1 Basics

2 System components
Training Course
3 PAS Software Setup

4 Starting Parameterization
SICAM PAS -
Parameterization 5 UI-Operation

6 Value Viewer

7 Telecontrol with IEC101 Slave

8 Serial Hub 7XV5655

9 Station Unit 6MD9100

10 HMI-Interface

11 System Variables

12 Control Authority

13 Remote WinCC

14 OPC

15 CFC

16 Programming Language ST

17 ST - practicle example

18 IEC61850

19 Trace function

20 Server-DIP configuration

Edition: March 2005 21 IECTEST


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
PTD SE
22
SICAM PAS
Basics

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Tasks
• Substation Automation System with de-central architecture
and IEC 61850 communication
• Tele-communication to one or several Control Centres
• Automation functions
• Local visualization, archiving and logging (SICAM PAS CC)
• Remote visualization, archiving and logging (Web Navigator)
• Interface to IEDs and substations
• Data exchange with OPC
• Data acquisition and transmission under Real-Time-Conditions

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Distributed Intelligence

No more bottlenecks and classical master / slave


architecture
Intelligence moves closer to the process due to
distributed functionality using enhanced bay controllers
SCADA Corporate
Network TCP/IP
SCADA Engineering HMI
Communication Browser
SCADA / WAN
Station Unit
Master
HMI
Unit Station Bus

Ethernet IEC 61850


Slave Slave BU PU BU PU
e.g. I/O Unit e.g. I/O Unit
independent
communication
Process

Master / Slave Architecture Client / Server Architecture providing distributed intelligence

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
All-in-One-Configuration

For small applications


Up to 10-15 Bay devices
SICAM PAS and SICAM PAS CC
together at the same Station Unit
Server computer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Station Unit and HMI separated
Corporate
Network TCP/IP

Zentrale

IEC T101 IEC T104


“Full Server”
SICAM PAS CC

Station Bus

Ethernet IEC61850

Up to 100 IEDs
Up to 5.000 data points

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Full Server – DIP configuration Up to 6 DIPs

Corporate
Up to 150 IEDs
Network TCP/IP

Zentrlae
Up to 10.000 Data points
IEC T101 IEC T104
“Full Server” SICAM PAS CC “DIP”

Station Bus

Ethernet IEC61850

DIP = Device Interface Processor


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Redundant configuration
IEDs with IEC 61850
IEDs with Profibus FMS
Corporate
………HMI Clients…….. RTUs with Dual-Master-
Network TCP/IP
Protocol
Zentrale

IEC T104
“Full Server” “Full Server”

Redundanter
HMI Server

Ethernet IEC61850 Station Bus

Profibus FMS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS – a scalable system


SICAM PAS UI – Highlights
Easy & Efficient Configuration
No compilation and loading into a
separate runtime system necessary

Online changes w/o restarting


the whole system

Tools for test & diagnostics


Integrated tools, Value Viewer….

SCD-
Reduced engineering effort XML File

Bottom-up configuration
Data exchange

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Basic Package SICAM PAS UI
Depending on the requirements, different basic packages are available
Basic package Full Server and DIP are available in two variants
A pure engineering package is available additionally
Full Server RunTime RunTime DIP
& &
Configuration Configuration
RunTime RunTime

SICAM PAS UI
Configuration

The basic package contents:


Value-Viewer
OPC Server
Sybase SQL data-base-system
Real-time data handler - Distributed System Infrastructure (DSI)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
SICAM PAS UI – 3 Tools
SICAM PAS UI – Configuration
for parameterization of the project specific applications

SICAM PAS UI – Operation


- provides an overview of:
applications, interfaces and device connections

SICAM PAS Value Viewer


- a tool for engineering, commissioning and operation
- permits the visualization of:
process- and system status
and the command execution for test purposes

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

PAS UI Configuration

Structured work by 4 views


• Configuration - to configure functions and interfaces

• Mapping - to route information

• Topology - to designate messages

• Templates - for multiple use

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Configuration
4 views for structured work:
Configuration / Mapping / Topology / Templates

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Configuration
4 views for structured work:
Configuration / Mapping / Topology / Templates

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Configuration
4 views for structured work:
Configuration / Mapping / Topology / Templates

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Configuration
4 views for structured work:
Configuration / Mapping / Topology / Templates

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Operation
Applications / Interfaces / Device connections overview

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable system


SICAM PAS UI – Value Viewer
• A tool for engineering, testing, commissioning and operation.
• It allows the visualization of the process and system
information without additional engineering expenses and
provides information about current status and quality.
• Also the command direction can be tested.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SINAUT Spectrum Power CC

SICAM PAS - a scalable System Import of engineering data


- IEC 60870-5-101

Data Exchange - IEC 60870-5-104

SICAM PAS
SICAM PAS Export of T101 / !04
Import of engineering (Slave)- engineering data
data
- IEC 61850 XML-
- Profibus FMS Export-
- IEC 60870-5-103 file
- IEC 60870-5-101

Export of T101 Export of T103 Export of Profibus FMS Export of IEC 61850
(Slave) engineering data engineering data for Engineering data engineering data
for SAS, RTU, eRTU from SIPROTEC 4 for SIPROTEC 4 for SIPROTEC 4
SICAM plusTOOLS > V4.0
Dbase- XML- DIGSI 4 SCD-
XML- DIGSI 4 Export- DIGSI 4 Export- Export-
Export- file file file
file
SICAM PAS or PCC

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS – a scalable System


Software: Basic Package and Options
Option
IED-
protocols Option
Option
TC-
x
SICAM PAS Protocol Order only what you need:
Basic Basic package + required
package options
Option
Automation
Option
x
Option
x

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable System


Software – Options
• Protocols for connection to IEDs and substations
– IEC 61850 => Version V5.1, app. 07/04
– Profibus FMS (SICAM / SIPROTEC specified protocols)
– IEC 60870-5-103
Options
– DNP V3.00
– Profibus DP
– Modbus
– ILSA (internal LSA protocol) => Version V5.1, app. 07/04
• Protocols for connection to control centers
– IEC 60870-5-101
– IEC 60870-5-104
– DNP V3.00
• Open communication e.g. data exchange with SIMATIC
– OPC Client
• Automation with CFC and Structured Text
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable System


Option – OPC-Client
– Data exchange and communication with OPC Server OPC
using the OPC Client Client
– The communication partner OPC Server can be located
on the same PC or on another PC connected
via TCP/IP (Ethernet)
– The open communication can especially be used for the data
exchange with automation devices e.g. SIMATIC
Station Unit
SICAM PAS SIMATIC

CP
OPC
1 Ethernet, S7-Protocol
OPC OPC 6
Client Server 1
3

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS - a scalable System


Option – Automation
The Automation task is implemented with SoftPLC.
– CFC = Continuous Function Chart Auto-
– or with Structured Text (ST) mation
– library with specific system-tested function blocks

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 22

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Option - Automation

Auto-
mation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Time Synchronization
Use of a „time-synchronization module“ in the Station Unit
SICAM
PAS CC
Antenna
Ethernet (TCP/IP)
Station Unit

Time-
Time Master
Module /-server
Hopf

IEC 61850
T103

T101
Profibus FMS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 24

24
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Time Synchronization
• A separate time master for Ethernet can be used
• SNTP-Server (Simple Network Time Protocol)
• Synchronization of all connected devices (SNTP-Clients)
Antenna
Station Unit

SICAM
PAS CC

(Time-) SNTP Time Master


Master clock -Client /-server
SNTP-Server
by Meinberg
or Siclock

IEC 61850
Ethernet (TCP/IP) T103

T101
Profibus FMS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 25

25
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Fault Recording
Fault recording of protection devices connected via
• IEC 60870-5-103, Profibus FMS and IEC 61850
• Automatic transmission of fault records
• Automatic archiving of fault records on the Full Server or DIP
• SICAM Recpro consists of:
– SICAM Recpro Explorer
– SICAM Recpro Collector
– Comtrade Viewer
• SIGRA 4 can be used for a more sophisticated analysis of fault records
(not included in SICAM Recpro)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 26

26
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Fault Recording
SICAM Recpro SICAM Recpro Collector
Explorer and Automatic transmission of
Comtrade archives of the station units to
Viewer a superior level fault record archive

SICAM Recpro PC

Ethernet TCP/IP

Full Server DIP Full Server

IEC 61850
IEC 60870
Profibus FMS -5-103

= communication- specific fault recording archive


= collected fault recording archives, higher level fault recording
archives
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 27

27
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Differences to SICAM SAS and SICAM PCC
communication to SCADA systems
PAS SAS PCC Remarks (PAS)
number of connections 5 3 5
IEC 60870-5-101 slave ☺ ☺ ☺
- balanced ☺ ☺ ☺
- unbalanced ☺ ☺ ☺
- dual channel ☺ available in V6.0
- Norway user convention ☺ available in V6.0
IEC 60870-5-104 slave ☺ ☺ ☺
- dual channel ☺ available in V6.0
- Norway user convention ☺ available in V6.0
SINAUT-8FW slave ☺
DNP V3.00 ☺ ☺ level 2
TG800 slave ☺
TG8979 slave ☺
Ferranti slave ☺
IEC 60870-6 Tase.2 (ICCP) ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 28

28
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Differences to SICAM SAS and SICAM PCC
communication to sub-systems / IEDs
PAS SAS PCC Remarks (PAS)
IEC 60870-5-101 master ☺ ☺ ☺
- balanced ☺ ☺
- unbalanced ☺ ☺ ☺
- dial up ☺ ☺
DNP V3.00 ☺ ☺ ☺ level 2
IEC 61850 client ☺
IEC 60870-5-103 ☺ ☺ ☺
Profibus FMS (UPF) ☺ ☺ no station interlocking for local control
Profibus DP ☺ ☺ ☺ SIMEAS Q can not be connected
Modbus ☺
SEAbus+ ☺

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 29

29
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Differences to SICAM SAS and SICAM PCC
open communication
PAS SAS PCC Remarks (PAS)
OPC server ☺ ☺
OPC client ☺
TCP/IP / OSI ☺ ☺ SAS: only S7-functions
ODBC (Database Gateway) ☺ PAS/SAS: possible in WinCC

architecture of HMI
PAS SAS PCC Remarks (PAS)
all-in-one possible ☺ ☺
1 HMI for several controller ☺ ☺
several HMI for 1 controller ☺ ☺
client-server architecture ☺ ☺ ☺
redundant server ☺ ☺
multi-server architecture ☺ ☺
remote HMI via www ☺ ☺ ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 30

30
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Differences to SICAM SAS and SICAM PCC
architecture / central tasks
PAS SAS PCC Remarks (PAS)
automation ☺ ☺
switching authority ☺ ☺ channel specific
bay blocking ☺ ☺
station blocking ☺ ☺ channel specific
hot-hot redandancy ☺ ☺ IEC 61850, Profibus FMS
distibuted architecture ☺ ☺ SAS: IEDs, frame coupling
direct I/O connection ☺
diagnostic tools on board ☺ ☺ value-viewer
remote diagnostic ☺ SICAM Diamond in V5.1
SOE logger ☺ PAS / SAS in WinCC
Trace Control Centre ☺
Tool-kit (IED protocols) ☺ with OPC possible
fault records ☺ ☺ ☺
- central archiv ☺ ☺
- comtrade format ☺
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 31

31
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Hardware and System requirements
Operating system
• Windows XP professional
• Windows XP embedded
• Windows 2000 professional
• Windows 2000 Server

Hardware Platform
• Pentium III processor 800 MHz
• 256 Mbyte RAM
• 512 Mbyte hard disk capacity
• VGA-card for 1280 x 1024 resolution
• CDROM- drive
If used together with SIMATIC WinCC, the system requirements for SIMATIC WinCC must also
be observed!

