Mechanical Layout

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 33

GENERAL NOTES FOR MECHANICAL WORKS: AIR DISTRIBUTION SYSTEM:

ISSUED FOR TENDER:


SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

HIGH WALL SPLIT TYPE A.C. UNITS:

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid


GENERAL NOTES FOR AC
LAYOUT

M-000

REV-00
2ND FLOOR
HIGH WALL SPLIT UNIT SCHEDULE (INDOOR / OUTDOOR) ISSUED FOR TENDER:
HIGH WALL SPLIT UNIT SCHEDULE (INDOOR / OUTDOOR) SIGNED:
DATE: 21 September 2021

ELECTRICAL ELECTRICAL EQUAL AND


QTY REMARKS EQUAL AND SERIAL TAG .NO: AREA SERVING TR QTY REMARKS
SERIAL TAG .NO: AREA SERVING TR INPUT INPUT APPROVED
APPROVED NO.
NO. PH VOLT HZ GENERAL NOTES:
PH VOLT HZ

1 MSU-GF/WS-01 GROUND FLOOR 1 MSU-SF/RM-01 SECOND FLOOR 2.0 1 220-240 50 1NO


2.5 1 220-240 50 1NO ROOM -01
CU-GF/WS-01 WORKSHOP -01 CU-SF/RM-01

CARRIER, MSU-SF/RM-02 SECOND FLOOR CARRIER,


2 MSU-GF/WS-02 GROUND FLOOR 1 220-240 50 2 2.0 1 220-240 50 1NO
2.5 1NO HIGHWALL YORK & CU-SF/RM-02 ROOM -02 HIGHWALL YORK &
CU-GF/WS-02 WORKSHOP -02
SUPER SUPER
GENERAL GENERAL
3 MSU-GF/WS-03 GROUND FLOOR 3 MSU-SF/RM-03 SECOND FLOOR 2.0 1 220-240 50 1NO
2.5 1 220-240 50 1NO ROOM -03
CU-GF/WS-03 WORKSHOP -03 CU-SF/RM-03

4 MSU-GF/WS-04 GROUND FLOOR 4 MSU-SF/RM-04 SECOND FLOOR 2.0 1 220-240 50 1NO


2.5 1 220-240 50 1NO ROOM -04
CU-GF/WS-04 WORKSHOP -04 CU-SF/RM-04

5 MSU-GF/WS-05 GROUND FLOOR 5 MSU-SF/RM-05 SECOND FLOOR 2.0 1 220-240 50 1NO


2.5 1 220-240 50 1NO CARRIER,
CU-GF/WS-05 WORKSHOP -05 CU-SF/RM-05 ROOM -05 CARRIER,
HIGHWALL YORK &
SUPER HIGHWALL YORK &
GENERAL MSU-SF/RM-06 SECOND FLOOR SUPER
6 MSU-GF/PR GROUND FLOOR 1 220-240 50 6 2.0 1 220-240 50 1NO
1.5 1NO CU-SF/RM-06 ROOM -06 GENERAL
CU-GF/PR PUMP RM

7 MSU-GF/ELE GROUND FLOOR 7 MSU-SF/RM-07 SECOND FLOOR 2.0 1 220-240 50 1NO


2.0 1 220-240 50 1NO ROOM -07
CU-GF/ELE ELECTRICAL RM CU-SF/RM-07

8 MSU-MZ/WS-01 MEZZANINE 8 MSU-SF/RM-08 SECOND FLOOR 2.0 1 220-240 50 1NO LEGEND


2.5 1 220-240 50 1NO ROOM -08
CU-GMZ/WS-01 WORKSHOP -01 CU-SF/RM-08

9 MSU-MZ/WS-02 MEZZANINE 9 MSU-SF/RM-09 SECOND FLOOR 2.0 1 220-240 50 1NO


2.5 1 220-240 50 1NO ROOM -09
CU-MZ/WS-02 WORKSHOP -02 CU-SF/RM-09

CARRIER, SECOND FLOOR CARRIER,


10 MSU-MZ/WS-03 MEZZANINE 10 MSU-SF/RM-10 2.0 1 220-240 50 1NO
2.5 1 220-240 50 1NO HIGHWALL YORK & ROOM -10 HIGHWALL YORK &
CU-MZ/WS-03 WORKSHOP -03 CU-SF/RM-10
SUPER SUPER
GENERAL GENERAL
11 MSU-MZWS-04 MEZZANINE 11 MSU-SF/RM-11 SECOND FLOOR 2.0 1 220-240 50 1NO
2.5 1 220-240 50 1NO ROOM -11
CU-MZ/WS-04 WORKSHOP -04 CU-SF/RM-11

12 MSU-MZ/WS-05 MEZZANINE 12 MSU-SF/RM-12 SECOND FLOOR 2.0 1 220-240 50 1NO


2.5 1 220-240 50 1NO ROOM -12
CU-MZ/WS-05 WORKSHOP -05 CU-SF/RM-12

3RD FLOOR
1ST FLOOR
HIGH WALL SPLIT UNIT SCHEDULE (INDOOR / OUTDOOR)
HIGH WALL SPLIT UNIT SCHEDULE (INDOOR / OUTDOOR) REVISIONS
ELECTRICAL EQUAL AND No. Ref.No. Description Issue Date
SERIAL TAG .NO: AREA SERVING TR INPUT QTY REMARKS
ELECTRICAL EQUAL AND APPROVED
SERIAL TAG .NO: AREA SERVING TR INPUT QTY REMARKS NO.
APPROVED PH VOLT HZ
NO.
PH VOLT HZ
1 MSU-TF/RM-01 THIRD FLOOR 2.0 1 220-240 50 1NO
1 MSU-FF/OF-01 FIRST FLOOR CU-TF/RM-01 ROOM -01
2.0 1 220-240 50 1NO
CU-FF/OF-01 OFFICE -01
CARRIER, 0 REV-00 - dd-mm-yy
2 MSU-TF/RM-02 THIRD FLOOR 2.0 1 220-240 50 1NO
CARRIER, CU-TF/RM-02 ROOM -02 HIGHWALL YORK &
2 MSU-FF/OF-02 FIRST FLOOR 2.0 1 220-240 50 1NO HIGHWALL YORK & SUPER
CU-FF/OF-02 OFFICE -02
SUPER GENERAL
GENERAL 3 MSU-TF/RM-03 THIRD FLOOR 2.0 1 220-240 50 1NO
3 MSU-FF/OF-03 FIRST FLOOR CU-TF/RM-03 ROOM -03
2.0 1 220-240 50 1NO
CU-FF/OF-03 OFFICE -03
4 MSU-TF/RM-04 THIRD FLOOR 2.0 1 220-240 50 1NO
4 MSU-FF/OF-04 FIRST FLOOR CU-TF/RM-04 ROOM -04
2.0 1 220-240 50 1NO
CU-FF/OF-04 OFFICE -04
5 MSU-TF/RM-05 THIRD FLOOR 2.0 1 220-240 50 1NO
5 MSU-FF/OF-05 FIRST FLOOR CU-TF/RM-05 ROOM -05 CARRIER,
2.0 1 220-240 50 1NO
CU-FF/OF-05 OFFICE -05 CARRIER, HIGHWALL YORK &
HIGHWALL YORK & MSU-TF/RM-06 THIRD FLOOR SUPER
6 2.0 1 220-240 50 1NO
SUPER CU-TF/RM-06 ROOM -06 GENERAL
6 MSU-FF/OF-06 FIRST FLOOR 2.0 1 220-240 50 1NO
CU-FF/OF-06 OFFICE -06 GENERAL

