WG20.../1-C, version Z-LN (Low NOx)

G
Installation and operating instructions

as
M pre
ul ss
t
B ifun ure
al ct s
l v io w
al n itc
ve as h
se
m
bl
yW
-M
F

Info for engineers


83054602 – 1/2002
Conformity Certification
to ISO/IEC Guide 22
Confirmed by: Max Weishaupt GmbH

Address: Max Weishaupt Straße


D-88475 Schwendi

Product: Gas burner with fan


Type: WG20…/1-C, vers. Z

The products described above conform to

Document No.: EN 676


EN 292
EN 50 081-1
EN 50 082-1
EN 60 335

In accordance with the guidelines

90/396/EC Gas Appliances Directive


89/336/EC Electromagnetic Compatibility Directive
73/23/EC Low Voltage Directive
92/42/EC Hot Water Boiler Efficiency Directive
98/37/EC Machinery Directive

these products are labelled as follows

CE-0085BM0216

Schwendi 18.10.2001

ppa. ppa.
Dr. Lück Denkinger

Comprehensive Quality Assurance is ensured


by a certified Quality Management System to
DIN ISO 9001.

Regular maintenance saves energy and protects the environment


We recommend regular plant maintenance of all combustion quality is a pre-requisite for
combustion equipment. It saves fuel and ensures environmentally friendly operation.
constantly good combustion results. Excellent
Contents
1 General information 4

2 Safety information 5

3 Technical description 7
3.1 Permissible applications 7
3.2 Function 7

4 Installation 9
4.1 Safety information on installation 9
4.2 Delivery, transportation and storage 9
4.3 Preparation for installation 9
4.4 Burner installation 10
4.5 Valve train installation 11
4.6 Soundness test of valve train 12
4.7 Electrical connection 13

5 Commissioning and operation 14


5.1 Safety information on initial commissioning 14
5.2 Preparations for initial commissioning 14
5.3 Commissioning and setting 16
5.4 Shut down periods 20
5.5 Sequence of operation and wiring diagram 21
5.6 Operating the W-FM1023 23

6 Fault conditions and procedures for rectification 24

7 Servicing 26
7.1 Safety information on servicing 26
7.2 Servicing plan 26
7.3 Mixing head - removal and refitting 27
7.4 Mixing head - setting 27
7.5 Ignition electrode and sensor electrode setting 28
7.6 Service position of housing cover 28
7.7 Removing and refitting fan motor
and fan wheel 29
7.8 Removal and refitting of air servomotor
and air damper angle drive 29
7.9 Removing and refitting gas butterfly valve 30
7.10 Removing and refitting air regulator housing 30
7.11 Removing and refitting coil on multifunction
assembly (W-MF...) 31
7.12 Removing and refitting gas filter on W-MF 31
7.13 Replacing internal fuse W-FM10 32

8 Technical Data 33
8.1 Burner equipment 33
8.2 Capacity graphs 33
8.3 Permissible fuels 33
8.4 Electrical data 33
8.5 Permissible ambient conditions 33
8.6 Dimensions 34
8.7 Valve train 35
8.8 Weights 35

Appendix
Gas throughput calculation 36
Combustion analysis 37
Notes 38

3
1 General information
These installation and operating instructions Hand-over and operating instructions
• are an integral part of the equipment and must be kept The contractor is responsible for passing the operating
permanently on site. instructions to the plant operator prior to hand-over.
He should also inform the plant operator that these
• are for the use of qualified personnel only. instructions should be kept with the heating appliance.
The address and telephone number of the nearest service
• contain the relevant information for the safe assembly, centre should be entered on the reverse of the operating
commissioning and servicing of the equipment instructions. The plant operator must note that an agent
of the contractor or other suitably qualified person must
• are for the attention of all personnel working with the inspect the plant at least once a year. To ensure regular
equipment. inspections, -weishaupt- recommends a service contract.

Explanation of notes and symbols The contractor should instruct the plant operator in the use
This symbol is used to mark instructions, of the equipment prior to hand-over and inform him as and
which, if not followed, could result in death or when necessary of any further inspections that are
serious injury. required before the plant can be used.

DANGER Guarantee and liability


In principle, our “Conditions of Sale” are in force.
This symbol is used to mark instructions, Weishaupt will not accept liability or meet any guarantee
which, if not followed, could result in life claims for personal injury or damage to property arising as
threatening electric shock. a result of one or more of the causes below:

DANGER • Failure to use the equipment as intended


• Improper assembly, commissioning, operating or
servicing of the equipment.
• Operating the appliance with defective safety
This symbol is used to mark instructions, equipment, or with non-recommended or
which, if not followed, could result in damage nonfunctioning safety and protection devices
to, or the destruction of the equipment and en- • Failure to follow the information in the Installation and
vironmental damage. Operating Instructions
ATTENTION • Alterations made to the construction of the equipment
by the plant operator
• Fitting additional components not tested or approved
☞ This symbol is used to mark procedures, for use with the equipment.
which you should follow. • Alterations made to the equipment by the plant operator
(e.g. motor ratio - rating and speed)
1. Procedures with more than one step are • Alterations made to the combustion chamber, which
numbered. hinders constructive, predetermined flame formation
2. • Inadequate monitoring of parts liable to wear and tear
3. • Improperly executed repairs
• Acts of God
❑ This symbol is used when you are required • Damage caused by continued use despite the
to carry out a test. occurrence of a fault
• Use of incorrect fuel
• This symbol is used to list points. • Obstruction or damage of the supply lines
• Use of non-original -weishaupt- spare parts
Abbreviations
Tab. Table
Ch. Chapter

4
2 Safety information
Dangers when using the equipment Electrical safety
Weishaupt products are manufactured in accordance with • Work on the electrical supply should be carried out by a
the relevant existing standards and guidelines and the qualified electrician.
recognised safety laws. However, improper use of the • Electrical components should be checked during
equipment could endanger life of the user or a third party, servicing. Loose connections and heat damaged cables
or result in damage to the plant. should be dealt with immediately.
• The control panel should be locked at all times. Access
To avoid unnecessary danger, the equipment is only to be should be restricted to authorised key holder personnel.
used: • Should it be necessary to carry out work on live parts,
• for its intended purpose a second person should be present to switch off the
• under ideal safety conditions mains supply in an emergency.
• with reference to all the information in the installation
and operating instructions Maintenance and fault rectification
• in accordance with inspection and service work • Necessary installation, service and inspection work
should be carried out at the specified time.
Faults, which could affect the safe operation of the burner, • Inform the operator before beginning any service work.
should be rectified immediately. • For all service, inspection and repair work, electrically
isolate the equipment and ensure the mains switch
Personnel training cannot be accidentally switched back on. Cut off the
Only competent personnel may work on the appliance. fuel supply.
Competent personnel according to this operating manual • If, during servicing or testing, control seal joints have to
are persons who are familiar with the installation, be opened, these have to be thoroughly cleaned to
mounting, setting and commissioning of the product and ensure tight sealing when re-assembling.
have the necessary qualifications such as:- Damaged seals must be replaced. Carry out a
soundness test!
• Training, instruction or authorisation to switch electrical • Flame monitoring devices, limit controls, correcting
circuits and electrical devices on and off, to earth them elements and all other safety devices must be
and to mark them in accordance with the safety commissioned by, and may only be replaced by, the
standards. manufacturer or an authorised agent.
• Screwed connections, which have been loosened, must
Organisational measures be re-tightened without cross-threading.
• The necessary protective clothing should be worn by • Following service work, all safety devices should be
everyone working on the plant. tested to ensure they are functioning correctly.
• All safety devices should be checked regularly.
Alterations to the construction of the equipment
Informal safety measures • No alterations to the equipment are to be made without
• In addition to the installation and operating instructions, the approval of the manufacturer.
local codes of practice should also be adhered to. All conversions require written confirmation from Max
Special attention should be paid to the relevant Weishaupt GmbH.
installation and safety guidelines (i.e. Local Codes of • Any parts not in perfect working order should be
Practice). replaced immediately.
• All safety and danger notices should be kept in a legible • No additional components may be fitted, which have not
condition. been tested for use with the equipment
• Use only -weishaupt- replacement and connection
Safety measures in normal operation parts. Parts from other manufacturers are not
• Only use the equipment when all the safety devices are guaranteed to be suitable to meet the necessary
fully functional. operational and safety requirements.
• At least once a year the equipment, including the safety
devices, should be checked for signs of visible damage Alterations to the combustion chamber
and to ensure that the safety devices are operating • No alterations are to be made to the combustion
correctly. chamber, which hinder constructive predetermined
• More frequent safety check may be required depending flame formation.
on plant conditions.
Cleaning of the equipment and waste disposal
Safety measures when gas can be smelt • All materials used should be handled and disposed of
• Avoid open flames and spark generation (e.g. switching correctly, with due regard to the environment.
lights and electric units on and off)
• Open doors and windows
• Close gas shut off valve
• Warn all occupants and evacuate the building
• Inform heating company/installer and gas supplier - from
outside of the building

