Training Course SICAM PAS
Training Course SICAM PAS
2 System components
Training Course
3 PAS Software Setup
4 Starting Parameterization
SICAM PAS -
Parameterization 5 UI-Operation
6 Value Viewer
10 HMI-Interface
11 System Variables
12 Control Authority
13 Remote WinCC
14 OPC
15 CFC
16 Programming Language ST
17 ST - practicle example
18 IEC61850
19 Trace function
20 Server-DIP configuration
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Tasks
• Substation Automation System with de-central architecture
and IEC 61850 communication
• Tele-communication to one or several Control Centres
• Automation functions
• Local visualization, archiving and logging (SICAM PAS CC)
• Remote visualization, archiving and logging (Web Navigator)
• Interface to IEDs and substations
• Data exchange with OPC
• Data acquisition and transmission under Real-Time-Conditions
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Distributed Intelligence
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
All-in-One-Configuration
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Station Unit and HMI separated
Corporate
Network TCP/IP
Zentrale
Station Bus
Ethernet IEC61850
Up to 100 IEDs
Up to 5.000 data points
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Full Server – DIP configuration Up to 6 DIPs
Corporate
Up to 150 IEDs
Network TCP/IP
Zentrlae
Up to 10.000 Data points
IEC T101 IEC T104
“Full Server” SICAM PAS CC “DIP”
Station Bus
Ethernet IEC61850
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Redundant configuration
IEDs with IEC 61850
IEDs with Profibus FMS
Corporate
………HMI Clients…….. RTUs with Dual-Master-
Network TCP/IP
Protocol
Zentrale
IEC T104
“Full Server” “Full Server”
Redundanter
HMI Server
Profibus FMS
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SCD-
Reduced engineering effort XML File
Bottom-up configuration
Data exchange
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Basic Package SICAM PAS UI
Depending on the requirements, different basic packages are available
Basic package Full Server and DIP are available in two variants
A pure engineering package is available additionally
Full Server RunTime RunTime DIP
& &
Configuration Configuration
RunTime RunTime
SICAM PAS UI
Configuration
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
SICAM PAS UI – 3 Tools
SICAM PAS UI – Configuration
for parameterization of the project specific applications
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS UI Configuration
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
SICAM PAS Export of T101 / !04
Import of engineering (Slave)- engineering data
data
- IEC 61850 XML-
- Profibus FMS Export-
- IEC 60870-5-103 file
- IEC 60870-5-101
Export of T101 Export of T103 Export of Profibus FMS Export of IEC 61850
(Slave) engineering data engineering data for Engineering data engineering data
for SAS, RTU, eRTU from SIPROTEC 4 for SIPROTEC 4 for SIPROTEC 4
SICAM plusTOOLS > V4.0
Dbase- XML- DIGSI 4 SCD-
XML- DIGSI 4 Export- DIGSI 4 Export- Export-
Export- file file file
file
SICAM PAS or PCC
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
CP
OPC
1 Ethernet, S7-Protocol
OPC OPC 6
Client Server 1
3
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Option - Automation
Auto-
mation
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Time Synchronization
Use of a „time-synchronization module“ in the Station Unit
SICAM
PAS CC
Antenna
Ethernet (TCP/IP)
Station Unit
Time-
Time Master
Module /-server
Hopf
IEC 61850
T103
T101
Profibus FMS
24
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Time Synchronization
• A separate time master for Ethernet can be used
• SNTP-Server (Simple Network Time Protocol)
• Synchronization of all connected devices (SNTP-Clients)
Antenna
Station Unit
SICAM
PAS CC
IEC 61850
Ethernet (TCP/IP) T103
T101
Profibus FMS
25
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Fault Recording
Fault recording of protection devices connected via
• IEC 60870-5-103, Profibus FMS and IEC 61850
• Automatic transmission of fault records
• Automatic archiving of fault records on the Full Server or DIP
• SICAM Recpro consists of:
– SICAM Recpro Explorer
– SICAM Recpro Collector
– Comtrade Viewer
• SIGRA 4 can be used for a more sophisticated analysis of fault records
(not included in SICAM Recpro)
26
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Fault Recording
SICAM Recpro SICAM Recpro Collector
Explorer and Automatic transmission of
Comtrade archives of the station units to
Viewer a superior level fault record archive
SICAM Recpro PC
Ethernet TCP/IP
IEC 61850
IEC 60870
Profibus FMS -5-103
27
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Differences to SICAM SAS and SICAM PCC
communication to SCADA systems
PAS SAS PCC Remarks (PAS)
number of connections 5 3 5
IEC 60870-5-101 slave ☺ ☺ ☺
- balanced ☺ ☺ ☺
- unbalanced ☺ ☺ ☺
- dual channel ☺ available in V6.0
- Norway user convention ☺ available in V6.0
IEC 60870-5-104 slave ☺ ☺ ☺
- dual channel ☺ available in V6.0
- Norway user convention ☺ available in V6.0
SINAUT-8FW slave ☺
DNP V3.00 ☺ ☺ level 2
TG800 slave ☺
TG8979 slave ☺
Ferranti slave ☺
IEC 60870-6 Tase.2 (ICCP) ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 28
28
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Differences to SICAM SAS and SICAM PCC
communication to sub-systems / IEDs
PAS SAS PCC Remarks (PAS)
IEC 60870-5-101 master ☺ ☺ ☺
- balanced ☺ ☺
- unbalanced ☺ ☺ ☺
- dial up ☺ ☺
DNP V3.00 ☺ ☺ ☺ level 2
IEC 61850 client ☺
IEC 60870-5-103 ☺ ☺ ☺
Profibus FMS (UPF) ☺ ☺ no station interlocking for local control
Profibus DP ☺ ☺ ☺ SIMEAS Q can not be connected
Modbus ☺
SEAbus+ ☺
29
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Differences to SICAM SAS and SICAM PCC
open communication
PAS SAS PCC Remarks (PAS)
OPC server ☺ ☺
OPC client ☺
TCP/IP / OSI ☺ ☺ SAS: only S7-functions
ODBC (Database Gateway) ☺ PAS/SAS: possible in WinCC
architecture of HMI
PAS SAS PCC Remarks (PAS)
all-in-one possible ☺ ☺
1 HMI for several controller ☺ ☺
several HMI for 1 controller ☺ ☺
client-server architecture ☺ ☺ ☺