7 MSU-TF/RM-07 THIRD FLOOR 2.0 1 220-240 50 1NO


7 MSU-FF/OF-07 FIRST FLOOR CU-TF/RM-07 ROOM -07
2.0 1 220-240 50 1NO
CU-FF/OF-07 OFFICE -07
8 MSU-TF/RM-08 THIRD FLOOR 2.0 1 220-240 50 1NO
8 MSU-FF/OF-08 FIRST FLOOR CU-TF/RM-08 ROOM -08
2.0 1 220-240 50 1NO
CU-FF/OF-08 OFFICE -08
9 MSU-TF/RM-09 THIRD FLOOR 2.0 1 220-240 50 1NO Mr. JAMAL AL KOOHEJI AND
MSU-FF/OF-09 FIRST FLOOR CU-TF/RM-09 ROOM -09
9
CU-FF/OF-09 OFFICE -09
2.0 1 220-240 50 1NO Mr. HISHAM AL RAYYES
10 MSU-TF/RM-10 THIRD FLOOR CARRIER,
2.0 1 220-240 50 1NO
CARRIER, CU-TF/RM-10 ROOM -10 HIGHWALL YORK &
10 MSU-FF/OF-10 FIRST FLOOR 2.0 1 220-240 50 1NO HIGHWALL YORK & SUPER
CU-FF/OF-10 OFFICE -10
SUPER GENERAL
11 MSU-TF/RM-11 THIRD FLOOR 2.0 1 220-240 50 1NO
GENERAL
11 MSU-FF/OF-11 FIRST FLOOR CU-TF/RM-11 ROOM -11 PROPOSED 4-STOREY COMMERCIAL
2.0 1 220-240 50 1NO
CU-FF/OF-11 OFFICE -11
MSU-TF/RM-12 THIRD FLOOR
BUILDING
12 2.0 1 220-240 50 1NO
FIRST FLOOR CU-TF/RM-12 ROOM -12 @ Halet Um Al Bhaid
12 MSU-FF/OF-12 2.0 1 220-240 50 1NO
CU-FF/OF-12 OFFICE -12

SCHEDULE FOR AC LAYOUT

M-001

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

MSU-GF/WS-05 MSU-GF/WS-04 MSU-MF/WS-04


MSU-MF/WS-05
CU-2.5TR CU-2.5TR CU-2.5TR MSU-MF/WS-03
CU-2.5TR
CU-2.5TR
LEGEND

MSU-GF/PU
CU-1.5TR

MSU-GF/WS-05
CU-2.5TR

MSU-GF/PU
MSU-GF/WS-04 CU-1.5TR
CU-2.5TR
WC WC WC WC

WC
WC
MSU-GF/WS-03
CU-2.5TR

WC
WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
MSU-GF/WS-02
CU-2.5TR

WC
WC WC WC WC

MSU-GF/ELE
CU-2.0TR

MSU-GF/WS-01
CU-2.5TR
MSU-GF/ELE
CU-2.0TR

Mr. JAMAL AL KOOHEJI AND


MSU-GF/WS-01 MSU-GF/WS-02 MSU-GF/WS-03 Mr. HISHAM AL RAYYES
CU-2.5TR CU-2.5TR CU-2.5TR

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid
MSU-MF/WS-02
MSU-MF/WS-01
CU-2.5TR
CU-2.5TR

GROUND FLOOR AC LAYOUT

M-101

REV-00
Xref D:\MEP\2021\2116\Working drawing\2116-Xref\2116_Xref column.dwg
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

MSU-MF/WS-05
CU-2.5TR

MSU-MF/WS-04
CU-2.5TR

MSU-MF/WS-03
CU-2.5TR

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

MSU-MF/WS-02
CU-2.5TR

MSU-MF/WS-01
CU-2.5TR

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

MEZZANINE FLOOR AC LAYOUT

M-102

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

MSU-1ST/OF-06
CU-2.0TR

WC WC WC WC

WC
WC
MSU-1ST/OF-01 MSU-1ST/OF-02 MSU-1ST/OF-03 MSU-1ST/OF-04 MSU-1ST/OF-05

WC
CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

MSU-1ST/OF-07 MSU-1ST/OF-08 MSU-1ST/OF-09 MSU-1ST/OF-10 MSU-1ST/OF-11


CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

MSU-1ST/OF-12
CU-2.0TR

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

FIRST FLOOR AC LAYOUT

M-103

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

MSU-2ND/RM-06
CU-2.0TR

WC WC WC WC

WC
WC
MSU-2ND/RM-01 MSU-2ND/RM-02 MSU-2ND/RM-03 MSU-2ND/RM-04 MSU-2ND/RM-05

WC
CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

MSU-2ND/RM-07 MSU-2ND/RM-08 MSU-2ND/RM-09 MSU-2ND/RM-10 MSU-2ND/RM-11


CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

MSU-2ND/RM-12
CU-2.0TR

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

SECOND FLOOR AC LAYOUT

M-104

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

MSU-3RD/RM-06
CU-2.0TR

WC WC WC WC

WC
WC
MSU-3RD/RM-01 MSU-3RD/RM-02 MSU-3RD/RM-03 MSU-3RD/RM-04 MSU-3RD/RM-05

WC
CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

MSU-3RD/RM-07 MSU-3RD/RM-08 MSU-3RD/RM-09 MSU-3RD/RM-10 MSU-3RD/RM-11


CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

MSU-3RD/RM-12
CU-2.0TR

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

THIRD FLOOR AC LAYOUT

M-105

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

MSU-1ST/OF-02 MSU-1ST/OF-03 MSU-1ST/OF-04 MSU-1ST/OF-06


CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR
MSU-2ND/RM-02 MSU-2ND/RM-03 MSU-2ND/RM-04 MSU-2ND/RM-06
CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR
MSU-3RD/RM-02 MSU-3RD/RM-03 MSU-3RD/RM-04 MSU-3RD/RM-06
CU-2.0TR CU-2.0TR CU-2.0TR CU-2.0TR