5
General information for gas operation Gas characteristics
• When installing a gas combustion system, regulations The following information must be obtained from the gas
and guidelines must be observed (i.e. Local Codes of supplier:
Practice and Regulations). • Type of gas
• The subcontractor responsible for the installation or • Calorific value in MJ/m3 or kWh/m3
changes of the gas system must inform the gas supplier • Max. CO2 content of flue gas
of the type and extent of the installation planned and the • Gas supply pressure.
intended work.
The subcontractor must ascertain that an adequate gas Pipe thread connection
supply to the installation is ensured. • Only tested and approved sealing material should be
• Installations, alterations and maintenance work on gas used. Please observe the prevailing user instructions!
systems in buildings and below ground, must only be
carried out by installers who have a contract with the Soundness test
gas supplier. • see Ch. 4.6
• The gas pipework must be subject to a preliminary and
main test or the combined loading test and soundness Conversion to other gases
test, according to the pressure range intended. Burner • When converting to another gas type, a conversion kit
must be isolated. and re-commissioning is required.
• The air or purge gas required for the test must be
expelled from the pipework. The pipework must be
completely purged.

6
3 Technical description
3.1 Permissible applications
The Weishaupt WG20 gas burner is suitable for: • The burner must only be operated with the type of gas
• mounting on heat exchangers according to EN303-3 or given on the burner plate.
DIN4702-1 • The burner must only be operated under the permissible
• on warm water plant with intermittent or continuous ambient conditions (see Ch. 8.5)
operation (combustion manager will switch off once • The burner must not be used outside. It is only suited for
during 24h) operation inside.
• The burner must not be used outside of its capacity
Any other use is only permissible with the written range (see capacity graphs, Ch. 8.2).
agreement of Max Weishaupt GmbH. • The gas supply pressure must not exceed the gas
pressure given on the burner plate.

3.2 Function
Burner type Flame sensor
Forced draught gas burner for single or two stage Monitors the flame signal during every operating phase. If
operation. the flame signal does not concur with the sequence of
• Single stage: Ignition load ➱ full load via 4 pole operation, a safety shutdown is activated.
connection plug (supplied loose, fitted with bridge
according to wiring diagram) Air pressure switch
• Two stage: Ignition load ➱ partial load ➱ full load If the air supply fails the air pressure switch activates a
via 4 pole plug from heat exchanger safety shutdown.

Digital combustion manager Sequence of operations


Main points: Demand for heat from the boiler controller:
• Protection via internal fuse • Servomotor is tested
• Control and monitoring of all burner functions • Fan start - prepurge of the combustion chamber
• Safety via two microprocessors (reciprocal monitoring) • Ignition on
• Data bus connection (eBUS) • Solenoid valves open - fuel release
• Signal lamp to show operational status: • Flame formation
Green Burner operating • Depending on heat demand the air damper and gas
Flashing green Burner operating with weak butterfly open in compound
ionisation current • After 24 hrs. continuous operation a controlled
Orange Burner start, internal test shutdown is activated.
Flashing orange Ignition phase
Red Burner lockout Sufficient heat attained:
Flashing orange / red Low voltage or internal fuse fault • Solenoid valves close
Flashing green / red Extraneous light • Post-purge of the combustion chamber
Flashing red/ orange Over-voltage • Valve proving of solenoid valves
Short pause • Burner switches off - Standby
Flashing red Insufficient gas

Servomotor
A servomotor on the air damper drive controls the gas/air Schematic of gas valve trains
compound via mechanical connection with the gas
butterfly valve.

Multifunction assembly W-MF-055
with the following functions: ➁
• Pressure regulator ➂
Equalises possible gas pressure variations of the gas
supply main, ensures a constant gas pressure and an ➀
even gas throughput. Regulating pressure is adjusted
with the setting screw.

• 2 Solenoid valves (class A) P


• Gas filter
• Gas pressure switch
• If the gas pressure is insufficient the low gas
programme is initiated. The gas pressure switch ➀ Ball valve
is also employed for automatic valve proving. ➁ Multifunction assembly
➂ Gas butterfly valve
➃ Burner

7
Start up test at burner start Valve proving
At each burner start, a function test of the servomotor and Following a controlled shutdown of the burner valve
the air pressure switch is carried out. If a deviation from the proving is activated automatically. The combustion
intended programme is detected, start up is interrupted manager checks for incorrect pressure increase and
and the burner goes to lockout. decrease within the gas section.
If the gas pressure increase is correct and no pressure
Low gas programme loss is present, the burner goes to “Standby”.
The gas pressure switch monitors the min. gas pressure
between the two valve seats of the W-MF. If the gas If the burner goes to lockout or shuts down due to power
pressure switch has not been activated due to low gas failure, valve proving is carried out at the next burner start:
pressure the burner start is interrupted. After a waiting
time of 10 minutes a re-start of the burner is attempted. If • Automatic restart
the gas pressure is still too low, a third attempt at • Valve proving
restarting the burner will commence after a further waiting • Burner starts
time of 10 minutes. After the fifth unsuccessful attempt to
start the burner, the start will only be attempted after a
waiting time of one hour.

8
4 Installation
4.1 Safety information on installation
Electrically isolate the plant
Prior to installation switch off the mains switch
and the safety switch.

Failure to comply could cause death or se-


DANGER rious injury by electric shock.

4.2 Delivery, transportation and storage


Check delivery
Check the delivery to see that it is complete and that there
has been no damage in transit. If the delivery is incomplete
or damaged, contact the supplier.

Transport
For the transport weights see Ch. 8.8.

Storage
Please note the permissible ambient conditions for
storage (see Ch. 8.5).

4.3 Preparation for assembly


Check burner nameplate
❏ The burner rating must be within the operating range of
the heating appliance.
The ratings given on the burner nameplate are the
minimum and maximum possible firing rates of the
burner; see capacity graphs Ch 8.2.

Space requirement
Burner and valve train dimensions see Ch. 8.6.

9
4.4 Burner installation

Preparing the heat exchanger Refractory and drilling dimensions


The diagram shows the refractory for a heating appliance
without cooled front. The front edge of the combustion Drilling dimensions
head should protrude approx. 30 mm beyond the on heat exchanger
refractory. The refractory can, however, take a conical Refractory d4
shape (≥60°). Refractory may not be required on boilers d2
with water-cooled fronts, unless the manufacturer gives Flange gasket
other instructions. The gap between 45°
combustion head and
Comb. Dimensions in mm refractory must be d1 d5
filled with resilient,
head d1 d2 d3 d4 d5 l1 non combustible
insulating material.
WG20-C 120 M8 170 130 135 140 Do not make solid. I1 d3

** Depending on type of heat exchanger.


See manufacturers information! 0…30**

Burner mounting Burner mounting


1. Remove mixing head ➄ (see Ch. 7.3)
2. Loosen screw ➃.
3. Separate burner flange ➁ with flame tube from housing.
4. Fix burner flange with screw ➂ to the boiler plate.
5. Place burner housing onto stay bolts ➅.
6. Screw in screws ➃ and tighten. ➀
7. Check setting of ignition and ionisation electrodes (see ➁
Ch. 7.5).
8. Refit mixing head (see Ch. 7.3) ➄ ➅
Ensure the gasket is placed correctly.

Fitting burner rotated by 180° ➂


For valve trains fitted from the left, the burner can be
rotated by 180°. No other conversion work is required.

Danger of getting burnt
Some burner parts (e.g. flame tube, burner
flange, etc.) become hot during burner opera- ➃
tion and should be allowed to cool prior to ser-
DANGER vice work being carried out.

