Professional Documents
Culture Documents
Fire Gas Detection Philosophy 1641849168
Fire Gas Detection Philosophy 1641849168
PROJECT: NAFT SEFID OIL FIELD GAS & OIL SYSTEM OPTIMIZATION &
RENOVATION PROJECT
Project No.: 53-85204
REV.: 00 PAGE: 1 OF 16
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 2 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 3 of 44
TABLE OF CONTENT
1. INTRODUCTION...................................................................................................................................... 6
2. SCOPE .................................................................................................................................................... 7
3. GENERAL ............................................................................................................................................... 7
4. TERMS AND DEFINITIONS ....................................................................................................................... 7
5. ABBREVIATION ...................................................................................................................................... 8
6. CODES AND STANDARDS ........................................................................................................................ 8
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 4 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 5 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 6 of 44
1. INTRODUCTION
Existing Naft Sefid Production Unit with crude oil processing capacity of 20000-25000
STB/Day has been located in North of Ahwaz which its produced crude oil is transferred to
AHWAZ. Also 25000 STB/Day Dead oil is received in the Naft Sefid Production Unit, from
Masjed Soleiman to Naft Sefid, and pumps to AHWAZ with no process on it. Existing unit is
at 70 km northeast of Ahwaz and 75 km of Masjed Soleiman.
NISOC intends to establish a new production unit to optimize Oil and Gas processing in Naft
Sefid oil field due to depreciation of the existing unit and lack of sweetening facilities in this
unit.
This project consists of design and construction of new oil production unit and gas gathering
and compression station in Naft Sefid oil field to produce 20000 STB/Day sweet crude oil
for transfer to Haftkel via main oil transfer pumps. Separated gases from production unit will
be gathered and compressed in several stages and then will be transferred to Masjed
Soleiman in conjunction with incoming gases from separation station. New Oil and Gas
production unit will be located at 2.4 km southeast of existing production unit.
Moreover, 25000 STB/Day dead oil from Masjed Soleiman will be received in production
tank and then transferred to Ahwaz via dead oil transfer pumps.
This project consists of the following items:
1. Inlet manifold for 9 HP/LP incoming flow lines.
2. Production unit including production separators, stripper column, degassing tank and main
oil transfer pumps to Haftkel.
3. Production Tank for incoming dead oil from Masjed Soleiman and main oil transfer
pumps to transfer dead oil to Ahwaz.
4. Gas gathering and compression unit including several compression stages to transfer gas to
Masjed Soleiman.
5. Route change or optimization of incoming flow lines to the new Naft Sefid inlet
manifolds.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 7 of 44
6. Design and construction of 8″ crude oil pipeline from new production unit to Haftkel.
7. Design and construction of new 8″ Dead Oil pipeline from new production unit to the tie-
in point of existing 8″ and 12″ pipelines in old Naft Sefid production unit.
8. Design and construction of 6″ gas pipeline from separation station to the new Naft Sefid
production unit.
9. Design and construction of new 8″ gas transfer pipeline from new production unit to the
tie-in point of existing 8″ pipeline in old Naft Sefid production unit.
2. SCOPE
This specification covers the minimum requirements for gas and fire detection used in
Naft Sefid Project. It is applicable for the selection of detectors (type), their location and
the alarms and actions initiated when detectors are activated.
3. GENERAL
Client National Iranian south oil company (NISOC)
Title of project Naft Sefid Oil Field Gas & Oil System Optimization & Renovation
Project
Location Naft Sefid oil field is located about 70 km North-east of Ahwaz.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 8 of 44
5. ABBREVIATION
CGD Catalytic Gas Detector
DCS Distributed Control System
ESD Emergency Shut Down System
EWSD Early Warning Smoke Detector
F&G Fire and Gas Detection System
HVAC Heating Ventilating and Air Conditioning
IR Infra-Red
IRGD Infra Red Gas Detector
LED Light Emitting Diode
LEL Lower Explosive Level
MAC Manual Alarm Call Point
MW Molecular Weight
OD Outer Diameter
PSH High Pressure Switch
PSL Low Pressure Switch
ROR Rate-of-Rise
SD Smoke Detector
TGD Toxic Gas Detector
UV Ultra-Violet
LCP Local Control Panel
UCP Unit Control Panel
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 9 of 44
7. BASIS OF DESIGN
7.1 DESIGN PHILOSOPHY
Fire and gas detection devices shall be installed throughout the plant to detect hazardous
conditions resulting from gas leakage or fire, and to initiate appropriate alarms and
actions.
The actions could be an alarm, a fire extinguishing system activation, HVAC shutdown or
a trip signal (when required) to other systems such as ESD system. The alarms and actions
generated by the activation of each detector will be detailed in “F&G Cause & Effect
Charts” for each area.