MSU-1ST/OF-01 MSU-1ST/OF-05
CU-2.0TR CU-2.0TR

MSU-2ND/RM-01 MSU-2ND/RM-05
CU-2.0TR CU-2.0TR

MSU-3RD/RM-01 MSU-3RD/RM-05
CU-2.0TR CU-2.0TR
REVISIONS
No. Ref.No. Description Issue Date

MSU-1ST/OF-07 MSU-1ST/OF-10 MSU-1ST/OF-11


CU-2.0TR CU-2.0TR CU-2.0TR
0 REV-00 - dd-mm-yy

MSU-2ND/RM-07 MSU-2ND/RM-10 MSU-2ND/RM-11


CU-2.0TR CU-2.0TR CU-2.0TR

MSU-3RD/RM-07 MSU-3RD/RM-10 MSU-3RD/RM-11


CU-2.0TR CU-2.0TR CU-2.0TR

MSU-1ST/OF-08 MSU-1ST/OF-09 MSU-1ST/OF-12


CU-2.0TR CU-2.0TR CU-2.0TR
Mr. JAMAL AL KOOHEJI AND
MSU-2ND/RM-08 MSU-2ND/RM-09 MSU-2ND/RM-12
CU-2.0TR CU-2.0TR CU-2.0TR Mr. HISHAM AL RAYYES
MSU-3RD/RM-08 MSU-3RD/RM-09 MSU-3RD/RM-12
CU-2.0TR CU-2.0TR CU-2.0TR

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

ROOF DECK AC LAYOUT

M-106

REV-00
GENERAL NOTES FOR DRAINAGE WORKS: SPECIAL NOTES FOR DRAINAGE SYSTEM
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

CONDENSATE DRAIN PIPING:


1. THE PIPE WORK SHALL BE SUPPORTED WITH SUITABLE CHANNEL/ ANGLE IRON BRACKETS & GI THREADED RODS FROM MAIN STRUCTURAL
MEMBERS.

2. CONDENSATE DRAIN PIPE SHALL BE OF SCHEDULE 40 ASTM D 1785 UPVC MATERIALS. Mr. JAMAL AL KOOHEJI AND
3. THE COMPLETE SUPPORTING ARRANGEMENT SHALL BE PAINTED WITH SUITABLE ANTI CORROSIVE PAINT OF APPROVED COLOR.
Mr. HISHAM AL RAYYES

4. PROPER 'U' SEAL SHALL BE PROVIDED FOR EACH FAN COIL UNITS, CONDENSATE DRAIN PIPES.

5. ALL CONDENSATE DRAIN PIPE SHALL BE OF INSULATED WITH 12 MM THICK CLOSED CELL INSULATION THROUGH OUT THE LENGTH WITHIN
INSIDE BUILDING. PROPOSED 4-STOREY COMMERCIAL
BUILDING
6. ALL CONDENSATE DRAIN PIPES SHALL BE INSULATED WITH 25 MM THICK FIBRE GLASS RIGID PIPE SECTIONS FINISHED WITH CANVAS
@ Halet Um Al Bhaid
SELFAS THROUGH OUT

7. ALL FLOOR DRAIN (FD) CONNECTED TO CONDENSATE DRAIN SHOULD BE INSULATED.


GENERAL NOTES FOR DRAINAGE
LAYOUT

D-000

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

150

ROOF DRAIN

FINISHED FLOOR
FLOOR DRAIN
EXTENSION PIPE

ROOF VENT TERMINAL TYPICAL DETAIL OF SOAK PIT


LEGEND
100Ø RWP PIPE

AREA DRAIN DETAILS

RAIN WATER DISCHARGE DETAIL


REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

FLOOR DRAIN (FOR UPPER FLOOR)

RAIN WATER PIPE DETAIL


3200

600

600

150 1700 150


150

A A
1000
150

PLAN PIPE SCHEDULE

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES
30 min
VARIES

INLET OUTLET
PROPOSED 4-STOREY COMMERCIAL
BUILDING
800

@ Halet Um Al Bhaid
150

NOTE:
DETAILS FOR DRAINAGE LAYOUT
THIS GREASE TRAP IS DESIGNED TO ACCEPT
A FLOW OF 3 LITRES PER SECOND AND IS
SUITABLE FOR AN ESTABLISHMENT PREPARING
500 MEALS PER DAY. LARGER ESTABLISHMENTS SECTION A-A
INCREASE THE LENGTH BY 200mm FOR EVERY SECTION OF MANHOLE
100 ADDITIONAL MEALS SERVED UP TO A MAXIMUM
OF 1000 MEALS PER DAY.

TYPICAL SANITARY MANHOLE DETAIL D-001


TYPICAL GREASE TRAP DETAIL

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

75Ø RWP PIPE F/A


FREE DISCHARGE LEGEND
CO CO

75Ø RWP PIPE F/A


FREE DISCHARGE

110Ø WASTE PIPE F/A,T/B


75Ø RWP PIPE F/A 50Ø VENT PIPE T/A
FREE DISCHARGE 110Ø SOIL PIPE F/A,T/B
50Ø VENT PIPE T/A
COCO

110Ø WASTE PIPE @


110Ø WASTE PIPE @ UNDER GROUND WC WC WC WC

WC
UNDER GROUND
110Ø WASTE PIPE
110Ø SOIL PIPE @

WC
CO UNDER GROUND
CO

110Ø WASTE PIPE

WC
110Ø SOIL PIPE @
UNDER GROUND

WC
REVISIONS
CO
No. Ref.No. Description Issue Date
110Ø WASTE PIPE @

WC
UNDER GROUND
NOTE:

WC
1- DEPTH OF SEPTIC TANK SHALL BE
FROM INVERT LEVEL.
2- HIGH LEVEL ALARM SHALL BE 0 REV-00 - dd-mm-yy
110Ø WASTE PIPE

WC
PROVIDED FROM SEPTIC TANK WITH CO
CO 110Ø SOIL PIPE @
CONTROL PANEL.
UNDER GROUND
SEWERAGE HOLDING TANK

WC
WC WC WC WC

SIZE:12000LX4600W
EFFECTIVE DEPTH =1500H 110Ø WASTE PIPE @
CAPACITY-105M³ (7Days capacity) UNDER GROUND
110Ø WASTE PIPE BIG
110Ø SOIL PIPE @ MH-01
UNDER GROUND IL=-0.600
50Ø VENT PIPE T/A
110Ø SOIL PIPE F/A,T/B