redundant server ☺ ☺
multi-server architecture ☺ ☺
remote HMI via www ☺ ☺ ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 30
30
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Differences to SICAM SAS and SICAM PCC
architecture / central tasks
PAS SAS PCC Remarks (PAS)
automation ☺ ☺
switching authority ☺ ☺ channel specific
bay blocking ☺ ☺
station blocking ☺ ☺ channel specific
hot-hot redandancy ☺ ☺ IEC 61850, Profibus FMS
distibuted architecture ☺ ☺ SAS: IEDs, frame coupling
direct I/O connection ☺
diagnostic tools on board ☺ ☺ value-viewer
remote diagnostic ☺ SICAM Diamond in V5.1
SOE logger ☺ PAS / SAS in WinCC
Trace Control Centre ☺
Tool-kit (IED protocols) ☺ with OPC possible
fault records ☺ ☺ ☺
- central archiv ☺ ☺
- comtrade format ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 31
31
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Hardware and System requirements
Operating system
• Windows XP professional
• Windows XP embedded
• Windows 2000 professional
• Windows 2000 Server
Hardware Platform
• Pentium III processor 800 MHz
• 256 Mbyte RAM
• 512 Mbyte hard disk capacity
• VGA-card for 1280 x 1024 resolution
• CDROM- drive
If used together with SIMATIC WinCC, the system requirements for SIMATIC WinCC must also
be observed!
32
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Interfaces to IEDs and Substations
• Profibus FMS 2 CP5613 per Station Unit with up to 30 IEDs each
• Profibus DP 2 CP5613 per Station Unit (recommendation) with up
to 30 IEDs each
• IEC60870-5-103, IEC60870-5-101, DNP V3.00, Modbus
- Use of COM expanders (e.g.Rocket Ports) or serial hubs
- Up to 2 internal COM expanders with up to 32 interfaces each
- Up to 100 devices connected to one Full Server or DIP
• IEC 61850 Up to 100 devices connected to one Full Server or DIP
33
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication options: IEC 61850
IEC 61850
The new communication standard for the station bus
• based on Ethernet
• Up to 128 IEDs
• Ethernet components from Ruggedcom recommend
• IEC 61850-Goose-mechanism
– Inter-bay-interlocks
– Communication between IEDs
TP
62,5µ or 50µ Fibre
TP TP
TP Cu Twisted Pair (TP)
Shielded cable
max. 20m
34
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication options: PROFIBUS FMS
Profibus FMS
• Up to 2 x CP5613 per Station Unit
• Up to 30 IEDs (100 information each) per CP5613
• Profibus components from A&D, e.g. OLM
35
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication options: IEC 60870-5-103
• Connection with serial interfaces
• Extension of interfaces:
IEC 60870-5-
– Internal COM-Expander 103
– Serial hubs => connection to Ethernet-LAN
– RS232 --> RS485 Converter
– Star coupler 7XV5.... (not 7XV57)
Ethernet TCP/IP
Serial Hub
RS485, RS232
36
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication options: Other IED protocols
• DNP V3.00
IED-
– Serial interface
protocols
=> IEC 60870-5-103
• Profibus DP
– Up to 2 x CP5613 per Station Unit
– Up to 31 devices per CP5613
– Profibus components from A&D, e.g. OLMs
=> Profibus FMS
• Modbus
– Serial interface via RS485 (COM-Expander or serial Hub)
37
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication options: IEC 60870-5-101 Master
• Operating modes
– Balanced
– Unbalanced (up to 16 satellite RTUs) Recommendation:
Use of COM-
Expanders (e.g.
• Dial-up traffic (IAWD; analog, ISDN, GSM) Rocket-Ports) =>
Reducing CPU load
– Operating modes
IEC 60870-5-
• Unbalanced ( mRTU) Modem Modem
101
• Balanced master
• Recommended modem – INSYS Public
Telephone
Network
– Back-up modem possible
Recommendation:
max. 8 substations on
one ‘PAS-Modem’
38
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Hardware and System requirements
Communication to up to 5 control centers
• IEC 60870-5-101
– balanced TC-
– unbalanced protocols
– Baud rate 1,2 .. 38,4 kBaud
– Communication via serial interface
• IEC 60870-5-104
– Communication via Ethernet interface
• DNP V3.00
– Baud rate 1,2 .. 38,4 kBaud
– Communication via serial interface
39
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Energy must be safe
SICAM
PAS CC SICAM
eRTU
SICAM
PAS
SIPROTEC
SICAM
SICAM
mini/micro
Diamond
RTU
40
SICAM PAS
System Components
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Contents
SICAM PAS Station units
– Communication modules CP5613 / CP1613
– Time receiver module
Operator desk / Engineering PCs
Ethernet Components
– OSMs / ESM
Serial Components
– Rocket ports
– Rocket port serial Hub
– Converters
IEC 61850 - Components
Others
– Time receiver device
– Modem
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Station Unit
• Station Unit 6MD9100
• Fan less operation
• No rotating hard disk
=> silicon flash disk
• Secure operation with high availability
• Watchdog, temperature monitoring
• Versions:
» PIII 933 MHz / 384 MB Ram
» With / w.o PCI-bridge (for 4 standard PCI cards)
» Windows XP embedded; Silicon Flash Disk: 1 GB (separate HMI)
– Max. 6 DIPs
– max. 100 devices to one PAS Full Server / max. 5000 variables
• max. 100 devices to one PAS DIP / max. 5000 variables
• max. 150 devices to one PAS system
(Full Server and DIP) / max. 10.000 variables
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Station Unit 6MD9100
1x LAN 2x USB 2x RS232
Option: PCI–bridge
with 4 slots
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Industrial Ethernet Card CP1613
– Use for the data exchange with
OPC functionality to the automation devices
e.g. SIMATIC
– OPC Server software package included
– Example
A Simatic S7-400 is connected to a SICAM PAS Station Unit through a CP1613
and via the Ethernet. The communication used between the S7-400 and the
CP1613 is the S7 protocol. An OPC server for the CP1613 card is available
from SIMATIC. In this way data can be exchanged with the SICAM PAS OPC
Client. Ethernet, S7-Protocol
Station Unit CP443-1 S7-400
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Profibus FMS and DP
– Profibus FMS e.g. SIPROTEC 4 devices
– Profibus DP e.g. ET200, SIMEAS P
– Max. 4 Profibus modules CP5613 in each Station Unit.
