMAND SELECTED CLOSE / OPEN CB A401 CLOSE / OPEN 1023 0

BH08-BS INTERNAL INTERNAL BCPU / REF 620 CB A401 COMMAND EXECUTED CLOSE / OPEN CB A401 CLOSE / OPEN 1024 0

BH10/AUX COMMANDS

BH10-SST INTERNAL INTERNAL BCPU / REF 620 CB B421 COMMAND SELECTED CLOSE / OPEN CB B421 CLOSE / OPEN 1025 0

BH10-SST INTERNAL INTERNAL BCPU / REF 620 CB B421 COMMAND EXECUTED CLOSE / OPEN CB B421 CLOSE / OPEN 1026 0

BH11/OG COMMANDS

BH11-O/G INTERNAL INTERNAL BCPU / REF 620 CB B422 COMMAND SELECTED CLOSE / OPEN CB B422 CLOSE / OPEN 1027 0

BH11-O/G INTERNAL INTERNAL BCPU / REF 620 CB B422 COMMAND EXECUTED CLOSE / OPEN CB B422 CLOSE / OPEN 1028 0

BH12/IC COMMANDS

BH12-I/C INTERNAL INTERNAL BCPU / REF 620 CB A403 COMMAND SELECTED CLOSE / OPEN CB A403 CLOSE / OPEN 1029 0

BH12-I/C INTERNAL INTERNAL BCPU / REF 620 CB A403 COMMAND EXECUTED CLOSE / OPEN CB A403 CLOSE / OPEN 1030 0

BH13/CAP COMMANDS

BH13-CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 COMMAND SELECTED CLOSE / OPEN CB B423 CLOSE / OPEN 1031 0

BH13-CAP INTERNAL INTERNAL BCPU / REF 620 CB B423 COMMAND EXECUTED CLOSE / OPEN CB B423 CLOSE / OPEN 1032 0

BH14/OG COMMANDS

BH14-O/G INTERNAL INTERNAL BCPU / REF 620 CB B424 COMMAND SELECTED CLOSE / OPEN CB B424 CLOSE / OPEN 1033 0

BH14-O/G INTERNAL INTERNAL BCPU / REF 620 CB B424 COMMAND EXECUTED CLOSE / OPEN CB B424 CLOSE / OPEN 1034 0

UF COMMANDS

ED-682330, Rev-2 PAGE 73 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3 DOC. NO: ED-682330

SAS POINT LIST REV-2

33kV COMMANDS

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850 OPEN
SOURCE DEVICE IEC 101/104 TYPE
SOURCE ADDRESS / IED NAME POINT LOOP REMARKS
PANEL NAME/NUMBER ADDRESS ID DEVICE CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM TEST LDC
TYPE CENTRE
CODE
33KV UNDER FREQUENCY RELAY 81-1 STAGE-1/2 COMMAND
+3UFLS INTERNAL INTERNAL 81-1_P142 IN /OUT U/F RLY 81-1 STAGE-1/2 IN /OUT 1035
EXECUTED

33KV UNDER FREQUENCY RELAY 81-1 STAGE-3/4 COMMAND


+3UFLS INTERNAL INTERNAL 81-1_P142 IN /OUT U/F RLY 81-1 STAGE-3/4 IN /OUT 1036
EXECUTED

33KV UNDER FREQUENCY RELAY 81-2 STAGE-1/2 COMMAND


+3UFLS INTERNAL INTERNAL 81-2_P142 IN /OUT U/F RLY 81-2 STAGE-1/2 IN /OUT 1037
EXECUTED

33KV UNDER FREQUENCY RELAY 81-2 STAGE-3/4 COMMAND


+3UFLS INTERNAL INTERNAL 81-2_P142 IN /OUT U/F RLY 81-2 STAGE-3/4 IN /OUT 1038
EXECUTED

UV COMMANDS

+3UVLS-1 INTERNAL INTERNAL 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-1 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-1 IN/OUT 1039

+3UVLS-1 INTERNAL INTERNAL 27-1_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-2 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-2 IN/OUT 1040

+3UVLS-1 INTERNAL INTERNAL 27-1A_P142 33KV UNDER VOLTAGE RELAY-1 STAGE-3 COMMAND EXECUTED IN/OUT U/V RLY-1 STAGE-3 IN/OUT 1041

+3UVLS-2 INTERNAL INTERNAL 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-1 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-1 IN/OUT 1042

+3UVLS-2 INTERNAL INTERNAL 27-2_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-2 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-2 IN/OUT 1043

+3UVLS-2 INTERNAL INTERNAL 27-2A_P142 33KV UNDER VOLTAGE RELAY-2 STAGE-3 COMMAND EXECUTED IN/OUT U/V RLY-2 STAGE-3 IN/OUT 1044

ACCS COMMANDS

=3ACCS INTERNAL INTERNAL C264 33KV ACCS COMMAND EXECUTED AUTO/MANUAL ACCS AUTO/MANUAL 1045

SPARE ADDRESS:

SPARE ADDRESS (FROM) 1046

SPARE ADDRESS (TO) 1052

ED-682330, Rev-2 PAGE 74 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

33KV MEASUREMENTS

ED-682330, Rev-2 PAGE 75 OF 104


DOC. NO: EA-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST REV-2

33kV MEASUREMENTS

LOCAL RANGE SCADA RANGE CONTROL


FULL IEC 61850 DEVICE OPEN CLOSE LOOP TEST
HARDWIRE SOURCE IEC 101/104 SYSTEM
SOURCE PANEL ADDRESS / NAME/NUM IED NAME CT RATIO VT RATIO UNIT LOOP REMARKS
TB ADDRESS DATA/DEVICE
IDENTIFIER BER MIN MAX MIN MAX TEST CONTROL LDC
TYPE CENTRE

BH03/OG MEASUREMENTS

BH03-O/G INTERNAL CONFIGURATION A 2013 0 960 0 +32767


1250-800/1A
BH03-O/G INTERNAL CONFIGURATION 33KV / √3 : 120 - 120/ √3 V MW 2014 -54.86 54.86 -32767 +32767

BH03-O/G INTERNAL CONFIGURATION MVAR 2015 -54.86 54.86 -32767 +32767

BH04/CAP MEASUREMENTS

BH04-CAP INTERNAL CONFIGURATION KV 2016 0 39.6 -32767 +32767


1250-800/1A 33KV / √3 : 120 - 120/ √3 V
BH04-CAP INTERNAL CONFIGURATION MVAR 2017 -54.86 54.86 -32767 +32767

BH05-I/C MEASUREMENTS

BH05-I/C INTERNAL CONFIGURATION A 2018 0 2400 0 +32767

BH05-I/C INTERNAL CONFIGURATION KV 2019 0 39.6 -32767 +32767


2000/1A 33KV / √3 : 120 - 120/ √3 V
BH05-I/C INTERNAL CONFIGURATION MW 2020 -137.17 137.17 -32767 +32767

BH05-I/C INTERNAL CONFIGURATION MVAR 2021 -137.17 137.17 -32767 +32767

BH06/OG MEASUREMENTS

BH06-O/G INTERNAL CONFIGURATION A 2022 0 960 0 +32767


1250-800/1A
BH06-O/G INTERNAL CONFIGURATION 33KV / √3 : 120 - 120/ √3 V MW 2023 -54.86 54.86 -32767 +32767

BH06-O/G INTERNAL CONFIGURATION MVAR 2024 -54.86 54.86 -32767 +32767

BH07/AUX MEASUREMENTS

BH07-SST INTERNAL CONFIGURATION A 2025 0 240 0 +32767

BH07-SST INTERNAL CONFIGURATION 1250-800-400-200/1A 33KV / √3 : 120 - 120/ √3 V MW 2026 -13.71 13.71 -32767 +32767

BH07-SST INTERNAL CONFIGURATION MVAR 2027 -13.71 13.71 -32767 +32767

33kV BUSBAR-1/2 MEASUREMENTS

BH08-BS INTERNAL CONFIGURATION A 2028 0 3600 0 +32767


3000/1A
BH08-BS INTERNAL CONFIGURATION 33KV / √3 : 120 - 120/ √3 V KV 2029 0 39.6 -32767 +32767

BH08-BS INTERNAL CONFIGURATION HZ 2030 55 65 0 +32767

BH10/AUX MEASUREMENTS

BH10-SST INTERNAL CONFIGURATION A 2031 0 240 0 +32767

BH10-SST INTERNAL CONFIGURATION 1250-800-400-200/1A 33KV / √3 : 120 - 120/ √3 V MW 2032 -13.71 13.71 -32767 +32767

BH10-SST INTERNAL CONFIGURATION MVAR 2033 -13.71 13.71 -32767 +32767

BH11/OG MEASUREMENTS

BH11-O/G INTERNAL CONFIGURATION A 2034 0 960 0 +32767


1250-800/1A
BH11-O/G INTERNAL CONFIGURATION 33KV / √3 : 120 - 120/ √3 V MW 2035 -54.86 54.86 -32767 +32767

BH11-O/G INTERNAL CONFIGURATION MVAR 2036 -54.86 54.86 -32767 +32767

ED-682330, Rev-2 PAGE 76 OF 104


DOC. NO: EA-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST REV-2

33kV MEASUREMENTS

LOCAL RANGE SCADA RANGE CONTROL


FULL IEC 61850 DEVICE OPEN CLOSE LOOP TEST
HARDWIRE SOURCE IEC 101/104 SYSTEM
SOURCE PANEL ADDRESS / NAME/NUM IED NAME CT RATIO VT RATIO UNIT LOOP REMARKS
TB ADDRESS DATA/DEVICE
IDENTIFIER BER MIN MAX MIN MAX TEST CONTROL LDC
TYPE CENTRE