150Ø SP PIPE 1:100 SLOPE


50Ø VENT PIPE T/A
75Ø RWP PIPE F/A HEPWORTH GREASE 110Ø WASTE PIPE F/A,T/B
FREE DISCHARGE TRAP CLASS B 75Ø RWP PIPE F/A
U/G TYPE HEPWORTH GREASE FREE DISCHARGE
TRAP CLASS B
U/G TYPE

75Ø RWP PIPE F/A


FREE DISCHARGE
FUTURE SEWER LINE Mr. JAMAL AL KOOHEJI AND
CONNECTION BIG BIG BIG
Mr. HISHAM AL RAYYES
MH-02
IL=-0.630
150Ø SP PIPE 1:100 SLOPE 150Ø SP PIPE 1:100 SLOPE 150Ø SP PIPE 1:100 SLOPE 150Ø SP PIPE 1:100 SLOPE
MH-04 MH-04 150Ø SP PIPE 1:100 SLOPE MH-03
IL=-0.776 IL=-0.776 IL=-0.740
PROPOSED 4-STOREY COMMERCIAL
TANK COLLECTOR
BUILDING
LINE @ Halet Um Al Bhaid
Ø150 TANKER CONNECTION
WITH QUICK COUPLING
GROUND FLOOR DRAINAGE
LAYOUT

D-101

REV-00
Xref D:\MEP\2021\2116\Working drawing\2116-Xref\2116_Xref column.dwg
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND
75Ø RWP PIPE T/B

75Ø RWP PIPE T/B

75Ø RWP PIPE F/A


75Ø RWP PIPE F/A 75Ø RWP PIPE T/B

50Ø VENT PIPE T/A

50Ø VENT PIPE T/A


110Ø WASTE PIPE F/A,T/B
50Ø VENT PIPE T/A
110Ø SOIL PIPE F/A,T/B

REVISIONS
No. Ref.No. Description Issue Date
50Ø VENT PIPE T/A

0 REV-00 - dd-mm-yy
110Ø SOIL PIPE F/A,T/B
50Ø VENT PIPE T/A
110Ø WASTE PIPE F/A,T/B

50Ø VENT PIPE T/A

75Ø RWP PIPE F/A 50Ø VENT PIPE T/A

75Ø RWP PIPE T/B


75Ø RWP PIPE F/A 75Ø RWP PIPE T/B

75Ø RWP PIPE T/B


Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

MEZZANINE FLOOR DRAINAGE


LAYOUT

D-102

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

SLOPE SLOPE
SLOPE SLOPE
75Ø RWP PIPE T/B SLOPE 75Ø RWP PIPE T/B
SLOPE
SLOPE
50Ø VENT PIPE T/A
75Ø RWP PIPE T/B 110Ø SOIL PIPE F/A,T/B
50Ø VENT PIPE T/A
110Ø WASTE PIPE 110Ø WASTE PIPE F/A,T/B
110Ø SOIL PIPE @
UNDER GROUND
WC WC WC WC 50Ø VENT PIPE T/A

WC
CCO

WC
CCO

110Ø WASTE PIPE

WC
110Ø SOIL PIPE @
50Ø VENT PIPE T/A UNDER GROUND

WC
CCOCCO REVISIONS
No. Ref.No. Description Issue Date

WC
110Ø WASTE PIPE
110Ø SOIL PIPE @

WC
UNDER GROUND
CCO 0 REV-00 - dd-mm-yy

WC
CCO

110Ø WASTE PIPE 50Ø VENT PIPE T/A

WC
110Ø SOIL PIPE @
WC WC WC WC

UNDER GROUND

75Ø RWP PIPE T/B 75Ø RWP PIPE T/B 110Ø SOIL PIPE F/A,T/B
50Ø VENT PIPE T/A
110Ø WASTE PIPE F/A,T/B
50Ø VENT PIPE T/A

SLOPE 75Ø RWP PIPE T/B


SLOPE
SLOPE
SLOPE SLOPE

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

FIRST FLOOR DRAINAGE LAYOUT

D-103

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

LEGEND

SLOPE SLOPE
SLOPE SLOPE
75Ø RWP PIPE T/B SLOPE 75Ø RWP PIPE T/B
SLOPE
SLOPE

75Ø RWP PIPE T/B 110Ø SOIL PIPE F/A,T/B


50Ø VENT PIPE T/A
110Ø WASTE PIPE F/A,T/B

110Ø WASTE PIPE


110Ø SOIL PIPE @
50Ø VENT PIPE T/A
UNDER GROUND WC WC WC WC

WC
CCO

WC
CCO

110Ø WASTE PIPE

WC
110Ø SOIL PIPE @
50Ø VENT PIPE T/A UNDER GROUND

WC
CCOCCO REVISIONS
No. Ref.No. Description Issue Date

WC
110Ø WASTE PIPE
110Ø SOIL PIPE @ 110Ø WASTE PIPE
UNDER GROUND 110Ø SOIL PIPE @

WC
UNDER GROUND
CCO 0 REV-00 - dd-mm-yy

WC
CCO

50Ø VENT PIPE T/A

WC
WC WC WC WC

75Ø RWP PIPE T/B 75Ø RWP PIPE T/B 110Ø SOIL PIPE F/A,T/B
50Ø VENT PIPE T/A
110Ø WASTE PIPE F/A,T/B

SLOPE 75Ø RWP PIPE T/B


SLOPE
SLOPE
SLOPE SLOPE

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

SECOND FLOOR DRAINAGE


LAYOUT

D-104

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

75Ø RWP PIPE F/A LEGEND

SLOPE SLOPE
SLOPE SLOPE
75Ø RWP PIPE T/B SLOPE 75Ø RWP PIPE T/B
SLOPE
SLOPE
110Ø SOIL PIPE T/B
75Ø RWP PIPE T/B 50Ø VENT PIPE T/A
110Ø WASTE PIPE T/B

110Ø WASTE PIPE WC WC WC WC 50Ø VENT PIPE T/A

WC
110Ø SOIL PIPE @
UNDER GROUND
CCO

WC
CCO

110Ø WASTE PIPE

WC
110Ø SOIL PIPE @
50Ø VENT PIPE T/A UNDER GROUND

WC
CCOCCO REVISIONS
No. Ref.No. Description Issue Date

WC
110Ø WASTE PIPE
110Ø SOIL PIPE @ 110Ø WASTE PIPE
UNDER GROUND 110Ø SOIL PIPE @

WC
UNDER GROUND
CCO 0 REV-00 - dd-mm-yy

WC
CCO

50Ø VENT PIPE T/A

WC
WC WC WC WC

110Ø WASTE PIPE T/B


75Ø RWP PIPE T/B 75Ø RWP PIPE T/B 50Ø VENT PIPE T/A
110Ø SOIL PIPE T/B

SLOPE 75Ø RWP PIPE T/B


SLOPE
SLOPE
SLOPE SLOPE

75Ø RWP PIPE F/A


Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

THIRD FLOOR DRAINAGE


LAYOUT

D-105

REV-00
SLO
PE
SLO
ISSUED FOR TENDER:

