Operation Instructions DCM-Modul 2.x

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Operating Instructions DCM Module

Table of Contents

Preliminary Remark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1 Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Path--dependent control of SCHOTTEL systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Path--dependent speed setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Further applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Structure and Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating mode switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Analog output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DCM Module: View of front side and boards, left-- and right--hand side . . . . . . . . . . 9

2 Configuration, Mounting and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Overview on jumper configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pulling out the contact connector strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inserting the contact connector strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pulling the DCM Module out of the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inserting the DCM Module into the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
General check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Functional check of path--dependent control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Functional check of path--dependent speed setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Parameterisation of CAN sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Path--dependent control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Path--dependent speed setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3 Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

4 Measuring points and nominal data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24


Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Alarm relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
CAN bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 1 / 31


5 Pin Configuration and Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

2 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Preliminary Remark
These instructions shall be of information and help for Important instructions relevant to technical and
every person engaged in initial start--up, operation and operational safety are pointed out by the following
maintenance of SCHOTTEL systems. This requires to symbols:
read, understand and observe these documents.
These instructions are to be made available to ! CAUTION
everybody carrying out works on the system.
We do not accept any liability for damages and troubles Indicates working and operating methods that are to be
in operation resulting from disregard of these strictly observed to exclude any risk for persons.
instructions.
It is taken for granted that every user is familiar with the
systems and informed on all possible dangers.
! ATTENTION
Refers to working and operating methods that are to be
Only professional electricians are allowed to carry out strictly observed to avoid damages to or destruction of
any work on the system. the material.
References to illustrations in the text are written in
brackets, e.g. (1/3). The first number indicates the NOTE
illustration number in the manual, the second number
is the position number in the illustration. Indicates exceptional features in the working process
that are to be observed.
All illustrations are diagrammatic projections without
any claim for completeness.
i INFORMATION
Any technical modification to SCHOTTEL systems not
carried out by personnel appointed by SCHOTTEL Application references and information.
does require written consent.
This excludes modifications or control settings detailed During any work carried out on SCHOTTEL systems it
in our instructions. is required to observe the ”Safety and Environmental
Protection Regulations SV 1” as well as the relevant
laws in force in each country of utilisation.
Given that SCHOTTEL systems are subject to further
development we reserve the right of technical
modifications.

These instructions were elaborated with utmost care.


In case of further information required, please contact:

SCHOTTEL GmbH
Mainzer Straße 99
D--56322 Spay
Phone +49 (0) 2628 / 61--0
Fax +49 (0) 2628 / 61--300
E--Mail info@schottel.de

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 3 / 31


4 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en
1 Technical Description

Application
The DCM Module (1/2) is an electronic module, which
reads, processes outputs control signals . Generally it
is applied for the following system applications:
D Path--dependent control of SCHOTTEL systems

D Speed setting of driving motors

Path--dependent control of SCHOTTEL systems


Figure 1 shows a diagrammatic view of the application
of the DCM Module for the control of SCHOTTEL
systems (1/4). 1
D In case of the path--dependent control, the DCM
Module compares the current setting on the
steering stand (1/1) with the current feed--back
(1/5). The differential value from setting and
feed--back is calculated by the DCM Module and
transmitted to the amplifier unit (1/3) (e.g. DPV
Module). 2

D Depending on the differential value transmitted


from the DCM Module, the amplifier unit controls
the SCHOTTEL system until the feed--back value
matches the value of the setting (differential value
= 0).

5
3
Path--dependent speed setting
Also with the path--depending speed setting, a set
value from the steering stand is read--in into the DCM
Module. According to the read--in set value, the DCM
Module provides an output signal.