(only 2 modules can be used for Profibus FMS) CP5613
OLM
Repeater
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Time Sychronisation Module in the Station Unit
• PC-card for DCF77 and GPS from Hopf (www.hopf-time.com)
• For time synchronization of the Station Unit and the connected IEDs (if
supported by the protocol) and the connected HMI-PCs (SICAM PAS CC)
SICAM
antenna PAS CC
Ethernet (TCP/IP)
Station Unit
Time.-
Receiver Time master
module /-server
Hopf
IEC 61850
T103
T101
Profibus FMS
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Operator Desk / Engineering PCs
Industrial Rack PC
• SIMATIC rack PC IL40
– 19”-rack platform
– High performance under harshest conditions
– 1 Gbyte main memory
– Integrated security function (watchdog, temperature and fan control)
¾ Server PC in a SICAM PAS CC Client/Server – HMI System
¾ Operator desk in a SICAM PAS CC Single user system
CELSIUS Workstation
• Type M420
– 1 GB main memory
¾ Client PC in a SICAM PAS CC Client/Server – HMI System
¾ Operator desk in a SICAM PAS CC Single user system
¾ Engineering Desk
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System components
PTD-SE-A0/ 8
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OSM / ESM
OSM – Optical Switch Modules 10/100 MBit
OSM TP22 2x RJ45 ports max. 3000m
OSM TP62 6x RJ45 ports max. 3000m
OSM TP62LD 6x RJ45 ports max. 26 km
Additional Feature:
Optical 100 Mbit/s-ring with High-speed redundant ring
(reconfiguration time of the ring, up to 0.3 seconds)
RJ45, 10/100 BaseTX
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System components
PTD-SE-A0/ 9
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Com-Expander: Rocket Port
Additional serial Com-interfaces RS232: 4, 8, 16, 32
max. 2 Rocket Ports with 32 interfaces each
max. 100 devices on one Full-Server or DIP
PCI-card for PC
Com-interfaces
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Comtrol Serial Hub
Decentral serial connection via Ethernet-LAN
2 serial ports RS232/RS485
http://www.comtrol.com
Ethernet-LAN-Interface
2 pcs. Com-interface
Ethernet TCP/IP
Serial Hub
RS485 RS232
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Converters
Converter RS232/485 (2 ports)
Meilhaus: IRK-100
2x RS485
http://www.meilhaus.com
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Converters
Converter 7XV565*
FO/RS485 (bus)
FO/RS485 (ring)
FO/RS232
RS 232 Interface
FO-Interface
(4 output; 1 income)
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication with IEC 61850
– The communication standard for the station bus based on Ethernet
– Max. Number of connected devices 128
– We recommend the use of Ethernet components from Ruggedcom
http://www.ruggedcom.com
TP
62,5µ or 50µ Fibre
100 Mbit/s redundant switched Ethernet ring
Bay cubicle
No redundancy,
Cost-optimized
TP TP
TP
Cu Twisted Pair (TP)
Shielded cable
max. 20m
TP=Twisted Pair
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication with IEC 61850
9 RUGGEDCOM Ethernet-Switch, complies with IEC61850 requirements
9 Rail mounting
9 Output relay
9 Fan free operation
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication with IEC 61850
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication with IEC 61850 2x FO- ports (MTRJ)
14x RJ45-ports
No redundancy
Cost-optimized
Cu Shielded Pair
max. 20m
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Communication with IEC 61850
9 Ethernet-
Switch,
complies with
IEC61850
requirements
9 Redundant
power supply
9 Output relay
9 Fan free
operation
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Time Synchronisation
Siemens SICLOCK
A separate time master can be used especially in configuration
with the Ethernet station bus (IEC 61850) via SNTP-Server
(Simple Network Time Protocol).
– It synchronizes all connected devices
(SNTP-Clients), incl. the Station Unit. Station Unit
is the time master for all connected devices.
SICAM
PAS CC
Meinberg
(Time-) SNTP Time master
Master clock -Client /-server
SNTP-Server
by Meinberg
or Siclock
IEC 61850
Ethnernet (TCP/IP) T103
T101
Profibus FMS
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Modems
Insys Modem for ISDN and GSM
IEC 60870-5-101 supports the
– Dial-up traffic
– IAWD
– ISDN
– GSM
– Analog
– Operating modes
– Unbalanced ( Ù Use of SICAM miniRTU)
– Balanced
20
SICAM PAS
Software Setup
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Starting Setup.exe
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Setup
SICAM PAS
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Everything is already
checked by default Operation language
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Demo or licensed
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
SICAM PAS
Starting Parameterisations
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS Server
SICAM eRTU
IEC 101
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Feature Enabler
Distributed System
Infrastructure
(Data Router)
To use automation
functions (CFC)
All other applications are communication tasks
and depend on the desired communication interfaces
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Installing applications
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuration Window
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuration Window
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuration Window
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Computer Settings
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Creating an interface
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
If the COM ports were not defined before (refer to page 10), the
parameter appeared in red colour.