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 32

32
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Interfaces to IEDs and Substations
• Profibus FMS 2 CP5613 per Station Unit with up to 30 IEDs each
• Profibus DP 2 CP5613 per Station Unit (recommendation) with up
to 30 IEDs each
• IEC60870-5-103, IEC60870-5-101, DNP V3.00, Modbus
- Use of COM expanders (e.g.Rocket Ports) or serial hubs
- Up to 2 internal COM expanders with up to 32 interfaces each
- Up to 100 devices connected to one Full Server or DIP
• IEC 61850 Up to 100 devices connected to one Full Server or DIP

• Up to 100 devices to one “Full Server” & up to 5000 variables


• Up to 100 devices to one “DIP” & up to 5000 variables
• Up to 150 devices to one PAS system (Full Server and DIP) &
up to 10000 variables

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 33

33
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication options: IEC 61850
IEC 61850
The new communication standard for the station bus
• based on Ethernet
• Up to 128 IEDs
• Ethernet components from Ruggedcom recommend
• IEC 61850-Goose-mechanism
– Inter-bay-interlocks
– Communication between IEDs

TP
62,5µ or 50µ Fibre

100 Mbit/s redundant switched Ethernet ring


No Redundancy,
Bay Cubicle Cost-optimized

TP TP
TP Cu Twisted Pair (TP)
Shielded cable
max. 20m

Small medium voltage switchgear

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 34

34
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication options: PROFIBUS FMS
Profibus FMS
• Up to 2 x CP5613 per Station Unit
• Up to 30 IEDs (100 information each) per CP5613
• Profibus components from A&D, e.g. OLM

RS485-single bus FO single ring FO double ring

Remarks – no interbay interlocking during local control


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS Basics
PTD-SE-A0/ 35

35
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication options: IEC 60870-5-103
• Connection with serial interfaces
• Extension of interfaces:
IEC 60870-5-
– Internal COM-Expander 103
– Serial hubs => connection to Ethernet-LAN
– RS232 --> RS485 Converter
– Star coupler 7XV5.... (not 7XV57)

Ethernet TCP/IP
Serial Hub
RS485, RS232

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 36

36
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication options: Other IED protocols

• DNP V3.00
IED-
– Serial interface
protocols
=> IEC 60870-5-103

• Profibus DP
– Up to 2 x CP5613 per Station Unit
– Up to 31 devices per CP5613
– Profibus components from A&D, e.g. OLMs
=> Profibus FMS

• Modbus
– Serial interface via RS485 (COM-Expander or serial Hub)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 37

37
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication options: IEC 60870-5-101 Master
• Operating modes
– Balanced
– Unbalanced (up to 16 satellite RTUs) Recommendation:
Use of COM-
Expanders (e.g.
• Dial-up traffic (IAWD; analog, ISDN, GSM) Rocket-Ports) =>
Reducing CPU load
– Operating modes
IEC 60870-5-
• Unbalanced ( mRTU) Modem Modem
101
• Balanced master
• Recommended modem – INSYS Public
Telephone
Network
– Back-up modem possible

• Serial interface Modem Modem Modem


=> IEC 60870-5-103
SICAM SICAM SICAM
miniRTU miniRTU miniRTU

Recommendation:
max. 8 substations on
one ‘PAS-Modem’

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 38

38
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Hardware and System requirements
Communication to up to 5 control centers
• IEC 60870-5-101
– balanced TC-
– unbalanced protocols
– Baud rate 1,2 .. 38,4 kBaud
– Communication via serial interface

• IEC 60870-5-104
– Communication via Ethernet interface

• DNP V3.00
– Baud rate 1,2 .. 38,4 kBaud
– Communication via serial interface

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 39

39
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Energy must be safe

SICAM
PAS CC SICAM
eRTU
SICAM
PAS
SIPROTEC
SICAM
SICAM
mini/micro
Diamond
RTU

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS Basics
PTD-SE-A0/ 40

40
SICAM PAS
System Components

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Contents
SICAM PAS Station units
– Communication modules CP5613 / CP1613
– Time receiver module
Operator desk / Engineering PCs
Ethernet Components
– OSMs / ESM
Serial Components
– Rocket ports
– Rocket port serial Hub
– Converters
IEC 61850 - Components
Others
– Time receiver device
– Modem

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Station Unit
• Station Unit 6MD9100
• Fan less operation
• No rotating hard disk
=> silicon flash disk
• Secure operation with high availability
• Watchdog, temperature monitoring
• Versions:
» PIII 933 MHz / 384 MB Ram
» With / w.o PCI-bridge (for 4 standard PCI cards)
» Windows XP embedded; Silicon Flash Disk: 1 GB (separate HMI)
– Max. 6 DIPs
– max. 100 devices to one PAS Full Server / max. 5000 variables
• max. 100 devices to one PAS DIP / max. 5000 variables
• max. 150 devices to one PAS system
(Full Server and DIP) / max. 10.000 variables

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Station Unit 6MD9100
1x LAN 2x USB 2x RS232

Option: PCI–bridge
with 4 slots

CPU Power Supply


DC 24V
AC 110V to 250V

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Industrial Ethernet Card CP1613
– Use for the data exchange with
OPC functionality to the automation devices
e.g. SIMATIC
– OPC Server software package included

– Example
A Simatic S7-400 is connected to a SICAM PAS Station Unit through a CP1613
and via the Ethernet. The communication used between the S7-400 and the
CP1613 is the S7 protocol. An OPC server for the CP1613 card is available
from SIMATIC. In this way data can be exchanged with the SICAM PAS OPC
Client. Ethernet, S7-Protocol
Station Unit CP443-1 S7-400

SICAM PAS SIMATIC


CP
OPC 1
OPC OPC 6
Client Server 1
3

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Profibus FMS and DP
– Profibus FMS e.g. SIPROTEC 4 devices
– Profibus DP e.g. ET200, SIMEAS P
– Max. 4 Profibus modules CP5613 in each Station Unit.
(only 2 modules can be used for Profibus FMS) CP5613

– Max. 30 devices (100 data points per unit) on each CP5613


– Use of Profibus components from A&D (e.g. OLM)
„ RS485 line „ FO double bus

OLM
Repeater

ƒ Remarks – no inter-bay interlocking during local control


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System components
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Time Sychronisation Module in the Station Unit
• PC-card for DCF77 and GPS from Hopf (www.hopf-time.com)
• For time synchronization of the Station Unit and the connected IEDs (if
supported by the protocol) and the connected HMI-PCs (SICAM PAS CC)

SICAM
antenna PAS CC
Ethernet (TCP/IP)
Station Unit

Time.-
Receiver Time master
module /-server
Hopf

IEC 61850
T103
T101
Profibus FMS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Operator Desk / Engineering PCs
Industrial Rack PC
• SIMATIC rack PC IL40
– 19”-rack platform
– High performance under harshest conditions
– 1 Gbyte main memory
– Integrated security function (watchdog, temperature and fan control)
¾ Server PC in a SICAM PAS CC Client/Server – HMI System
¾ Operator desk in a SICAM PAS CC Single user system

CELSIUS Workstation
• Type M420
– 1 GB main memory
¾ Client PC in a SICAM PAS CC Client/Server – HMI System
¾ Operator desk in a SICAM PAS CC Single user system
¾ Engineering Desk
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System components
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OSM / ESM
OSM – Optical Switch Modules 10/100 MBit
„ OSM TP22 2x RJ45 ports max. 3000m
„ OSM TP62 6x RJ45 ports max. 3000m
„ OSM TP62LD 6x RJ45 ports max. 26 km

ESM - Electrical Switch Module 10/100 MBit


„ ESM TP40 4x RJ45 ports max. 100m
„ ESM TP80 8x RJ45 ports max. 100m

„ Additional Feature:
„ Optical 100 Mbit/s-ring with High-speed redundant ring
(reconfiguration time of the ring, up to 0.3 seconds)
„ RJ45, 10/100 BaseTX
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System components
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Com-Expander: Rocket Port
Additional serial Com-interfaces RS232: 4, 8, 16, 32
„ max. 2 Rocket Ports with 32 interfaces each
„ max. 100 devices on one Full-Server or DIP
PCI-card for PC

Com-interfaces

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Comtrol Serial Hub
„ Decentral serial connection via Ethernet-LAN
2 serial ports RS232/RS485
http://www.comtrol.com

Ethernet-LAN-Interface
2 pcs. Com-interface

Ethernet TCP/IP
Serial Hub

RS485 RS232

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Converters
„ Converter RS232/485 (2 ports)
Meilhaus: IRK-100
2x RS485
http://www.meilhaus.com

„ Communication board (PCI) (4 ports)


Moxa: Industrio CP114-I
2x selectable RS232 or RS485
2x RS485
http://www.moxatech.de

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Converters

„ Converter 7XV565*
„ FO/RS485 (bus)
„ FO/RS485 (ring)
„ FO/RS232

„ Mini Star Coupler 7XV5450 (not 7XV57)


„ Max. 1.5 km 62.5/125 um
„ Cascadable

RS 232 Interface

FO-Interface
(4 output; 1 income)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication with IEC 61850
– The communication standard for the station bus based on Ethernet
– Max. Number of connected devices 128
– We recommend the use of Ethernet components from Ruggedcom
http://www.ruggedcom.com

TP
62,5µ or 50µ Fibre
100 Mbit/s redundant switched Ethernet ring
Bay cubicle
No redundancy,
Cost-optimized

TP TP
TP
Cu Twisted Pair (TP)
Shielded cable
max. 20m

Small medium voltage switchgears

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 14

TP=Twisted Pair

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication with IEC 61850
9 RUGGEDCOM Ethernet-Switch, complies with IEC61850 requirements
9 Rail mounting
9 Output relay
9 Fan free operation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication with IEC 61850

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication with IEC 61850 2x FO- ports (MTRJ)
14x RJ45-ports

No redundancy
Cost-optimized

Cu Shielded Pair
max. 20m

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Communication with IEC 61850

9 Ethernet-
Switch,
complies with
IEC61850
requirements
9 Redundant
power supply
9 Output relay
9 Fan free
operation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Time Synchronisation
Siemens SICLOCK
A separate time master can be used especially in configuration
with the Ethernet station bus (IEC 61850) via SNTP-Server
(Simple Network Time Protocol).
– It synchronizes all connected devices
(SNTP-Clients), incl. the Station Unit. Station Unit
is the time master for all connected devices.

antenna Station Unit

SICAM
PAS CC
Meinberg
(Time-) SNTP Time master
Master clock -Client /-server
SNTP-Server
by Meinberg
or Siclock
IEC 61850
Ethnernet (TCP/IP) T103
T101
Profibus FMS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Modems
Insys Modem for ISDN and GSM
IEC 60870-5-101 supports the
– Dial-up traffic
– IAWD
– ISDN
– GSM
– Analog
– Operating modes
– Unbalanced ( Ù Use of SICAM miniRTU)
– Balanced

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System components
PTD-SE-A0/ 20

20
SICAM PAS
Software Setup

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting Setup.exe

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Software Setup
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Setup

Select setup language

SICAM PAS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Software Setup
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Running Software Installation

Everything is already
checked by default Operation language

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Software Setup
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Setup dialog boxes

Demo or licensed

Full Server or DIP

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Software Setup
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Setup dialog boxes

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Software Setup
PTD-SE-A0/ 6

6
SICAM PAS
Starting Parameterisations

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Our desired configuration

PAS Server
SICAM eRTU

IEC 101

COM-Port1=>T101 Master interface

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening the Feature Enabler

The Feature Enabler enables the


applications we wish to use in our project

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Feature Enabler

These features are nearly always necessary !