Further applications
The path--dependent control of SCHOTTEL systems 4
and the path--dependent speed setting are appli--
cations, which are taken into consideration in this
document.
Further applications of the DCM Module are described
in the according construction information.
Figure 1

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 5 / 31


Structure and Function
The DCM Module essentially consists of:
1
D 2 boards with electronic main components, The
DIL switches and jumpers for hardware configu--
ration of the module, see Figure 5, page 9.
D 8 digital inputs (2/2)
D 4 digital outputs (2/1)
D 4 analog inputs (2/3) 10 V / 0 ... 20 mA, 2
(depending on configuration of jumper J7 and J8)
According to the jumper configuration, 2 analog
inputs are positioned on the potentiometers AI3
(3/1) and AI4 (3/2) or externally onto the terminal
connections 23 (3/3) and 24 (3/4) 3
D 2 analog outputs (2/4) (0 ... 10 V / 0 ... 20 mA) 2
D LED’s for indicating status and operating condi--
tions, see section ”LED indications”.

Figure 2

3
4

Figure 3

6 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


LED indications

18 LED’s indicate the following operating conditions:


1
LED Operating condition CAN DPV 1
F 100 shines with an error in CAN bus
shines with an error of
F 101 DCM DPV 2
power supply
F 102 shines with an error Setpoint
F 103 shines with an error of feed--back
F 104 shines with a programmed error
2
F 105 shines with a programmed error
flashes/shines during parameterisa-
SF 1
tion
SF 2 Special function
shines with operating voltage pres-
PWR
ent on the module
shines with functional readiness
RUN
and goes out with a failure
IN 0 shines with active digital input 0.0
IN 1 shines with active digital input 0.1
IN 2 shines with active digital input 0.2
IN 3 shines with active digital input 0.3
OUT 0 shines with active digital input 0
OUT 1 shines with active digital input 1
OUT 2 shines with active digital input 2
OUT 3 shines with active digital input 3

With a failure, one of the LED’s F100 ... F 105 shines.


In trouble free condition, the LED’s PWR and RUN
shine, and depending on the operational situation the
LED’s IN 0 ... IN 3, OUT 0 ... OUT 3, or SF 1 or SF 2.

Operating mode switch


The operating switch (4/3) is used to set the operating
mode ON and LD. With operating mode LD the DCM
Module is fitted with up--dated software.
During utilization of the ship, the switch must always be
in position ON.
3

System diagnosis
Via the interfaces (4/1) and (4/2), a SCHOTTEL Service Figure 4
engineer is always able to do a quick hardware
diagnosis.

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 7 / 31


Software configuration Analog input signals
According to the use, the DCM Module is programmed The DCM Module can be approached with analog input
ex works with a system software. The system software signals (0 ... 10 V or 0 ... 20 mA) – depending on the
is decisive for the application (path--dependent control, jumper configuration.
path--dependent speed setting, etc.). For transmitting
the system software onto the DPV Module, the Both inputs are optionally adjustable with the
operating mode switch (5/4) must be in position LD. potentiometers AI3 and AI4.
During operation, the operating mode switch must
always be in position ON. Analog output signals
By standard, in case of SCHOTTEL systems, the
Hardware configuration analog output signal 0 ... 10 V is put onto a buffer
amplifier (5/3). Over the buffer amplifier, the according
With a defect of one DCM Module, an according spare component is approached with an output signal from 4
module can be replaced in the SCHOTTEL electric mA up to 20 mA.
systems without much efforts by professional
personnel. Because of the various application Optionally, the DCM Module as analog output signal
possibilities, it is required to observe the Ident No. of the can also transmit an electric signal from 4 to 20 mA,
DCM Module. The hardware of the DCM Module first is depending on the configuration of the jumpers.
to be specifically configured for the according
application, and thereafter to be mounted and
application--specific installed. Alarm relay
For configuration, the DCM Module has to be taken out The DCM-- Module is fitted with an alarm relay, of which
of the housing beforehand. Then, on the boards on the the potential--free make--contact is available at the
left--hand side (5/12) are adjusted the DIL switches contact connector strips, and normally is used for
(5/13) and the CAN load resistance (5/3). On both changing from path--dependent to time--dependent
boards the jumpers have to be inserted according to operation, if the DCM Module is no longer ready for
application. operation. Furthermore, a message is transmitted via
the make--contact to the ship’s warning system.
The left--side board (5/12) has 8 jumper consoles, the
right--side board (5/11) has 14 jumper consoles. In case
of the jumper consoles with 2 sockets (5/1) one jumper Battery
might be inserted or not. In case of the jumper consoles
with 3 sockets (5/2), the jumper on the bridges 1, 2, or The DCM Module is fitted with a battery (5/10) for
on the bridges 2, 3 might be inserted or not. The socket saving date and hour. The battery is of no influence on
identification 1, 2, 3 (5/9) is printed on the boards. the system software. The battery cannot be replaced.