BH12-I/C MEASUREMENTS

BH12-I/C INTERNAL CONFIGURATION A 2037 0 2400 0 +32767

BH12-I/C INTERNAL CONFIGURATION KV 2038 0 39.6 -32767 +32767


2000/1A 33KV / √3 : 120 - 120/ √3 V
BH12-I/C INTERNAL CONFIGURATION MW 2039 -137.17 137.17 -32767 +32767

BH12-I/C INTERNAL CONFIGURATION MVAR 2040 -137.17 137.17 -32767 +32767

BH13/CAP MEASUREMENTS

BH13-CAP INTERNAL CONFIGURATION KV 2041 0 39.6 -32767 +32767


1250-800/1A 33KV / √3 : 120 - 120/ √3 V
BH13-CAP INTERNAL CONFIGURATION MVAR 2042 -54.86 54.86 -32767 +32767

BH14/OG MEASUREMENTS

BH14-O/G INTERNAL CONFIGURATION A 2043 0 960 0 +32767


1250-800/1A
BH14-O/G INTERNAL CONFIGURATION 33KV / √3 : 120 - 120/ √3 V MW 2044 -54.86 54.86 -32767 +32767

BH14-O/G INTERNAL CONFIGURATION MVAR 2045 -54.86 54.86 -32767 +32767

SPARE ADDRESS:

SAPRE ADDRESS (FROM) 2046

SAPRE ADDRESS (TO) 2053

ED-682330, Rev-2 PAGE 77 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

GENERAL ALARMS

ED-682330, Rev-2 PAGE 78 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

=MAIN ACDB XLOR-1:2 LOR-1 (6,8) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER F86 LOCK OUT RELAY OPTD ALARM/NORMAL

=MAIN ACDB XVR1:2 R3 (03,04) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER U/V PROTECTION OPTD ALARM/NORMAL

=MAIN ACDB XRLA-1:3,4 RL3 (5, 6) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER 50/51N PROTECTION OPTD ALARM/NORMAL

=MAIN ACDB 1AX:5,6 R8 (53,54) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER MCCB TRIP ALARM/NORMAL

=MAIN ACDB 1AX:3,4 R5A (21,22) BCU1_6MD85 NT MAIN ACDB BUS-A INCOMER MCCB OFF ALARM/NORMAL

XA1:1 Q1.1~Q1.19 (AUX.


=MAIN ACDB BCU1_6MD85 NT MAIN ACDB BUS -A O/G MCB/MCCB'S TRIP ALARM/NORMAL
XA2:1 1,2)

=MAIN ACDB XLOR-2:2 LOR-2 (6,8) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER F86 LOCK OUT RELAY OPTD ALARM/NORMAL

=MAIN ACDB XVR2:2 R4 (03,04) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER U/V PROTECTION OPTD ALARM/NORMAL

=MAIN ACDB XRLA-2:3,4 RL3 (5, 6) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER 50/51N PROTECTION OPTD ALARM/NORMAL

=MAIN ACDB 2AX:5,6 R9 (53,54) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER MCCB TRIP ALARM/NORMAL

=MAIN ACDB 2AX:3,4 R6A (21,22) BCU1_6MD85 NT MAIN ACDB BUS-B INCOMER MCCB OFF ALARM/NORMAL

=MAIN ACDB 3AX:5,6 R10 (03,04) BCU1_6MD85 NT MAIN ACDB BUS TIE MCCB TRIP ALARM/NORMAL

=MAIN ACDB 3AX:3,4 R7A (21,22) BCU1_6MD85 NT MAIN ACDB BUS TIE MCCB OFF ALARM/NORMAL

XB1:1 Q2.1~Q2.21 (BUX.


=MAIN ACDB BCU1_6MD85 NT MAIN ACDB BUS -B O/G MCB/MCCB'S TRIP ALARM/NORMAL
XB2:1 1,2)

XA1:1 Q1~Q33 (11,12),-QM


=SDB-1 BCU1_6MD85 NT SUB ACDB-1 (CONTROL ROOM) MCCB/MCB TRIP ALARM/NORMAL
XA2:1 (11,12)

XA1:1 Q1~Q44 (11,12), QM


=SDB-2 BCU1_6MD85 NT SUB ACDB-2 (CONTROL ROOM) MCCB/MCB TRIP ALARM/NORMAL
XA2:1 (11,12)
SPARK SS # 3 URGENT
XA1:1 Q1~Q6 (11,12), QM ALARM/NORMAL 4105
=SDB-3 BCU1_6MD85 NT SUB ACDB-3 (COMM. ROOM) MCCB/MCB TRIP ALARM/NORMAL ALARM
XA2:1 (11,12)

XA1:1 Q1~Q22 (11,12),


=ILP BCU1_6MD85 NT SUB ACDB ILP (CONTROL ROOM) MCCB/MCB TRIP ALARM/NORMAL
XA2:1 QM (111,2)

XA1:1 Q1~Q19 (11,12),


=OLP BCU1_6MD85 NT SUB ACDB ILP (CONTROL ROOM) MCCB/MCB TRIP ALARM/NORMAL
XA2:1 QM (111,2)

HVAC-PP1 X5:2 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 MCCB/MCB OFF ALARM / NORMAL

HVAC-PP1 X5:3 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 MCCB/MCB TRIP ALARM / NORMAL

HVAC-PP1 X5:4 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-1 IN MANUAL MODE ALARM / NORMAL

HVAC-PP2 X5:5 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 MCCB/MCB OFF ALARM / NORMAL

HVAC-PP2 X5:6 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 MCCB/MCB TRIP ALARM / NORMAL

HVAC-PP2 X5:7,9 CRXX-1(170,171) BCU1_6MD85 NT SUB ACDB HVAC-PP-2 IN MANUAL MODE ALARM / NORMAL

HVAC-CP1 X5:10 CR77-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM TEMP. HIGH ALARM ALARM / NORMAL

HVAC-CP1 X5:11 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM TEMP. HIGH ALARM ALARM / NORMAL

HVAC-CP1 X5:12,13 CRXX-1(170,171) BCU1_6MD85 NT RECORD ROOM TEMP. HIGH ALARM ALARM / NORMAL

HVAC-CP1 X5:14 CRXX-1(170,171) BCU1_6MD85 NT COMMUNICATION ROOM TEMP. HIGH ALARM ALARM / NORMAL

ED-682330, Rev-2 PAGE 79 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

HVAC-CP2 X5:15 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWGR ROOM TEMP. HIGH ALARM ALARM / NORMAL

HVAC-CP2 X5:16,18 CRXX-1(170,171) BCU1_6MD85 NT BATTERY ROOM TEMP. HIGH ALARM ALARM / NORMAL

HVAC-CP2 X5:17 CRXX-1(170,171) BCU1_6MD85 NT SECURITY ROOM TEMP. HIGH ALARM ALARM / NORMAL

+3UFLS X6:1,2 81-1 (F11,F12) BCU1_6MD85 NT SEC-A UNDER FREQUENCY RELAY 81-1 FAULTY ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-1_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 BLOCK ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-1_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 VT MCB TRIP ALARM/NORMAL

QA1(21,22)
+3UFLS X6:3 BCU1_6MD85 NT SEC-A UNDER FREQUENCY RELAY 81-1 DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA(11,3)

+3UFLS X6:8 81-2 (F11,F12) BCU1_6MD85 NT SEC-B UNDER FREQUENCY RELAY 81-2 FAULTY ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 BLOCK ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 VT MCB TRIP ALARM/NORMAL

QB1(21,22)
+3UFLS X6:9 BCU1_6MD85 NT SEC-B UNDER FREQUENCY RELAY 81-2 DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLC(11,3)

+3UFLS 81-1:B2 TS1(15,16) 81-2_P142 NT SEC-A UNDER FREQUENCY RELAY 81-1 UNDER TEST ALARM/NORMAL

+3UFLS 81-2:D14 TS2(15,16) 81-2_P142 NT SEC-B UNDER FREQUENCY RELAY 81-2 UNDER TEST ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 NT UFLS-1A SAS COMMUNICATION FAIL CH-1& CH-2 ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 NT UFLS-1B SAS COMMUNICATION FAIL CH-1& CH-2 ALARM/NORMAL

=SAS+CAP.1 X8:8 BCU1 (B10, B7) BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX FAULTY ALARM/NORMAL

Q1.3 (21,22)
=SAS+CAP.1 X8:4 BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX DC SUPPLY FAIL ALARM/NORMAL
74DC (14,6)

Q1.1 (21,22)
=SAS+CAP.1 X8:3 BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX DC MCB TRIP ALARM/NORMAL
Q1.2 (21,22)