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Importing a file
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Importing a file
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Exporting data
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Rename list
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The imported
information
appears under
Mapping
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Ticking the USE means to make a message available for further processing,
i.e. to send to an HMI-system, to send to a telecontrol center, to process in
logic functions etc.
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
To select a whole column, click once on the headline, then move the cursor
into the selected area and click right to obtain the yes-no-menu
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 23
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Minimum one message must be assigned to the GI-List for a standard GI.
More than one message means, to enable a completeness check Æ all ticked
messages have to be received during a GI.
24
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Topology allows us to
create certain
information levels to
structure information.
The topological levels´
names together with
the information name is
the text used in the HMI
system.
25
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The topology partly defines the text string for the HMI system
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 26
26
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
27
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
28
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Sorting information
29
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Marking information
Select the first line of the desired group, keep the shift-button pressed while
(scrolling down and) selecting the last line.
30
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Moving information
31
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Disable filter
32
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
33
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
No saving necessary
The next topic will show, how we can test our new
configuration.
34
SICAM PAS
UI-Operation
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Starting UI-Operation
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
UI-Operation Window
The Operation
window displays all
the components we
defined in UI-
Configuration, but this
is an online-view
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Operation functions
Each level shows the current state and can manually be started or stopped
The IED level additionally contains buttons for Bay-Blocking and Telecontrol-Blocking
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Operation functions
With the context menu we also can start or stop including all the sublevels
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Startup completed
After a few seconds all the levels have started and are running now
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
UI-Operation
PTD-SE-A0/ 10
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Important Notes
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Fault Diagnosis
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS Services
1)
2)
3)
3)
2)
15
SICAM PAS
Value Viewer
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
•Every line represents an information point, e.g. SP, DP, ME_FL, IT...
•Various components are displayed in columns, e.g. Value, Cause, Validity
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The selection of the top level displays all information in the substation
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Value Viewer
PTD-SE-A0/ 4
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Important columns
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Important columns
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Important columns
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Control function
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Testing data
11
IEC60870-5-101
Slave Interface
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Mapping
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Change to UI-Operation
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
After Starting the IEC101-Slave including the sublevels, the slave changes into
Pending Up mode.
As no Control Center is connected, the communication will not yet run.
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SIPROTEC
8
The SICAM Station Unit
for Commissioning Engineers
The year of Profitable Growth
1
Power Transmission and Distribution
Power Automation
Progress. It‘s that simple.
2
Power Transmission and Distribution
Introduction
Power Automation
Progress. It‘s that simple.
Introduction
Introduction BIOS Settings
BIOS Settings
Hardware
Hardware
Harddisk Harddisk
WXPE
EWF WXPE
Delivery State
Commissioning
EWF
Trouble Shooting Delivery State
Commissioning
Trouble Shooting
3
Power Transmission and Distribution
BIOS Settings
Power Automation
Progress. It‘s that simple.
BIOS:
Introduction
BIOS Settings
Hardware Standard CMOS Features Frequency/Voltage Control
Harddisk
Advanced BIOS Features Load Fail-Safe Defaults
WXPE
EWF Advanced Chipset Features Load Optimized Defaults
Delivery State
Integrated Peripherals Set Supervisor Password
Commissioning
Trouble Shooting IMC Miscellaneous Set User Password
Power Management Save and Exit Setup
PNP/PCI Configurations Exit Without Saving
PC Health Status
4
Power Transmission and Distribution
BIOS Setup
Power Automation
Progress. It‘s that simple.
5
Power Transmission and Distribution
BIOS Setup
Power Automation
Progress. It‘s that simple.
IMC Miscellaneous:
Introduction SMP 16-Bus: Disable
BIOS Settings
Hardware
PNP/PCI Configuration:
Harddisk Assign IRQ for USB: Enable
WXPE
EWF PC Health Status:
Delivery State
Commissioning
Throttling Temperature: 110°C/230°F
Trouble Shooting
6
Power Transmission and Distribution
Hardware
Power Automation
Progress. It‘s that simple.
7
Power Transmission and Distribution
Harddisk
Power Automation
Progress. It‘s that simple.
8
Power Transmission and Distribution
Windows XP Embedded
Power Automation
Progress. It‘s that simple.
Introduction
BIOS Settings
Hardware
Harddisk
WXPE
EWF
Delivery State
Commissioning What is Windows XP Embedded?
Trouble Shooting
9
Power Transmission and Distribution
10
Power Transmission and Distribution
Benefits
Power Automation
Progress. It‘s that simple.
Enhanced Performance
Specially tailored reduced operating system for SICAM
PAS
Accelerated boot and shut down process
XP Professional XP Embedded improvement
Boot ~ 30 sec ~ 24 sec 25%
Shut Down ~28 sec ~ 7 sec 400%
Better Reliability
Robust operating system
Allows a closed-case design, limiting the ability for end-
users to add/subtract/modify the operating system or
application
Higher Security
Most threats / viruses do not run or can not be installed
Energy Automation Dr. H. Hitzeroth 10.2004 11
11
Power Transmission and Distribution
Read/write
12
Power Transmission and Distribution
13
Power Transmission and Distribution
14
Power Transmission and Distribution
15
Power Transmission and Distribution
16
Power Transmission and Distribution
17
Power Transmission and Distribution
18
Power Transmission and Distribution
19
Power Transmission and Distribution
20
Power Transmission and Distribution
Standard PCs are more sensitive to surge SICAM PAS uses SIEMENS Industrial PCs
effects (IPC) compliant with highest industrial
standards
Low reliability of PC, e.g. hard disk failures SICAM PAS uses IPC & flash memory
no watchdog drives, i.e. no moving parts such as hard
disks or fans
SIEMENS IPC has a built in watchdog
Lower reliability of Windows based SICAM PAS can run under Windows XP
systems Embedded (WXPE) OS, i.e. the OS is
specially tailored for the SA application
Power Supply failure w/o proper shut SICAM PAS Station uses the enhanced
down can lead system to hang, i.e. no write filter technology to protect system
automatic unattended reboot partition
PC / Windows system: Danger of viruses SICAM PAS uses WXPE OS, i.e. the OS is
specially tailored for improved virus
protection
21
Power Transmission and Distribution
Standard PCs have reduced temperature SICAM PAS uses IPC with higher
range temperature range Æ up to 75° C
environment temperature w/o fan
Standard PCs are leading users to "play" SICAM Station Unit has no floppy & CD
with the systems Rom drive
SICAM Station Unit runs Windows XP
Embedded (WXPE) OS, i.e. the OS is
specially tailored for the SA application
Î no games, multimedia etc.