➀ Flange gasket ➃ Hexagonal screw


➁ Burner flange ➄ Mixing head
➂ Hexagonal screw ➅ Stay bolt

10
4.5 Valve train installation
Risk of explosion! ☞ Valve trains must be mounted tension-free.
Gas leaks can lead to the build-up of explosive Do not compensate for misalignment by over-tigh-
gas/air mixtures. With the presence of an tening. Do not tighten or seal pipe thread connections
ignition source, these then result in while mounted on the burner.
DANGER explosions. ☞ The valve trains must be fixed and supported securely.
They must not be allowed to vibrate during operation.
To avoid accidents, please follow the following safety Supports suitable for the site should be fitted during
instructions on valve train installation. installation.
☞ Before beginning work, close all the relevant shut ☞ Only sealing agents tested and approved by the gas
off devices and ensure they cannot be accidentally supplier must be used.
reopened. The double nipples supplied have already been coated
☞ Ensure the valve train components are correctly alig- with an approved substance; therefore no other sealing
ned and that all the joints are clean. is required when mounting the double nipples. When
☞ Flange seals must be fitted correctly on the machined remounting the nipples, the old coating has to be
faces. removed and a new sealing agent used.
☞ Tighten screws evenly diagonally opposite.

Mounting the valve train from the right Note W-MF: Can be mounted in the horizontal
1. Remove the protective film from the gas connection or vertical plane.
flange.
2. Mount the components, pre-assembled, in the order
shown in the diagram.
Installation example

➁ ➃

➀ ➁
➀ ➀

➀ Double nipple
➁ Multifunction assembly W-MF...
➂ Elbow
➃ Ball valve with flange

Mounting the valve train from the left Converting gas pressure switch for valve train from the left
With the burner rotated through 180°, the valve train as
described above can be fitted from the left.
However, the following measures are required.

1. Prior to mounting the multifunction assembly:


Remove gas pressure switch ➂ .
2. Remove closing plug ➀ .
3. Fit gas pressure switch on opposite site. Pay attention ➀
when fitting the O ring ➁ !
4. Refit closing plug on opposite site.

➁ ➂

11
4.6 Soundness test of valve train
❏ The valve train soundness test must be carried out with Soundness test
the ball valve and solenoid valve closed.

Test pressure in valve train ___________ approx 100 mbar


Waiting time for pressure equalisation ________ 5 minutes
Test time ________________________________ 5 minutes
Max. permissible pressure drop ________________ 1 mbar
(gas train design pressure _____________ max. 500 mbar)

First test phase:


Ball valve up to first valve seat
1. Connect test assembly to test point ➀ .
2. Open test point ➁ .

Second test phase: ➀


Between the valves and second valve seat
1. Connect test assembly to test point ➁ .
2. Open test point ➂ . ➂

Third test phase:
Valve train connection parts and gas butterfly valve ➁
1. Fit blanking plate ➀ .
(see notes Ch. 7.3)
2. Fit measuring device to test point ➂ once soundness 3rd Test phase 2nd Test phase 1st Test phase
test is complete.
3. Spray with leak detecting solution during operation.
4. Tighten Torx screws on mixing head. ➀ Blanking plate
➁ Measuring device (U tube or manometer)
Note: To carry out a soundness test, brush connection ➂ Manual pump
points with foam forming agents or similar, ➃ Hose clamp
non-corrosive material

Test points on multifunction assembly Test points on W-MF 507 / 512


For the soundness test, the test points must be opened
by loosening the screw in the test nipple.

☞ Close all test points once the soundness test


is completed!

Documentation
☞ The results of the soundness test must be documented ➌ ➋ P ➊
in the service report.


➋ ➊

Test point ➊ : Pressure into filter (inlet)


Test point ➋ : Pressure between V1 and V2
Test point ➌ : Gas setting pressure

12
4.7 Electrical connection
1. Check polarity of the connection plugs ➀ and ➁ . Electrical connection
Wiring diagram see Ch. 5.5.

2. Plug 4 pole connection plug ➀ for ratings regulator into
combustion manager.
Single stage operation: Fit enclosed plug with bridge
as per wiring diagram. ➃
Two stage operation: Connect plug to heat exchanger
as per wiring diagram.

3. Plug in 7 pole connection plug of the boiler control.

4. Plug cables ➂ and ➃ leading from the burner housing


into the gas pressure switch and multifunction
assembly (W-MF) (plugs are coded) and tighten
screws.

Connection to the mains supply should be carried out to


the wiring diagram relevant for the type of unit. ➁

Notes for Austria
Electrical isolation having a minimum of 3 mm contact gap,
acting on all poles, must be fitted adjacent to the burner.
Possibilities are: ➀ 4 pole connection plug for ratings regulation
➁ 7 pole connection plug of boiler control
• Switch (without micro-contacts) ➂ Connection plug multifunction assembly (W-MF)
with required separation characteristics ➃ Connection plug gas pressure switch
• Circuit breaker
• Contactor
• Screw in type fuse with clearly recognisable
designation

13
5. Commissioning and operation
5.1 Safety information on initial commissioning
The initial commissioning must only be carried out by the Furthermore, the correct fusing of the circuits and
supplier, manufacturer or their appointed agent. At this measures for protection of electrical equipment and of
time, all control and safety equipment must be checked associated wiring must be checked.
to ensure correct operation and, if they can be adjusted, it
should be checked they have been set correctly.

5.2 Preparations for initial commissioning


Purging the gas supply line Note If work has been carried out on the gas line,
The gas supply line may only be purged by the local gas i.e. exchanging of parts, valve trains or gas meters,
authority. Lines have to be purged with gas until the re-commissioning may only be carried out after the
remaining air or inert gas has been expelled from the line. relevant lines have been purged by the local gas
The ball valve on the gas train must be kept closed during authority.
supply line pressure tests and purging

Check gas supply pressure Check gas supply pressure


Risk of explosion!
Max Weishaupt GmbH, 88475 Schwendi
If the supply pressure is too high it can da-
mage the valve train. The gas supply pressure Burner type
Version
must not exceed the maximum permissible
DANGER valve train pressure given on the burner plate. 0085 Cat. Gas type N
Conn. pressure min. max mbar
Check the supply pressure before purging the Rating kW kg/h
valve train: Oil
Mains
to DIN 51 603 BN
V~ Hz A gl
el. rating kW kW
Year of m.
1. Connect pressure gauge to the inlet of the multi- Serial No.

function assembly ( test point ➊ ).


2. Slowly open the ball valve while watching the pressure
gauge.
3. Close the ball valve immediately the supply pressure
exceeds the maximum permissible valve train pressure
(500 mbar).
Do not start burner!
Inform the plant operator.

Purging the valve train Purging the valve train


❏ The gas supply pressure must be correct.
1. Connect a hose, leading out to safe atmosphere, to
test point ➊ .
2. Open the ball valve.
The gas in the valve train is vented to safe atmosphere
via the hose.

For smaller gas quantities, a suitable test burner can be fit-


ted to the outlet of the hose to burn off the gas.

14
Connect gas manometer Connecting gas manometer
To measure the gas pressure during commissioning.
(Test point ➌ ).

Checklist for initial commissioning ❑ Thermostat, pressure switch and other safety devices
❑ The heating appliance must be assembled ready for must be in operating position.
operation. ❑ There must be a demand for heat.
❑ The operating instructions of the heat exchanger must ❑ Fuel lines must be purged of air.
be followed. ❑ The soundness of the valve train must be tested and
❑ The whole plant must be wired correctly. documented.
❑ The heating appliance and the heating system must ❑ The gas supply pressure must be correct.
be sufficiently filled with heating medium. ❑ Fuel cut off devices must be closed.
❑ Flues must be free from obstructions.
❑ The ventilators on air heaters must work correctly. Note Dependent on site requirements, further checks
❑ Sufficient fresh air must be available. may be necessary. Note the instructions for the
❑ The required test points for combustion analysis must individual items of plant equipment.
be available.
❑ Ensure that the heat exchanger and the flue gas
section up to the test opening are sound, so that the
test results are not corrupted by extraneous air.
❑ Liquid level controls must be set correctly.

15
5.3 Commissioning and setting
Determine values for pre-setting The values have been calculated on test flame tubes
1. Select and set the required pre-setting for the air (EN 676) under idealised atmospheric and combustion
damper and diffuser. chamber conditions (maximum combustion chamber
resistance to EN 303). Therefore small variations may
2. Select gas setting pressure. occur when commissioning depending on individual
(setting carried out during burner operation) installations.
These values result in an air factor of λ 1.15.