PE
SIGNED:
DATE: 21 September 2021

75Ø RWP PIPE T/B

75Ø RWP PIPE T/B

SLOPE SLOPE SLOPE


SLOPE SLOPE SLOPE SLOPE SLOPE
75Ø RWP PIPE T/B 75Ø RWP PIPE T/B
SLOPE SLOPE

SLOPE
SLOPE SLOPE SLOPE SLOPE
SLOPE

SLOPE
50Ø VENT PIPE F/B
DISCHARGE ABOVE FFL
WITH VENT COWL
SLOPE
SLOPE SLOPE
50Ø VENT PIPE F/B
SLOPE

SLOPE
SLOPE
DISCHARGE ABOVE FFL
WITH VENT COWL
75Ø RWP PIPE F/A
SLOPE

SLOPE
SLOPE FREE DISCHARGE SLOPE

SLOPE SLOPE
SLOPESLOPE

SLOPESLOPE
REVISIONS
No. Ref.No. Description Issue Date

SLOPE
50Ø VENT PIPE F/B
SLOPE

SLOPE
DISCHARGE ABOVE FFL
WITH VENT COWL

SLOPE SLOPE
SLOPE

SLOPE

SLOPE
50Ø VENT PIPE F/B
SLOPE DISCHARGE ABOVE FFL
WITH VENT COWL
0 REV-00 - dd-mm-yy

50Ø VENT PIPE F/B


SLOPE SLOPE DISCHARGE ABOVE FFL
SLOPE

SLOPE
SLOPE WITH VENT COWL
SLOPE
SLOPE

SLOPE

SLOPE SLOPE SLOPE SLOPE

75Ø RWP PIPE T/B SLOPE SLOPE 75Ø RWP PIPE T/B

SLOPE SLOPE SLOPE SLOPE


SLOPE SLOPE SLOPE SLOPE

75Ø RWP PIPE T/B

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

ROOF DECK DRAINAGE


LAYOUT

D-106

REV-00
GENERAL NOTES FOR WATER SUPPLY WORKS: SPECIAL NOTES FOR WATER SUPPLY SYSTEM:

ISSUED FOR TENDER:


SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

SCHEDULE FOR WATER TANKS:


SL SIZE OF TANKS CAPACITY LOCATION QTY
TYPE
NO. IN LTRS

1 138000L 1 NO UNDER GROUND WATER TANK


9800Lx6400Wx2200H GROUND FLOOR

Mr. JAMAL AL KOOHEJI AND


2 2400HX1550ØW 4000L ROOF DECK 4 NOS HORIZONTAL WATER TANK Mr. HISHAM AL RAYYES

SCHEDULES FOR PUMPS: PROPOSED 4-STOREY COMMERCIAL


ELETRICAL INPUT BUILDING
SERIAL SERVICE LOCATION CAPACITY BAR TYPE @ Halet Um Al Bhaid
NO. LPS
PH VOLT HZ
NOTE:
GRUNDFOS PUMP OR EQUIVALENT AND APPROVED WITH FLOW SWITCH DUTY WITH AUTO FINAL SELECTION OF THE PUMP MUST BE DONE
1 TRANSFER PUMP GROUND FLOOR 2.0 2.0 3 380-415 50 CHANGE OVER PANEL AND DRY RUN PROTECTION COPPER MANIFOLD ALL WETTED PARTS BASED ON MANUFACTURE HEAD CALCULATION
GENERAL NOTES FOR PLUMBING
SHALL BE OF SS TO AISI 316 (WITH ENCLOSURE)
(NPSH TO BE CALCULATED AS PER REQUIREMENT)
DESIGN.
(SUBJECT TO ENGINEER'S APPROVAL)
LAYOUT
GRUNDFOS OR EQUAL AND APROVED,WITH PRESSURE VESSEL, 1 VERTICAL,
MULTISTAGE, CENTRIFUGAL WITH GATE VALVE & NRV AT PUMP INLET/OUTLET, PG,
PIPING, RUBBER FLEXIBLE CONNECTIONS, NEED TO VFD,SUCTION & DISCHARGE SS
2 BOOSTER PUMP ROOF DECK 4.5 3.0 3 380-415 50
MANIFOLD, FLOAT SWITCH FOR DRY RUN PROTECTION AND ALL MOUNTED ON A
COMMON FRAME (WITH ENCLOSURE)

P-000

REV-00
FLIP VALVE WOODEN BOX
WATER METER FIXING POINT

MODIFIED SUPPORT
STAINLES STEEL HINGES & PIN ISSUED FOR TENDER:
SIGNED:
(SEE DETAIL-A
'C' CHANNEL
BLOCK & SADDLE DATE: 21 September 2021

(TYP.) SUPPORT CLAMPS AS ASSEMBLED 90% TRANSPARENT


CLEAR OR ACRYLIC
SIZE OF GENERAL NOTES:
160Ø CWS PPR FIXED WITH RUBBER
GRAVITY SUPPLY OPENNING-300MMX170MM B GASKET TO ALUMINIUM

50
0
10mm THK.
90° ELBOW NOTE: SIZE OF OPENING
PRV WITH
BFV (O)
BUILT-IN PG
BFV (O)
RUBBER PAD (TYP.)
WOODEN BOX (300MM X 170MM)
RD INC
WDD"S LIMIT OF WORK POWDER COATED ALUMINIUM
1 45 SERIES OR EQUIVALENT

400
2"X20MM LD/MD COUPLER C
M
LOCKING ARRANGEMENT
PRV WITH 50Ø DUCT HOLE

120
BFV (C) BUILT-IN PG BFV (C)
(MODEL 7150,HINAKA
160Ø CWS PPR
WITH RUBBER BUSH
RD INC
MFG.CO.LTD,JAPAN

400
BFV (C) 120 260 120
(KEY NO: 42421)
500

775
160Ø CWS PPR 'C' CHANNEL
SLEEVE IN SLAB SUPPORT (TYP.)
WITH FIRE SEAL

WALL
DETAIL - ALUMINIUM FRAME & DOOR
(CAVITY WALL TYPE)
DETAIL A-A water water
out in
SECTIONAL DETAIL OF RISER PRV STATION
NOT TO SCALE