=SAS+CAP.1 INTERNAL INTERNAL BCU1_6MD85 NT BCU1_6MD85 BCU-1 I/O BOX SAS COMM.FAIL CH-1 & CH-2 ALARM/NORMAL

27-1 (F11,F12) SPARK SS # 3


+3UVLS-1 X6:1,2 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-1/27-1A FAULTY ALARM/NORMAL FAULTY/ NORMAL 4106
27-1A (F11,F12) PROT. FLTY ALARM

27-2 (F11,F12)
+3UVLS-2 X6:1,2 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-2/27-2A FAULTY ALARM/NORMAL
27-2A (F11,F12)

+3UVLS-1 INTERNAL INTERNAL 27-1_P142 NT UNDER VOLTAGE RELAY 27-1/27-1A BLOCK ALARM/NORMAL

+3UVLS-2 INTERNAL INTERNAL 27-2_REC670 NT UNDER VOLTAGE RELAY 27-2-27-2A BLOCK ALARM/NORMAL

=E01+LCC F33 (2/11,2/12) F33 (2/11,2/12) 27-1 (P142) NT UNDER VOLTAGE RELAY 27-1/27-1A VT SUPPLY FAIL ALARM/NORMAL

=E02+LCC F33 (2/11,2/12) F33 (2/11,2/12) 27-2 (P142) NT UNDER VOLTAGE RELAY 27-2-27-2A VT SUPPLY FAIL ALARM/NORMAL

+3UVLS-1 27-1:B4 TS-1(15,16) 27-1_P142 NT UNDER VOLTAGE RELAY 27-1/27-1A UNDER TEST ALARM/NORMAL

TS-1(30,29), TS-
+3UVLS-2 27-1:B4 27-2_P142 NT UNDER VOLTAGE RELAY 27-2/27-2A UNDER TEST ALARM/NORMAL
4(29,30)

Q1A(21,22)
+3UVLS-1 X6:3 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-1/27-1A DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA (11, 3)

Q1A(21,22)
+3UVLS-2 X6:3 BCU1_6MD85 NT UNDER VOLTAGE RELAY 27-2/27-2A DC MCB TRIP/SUPPLY FAIL ALARM/NORMAL
RLA (11, 3)

ED-682330, Rev-2 PAGE 80 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

+3UVLS-1 INTERNAL INTERNAL 27-1_P142 NT UVLS-1 27-1 SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL

+3UVLS-1 INTERNAL INTERNAL 27-1A_P142 NT UVLS-1 27-1A SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL

+3UVLS-2 INTERNAL INTERNAL 27-2_P142 NT UVLS-2 27-2 SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL

+3UVLS-2 INTERNAL INTERNAL 27-2A_P142 NT UVLS-2 27-2A SAS COMMUNICATION CH-1 & CH-2 FAIL ALARM/NORMAL

=MAIN ACDB XRLA-1:1,2 RL2 (3,4) BCU1_6MD85 NT MAIN ACDB BUS-A 50/51N RELAY FAULTY ALARM/NORMAL

=MAIN ACDB XRLA-2:1,2 RL2 (3,4) BCU1_6MD85 NT MAIN ACDB BUS-B 50/51N RELAY FAULTY ALARM/NORMAL

=MAIN ACDB XTCS-1:1,2 TCS-1(7,9) BCU1_6MD85 NT MAIN ACDB BUS INCOMER-1 TC FAULTY ALARM/NORMAL

=MAIN ACDB XTCS-2:1,2 TCS-2(7,9) BCU1_6MD85 NT MAIN ACDB BUS INCOMER-2 TC FAULTY ALARM/NORMAL

=MAIN ACDB XTCS-3:1,2 TCS-3(7,9) BCU1_6MD85 NT MAIN ACDB BUS -TIE TC FAULTY ALARM/NORMAL

HVAC-CP1 X5:18 CRXX-1(170,171) BCU1_6MD85 NT HVAC-1 BCU1_6MD85 FAULT PACU (1A/1B) ALARM/NORMAL

HVAC-CP2 X5:19 CRXX-1(170,171) BCU1_6MD85 NT HVAC-2 BCU1_6MD85 FAULT PACU (2A/2B) ALARM/NORMAL

HVAC-CP1 X5:20 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS/CONTROL ROOM PACU-1A & 1B FAULTY ALARM / NORMAL

HVAC-CP1 X5:21 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS BUILDING VENTILATION FAULTY ALARM / NORMAL

HVAC-CP1 X5:22 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS BUILDING AIR CONDITION SYSTEM FAULTY ALARM / NORMAL

HVAC-CP1 X5:23 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM VENTILATION FAULTY ALARM / NORMAL

HVAC-CP1 X5:24 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM AIR CONDITION SYSTEM FAULTY ALARM / NORMAL

HVAC-CP1 X5:25 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM HIGH HUMIDITY-1 ALARM ALARM / NORMAL

HVAC-CP1 X5:26 CRXX-1(170,171) BCU1_6MD85 NT 115KV GIS ROOM HIGH HUMIDITY-2 ALARM ALARM / NORMAL

HVAC-CP1 X5:27 CRXX-1(170,171) BCU1_6MD85 NT CONTROL ROOM HIGH HUMIDITY ALARM ALARM / NORMAL

HVAC-CP2 X5:28 CRXX-1(170,171) BCU1_6MD85 NT TELECOM ROOM HIGH HYDROGEN ALARM ALARM / NORMAL

HVAC-CP2 X5:29 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWITCH GEAR BUILDING VENTILATION FAULTY ALARM / NORMAL

HVAC-CP2 X5:30 CRXX-1(170,171) BCU1_6MD85 NT 33KV SWITCH GEAR BUILDING AIR CONDITION SYSTEM FAULTY ALARM / NORMAL SPARK SS # 3
ALARM/
NON URGENT 4107
NORMAL
ALARM
HVAC-CP2 X5:31 CRXX-1(170,171) BCU1_6MD85 NT 33kV SWITCHGEAR ROOM HIGH HUMIDITY ALARM ALARM / NORMAL

HVAC-CP2 X5:32 CRXX-1(170,171) BCU1_6MD85 NT BATTERY ROOM VENTILATION FAULTY ALARM/NORMAL

QFHT (21,22)
=6D01+CBF/TCS.R1 50BF:D8 BCU1_6MD85 NT CBF/TCS PROTECTION PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)

QFHT (21,22)
=6D02+CBF/TCS.R1 50BF:D8 BCU1_6MD85 NT CBF/TCS PROTECTION PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)

QFHT (21,22)
+3UVLS-1 27-1:B2 BCU1_6MD85 NT UNDER VOLTAGE PANEL-1 AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)

+3UVLS-2 27-1:B2 C1(11,12) BCU1_6MD85 NT UNDER VOLTAGE PANEL-2 AC SUPPLY FAIL ALARM/NORMAL

QFPS(21,22)
+3UFLS 81-1(D12) BCU1_6MD85 NT UNDER FREQUENCY PANEL AC SUPPLY FAIL ALARM/NORMAL
QFHT(21,22)

QFHT (21,22)
=SAS+CAP.1 X8:7 QFPS (21,22) BCU1_6MD85 NT SAS CAP.1 PANEL AC SUPPLY FAIL ALARM/NORMAL
KAC (14, 6)

QFHT (21,22)
AMI X6:5 BCU1_6MD85 NT AMI PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)

QFHT (21,22)
=3RM1 X6:3 BCU1_6MD85 NT REVENUE METER PANEL AC SUPPLY FAIL ALARM/NORMAL
QFPS (21,22)

FRM-1_L2-M368 (T9,
FACP X6:3 BCU1_6MD85 NT 115kV GIS ROOM FIRE SYSTEM OPTD ALARM / NORMAL
T10)

FRM-1_L1-M353 (T9,
FACP X6:4 BCU1_6MD85 NT 33KV SWITCH GEAR FIRE SYSTEM OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M354 (T9,
FACP X6:5 BCU1_6MD85 NT CONTROL ROOM FIRE SYSTEM OPTD ALARM / NORMAL
T10)

ED-682330, Rev-2 PAGE 81 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
FRM-1_L1-M355 (T9,
FACP X6:6 BCU1_6MD85 NT SECURITY EQUIPMENT ROOM FIRE SYSTEM OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M77 (T9,
FACP X6:7 BCU1_6MD85 NT CLEAN AGENT MANUAL RELEASE OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M77 (T9, OPERATION OF CLEAN AGENT/CO2 PRESSURE SWITCH ON SYSTEM


FACP X6:8 BCU1_6MD85 NT ALARM / NORMAL
T10) HEADER

FRM-1_L1-M102 (T9, SPARK SS # 3 SSGA FIRE


FACP X6:9 BCU1_6MD85 NT CLEAN AGENT/CO2 MANUAL RELEASE UNIT OPERATED ALARM / NORMAL OPERATE/NORMAL 4108
T10) PROT. OPTD

FRM-1_L1-M104 (T9,
FACP X6:10 BCU1_6MD85 NT FIRE SYSTEM COMPRESSOR OPTD ALARM / NORMAL
T10)