Example 1 Example 2
Required combustion heat rating: 100 kW Required combustion heat rating: 150 kW
Combustion chamber pressure: 1.5 mbar Combustion chamber pressure: 1.0 mbar

Results in:
Diffuser setting: 0 mm Results in:
Air damper setting: 50° Diffuser setting: 5 mm
Air damper setting: 80°

Setting diagram for pre-setting air damper - diffuser


3
70°
Air damper setting 50° 60° 80°
2.5
2,5 40°
Combustion chamber pressure [mbar]

30°
1.5
1,5 Example 1

20°
1 Example 2

0.5
0,5 10°

0 14

-0.5
-0,5
0 2 4 6 8 10 12
Diffuser setting
-1
20 40 60 80 100 120 140 160 180 200 220

Combustion heat rating [kW]

Note: Combustion heat rating for full load should not be Setting screw for diffuser setting (dimension X)
selected below 80kW.

The setting screw is flush with the


housing when dimension X = 0
Factory pre-set: X = 5

16
Setting and connection pressures

Burner Setting pressure Connection pressure min.


rating after pressure (flow pressure in mbar into shut off valve)
[kW] regulator [mbar] Nominal diameter of valve train
W-MF 507 W-MF 512
3/4” 1” 1”

Natural Gas E, Hi = 37.26 MJ/m3 (10.35 kWh/m3), d = 0.606, Wi = 47.84 MJ/m3

80 8,5 – 13 –
90 8,5 – 13 –
100 8,5 – 13 –
110 8,5 – 14 –
120 8,5 – 14 –
130 8,9 – 15 –
140 9,3 – 15 –
150 9,6 – 16 –
160 9,8 – 16 –
170 10,1 – 16 –
180 10,3 – 16 –
190 10,6 – 17 –
200 10,9 – 18 –

Natural Gas LL, Hi = 31.79 MJ/m3 (8.83 kWh/mn3), d = 0.641, Wi = 36.67 MJ/m3

80 11,0 – 15 13
90 11,0 – 15 13
100 11,0 – 15 14
110 11,0 – 16 14
120 11,0 – 16 15
130 11,4 – 17 16
140 11,7 – 18 16
150 12,2 – 18 17
160 12,7 – 19 17
170 13,2 – 20 18
180 13,6 – 21 18
190 14,0 – 22 19
200 14,4 – 23 20

Liquid Petroleum Gas B/P, Hi = 93.20 MJ/m3 (25.89 kWh/m3),


d = 1.555, Wi = 74.74 MJ/m3

80 9,3 13 – –
90 9,3 13 – –
100 9,3 13 – –
110 9,3 14 – –
120 9,3 14 – –
130 9,6 14 – –
140 9,9 14 – –
150 10,2 15 – –
160 10,4 15 – –
170 10,7 16 – –
180 11,0 17 – –
190 11,9 18 – –
200 12,8 19 – –

The information given for calorific value Hi and the Wobbe index Wi relate to 0°C and 1013.25 mbar.

The results of the table have been calculated on flame Set gas pressure
tubes under idealised conditions (pF = 0 mbar). The values
are therefore guidelines for basic settings. Small variations
may occur when commissioning depending on individual
installations.

Note The combustion chamber pressure has to be


added to the setting pressure calculated.
20
4

8
12 16

Factory pre-setting: 7 mbar


17
Function test Setting the limit switch
1. Open ball valve and close again for sequence test with
ball valve closed.
2. Switch on burner. Burner starts in line with the
sequence of operation.
3. The gas pressure switch detects insufficient gas. The
combustion manager goes to the low gas programme

ST0 ST2 ST1


(flashing red).
4. Reset low gas programme by pressing the reset-button.

Commissioning MV2 ZL
ZL
MV2
❑ Presettings of diffuser, air damper, multifunction Oil Gas
Öl Gas
assembly must have been carried out.
❑ Ignition (ZL) and partial load (ST1) switches must be
set to 5° (factory setting).
❑ Set full load limit switch (ST2) to previously calculated
value.

Danger of explosion!
CO build-up due to incorrect setting of the
burner. Check CO levels and when there is Factory pre-setting:
a CO reading above desired value optimise
DANGER combustion. CO should not exceed 50 ppm. ST0 : __________ 0°
ST2 : _________ 60°
Single stage operation: ST1 : __________ 5°
1. Remove 4 pole connection plug (with bridge as per ZL : __________ 5°
wiring diagram)
2. Open gas ball valve and switch on burner.
3. Pre-purge starts in full load position. Two stage operation:
4. Following pre-purge the servomotor goes to ignition 1. Remove 4 pole connection plug and replace with plug
load. switch (order No. 130 103 1501/2)
5. Flame formation following valve proving. 2. Open gas ball valve and switch on burner.
6. Set setting pressure to table value. 3. Pre-purge starts in full load position.
7. Plug in 4 pole connection plug ➯ burner runs to full 4. Following pre-purge the servomotor goes to ignition load.
load. 5. Flame formation following valve proving.
8. Carry out combustion control (see appendix) and gas 6. Set setting pressure to table value.
throughput measurement. 7. Drive to full load via plug switch.
9. Correct gas quantity by adjusting gas setting pressure. 8. Carry out combustion control (see appendix) and gas
10. Correct excess air by adjusting air damper and diffuser throughput measurement.
setting. 9. Correct gas quantity by adjusting gas setting pressure.
11. Remove connection plug again ➯ burner goes to 10. Correct excess air by adjusting air damper and diffuser
ignition load, carry out combustion control and set setting.
excess air (see table Setting values ignition load) by 11. Drive to ignition load via plug switch, carry out
adjusting the gas quantity at setting screw 1. combustion control and set excess air (see table
12. Plug in connection plug (4 pole). Setting values ignition load) by adjusting the gas
quantity at setting screw 1.
12. Set partial load at limit switch ST1 whilst observing the
instructions given by the manufacturer and carry out
combustion control
Set excess air at setting screw 2.
Correct gas throughput by adjusting limit switch (ST1).
13. Plug in connection plug (4 pole).

Note After adjusting a limit switch, its new switch point Setting screw gas butterfly valve
has to be restarted. On single stage operation this
is done with the 4 pole connection plug, on two
stage operation with the commissioning plug
switch.

Setting values ignition load 3


2
Gas type CO2 O2 1
Nat. Gas LL 8.8 - 9.3% 5 -4%
Nat. Gas E 9.0 - 9.5% 5 -4%
Liquid Petroleum Gas 10.3 - 11.0% 5 -4%
Effective range of setting screws:
Screw 3 :________________ 50° to 80°
Screw 2 :________________ 20° to 50°
Screw 1 : _________________ 0° to 20°

Manufactured settings: ____screw heads flush with housing


18
Carry out controlled start Correcting measures with poor start behaviour:
Open control circuit. • Reduce mixing pressure by turning the setting screw of
• Valve proving is carried out. the diffuser to the left (increase distance diffuser -
combustion head front edge).
Close control circuit and monitor start behaviour of burner • With poor flame formation (observe ionisation current)
• Burner start. increase gas quantity at the ignition load limit switch
• Ignition load is started. (ZL).
• Following flame formation servomotor drives to ignition • With start up impact reduce gas quantity at ignition load
or full load. limit switch (ZL).

Note If further changes of the gas setting pressure or the


diffuser setting are required, the whole burner
setting (including pre-setting) has to be repeated.

Measuring ionisation current Measuring ionisation current


If a flame is present, an ionisation current flows.

Response sensitivity of the flame sensor: __________ 1 µA


Minimum recommended ionisation current:_________ 5 µA

Test unit:
Multimeter or ammeter.

Connection:
A plug coupling in the ionisation line is used to connect the
test unit.

Setting the gas pressure switch Gas pressure switch


Factory pre-setting: 12 mbar
The switch point must be checked and adjusted during
commissioning
Test point
1. Connect a manometer at the test point between V1
and V2 of the W-MF.
2. Remove protective cap of the gas pressure switch.
3. Start the burner (full load).
4. Slowly close the ball valve until the gas pressure drops
to half the value, monitoring CO value and flame
stability.
5. Turn setting cam to the right, until the combustion
manager starts the low gas pressure program
Minimum value: 12 mbar.
6. Open ball valve.
7. Press reset-button to interrupt the low gas pressure
program.
Burner must start without low gas pressure program.