Fire and Gas Detection System shall include, but not limited to, the following type of
input/output:
• Gas detectors (flammable/toxic);
• Flame detectors;
• MCPs activation;
• Deluge valves activation (If any);
• Audible and visual alarm devices;
• Total flooding discharge system activation;
• ESD system activation (If required);
• HVAC shut down.
• Smoke Detectors
• Heat Detectors
The process plant Fire and Gas Detection System shall be provided with sufficient and
reliable detectors to ensure personnel warning and allow immediate response to minimize
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 10 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 11 of 44
7.3.1 Capacity
Unless otherwise permitted or required by (a) or (b), the secondary power supply shall
have sufficient capacity to operate the fire alarm system under quiescent load (system
operating in a non alarm condition) for a minimum of 24 hours and, at the end of that
period, shall be capable of operating all alarm notification appliances used for evacuation
or to direct aid to the location of an emergency for 5 minutes.
(A) The secondary power supply for emergency voice/alarm communications service shall
be capable of operating the system under quiescent load for a minimum of 24 hours and
then shall be capable of operating the system during a fire or other emergency condition
for a period of 15 minutes at maximum connected load.
(B) The secondary power supply capacity for supervising station facilities and equipment
shall be capable of supporting operations for a minimum of 24 hours.
The secondary power supply capacity required shall include all power supply loads that
are not automatically disconnected upon the transfer to secondary power supply.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 12 of 44
particular by the presence of H2S. If located outdoors the detector shall not be sensitive to
the ambient humidity. Therefore, with the exception of hydrogen detectors, if used,
Infrared Gas Detectors (IRGD) should be given preference over Catalytic Gas Detectors
(CGD).
Flammable gas detectors shall be located taking into account the following criteria:
1. The most likely sources of leakage;
2. The proximity to possible sources of ignition;
3. The prevailing wind direction and wind speed;
4. The environment (dust, sand storms, humidity, vibrations and alignment).
5. Detectors shall be located on surfaces free from vibration and shall be fitted with
guards as protection from mechanical damage and the effects of rain, water, dust
and sand.
6. The density of gas leak; detector shall be positioned under the expected leak source
for heavier than air gases and above the expected leak source for lighter than air
gases. For detection of heavier than air gases, detectors shall be installed at a
height of 500 mm to 1000 mm above ground level or below source of leak (if
source of leak located on a platform, structure or higher elevation). For detection
of lighter than air gases, the detectors shall be installed at a height of around 500
mm above the potential source of leakage.
7. Gas can be considered heavier than air if its MW (molecular weight) > 33, lighter
than air if its MW < 23 and if 23< MW < 33, the conditions of release shall be
studied. If the condition of release is not conclusive, gas shall be considered as
being both heavier and lighter than air.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 13 of 44
the formation of flammable gas clouds and includes the following locations:
1. Seals of flammable gas compressors,
2. Pumps handling flammable liquids with Temp. > flash point,
3. Manifolds where many control valves are grouped,
Open path Infra Red (IR) detectors (commonly referred to as line of sight or beam
detectors) can be used in open process areas with inventories of flammable gas. They can
also be used where there is a need to identify that flammable gas is migrating to a non-
hazardous area or beyond the site boundary.
Open path gas detectors can be useful in monitoring gas migration across the interfaces
between hazardous and non-hazardous areas. Below cases could be considered as
examples:
1. The area where industrial zone and technical/non-technical buildings are separated.
2. Where high probability of gas cloud passage through technical/non-technical
buildings due to prevailing wind direction.
The application of open path IRGD for above mentioned areas is recommended for alarm
purposes only.
When using IR open path detection due consideration must be given to factors which can
affect the operation of such instrumentation and give rise either to spurious trips or beam
block warnings. Such affects include:
1. Obscuration due to fog,
2. Low level sunlight interference,
3. Lack of rigidity of mounting,
4. Lines of sight, including blockage by personnel, maintenance operations or
mechanical handling equipment.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 14 of 44
When 50% of LFL is confirmed by two detectors, appropriate level of Emergency Shut-
Down (ESD) of related process isolation section (corresponding to fire & gas detection
zone) shall be initiated.
When 3 LFLm is confirmed by two beam type detector, audible and visual alarm (red
flashing beacons) in whole plant shall be initiated.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 15 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 16 of 44
When 50% of LFL is reached by one detector, the following alarms shall be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm at the UCP.
4. Audible and visual alarm (red flashing beacons) in the process area.
When 50% of LFL is confirmed by 2oo3 voting logic, following alarms and actions shall
be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm at the UCP.