The overview of the jumper configurations J1 to J12


can be found on page 10.
With the DIL switches (5/13) are activated those
functions, which are required for adaptation to the
SCHOTTEL system.
During installation, the housing of the DCM Module is
mounted onto the mounting rail. During the electric
installation, the contact connector strips (5/6) can be
pulled out of a defective module and then can be
pushed into an exchange module.

8 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


6
7
5

2 2
3 9 10

1 1 1
2 2

6
1
1

OFF 123
ON

3
3 1
1

321
321

12 11 1

13 2 9 2 2 2
9

Figure 5 DCM Module: View of front side and boards, left-- and right--hand side

1 Jumper console with 2 sockets 10 Battery CR2032

2 Jumper console with 3 sockets 11 DCM Module, board right--hand side

3 CAN Bus load resistance 12 DCM Module, board left--hand side

4 Operating mode switch 13 DIL switch


top: block S4
5 LED indications for operating states,
bottom: block S3
see page 7
(marked on the board)
6 Contact connector strips

7 LED indications of the digital and analog outputs,


see page 7

8 Potentiometer AI 3 and AI 4

9 Socket identification 1, 2, 3
with jumper console with 3 sockets

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 9 / 31


2 Configuration, Mounting and Setting

! ATTENTION
Overview on jumper configurations

According to its use, the DCM Module is to be first Name Function


configured, then mounted and set for the
application. Terminal connection 31
Analog output AO 0
Pin 1--2: AO 0 voltage output

! ATTENTION J1 Pin 2--3: AO 0 current output

All the following instructions are to be carefully Pin 1--2: AO 0 voltage output
observed for being able to insert the total system J2 Pin 2--3: AO 0 current output
operationally reliable subsequent to the replacement of
a DCM Module. Pin 1--2: AO 0 voltage output
J3 Pin 2--3: AO 0 current output

Terminal connection 32
Configuration Analog output AO 1
Pin 1--2: AO 1 voltage output
1. Switch the electric system off and secure against J4 Pin 2--3: AO 1 current output
unintended switch--on.
2. For pulling out the contact connector strips from Pin 1--2: AO 1 voltage output
the defective DCM Module, see page 12. J5 Pin 2--3: AO 1 current output
Do not loosen any electric installations on the
contact connector strips. Pin 1--2: AO 1 voltage output
J6 Pin 2--3: AO 1 current output
3. Pull the defective and the new DCM Module out of
the housing, see Figure 8, page 12. Terminal connection 24
Wiring AI4
4. Transfer the positions of all DIL switches (6/3) from
the defective module to the new DCM Module. J7 Pin 1--2: 0 -- 10 V / 0 -- 20 mA
Pin 2--3: potentiometer AI 4
5. Transfer the positions of all jumper positions (6/1)
from the defective module to the new DCM Module Terminal connection 23
Overview on the jumper configurations, see Wiring AI3
right--hand column. Jumpers J13 and J14 must Pin 1--2: 0 -- 10 V / 0 -- 20 mA
always be put onto pin 2 and 3. J8
Pin 2--3: potentiometer AI 3
6. Transfer the position of the load resistance (6/2)
from the defective module to the new DCM Input wiring
Module. Open: AI 2: voltage input
J9 Plugged: AI 2: current input

! ATTENTION
J 10
Open: AI 1: voltage input
Plugged: AI 1: current input
The load resistance (7/1) as last CAN bus element
must be always in pos. ON, see the diagrammatic Open: AI 3: voltage input
section in Figure 7 and in the wiring diagram. J 11 Plugged: AI 3: current input
7. Push the new DCM Module into to the housing Open: AI 4: voltage input
inside the switch cabinet and insert the contact
J 12 Plugged: AI 4: current input
connector strips in the module.

