Professional Documents
Culture Documents
General Standards 019841 MBP
General Standards 019841 MBP
General Standards 019841 MBP
FOREWORD ill
1 INTRODUCTION 1
2 SITE 1
2-1 Location 1
3 SITE SURVEY 1
3-i General 1
4 SUBSOIL INVESTIGATION 2
4-1 General 2
4-2 Special considerations 2
5 EQUIPMENT 3
5-1 General 3
5-2 Classification 3
5-3 Applicant's responsibility , 3
8 GENERAL HOSPITAL 9
8-1 Special considerations 9
8-2 Nursing unit 9
8-3 Newborn nursery unit . 10
8-4 Pediatric unit 10
8-5 Psychiatric unit 11
8-6 Surgical suite 11
8-7 Obstetrical suite 12
8-8 Outpatient suite 12
8-9 Radiology suite , 13
8-10 Laboratory suite 13
8-11 Pharmacy or drug room .
13
8-12 Dietary department 13
8-13 Administration department 13
8-14 Medical records unit 14
8-15 Central medical and surgical supply department 14
8-16 Laundry 14
8-17 Central stores 14
8-18 Employees' facilities 14
8-19 Engineering service and equipment areas , 14
iv
CONTENTS ( CON.)
10 NURSES' RESIDENCE 39
VI
1 INTRODUCTION
The standards set forth herein have been es- essary modifications for special or unusual re-
tablished by the Surgeon General of the U.S. Public quirements .
and operated to furnish adequate services. some of which may exceed those detailed herein.
Neither these general standards nor the guide ma-
In the case of hospitals not specifically dis- terials of the Public Health Service are intended
cussed herein such as tuberculosis hospitals, the in any way to restrict design initiative or con-
standards for general hospital s will apply with nec- struction techniques .
2 SITE
B. Facilities shall be located in relation to the A . Roads and walks shall be provided within the
center of population, close to where competent lot lines to the main entrance, ambulance en-
medical and surgical consultation Is readily avail- trance, community activities, and services , in-
able, and where employees can be recruited and cluding loading and unloading space for delivery
retained. trucks .
3 SITE SURVEY
The applicant shall provide for a survey of the The survey drawing shall show:
site. The purpose of this survey is to obtain all
information necessary for the development of the A, The courses and distances of property lines
site and for making the mechanical and electrical of all parcels which comprise the hospital site .
C . Details of party walls, or walls and foundations holes, upon, over, or under the site, or adjacent
within the limits of the survey.
to the site, if
adjacent to the lot lines .
D. The position, dimensions, and elevations of J. The probability of freshets overrunning the site
all cellars, excavations, wells, back-filled areas, shall be investigated.
and similar and the elevation of
existing openings,
any water therein. K. Official datum upon which elevations are based
and a bench mark established on or adjacent to the
E . All trees which may be affecied by the building site.
operations ,
ing buildings which are to be modernized or to which N. Contemplated date and description of any pro-
additions will be constructed . posed improvements to approaches or utilities
adjacent to the site.
H. All utility services including pipe sizes, pres-
sures, and electrical characteristics . O, Certification on the survey drawing by the
city engineer or other qualified official that the
I. The location and invert elevations of all piping, officially established street lines, grades of curbs ,
mains, sewers, poles, wires, hydrants, and man- sidewalks, and sewers arc correctly given.
4 SUBSOIL INVESTIGATION
5 EQUIPMENT
ispermanently affixed to the building or which must State agency, in triplicate, a complete list with
be connected to a service distribution system de- an itemized estimate of cost of all proposed fixed
signed and installed during construction for the equipment not included in the construction con-
specific use of the equipment. It includes items tract and all movable equipment.
such as extractors, walk-in refrigerators, inter-
communication systems, and built-in casework.
D. Applicants who do not include all fixed equip-
ment in the construction contract and let separate
contracts for furnishing and installing certain
B. Movable equipment is defined as all items of items of fixed equipment must include in such sep-
equipment which are not considered to be fixed arate contracts all provisions for contract se-
equipment. It includes items such as operating curity, insurance, and compliance with labor stan-
tables, obstetrical tables, anesthesia apparatus, dards as provided under sec. 6-3B, except that
wheeled equipment, portable paging systems, labor standards need not be included for contracts
chinaware, and surgical instruments. under $2000.
331-D67 O-69-2
PLANS, SPECIFICATIONS, AND ESTIMATES
Section S-l
C. Description of Site
B. Out! ine Sp ecif ications
1. The site shall be described by means of the
survey drawing- and soil investigation report, or 1. General description of the construction, in-
by means of an. outline description containing the cluding interior finishes, types and locations of
following general characteristics of the site: acoustical material, and special floor covering.
a. Easements.
2. Description of the air-conditioning, heating,
b. Availability ofeleciricity, water, and sewer and ventilation systems and their controls; duct
lines .
and piping systems; and dietary, laundry, steri-
c. Main roadway approaches.
lizing, and other special equipment.
d. Direction of prevailing breezes .
e. Orientation.
3. General description of electrical service in-
2. A map shall be submitted indicating location cluding voltage, number of feeders, and whether
of the hospital inils geographic area with particu- feeders are overhead or underground,
lar reference to requirements given under sec. 2.