FRM-1_L1-MXXX (T9,
FACP X6:11 BCU1_6MD85 NT AUXILIARY TRANSFORMER-1 FIRE SYSTEM OPTD ALARM / NORMAL
T10)

FRM-1_L1-MXXX (T9,
FACP X6:12 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 FIRE SYSTEM OPTD ALARM / NORMAL
T10)

FRM-1_L1-M84 (T9,
FACP X6:13 BCU1_6MD85 NT FIRE SYSTEM DIESEL PUMP OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M85 (T9,
FACP X6:14 BCU1_6MD85 NT FIRE SYSTEM ELECTRIC PUMP OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M82 (T9,
FACP X6:15 BCU1_6MD85 NT FIRE PUMP HOUSE FIRE SYSTEM OPERATED ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9,
FACP X6:3 BCU1_6MD85 NT 115KV GIS ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M353 (T9,
FACP X6:4 BCU1_6MD85 NT CONTROL ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M354 (T9,
FACP X6:5 BCU1_6MD85 NT 33KV SWGR ROOM SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M355 (T9,
FACP X6:6 BCU1_6MD85 NT MANUAL CALL POINT OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M77 (T9,
FACP X6:7 BCU1_6MD85 NT SECURITY ROOM/ GUARD HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M77 (T9,
FACP X6:8 BCU1_6MD85 NT CAPACITOR BANK-1 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10) SPARK SS # 3 SSGA
SMOKE DETECTOR OPERATE/NORMAL 4109
FRM-1_L1-M102 (T9, OPTD
FACP X6:9 BCU1_6MD85 NT CAPACITOR BANK-2 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M104 (T9,
FACP X6:10 BCU1_6MD85 NT AUXILIARY TRANSFORMER-1 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-MXXX (T9,
FACP X6:11 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-MXXX (T9,
FACP X6:12 BCU1_6MD85 NT FIRE PUMP HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M84 (T9,
FACP X6:13 BCU1_6MD85 NT GUARD HOUSE SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M85 (T9,
FACP X6:14 BCU1_6MD85 NT TELECOM SHELTER SMOKE DETECTOR OPERATED ALARM / NORMAL
T10)

FRM-1_L1-M80 (T9,
FACP X6:16 BCU1_6MD85 NT 115kV GIS ROOM FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L1-MXX (T9,
FACP X6:17 BCU1_6MD85 NT CONTROL BUILDING FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L1-M79 (T9,
FACP X6:18 BCU1_6MD85 NT 33kV SWGR BUILDING FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L2-M362 (T9,
FACP X6:19 BCU1_6MD85 NT SECURITY HOUSE FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L1-M78 (T9,
FACP X6:20 BCU1_6MD85 NT CAPACITOR BANK-1 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L2-M364 (T9,
FACP X6:21 BCU1_6MD85 NT CAPACITOR BANK-2 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9, FAULTY/


FACP X6:22 BCU1_6MD85 NT AUXILIARY TRANSFORMER-1 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL SSGA FIRE SYSTEM 4110
T10) NORMAL

ED-682330, Rev-2 PAGE 82 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA
SSGA FIRE LITRA
SYSTEM
FAULTY/
TEXT INDEX 4110 NAME/ALARM LDC
NORMAL TYPE CENTRE
CODE
FRM-1_L2-M365 (T9,
FACP X6:23 BCU1_6MD85 NT AUXILIARY TRANSFORMER-2 FIRE ALARM SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9,
FACP X6:24 BCU1_6MD85 NT LOW FUEL IN DIESEL TANK ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9,
FACP X6:25 BCU1_6MD85 NT CLEAN AGENT SYSTEM IN MANUAL MODE ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9,
FACP X6:26 BCU1_6MD85 NT CLEAN AGENT FIRE SYSTEM FAULTY ALARM / NORMAL
T10)

FRM-1_L1-M83 (T9,
FACP X6:27 BCU1_6MD85 NT FIRE SYSTEM COMPRESSOR FAULTY ALARM / NORMAL
T10)

FRM-1_L2-M365 (T9,
FACP X6:28 BCU1_6MD85 NT FIRE FIGHTING SYSTEM IN MANUAL MODE ALARM / NORMAL
T10)

ED-682330, Rev-2 PAGE 83 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

+3UVLS-1 27-1:D2 94UV-11(1,3) 27-1_P142 NT UNDER VOLTAGE 27-1 STAGE-1 OPTD ALARM/NORMAL

+3UVLS-1 27-1:D4 94UV-21(1,3) 27-1_P142 NT UNDER VOLTAGE 27-1 STAGE-2 OPTD ALARM/NORMAL

+3UVLS-1 27-1:D6 94UV-31(1,3) 27-1A_P142 NT UNDER VOLTAGE 27-1 STAGE-3 OPTD ALARM/NORMAL

+3UVLS-2 27-2:D2 94UV-11(1,3) 27-2_P142 NT UNDER VOLTAGE 27-2 STAGE-1 OPTD ALARM/NORMAL

+3UVLS-2 27-2:D4 94UV-21(1,3) 27-2_P142 NT UNDER VOLTAGE 27-2 STAGE-2 OPTD ALARM/NORMAL

+3UVLS-2 27-2:D6 94UV-31(1,3) 27-2A_P142 NT UNDER VOLTAGE 27-2 STAGE-3 OPTD ALARM/NORMAL
SPARK SS # 3 UV LOAD
OPERATE / NORMAL 4111
SHED OPTD.
+3UVLS-1 X6:4 94-11 (14,16) 27-1_P142 NT UNDER VOLTAGE STAGE-1 TRIP RELAYS (94UV-11) OPTD ALARM/NORMAL

+3UVLS-1 X6:5 94-21 (14,16) 27-1_P142 NT UNDER VOLTAGE STAGE-2 TRIP RELAYS (94UV-21) OPTD ALARM/NORMAL

+3UVLS-1 X6:6 94-31 (14,16) 27-1A_P142 NT UNDER VOLTAGE STAGE-3 TRIP RELAYS (94UV-31) OPTD ALARM/NORMAL

+3UVLS-2 X6:4 94UV-11(1,3) 27-2_P142 NT UNDER VOLTAGE STAGE-1 TRIP RELAYS (94UV-11) OPTD ALARM/NORMAL

+3UVLS-2 X6:5 94UV-21(1,3) 27-2_P142 NT UNDER VOLTAGE STAGE-2 TRIP RELAYS (94UV-21) OPTD ALARM/NORMAL

+3UVLS-2 X6:6 94UV-31(1,3) 27-2A_P142 NT UNDER VOLTAGE STAGE-3 TRIP RELAYS (94UV-31) OPTD ALARM/NORMAL

ED-682330, Rev-2 PAGE 84 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-1 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-2 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-3 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-1_P142 T SEC A UNDER FREQUENCY STAGE-4 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-1 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-2 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-3 OPTD ALARM/NORMAL

+3UFLS INTERNAL INTERNAL 81-2_P142 T SEC B UNDER FREQUENCY STAGE-4 OPTD ALARM/NORMAL
SPARK SS # 3 UF LOAD
OPERATE / NORMAL 4112
SHED OPTD.
+3UFLS X6:4 '94UF-11(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-1 TRIP RELAY (94UF-1A) OPTD ALARM/NORMAL

+3UFLS X6:5 94UF-21(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-2 TRIP RELAY (94UF-2A) OPTD ALARM/NORMAL

+3UFLS X6:6 '94UF-31(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-3 TRIP RELAY (94UF-3A) OPTD ALARM/NORMAL

+3UFLS X6:7 '94UF-41(82,88) 81-1_P142 T SEC A UNDER FREQUENCY STAGE-4 TRIP RELAY (94UF-4A) OPTD ALARM/NORMAL

+3UFLS X6:10 '94UF-12(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-1 TRIP RELAY (94UF-1B) OPTD ALARM/NORMAL

+3UFLS X6:11 94UF-22(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-2 TRIP RELAY (94UF-2B) OPTD ALARM/NORMAL

+3UFLS X6:12 '94UF-32(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-3 TRIP RELAY (94UF-3B) OPTD ALARM/NORMAL

+3UFLS X6:13 '94UF-42(82,88) 81-2_P142 T SEC B UNDER FREQUENCY STAGE-4 TRIP RELAY (94UF-4B) OPTD ALARM/NORMAL

FACP X6:1 L1-M16-Z22 BCU1_6MD85 NT FIRE ALARM TROUBLE ALARM/NORMAL


SPARK SS # 3 FIRE
FAULTY/ NORMAL 4113
SYSTEM
FACP X6:3 L1-M17-Z22 BCU1_6MD85 NT NOVAC SYSTEM TROBLE ALARM/NORMAL

Q101, Q102, Q103


=MAIN DCDB XMA:1,2 BCU1_6MD85 NT MAIN DCDB INCOMER A & B (CONTROL ROOM) MCCB TRIP ALARM/NORMAL
(11, 12)

Q1.1~Q1.33 (11,12),
=SUB DCDB-1 X1A:1,2 Q2.1~Q2.30 (11,12), BCU1_6MD85 NT SUB DCP-1 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)

Q1.1~Q1.24 (11,12),
=SUB DCDB-2 X1A:1,2 Q2.1~Q2.24 (11,12), BCU1_6MD85 NT SUB DCP-2 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)