19
Set air pressure switch Air pressure switch
Factory pre-set: 3.5 mbar
The switch point must be checked and adjusted during
commissioning.
For this a differential pressure measurement between
points 1 and 2 is required.

1. Install manometer as shown in the picture. 5 4


2. Start the burner.

3
LG
3. Drive through the setting range of the burner, observing

2
10
A2
8
pressure behaviour at manometer.

1
9 10

4. Determine the lowest differential pressure value.


5. Set 80% of the lowest differential pressure at the
setting adjuster dial.

Example:
Lowest differential pressure: ________________4.4 mbar
Switch point air pressure switch: ___4.4 x 0.8 = 3.5 mbar

Note Installation dependant influences on the air


pressure switch, such as flue gas system, heat
exchanger, installation or air supply, the settings
may result in adjustments having to be made. Differential pressure test

➀+
➁–

Concluding work
1. Record test results of the flue gas test on the
inspection card.
2. Fit burner cover.
3. Advise operator on use of equipment.

5.4 Shutdown periods


For short breaks in operation
(e.g. flue cleaning etc.)
☞ Isolate the burner from the power supply.

During longer shutdown periods


1. Isolate the burner from the power supply.
2. Close all fuel shut off devices.

20
5.5 Sequence of operation and wiring diagram
Sequence of operation diagram

Boiler control Start ignition Release ratings Boiler control


ON load regulator OFF
Air damper to Start full
Ignition Valve proving
full load setting load
Gas valve Ready for
Pre-purge
open operation
(Standby)
Start partial
load

Boiler control
TN
Burner motor
TV
Air pressure
switch
TNZ
Ignition unit

Gas pressure
switch
TS
Flame signal
TVZ TP1 TP2
1st. valve

2nd. valve
TW
(3rd. valve)
TF
Ratings regulator

TVK TVK
Servomotor GL

KL

ZL

Zu

Switch times Valve proving


Start-up waiting time (test) TW 3 secs. Following a power cut, the low gas pressure programme
Pre-purge time TV 20 secs. or a burner lockout, valve proving is activated at the
Pre-ignition time TVZ 2 secs. beginning of the burner start.
Post ignition time TNZ 3.5 secs.
Safety time TS 2.8 secs.
Residence time partial load TVK 5 secs.
Flame stabilisation time TF 2 secs.

Test time valve proving


Phase 1 TP1 ( 1. valve ) 9.3 secs.
Phase 2 TP2 ( 2. valve ) 9.7 secs.

Post purge time TN 24 secs.

Servomotor run time in operation


full setting movement 0° – 90° approx. 3 secs.

21
22
W-FM10 62162/000204
K1
K3 K2

K3 K4 K5
Basic wiring diagram

A1
F7

L PE N T1 T2 S3 B4 B5 T6 T7 T8

X4:1
X3:11
X3:3
X3:4
X3:13
X3:12
X3:5
X3:1
X3:6
X5:1

X6 X7

X9

(L1)
(N)
(L2)
(PE)
(N)
(PE)
(L1)
(L2)

_
X8
+ A B 1 2 3 1 PE 2 3
ϑ
M1 M
P M P
~ P 1 2
S2

Air/Gas
F4
ϑ ϑ Y20 F10 C1 T1 F11 Y2 Y4
P P
H2
F2
F3 Combustion managers
➀ are safety devices.
Do not open!

h DANGER
S1 H1 P1
F1
F7
Max.
16A X6 + X7
Legend: S1 Main switch
L PE N A1 Combustion manager with plug connector S2 Remote reset (optional)
230V 1/N/PE 50/60Hz B1 Flame sensor T1 Ignition unit
C1 Motor capacitor X3 Plug console 5
F1 External fusing (max. 16 A) X4 Printed circuit boards - direct plug (servomotor)
1
F2 Temperature / pressure limit controller X5 Printed circuit boards - direct plug (Bus/S2)
F3 Temperature / pressure controller X6, X7 Burner connection plug 4
F4 Temperature / pressure controller full load ➀ Bridging plug X7 for single stage operation 6
F7 Internal fuse 6.3A X8 Flame sensor test plug
F10 Air pressure switch X9 Double solenoid valve plug 11
F11 Low gas pressure switch Y2 Double solenoid valve 3
H1 Fault lamp Y4 External valve (liquid petroleum gas)
H2 Operation lamp Y10 Three way valve 12
M1 Burner motor Y20 Servomotor 13
P1 Hours run meter (optional)
5.6. Operating the W-FM 10

Function of signal button Accidental operation of the button for less than 1 second:
The signal button incorporated into the W-FM 10 carries Code deleted, manager remains in lockout.
out the following functions:
• Resetting burner lockout
• Transmitting an optical diagnostic code
• Optical data transfer** Press illuminated push button only slightly until
Depending on the existing situation (burner operating or in its switch point can be felt. Pressing the push
lockout) the signal button has to be pressed for either 1 or button too hard can damage the combustion
5 seconds to start the required function. manager.
ATTENTION

Burner operation > switch off Burner lockout > reset

green orange green red orange grün


green

~ 1 sec. ~ 1 sec.

On On Off On

Burner lockout > diagnostic code ON Burner lockout > diagnostic code OFF

red orange flashing red* flashing red* orange green

~ 5 sec. ~ 1 sec.

Off Off On

If accidental pressing of the button has activated the


optical data transfer, this can be deactivated by pressing
the button again and following the sequence diagram
below.

Lockout > diagnostic code > data transfer ON** Lockout > diagnostic code > data transfer OFF**

flickering red orange flickering red flickering red orange green

~ 5 sec. ~ 1 sec.

Off Off On

Lockout > diagnostic code > data transfer ON** Lockout > diagnostic code > data transfer OFF**

green flickering red flickering red orange green

~ 5 sec. ~ 5 sec.

On Off On On Off On

* Matching of diagnostic codes see Ch. 6


** is not used
23
6 Fault conditions and procedures for rectification
The burner is found either out of operation, in lockout To avoid damage to the plant, do not reset the
(signal lamp shows red) or burner operation is interrupted burner more than twice.
(signal lamp flashes yellow / red or green / red).
If the burner locks out for a third time call for a
If faults occur, check first that the basic requirements for ATTENTION service engineer.
operation are met.
Fault conditions should be rectified only by
❑ Is there a supply of electricity? qualified and experienced personnel.
❑ Is the gas pressure supplied by the mains correct and
is the ball valve open?
❑ Are all controls for room and boiler, liquid level DANGER
interlocks, limit switches etc. set correctly?
Reset: with diagnostic code output (see Ch. 5.6):
If it has been established that the lockout is not due to any From the onset of lockout wait for the error
of the above, all the burner functions must be checked. analysis time of approx. 5 seconds, then press
reset-button until the signal lamp switches to
orange (approx. 5 secs.), determine flashing code,
then press reset-button for a further second to
reset.

without diagnostic code output:


Press reset-button until the red light goes out
(approx. 1 second).

Condition Cause Remedy


Combustion manager W-FM10
Signal lamp codes

Red Lockout
Diagnostic codes for probable causes:
(press reset-button approx. 5 seconds)
2 x flashes no flame at end of safety time
3 x flashes air pressure switch fault
4 x flashes flame simulation
6 x flashes servomotor fault
7 x flashes flame failure during operation
(partial load)
9 x flashes flame failure during operation
(full load)
10 x flashes no specific error code
12 x flashes valve proving valve 1 leaking
13 x flashes valve proving valve 2 leaking
By pressing reset-button (approx. 1 secs.)
the flashing code list in the internal
memory is deleted

Flashing red/green Flame signal at burner start Find cause and rectify

Flashing red/orange Over-voltage Check external voltage supply


then short pause

Flashing orange/red Low voltage or Check external voltage supply


internal fault replace combustion manager

Internal fuse has blown Replace fuse (Ch. 7.13)

Flashing red Low gas pressure Check burner setting or gas


pressure supply

Orange, after 30 secs. red Air pressure switch not switching Check air supply, air pressure switch

Flashing green Flame sensor current too low Check burner setting and
sensor electrode / cable

Voltage supply
Signal lamp remains off after Supply voltage lost Check voltage supply
heat demand from boiler control
Combustion manager defective Replace combustion manager