Distributed System
Infrastructure
(Data Router)

To configure a PAS System

To use automation
functions (CFC)
All other applications are communication tasks
and depend on the desired communication interfaces

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Installing applications

To install the features we must


enter a password.
A unique password list is
provided together with the PAS
dongle.

Installation just takes a few


seconds each.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening the Parameterization Tool

UI-Configuration is the parameterization


tool for SICAM PAS system. All the
information to be processed and all the
communication interfaces have to be
defined here.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration Window

The tree view The Properties


The current function
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration Window

The entered name


appears in the tree
The parameter settings A short description
view
for each parameter
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 8

PAS ID is the identification address for remote WinCC

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration Window

The whole window for the configuration tree...


or
...a properties pane inside

A needle pin to fix the properties pane

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating a Full Server Computer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Computer Settings

The IP-Address is entered automatically.

The available COM ports are entered after


pressing Search.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating an IEC101-Master to connect an eRTU

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating an interface

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

IEC 101 Parameters

The first free COM-port is automatically entered


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

If COM ports were not defined...

If the COM ports were not defined before (refer to page 10), the
parameter appeared in red colour.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Importing a file

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Importing a file

After a verification, which is


reported, another selection
window occurs to select the
desired interface

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Getting an XML-File from SICAM plusTOOLS

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Exporting data

The export is logged in a report window.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating a General Interrogation List

Rename list

Important to interrogate the eRTU


substation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Mapping shows the Information Volume

The imported
information
appears under
Mapping

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Selecting desired messages

Ticking the USE means to make a message available for further processing,
i.e. to send to an HMI-system, to send to a telecontrol center, to process in
logic functions etc.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 22

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How to select a group of messages

To select a whole column, click once on the headline, then move the cursor
into the selected area and click right to obtain the yes-no-menu
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Enable the General Interrogation

Minimum one message must be assigned to the GI-List for a standard GI.

More than one message means, to enable a completeness check Æ all ticked
messages have to be received during a GI.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 24

What is a General Interrogation ?


A GI consists of a GI-command sent down from the higher level system (in our example the
PAS system) to the lower level RTU (in our example the eRTU) and a GI-response from the
lower level system.
The response from the eRTU mainly contains a process image of the switchgear.

24
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Were to structure information

Topology allows us to
create certain
information levels to
structure information.
The topological levels´
names together with
the information name is
the text used in the HMI
system.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 25

25
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How to create your own levels

The topology partly defines the text string for the HMI system
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 26

26
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

All information is still located in the top level

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 27

27
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Using filter functions

To display the messages belonging to the eRTU, use the filter


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Starting Parameterisations
PTD-SE-A0/ 28

28
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Sorting information

Double click the headline of a column to sort according names:


All messages beginning with _ are at the top now

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 29

29
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Marking information

Select the first line of the desired group, keep the shift-button pressed while
(scrolling down and) selecting the last line.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 30

30
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Moving information

...and move it to the desired level

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 31

31
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Disable filter

...do not forget to disable the filter, to display everything again

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 32

32
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Remaining messages in the top level

These are all “Status Messages” (System internal messages)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 33

33
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

No saving necessary

This finishes the first part of the parameterization.


There is no save-function, because all the entries are
directly written into the data base.

The configured PAS system should now be able to run.

If we connected the eRTU the communication should


work.

The next topic will show, how we can test our new
configuration.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Starting Parameterisations
PTD-SE-A0/ 34

34
SICAM PAS
UI-Operation

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting UI-Operation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

UI-Operation Window

The Operation
window displays all
the components we
defined in UI-
Configuration, but this
is an online-view

The connection to DSI is not yet running


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
UI-Operation
PTD-SE-A0/ 3

DSI = Distributed System Infrastructure (Data Router)

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Updating the System

For the first time


we have to update
the system to get it
run

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

The Update Buttons

If new applications were inserted,


to update and to restart runtime system

If an additional component was added

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

The Tree View

eRTU is not valid


Interface is not valid
101-Master is in STOP
Full Server is running

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Operation functions

Each level shows the current state and can manually be started or stopped

The IED level additionally contains buttons for Bay-Blocking and Telecontrol-Blocking

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Operation functions

With the context menu we also can start or stop including all the sublevels

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting the 101-Master

After starting all, the master


turns to Pending-Up state
which means it is trying to
start, but did not yet succeed.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Startup completed

After a few seconds all the levels have started and are running now
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
UI-Operation
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Important Notes

The runtime system is independent from the


UI-Operation Tool

I.e. even if you close UI-Operation, PAS system


keeps running

Even after shutting down and restarting the


computer, the runtime will automatically start

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Fault Diagnosis

How can I check, whether the


runtime components are working ?

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening Administrative Tools

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening Local Services Window

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

PAS Services

1)

2)
3)
3)
2)

1) The most important service (Database service)


2) DSI Server and Central Driver must always run
3) Configured communication applications

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


UI-Operation
PTD-SE-A0/ 15

15
SICAM PAS
Value Viewer

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

What does a Value Viewer do?

The Value Viewer displays information components online in form of a table

•Every line represents an information point, e.g. SP, DP, ME_FL, IT...
•Various components are displayed in columns, e.g. Value, Cause, Validity

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 2

SP= Single Point Indication


DP= Double Point Indication
ME_FL= Measured Value-Float
IT= Integreated Total (counter value)

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening the Value Viewer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

List of all Information

The selection of the top level displays all information in the substation
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Value Viewer
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Important columns

Time Stamp: Time of last aquisition


Time Stamp Status: Valid=Time from PAS, TrueTime=Time from processing device
Value Path: Path from Configuration (not from Topology)
Value: Current value (on, off, raised, cleared...)
Initiator Category: Source of information (Local, remote, automatic...)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Value Viewer
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Important columns

Cause of Transmission: Reason, why message appeared


Validity: Message can be invalid, if device was faulty or switched off
Additional cause: i.e. interlocking, switching current check, control authority violation,
set=actual, chatter blocking, upper or lowwer limit,...

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Important columns

COV Counter: not supported any more


Identification Number: Fault record number
Supplementary Information: Relative time for protection messages
Block State: Indicates Bay Blocking or Telecontrol Blocking

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

The properties of a message

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Properties page in detail

Here we can watch or modify


information:

Entering a 1, we initialize a change


from raised to cleared
To activate simulation, click on
Transmit

As this message is originally a binary


input, it will change back after a
while due to the cyclic interrogation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Control function

We can also control commands:

After selecting a command, we can


enter the control value.

Control must be checked.

Transmit now executes the


command

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Testing data

With the Value Viewer we have got a tool, that allows us


to to test all information without using an HMI system or
telecontrol interface.

We even could simulate certain messages or values, which


usually may not appear.

The control function allows us to control any command.

Be careful with the Value Viewer on a hot substation !!

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Value Viewer
PTD-SE-A0/ 11

11
IEC60870-5-101
Slave Interface

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Entering the necessary objects

The interface is automatically assigned


to COM2.
All the objects have their default
settings which could be modified in the
properties page.
The List object is important, as this
means the General Interrogation List.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Mapping

Select Control Center


Mark the whole List-column
Select Yes for all
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
IEC 60870-5-101 Slave
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Entering Telegram Addresses

Mark the Telegram Address column


Select Automatic Value Input
Enter a start value for calculation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Commands have to be defined as well

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Change to UI-Operation

The View has to be updated now

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting up the 101-Slave

After Starting the IEC101-Slave including the sublevels, the slave changes into
Pending Up mode.
As no Control Center is connected, the communication will not yet run.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Our current configuration

PAS Server Control Center

SIPROTEC

IEC 103 IEC 101

Instead of a real Control Center


we are going to use IECTEST

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


IEC 60870-5-101 Slave
PTD-SE-A0/ 8

8
The SICAM Station Unit
for Commissioning Engineers
The year of Profitable Growth

Global network of innovation

1
Power Transmission and Distribution

Power Automation
Progress. It‘s that simple.

Welcome to our SICAM


Station Unit Training!
HelmuthHitzeroth
Helmuth Hitzeroth
SiemensAG,
Siemens AG,PTD
PTDEA
EA22
Product Management
Product Management
PowerAutomation
Power Automationand
andTelecontrol
TelecontrolSystems
Systems
Phone +49
Phone +49911
911/ /433-7085
433-7085
Email:helmuth.hitzeroth@siemens.com
Email: helmuth.hitzeroth@siemens.com

Energy Automation Dr. H. Hitzeroth 10.2004 2

2
Power Transmission and Distribution

Introduction
Power Automation
Progress. It‘s that simple.

„Introduction
„Introduction „BIOS Settings
„BIOS Settings
„Hardware
„ Hardware
„Harddisk „ Harddisk
„WXPE
„EWF „ WXPE
„Delivery State
„Commissioning
„ EWF
„Trouble Shooting „ Delivery State
„ Commissioning
„ Trouble Shooting

Energy Automation Dr. H. Hitzeroth 10.2004 3

3
Power Transmission and Distribution

BIOS Settings
Power Automation
Progress. It‘s that simple.

BIOS:
„Introduction
„BIOS Settings
„Hardware Standard CMOS Features Frequency/Voltage Control
„Harddisk
Advanced BIOS Features Load Fail-Safe Defaults
„WXPE
„EWF Advanced Chipset Features Load Optimized Defaults
„Delivery State
Integrated Peripherals Set Supervisor Password
„Commissioning
„Trouble Shooting IMC Miscellaneous Set User Password
Power Management Save and Exit Setup
PNP/PCI Configurations Exit Without Saving
PC Health Status

Energy Automation Dr. H. Hitzeroth 10.2004 4

4
Power Transmission and Distribution

BIOS Setup
Power Automation
Progress. It‘s that simple.

Standard CMOS Setup:


„Introduction Date & Time: Set these
„BIOS Settings
„Hardware
Advanced BIOS Features:
„Harddisk First Boot Device: CDROM
„WXPE
„EWF Second Boot Device: USB-CDROM
„Delivery State
„Commissioning
Third Boot Device: USB-ZIP
„Trouble Shooting Award Pre Boot Agent: Disable
Integrated Peripherals:
On-Chip Secondary PCI DIE: Enable
USB Controller: Enable
USB Keyboard Support: Enable
USB Mouse Support: Enable

Energy Automation Dr. H. Hitzeroth 10.2004 5

5
Power Transmission and Distribution

BIOS Setup
Power Automation
Progress. It‘s that simple.

IMC Miscellaneous:
„Introduction SMP 16-Bus: Disable
„BIOS Settings
„Hardware
PNP/PCI Configuration:
„Harddisk Assign IRQ for USB: Enable
„WXPE
„EWF PC Health Status:
„Delivery State
„Commissioning
Throttling Temperature: 110°C/230°F
„Trouble Shooting

Several other features can be used for trouble shooting e.g.:


Video: Graphics card
Halt On: Pause upon error
And others

Energy Automation Dr. H. Hitzeroth 10.2004 6

6
Power Transmission and Distribution

Hardware
Power Automation
Progress. It‘s that simple.