Q1.1~Q1.39 (11,12),
=SUB DCDB-3 X1A:1,2 Q2.1~Q2.39 (11,12), BCU1_6MD85 NT SUB DCP-3 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)

Q1.1~Q1.63 (11,12),
=SUB DCDB-4 X1A:1,2 Q2.1~Q2.60 (11,12), BCU1_6MD85 NT SUB DCP-4 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)

Q1.1~Q1.9 (11,12),
=SUB DCDB-5 X1A:1,2 Q2.1~Q2.9 (11,12), BCU1_6MD85 NT SUB DCP-5 (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
R8,9,10(13,14)

Q1~Q6 (11,12),
=SUB DCDB-1C X1A:1,2 BCU1_6MD85 NT SUB DCP-1C (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL
A001 (95,96)
SPARK SS # 3
Q1~Q6 (11,12), ALARM/NORMAL 4114
=SUB DCDB-2C X1A:1,2 BCU1_6MD85 NT SUB DCP-2C (CONTROL ROOM) MCB TRIP/OFF ALARM/NORMAL DC SUPPLY FAIL
A001 (95,96)

ED-682330, Rev-2 PAGE 85 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER SPARK SS # 3
ALARM/NORMAL ADDRESS
4114 ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA
DC SUPPLY FAIL TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE
Q1.1~Q1.8
=MAIN DCDB X1A:1,2 BCU1_6MD85 NT MAIN DCDB BUS-A (CONTROL ROOM) MCCB OFF ALARM/NORMAL
(11, 12)

Q2.1~Q2.7
=MAIN DCDB X1B:1,2 BCU1_6MD85 NT MAIN DCDB BUS-B (CONTROL ROOM) MCCB OFF ALARM/NORMAL
(11, 12)

RLB(11,3)
+UVLS-1 27-1:D14 27-1_P142 NT UNDER VOLTAGE PANEL RELAY 27-1/27-1A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLB(11,3)
+UVLS-2 27-2:D14 27-2_P142 NT UNDER VOLTAGE PANEL RELAY 27-2/27-2A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLC(11,3)
+UVLS-1 27-1:D16 27-1_P142 NT UNDER VOLTAGE PANEL RELAY 27-1/27-1A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QA3(21,22)
RLC(11,3)
+UVLS-2 27-2:D16 27-2_P142 NT UNDER VOLTAGE PANEL RELAY 27-2/27-2A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QA3(21,22)
RLB(11,3)
+UFLS 81-1:DI4 81-1_P142 NT UNDER FREQUENCY PANEL RELAY 81-A IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QA2(21,22)
RLD(11,3)
+UFLS 81-2:DI2 81-2_P142 NT UNDER FREQUENCY PANEL RELAY 81-B IN/OUT DC SUPPLY FAIL ALARM / NORMAL
QB2(21,22)
RLE(11,3)
+UFLS 81-1:DI6 81-2_P142 NT UNDER FREQUENCY PANEL RELAY 81-A INDICATION DC SUPPLY FAIL ALARM / NORMAL
QC1(21,22)

AVC.1 X6:4 Q16 (21,22) BCU1_6MD85 NT GT-1 AVC PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL

AVC.2 X6:4 Q16 (21,22) BCU1_6MD85 NT GT-2 AVC PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL

QDC1(21,22)
ACCS X6:5 BCU1_6MD85 NT ACCS PANEL INDICATION DC SUPPLY FAIL ALARM / NORMAL
RLA(11,3)

125V DC CHARGER-1 X30:1,3 BA300 (X30:1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1/2 EARTH FAULT ALARM/NORMAL

125V DC CHARGER-2 X30:4,5 BA300 (X30:4,5) BCU1_6MD85 NT 125V BATTERY CHARGER-1/2 URGENT ALARM ALARM/NORMAL

125V DC CHARGER-1 X5:16,18 J6(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 MAINS MCCB TRIP ALARM/NORMAL

125V DC CHARGER-1 X5:22,24 J8(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 BATTERY MCCB TRIP ALARM/NORMAL

125V DC CHARGER-1 X5:19,21 J7(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 DC MCCB TRIP ALARM/NORMAL

125V DC CHARGER-1 X5:1,3 J1(1,2) BCU1_6MD85 NT 125V BATTERY CHARGER-1 FAILURE ALARM/NORMAL

125V DC CHARGER-1 X5:13,15 J5(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 AC SUPPLY FAIL ALARM/NORMAL

125V DC CHARGER-1 X5:10,12 J4(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 TEMPERATURE HIGHALARM ALARM/NORMAL

125V DC CHARGER-1 X5:7,9 J3(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 UNDER VOLTAGE ALARM ALARM/NORMAL
SPARK SS # 3 125V
BATTERIES CHARGER ALARM / NORMAL 4115
FAIL
125V DC CHARGER-1 X5:4,6 J2(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-1 UNDER/OVER VOLTAGE ALARM ALARM/NORMAL

125V DC CHARGER-1 X5:1,3 J1(1,3) BCU1_6MD85 NT 125V BATTERY FAILURE ALARM ALARM/NORMAL

125V DC CHARGER-1 X5:16,18 J6(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 MAINS MCCB TRIP ALARM/NORMAL

125V DC CHARGER-2 X5:19,21 J7(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 DC MCCB TRIP ALARM/NORMAL

125V DC CHARGER-2 X5:22,24 J8(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 FAILURE ALARM/NORMAL

125V DC CHARGER-2 X5:13,15 J5(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 AC SUPPLY FAIL ALARM/NORMAL

125V DC CHARGER-2 X5:7,9 J3(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 TEMPERATURE HIGHALARM ALARM/NORMAL

125V DC CHARGER-2 X5:4,6 J2(1,5) BCU1_6MD85 NT 125V BATTERY CHARGER-2 UNDER VOLTAGE ALARM ALARM/NORMAL

125V DC CHARGER-2 X5:10,12 J4(1,3) BCU1_6MD85 NT 125V BATTERY CHARGER-2 UNDER/OVER VOLTAGE ALARM ALARM/NORMAL

ED-682330, Rev-2 PAGE 86 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

QFRM1 (21,22)
QFRM2 (21,22)
QFRM3 (21,22)
=3RM1 X6:1,2 BCU1_6MD85 NT REVENUE METER PANEL DC MCB TRIP ALARM/NORMAL
QFRM4 (21,22)
QFRM5 (21,22)
QFRM6 (21,22)

QFVRM1 (21,22)
QFVRM3 (21,22)
=3RM1 X6:4 BCU1_6MD85 NT RM VT MCB TRIP ALARM/NORMAL
QFVRM5 (21,22)
QFVRM6 (21,22)

=3RM1 X5:3,4 RM1 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-1 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

=3RM1 X5:12,13 RM2 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-2 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

=3RM1 X5:21,22 RM3 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-3 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-3 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

=3RM1 X5:30,31 RM4 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-4 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-4 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

=3RM1 X5:39,40 RM5 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-5 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-5 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

=3RM1 X5:48,49 RM6 (50, 51) BCU1_6MD85 NT REVENUE METER PANEL-1 RM-6 FAULTY ALARM/NORMAL

=3RM1 INTERNAL INTERNAL BCU1_6MD85 NT REVENUE METER PANEL-1 RM-6 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL SPARK SS # 3
AMR/AMI NON URGENT ALARM / NORMAL 4116
ALARM
AMI X5:8 RM1 (50, 51) BCU1_6MD85 NT AMI PANEL RM1 METER FAULTY ALARM/NORMAL

AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL RM1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

AMI X5:9 RM2 (50, 51) BCU1_6MD85 NT AMI PANEL RM2 METER FAULTY ALARM/NORMAL

AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL RM2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

AMI X5:10 PQM1 (4C, 4NC) BCU1_6MD85 NT AMI PANEL PQM-1 METER FAULTY ALARM/NORMAL

AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL PQM-1 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

AMI X5:11 PQM2 (4C, 4NC) BCU1_6MD85 NT AMI PANEL PQM-2 METER FAULTY ALARM/NORMAL

AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI PANEL PQM-2 TELECOMM. BOTH CHANNELS FAIL ALARM/NORMAL

ES (C01,NC1)
AMI X6:12 BCU1_6MD85 NT AMI ETHERNET SWITCH FAIL ALARM/NORMAL
ES (C02,NC2)

AMI INTERNAL INTERNAL BCU1_6MD85 NT AMI FILING OF METER MEMORY ALARM/NORMAL

QFVPQM1 (21, 22)


QFVRM1 (21, 22)
AMI X6:4 BCU1_6MD85 NT PQM/RM VT MCB TRIP ALARM/NORMAL
QFVRM2 (21, 22)
QFVPQ1 (21, 22)

QFDC1 (21,22)
AMI X6:2 BCU1_6MD85 NT AMI PANEL DC MCB TRIP ALARM/NORMAL
QFDC2 (21,22)

QFRM1 (21,22)
QFRM2 (21,22)
QFPQM1 (21,22)
AMI X6:3 BCU1_6MD85 NT AMI PANEL DC SUPPLY FAIL ALARM/NORMAL
QFPQM2 (21,22)
QES (21,22)
QFVTF (21,22)