24
Condition Cause Remedy
Motor
Does not run Burner motor defective Replace burner motor (see Ch. 7.7)

Capacitor defective Replace capacitor

Air pressure switch Replace air pressure switch


contact continuously closed

Signal lamp orange


lockout after 20 secs. Combustion manager defective Replace combustion manager
motor runs continuously
Air pressure switch defective Replace air pressure switch

Insufficient air
Lockout after motor start Air pressure switch contact not made Correct setting of air pressure
switch, check air supply

Lockout during pre-purge Air pressure switch contact is Correct setting of air pressure
or during operation interrupted due to insufficient air pressure switch, check air supply

Pressure or negative Replace hose


pressure hose defective

Fan soiled Clean fan wheel and air duct


(see Ch. 7.6 and 7.7)

Air pressure switch defective Replace air pressure switch

Insufficient gas
Burner start is interrupted after solenoid No gas pressure available, Open fuel shut off device. If there
valve is opened.Signal lamp flashes or ball valve closed is insufficient gas for a prolonged
red re-start after 10 min. time period, contact gas supplier.
To interrupt the low gas program:
Press reset-button

Burner operation is interrupted, Gas pressure drop i.e Replace filter


signal lamp flashes red; due to soiled course filter
automatic restart after 10 min.

Ignition
No ignition audible Ignition electrode gap too large Adjust ignition electrode
Lockout (see Ch. 7.5)

Ignition electrode or ignition line Rectify short to earth by replacing


has earthed the defective parts

Ignition unit defective Replace ignition unit

No voltage on plug for the Combustion manager defective Replace combustion manager
ignition unit on combustion manager

Flame monitoring
After the boiler control has switched off, Flame formation due to Replace multifunction assembly
signal lamp flashes red/green; leaking solenoid valves
lockout after 20 secs.

Signal lamp flashes green Sensor current too low Check burner setting and
(see Ch. 5.3) sensor electrode / cable

Servomotor
Servomotor does not start Plug connection incorrect Check plug connection

Servomotor defective Replace servomotor (Ch. 7.8)

Servomotor starts then lockout Setting of the limit switch incorrect Correction of limit switch settings,
closed, ignition load and partial load
limit switches (STO/ZL/ST1) must
not be set above full load (ST2)

25
7 Servicing
7.1 Safety notes on servicing
Failure to carry out maintenance and service Endangering operational safety
work properly can have severe consequences, Maintenance work on the following individual components
including the loss of life. Pay close attention to may only be carried out by the manufacturer or their
the following safety notes. appointed agent:
DANGER • Servomotor
• Flame sensor
Qualified personnel • Combustion manager
Only qualified and experienced personnel must carry out • Gas pressure switch
maintenance and service work. • Air pressure switch

Before all maintenance and service work: Risk of explosion due to a gas leak
1. Electrically isolate the equipment Take care when dismantling and assembling parts in the
2. Close the ball valve gas line to ensure they are correctly aligned, clean and in
3. Remove the 7-pole connection plug from the boiler good condition, and that the fixing screws are correctly
controller tightened.

After all maintenance and service work:


1. Function test with ball valve closed. Danger of getting burnt!
2. Check flue gas losses and CO2 / O2 / CO values. Some burner parts (e.g. flame tube, burner
3. Complete a test sheet. flange, electrodes, etc.) become hot during
burner operation and should be allowed to
DANGER cool prior to service work being carried out.

7.2 Servicing plan


Service interval
The operator should ensure that combustion plant is
serviced at least
- once a year - by an agent of the supplier or other suitably
qualified person.

Test and clean


• Fan wheel and air inlet (see Ch. 7.6 and 7.7)
• Ignition equipment (see Ch. 7.5)
• Combustion head and diffuser (see Ch. 7.4)
• Filter insert (see Ch. 7.12)
• Air damper (see Ch. 7.6 ,7.10)
• Servomotor / compound (see Ch. 7.8)
• Flame sensor

Function test
• Operation of the burner with the sequence of
operations (see Ch. 5.4 and 5.5)
• Ignition equipment
• Air pressure switch
• Gas pressure switch
• Flame monitoring
• Soundness test of gas valve trains (see CH. 4.6)
• Purging valve trains (when replacing; see CH. 5.2)

26
7.3 Mixing head - removal and refitting
Removing Removal and refitting the mixing head
1. Remove the flame sensor or ionisation line ➂ .
2. Remove the ignition cable ➀ from the ignition unit.
3. Loosen screws ➃ .
4. With a slight twist, pull out the mixing head ➁ from the
housing.

Refitting
Danger of explosion!
Misalignment of the seal ➄ can result in a gas
leak during burner operation.
When refitting the mixing head ensure the seal
➀ ➄
DANGER is clean and aligned correctly. Replace it if ➁
necessary. When commissioning the burner
check the seal is sound with a leak detection
spray.

To refit, reassemble in the reverse order. ➃ ➃


➀ Ignition cable ➃ Kombi-Torx screw


➁ Mixing head ➄ Seal
➂ Flame sensor

7.4 Mixing head setting


The distance between the diffuser disc and the edge of the Setting the mixing head
flame tube (dimension S1) cannot be measured whilst it is
mounted. To check, remove the mixing head and measure
dimension L.

1. Remove the mixing head (see Ch. 7.3.) L


2. Turn the setting screw ➀ until it is level with the mixing
chamber housing (scale setting “0” or dimension X = 0).
3. Loosen screw ➁ . L
4. After setting dimension L, fix the collar ➂ with the lock

nuts ➁ . X ➁

Setting dimensions
Dimension X ________________________________ 0 mm
Dimension L _____________________________ 322 mm ➂
Dimension S1 ___________________________________________ 14 mm

Note: After loosening the lock nut check position of


electrodes and gas drillings (control dimension K) S1

Control dimension K _________________________ 65 mm
ca.
45°

➀ Setting screw ➃ Diffuser


➁ Lock nut ➄ Flame tube
➂ Collar

27
7.5 Ignition electrode and sensor electrode setting
☞ Remove the mixing head (see Ch. 7.3). For setting Setting dimension ignition electrode
dimensions see illustration.
11,5.5
If necessary, the setting of the sensor electrode can be .....2
adjusted to match site-specific conditions.

ca.
45°
1,5...2

➀ Sensor electrode with 6.3 mm diameter plug


➁ Ignition electrode with 4.0 mm diameter plug

7.6 Service position of fan housing cover

The servicing position of the fan housing cover permits: Procedure


• Cleaning of the air channel and fan wheel 1. Disconnect electrical connection ➀ .
• Access to the air damper 2. Remove mixing head (note Ch. 7.3).
• The fitting and removal of the fan motor 3. Hold the fan housing cover in place and loosen the
screws.
Note If the burner has been mounted rotated through 4. Hang the fan housing cover on the support ➁ .
180° it is not possible to put the fan housing cover
in the servicing position. Reassemble the fan housing cover in reverse order.

28
7.7 Removal and refitting fan wheel and fan motor
Removal Removal and refitting fan wheel and fan motor
1. Put the fan housing in the servicing position (see Ch. 7.6.)
2. Loosen the threaded pin ➀ .
3. Remove the fan wheel.
4. Remove plug No. 3 and No. 11.
5. Remove air pressure switch ➁ .
6. Holding the motor in place, loosen the screws ➂ .
7. Remove the motor from the housing.

3

11

Refitting
Reassemble in the reverse order.
☞ Turn the fan wheel by hand to check freedom of
movement.

7.8 Removal and refitting servomotor and angle drive of air damper
Removal Removal and refitting servomotor and angle drive
1. Remove the plug ➀ from combustion manager.
2. Loosen the screws ➁ .
3. Unhinge drive shaft ➃ on the gas butterfly valve.
4. Remove servomotor ➂ and drive shaft ➃ .
The air damper will open due to the spring relaxing.
5. Loosen screw and remove frame ➄.

6. Loosen screw and remove angle drive ➅.

Refitting
Damage to the servomotor!
Do not turn the hub of the servomotor, either
by hand or with a tool.
ATTENTION


1. Mount angle drive ➅. The air damper must be fully open
(90°) (see Ch. 7.11)
2. Refit frame ➄ and tighten screws. ➃
3. Refit drive shaft ➃ to servomotor. ➄
4. Set indicator ➆ of the angle drive to “Closed position”
of the servomotor and hold in this position.
5. Place drive shaft into the groove of the indicator and
tighten servomotor. ➂
6. Fix drive shaft to gas butterfly,

7. Fit plug ➀ to combustion manager.

Ensure correct alignment of drive shaft. The ➀


drive shaft must be connected tightly to the
gas butterfly valve.