4. Audible and visual alarm (red flashing beacons) in the process area,
5. The air inlet shall be closed and the ventilation fans shall be shut-down,
6. The fired heater shall be shut-down.
When 50% of LFL is reached by one detector, the following alarms shall be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 17 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 18 of 44
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm at the UCP.
4. Audible and visual alarm (red flashing beacons) in the process area.
When 50% of LFL is confirmed by 2oo3 voting logic, following alarms and actions shall
be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm at the UCP.
4. Audible and visual alarm (red flashing beacons) in the process area,
5. The air compressor shall be shut down.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 19 of 44
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. Audible and visual alarm (red flashing beacons) in the process area.
When 50% of LFL is confirmed by two detectors, appropriate level of Emergency Shut-
Down (ESD) of related process isolation section (corresponding to fire & gas detection
zone) shall be initiated.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 20 of 44
When 25% of LFL is reached by any detector, the following alarms and actions shall be
activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. Audible and visual alarm (red flashing beacons) in the process area.
4. A visual alarm (red flashing beacon) outside the analyzer house.
5. Equipment of the analyzer house not suitable for zone-1 shall be shut-down and
electrically isolated,
6. The fresh air intake shall be kept open to decrease the gas concentration in the analyzer
house.
8.5.2.2 Flammable Gas Detectors at HVAC Air Intake
For the three (3) detectors located in the HVAC air intake, a two (2) out of three (3) voting
system shall be provided.
When 10% of LFL is reached by any detector:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (continuous red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm inside the analyzer house.
When 25% of LFL is reached by any detector, the following alarms and actions shall be
activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm inside the analyzer house.
4. Audible and visual alarm (red flashing beacons) in the process area.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 21 of 44
When two (2) out of three (3) logic is achieved, the following alarms and actions shall be
activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm inside the analyzer house.
4. Audible and visual alarm (red flashing beacons) in the process area.
5. A visual alarm (red flashing beacon) outside the analyzer house.
6. Equipment of the analyzer house which is not suitable for zone 1 shall be shut-
down and electrically isolated.
7. The fresh air inlet shall be closed and fans stopped.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 22 of 44
For detectors located at HVAC air intake, a two (2) out of three (3) voting system shall
be provided. When two (2) out of three (3) logic is achieved, the following alarms and
actions shall be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control
room.
2. A common audible alarm and a visual alarm (flashing red light of related fire
& gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm in the concerned building.
4. The inlet and outlet dampers shall be closed via HVAC PLC output.
5. The HVAC system shall be shut-down.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 23 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 24 of 44
• When 25% of LEL is reached by any detector, the following alarm and action
shall in addition be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control
room.
2. A common audible alarm and a visual alarm (flashing red light of related fire
& gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm in the concerned building.
4. The battery feeder shall be isolated,
5. The extraction fans shall be kept in operation to decrease the hydrogen
concentration.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 25 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 26 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 27 of 44
fire & gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm in the analyzer house.
When 15 ppm H2S is reached by any detector, the following alarms and actions shall
in addition be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing yellow light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm in the analyzer house.
4. Audible and visual alarm (yellow flashing beacons) in the process area.
5. A visual alarm (yellow flashing beacon) outside the analyzer house.
6. The fresh air intake shall be kept open to decrease the gas concentration in the
analyzer house.
7. Fans system shall continue to run with maximum RPM.
• Toxic Gas Detectors at HVAC Air Intake
When 5 ppm H2S is reached, personnel shall escape from the area wearing masks, and
any one detector shall activate:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (continuous yellow light of related
fire & gas detection zone) in F&G matrix panel in the control room.
3. An audible alarm in the analyzer house.
When 15 ppm H2S is reached by any detector, the following alarms and actions shall
be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing yellow light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. Audible and visual alarm (yellow flashing beacons) in the process area.
4. An audible alarm in the analyzer house.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 28 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 29 of 44
1. In the air intake ducts provided for the heating ventilation and air conditioning
(HVAC) systems (if any),
Inside the airlocks of these buildings (if any); one (1) flammable gas detector for each
airlock.
2. A common audible alarm and a visual alarm (continuous yellow light of related fire & gas
detection zone) in F&G matrix panel in the control room.
When 15 ppm H2S is reached, the following alarm and actions shall be activated:
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing yellow light of related fire & gas
detection zone) in F&G matrix panel in the control room.
3. Audible and visual alarm (yellow flashing beacons) in the concerned building.
4. The inlet and HVAC Fire /Gas outlet dampers (if any) shall automatically be closed.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 30 of 44
times by the worker it has been issued to. They shall be set to alarm at 5ppm and have
an operating range of 0 to 100ppm.