Standard PCs are leading users to "play" SICAM PAS Station Unit guarantees up to
with the systems 10 years spare parts availability
ÎIt is very difficult to get spare parts due
to fast developments in IT
22
Power Transmission and Distribution
23
Power Transmission and Distribution
SICAM PAS
SICAM PAS Station Unit – Order number
Power Automation SICAM ENERGY AUTOMATION
Progress. It‘s that simple. SICAM PAS Station Unit
Product description
SICAM PAS Station Unit based on Industrial Microcomputer
19" housing
950 MHZ Pentium III CPU 320 Mbyte Ram
1 Mbyte -Flash-EPROM
10 LEDs , VGA, LAN 10/100, 2 x USB, 2x COM, keyboard-mouse (shared)
fan less, without moving components
SICAM PAS Software preinstalled
L G F
Base price 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Order-Number 6 M D 9 1 0 0 - 0 - 0 A A 0
| | | | |
| | | | |
Power Supply 8 | | | |
DC 24V 3 | | | |
AC 110 - 230V 7 | | | |
Configuration / Operating System 9 | | |
Flash disk 1 GB / Windows XP embedded A | | |
Language of Operating System and SICAM PAS 10 | |
German A | |
English B | |
PCI-Bridge 11 |
without 0 |
included (empty) 1 |
Function 12
Full Server 0
Device Interface Processor (DIP) 1
Energy Automation Dr. H. Hitzeroth 10.2004 24
24
Power Transmission and Distribution
Delivery State
Power Automation
Progress. It‘s that simple.
Preinstalled with:
Operating System
Tweak Tools
Acrobat Reader
Simatic Net (Authors W, Simatic Net PC) (on D:)
PAS FS / DIP D / E (on D:)
25
Power Transmission and Distribution
Comissioning
Power Automation
Progress. It‘s that simple.
Load the PAS Database into the PAS on to the Station Unit.
26
Power Transmission and Distribution
Trouble Shooting
Power Automation
Progress. It‘s that simple.
27
Power Transmission and Distribution
Power Automation
Progress. It‘s that simple.
28
IEC60870-5-103
via Siemens Serial
Hub 7XV5655
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS Server
SIPROTEC
Serial Hub
7XV5655
Mini Bay Unit
6MB525
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The Configuration Tool has always to be installed to be able to do the settings on the
hub.
The firmware is usually not necessary, as it should be already installed on the hub by
the factory.
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 5
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Downloading files
After downloading
we get these
packed files
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Extracting files
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuration
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configure name
The name should be set to make it easier to identify the hub, if there were several
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configure IP-address
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configure properties
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Diagnostic
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS Configuration
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuration
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Creating an interface
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Communication Parameters
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Creating a device
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
24
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The import is
logged in a
report
window.
25
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Device Parameters
26
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
The imported
information
appears under
Mapping
27
SICAM PAS
HMI-Interface
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Routing to HMI
Do not mix up
the 2 Control
centers !
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Explaination follows
on next pages
Explaination:
If there was any change in Topology, the texts for WinCC also changes.
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Explaination
Text due to the defined topolgy These text strings are usually just copies
Explaination:
If there was any change in Topology, the texts for WinCC also changes.
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Explaination
The question now means, if there was a difference between those text strings, a „YES“
changes the „WinCC-Texts“ according to the topological text strings,
a „NO“ keeps the differences.
Explaination:
If there was any change in Topology, the texts for WinCC also changes.
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
PAS Server
and HMI-System
7
SICAM PAS
System Variables
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
System Variables
_Adm = control information Æ 1= enable communication with device, 0= stop communication with device
_Opr = monitoring information Æ 1= communication with device running, 0= communication with device stopped
_BlkAdm = control information for Bay Blocking and Telecontrol Blocking Æ 131072=block bay level
Æ 196608=block teletransmission
Æ 262144=block both
Æ 65536=disable blockings
_BlkOptr = monitoring information for Bay Blocking and Telecontrol Blocking Æ 131072=Bay blocked
Æ 196608=Teletransmission blocked
Æ 262144=both blocked
Æ 65536=no blockings
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System Variables
PTD-SE-A0/ 2
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Bay Blocking
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
7
SICAM PAS
Switching Authority
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Matrix
The one we are defining, is the white line, while all othter interfaces
are grey coloured.
You can assign only your interface in the white line.
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Simple symbol
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Advanced symbol
The button
disappears, when
a checkbox was
ticked and written
8
SICAM PAS CC
Remote WinCC
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS CC
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Settings in UI-Configuration
We have to configure a DIP with a subleveled HMI (although there is no real DIP)
Select the computer name of the HMI computer
The IP-address of the HMI computer appears then automatically
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
WinCC Explorer
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Properties windows
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Connection properties
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
7
SICAM PAS
OPC Communication
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
What is OPC ?
OPC
• stands for OLE (Object Linking and Embedding) for Process Control
• is the automation industry‘s version of OLE
• provides an open, flexible, plug-and-play software standard for software
interoperability in the automation industry
• specific to the automation industry and its' unique needs for data
communication (alarming, historical data access and trending, batch and
more)
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
What is OPC ?