FRONT VIEW

MANIFOLDS SYSTEM
M

REVISIONS
No. Ref.No. Description Issue Date

WALL

TAPE

0 REV-00 - dd-mm-yy

32Ø CWS PIPE@ INSULATION CLOTH


RUNS THROUGH PPR PIPE
FLOOR

2
ROOF PIPE
WATER TANK INSTALLATION DETAILS
DETAILS

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

DETAILS FOR PLUMBING LAYOUT

3 WATERSUPPLY PIPE 4 ROOF PIPE SUPPORT 5 WATER HEATER INSTALLATION


DETAILS P-001
RISER DETAILS DETAILS
REV-00
CENTRALISED ELETRIC WATER HEATER
300 LITER CAPACTIY
(4NOS)
2ND FLOOR
CENTRALISED ELETRIC WATER HEATER CENTRALISED ELETRIC WATER HEATER WATER TANK AND PUMP ROOM
300 LITER CAPACTIY 300 LITER CAPACTIY VMS BOOSTER PUMP SET (WITH SHADE)
(4NOS) (4NOS) ONE DUTY/ ONE STANDBY HORIZONTAL WATER TANK ISSUED FOR TENDER:
1ST FLOOR WITH VFD CONTROL PANEL 4.5L/S SIZE:2400H X 1550ØW 50Ø CWS PIPE@ SIGNED:
3RD FLOOR DATE: 21 September 2021
@ 3.0 BAR WITH COMPLETE 4000L CAPACITY (4nos) TRANSFER LINE
ACCESSORIES WITH PRESSURE RUNS TTHROUGH
VESSEL-100LITRE. FLOOR
GENERAL NOTES:

CENTRALISED ELETRIC WATER HEATER


300 LITER CAPACTIY HWSNRV IV

(4NOS) HWSNRV IV

HWSNRV IV
GROUND FLOOR 32Ø CWS PIPE@
HWSNRV IV
BOOSTER LINE T/B PRV

ROOF DECK FINISH LVL


32Ø HWS PIPE@
BOOSTER LINE
F/A to T/B
32Ø CWS PIPE@
BOOSTER LINE T/B

32Ø HWS PIPE


32Ø DWS PIPE @
60Ø CWS PIPE@
ABOVE CEILING
40Ø CWS PIPE@ BOOSTER LINE
BOOSTER LINE T/B F/A to T/B
3RD FLOOR FINISH LVL
32Ø HWS PIPE@
BOOSTER LINE
F/A to T/B 32Ø CWS PIPE@
50Ø CWS PIPE@
BOOSTER LINE T/B
TRANSFER LINE T/A
ROOF TANKS

32Ø HWS PIPE


32Ø DWS PIPE @ 60Ø CWS PIPE@
ABOVE CEILING 40Ø CWS PIPE@ BOOSTER LINE
2ND FLOOR FINISH LVL BOOSTER LINE T/B F/A to T/B

32Ø HWS PIPE@


BOOSTER LINE 32Ø CWS PIPE@
F/A to T/B BOOSTER LINE T/B

32Ø HWS PIPE 40Ø CWS PIPE@ 60Ø CWS PIPE@


32Ø DWS PIPE @ BOOSTER LINE T/B BOOSTER LINE
ABOVE CEILING F/A to T/B
1ST FLOOR FINISH LVL M

REVISIONS

32Ø CWS PIPE@ 50Ø CWS PIPE@ No. Ref.No. Description Issue Date

32Ø HWS PIPE@ BOOSTER LINE T/B TRANSFER LINE T/A


BOOSTER LINE ROOF TANKS
F/A to T/B

40Ø CWS PIPE@ 60Ø CWS PIPE@ 0 REV-00 - dd-mm-yy


BOOSTER LINE T/B BOOSTER LINE
MEZZANINE FLOOR FINISH LVL F/A to T/B

PRV
M M M M
WATER METER FIXING ON
32Ø HWS PIPE WALL 1500MM FROM FFL
32Ø DWS PIPE @
ABOVE CEILING

32Ø CWS PIPE@


BOOSTER LINE F/A
TO GT LINE 50Ø CWS PIPE@
SUPPLY FROM WDD TRANSFER LINE T/A
40Ø CWS PIPE FOR ROOF TANKS
INCOMING WATER LINE
M NRV

GROUND FLOOR FINISH LVL


Mr. JAMAL AL KOOHEJI AND
40Ø CWS PIPE@ Mr. HISHAM AL RAYYES
A 50Ø CWS PIPE@ 50Ø CWS PIPE@
UNDER GROUND
TRANSFER LINE T/A TRANSFER LINE T/A
OVERFLOW ALARM ROOF TANKS ROOF TANKS
INTERFACED TO BUZZER
& ALARM PANEL TRANSFER PUMP SET
ONE DUTY/ ONE STANDBY PROPOSED 4-STOREY COMMERCIAL
UNDER GROUND WITH VFD CONTROL PANEL 2.0 L/S BUILDING
CONCRETE WATER TANK @ 2.0 BAR WITH COMPLETE NOTE: @ Halet Um Al Bhaid
SIZE: 9800L X 6400W X 2200H(EFFECTIVE DEPTH) ACCESSORIES FOLLOW AS PER NEW WDD REGULATION
TOTAL CAPACITY:- 138.0M³
FIRE FIGHTING CAPACITY:- 90M³
SCHEMATIC FOR PLUMBING
DOMESTIC WATER CAPACITY:-45M³ LAYOUT

SCHEMATIC DIAGRAM
P-002

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

UNDER GROUND
CONCRETE WATER TANK
SIZE: 9800L X 6400W X 2200H(EFFECTIVE DEPTH)
TOTAL CAPACITY:- 138.0M³
FIRE FIGHTING CAPACITY:- 90M³
DOMESTIC WATER CAPACITY:-45M³
M