10 Nos. of portable toxic gas detector shall be provided for the Naft Sefid project
which are stored in control room building.
The detector as a minimum should have the following features:
1. Design code ATEX II 2G EEx iad IIC T4 (T amb -20°C to 65°C)
5. Rechargeable battery
8. Visual alarm
9. Vibrating alarm
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 31 of 44
in order to provide safety of employees by ensuring quick and safe leaving and
minimize asset damage.
In locating the fire detectors, the environmental criterion shall be taken into account
(sunrise, sunset, dust, sand storms, humidity, vibrations and alignment).
All detectors shall be suitable for use in Zone I, Gas Group IIB, and Temperature
Class T3.
Fire detectors are installed to detect one or more of the three characteristics of fire,
namely:
• Smoke
• Heat
• Infra-red or ultraviolet radiation
In some fire detection systems, a fire signal is initiated when the characteristic reaches
a pre-determined threshold. A signal may, instead or in addition, be initiated when the
rate-of-change of the characteristic is representative of a fire.
In the case of point detectors, the characteristic is detected at a defined point(s) within
the protected area. In contrast “line” detectors are capable of detecting the
characteristic along a defined line within the protected space.
In combined (multi-sensor) fire detectors, each detector contains more than one sensor
and thus monitors more than one of the fire characteristics (e.g. combined heat and
smoke detector).
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 32 of 44
However, other factors, such as cost, suitability for the environment and maintenance
requirements might need to be considered. In some circumstances, a mixture of
different types of detector may be appropriate to optimize speed of detection or to
minimize false alarms.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 33 of 44
1. A common audible alarm and a visual alarm on F&G panel in the control room.
2. A common audible alarm and a visual alarm (flashing red light of related fire &
gas detection zone) in F&G matrix panel in the control room.
3. Audible and visual alarm (red flashing beacons) in the process area.
4. Activation of related water spray system (dedicated deluge valve)
When 2ooN UV/IR detectors are activated for each designated area, appropriate level
of Emergency Shut-Down (ESD) of related process isolation section (corresponding to
fire & gas detection zone) shall be initiated.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 34 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 35 of 44
Linear heat detector located inside the tank shall be considered for automatic actuation
of foam system. Water spray ring should consist of two half rings.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 36 of 44
from cooking. Where there is a likelihood of false alarms caused by any of these
effects, a heat detector should be used instead. Therefore, smoke detectors should
never be installed in kitchens, bathrooms and shower rooms.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 37 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 38 of 44
meaning that there would be a risk of false alarms when using a ROR device. In this
case a fixed temperature detector would be suitable.
ROR heat detectors shall be provided for the following areas:
• Kitchen (if any)
• Bathrooms and shower rooms (if any)
The minimum static response temperature of heat detectors should not be less than
29oC above the ambient temperature that the detector can be expected to experience
for long periods of time, and not less than 4 oC above the maximum temperature that
the detector can be expected to experience for short periods of time under normal
conditions.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 39 of 44
Duplex loops shall be provided in areas for activation of total flooding system. Where
such an action is not required one single loop is acceptable.
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 40 of 44
For activation of CO2 total flooding systems, “2 out of dual circuits” voting logic shall
be provided (MV & LV switch gear room and cable gallery of substation building).
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 41 of 44
They shall be certified for Zone 1, Gas Group IIB, and Temperature Class T3.
Operation of a MACP shall activate:
1. A common audible alarm and a visual alarm on F&G panel in the control
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 42 of 44
room.
2. A common audible alarm and a visual alarm (flashing red light of related fire
& gas detection zone) in F&G matrix panel in the control room.
3. An audible and visual alarm in the concerned building (for MACPs located
inside building).
4. An audible and visual alarm in the process area (for MACPs located in process
area).
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 43 of 44
Document title:
Fire & Gas Detection Philosophy
Project No: 53-85204
National Iranian South Oil Company Document No.:85204-ED-HS-PHY-0003
Engineering & Construction Management
N.I.S.O.C Date: 95/08/25
Project: Naft Sefid Oil Field Gas & Oil System Optimization Rev: 00
& Renovation Project Page: 44 of 44
Visual alarms should be clearly distinguishable from other warning lights and should flash at a
rate of 30 to 130 flashes per minute. The recommended mounting height is above 2.1m;
however, they should not be mounted closer than 150mm from ceiling. They should be
positioned so that any alarm is clearly visible from all locations within the area in which they
are provided.
Explosion proof horns and beacons within the plant area shall be certified for use in Zone I
areas, Gas Group IIB, temperature class T3. They shall be accessible for maintenance
purposes.
Document title:
Fire & Gas Detection Philosophy