OPC
• is based on OLE, COM (component object model) and DCOM
(distributed component object model) technologies
• consists of a standard set of interfaces, properties and methods
for use in process- control and manufacturing automation
application
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Why OPC ?
• Openness
– System-wide operation between automation products of different
manufacturers
– Data are only acquired once from field level right up to operational control
level
– Access to MS-Office under Windows
• Ease of Use
– Same user interface for different components
• Performance
– C++ interface
– Efficient data access through volume operations
– Requirement-oriented client-server communication
• Connectability
– Can be reached by any computer in the LAN/WAN (via COM/DCOM)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
OPC Communication
PTD-SE-A0/ 4
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
How does OPC work ?
• OPC Client
OPC – Initiates OPC communications
Client
– Read/write requests
• OPC
OPC
– Communications based on COM/DCOM
– Data: single or in groups
OPC
• OPC Server
Server
– Executes client requests
– Cyclically/change-driven
– Makes own data available
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Overview of OPC data flow
Network
Network
From any server
PAS CC To any client
HMI system
Routing
Substation
IEC101-Master
Controller
IEC101-slave
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
How to configure an OPC server – COM/DCOM-Service
dcomcnfg
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server – COM/DCOM - General properties
Select „NONE“
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server – Location and Security
No modification required
=default
=default
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server - Security
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server – Identity and Endpoints No modification required
=default
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server Æ UI-Configuration
Have to be entered
For OPC server we have not to use the feature enabler, because it is a free standard function in
PAS.
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server Æ Mapping
Enable
information,
which has to
be available
for OPC
clients
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC server Æ UI-Operation
Update configuration
OPC Server remains in „Pending Up“ until the OPC client accesses
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client
Enter OPC client and
interface.
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Selecting an OPC server
Select the Computer Name parameter and hit the browser button to select a OPC
server computer.
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Selecting an OPC server
Open your network, select the desired computer name, and mark the OPC server
object.
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Selecting an OPC server
Computer
name and
OPC server
are now
entered.
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Entering a Device
Enter a device now and browse for the desired variables.
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Variables supplied by a server
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Templates
The new OPC device appears as a Template
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Correct protocol information types
The protocol
information types have
to be corrected
manually, because
they all appear as SP.
Commands always
appear as SC and they
remain as such !
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
OPC Communication
PTD-SE-A0/ 22
OPC does not support exchange of PAS information types. That´s why we must correct them
manually.
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client – Mapping
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
OPC client Æ UI-Operation
Update configuration
Start OPC-Client
It takes a while (about 1 min) until the OPC client has accessed the server.
While the client is pending up, the server already turns to RUN.
24
SICAM PAS
CFC Logic Function
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Grouping of information
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Information to CFC
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Duplicating information
As information has to
be unique, we have
to rename our new
message.
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Choose type
Position block
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
M=Master
S=Slave
G=Group
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
M=Master
S=Slave
G=Group
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Compilation
Compilation finished
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Run Sequence
1st
The width of a chart
is just one page, but
the length is
endless.
The Run Sequence
depends of the
position of a block.
System starts
always at the left
last hand side top of the
1st page, goes
down to the bottom
of the last page,
and then to the top
of the next column.
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
CFC Diagnostics
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
CFC Diagnostics
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Online View
Online values
24
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
CFC Diagnostics
25
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Training
Page 1
SICAM PAS automation with ST, 16.06.04 Nürnberg
1
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Structure:
Overview
 Basics IEC 61131
 Instructions in ST
 Summary
Page 2
SICAM PAS automation with ST, 16.06.04 Nürnberg
2
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 3
SICAM PAS automation with ST, 16.06.04 Nürnberg
3
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 4
SICAM PAS automation with ST, 16.06.04 Nürnberg
4
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 5
SICAM PAS automation with ST, 16.06.04 Nürnberg
5
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
z No recursion !
Page 6
SICAM PAS automation with ST, 16.06.04 Nürnberg
6
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
IEC61131 z Example
Page 7
SICAM PAS automation with ST, 16.06.04 Nürnberg
7
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
z Function blocks can use internal variables, their values can be preserved
after leaving
z Standard function blocks are already defined in the Standard
z no recursion!