10 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


1 1 2 1 1

1
J13 1
J14
ON OFF

J9
J10 1
J8
J11 J7 1
J1
J12 J2
J3

1
J4
J5
J6

Figure 6

CAN

1
OFF OFF ON

Figure 7

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 11 / 31


Installation
Pulling out the contact connector strips

D Pull the contact connector strips (8/1) out of a


defective DCM Module (8/4) using a screwdriver. 1

2
Inserting the contact connector strips

D Insert the contact connector strips (8/1) after the 3


configuration on the new DCM Module.

4
! ATTENTION
When inserting the contact connector strips (8/1) all 1
contact connector numbers (8/3) have to tie in. Wrong
insertion may cause the destruction of the DCM
Module.
All contact connector strips must be tightly seated in the
DCM Module.

Pulling the DCM Module out of the housing 1

D Push the catches (8/2) down with a screwdriver,


Figure 8
and pull the DDCM Module (8/4) out. For
configuration of the DCM Module it is required to
pull the DCM Module out of the housing.
1 2 1 2

Inserting the DCM Module into the housing

D Push the DCM Module in until it engages in the


housing.

3 3

General check
After configuration and installation, the following
checks are to be carried out:

D Check position of all operating mode switches


(9/3). Prior to connecting the electric system, on all
modules these have to be in position ON.
1 2
D Connect the electric system. The LED PWR (9/1)
and RUN (9/2) of all modules have to shine. If on
one module one of the mentioned LED’s does not 3
shine, the electric system or the DCM Module is
not ready for operation, for this, see chapter
”Trouble Shooting”, page 20.
Figure 9

12 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


NOTE

For further information on the functional check of the


path--dependent control, see page 14.
For further information on the functional check of the
path--dependent speed setting, see page 15.

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 13 /31


Functional check of path--dependent control
(10/2). The propulsion units (10/4) for setting the
i INFORMATION path--dependent control are approached by the
amplifier unit until the set value and feed--back value
When using the DCM Module (10/5) for the are identical.
path--dependent control, no other settings are required
after configuration and installation are carried out. After If setting and feed--back devices (10/1) are fitted with
switch--on of the entire system, the DCM Module CAN sensors as shown in Figure 10, in case of need,
approaches the amplifier unit (10/3) after changing the these can be parameterized via the DCM Module, see
path--dependent thrust direction on the default unit page 16.

3 4
1 2
M

24 V GND

Figure 10

14 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Functional check of path--dependent speed setting

i INFORMATION
When using the DCM Module for the path--dependent According to the configuration, the output signal can be
speed setting, the following settings are required after checked with an universal measuring device (11/2)
configuration and installation are carried out. After (measuring range from 0 ... 20 V or 0 ... 25 mA).
switch--on of the entire system, the DCM Module
approaches the amplifier unit (11/3) after changing the Figure 11 shows the application with analog output
path--dependent speed on the default unit (11/1). signal 0 .. 10 V.

