66 KV Over Head Transmission Lines

Names of Manufacturers, Places of Manufacture

Testing - Inspection and Standard Specification

Item Name of Place of Standard Place of


manufactures manufacture specifications test

1-ACSR380/50mm2(NA)

2-GSW 75 mm'

The words "similar or equivalent ... etc. "will not be accepted.


Tenderers should include the names of all manufactures they envisage
may be used in the event of the tender being successful.

In the event of award of contract no manufactures or subcontractors


other than those named above will be accepted by the owner for
appropriate service or production.

Date:

Signature of Tenderer

41
Schedule (2): ALUMINUM CONDUCTOR STEEL REINROCED (ACSR)
380/50 mm2

Required Offered

Specification Specification

1. Nominal cross section mm 431.5

2.Number & diameter of wires No./mm AL 54/3 mm

ST 7/3 mm

3.Over all diameter mm 27

4.Weight without grease kg/km 1442

5.weight of grease(max) kg/km 52

6.0timotc tcnilc strength kg 12310

7.Equivalent modulus ot elasticity kg/mm' 7000

8.Equivalent coefficient. linear expansion per °C 19.3x10 6

9.D.0 resistance at 20C a/km 0.0757

10. Current carrying capacity at 470 min Amp 716

11. length of conductor on drum > 1700


(Min length 1700) m

12. grease drop point 220°c

42
Schedule (3): 66KV Over Head Transmission lines GSW 75 mm 2

Required Offered
NO ITEM
Specification Specification
General specfication standard lEC 60888

Properties of complete conductor


1 Nominal Area mm 75
2 Construction GAL.Steel
(No of wires/ wire diameter)
3 No/ mm 7/3.7
Steel wires
4 Over all diameter of conductor Mm 11.1

5 Weight (without grease) Kg/km 595

6 Modulus of elasticity Kg/mm' 19300

7 Coefficient of linear expansion Per C 11.5x10


C) VV i
,_;_,_-
e ght
_i
UI
-,.-.-,,--, I
5111p 11

Ultimate tensile strengUi(aH.er


9 KN 92.2
'tr3nd1ng)

length of conductor on drum(min 1700


10 M
length 1700)

I'ropertic of wlrcs hotoro


11
stranding
Nominal diameter Steel wires
A Mm 3.7

Ultimate tensile stress (Before


B MPa 1290
stranding)
Min percentage elongation Steel
C wires % 4