Page 8
SICAM PAS automation with ST, 16.06.04 Nürnberg
8
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
IEC61131 z Example
Page 9
SICAM PAS automation with ST, 16.06.04 Nürnberg
9
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 10
SICAM PAS automation with ST, 16.06.04 Nürnberg
10
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Example
FB:
Page 11
SICAM PAS automation with ST, 16.06.04 Nürnberg
11
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
z Syntax of a declaration:
IEC61131
Example
PROG:
Page 12
SICAM PAS automation with ST, 16.06.04 Nürnberg
12
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 13
SICAM PAS automation with ST, 16.06.04 Nürnberg
13
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
z Example:
TYPE
State : BYTE:=4;
END_TYPE
14
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 15
SICAM PAS automation with ST, 16.06.04 Nürnberg
15
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 16
SICAM PAS automation with ST, 16.06.04 Nürnberg
16
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Example FB in ST
ST
Page 17
SICAM PAS automation with ST, 16.06.04 Nürnberg
17
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Command in ST
Operand1
Expression1 Operator
Expression2
ST-Programm
Statement
Page 18
SICAM PAS automation with ST, 16.06.04 Nürnberg
18
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Keywords in ST
Keyw ord Description Remarks
ST := Definition Functions are always used in a
definition
Call and Use of FBs has to be declared in the
declaration part
RET URN Return
; Blank command
Page 19
SICAM PAS automation with ST, 16.06.04 Nürnberg
19
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Operators in ST
Priority
ST
Operator Description high
() in brackets
Function call
** Potentiation
- Negation
NOT Complement
* Multiplication
/ Division
MOD Modulo
+ Addition
- Subtraction
<, >, <=, >= Equation
= Equality
<> inequality
&, AND Boolean AND
low
XOR Exklusive Boolean OR
OR Boolean OR
Page 20
SICAM PAS automation with ST, 16.06.04 Nürnberg
20
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Definition in ST
ST z Syntax:
Designator := Expression
z Example:
Trigger := TRUE;
a := 4 / 2 + 1;
b := FunctionA(4);
Page 21
SICAM PAS automation with ST, 16.06.04 Nürnberg
21
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
ST z FB-Call (Example):
Declaration Program
VAR
FB_TEST : PAS_SASS; FB_TEST(EN:=TRUE);
END_VAR b:=FB_TEST.MARKER;
z RETURN (Example)
RETURN;
Page 22
SICAM PAS automation with ST, 16.06.04 Nürnberg
22
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
IF Clause
ST z Syntax:
z Example:
Page 23
SICAM PAS automation with ST, 16.06.04 Nürnberg
23
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
ST z Syntax:
CASE Print OF
Print value: Command block;
ELSE Command block;
END_CASE;
z Example:
CASE value1 OF
1: RETURN;
2: flag:=TRUE;
ELSE flag:=FALSE;
END_CASE;
Page 24
SICAM PAS automation with ST, 16.06.04 Nürnberg
24
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
FOR - Loops
ST z Syntax:
z Example:
FOR i:=5 to 1 BY -1 DO
value[i]:= i;
END_FOR;
25
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
WHILE - Loops
ST z Syntax:
WHILE Print DO
Command block;
END_WHILE;
z Example:
WHILE flag=TRUE DO
wert:=wert-1;
if wert<5 THEN flag:=FALSE;
END_IF;
END_WHILE;
Page 26
SICAM PAS automation with ST, 16.06.04 Nürnberg
26
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
REPEAT - Loops
ST z Syntax:
REPEAT
Command block;
UNTIL Print
END_REPEAT;
z Example:
REPEAT
value:=wert+1;
UNTIL value>5
END_REPEAT;
Page 27
SICAM PAS automation with ST, 16.06.04 Nürnberg
27
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
(* Comment *)
z Example:
(* This is a comment *)
Page 28
SICAM PAS automation with ST, 16.06.04 Nürnberg
28
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 29
SICAM PAS automation with ST, 16.06.04 Nürnberg
29
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
VAR_INPUT FUNCTION_BLOCK
SIGNAL : BOOL; IF DEF_SET=FALSE THEN
RESET : BOOL; COUNT:=DEFAULT;
DEFAULT : INT;
END_VAR DEF_SET:=TRUE;
END_IF;
VAR_OUTPUT
COUNT : INT; (* READING CHANGE OF SIGNAL *)
END_VAR IF SIGNAL<>OLD_SIG THEN
COUNT:=COUNT+1;
VAR OLD_SIG:=SIGNAL;
DEF_SET : BOOL:=FALSE; END_IF
OLD_SIG : BOOL:=FALSE;
END_VAR
(* READING RESET *)
IF RESET=TRUE THEN
COUNT:=0;
COUNT:=DEFAULT;
END_IF
END_FUNCTION_BLOCK
Page 30
SICAM PAS automation with ST, 16.06.04 Nürnberg
30
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
PAS and ST
z SICAM PAS already contains Firmware FBs
z These FBs can be used in your own FBs
z Interface-variables have their own datatype in PAS:
– PASDATABLOCK
– PASCOMMANDBLOCK
– PASGROUP
z These interface-types are structures with one element, a
pointer
z Interface-variables must have a constant value!!!
Page 31
SICAM PAS automation with ST, 16.06.04 Nürnberg
31
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Page 32
SICAM PAS automation with ST, 16.06.04 Nürnberg
32
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
PAS and ST
z Written ST- function blocks or ST-functions can be used in a
CFC chart
z Using of most adequate language is possible
z Import/Export -> use in other projects
z Theoretical only: In CFC rendered blocks can be used
in ST
z Mixing of both languages is possible
Page 33
SICAM PAS automation with ST, 16.06.04 Nürnberg
33
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D
Any question?
Summary
Page 34
SICAM PAS automation with ST, 16.06.04 Nürnberg
34
Programming
Language ST
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Create an ST File
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Result
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
New Example
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Declaration of variables
External Variables
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Declaration of variables
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Programming Part
LOGIC:
110 or
101 or
011
THEN ÆOUT=1, otherwise 0
Create Indication,Enable = 1, Cause= spontaneous, Indictype= SP, Signal_1Æreceives current value from
The boolean variable OUT, ChangeÆ to trigger the block, Send Æto execute during startup!
OUT_IND is the resultant variable and gets the result from CRI-output INDIC
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
11
IEC61850
The new Standard in
Substations
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
...and in future
IEC 61850
One World
One Technology
One Standard
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
International Standard
• Covers all substation functions like
protection, automation and monitoring
• Is a global standard and the key for
interoperable solutions
• Investment security through openness,
exppandability and garanteed future
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Reduced Engineering
No multiple inputs because of data im/export from/to DIGSI
for further use e.g. in a control centr system
XML Import / Export reduces number of errors.
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Security of Investment
Architecture & data model are future proof and support future extensions
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Interoperability
the ability of two or more IEDs from the same vendor, or from
different vendor, to exchange information and to use that
information for correct execution of specific functions
Interchangeability
the ability to replace a device supplied by one manufacturer
with a device supplied by another manufacturer, without
making change to the other elements in the system
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Engineering
The Engineering requires to configure the structure of the system,
which consists of Busses, Hubs, Switches, Routers, IEDs, Merging
Units ect.
The chosen topology determines the assignment to the primary process and
the physical redundancy of the system.