ATTENTION

➀ Plug ➄ Frame
➁ Kombi Torx screw ➅ Angle drive
➂ Servomotor ➆ Indicator with groove
➃ Drive shaft

29
7.9 Removal and refitting gas butterfly valve
Risk of explosion! Removal and refitting gas butterfly valve
Uncontrolled gas leakage can lead to an ex-
plosive mixture of gas and air. If ignition source
is present this can lead to an explosion.
DANGER

Removing
1. Close gas ball valve.
2. Isolate burner from electrical supply.
3. Loosen outlet flange ➀ from the multifunction assembly
W-MF (see Ch. 4.5)
4. Remove double nipple
5. Remove mixing head (see Ch. 7.3)
6. Loosen drive rod ➁ . ➄
7. Loosen screws ➂ . ➃
8. Remove gas butterfly valve ➃ .

Refitting ➁
When refitting the mixing head ensure correct ➂
fitting and cleanliness of gasket ➄ .
If necessary replace gasket. During
commissioning check soundness with leak ➀
ATTENTION detecting spray.

1. Fit gas butterfly


2. Fit drive rod ➁ . ➀ Double nipple with ➂ Kombi Torx screw
3. Refit mixing head (note Ch. 7.3) flange ➃ Gas butterfly
4. Replace double nipple. ➁ Drive rod ➄ Gasket
5. Fit outlet flange to multifunction assembly W-MF (note
Ch. 4.5)
6. Carry out soundness test (note Ch. 4.6)
7. Switch on electrical supply.
8. Open gas ball valve.
9. Check combustion values, if necessary
re-commissioning burner.

7.10 Removal and refitting air regulator housing


Removal Air regulator housing
1. Close gas ball valve.
2. Isolate burner from electrical supply (see Ch. 4.7)
3. Loosen outlet flange from the multifunction assembly
W-MF (see Ch. 4.5)
4. Remove burner from heat exchanger (see Ch. 4.4)
5. Unplug servomotor of air damper
6. Loosen screws ➀ and remove air intake housing
7. Loosen screws ➁ and remove air regulator housing. ➀
Refit following instructions in reverse.

30
7.11 Removal and refitting coil on multifunction assembly (W-MF...)
Removal Solenoid replacement on W-MF...
1. Unscrew cover.
2. Remove coil.
Pay close attention to solenoid No. and voltage!

Refitting
Refit in reverse action.

7.12 Removal and refitting gas filter on W-MF...


Removal Removal and refitting filter insert
1. Close gas ball valve.
2. Loosen screws
3. Remove cover
4. Remove filter insert.
5. Check gasket in cover, replace if necessary.

Refitting
1. Fit new filter insert carefully.
2. Fit gasket, ensuring correct placement.
3. Replace cover.
4. Fit screws and tighten.
5. Carry out soundness test (see Ch. 4.6).
6. Vent valve train (see Ch. 5.2)

31
7.13 Replacing internal fuse W-FM10

T6,3H250V

32
8 Technical data
8.1 Burner equipment
Burner Combustion Motor Servomotor Ignition Gas pressure Air pressure Flame
type manager unit switch switch sensor

WG20…/1-C W-FM10 ECK04/F-2 STD 4.5 W-ZG 01 GW50 A5/1 LGW 10 A2 Ionisation
vers. Z-LN 230V, 50Hz BO. 36/6-4NL
28501/min 24V; 3.5W
0.21kW, 1.3A
Cond. 8µF

8.2 Capacity graphs


Burner type WG20…/1-C
Combustion head WG20-C
Heat rating 35...200 kW
Combustion chamber pressure [mbar]

2,5

1,5 Full load range


1

0,5

-0,5
-1
20 40 60 80 100 120 140 160 180 200 220

Burner rating [kW]

The capacity graph is in accordance with EN 676. There is


a ratings reduction dependent on the altitude of the
installation: approx. 1% per 100 m above sea level.

8.3 Permissible fuels


Natural gas E
Natural gas LL
Liquid petroleum gas B / P

8.4 Electrical data


WG20…/1-C
Mains voltage _______________________________ 230 V
Mains frequency __________________________ 50/60 Hz
Consumption-Start__________________________ 460 VA
-Operation _____________________ 290 VA
Current intake ________________________________1.3 A
External fusing ____________________________ 16A slow
Internal fusing ____________________________ 6.3A slow

8.5 Permitted ambient conditions


Temperature Humidity Requirements for EMC Low voltage guideline

In operation: max. 80% Guideline 89/336/EEC Guideline 73/23/EEC


-15°C…+40°C rel. humidity EN 50081-1 EN 60335
Transport / storage: EN 50082-1
-20…+70°C

33
8.6 Dimensions
Size in mm
I1 I2 I3 I4 b1 b2 b3 h1 h2 h3 h4 h5 d1 d2 d3 d4 Rp α°

397 140 32 158 358 178 182 376 96.5 20 284.5 182 120 M8 130 170 1” 45°

Rp

–weishaupt–

d1 h 5
h3
h2
h1
h4

l4 b1

l1 l2

d4
d3

b3

α° d2
b2
l3

34
8.7 Valve train

a b c d e f g c d e f g

➁ ➂

a Double nipple e Multifunction assembly W-MF


b Elbow f W-MF Flange
c Double nipple g Ball valve
d W-MF Flange

Gas valve train (approx. dimensions in mm)

Type ➀ ➁ ➂

W-MF507 (3/4”) 70 350/338* 295/283*


(1”) 70 365/345* 310/290*

W-MF512 (1”) 70 395/375* 340/320*

* without thermal shut off device

Connection Components
R a b c d e f g

3/4” (W-MF507) 1” x 80 1” 1” x 50 1” W-MF507 3/4” 3/4”


1” (W-MF507) 1” x 80 1” 1” x 50 1” W-MF507 1” 1”
1” (W-MF512) 1” x 80 1” 1” x 50 1” W-MF512 1” 1”

8.8 Weight
Burner Valve train

WG20/1-C, vers. Z-LN approx. 20 kg with W-MF 507 ca. 6 kg


with W-MF 512 ca. 7 kg

35
Appendix
Calculation of gas throughput
To provide the correct thermal input to the heat exchanger, Example:
the required gas throughput must be determined Height above sea level = 500 m
beforehand. Barometric air pressure PBaro. fromTab. = 953 mbar
Gas pressure PG at meter = 20 mbar
Conversion from standard to operating conditions Total pressure Ptot (Bo+PG) = 973 mbar
The calorific value (Hi) of combustible gases is generally Gas temperature tG = 10 °C
given in relation to the standard barometric conditions Conversion factor f from Tab. = 0.9266
(0° C, 1013 mbar). Appliance rating QN = 165 kW
Efficiency η (assumed) = 91 %
Calorific value Hi = 10.35 kWh/m3

Normal volume:
QN 165
VN = VN = → VN ≈ 17.5 m3/h
η • Hi 0.91 • 10.35

Operating volume:
VN QN 17.5
VB = or VB = VB = → VB ≈ 18.9 m3/h
f η • Hi,B 0.9266

Measuring time in seconds for 1m3 of gas throughput Measuring time when gas meter reads 1m3
3600 • 1 [ m3 ] 3600
Measuring time [ s ] = –––––––––––––– Measuring time = –––––– → Measuring time ≈ 190 s
VB [ m3/h ] 18.9

For two stage version calculate and check partial load in


the same way.