The Station Unit Comprises:


„Introduction
„BIOS Settings „19’’rack system
„Hardware
„IndustrialMicrocomputer
„Harddisk
„Low Voltage Pentium III, 933 MHZ
„WXPE
„EWF
„320 MByte SDRAM PC 133 MHz

„Delivery State „1 MByte-Flash-EPROM


„Commissioning „512 kByte BIOS
„Trouble Shooting „512 kByte User-System (reserve, for own applications, not used by PAS)
„On Board Graphics: 1280 x 1024 / 16,7 Million Colours (DB15f)
„10 Status LEDs (Run, Watchdog, preset Harddisk & LAN, 4 unconfigured)
„Interfaces: 2xRS232 (DB9m), 2xUSB, 1xPS/serial-Mouse/Keyboard, LAN: 10/100 (RJ45)
„1 GByte SILICON Flash Disk (old model with H new with J)
„Safety functions: HW-Watchdog, Temperature / Voltage monitoring of CPU
„Fanless Operation, without Moving Components

Energy Automation Dr. H. Hitzeroth 10.2004 7

7
Power Transmission and Distribution

Harddisk
Power Automation
Progress. It‘s that simple.

1 GB Flash Drive (non moveable)


„ Sufficiently long life time, even increased with use of EWF
„Introduction „ Write access time a little longer
„BIOS Settings
„Hardware
„Harddisk
„WXPE
Three Partitions:
„EWF „ NTFS: „WXPE“
„Delivery State „ Active Primary Partition
„Commissioning „ Currently: 500 MB, later: 600 MB
„Trouble Shooting „ C:
„ NTFS: „ProDat“
„ Primary Partition
„ Currently: 470 MB, later 370 MB
„ D:
„ EWF (EWF Configuration Information)
„ Hidden
„ Approximately 30 MB unallocated space
„ Used for the EWF

Energy Automation Dr. H. Hitzeroth 10.2004 8

8
Power Transmission and Distribution

Windows XP Embedded
Power Automation
Progress. It‘s that simple.

„Introduction
„BIOS Settings
„Hardware
„Harddisk
„WXPE
„EWF
„Delivery State
„Commissioning What is Windows XP Embedded?
„Trouble Shooting

Energy Automation Dr. H. Hitzeroth 10.2004 9

9
Power Transmission and Distribution

What is Windows XP Embedded?


Power Automation
Progress. It‘s that simple.

A member of Windows XP family


Launched in November, 2002

Componentised version of Windows XP Pro


Unmodified XP Pro binaries
Only required components
Minimal Dependancies
Flexible build of reduced-footprint designs
WXP Prof. ~ 1000 MByte

WXP Emb. for PAS ~ 150-200 MByte


or DIGSI
Energy Automation Dr. H. Hitzeroth 10.2004 10

10
Power Transmission and Distribution

Benefits
Power Automation
Progress. It‘s that simple.
Enhanced Performance
Specially tailored reduced operating system for SICAM
PAS
Accelerated boot and shut down process
XP Professional XP Embedded improvement
Boot ~ 30 sec ~ 24 sec 25%
Shut Down ~28 sec ~ 7 sec 400%

Better Reliability
Robust operating system
Allows a closed-case design, limiting the ability for end-
users to add/subtract/modify the operating system or
application
Higher Security
Most threats / viruses do not run or can not be installed
Energy Automation Dr. H. Hitzeroth 10.2004 11

11
Power Transmission and Distribution

SCIAM PAS - EWF Architecture


Power Automation
Progress. It‘s that simple.

Read/write

Enhanced write filter


Read /
After commissioning
commissioning system
system
write
After
can be
can be frozen
frozen
System partition
System partition is
is read
read only
only Æ Æ Read
fully write
fully write protected
protected
System can
System can be
be switched
switched off off //
reset at
reset at any
any time
time
RAM Overlay D:
Reduced write
Reduced write cycles
cycles toto Flash
Flash
disk
disk
1 GByte Flash disk RAM Overlay C:

Energy Automation Dr. H. Hitzeroth 10.2004 12

12
Power Transmission and Distribution

Enhanced Write Filter


Power Automation
Progress. It‘s that simple.
Protect SICAM PAS Station Unit System Overlay 3
Files
Non-persistent
Overlay 2
Redirects disk writes
to memory
Use of overlays Overlay 1
Allow multiple levels of protection
and “undo”
Multiple volume support Original Disk
Contents

Energy Automation Dr. H. Hitzeroth 10.2004 13

13
Power Transmission and Distribution

SICAM PAS Station Unit


Power Automation
Progress. It‘s that simple.

Energy Automation Dr. H. Hitzeroth 10.2004 14

14
Power Transmission and Distribution

EWF Manager Console


Only available to Administrator
Power Automation EWFMGR Æ
EWFMGR Æ starts
starts console
console
Progress. It‘s that simple. State of
of protected
protected volume
volume
This is the delivery state State
Pending boot
Pending boot command
command

Energy Automation Dr. H. Hitzeroth 10.2004 15

15
Power Transmission and Distribution

EWF Manager Console


Enable after commissioning EWFMGR d: d: -enable
-enable
EWFMGR
Power Automation Æ enable
enable write
write protection
protection
Æ
Progress. It‘s that simple.
after commissioning
after commissioning
Active after
Active after reboot
reboot

Energy Automation Dr. H. Hitzeroth 10.2004 16

16
Power Transmission and Distribution

EWF Manager Console


Commit after changes
Power Automation EWFMGR d:
EWFMGR d: -commit
-commit
Progress. It‘s that simple. Æ commit
Æ commit allall changes
changes made
made until
until
reboot
reboot
Active after
Active after reboot
reboot

Energy Automation Dr. H. Hitzeroth 10.2004 17

17
Power Transmission and Distribution

EWF Manager Console


Disable before installing new components
Power Automation EWFMGR d:
EWFMGR d: -disable
-disable
Progress. It‘s that simple. Æ disable
Æ disable EWF
EWF after
after
reboot
reboot

Energy Automation Dr. H. Hitzeroth 10.2004 18

18
Power Transmission and Distribution

Strength of using Standard HW & SW


in Substation Automation SystemsI
Power Automation
Progress. It‘s that simple. Very open platform based on a standard
Windows system

Easy Substation Integration


Î Utilities & OEM companies can develop IED drivers &
automation applications

User Interface (UI) and remote access capability are


integrated part of the OS
Î Remote Desktop, Internet Information Server, Web
Services, etc.

Support of remote access to IEDs for test & diagnostics


and configuration & setting, e.g. DIGSI

Energy Automation Dr. H. Hitzeroth 10.2004 19

19
Power Transmission and Distribution

Strength of using Standard HW & SW in Substation


Automation SystemsII
Power Automation
Progress. It‘s that simple. Open interfaces to the built in substation
database (OPC & ODBC)

Automatic download of fault records and


historical data from protection devices / IEDs
Î Storage on the substation database

Use of standard components based on PC


technology
Î users are familiar, i.e. reduced training effort

Configuration with built in operation mode is


very user friendly

Energy Automation Dr. H. Hitzeroth 10.2004 20

20
Power Transmission and Distribution

Comparison of Standard HW & SW with SICAM PAS I


Power Automation
Progress. It‘s that simple.

Standard HW / SW (Windows XP) SICAM PAS enhanced Solution

Standard PCs are more sensitive to surge SICAM PAS uses SIEMENS Industrial PCs
effects (IPC) compliant with highest industrial
standards

Low reliability of PC, e.g. hard disk failures SICAM PAS uses IPC & flash memory
no watchdog drives, i.e. no moving parts such as hard
disks or fans
SIEMENS IPC has a built in watchdog
Lower reliability of Windows based SICAM PAS can run under Windows XP
systems Embedded (WXPE) OS, i.e. the OS is
specially tailored for the SA application
Power Supply failure w/o proper shut SICAM PAS Station uses the enhanced
down can lead system to hang, i.e. no write filter technology to protect system
automatic unattended reboot partition
PC / Windows system: Danger of viruses SICAM PAS uses WXPE OS, i.e. the OS is
specially tailored for improved virus
protection

Energy Automation Dr. H. Hitzeroth 10.2004 21

21
Power Transmission and Distribution

Comparison of Standard HW & SW with SICAM PAS II


Power Automation
Progress. It‘s that simple.

Standard HW / SW (Windows XP) SICAM PAS enhanced Solution

DC – AC converter is required to power SICAM PAS uses SIEMENS IPC with a DC


the PC from the station battery Power Supply

Standard PCs have reduced temperature SICAM PAS uses IPC with higher
range temperature range Æ up to 75° C
environment temperature w/o fan

Standard PCs are leading users to "play" SICAM Station Unit has no floppy & CD
with the systems Rom drive
SICAM Station Unit runs Windows XP
Embedded (WXPE) OS, i.e. the OS is
specially tailored for the SA application
Î no games, multimedia etc.
Standard PCs are leading users to "play" SICAM PAS Station Unit guarantees up to
with the systems 10 years spare parts availability
ÎIt is very difficult to get spare parts due
to fast developments in IT

Energy Automation Dr. H. Hitzeroth 10.2004 22

22
Power Transmission and Distribution

SICAM PAS a scalable system:


Hardware - architecture: SICAM PAS Station Unit
Power Automation
Progress. It‘s that simple.
SICAM PAS Station Unit 9 Fanless operation
9 No rotating hard disk
=> silicon flash disk
9 Secure operation with
high availability (>25 years MTBF)
9 Windows XP embedded OS
9 Watchdog, temperature supervision
9 Separate SICAM PAS CC hardware
9 SICAM PAS Software preinstalled

Energy Automation Dr. H. Hitzeroth 10.2004 23

23
Power Transmission and Distribution

SICAM PAS
SICAM PAS Station Unit – Order number
Power Automation SICAM ENERGY AUTOMATION
Progress. It‘s that simple. SICAM PAS Station Unit
Product description
SICAM PAS Station Unit based on Industrial Microcomputer
19" housing
950 MHZ Pentium III CPU 320 Mbyte Ram
1 Mbyte -Flash-EPROM
10 LEDs , VGA, LAN 10/100, 2 x USB, 2x COM, keyboard-mouse (shared)
fan less, without moving components
SICAM PAS Software preinstalled

L G F

Base price 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Order-Number 6 M D 9 1 0 0 - 0 - 0 A A 0
| | | | |
| | | | |
Power Supply 8 | | | |
DC 24V 3 | | | |
AC 110 - 230V 7 | | | |
Configuration / Operating System 9 | | |
Flash disk 1 GB / Windows XP embedded A | | |
Language of Operating System and SICAM PAS 10 | |
German A | |
English B | |
PCI-Bridge 11 |
without 0 |
included (empty) 1 |
Function 12
Full Server 0
Device Interface Processor (DIP) 1
Energy Automation Dr. H. Hitzeroth 10.2004 24

24
Power Transmission and Distribution

Delivery State
Power Automation
Progress. It‘s that simple.

Preinstalled with:
Operating System
Tweak Tools
Acrobat Reader
Simatic Net (Authors W, Simatic Net PC) (on D:)
PAS FS / DIP D / E (on D:)

Operating System has been configured e.g.:


Users: Siemens (ptdptd) / Customer (customer) /
SICAM-Administrator (pas)
autologon for user siemens
show / hide files for different users
resolution: 1024X768
refresh rate: 60 Hz
remote desktop
Etc.

only the user siemens has rights to the file: ewfmgr.exe

Energy Automation Dr. H. Hitzeroth 10.2004 25

25
Power Transmission and Distribution

Comissioning
Power Automation
Progress. It‘s that simple.

The HOPF card can be plugged if required. HOPF card needs


to be configured.

The Profibus FMS card can be plugged. Software previously


installed.

Load the PAS Database into the PAS on to the Station Unit.