Figure 11 shows the application of the DCM Module for If the default unit is fitted with a CAN sensor (no
the path--dependent speed setting (11/1) with analog illustration), in case of need this sensor can be
output AO1 and AGND. After the configuration and parameterized via the DCM Module, see page 18.
installation, the following settings are required,
depending on the configuration of jumper J7 and J8:
D Starting point from which the speed of the motor
(11/5) shall be increased – to be set at
potentiometer AI3 (11/3)
(Position of the setting lever (11/6)
D Maximum motor speed – to be set at potentiometer
AI4 (11/4)

2
6
1
000.0

min 0 GND
.
max.
V DC
3 U

I
4

5
24 V GND

AO1
AGND

Figure 11

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 15 /31


Parameterisation of CAN sensors
Path--dependent control
6. Connect the DCM Module for path--dependent
i INFORMATION control. LED PWR and RUN are shining,
After the replacement of a CAN sensor (12/1) in the LED SF 1 (13/7) is flashing.
default unit of the path--dependent control (12/4) or in
the feed--back unit (12/2), parameterisation can be
carried out via the DCM Module (12/3). 7. Within 10 seconds after switch--on of the DCM
Module, give two short 24 V--pulses at connection
17 of the contact connector strip (13/4). LED SF 1
NOTE is shining.
Installation of the new CAN sensors must be
completely terminated.
DCM Module for path--dependent control must be
ready for operation. NOTE
The settings driving direction ahead (0o) must not be
1. For parameterisation (zero position setting) of the changed during the parameterisation.
path--dependent control, the SCHOTTEL
propulsion (13/3) is to be manually set into driving After the 10 seconds have elapsed, the DCM Module
direction ahead (0o). Switch off the electric blocks the release of zero position setting. LED SF 1 is
approach on the propulsion units (13/2) for flashing in a slow rhythm.
path--dependent control.
If the zero position setting is to be repeated, beforehand
it is required to switch off the DCM Module for the
2. Turn the default unit for path--dependent control path--dependent control. Thereafter, the positions 6.
(13/1) into driving direction ahead (0o). and 7. are to be repeated.

3. Switch off the DCM Module for path--dependent 8. After successful parameterisation, switch the
control (13/5) . LED PWR (13/8) and RUN (13/6) DCM Module for path--dependent control off.
do not shine. LED PWR and RUN are not shining.

4. Pull the contact connector strips (13/4) out from 9. Pull the contact connector strips out from the DCM
the DCM Module and open the module, see page Module and open the module, see page 12.
12.

5. Put the DIL switch S 3.8 (13/10) on the switch 10. Put DIL switch S3.8 on the switch block S 3 in
block S3 (13/9) to pos. ON. Push the DCM Module OFF--position. Push the DCM Module into the
into the housing and insert the contact connector housing and insert the contact connector strips in
strips in the DCM Module, see page 12. the DCM Module, see page 12.

16 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


1 1

4 3

Figure 12

1 2 2
0o
0o
M

3
8 6
4

S4

S3
5 24 V GND
10

Figure 13

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 17 /31


Path--dependent speed setting
5. Connect the DCM Module for path--dependent
i INFORMATION speed regulation. LED PWR and RUN are shining.
LED SF 1 (15/2) is flashing.
After the replacement of a CAN sensor (14/1) in the
default unit of the path--dependent speed regulation 6. Within 10 seconds after switch--on of the DCM
(14/2), parameterisation can be carried out via the Module , give two short 24 V--pulses at connection
DCM Module (14/3). 17 of the contact connector strip (15/5). LED SF
1 is shining.

NOTE
NOTE
Installation of the new CAN sensors must be
completely terminated. Setting of the zero position for the speed setting must
DCM Module for path--dependent speed regulation not be changed during the parameterisation.
must be ready for operation. After the 10 seconds have elapsed, the DCM Module
blocks the release of parameterisation. LED SF 1 is
1. Put the default unit for path--dependent speed flashing in a slow rhythm.
regulation (15/1) to zero position.
If the parameterisation is to be repeated, it is required
to switch off the DCM Module for the path--dependent
2. Switch off the DCM Module for path--dependent speed regulation beforehand. Thereafter, the positions
speed regulation (15/6) . LED PWR (15/3) and 5. and 6. are to be repeated.
RUN (15/4) do not shine.
7. After successful parameterisation, switch the
DCM Module for path--dependent speed
3. Pull the contact connector strips out from the DCM regulation off. LED PWR and RUN are not shining.
Module and open the module, see page 12.