Determination of factor f
Total pressure PBaro. + PGas [mbar] ➞
950 956 962 967 973 979 985 991 997 1003 1009 1015 1021 1027 1033 1036
0 0.9378 0.9437 0.9497 0.9546 0.9605 0.9664 0.9724 0.9783 0.9842 0.9901 0.9961 1.0020 1.0079 1.0138 1.0197 1.0227
2 0.9310 0.9369 0.9427 0.9476 0.9535 0.9594 0.9653 0.9712 0.9770 0.9829 0.9888 0.9947 1.0006 1.0064 1.0123 1.0153
4 0.9243 0.9301 0.9359 0.9408 0.9466 0.9525 0.9583 0.9642 0.9700 0.9758 0.9817 0.9875 0.9933 0.9992 1.0050 1.0079
Gas temperature tG [°C]

6 0.9176 0.9234 0.9292 0.9341 0.9399 0.9457 0.9514 0.9572 0.9630 0.9688 0.9746 0.9804 0.9862 0.9920 0.9978 1.0007
8 0.9111 0.9169 0.9226 0.9274 0.9332 0.9389 0.9447 0.9504 0.9562 0.9619 0.9677 0.9734 0.9792 0.9850 0.9907 0.9936
10 0.9047 0.9104 0.9161 0.9209 0.9266 0.9323 0.9380 0.9437 0.9494 0.9551 0.9609 0.9666 0.9723 0.9780 0.9837 0.9866
12 0.8983 0.9040 0.9097 0.9144 0.9201 0.9257 0.9314 0.9371 0.9428 0.9484 0.9541 0.9598 0.9655 0.9711 0.9768 0.9796
14 0.8921 0.8977 0.9033 0.9080 0.9137 0.9193 0.9249 0.9306 0.9362 0.9418 0.9475 0.9531 0.9587 0.9644 0.9700 0.9728
16 0.8859 0.8915 0.8971 0.9017 0.9073 0.9129 0.9185 0.9241 0.9297 0.9353 0.9409 0.9465 0.9521 0.9577 0.9633 0.9661
18 0.8798 0.8854 0.8909 0.8955 0.9011 0.9067 0.9122 0.9178 0.9233 0.9289 0.9344 0.9400 0.9456 0.9511 0.9567 0.9594
20 0.8738 0.8793 0.8848 0.8894 0.8949 0.9005 0.9060 0.9115 0.9170 0.9225 0.9281 0.9336 0.9391 0.9446 0.9501 0.9529
22 0.8679 0.8734 0.8788 0.8834 0.8889 0.8944 0.8998 0.9053 0.9108 0.9163 0.9218 0.9273 0.9327 0.9382 0.9437 0.9464

24 0.8620 0.8675 0.8729 0.8775 0.8829 0.8883 0.8938 0.8992 0.9047 0.9101 0.9156 0.9210 0.9265 0.9319 0.9373 0.9401

1 mbar = 1 hPa = 10.20 mm WS 1 mm WS = 0.0981 mbar = 0.0981 hPa

The figures in the table are based on the following simple The moisture content of the gas is negligible and
formula: therefore is not considered in the table. The table allows
for conversion factors in the low pressure range
PBaro + PG 273 (up to > 100 mbar).
f = • The factor can also be determined in the high pressure
1013 273 + tG range according to the formula to the left.

Average yearly air pressure


Average goedetic height from 1 51 101 151 201 251 301 351 401 451 501 551 601 651 701
of installation to 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750
Average yearly air pressure mbar 1016 1013 1007 1001 995 989 983 977 971 965 959 953 947 942 936 930
above sea level mbar

Legend:
QN = Appliance rating [kW] f = Conversion factor
η = Efficiency [%] PBaro. = Barometric pressure [mbar]
Hi = Calorific value [ kWh/m3 ] PG = Gas pressure at meter [mbar]
Hi,B = Operating calorific value [ kWh/m3 ] tG = Gas temperature at meter [°C]
36
Combustion analysis
For safe and economic operation of the plant, flue gas Determination of flue gas losses
measurements are essential when commissioning. The oxygen content of the undiluted flue gas and the
difference between the flue gas temperature and the
Example of a simplified combustion air inlet temperature must be determined.
calculation for the required CO2 value The oxygen content and the flue gas temperature must be
measured at the same time at one point. Instead of oxygen
Given that: CO2 max. = 12% content, the carbon dioxide content of the flue gas can
also be measured. The combustion air temperature is
At CO limit of approx 100 ppm: CO2 measured = 11.5% measured in the proximity of the burner air intake.

CO2 max. 12 The flue gas losses are calculated when measuring the
Gives excess air λ = = = 1.04 oxygen content according to the equation:
CO2 meas. 11.5
A2
qA = (tA - tL) • ( +B)
To provide for a safe amount of excess air, increase excess 21 – O2
air by 15%: 1.04 + 0.15 = 1.19
If the carbon dioxide content is measured instead of the
CO2 value to be set with excess air λ = 1.19 and with CO2 oxygen content, the calculation is carried out according to
max potential of 12%.: the equation:

CO2 max. 12 A1
CO2 = = ≈ 10.1 % qA = (tA - tL) • ( +B)
λ 1.19 CO2

The final CO content must not exceed 50 ppm.


whereby:
Observe flue gas temperature qA = flue gas losses in %
Flue gas temperature for nominal load (high-fire) is the tA = flue gas temperature in °C
result of burner setting at nominal loading. tL = combustion air temperature in °C
CO2 = of carbon dioxide content in dry flue gas
The flue gas temperature at partial load (low-fire) is the O2 = of oxygen content in dry flue gas
result of the commissioned control range. The appliance
manufacturer’s instructions must be adhered to in respect
the partial load (low-fire) setting. This might be 50 - 60% Natural Liquid Petroleum
of nominal load setting, or even higher with an air-heater, Gas Gas and
whereas a condensing boiler may require the maximum LPG / Air mix
available turndown within the burner’s capacity range.
Often the partial load (low-firing-rate) is shown on the A1 = 0.37 0.42
appliance’s data plate. A2 = 0.66 0.63
B = 0.009 0.08
The flue gas installation should also be set out to protect
against damage due to condensation (excluding
acid-proof chimneys).

Calorific values and max. CO2 (guide values) of various types of gases

Gas type Calorific value Hi CO2 max.


MJ/m3 kWh/m3 %

1st gas family


Group A (town gas) 15.12…17.64 4.20…4.90 12…13
Group B (grid gas) 15.91…18.83 4.42…5.23 10

2nd gas family


Group LL (natural gas) 28.48…36.40 7.91…10.11 11.5…11.7
Group E (natural gas) 33.91…42.70 9.42…11.86 11.8…12.5

3rd gas family


Propanee P 93.21 25.99 13.8
Butane B 123.81 34.30 14.1

For the various maximum CO2 contents contact the gas supplier.

37
Notes

38
39
Weishaupt products Max Weishaupt GmbH, D-88475 Schwendi
Tel. (0 73 53) 8 30, Fax (0 73 53) 8 33 58
Print No 83054602, February 2002

and service Printed in Germany. We reserve the right to


make changes. All rights reserved.

Weishaupt (U.K.) Ltd.


Stoke Gardens, Slough SL1 3QD
Tel. (01753) 51 23 45
Fax (01753) 51 25 85

Neachells Lane, Willenhall


West Midlands, WV13 3RG
Tel. (01902) 60 98 41, Fax (01902) 63 33 43

Oil, gas and dual fuel burners types W and WG/WGL


up to 570 kW
They are used mainly in houses and small buildings.
Advantages: fully automatic, reliable operation, individual
components easily accessible, easy to service, quiet operation.

Oil, gas and dual fuel burners types Monarch


R, G, GL, RGL – up to 10.900 kW
These are used on all types and sizes of central heating
plant. The basic model which has proved successful over
many years is the basis for a variety of versions. These
burners have founded the outstanding reputation of
Weishaupt products.

Oil, gas and dual fuel burners types WK –


up to 17.500 kW
WK types are decidedly industrial burners.
Advantages: Built to the modular system, load dependent
variable combustion head, sliding two stage or modulating
operation, easy to service.

Weishaupt control panels, the proven complement to


Weishaupt burners
Weishaupt burners and Weishaupt control panels form
the ideal unit, a combination which has already proved
successful in hundreds of thousands of combustion
installations. The advantages: Cost saving during planning,
installation, servicing and guarantee work. The responsibility
belongs to one manufacturer.

Weishaupt Thermo Unit / Weishaupt Thermo Gas.


These Units combine the technical innovations and operating
efficiencies developed from over 1 million installations.
Weishaupt Thermo Gas and Weishaupt Thermo Unit
provide the ideals of complete heating centres for houses
and appartments.

Product and service are the complete


Weishaupt achievement
An extensive service organisation guarantees Weishaupt
customers the greatest possible reliability. In addition
our customers are looked after by heating firms who have
been working with Weishaupt for many years.

You might also like