Use the EWF Manager to commit the changes.

Energy Automation Dr. H. Hitzeroth 10.2004 26

26
Power Transmission and Distribution

Trouble Shooting
Power Automation
Progress. It‘s that simple.

Disable the ewf if several changes need to be done (eg.


configurations, installation of additional software).

A recovery CD with the appropriate image can be obtained.

To install the image:


Boot the Station Unit with DOS (Windows 98).
Connect your laptop to the Station Unit by Ethernet.
Copy the image on to the laptop.
Use net use to map the image directory of the laptop.
Use sdimgr <filename.sdi> /writedisk:0 /yes to copy the image.

Energy Automation Dr. H. Hitzeroth 10.2004 27

27
Power Transmission and Distribution

Power Automation
Progress. It‘s that simple.

Energy Automation Dr. H. Hitzeroth 10.2004 28

28
IEC60870-5-103
via Siemens Serial
Hub 7XV5655

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Our desired configuration

PAS Server
SIPROTEC

IEC 103 IEC 103


electrical via
or optical Ethernet

Serial Hub
7XV5655
Mini Bay Unit
6MB525

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How to configure the Serial Hub

• With a Serial Hub (or Serial Modem) we get an


Installation-CD

• The configuration software as well as the firmware


has to be installed on our computer

• The hub must be connected to the network via


ethernet

• Opening the configuration tool „ipether“ displays the


connected hub for configuration settings

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting software setup

Select „Accessories“ and


then „7XV5655“
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

The necessary software

The Configuration Tool has always to be installed to be able to do the settings on the
hub.
The firmware is usually not necessary, as it should be already installed on the hub by
the factory.
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Downloading files

After downloading
we get these
packed files

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Extracting files

After extracting files

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Installing Configuration Tool

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Installation supported by a Wizard

After some dialog boxes the installation


has finished.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting Configuration tool

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration

After short time the existing hub appears

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configure name

The name should be set to make it easier to identify the hub, if there were several

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configure IP-address

The IP address must be entered according to the computer´s network

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configure properties

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configure COM port

Assign a COM port..................................and enable RS485 half duplex

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Diagnostic

Settings are immiadeately active.


Hub is available in the network.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

PAS Configuration

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration

The new COM port has been found

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating an IEC103-Master for IEDs

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating an interface

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Communication Parameters

The next free COM-port is automatically entered


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating a device

A device can either be defined by


using a template or by import function

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 22

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Importing a Device File

To be able to import a device, a


special device file must exist

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Getting a DBF-File from DIGSI


DIGSI is able to
generate certain
device files.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 24

24
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Importing a Device File

The import is
logged in a
report
window.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 25

25
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Device Parameters

Some general device


parameters have to
be entered manually

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 26

26
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Mapping shows the Information Volume

The imported
information
appears under
Mapping

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – T103 via Serial Hub
PTD-SE-A0/ 27

27
SICAM PAS
HMI-Interface

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating an HMI Interface

We have to create 3 levels


• a PAS CC
• an Interface
• a Control Center (Local Operator
Station)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


HMI Interface
PTD-SE-A0/ 2

Do not mix up a Local Operator Station with a Remote Control Center

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Routing to HMI

Do not mix up
the 2 Control
centers !

Everything, that has to be displayed or


logged in PAS CC, has to be checked
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
HMI Interface
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Export of HMI information

Explaination follows
on next pages

A *.PXD file is created, which has to be imported into WinCC later.


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
HMI Interface
PTD-SE-A0/ 4

Explaination:
If there was any change in Topology, the texts for WinCC also changes.

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Explaination

Text due to the defined topolgy These text strings are usually just copies

In case of a modification, either of the copies or of the topology,


the topological text string and the „WinCC-text-Strings“ would be different.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


HMI Interface
PTD-SE-A0/ 5

Explaination:
If there was any change in Topology, the texts for WinCC also changes.

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Explaination

The question now means, if there was a difference between those text strings, a „YES“
changes the „WinCC-Texts“ according to the topological text strings,
a „NO“ keeps the differences.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


HMI Interface
PTD-SE-A0/ 6

Explaination:
If there was any change in Topology, the texts for WinCC also changes.

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Our future configuration

PAS Server
and HMI-System

WinCC Control Center


SIPROTEC

IEC 103 IEC 101

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


HMI Interface
PTD-SE-A0/ 7

7
SICAM PAS
System Variables

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

System Variables

Each communication object has got a some system variables

_Adm = control information Æ 1= enable communication with device, 0= stop communication with device

_Opr = monitoring information Æ 1= communication with device running, 0= communication with device stopped

_BlkAdm = control information for Bay Blocking and Telecontrol Blocking Æ 131072=block bay level
Æ 196608=block teletransmission
Æ 262144=block both
Æ 65536=disable blockings

_BlkOptr = monitoring information for Bay Blocking and Telecontrol Blocking Æ 131072=Bay blocked
Æ 196608=Teletransmission blocked
Æ 262144=both blocked
Æ 65536=no blockings
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
System Variables
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Diagnosis with Operation Tool and Value Viewer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System Variables
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Stopping the device with the STOP button

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System Variables
PTD-SE-A0/ 4

After stopping the communication the following actions happen:


•Stop button disabled (turns to grey)
•Start button enabled
•Stop symbol appears for the current state
•Stop symbol appears in the tree view
•The value viewer indicates 0 for _Opr and _Adm

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Bay Blocking

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System Variables
PTD-SE-A0/ 5

A padlock appears at the running symbol

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Blocking functions via Value Viewer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System Variables
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Blocking functions via Value Viewer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


System Variables
PTD-SE-A0/ 7

7
SICAM PAS
Switching Authority

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Switching Authority Group


Every control interface has got a parameter called „Switching Authority Group Assignment“

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Matrix

The one we are defining, is the white line, while all othter interfaces
are grey coloured.
You can assign only your interface in the white line.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Alarm logging entry

Under „Mapping“ in „Monitoring Direction“ in the tab „Status“, we find a message


„AuthorityValue“ (Type SP).
This is the one to log in an event list.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Control Authority Tag


In WinCC automatically creates a tag group „SicamAdmin_xxx, inside a tag
„AuthVID_xxx“. This is the one to control and display.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM symbol library

In the library we find 2 templates to control the switching authority.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Simple symbol

The simple one has a disadvantage:


On the first startup of PAS, the tag „AuthVID_xxx“
has no valid value, i.e. the switching authority is
neiter local nor remote.
Pressing the button does not even change the
authority value.

The text in runtime


is „local“ or „remote“

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Advanced symbol

...is made for testing reasons. It can


read and write authority settings.
After first startup of PAS it can set
the authority value.

The button
disappears, when
a checkbox was
ticked and written

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Switching Authority
PTD-SE-A0/ 8

8
SICAM PAS CC
Remote WinCC

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

What does Remote WinCC mean?

„Remote WinCC“ means PAS CC and Full


Server on two different computers

SICAM PAS CC

Station Bus TCP/IP

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Settings in UI-Configuration

We have to configure a DIP with a subleveled HMI (although there is no real DIP)
Select the computer name of the HMI computer
The IP-address of the HMI computer appears then automatically

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

WinCC Explorer

Open PAS Data Server properties

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Properties windows

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Connection properties

Enter IP-address of Full Server

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

The rest has to be configured as usual !

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Remote WinCC
PTD-SE-A0/ 7

7
SICAM PAS
OPC Communication

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
What is OPC ?
OPC
• stands for OLE (Object Linking and Embedding) for Process Control
• is the automation industry‘s version of OLE
• provides an open, flexible, plug-and-play software standard for software
interoperability in the automation industry
• specific to the automation industry and its' unique needs for data
communication (alarming, historical data access and trending, batch and
more)

OPC Foundation with now more than 220 companies, an independent


organization, is responsible for the specification.
www.opcfoundation.org

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
What is OPC ?
OPC
• is based on OLE, COM (component object model) and DCOM
(distributed component object model) technologies
• consists of a standard set of interfaces, properties and methods
for use in process- control and manufacturing automation
application

OPC will bring the same benefits to


industrial hardware and software that
standard printer drivers brought to word-
processing.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Why OPC ?
• Openness
– System-wide operation between automation products of different
manufacturers
– Data are only acquired once from field level right up to operational control
level
– Access to MS-Office under Windows
• Ease of Use
– Same user interface for different components
• Performance
– C++ interface
– Efficient data access through volume operations
– Requirement-oriented client-server communication
• Connectability
– Can be reached by any computer in the LAN/WAN (via COM/DCOM)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
OPC Communication
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
How does OPC work ?
• OPC Client
OPC – Initiates OPC communications
Client
– Read/write requests
• OPC
OPC
– Communications based on COM/DCOM
– Data: single or in groups

OPC
• OPC Server
Server
– Executes client requests
– Cyclically/change-driven
– Makes own data available

Note: SICAM PAS supports OPC server and OPC Client


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
OPC Communication
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Overview of OPC data flow
Network
Network
From any server
PAS CC To any client

HMI system

PAS OPC-Client OPC-Server

Routing

Substation
IEC101-Master
Controller
IEC101-slave

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
How to configure an OPC server – COM/DCOM-Service

dcomcnfg

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 7

COM=component object model


DCOM=distributed component object model

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server – COM/DCOM - General properties

Select „NONE“

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 8

COM=component object model


DCOM=distributed component object model

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server – Location and Security
No modification required

=default

=default

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server - Security

In all 3 categories we must release user access rights.


This can be done user related as well!

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server – Identity and Endpoints No modification required

=default

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server Æ UI-Configuration

Have to be entered

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 12

For OPC server we have not to use the feature enabler, because it is a free standard function in
PAS.

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server Æ Mapping

Enable
information,
which has to
be available
for OPC
clients

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC server Æ UI-Operation

Update configuration

Start OPC Server

Data is now ready for


being polled by a client

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 14

OPC Server remains in „Pending Up“ until the OPC client accesses

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client
Enter OPC client and
interface.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Selecting an OPC server
Select the Computer Name parameter and hit the browser button to select a OPC
server computer.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Selecting an OPC server

Open your network, select the desired computer name, and mark the OPC server
object.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Selecting an OPC server

Computer
name and
OPC server
are now
entered.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Entering a Device
Enter a device now and browse for the desired variables.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Variables supplied by a server

Browse to the level that display your desired


information and map it.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Templates
The new OPC device appears as a Template

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Correct protocol information types

The protocol
information types have
to be corrected
manually, because
they all appear as SP.

Command-Feedback ...either here or here


assignment

Commands always
appear as SC and they
remain as such !
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
OPC Communication
PTD-SE-A0/ 22

OPC does not support exchange of PAS information types. That´s why we must correct them
manually.

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client – Mapping

With the USE


information is made
available for all the
routing, e.g. it can be
routed to WinCC

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
OPC client Æ UI-Operation

Update configuration

Start OPC-Client

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


OPC Communication
PTD-SE-A0/ 24

It takes a while (about 1 min) until the OPC client has accessed the server.
While the client is pending up, the server already turns to RUN.

24
SICAM PAS
CFC Logic Function

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuring a CFC Logic Function

information from CFC,


e.g. a group message,
or a derived command
information into CFC
to be processed there,
e.g. alarm indications

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Information from/to CFC

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Grouping of information

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuration Tree finished

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Information to CFC

Just check these

These automatically appear

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Information from CFC...

....is already connected to a PLC Master Device which is a Device Template

To configure the PLC Master Device we have to open Templates

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Template PLC Master Device

Here we find one piece of information of every type.


To keep existing information, we duplicate the desired type, which has to serve
as a grouped message.