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
• Server
supports
connection at the
same time to
several clients
Server
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 13
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Multicast
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
configuration
data
input output
data data
Basic Function
(e.g. Protection)
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Logical Nodes
MMXU Measuring (Measurand unit)
Group Indicator Logical node groups MMTR Metering
MSQI Sequence and Imbalance
A Automatic Control MHAI Harmonics and Inter-harmonics
MDIF Differential Measurements
C Supervisory control
PSCH Protection Scheme
G Generic Function References PTEF Transient Earth Fault
I Interfacing and Archiving PZSU Zero speed or
underspeed
L System Logical Nodes PDIS Distance protection
…more
M Metering and Measurement
P Protection functions
SIMG Insulation medium meas unit
R Protection related functions
SARC Monitoring and diagnostics for arcs
S Sensors SPDC Monitoring and diagnostics for partial
discharge
T Instrument Transformer
X Switchgear
Y Power Transformer
XCBR Circuit Breaker
Z Further (power system) XSWI Circuit Switch
equipment
16
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
17
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
18
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Example
Logical Device
IED3 IED2
Circuit Breaker
TCTR XCBR
T1 Q0
IED - Intelligent Electronic Device (every device with a communication interface)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 19
19
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
IED1/CBCSWI1.Pos.ctlVal
20
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configurations
The new communication standard for the station bus
• based on Ethernet
• Up to 128 IEDs
• Ethernet components from Ruggedcom recommend www.ruggedcom.com
• IEC 61850-Goose-mechanism
– Inter-bay-interlocks
– Communication between IEDs For small medium voltage plants
TP
62,5µ or 50µ Fibre
Inter-bay-interlocking independent from the Station Unit via IEC 61850-Goose mechanism
21
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
RS8000T
9 Ethernet switch
according IEC61850
specification
9 DIN-Rail Mount
9 Fanless operation
22
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
20m
23
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
No Redundancy
cost optimized
Cu Shielded Pair
max. 20m
24
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
9 Ethernet switch,
according
IEC61850
spezification
9 Redundant
power supply
9 Fan less
operation
25
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Ruggedcom-Switches - Interfaces
RS8000T
RS1600T
RS1600F
RS1600
RS8000
RS400
Interfaces / Device type
FO-Ports (MTRJ-connector)
100BaseFX 1300nm 2 2 2 8 16
max. 2000m
RJ45-Ports
10/100BaseTX 6 14 4
max. 20m
FO-Ports (ST-Stecker)
12
100BaseFL 820nm
http://www.ruggedcom.com
26
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
27
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Engineering System
Device Device file configurator
Device library vendor A
vendor B engineering vendor B
tool vendor B
Device Device
Each device must have a self-description file engineering engineering
tool vendor B tool vendor A
Device file
vendor X
Standardized file
28
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
System Configurator
(part of Digsi)
29
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
30
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
User specific
data
in LD CTRL /
SIPROTEC data (Siemens- LN GGIOs
specific) in LD CTRL / LN GGIOs
31
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
System configurator
for inter-bay communication
32
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
33
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Defining IP-Addresses
34
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
35
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Distribution of mapping to
involved devices
36
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
IEC 61850
• Modbus
• DNP 3.0
EN100
Module
• Substation communication
• Transmission of fault records
• Downloading and uploading parameter files
• IED configuration
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 37
37
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
FO cable (Multimode)
Serial interface:
Ethernet cable (max. 20 m) - Substation automation with serial protocol
RS485 – Bus (Optional: IEC 60870-5-103 via device port B
Serial FO-Bus. No parallel - DIGSI via device service port C
operation possible) Ethernet interface:
- IEC61850 / DIGSI via ethernet module on
device port B
Modem
Router
Ethernet
LAN (INTRANET) Addressing of serial
hubs like two virtual
COM-Ports on the
Switch
Station Unit
IEC61850 and Substation
DIGSI via Ethernet
Ethernet module
INPUT INPUT
Serial Serial
Serial 7XV5450
7XV5655
-0BA00
7XV5450
7XV5655
-0BA00
IEC 103 DIGSI
Mini- Mini-
hub
Serial Hub
Sternkoppler
Serial Hub
Sternkoppler Port B Port C
SIEMENS SIPROTEC SIEMENS SIPROTEC SIEMENS SIPROTEC
RUN ERROR RUN ERROR RUN ERROR
Anr. L1
Anr. L2
RUN
L1 402,1A
SIPROTEC
ERROR
Max450.1A
SIEMENS
L1 402,1A
RUN
SIPROTEC
ERROR
Max450.1A
SIEMENS
L1 402,1A
RUN
SIPROTEC
ERROR
Max450.1A
38
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
39
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
40
SICAM PAS
Trace Function
Applications dsiTest and TraceControlCenter
are for testing only !!!
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
What is a Trace Function ?
• With a specified trace the PAS system creates a text file with detailed
internal data for a certain application.
• This function is mainly used to find out unidentified errors in the
parameterization as well as in the system software.
• The text file is usually sent to the customer support center to be evaluated
by system experts.
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Enter Password
The Password is 000000
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Local connection
Activate local
connection on local PC
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Online Diagnosis
Display Source
Information
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Identify Source ID
Source Information
Reference in UI-
Configuration
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Trace function
PTD-SE-A0/ 7
7
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Going Online
8
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Default values
9
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
What is the Trace Function doing now?
10
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Starting TraceControlCenter
11
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
TraceControlCenter: Settings
Select application, which is the
interface name of your desired
source ID (e.g. Protection Interface)
12
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
13
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Apply Settings
14
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
15
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Close DSITEST
16
SICAM PAS
Server-DIP
Configuration
1
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
SICAM PAS
Full Server – DIP Configuration Up to 6 DIPs
Corporate
Up to 150 Bay devices
Network TCP/IP
Station Bus
Ethernet IEC61850
2
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
3
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Select DIP
4
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Starting UI-Configuration
After opening UI-Configuration, it does not appear empty !
As the server computer is already running, it displays its project even on the DIP.
Modifications are possible on both of the computers.
5
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
6
Po w
s
e
Train r
in
Cent g
Power Transmission and Distribution Service er
Configuring a DIP