LPG

LPG
Ø100MM PVC PROVISION

LPG

LPG
LPG
LPG

LPG
LPG
FOR GAS PIPING (TYP)
40Ø CWS PIPE @ LPG

LPG

LPG
LPG
INCOMING WATER LINE

LPG
LPG

LPG
LPG
UNDER GROUND 25Ø CWS PIPE@ SUPPLY FROM WDD

LPG
SUPPLY FROM WDD RUNS THROUGH 40Ø CWS FOR INCOMING

LPG

LPG
50Ø TRANSFER LINE T/A

LPG
LPG LPG

LPG
LPG
40Ø CWS FOR INCOMING U/G LPG LPG WATER LINE

LPG
WATER LINE LPG LPG

LPG
GT

LPG

LPG
LPG

LPG
LPG

LPG
TRANSFER PUMP SET

LPG
LPG
C C ONE DUTY/ ONE STANDBY

RADIATOR RETURN LINE


LPG
LPG

LPG
2.0L/S @ 2.0 BAR WITH COMPLETE

LPG
LPG

LPG
H H

LPG
ACCESSORIES

LPG
LPG
C C

LPG
LPG
LPG

LPG
32Ø HWS PIPE H H

DIESEL TANK FOR DIESEL ENGINE


LPG
32Ø DWS PIPE @

CAPACITY250 US GALLONS
LPG
LPG

LPG
C C
ABOVE CEILING

LPG

LPG
RETURN

H H

SUPPLY
LPG

LPG
LPG
C C

LPG
C C C C C C C C
H H H C
C

LPG

LPG
WC WC WC WC
40Ø CWS PIPE F/B,T/A

WC
C C C
C C C C BOOSTER LINE
H LPG
H 40Ø CWS PIPE F/B,T/A
H H H H H C
C BOOSTER LINE
C C 32Ø HWS PIPE

WC
32Ø HWS PIPE C
32Ø DWS PIPE @ 32Ø HWS PIPE
H H 32Ø DWS PIPE @
ABOVE CEILING H C 32Ø DWS PIPE @
C
ABOVE CEILING

WC
C ABOVE CEILING
M
H C
C

WC
C REVISIONS
C H C H C H C H
C C C H C H C H C H C H C
32Ø HWS PIPE C No. Ref.No. Description Issue Date

WC
32Ø DWS PIPE @ C

M M M M
ABOVE CEILING H C 32Ø HWS PIPE
C
32Ø DWS PIPE @

WC
C
ABOVE CEILING
32Ø DWS PIPE @

PRV
H C
ABOVE CEILING C 0 REV-00 - dd-mm-yy

WC
C
C C C C C

H H H H C

WC
WC WC WC WC

C
C
C C C C C C C C C H

C 60Ø CWS PIPE F/A,T/B


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
C BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
32Ø HWS PIPE F/A
C

GT
25Ø CWS PIPE@
RUNS THROUGH Mr. JAMAL AL KOOHEJI AND
U/G
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

GROUND FLOOR PLUMBING


LAYOUT

P-101

REV-00
Xref D:\MEP\2021\2116\Working drawing\2116-Xref\2116_Xref column.dwg
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

50Ø TRANSFER LINE T/A

40Ø CWS PIPE F/B,T/A


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

60Ø CWS PIPE F/A,T/B


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
32Ø HWS PIPE F/A

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

MEZZANINE FLOOR PLUMBING


LAYOUT

P-102

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

50Ø TRANSFER LINE T/A

40Ø CWS PIPE F/B,T/A


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE

C C C C C C C C
H C
WC WC WC WC
C

WC
C C C C C

H H H H H C
C

WC
C
25Ø HWS PIPE
25Ø DWS PIPE @ H C
C

WC
ABOVE CEILING C
M
32Ø HWS PIPE
H C
C 32Ø DWS PIPE @

WC
C ABOVE CEILING REVISIONS
C H C H C H C H
H C H C H C H C H C No. Ref.No. Description Issue Date
C

WC
C

H C
C
25Ø HWS PIPE

WC
C
25Ø DWS PIPE @
H C
ABOVE CEILING C
40Ø HWS PIPE 0 REV-00 - dd-mm-yy

WC
C
C C C C
40Ø DWS PIPE @
ABOVE CEILING
H H H H C

WC
WC WC WC WC

C
C C C C C C C C C H

60Ø CWS PIPE F/A,T/B


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
32Ø HWS PIPE F/A

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

FIRST FLOOR PLUMBING


LAYOUT

P-103

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

50Ø TRANSFER LINE T/A

40Ø HWS PIPE F/A


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE

C C C C C C C C H C

WC WC WC WC
C

WC
C C C C C
H C 40Ø HWS PIPE
H H H H 40Ø DWS PIPE @
C
ABOVE CEILING

WC
C
25Ø HWS PIPE H C
25Ø DWS PIPE @ C

WC
ABOVE CEILING C
H C
C

WC
C REVISIONS
C H C H C H C H
H C
H C H C H C H C No. Ref.No. Description Issue Date
C

WC
C 32Ø HWS PIPE
H C 32Ø DWS PIPE @
C ABOVE CEILING
25Ø HWS PIPE

WC
C
25Ø DWS PIPE @ H C
ABOVE CEILING C 0 REV-00 - dd-mm-yy

WC
C
C C C C

H H H H C

WC
WC WC WC WC

C
C C C C C C C C C H

60Ø CWS PIPE F/A,T/B


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
32Ø HWS PIPE F/A
BOOSTER LINE

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

SECOND FLOOR PLUMBING


LAYOUT

P-104

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

50Ø TRANSFER LINE T/A

40Ø HWS PIPE F/A


BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE

C C C C C C C C H C

WC WC WC WC
C

WC
C C C C C
H C 40Ø HWS PIPE
H H H H 40Ø DWS PIPE @
C
ABOVE CEILING

WC
C
25Ø HWS PIPE H C
25Ø DWS PIPE @ C

WC
ABOVE CEILING C
H C
C

WC
C REVISIONS
C H C H C H C H
H C
H C H C H C H C No. Ref.No. Description Issue Date
C

WC
C 32Ø HWS PIPE
H C 32Ø DWS PIPE @
C ABOVE CEILING
25Ø HWS PIPE

WC
C
25Ø DWS PIPE @ H C
ABOVE CEILING C 0 REV-00 - dd-mm-yy

WC
C
C C C C

H H H H C

WC
WC WC WC WC

C
C C C C C C C C C H

60Ø CWS PIPE F/A,T/B


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
32Ø HWS PIPE F/A
BOOSTER LINE

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

THIRD FLOOR PLUMBING


LAYOUT

P-105

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

ELETRIC WATER HEATER ELETRIC WATER HEATER


300 LITER CAPACTIY 300 LITER CAPACTIY
(4NOS) (4NOS)
THIRD FLOOR THIRD FLOOR
50Ø TRANSFER LINE T/A

40Ø CWS PIPE F/B,T/A


BOOSTER LINE
40Ø CWS PIPE F/B,T/A
BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE

25Ø CWS PIPE@


RUNS THROUGH
FLOOR
GT

VMS BOOSTER PUMP SET (WITH SHADE)


ONE DUTY/ ONE STANDBY
WITH VFD CONTROL PANEL 4.5L/S
@ 3.0 BAR WITH COMPLETE
HORIZONTAL WATER TANK
ACCESSORIES WITH PRESSURE M
SIZE:2400H X 1550ØW
VESSEL-100LITRE.
4000L CAPACITY (4nos)
REVISIONS
No. Ref.No. Description Issue Date
PRV

0 REV-00 - dd-mm-yy
NOTE: 50Ø CWS PIPE
RUN THROUGH F/L
BOOSTER LINE

50Ø CWS PIPE


RUN THROUGH F/L 32Ø HWS PIPE F/A
HWS LINE BOOSTER LINE
40Ø HWS PIPE F/A
BOOSTER LINE
32Ø CWS PIPE F/B,T/A
BOOSTER LINE
32Ø CWS PIPE F/B,T/A
BOOSTER LINE
60Ø CWS PIPE F/A,T/B
BOOSTER LINE