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Duplicating information

As information has to
be unique, we have
to rename our new
message.

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Information from CFC

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Opening CFC Editor

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Creating a new CFC file

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Inserting a CFC block

Choose type

Position block

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Enter information group


1.The new block appears

2.Double click border column

3.Select desired group

4.The group name appears

M=Master
S=Slave
G=Group

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 14

M= Master Æ message created from CFC


S= Slave Æ message accessing CFC to trigger any logic (source information)
G= Group Æ defined group of messages for grouping information

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Connecting block and group

Select input and group name, than click


insert connection

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Connecting Group Alarm Message

M=Master
S=Slave
G=Group

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 16

M= Master Æ message created from CFC


S= Slave Æ message accessing CFC to trigger any logic
G= Group Æ defined group of messages for grouping information

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Linking to Active Resource

The new Logic function has to appear as a resource as well !

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Compilation

Compilation finished

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Feature Enabler – Enable SoftPLC

Soft PLC is the application for logic functions

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 19

SoftPLC = Software simulated PLC (Programmable Logic Controller)

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

UI-Operation – Update system/view and start


automation

We must start all


the automation
tree

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Run Sequence

1st
The width of a chart
is just one page, but
the length is
endless.
The Run Sequence
depends of the
position of a block.
System starts
always at the left
last hand side top of the
1st page, goes
down to the bottom
of the last page,
and then to the top
of the next column.

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

CFC Diagnostics

Open the desired file and select Resources...

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 22

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

CFC Diagnostics

Start Online mode...

...and double click file name...

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Online View

Online values

Displays cyclic update


Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
CFC Logic Function
PTD-SE-A0/ 24

24
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

CFC Diagnostics

Here we can modify values online

Copyright © SIEMENS AG PTD SE 2002. All rights reserved.


CFC Logic Function
PTD-SE-A0/ 25

25
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Training

SICAM PAS automation


with the programming language ST

Page 1
SICAM PAS automation with ST, 16.06.04 Nürnberg

1
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Structure:

Overview
 Basics IEC 61131

 Basics structured text (ST)

 Instructions in ST

 How to write your own function blocks

 Practical example SICAM PAS

 Combination of ST and CFC

 Summary

Page 2
SICAM PAS automation with ST, 16.06.04 Nürnberg

2
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What is IEC 61131 ?

IEC61131 z International Standard for programming of


programmable logic controllers (PLC)
z Part 3 of the standard defines usable
programming languages:
– Instruction list (IL)
– Structured text (ST)
– Functional block language (CFC)
– Ladder diagram (LL)
– Sequential function chart (SFC)
z Further Standard parts define general information about
PLCs, requirements on equipment and tests, guidelines for
users, communication

Page 3
SICAM PAS automation with ST, 16.06.04 Nürnberg

3
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Basics IEC 61131-3

IEC61131 z There are 3 „components“ for programming, the so-called


POEs (program organisation unit):
– Program (PROG)
– Function Block (FB)
– Function (FUN)
z Each POE is structured into a declaration part and in a source
code part
z All variables are defined in the declaration part (internal,
external, I/O variables)
z The actual programming code is in the source code part,
where the declared variables can be used
->declaration is necessary for all variables !

Page 4
SICAM PAS automation with ST, 16.06.04 Nürnberg

4
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What are programs ?

IEC61131 z Main program (multiple main programs


are possible)

z top level execution unit in a PLC

z for example a CFC chart or


a ST program

z Starts with the keyword PROGRAM


and ends with END_PROGRAM
(These are not directly visible in SICAM PAS,
is internally managed by the Editor)

z Be careful with re-naming of programs !

Page 5
SICAM PAS automation with ST, 16.06.04 Nürnberg

5
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What are functions ?

IEC61131 z Functions are subroutines

z They will be invoked/called by a program


z Functions have input values

z Functions only have one return value

z Functions can use internal variables,


their values are deleted after leaving the function
z Standard functions are already defined in the Standard
z Starts with the keyword FUNCTION and ends with
END_FUNCTION (not visible in PAS)

z No recursion !

Page 6
SICAM PAS automation with ST, 16.06.04 Nürnberg

6
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What are functions ? (2)

IEC61131 z Example

Page 7
SICAM PAS automation with ST, 16.06.04 Nürnberg

7
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What are function blocks ?

IEC61131 z Function blocks are subroutines

z They will be invoked/called by a program

z Function blocks have input and output(return) values

z Function blocks have a memory


-> Declaration of function blocks (see variables)

z Function blocks can use internal variables, their values can be preserved
after leaving
z Standard function blocks are already defined in the Standard

z SICAM PAS CFC blocks are function blocks

z Starts with the keyword FUNCTIONBLOCK and ends with


END_FUNCTIONBLOCK (not visible in PAS)

z no recursion!

Page 8
SICAM PAS automation with ST, 16.06.04 Nürnberg

8
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

What are function blocks? (2)

IEC61131 z Example

Page 9
SICAM PAS automation with ST, 16.06.04 Nürnberg

9
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Basic datatypes of variables in 61131-3

IEC61131 z Binary data types (bit pattern)


– BOOL
– BYTE
– WORD
– DWORD
z Integer (signed, unsigned)
– INT / UINT
– DINT / UDINT
z Floating point number
– REAL
z Special-Data types
– TIME
– DATE
z Function blocks!

Page 10
SICAM PAS automation with ST, 16.06.04 Nürnberg

10
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Declaration of variables in 61131-3

IEC61131 z declaration part of POE


Variable type PROG FB FUN
VAR x x x internal variables
VAR_INPUT x x input values
VAR_OUTPUT x output values
VAR_IN_OUT x I/O values
VAR_EXTERNAL x external variables
VAR_GLOBAL x global variables

Example
FB:

Page 11
SICAM PAS automation with ST, 16.06.04 Nürnberg

11
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Declaration of variables in 61131-3 (2)

z Syntax of a declaration:
IEC61131

<NAME> : <TYPE> := <Initial value> ;

z Declaration of variables always between VAR, VAR_xxx and


END_VAR
z No hardware addresses in SICAM PAS

Example
PROG:

Page 12
SICAM PAS automation with ST, 16.06.04 Nürnberg

12
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Access to different variables

IEC61131 z In SICAM PAS there is a special global program for


interfacing variables. This program does not include source
code -> global data file „pasglob.poe“

z Programs are able to access global variables of other


programs using VAR_EXTERNAL
-> like this it is possible to access interface variables

z Function blocks are able to access global variables of their


program via VAR_EXTERNAL
-> better with input/output variables

z Functions do not have access to global variables

Page 13
SICAM PAS automation with ST, 16.06.04 Nürnberg

13
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Definition of own datatypes

IEC61131 z It is possible to create your own datatype combining existing


datatypes

z Create a type file in SICAM PAS

z SICAM PAS interface variables have their own type:


PASDATABLOCK, PASCOMMANDBLOCK, PASGROUP

z Example:

TYPE
State : BYTE:=4;
END_TYPE

-> New type „State“


Page 14
SICAM PAS automation with ST, 16.06.04 Nürnberg

14
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Arrays and Structures

IEC61131 z It is possible to define an array variable


field1 : ARRAY[1..10] OF BOOL;

->Access via field1[1], field1[2], ...

z It is possible to define a structured variable


Test1 : STRUCT
Value1 : BOOL;
Value2 : BYTE;
END_STRUCT;

-> Access via Test1.Value1, Test1.Value2

z Both possibilities also work with type definitions

Page 15
SICAM PAS automation with ST, 16.06.04 Nürnberg

15
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

The programming language ST

ST z Textual programming language

z Similar to the programming language Pascal

z All constructs possible: PROG, FUN, FB

z clear, compact wording of the program function/algorithm

z Good possibilities to use in relation with CFC

Page 16
SICAM PAS automation with ST, 16.06.04 Nürnberg

16
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Example FB in ST

ST

Page 17
SICAM PAS automation with ST, 16.06.04 Nürnberg

17
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Command in ST

ST z A program in ST consists of statements

z Statements are separated by ;


(End-of-line <>End of statement!!)

Operand1

Expression1 Operator

Statement Keyword Operand2

Expression2
ST-Programm

Statement

Page 18
SICAM PAS automation with ST, 16.06.04 Nürnberg

18
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Keywords in ST
Keyw ord Description Remarks
ST := Definition Functions are always used in a
definition
Call and Use of FBs has to be declared in the
declaration part
RET URN Return

IF if clause Condition will be checked

CASE M ultiple choice Value comparison

FOR Loop 1 M ultiple cycle

WHILE Loop 2 upstream at-end-condition

REPEAT Loop 3 downstream at-end-condition

EXIT Loop interruption drop out of the loop

; Blank command

Page 19
SICAM PAS automation with ST, 16.06.04 Nürnberg

19
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Operators in ST
Priority

ST
Operator Description high
() in brackets
Function call
** Potentiation
- Negation
NOT Complement
* Multiplication
/ Division
MOD Modulo
+ Addition
- Subtraction
<, >, <=, >= Equation
= Equality
<> inequality
&, AND Boolean AND
low
XOR Exklusive Boolean OR
OR Boolean OR

Page 20
SICAM PAS automation with ST, 16.06.04 Nürnberg

20
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Definition in ST

ST z Syntax:

Designator := Expression

z Example:

Trigger := TRUE;
a := 4 / 2 + 1;
b := FunctionA(4);

Page 21
SICAM PAS automation with ST, 16.06.04 Nürnberg

21
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

FB-Call and RETURN in ST

ST z FB-Call (Example):

Declaration Program
VAR
FB_TEST : PAS_SASS; FB_TEST(EN:=TRUE);
END_VAR b:=FB_TEST.MARKER;

Multiple calls in a Program possible


Attention: All PAS firmware blocks with interface variables
have to be constant!!!

z RETURN (Example)

RETURN;

Page 22
SICAM PAS automation with ST, 16.06.04 Nürnberg

22
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

IF Clause

ST z Syntax:

IF Print THEN command block;


ELSE Command block;
END_IF;

z Example:

IF switch=5 THEN value:= 1;


ELSE value:=3;
END_IF;

Page 23
SICAM PAS automation with ST, 16.06.04 Nürnberg

23
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

CASE – Multiple choice

ST z Syntax:

CASE Print OF
Print value: Command block;
ELSE Command block;
END_CASE;

z Example:

CASE value1 OF
1: RETURN;
2: flag:=TRUE;
ELSE flag:=FALSE;
END_CASE;

Page 24
SICAM PAS automation with ST, 16.06.04 Nürnberg

24
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

FOR - Loops

ST z Syntax:

FOR controlling variable := Expression TO Expression BY


Expression DO
Command block;
END_FOR

z Example:

FOR i:=1 to 5 BY 1 DO or FOR i:=1 to 5 DO


value[i]:= i;
END_FOR;

FOR i:=5 to 1 BY -1 DO
value[i]:= i;
END_FOR;

z ATTENTION: Loops can deadlock automation!!!


(Loops take processor time, use short loops only)
Page 25
SICAM PAS automation with ST, 16.06.04 Nürnberg

25
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

WHILE - Loops

ST z Syntax:

WHILE Print DO
Command block;
END_WHILE;

z Example:

WHILE flag=TRUE DO
wert:=wert-1;
if wert<5 THEN flag:=FALSE;
END_IF;
END_WHILE;

z ATTENTION: Loops can deadlock automation!!!