DVM CABINET ,-- K01: (11,14) BCU1_6MD85 NT FOX615 DVM RACK MAJOR ALARM ALARM / NORMAL

SPARK SS # 3 ALARM/
MPLS-TP X101:1,3 K01: (21,24) BCU1_6MD85 NT MPLS MAJOR ALARM ALARM / NORMAL 4117
COMM URGENT NORMAL

MPLS-TP X101:1,6 K01: (31,34) BCU1_6MD85 NT MPLS MINOR ALARM ALARM / NORMAL

SPARK SS # 3 ALARM/
DVM CABINET ,-- K02: (11,14) BCU1_6MD85 NT FOX615 DVM RACK MINOR ALARM ALARM / NORMAL 4118
COMM NON-URGENT NORMAL

ED-682330, Rev-2 PAGE 87 OF 104


DOC. NO: ED-682330

REV-2

HMI / ALARM / EVENT TEXT RECEIVED AT CONTROL CENTRE CONTROL SYSTEM DATA CLOSE LOOPTEST
HARDWIRED FULL IEC 61850
DEVICE IEC 101/104 TYPE OPEN LOOP
SOURCE PANEL SOURCE ADDRESS / IED NAME TYPE T/NT POINT REMARKS
NAME/NUMBER ADDRESS ID DEVICE TEST CONTROL
TB. NO IDENTIFIER DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX NAME/ALARM LDC
TYPE CENTRE
CODE

SAPRE ADDRESS:

SPARE ADDRESS (FROM) 4118

SPARE ADDRESS (TO) 4121

ED-682330, Rev-2 PAGE 88 OF 104


CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3

SAS ALARMS

ED-682330, Rev-2 PAGE 89 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 APPLICATION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 LAN-A STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 LAN-B STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CENTRAL DB/STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CPU TEMPERATURE ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 CLIENT SERVER PROTOCOL ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 SNMP ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 APPLICATION LICENSE ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 HARD DISK CAPACITY ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-1 DC POWER SUPPLY ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-2 DC POWER SUPPLY ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 1 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 2CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 3 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 101 PORT NO 4 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 104 PORT NO 1 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL GATEWAY-1 GTW-1 NON-TRIP SCADA GATEWAY -1 IEC 104 PORT NO 2 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 APPLICATION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 LAN-A STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 LAN-B STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CENTRAL DB/STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CPU TEMPERATURE ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 CLIENT SERVER PROTOCOL ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 SNMP ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 APPLICATION LICENSE ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -1 HARD DISK CAPACITY ALARM / NORMAL

ED-682330, Rev-2 PAGE 90 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-3 DC POWER SUPPLY ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP CONVERTOR-4 DC POWER SUPPLY ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 1 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 2CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 3 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 101 PORT NO 4 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 104 PORT NO 1 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL GATEWAY-2 GTW-2 NON-TRIP SCADA GATEWAY -2 IEC 104 PORT NO 2 CONNECTION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 APPLICATION STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 LAN-A STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 LAN-B STATUS ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CPU TEMP ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 APPLICATION STATUS SYNCHRONISATION ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CLIENT SERVER PROTOCOL ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 SNMP ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 HARD CAPACITY ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP STATION SERVER -1 CENTRAL DB/STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 APPLICATION STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 LAN-A STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 LAN-B STATUS ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CPU TEMP ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 APPLICATION STATUS SYNCHRONISATION ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CLIENT SERVER PROTOCOL ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 SNMP ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 HARD DISK STATUS (HDD/SSD) ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 HARD CAPACITY ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP STATION SERVER -2 CENTRAL DB/STATUS ALARM / NORMAL

ED-682330, Rev-2 PAGE 91 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS STATUS ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS LAN-A STATUS ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS LAN-B STATUS ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS HARD DISK STATUS (HDD/SSD) ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS HARD DISK CAPACITY ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS CPU TEMP ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 3 INTERNAL EWS EWS NON-TRIP EWS SNMP ALARM / NORMAL

=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87T1(SET-1) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87T2(SET-2) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87T1(SET-1) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87T2(SET-2) PROTN RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 (CP1) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 (CP2) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 (CP1) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 (CP2) PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 27A PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-1 F1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-2 27A PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 F1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

ED-682330, Rev-2 PAGE 92 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 CLOCK SYNCHRONIZATION ERROR ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 POWER SUPPLY DC ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 DC-1 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -1 DC-2 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 POWER SUPPLY DC ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 DC-1 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SCADA GATEWAY -2 DC-2 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 POWER SUPPLY DC ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 DC-1 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -1 DC-2 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 POWER SUPPLY DC ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 DC-1 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP STATION SERVER -2 DC-2 MCB ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS ALARM ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS DC-1 MCB ALARM / NORMAL
SPARK SS # 3
STATION
=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP EWS DC-2 MCB ALARM / NORMAL Alarm/Normal 4122
URGENT
ALARM
=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 STATUS ALARM / NORMAL

ED-682330, Rev-2 PAGE 93 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT SPARK SS CENTER
#3 CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT
FULL IEC 61850 STATION OPEN
HARDWIRED TYPE Alarm/Normal IEC4122
101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME URGENT TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM ALARM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 DC-1 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 ROUTER-1 DC-2 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 STATUS ALARM / NORMAL

=SAS+SP 2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 DC-1 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 ROUTER-2 DC-2 MCB ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 STATUS ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 ANTENNA ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 GPS SYNC ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NTP SYNC ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NETWORK LAN-A ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 NETWORK LAN-B ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 1 SNMP GPS-1 GPS-1 NON-TRIP SAS PANEL SP1 GPS -1 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 STATUS ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 DC-1 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 GPS -1 DC-2 MCB ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 STATUS ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 ANTENNA ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 GPS SYNC ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NTP SYNC ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NETWORK LAN-A ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 NETWORK LAN-B ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 2 SNMP GPS-2 GPS-2 NON-TRIP SAS PANEL SP2 GPS -2 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 STATUS ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 DC-1 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 GPS -2 DC-2 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 1 TEMPERATURE HIGH ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 2 TEMPERATURE HIGH ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL 3 TEMPERATURE HIGH ALARM / NORMAL

ED-682330, Rev-2 PAGE 94 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 TEMPERATURE HIGH ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 TEMPERATURE HIGH ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 STATUS ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 DC-1 MCB ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 DC-2 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 DC-1 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 DC-2 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 DC-1 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 DC-2 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 DC-1 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 DC-2 MCB ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 STATUS ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 STATUS ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 STATUS ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 STATUS ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 DC-1 MCB ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 DC-2 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 DC-1 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 DC-2 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 DC-1 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 DC-2 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 DC-1 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 DC-2 MCB ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 STATUS ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 STATUS ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 STATUS ALARM / NORMAL

=SAS+SP1 SNMP ROUTER -1 FW-1 NON-TRIP SAS PANEL SP1 ROUTER-1 SETTING CHANGES ALARM / NORMAL

=SAS+SP2 SNMP ROUTER -2 FW-2 NON-TRIP SAS PANEL SP2 ROUTER-2 SETTING CHANGES ALARM / NORMAL

SAS+SLA1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ESWA11 SETTING CHANGES ALARM / NORMAL

SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ESWA01 SETTING CHANGES ALARM / NORMAL

SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ESWA02 SETTING CHANGES ALARM / NORMAL

SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ESWA03 SETTING CHANGES ALARM / NORMAL

SAS+SLB1 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ESWB11 SETTING CHANGES ALARM / NORMAL

SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ESWB11 SETTING CHANGES ALARM / NORMAL

ED-682330, Rev-2 PAGE 95 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ESWB02 SETTING CHANGES ALARM / NORMAL

SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ESWB03 SETTING CHANGES ALARM / NORMAL

SAS+SLA1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ESWA11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ESWA01 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ESWA02 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ESWA03 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLB1 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1ESWB11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1ESWB11 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1ESWB02 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1ESWB03 MAC- BASED PORT SECURITY VIOLATED ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA11 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 POWER SUPPLY DC-1 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 POWER SUPPLY DC-2 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 ETHERNET SWITCH-ESWA11 PORT01 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 ETHERNET SWITCH-ESWA11 PORT02 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS CONSOLE DESK A3-PRINTER ETHERNET SWITCH-ESWA11 PORT03 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 SRV-1 ETHERNET SWITCH-ESWA11 PORT05 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 SRV-2 ETHERNET SWITCH-ESWA11 PORT06 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 GW-1 ETHERNET SWITCH-ESWA11 PORT07 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 GW-2 ETHERNET SWITCH-ESWA11 PORT08 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP1 GPS-1 ETHERNET SWITCH-ESWA11 PORT09 ALARM / NORMAL

ED-682330, Rev-2 PAGE 96 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP2 GPS-2 ETHERNET SWITCH-ESWA11 PORT10 ALARM / NORMAL