8. Pull the contact connector strips out from the DCM


4. Put the DIL switch S 3.8 (15/7) on the switch block Module and open the module, see page 12.
S3 (15/3) to pos. ON. Push the DCM Module into
the housing and insert the contact connector strips 9. Put DIL switch S 3.8 to pos. OFF. Push the DCM
in the DCM Module, see page 12. Module into the housing and insert the contact
connector strips in the DCM Module, see page 12.

18 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


1 2 3

Figure 14

3 4

S4

S3
6 24 V GND
7

Figure 15

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 19 /31


3 Trouble Shooting

NOTE 1

The following table does only include possible defects,


which may generate because of wrong configuration,
installation or settings of the DCM Module.
Errors of the ship’s electrical system (e.g. defective
supply voltages, cable breakages and similar) are not 13 14 15 16 17 18 19 20
4A1
touched.
If it is not possible to remove the fault with these
measures it is required to inform the SCHOTTEL
Service.

The SCHOTTEL Service needs the following


information: 1410XXXX 115XXXX
=
+B
Bl.

D SCHOTTEL password, order number (16/2) and


wiring diagram Ident--no. (16/3) 2
D Denomination (16/1) of the DCM Module in the
wiring diagram 3

D Description of the error and how it affects the


function of the system.
Figure 16

i INFORMATION

For the perfect function of the DCM Module the


following basic prerequisites must be met:

1. The operating mode switch (17/1) must be in pos.


ON.
1
2. For the specific application, all jumpers must be
put onto the according pins, see pos. 1 in Figure 6,
page 11.

3. All DIL switches must be set for the specific


application, see pos. 3 in Figure 6, page 11. 2

4. The load resistance must be in pos. ON if the


module is the last device in the CAN loop. Within
the CAN loop, the load resistance of all modules
must be on OFF, see pos. 2 in Figure 6, page 11
and Figure 12 page 17.

With absence of one of the basic prerequisites, the


DCM Module is not ready for operation. Figure 17

20 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Malfunction/Error Possible cause Check / Removal

SCHOTTEL propulsion is perma- Setting and/or feed--back: Parameterisation of CAN sensor,


nently turning around CAN--Sensor not parameterized see page 16
(continuous run of the path--de-
pendent control)
Interchanged signal on the poten- Check connections and correct, if
tiometer of the default or feed-- required.
back unit.

Phase--sequence information to- Check phase--sequence informa-


wards the amplifier interchanged tion and correct, if required.
With hydraulics: change valves.
With frequency converter:
change phase--sequence in-
formation,
e.g. cw (=clockwise) with ccw
(=counterclockwise).

SCHOTTEL propulsion turns op- DIL switch 1 of switch block S3 in Correct DIL switch 1 of switch
posite to setting wrong position block S3 and parameterise CAN
(Wrong turning direction of the sensors of default and feed--
path--dependent control) back, see page 16

Check signals of feed--back AI3


Interchanged signal on the poten- and AI4 and change, if required.
tiometer of the default or feed-- Correct the position of the poten-
back unit. tiometer on the feed--back unit.

Check phase--sequence informa-


Phase--sequence information to- tion and correct, if required.
wards the amplifier interchanged With hydraulics: change valves.
With frequency converter:
change phase--sequence in-
formation,
e.g. cw (=clockwise) with ccw
(=counterclockwise).

Although the electric system is There is no voltage supply at the For checking the voltage supply
connected, LED PWR does not module. at the DCM Module, see page
shine. 24.

Ensure voltage supply at the


DCM Module, e.g. check function
of safety cut--out, check correct
function of the connections, etc.

DCM Module defective Replace the DCM Module

Although the electric system is Module not ready for operation. Check if one of the LED’s F100,
connected, LED RUN does not F101, F102, F103, F104 or F105
shine. is shining, see follow--up table.
(alarm message error)

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 21 /31


Malfunction/Error Possible cause Check / Removal

LED F100 shines. Error in the CAN bus system Check entire wiring of the CAN
bus system for correct connec-
tions, and wiring for damage.