(Loops take processor time, use short loops only)

Page 26
SICAM PAS automation with ST, 16.06.04 Nürnberg

26
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

REPEAT - Loops

ST z Syntax:

REPEAT
Command block;
UNTIL Print
END_REPEAT;

z Example:

REPEAT
value:=wert+1;
UNTIL value>5
END_REPEAT;

z Attention: Loops can deadlock automation!!!


(Loops take processor time, use short loops only)

Page 27
SICAM PAS automation with ST, 16.06.04 Nürnberg

27
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Comments in Source Code

ST z Comments help understanding

z Comments help reading the program code


z Syntax:

(* Comment *)

z Example:

(* This is a comment *)

Page 28
SICAM PAS automation with ST, 16.06.04 Nürnberg

28
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Write your own function blocks

Own FB z Why is it necessary to write own function blocks?


– Save functionality for multiple use
– Clearness during programming
– Functionality has to be written / changed only once
– Import/Export – possibility among projects
– Possibility of your own engineering solutions
z What do I have to do to write own function blocks?
– Define task of a functional module
– Define input/output values
– Define internal variables
– Writing of program code
– Test the function block

Page 29
SICAM PAS automation with ST, 16.06.04 Nürnberg

29
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Simple Counter Function block

z Block counts 1 per edge change


Own FB
z Reset counter

VAR_INPUT FUNCTION_BLOCK
SIGNAL : BOOL; IF DEF_SET=FALSE THEN
RESET : BOOL; COUNT:=DEFAULT;
DEFAULT : INT;
END_VAR DEF_SET:=TRUE;
END_IF;
VAR_OUTPUT
COUNT : INT; (* READING CHANGE OF SIGNAL *)
END_VAR IF SIGNAL<>OLD_SIG THEN
COUNT:=COUNT+1;
VAR OLD_SIG:=SIGNAL;
DEF_SET : BOOL:=FALSE; END_IF
OLD_SIG : BOOL:=FALSE;
END_VAR
(* READING RESET *)
IF RESET=TRUE THEN
COUNT:=0;
COUNT:=DEFAULT;
END_IF
END_FUNCTION_BLOCK
Page 30
SICAM PAS automation with ST, 16.06.04 Nürnberg

30
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

SICAM PAS and ST

PAS and ST
z SICAM PAS already contains Firmware FBs
z These FBs can be used in your own FBs
z Interface-variables have their own datatype in PAS:
– PASDATABLOCK
– PASCOMMANDBLOCK
– PASGROUP
z These interface-types are structures with one element, a
pointer
z Interface-variables must have a constant value!!!

Page 31
SICAM PAS automation with ST, 16.06.04 Nürnberg

31
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Practical example SICAM PAS

PAS and ST z Measured value multiplexer: 4 input measured values


z 1 Change-over switch (int-variable)
z One output measured value
z ERROR Output if change-over value is out of range

z CFC-chart with new block incl. setpoint value and 4


measurands
z Export of block -> use in a new project

Page 32
SICAM PAS automation with ST, 16.06.04 Nürnberg

32
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Combination of ST and CFC

PAS and ST
z Written ST- function blocks or ST-functions can be used in a
CFC chart
z Using of most adequate language is possible
z Import/Export -> use in other projects
z Theoretical only: In CFC rendered blocks can be used
in ST
z Mixing of both languages is possible

Page 33
SICAM PAS automation with ST, 16.06.04 Nürnberg

33
development.excellence
PTD PA D
Product Development -
Powered by PTD PA D

Any question?

Summary

Page 34
SICAM PAS automation with ST, 16.06.04 Nürnberg

34
Programming
Language ST

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How can I write my own Function Block?

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Create an ST File

Here we declare variables

My new file Here we have to write the program

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Example: OR with 3 inputs

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Result

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

New Example

We create a new Special_OR:

3 Indication Inputs, 1 Indication Output

Exactly 2 of 3 inputs must be raised!

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Declaration of variables

External Variables

Input VariablesÆinputs of new FB

Output VariablesÆouputs of new block

Internal VariablesÆprocessed within FB

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Declaration of variables

Each Input is a PAS data structure

The Output is also a data structure

We use 3 times a SASS function block to read the


3 messages
And once a CRI block to derive the resultant
message

We use boolean values for all the inputs and for


the output as well for easier programming and
diagnostic reasons

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Internally used PAS-Blocks

CRI creates an information structure e.g. for derived messages

SASS splits up an information structure into all it´s components

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Programming Part

Set the Enable to TRUE and


Link the INPUT to IN_x

If message was raised,


then set VAL to 1
Oherwise to 0

LOGIC:
110 or
101 or
011
THEN ÆOUT=1, otherwise 0

Create Indication,Enable = 1, Cause= spontaneous, Indictype= SP, Signal_1Æreceives current value from
The boolean variable OUT, ChangeÆ to trigger the block, Send Æto execute during startup!
OUT_IND is the resultant variable and gets the result from CRI-output INDIC

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

New function block : Special_OR

Connect to PAS Connect to derived indication


indications

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


ST-Programming Language
PTD-SE-A0/ 11

11
IEC61850
The new Standard in
Substations

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Today‘s situation in substation communication...

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

...and in future

IEC 61850
One World

One Technology
One Standard

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Requirements of electricity boards

‰ Long-term expandability of a systems


• Ability to combine differnt vendors
• Long-term exchangeability of devices for easy spare part
pooling
‰ Reduction of time and costs
• Investment- and operational costs
• Costs and expanditure of time for changes/extensions during
operation
• Implementation time of projects
‰ Managable complexity
• Continuous and consistent engineering

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

International Standard
• Covers all substation functions like
protection, automation and monitoring
• Is a global standard and the key for
interoperable solutions
• Investment security through openness,
exppandability and garanteed future

• Allows Improvement of substations for


different plant types

• Provides support of Engineering of the whole


substation through standardized
configuration language based on XML

• Uses available Ethernet technology and


modern communication components

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Tasks and Extensions


ƒ Substation Automation
IEC 61850
ƒ Tele Communication
in discussion/developement, IEC TC57 / Ad Hoc Working Group 07
ƒ Add On Power Quality Monitoring
in developement, IEC 57/624/NP
ƒ Product Standard for switching devices
in development IEC 62271−003
ƒ Control and monitoring of wind power plants
in developement, IEC 61400-25

ƒ Control and monitoring of distributed energy producers


in developement, IEC 57/660/NP

ƒ Control and monitoring of hydro power plants


in developement, IEC 57/661/NP
ƒ Settings for protection devices, archiving, fault recording
IEEE PSRC H5 (further groups H6, C3, JTF4)
ƒ Metering, gas, water
in discussion
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Benefits for the user


Saving of time during engineering, operation and maintenance
of substations

Saving of costs through worldwide competition and use of Ethernet


Interoperability international validity and testet

Reduced wiring and commissioning


One Ethernet communications platform
Common use of communication infrastructure
One protocol for all demands in substations

Reduced Engineering
No multiple inputs because of data im/export from/to DIGSI
for further use e.g. in a control centr system
XML Import / Export reduces number of errors.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Benefits for the user


Fast diagnosis, reduced down time
User friendly, comfortable remote access from office / home
Minimizes cost intensive plant visits

Economical Web-based HMI solutions


Standard-PC as test equipment
Easy and cost- & ressource optimized access via Internet Explorer

All devices can be integrated


IEC 61850, the worldwide Standard for interoperable solutions
Transformer regulator; switch monitoring; ...

Security of Investment
Architecture & data model are future proof and support future extensions

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Interoperability does not mean Interchangeability

Interoperability
the ability of two or more IEDs from the same vendor, or from
different vendor, to exchange information and to use that
information for correct execution of specific functions

Interchangeability
the ability to replace a device supplied by one manufacturer
with a device supplied by another manufacturer, without
making change to the other elements in the system

IEC 61850 Part 1


“Interchangeability is beyond this
communication standard.”
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

IEC61850-Services in SIPROTEC and SICAM PAS


1. Control
„Selectbefore Operate (SBO) with
enhanced security Æ all commands
to HV devices
„Direct Control with normal security
1 Æ all auxiliarx commands
5 2. Information Report
„ all informationen in monitoring
direction to PAS
4 2 3. GOOSE
„Inter-device communication Æ
Interlocking, blocking etc.
4. File Transfer
3
„Alarm lists, event lists, SOE
„Transmission of fault records
5. Time Synchronisation
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Engineering
The Engineering requires to configure the structure of the system,
which consists of Busses, Hubs, Switches, Routers, IEDs, Merging
Units ect.
The chosen topology determines the assignment to the primary process and
the physical redundancy of the system.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 11

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Information flow during Configuration


• IEC61850 – System- and IED
configuration-tool
• Substation Configuration
Language
• Standardized vendor
IED 1 spanning data exchange
Vendor A One
Data Base Ethernet with
IEC 61850
for
IED 2 Engineering IED 3
Vendor B Vendor C
Data

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Server Client Communication


Clients
• Client
communicates with
several servers

• Server
supports
connection at the
same time to
several clients
Server
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Publisher Subscriber Architecture


Fast inter-bay-communication (GOOSE)

redundant 100MBit/s Ethernet

Multicast

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Concept of a Logical Node

configuration
data
input output
data data

Basic Function
(e.g. Protection)

ƒ Functions still remain vendor-specific


ƒ Data exchange becomes standardized

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Logical Nodes
MMXU Measuring (Measurand unit)
Group Indicator Logical node groups MMTR Metering
MSQI Sequence and Imbalance
A Automatic Control MHAI Harmonics and Inter-harmonics
MDIF Differential Measurements
C Supervisory control
PSCH Protection Scheme
G Generic Function References PTEF Transient Earth Fault
I Interfacing and Archiving PZSU Zero speed or
underspeed
L System Logical Nodes PDIS Distance protection
…more
M Metering and Measurement
P Protection functions
SIMG Insulation medium meas unit
R Protection related functions
SARC Monitoring and diagnostics for arcs
S Sensors SPDC Monitoring and diagnostics for partial
discharge
T Instrument Transformer
X Switchgear
Y Power Transformer
XCBR Circuit Breaker
Z Further (power system) XSWI Circuit Switch
equipment

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 16

16
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Data Objects – approx. 350 classes are specified


Data Classes Number
A - Phase to ground amperes for
Phases 1, 2, and 3
System information 13 Amps - Current of a non three
phase circuit
Physical device inform. 11 Ang - Angle between phase voltage
and current
Measurands 66 AnIn - Analogue Input used for
generic I/O
ChAnVal - Array of analogue
Metered values 14 channel numbers and actual values
at a certain time (time tag)
Controllable Data 36 CircA - Measured circulating current
in a transformer paralleling
Status information 85 application
CtlV - Voltage on secondary of
transformer as used for voltage
Settings 130 control.
Den - Density of gas or other
355 insulating Medium
DQ0Seq - Direct, quadrature, and
zero axis quantity
Grouped in 28 Common Data Classes HaTdV - Voltage Total Harmonic
(Part 7-3). Distortion
More…..