=SAS+SP 1 SNMP ESWA11 ESWA11 NON-TRIP SAS PANEL SP3 EWS ETHERNET SWITCH-ESWA11 PORT11 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT01 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT02 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA01 PORT03 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT01 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT02 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA02 PORT03 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT01 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT02 ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP SAS PANEL SLA1 ETHERNET SWITCH-ESWA03 PORT03 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT01 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT02 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB11 PORT03 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS CONSOLE DESK A4-PRINTER ETHERNET SWITCH-ESWB11 PORT03 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 SRV-1 ETHERNET SWITCH-ESWB11 PORT05 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 SRV-2 ETHERNET SWITCH-ESWB11 PORT06 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 GW-1 ETHERNET SWITCH-ESWB11 PORT07 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 GW-2 ETHERNET SWITCH-ESWB11 PORT08 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP1 GPS-1 ETHERNET SWITCH-ESWB11 PORT09 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP2 GPS-2 ETHERNET SWITCH-ESWB11 PORT10 ALARM / NORMAL

=SAS+SP 2 SNMP ESWB11 ESWB11 NON-TRIP SAS PANEL SP3 EWS ETHERNET SWITCH-ESWB11 PORT11 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT01 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT02 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB01 PORT03 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT01 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT02 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB02 PORT03 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT01 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT02 ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP SAS PANEL SLB1 ETHERNET SWITCH-ESWB03 PORT03 ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-2/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 AC SUPPLY ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

ED-682330, Rev-2 PAGE 97 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 KVM-1 TRAY DC SUPPLY ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 AC SUPPLY ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 KVM 2 TRAY DC SUPPLY ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 AC SUPPLY ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 AC SUPPLY ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+SLA1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLA1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 AC SUPPLY ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+SLB1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SLB1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 AC SUPPLY ALARM / NORMAL

=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 DC SUPPLY-1 / MCB TRIP ALARM / NORMAL

=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 DC SUPPLY-2 / MCB TRIP ALARM / NORMAL

=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 COMMON BCU STATUS ALARM / NORMAL

=SAS+CAP1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL CAP1 COMMON BCU CONTROL SUPPLY ALARM / NORMAL

+FOPPA.1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP FOPPA.1 AC MCB TRIP ALARM / NORMAL

+FOPPB.1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP FOPPB.1 AC MCB TRIP ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PRINTER A3 AC MCB TRIP ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PRINTER A4 AC MCB TRIP ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP3 REMOTE SCREEN DC SUPPLY ALARM / NORMAL

=SAS+SP 3 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP LARGE SCREEN DC SUPPLY ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 REMOTE SCREEN DC SUPPLY ALARM / NORMAL

=SAS+SP 1 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP1 SPLITTER-1/2 FAIL ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 REMOTE SCREEN DC FAIL ALARM / NORMAL

=SAS+SP 2 HARDWIRED COMMON BCU-1/6MD85 COMBCU_1 NON-TRIP SAS PANEL SP2 SPLITTER-1/2 FAIL ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 STATUS ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 NETWORK ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 ONLINE ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 OUT OF PAPER ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 TONER ALARM / NORMAL

ED-682330, Rev-2 PAGE 98 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 DOOR ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A3 PRN-A3 NON-TRIP PRINTER A3 SUPPLY ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 STATUS ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 NETWORK ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 ONLINE ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 OUT OF PAPER ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 TONER ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 DOOR ALARM / NORMAL

=SAS CONSOLE SNMP PRN-A4 PRN-A4 NON-TRIP PRINTER A4 SUPPLY ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME# LOG-IN ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME# CHANGE USER# AUTHORITY ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME#CREATE NEW USER IS# ALARM / NORMAL

=SAS+SP 1 INTERNAL SERVER-1 SRV-1 NON-TRIP SAS USERNAME#DELETE USER IS# ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME# LOG-IN ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME# CHANGE USER# AUTHORITY ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME#CREATE NEW USER IS# ALARM / NORMAL

=SAS+SP 2 INTERNAL SERVER-2 SRV-2 NON-TRIP SAS USERNAME#DELETE USER IS# ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP CB A601 (BCU CH-A) ESWA01 PORT-05 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP CB A602 (BCU CH-A) ESWA01 PORT 06 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 87L1(FPFM CH-A) ESWA01 PORT 07 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 87L2(FPSM CH-A) ESWA01 PORT 08 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-1 (50CBFTCS CH-A) ESWA01 PORT 09 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 87L1(FPFM CH-A) ESWA01 PORT10 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 87L2(FPSM CH-A) ESWA01 PORT11 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP UGC FDR-2 (50CBFTCS CH-A) ESWA01 PORT12 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 87T1(SET-1 CH-A) ESWA01 PORT 13 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 (IO BOX CH-A) ESWA01 PORT14 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 87T2(SET-2 CH-A) ESWA01 PORT 15 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 87T1(SET-1 CH-A) ESWA01 PORT 16 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 (IO BOX CH-A) ESWA01 PORT 17 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 87T2(SET-2 CH-A) ESWA01 PORT 18 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-1 (AVC CH-A) ESWA01 PORT 19 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA01 ESWA01 NON-TRIP TRAFO-2 (AVC CH-A) ESWA01 PORT 20 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B413 (BCPU CH-A) ESWA02 PORT 05 FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 99 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B414 (BCPU CH-A) ESWA02 PORT 06 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A402 (BCPU CH-A) ESWA02 PORT 07 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B415 (BCPU CH-A) ESWA02 PORT 08FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B416 (BCPU CH-A) ESWA02 PORT 09 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A401 (BCPU CH-A) ESWA02 PORT 10FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B421 (BCPU CH-A) ESWA02 PORT 11 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B422 (BCPU CH-A) ESWA02 PORT 12FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB A403 (BCPU CH-A) ESWA02 PORT 13 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B423 (BCPU CH-A) ESWA02 PORT 14 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CB B424 (BCPU CH-A) ESWA02 PORT 15 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-1 (CP1 CH-A) ESWA02 PORT 16 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-1 (CP2 CH-A) ESWA02 PORT 17 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA02 ESWA02 NON-TRIP CAP.PANEL-2 (CP1 CH-A) ESWA02 PORT 18 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA02 NON-TRIP CAP.PANEL-2 (CP2 CH-A) ESWA02 PORT 19 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA02 NON-TRIP UNDER VOLTAGE-1 (27A CH-A) ESWA02 PORT 20 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-1 (F1 CH-A) ESWA03 PORT 05 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-2 (27A CH-A) ESWA03 PORT 06 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER VOLTAGE-2 (F1 CH-A) ESWA03 PORT 07 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER FREQUENCY (81A-1 CH-A) ESWA03 PORT 08 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP UNDER FREQUENCY (81A-2 CH-A) ESWA03 PORT 09 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP ACCS (CH-A) ESWA03 PORT 10 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP COMMON BCU 1 (CH-A) ESWA03 PORT 11 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A601 DGA1 (CH-A) ESWA03 PORT 12 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A602 DGA2 (CH-A) ESWA03 PORT 13 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A601_HSPOT1 (CH-A) ESWA03 PORT 14 FAIL ALARM / NORMAL

=SAS+SLA1 SNMP ESWA03 ESWA03 NON-TRIP A602 HSPOT2 (CH-A) ESWA03 PORT 15 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP CB A601 (BCU CH-B) ESWB01 PORT-05 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP CB A602 (BCU CH-B) ESWB01 PORT 06 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 87L1(FPFM CH-B) ESWB01 PORT 07 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 87L2(FPSM CH-B) ESWB01 PORT 08 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-1 (50CBFTCS CH-B) ESWB01 PORT 09 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 87L1(FPFM CH-B) ESWB01 PORT10 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 87L2(FPSM CH-B) ESWB01 PORT11 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP UGC FDR-2 (50CBFTCS CH-B) ESWB01 PORT12 FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 100 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 87T1(SET-1 CH-B) ESWB01 PORT 13 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 (IO BOX CH-B) ESWB01 PORT14 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 87T2(SET-2 CH-B) ESWB01 PORT 15 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 87T1(SET-1 CH-B) ESWB01 PORT 16 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 (IO BOX CH-B) ESWB01 PORT 17 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 87T2(SET-2 CH-B) ESWB01 PORT 18 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-1 (AVC CH-B) ESWB01 PORT 19 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB01 ESWB01 NON-TRIP TRAFO-2 (AVC CH-B) ESWB01 PORT 20 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B413 (BCPU CH-B) ESWB02 PORT 05 FAIL ALARM / NORMAL SPARK SS # 3
STATION NON
Alarm/Normal 4123
URGENT
=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B414 (BCPU CH-B) ESWB02 PORT 06 FAIL ALARM / NORMAL ALARM