Replace damaged lines, if re-


quired.
Pay attention to correct connec-
tions.

Check position of load resis-


tance, see point 6., page 10 and
20

Measure resistance between


CAN High and CAN Low: 60 Ω

LED F101 shines. Error in the voltage supply For checking the voltage supply
at the DCM Module, see page
24.

Checking the voltage supply.


Pay attention to the specifications
in the wiring diagram.

LED F102 shines. ”Setpoint” error


(error in the setting):

With setting via CAN sensor Check if LED F 100 shines


Check supply of the CAN sensor,
check CAN address (see wiring
diagram), replace CAN sensor, if
required
(also see failure / error,
LED F100 shines)

With setting via potentiometer Check wiring of the potentiometer


for damage.
Replace damaged lines, if re-
quired.
Pay attention to correct connec-
tions.
Check supply of the potentio-
meter, check signals, replace the
potentiometer, if required.

22 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Malfunction/Error Possible cause Check / Removal

LED F103 shines. ”Feedback” error


(error in feedback):
With setting via CAN sensor Check if LED F 100 shines
Check supply of the CAN sensor,
check CAN address (see wiring
diagram) replace CAN sensor, if
required.
(also see failure / error,
LED F100 shines)

With setting via potentiometer Check wiring of the potentiometer


for damage.
Replace damaged lines, if re-
quired.
Pay attention to correct connec-
tions.
Check supply of the potentio-
meter, check signals, replace the
potentiometer, if required.

LED F104 shines. Presently not used Consult SCHOTTEL.

LED F105 shines. Presently not used Consult SCHOTTEL.

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 23 /31


4 Measuring points and nominal data

Supply

D Contact connection 25 (18/1): GND


D Contact connection 26 (18/2): 24 V DC
D Contact connection 27 (18/1): GND
D Contact connection 28 (18/2): 24 V DC

24 V

1
2

Figure 18

9 10
Alarm relay
D Contact connection 9 (19/9): Potential--free
D Contact connection 10 (19/10): Potential--free

Figure 19

24 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


CAN bus
D Contact connection 1 (20/1): 5 V CAN--VCC
5V
D Contact connection 4 (20/4): CAN--GND
D Contact connection 2 (20/2): CAN--H 1
2
D Contact connection 3 (20/3): CAN--L
3
4

Figure 20

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 25 /31


Inputs
Analog inputs

D Contact connection 21 (21/21): AI 1


0 ... 10 V DC 0 ... 10 V
21
D Contact connection 22 (21/22): AI 2 22
0 ... 10 V DC 23

D Contact connection 23 (21/23): AI 3


0 ... 10 V DC / 0 ... 20 mA
depending on configuration of the jumpers J8

D Contact connection 24 (21/24): AI 4


0 ... 10 V DC / 0 ... 20 mA
depending on configuration of the jumpers J7

D Contact connection 29 (21/29): AGND


AGND for analog inputs AI 1, AI 2, AI 3 and AI 4

24
29
i INFORMATION

Optionally it is possible to use all analog inputs as Figure 21


current input. Each input processes a current signal
from 0 ... 20 mA. With a jumper, each analog input can
be configured accordingly.

26 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Digital inputs

D Contact connection 25 (22/25): GND


13
D Contact connection 13 (22/13): DI 0.0 High: 24 V 14
High: 24 V / Low: 0 V Low: 0 V
15
D Contact connection 14 (22/14): DI 0.1
High: 24 V / Low: 0 V 16

D Contact connection 15 (22/15): DI 0.2


High: 24 V / Low: 0 V

D Contact connection 16 (22/16): DI 0.3


High: 24 V / Low: 0 V

25

Figure 22

17
D Contact connection 25 (23/25): GND
High: 24 V
D Contact connection 17 (23/17): DI 1.0
High: 24 V / Low: 0 V Low: 0 V