32Ø CWS PIPE


RUN THROUGH F/L ELETRIC WATER HEATER
ELETRIC WATER HEATER 300 LITER CAPACTIY
300 LITER CAPACTIY BOOSTER LINE
(4NOS) Mr. JAMAL AL KOOHEJI AND
(4NOS) FIRST FLOOR
GROUND FLOOR Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

ROOF DECK PLUMBING


LAYOUT

P-106

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:
H.GENERAL NOTES :--

ZCV
UNDER GROUND
CONCRETE WATER TANK
SIZE: 9800L X 6400W X 2200H(EFFECTIVE DEPTH)
TOTAL CAPACITY:- 138.0M³
FIRE FIGHTING CAPACITY:- 90M³
DOMESTIC WATER CAPACITY:-45M³ REVISIONS
A.DESIGN NOTES :--
No. Ref.No. Description Issue Date
³

C.WET RISER & HOSE REEL SYSTEM


FIRE PUMPS SET FOR FIRE HOSE REEL 0 REV-00 - dd-mm-yy
CAPACITY - 300 GPM @ 8 BAR HEAD (UL LISTED)
1. ELECTRICAL PUMP
2. DIESEL ENGINE PUMP
3. JOCKEY PUMP
WITH CONTROL PANEL AND
COMPLETE ACCESSORIES
FIRE FIGHTING SCHEMATIC DIAGRAM
SCALE N.T.S.
D.FIRE WATER STORAGE :--

E.FIRE PUMPS :--

F.DESIGN CRITERIA :--

Mr. JAMAL AL KOOHEJI AND


03
Mr. HISHAM AL RAYYES

G.TESTING & COMMISSIONING :--


PROPOSED 4-STOREY COMMERCIAL
BUILDING
@ Halet Um Al Bhaid
DETAIL 'A'
THE FIRE FIGHTING CONTRACTOR SHOULD SUBMIT DETAILED SHOP DRAWINGS ZONE CONTROL VALVE GENERAL NOTES FOR FIRE
TO THE CIVIL DIFFENCE DEPT. FOR APPROVAL BEFORE STARTING THE WORK. SCALE N.T.S.
FIGHTING LAYOUT

F-000

REV-00
25mm Angle Valve
25Ø Pressure ISSUED FOR TENDER:
Reducing Valve SIGNED:
DATE: 21 September 2021
25mm Gate Valve 750
40 700 40 300

40
GENERAL NOTES:
25mm x 30M AUTOMATIC
FIRE HOSE REEL

700 40
1500

1640
820
40
250
SIDE VIEW
FRONT VIEW

ZCV
REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

Mr. JAMAL AL KOOHEJI AND


Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

DETAILS FOR FIRE FIGHTING


LAYOUT

F-001

REV-00
FIRE PUMPS SET FOR FIRE HOSE REEL ISSUED FOR TENDER:
CAPACITY - 300 GPM @ 8 BAR HEAD (UL LISTED) SIGNED:
DATE: 21 September 2021
1. ELECTRICAL PUMP
2. DIESEL ENGINE PUMP
3. JOCKEY PUMP GENERAL NOTES:
WITH CONTROL PANEL AND
COMPLETE ACCESSORIES

UNDER GROUND
CONCRETE WATER TANK
SIZE: 9800L X 6400W X 2200H(EFFECTIVE DEPTH)
TOTAL CAPACITY:- 138.0M³
FIRE FIGHTING CAPACITY:- 90M³
DOMESTIC WATER CAPACITY:-45M³

100Ø 100Ø 100Ø 100Ø 100Ø

2- WAY BREACHING INLET


FOR HOSE REEL AND DRY
RISER SYSTEM

100Ø DRY RISER T/A

FE FE

ZCV
100Ø DRY RISER T/A
100Ø 100Ø
PUMP
PUMP
JOCKEY

MOTOR
TANK

ENGINE
PRESSURE

PANEL

100Ø
FE WC WC WC WC

WC
WC
100Ø

WC
100Ø

WC
REVISIONS
No. Ref.No. Description Issue Date

WC
FE

WC
100Ø 100Ø
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

100Ø 100Ø

FE
FHRC 100Ø FHR PIPE F/A
100Ø DRY RISER F/B
Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

GROUND FLOOR FIRE FIGHTING


LAYOUT

F-201

REV-00
Xref D:\MEP\2021\2116\Working drawing\2116-Xref\2116_Xref column.dwg
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

100Ø DRY RISER F/B


100Ø FHR PIPE F/A

ZCV
REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

100Ø FHR PIPE F/A


100Ø DRY RISER F/B
Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

MEZZANINE FLOOR FIRE


FIGHTING LAYOUT

F-202

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

100Ø DRY RISER F/B


100Ø FHR PIPE F/A

ZCV
FE FE

FHRC
WC WC WC WC

WC
WC
WC
WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

FHRC

FE FE
100Ø FHR PIPE F/A
100Ø DRY RISER F/B
Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

FIRST FLOOR FIRE FIGHTING


LAYOUT

F-203

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

100Ø DRY RISER F/B


100Ø FHR PIPE F/A

ZCV
FE FE

FHRC
WC WC WC WC

WC
WC
WC
WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

FHRC

FE FE
100Ø FHR PIPE F/A
100Ø DRY RISER F/B
Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

SECOND FLOOR FIRE


FIGHTING LAYOUT

F-204

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

GENERAL NOTES:

100Ø DRY RISER F/B


100Ø FHR PIPE F/A

ZCV
FE FE

FHRC
WC WC WC WC

WC
WC
WC
WC
REVISIONS
No. Ref.No. Description Issue Date

WC
WC
0 REV-00 - dd-mm-yy

WC
WC
WC WC WC WC

FHRC

FE FE
100Ø FHR PIPE F/A
100Ø DRY RISER F/B
Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

THIRD FLOOR FIRE FIGHTING


LAYOUT

F-205

REV-00
ISSUED FOR TENDER:
SIGNED:
DATE: 21 September 2021

65Ø LANDING VALVE


AUTOMATIC AIR
VENT
100Ø DRY RISER F/B

REVISIONS
No. Ref.No. Description Issue Date

0 REV-00 - dd-mm-yy

AUTOMATIC AIR 65Ø LANDING VALVE


VENT

100Ø DRY RISER F/B


Mr. JAMAL AL KOOHEJI AND
Mr. HISHAM AL RAYYES

PROPOSED 4-STOREY COMMERCIAL


BUILDING
@ Halet Um Al Bhaid

ROOF DECK FIRE FIGHTING


LAYOUT

F-206

REV-00