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A402 (BCPU CH-B) ESWB02 PORT 07 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B415 (BCPU CH-B) ESWB02 PORT 08FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B416 (BCPU CH-B) ESWB02 PORT 09 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A401 (BCPU CH-B) ESWB02 PORT 10FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B421 (BCPU CH-B) ESWB02 PORT 11 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B422 (BCPU CH-B) ESWB02 PORT 12FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB A403 (BCPU CH-B) ESWB02 PORT 13 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B423 (BCPU CH-B) ESWB02 PORT 14 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CB B424 (BCPU CH-B) ESWB02 PORT 15 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-1 (CP1 CH-B) ESWB02 PORT 16 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-1 (CP2 CH-B) ESWB02 PORT 17 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB02 ESWB02 NON-TRIP CAP.PANEL-2 (CP1 CH-B) ESWB02 PORT 18 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP CAP.PANEL-2 (CP2 CH-B) ESWB02 PORT 19 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-1 (27A CH-B) ESWB02 PORT 20 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-1 (F1 CH-B) ESWB03 PORT 05 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-2 (27A CH-B) ESWB03 PORT 06 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER VOLTAGE-2 (F1 CH-B) ESWB03 PORT 07 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER FREQUENCY (81A-1 CH-B) ESWB03 PORT 08 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP UNDER FREQUENCY (81A-2 CH-B) ESWB03 PORT 09 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP ACCS (CH-B) ESWB03 PORT 10 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP COMMON BCU 1 (CH-B) ESWB03 PORT 11 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A601 DGA1 (CH-B) ESWB03 PORT 12 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A602 DGA2 (CH-B) ESWB03 PORT 13 FAIL ALARM / NORMAL

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A601_HSPOT1 (CH-B) ESWB03 PORT 14 FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 101 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=SAS+SLB1 SNMP ESWB03 ESWB03 NON-TRIP A602 HSPOT2 (CH-B) ESWB03 PORT 15 FAIL ALARM / NORMAL

=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU SAS COMM.CH-A FAIL ALARM / NORMAL

=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87L1(SET-1) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87L2(SET-2) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87L1(SET-1) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87L2(SET-2) PROTN RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 RELAY (CP1) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 RELAY (CP2) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 RELAY (CP1) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 RELAY (CP2) PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY SAS COMM.CH-A FAIL ALARM / NORMAL

=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 102 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU SAS COMM.CH-A FAIL ALARM / NORMAL

=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 SAS COMM.CH-A FAIL ALARM / NORMAL

=SAS+CAP2 INTERNAL COMMON BCU-2/6MD85 COMBCU2_6MD85 NON-TRIP COMMON BCU 2 SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 SAS COMM.CH-A FAIL ALARM / NORMAL

=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 SAS COMM.CH-A FAIL ALARM / NORMAL

=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 SAS COMM.CH-A FAIL ALARM / NORMAL

=A601 INTERNAL BCU/6MD85 A601_6MD85_BCU NON-TRIP CB A601 BCU SAS COMM.CH-B FAIL ALARM / NORMAL

=A602 INTERNAL BCU/6MD85 A602_6MD85_BCU NON-TRIP CB A602 BCU SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+L1.R1 INTERNAL 87L1/P546 A601_P546_87L1 NON-TRIP UGC FDR-1 87L1(FPFM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+L1.R2 INTERNAL 87L2/7SD522 A601_7SD522_87L2 NON-TRIP UGC FDR-1 87L2(FPSM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+CBF/TCS INTERNAL 50BF/7VK87 A601_7VK87_50BF NON-TRIP UGC FDR-1 50CBFTCS PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+L2.R1 INTERNAL 87L1/P546 A602_P546_87L1 NON-TRIP UGC FDR-2 87L1(FPFM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+L2.R2 INTERNAL 87L2/7SD522 A602_7SD522_87L2 NON-TRIP UGC FDR-2 87L2(FPSM) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+CBF/TCS INTERNAL 50BF/7VK87 A602_7VK87_50BF NON-TRIP UGC FDR-2 50CBFTCS PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+T601.R1 INTERNAL 87T1/P643 A601_P643_87T1 NON-TRIP TRAFO-1 87L1(SET-1) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+T601.R1 INTERNAL IO/P849 A601_P849_IO NON-TRIP TRAFO-1 IO BOX PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01+T601.R2 INTERNAL 87T2/7UT86 A601_7UT86_F87T2 NON-TRIP TRAFO-1 87L2(SET-2) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+T602.R1 INTERNAL 87T1/P643 A602_P643_87T1 NON-TRIP TRAFO-2 87L1(SET-1) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+T602.R1 INTERNAL IO/P849 A602_P849_IO NON-TRIP TRAFO-2 IO BOX PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02+T602.R2 INTERNAL 87T2/7UT86 A602_7UT86_F87T2 NON-TRIP TRAFO-2 87L2(SET-2) PROTN RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6RTCC1 INTERNAL 90/6RTV RTCC1_6RTV_90 NON-TRIP TRAFO-1 AVC RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=6RTCC2 INTERNAL 90/6RTV RTCC2_6RTV_90 NON-TRIP TRAFO-2 AVC RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3CBP1 INTERNAL CP1/REC670 B414_REC670_CP1 NON-TRIP CAP.PANEL-1 RELAY (CP1) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3CBP1 INTERNAL CP2/SEL487V B414_SEL487V_CP2 NON-TRIP CAP.PANEL-1 RELAY (CP2) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3CBP2 INTERNAL CP1/REC670 B423_REC670_CP1 NON-TRIP CAP.PANEL-2 RELAY (CP1) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3CBP2 INTERNAL CP2/SEL487V B423_SEL487V_CP2 NON-TRIP CAP.PANEL-2 RELAY (CP2) PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3UVLS1 INTERNAL 27/P142 UV1_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3UVLS1 INTERNAL F1/P923 UV1_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3UVLS2 INTERNAL 27/P142 UV2_P142_27 NON-TRIP UNDER VOLTAGE-1 RELAY 27A PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

ED-682330, Rev-2 PAGE 103 OF 104


DOC. NO: ED-682330
CONSTRUCTION OF SPARK 115/33kV SUBSTATION#3
SAS POINT LIST
REV. NO: 2

SAS ALARMS

HMI ALARM / EVENTS RECEIVED AT CONTROL


HMI ALARM / EVENTS TEXT CONTROL SYSTEM DATA COLOSE LOOP TEST
TEXT CENTER
FULL IEC 61850 OPEN
HARDWIRED TYPE IEC 101/104
SOURCE PANEL ADDRESS/ DEVICE NAME/ NUMBER IED NAME TYPE ID LOOP REMARKS
SOURCE TB.# T/NT ADDRESS
IDENTIFIER SIGNAL SOURCE FROM POINT NAME/ TEST CONTROL
DESCRIPTION TEXT INDEX SCADA LITRA TEXT INDEX DEVICE TYPE LDC
THE LOGICAL NODE ALARM CODE CENTER

=3UVLS2 INTERNAL F1/P923 UV2_P923_F1 NON-TRIP UNDER VOLTAGE-2 RELAY F1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3UFLS INTERNAL 81A1/P142 UF_P142_81A_1 NON-TRIP UNDER FREQUENCY 81A-1 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3UFLS INTERNAL 81A2/P142 UF_P142_81A_2 NON-TRIP UNDER FREQUENCY 81A-2 PROT. RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=3ACCS INTERNAL ACCS/C264 ACCS_C264 NON-TRIP ACCS RELAY SAS COMM.CH-B FAIL ALARM / NORMAL

=BH03 INTERNAL BCPU/REF620 B413_REF620_BCPU NON-TRIP CB B413 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH04 INTERNAL BCPU/REF620 B414_REF620_BCPU NON-TRIP CB B414 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH05 INTERNAL BCPU/REF620 A402_REF620_BCPU NON-TRIP CB A402 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH06 INTERNAL BCPU/REF620 B415_REF620_BCPU NON-TRIP CB B415 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH07 INTERNAL BCPU/REF620 B416_REF620_BCPU NON-TRIP CB B416 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH08 INTERNAL BCPU/REF620 A401_REF620_BCPU NON-TRIP CB A401 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH10 INTERNAL BCPU/REF620 B421_REF620_BCPU NON-TRIP CB B421 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH11 INTERNAL BCPU/REF620 B422_REF620_BCPU NON-TRIP CB B422 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH12 INTERNAL BCPU/REF620 A403_REF620_BCPU NON-TRIP CB A403 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH13 INTERNAL BCPU/REF620 B423_REF620_BCPU NON-TRIP CB B423 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=BH14 INTERNAL BCPU/REF620 B424_REF620_BCPU NON-TRIP CB B424 BCPU SAS COMM.CH-B FAIL ALARM / NORMAL

=SAS+CAP1 INTERNAL COMMON BCU-1/6MD85 COMBCU1_6MD85 NON-TRIP COMMON BCU 1 SAS COMM.CH-B FAIL ALARM / NORMAL

=SAS+CAP2 INTERNAL COMMON BCU-2/6MD85 COMBCU2_6MD85 NON-TRIP COMMON BCU 2 SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01-DGA INTERNAL A601/DGA1 A601_DGA1 NON-TRIP A601 DGA1 SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02-DGA INTERNAL A602/DGA2 A602_DGA2 NON-TRIP A602 DGA2 SAS COMM.CH-B FAIL ALARM / NORMAL

=6D01-HSPOT INTERNAL A601/HSPOT1 A601_HSPOT1 NON-TRIP A601_HSPOT1 SAS COMM.CH-B FAIL ALARM / NORMAL

=6D02-HSPOT INTERNAL A602/HSPOT2 A602_HSPOT2 NON-TRIP A602 HSPOT2 SAS COMM.CH-B FAIL ALARM / NORMAL

SAPRE ADDRESS:

SPARE ADDRESS (FROM) 4124

SPARE ADDRESS (TO) 4126