Electrical Plans and Schedule 5
Electrical Plans and Schedule 5
CCS EXTENSION BUILDING 2ND FLOOR ROOM: CCS LEC 7 CCS EXTENSION BUILDING 2ND FLOOR ROOM: CCS LEC 9
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P NO. (VA) (V) (A) AT AF P
1 100W L.O. and 75W CEILING FAN 8+4 1100 230 4.78 20 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC 1 100W L.O. and 75W CEILING FAN 8+4 1100 230 4.78 20 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
2 CONVENIENCE OUTLET 16 2880 230 12.52 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC 2 CONVENIENCE OUTLET 16 2880 230 12.52 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
3980 17.3 3980 17.3
TOTAL CONNECTION LOAD TOTAL CONNECTION LOAD
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED : SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 60A MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 60A
IT: (TOTAL x DF) I = 60 AMPS x 0.80 IT: (TOTAL x DF) I = 60 AMPS x 0.80
IT: (17.3 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire IT: (17.3 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 48 AMPS I = 48 AMPS
IT: 13.84 AMPERES IT: 13.84 AMPERES
CCS EXTENSION BUILDING 2ND FLOOR ROOM: CCS LEC 8 CCS EXTENSION BUILDING 2ND FLOOR ROOM: CCS LEC 10
CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION QTY CONDUCTORS CONDUIT DESCRIPTION QTY CONDUCTORS CONDUIT
NO. (VA) (V) (A) AT AF P NO. (VA) (V) (A) AT AF P
1 100W L.O. and 75W CEILING FAN 8+4 1100 230 4.78 20 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC 1 100W L.O. and 75W CEILING FAN 8+4 1100 230 4.78 20 50 2 2-2.0mm² THWN, Cu wire 20mmØ PVC
2 CONVENIENCE OUTLET 16 2880 230 12.52 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC 2 CONVENIENCE OUTLET 16 2880 230 12.52 20 50 2 2-3.5mm² THWN, Cu wire 20mmØ PVC
3980 17.3 3980 17.3
TOTAL CONNECTION LOAD TOTAL CONNECTION LOAD
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED : SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 60A MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 2P CB - 60A
IT: (TOTAL x DF) I = 60 AMPS x 0.80 IT: (TOTAL x DF) I = 60 AMPS x 0.80
IT: (17.3 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire IT: (17.3 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 48 AMPS I = 48 AMPS
IT: 13.84 AMPERES IT: 13.84 AMPERES
SAMPLE LOAD COMPUTATION AT 80% DEMAND FACTOR FOR MAIN PANEL PROTECTION USED :
MINIMUM AMPACITY OF MAIN PANEL: 230V, 60Hz, 3P CB - 175AT
IT: (TOTAL x DF) I = 175 AMPS x 0.80
IT: (69.2 x 0.80) 2-8.0mm2 THWN + 5.5mm2 tw CU Wire
I = 140 AMPS
IT: 55.36 AMPS
Group Assigned: PROJECT TITLE COURSE AND SECTION SHEET CONTENT SEM. AY SHEET NO
POWER DISTRIBUTION SCHEDULE OF
Group 2 & LOAD DIAGRAM BSEE 4B LOAD
1ST 2023
- 2024 ?
5