D Contact connection 18 (23/18): DI 1.1


High: 24 V / Low: 0 V

D Contact connection 19 (23/19): DI 1.2 18


High: 24 V / Low: 0 V
19
D Contact connection 20 (23/20): DI 1.3
High: 24 V / Low: 0 V

20
25

Figure 23

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 27 /31


Outputs
Analog outputs

D Contact connection 29 (24/29): AGND


GND for analog outputs 30, 31 and 32

D Contact connection 30 (24/30): 10 V DC


Reference voltage

D Contact connection 31 (24/31): 0 ... 10 V DC

D Contact connection 32 (24/32): 0 ... 10 V DC

0 ... 10 V DC
32
i INFORMATION
31
Optionally it is possible to use all analog outputs as 10 V DC
30
current output. Each output emits a current signal from 29
0 ... 20 mA. With a jumper, each analog output can be
configured accordingly.

Figure 24

Digital outputs
5
D Contact connection 5 (25/5): DO 0 High: 6
High: 24 V / Low: 0 V
24 V 7
D Contact connection 6 (25/6): DO 1 8
High: 24 V / Low: 0 V Low:
0V
D Contact connection 7 (25/7): DO 2
High: 24 V / Low: 0 V

D Contact connection 8 (25/8): DO 3


High: 24 V / Low: 0 V

D Contact connection 28 (25/28): GND

28

Figure 25

28 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


5 Pin configuration and Technical Data

Pin configuration

Pin configuration

Contact Designation

Voltage output CAN


1
(+ 5 V DC VCC)

2 CAN--Bus CAN--H

3 CAN--Bus CAN--L

Reference potential CAN


4
(CAN--GND)

5 Digital output 0 DO 0

6 Digital output 1 DO 1

7 Digital output 2 DO 2

8 Digital output 3 DO 0

9 Alarm relay

10 Alarm relay

11 RS 232 TXD

12 RS 232 RXD

13 Digital input 0 DI 0.0

14 Digital input 1 DI 0.1

15 Digital input 2 DI 0.2

16 Digital input 3 DI 0.3

Figure 26

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 29 /31


Pin configuration

Contact Designation

17 Digital input 0 DI 1.0

18 Digital input 1 DI 1.1

19 Digital input 2 DI 1.2

20 Digital input 3 DI 1.3

21 Analog input AI 1

22 Analog input AI 2

23 Analog input AI 3

24 Analog input AI 4

25 Voltage supply GND

26 Voltage supply 24V

27 Voltage supply GND

28 Voltage supply 24V

29 Analog reference potential AGND

Reference voltage output 10 V


30
10 V REF

31 Analog output AO 0

32 Analog output AO 1

Figure 27

30 / 31 STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 en


Technical Data

General
Prototype assay GL
Operating data
Power supply 24 V DC / 100 mA
Admissible voltage variation incl. residual ripple -- 25 % . . . +50 %
Current consumption in no--load operation < 200 mA
Admissible ambient temperature 0 . . . 70°C
Electric separation ----
Digital inputs
Digital inputs DI0.0 ... DI 0.3 24 V DC
Low: 0 ... 5 V, High: 15 ... 36 V
Digital inputs DI1.0 ... DI 1.3 24 V DC
Low: 0 ... 5 V, High: 15 ... 36 V
Digital outputs
Digital outputs DI0.0 ... DI 0.3 500 mA @ 24 V DC
Analog inputs
Analog input AI1 ... AI4 0 ... 10 V DC or 0 ... 20 mA
depending on jumper position
with 10--bit resolution
Reference voltage output 10 V DC ( IRef < 10 mA)
Analog outputs
Analog output AO0 ... AO1 0 ... 10 V DC or
0 ... 20 mA
with 12--bit resolution
Alarm relay switching contact
Switching contact 1000 mA @ 30 V DC

en STD--Ka Operating Instructions DCM Module 2.x 07/1384 1162900 31 /31

You might also like