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 17

17
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Standardizing Communication with Logical Nodes


Bay A Bay Unit BayA/XCBR.Pos.stVal
+ PTOC
+ RREC
- XCBR
+ Mode (Mode)
+ Beh (Behavior)
+ Health (Health)
+ Name (Name plate)
+ Loc (Local operation)
+ EEHealth (External equipment)
+ EEName (External equipment name plate)
+ OperCnt (Operation counter)
- Pos (Switch position)
ctlVal
stVal intermediate state (0)
pulseConfig off (1)
operTim
q cn (2)
…more bad state (3)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 18

18
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Example
Logical Device

Bay device with Time Over Current


IED1
• Time Overcurrent Protection
PTOC
• Control Function Auto Reclosing
RREC
• Auto-Reclose Function Switch Control
CSWI
Current
Transfomer MMXU Measurement Unit

IED3 IED2
Circuit Breaker
TCTR XCBR

T1 Q0
IED - Intelligent Electronic Device (every device with a communication interface)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 19

19
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Addressing to control a circuit breaker

IED1/CBCSWI1.Pos.ctlVal

Attribute Name (Norm)


Data Object Name (Norm)
Logical Node Name Suffix (free)
LN -
Logical Node Class (Norm)
Name
Logical Node Name Prefix (free)
Logical Device Name (free)
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 20

20
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configurations
The new communication standard for the station bus
• based on Ethernet
• Up to 128 IEDs
• Ethernet components from Ruggedcom recommend www.ruggedcom.com
• IEC 61850-Goose-mechanism
– Inter-bay-interlocks
– Communication between IEDs For small medium voltage plants

TP
62,5µ or 50µ Fibre

100 Mbit/s redundant


switched Ethernet ring No Redundancy,
cost optimized
Cubicle
TP TP Cu Twisted Pair (TP)
TP Shielded cable
max. 20m

Inter-bay-interlocking independent from the Station Unit via IEC 61850-Goose mechanism

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 21

21
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ruggedcom Switch RS8000T

RS8000T

9 Ethernet switch
according IEC61850
specification

9 DIN-Rail Mount

9 Fail save output relay

9 Fanless operation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 22

22
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ruggedcom Switch RS8000T

20m

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 23

23
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ruggedcom Switch RS1600T


2x FO-Ports (MTRJ)
14x RJ45-Ports

No Redundancy
cost optimized

Cu Shielded Pair
max. 20m

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 24

24
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ruggedcom Switch RS1600T

9 Ethernet switch,
according
IEC61850
spezification

9 Redundant
power supply

9 Fail save relay

9 Fan less
operation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 25

25
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ruggedcom-Switches - Interfaces

RS8000T

RS1600T

RS1600F
RS1600

RS8000

RS400
Interfaces / Device type

FO-Ports (MTRJ-connector)
100BaseFX 1300nm 2 2 2 8 16
max. 2000m
RJ45-Ports
10/100BaseTX 6 14 4
max. 20m

FO-Ports (ST-Stecker)
12
100BaseFL 820nm

http://www.ruggedcom.com

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 26

26
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Ethernet Master clocks

Meinberg LANTIME/GPS - www.meinberg.de

– A separate time master can


especially be used in
configurations with an Ethernet
station bus (IEC 61850) using an
Siemens SICLOCK SNTP-Server (Simple Network
Time Protocol).
– All connected devices (SNTP-
Clients) incl. Station Units are
synchronized. The Station Unit
is still time master for all it´s
directly connected devices
(T103, FMS, DNP3...)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 27

27
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Engineering System
Device Device file configurator
Device library vendor A
vendor B engineering vendor B
tool vendor B

Device library Device Device file System


vendor A engineering vendor A
tool vendor A
configuration
data

Device Device
Each device must have a self-description file engineering engineering
tool vendor B tool vendor A
Device file
vendor X

Standardized file

Vendor specific engineering tool


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 28

28
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Complete Engineering Process according IEC61850


ICD-
Library ICD- File Library

File Fremd- SSD-


gerät File System Specification
IED Configuration
Tool (???)
Tool (DIGSI)

System Configurator
(part of Digsi)

IED Configuration SCD-


Tool (Digsi)
File
Parameter
files

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 29

29
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Solution with DIGSI 4.6


Device
description
vendor X
Device description SIPROTEC
configuration
Siprotec
device
library
System
configuration
Device
System configuration
description vendor X
in SCL

Basic data Station controller

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 30

30
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Data assigned to system interface

System interface Mandatory data


IEC61850 in LD PROT/ e.g.
LN RREC
Î
are always
entered in SCD

User specific
data
in LD CTRL /
SIPROTEC data (Siemens- LN GGIOs
specific) in LD CTRL / LN GGIOs

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 31

31
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

System configurator in DIGSI 4.6

System configurator
for inter-bay communication

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 32

32
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Assigning IEDs to a 61850-Station

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 33

33
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Defining IP-Addresses

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 34

34
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Mapping GOOSE messages

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 35

35
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Updating device parameter files

„ Distribution of mapping to
involved devices

„ Data consistency guaranteed

„ DIGSI operates station-related


for the first time

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 36

36
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Communication modules for SIPROTEC


• Profibus DP • IEC 60870-5-103 +
• Profibus FMS VDEW extension

IEC 61850
• Modbus
• DNP 3.0
EN100
Module

• Substation communication
• Transmission of fault records
• Downloading and uploading parameter files
• IED configuration
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
SICAM PAS – IEC 61850
PTD-SE-A0/ 37

37
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

FO cable (Multimode)
Serial interface:
Ethernet cable (max. 20 m) - Substation automation with serial protocol
RS485 – Bus (Optional: IEC 60870-5-103 via device port B
Serial FO-Bus. No parallel - DIGSI via device service port C
operation possible) Ethernet interface:
- IEC61850 / DIGSI via ethernet module on
device port B

Modem

Router
Ethernet
LAN (INTRANET) Addressing of serial
hubs like two virtual
COM-Ports on the
Switch
Station Unit
IEC61850 and Substation
DIGSI via Ethernet
Ethernet module

INPUT INPUT
Serial Serial
Serial 7XV5450
7XV5655
-0BA00
7XV5450
7XV5655
-0BA00
IEC 103 DIGSI
Mini- Mini-

hub
Serial Hub
Sternkoppler
Serial Hub
Sternkoppler Port B Port C
SIEMENS SIPROTEC SIEMENS SIPROTEC SIEMENS SIPROTEC
RUN ERROR RUN ERROR RUN ERROR

L1 402,1A Max450.1A L1 402,1A Max450.1A L1 402,1A Max450.1A


L2 402,1A Max450.1A L2 402,1A Max450.1A L2 402,1A Max450.1A
L3 402,1A Max450.1A L3 402,1A Max450.1A L3 402,1A Max450.1A
E 00.0A E 00.0A E 00.0A

Anr . L1 Anr . L1 Anr . L1


Anr . L2 Anr . L2 Anr . L2
Anr . L3 Anr . L3 Anr . L3
Anr . Erde Anr . Erde Anr . Erde
Automat Automat Automat

Device with IEC103 SIEMENS

Anr. L1
Anr. L2
RUN

L1 402,1A
SIPROTEC
ERROR

Max450.1A
SIEMENS

L1 402,1A
RUN
SIPROTEC
ERROR

Max450.1A
SIEMENS

L1 402,1A
RUN
SIPROTEC
ERROR

Max450.1A

protocol and serial


Anr. L3 L2 402,1A Max450.1A L2 402,1A Max450.1A L2 402,1A Max450.1A
Anr. Erde L3 402,1A Max450.1A L3 402,1A Max450.1A L3 402,1A Max450.1A
Automat E 00.0A E 00.0A E 00.0A

Devices with EN100 – Ethernet modules on Port B interface (Port B) Aus L1


Aus L2
Aus L3
Aus Erde
Anr . L1
Anr . L2
Anr . L3
Anr . Erde
Automat
Anr . L1
Anr . L2
Anr . L3
Anr . Erde
Automat

are directly connected to a switch and DIGSI – Service-


interface (Port C)

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 38

38
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Networkview – A diagnosis tool

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 39

39
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

IEC-Browser – A diagnosis tool

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


SICAM PAS – IEC 61850
PTD-SE-A0/ 40

40
SICAM PAS
Trace Function
Applications dsiTest and TraceControlCenter
are for testing only !!!

Use on instruction of Siemens PTD Customer


Care Center only !!!

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
What is a Trace Function ?

• With a specified trace the PAS system creates a text file with detailed
internal data for a certain application.
• This function is mainly used to find out unidentified errors in the
parameterization as well as in the system software.
• The text file is usually sent to the customer support center to be evaluated
by system experts.

• To create such a trace files we need two programs, DSITest and


TraceControlCenter.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How to Start DSITEST

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 3

DSITEST starts a general error trace for a desired application

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Enter Password
The Password is 000000

Open connection to DSI Server

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Local connection

Activate local
connection on local PC

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Online Diagnosis

Start Online Diagnosis

Display Source
Information

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Identify Source ID

Source Information

E.g. Protection interface (5)

Reference in UI-
Configuration
Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Trace function
PTD-SE-A0/ 7

7
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Going Online

Enter desired Source ID...


...and go online

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 8

8
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting Trace writing

Default values

7=only error traces

Tick check box


Trace writing starts with OK!

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 9

9
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
What is the Trace Function doing now?

• The trace function is now working


• A trace file is being created.
• If any error occurs, it will be written into the trace text file

• But how can we configure specific traces?


Æ This is the TraceControlCenter for

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 10

10
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting TraceControlCenter

To define specific trace contents, we use the Trace Control Center

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 11

TraceControlCenter specifies certain trace levels of a running trace function

11
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

TraceControlCenter: Settings
Select application, which is the
interface name of your desired
source ID (e.g. Protection Interface)

Your trace is already enabled (by


previous DSITEST)

Specify the Trace Level by using


„Select“ button
Default: Only Error Traces, 0x07

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 12

12
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

TraceControlCenter: Settings (Available Trace Levels)


Here you find the Default Settings, which are only Error Traces, check boxes
binary coded Æ 7
Other Trace functions can be selected manually now.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 13

13
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Apply Settings

The new Trace Level according to


your previous settings

Apply new Trace Settings

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 14

14
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Where to find the Trace files

Trace files are text files (*.txt)

Send files to the customer


support center for evaluation

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 15

15
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Switch off Trace function


Start once more the DSITEST and proceed to the Trace Settings.

Trace function appears


unchecked by default.
Just press OK to stop Trace.

Close DSITEST

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Trace function
PTD-SE-A0/ 16

16
SICAM PAS
Server-DIP
Configuration

1
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

SICAM PAS
Full Server – DIP Configuration ‰ Up to 6 DIPs

Corporate
‰ Up to 150 Bay devices
Network TCP/IP

Control Center ‰ Up to 10.000 data points


IEC T101 IEC T104
“Full Server” SICAM PAS CC “DIP”

Station Bus

Ethernet IEC61850

DIP = Device Interface Processor


Copyright © SIEMENS AG PTD SE 2004. All rights reserved.
Server-DIP Configuration
PTD-SE-A0/ 2

2
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

How to make a Server a DIP


The decision to configure a computer as Server or DIP is made during the PAS
software setup.
A computer which is already set up to be a Server cannot be a DIP !
So we have to uninstall PAS software, which is again task of the setup
program.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Server-DIP Configuration
PTD-SE-A0/ 3

3
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

New PAS Software Setup

Select DIP

Enter the computer Enter the IP


name of the server address of the
computer server computer

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Server-DIP Configuration
PTD-SE-A0/ 4

4
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Starting UI-Configuration
After opening UI-Configuration, it does not appear empty !

As the server computer is already running, it displays its project even on the DIP.
Modifications are possible on both of the computers.

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Server-DIP Configuration
PTD-SE-A0/ 5

5
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Entering a DIP into the configuration

Enter a second system

The DIP computer automatically appears

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Server-DIP Configuration
PTD-SE-A0/ 6

6
Po w

s
e
Train r
in
Cent g
Power Transmission and Distribution Service er

Configuring a DIP

Configure once more a 103-IED


connection to the DIP

Copyright © SIEMENS AG PTD SE 2004. All rights reserved.


Server-DIP Configuration
PTD-SE-A0/ 7

You might also like