C Description of the Site. The survey drawing
.
agency) that the proposed water supply is potable. the first stage submittal.
A, Hans .
Preliminary sketch plans shall include
the following: 6-3 THIRD STAGE CONTRACT DOCUMENTS
Plans of basement, floors, and roof showing construction purposes . Drawings shall be pre-
a.
space assignment, sizes, and outline offixed pared for each of the following branches of the
and movable equipment work: architectural, structural, mechanical, and
.
g. Equipment. Location of all fixed equipment. (2) Heating and steam mams and branches
Layout of typical and special rooms indicating with pipe sizes .
all fixed equipment: and major items of mov- (3) Diagram of heating and steam risers with
able equipment. Equipment not included in pipe sizes .
the contract shall be so indicated. (4) Sizes, types, <ind heating surfaces of boil-
h. Conveying systems Details of construction,
.
ers, furnaces, with stokers and oil burn-
size and type of equipment, length and route ers, if any.
of travel, machine and control spaces nec- (5) Pumps, tanks, boiler breeching, andpip-
essary, and u til it y requirements, for the ing and boiler room accessories.
following; (6) Air-conditioning systems with required
equipment, water and refrigerant piping,
(1) Conveyors --gravity, and power driven, and ducts .
(2) Cranes. (7) Supply and exhaust ventilating systems
(3) Dumbwaiters --electric, hand, hydraulic. with steam connections and piping.
(4) Elevators freight, passenger, patient. (8) Air quantities for all room supply and ex-
(5) Hoists--electric, hand, hydraulic, pneu- haust ventilating- duct openings.
matic .
c. Dimensions betwe en floor levels, column (4) Riser diagram, of all plumbing stacks with
centers, and offsets. vents, water risers and fixture connec-
,
(2) All load assumptions . a. Electric service entrance with switches and
(3) Stresses and bending moments separately feedergJofiie public service feeders , char-
for each kind of loading. acteristics of the light and power current,
(4) Maximum stress and/or bending moment transformers and their connections if lo-
for which each member is designed, when cated in the building,
not readily apparent from (3). b. Location of main switchboard, power pan-
(5) Horizontal and vertical reactions at col - els, light panels,and equipment. Diagram
umn bases . of feeders and conduits with schedule of
feeder breakers or switches.
3 . Mechanical drawings c. Light outlets, receptacles, switches, power
outlets, and circuits.
a. Heating, steam piping, and air-conditioning d. Telephone layout showing service entrance,
systems .
telephone switchboard, strip boxes, tele-
phone outlets and branch conduits
,
.
(1) Radiators and steam heated equipment e. Nurses' call systems with outlets for beds,
such aa sterilizers, warmers, and steam duty stations, door signal lights, annunci-
tables . ators, and wiring diagrams.
PLANS, SPECIFICATIONS, AND ESTIMATES
Section 6-3
I . Fire alarm system with stations, signal de- Contractor's Protective Liability Insurance
vices, control board, and wiring diagrams.
g. Emergency electrical system with outlets,
$300, 000 -
Bodily Injury Liability $500, 000
transfer switch, sources of supply, feeders, -
Property Damage 100, 000 300, 000
and circuits .
-
B. Specifications Specifications shall supple-
. Bodily Injury Liability $300, 000 $500, 000
-
ment the drawings to fully describe types, sizes, Property Damage 100,000 300,000
capacities, workmanship, finishes, and other char-
acteristics of all materials and equipment and shall
include: d. Fire insurance. The contractor (or owner)
shall insure the building or buildings or other
1. Cover or title sheet. work included in the contract against lessor
damage by fire, and against loss or damage
2. Index. covered by the standard extended coverage
insurance endorsement, the amount of which
3. Instruction to bidders .
shall at all times be at least equal to the a-
mount paid on the account of work and ma-
4. Bid form .
terials plus the value of work or of materials
furnished or delivered but not yet paid for
5. Form of agreement . by the owner. The policy shall provide for
the inclusion of thename of all other con-
6. Performance and payment bond forms . tractors, subcontractors, and others em-
ployed on the premises as insureds, and
7. Labor Standards Provisions for Construction shall stipulate that the insurance com-
Grant Programs , panies shall have no right of subrogation a-
gainst any contractors subcontractors, or
,
8. Sections describing materials and workman- other parties employed on the premises, for
ship in detail for each class of work. any work of any nature whatsoever .
e .
Specifying of materials and equipment The .
for projects involving work in existing buildings B. The contractor shall deliver to the owner a
shall be the same as those required for new con- complete set of equipment installation and main-
struction. tenance manuals.
of the national building codes generally used in the 9-14A19, table 3) 50 cents
area for all components of the building type which
are not specifically covered by the minimum stan- International Standards Organization (ISO) Rec -
dards set forth herein provided the requirements ommendations No. 140-1960, Field and Lab-
of the code arc not inconsistent witli the minimum
oratory jylea3uremen_ts_ of Airborne and Impact
standards herein. Sound Transmission (sees. 8-20A15, table 1
and 9-14A19, table 3) $2.40
National Fire Protection Association (NFPA) American Society of Heating, Refrigerating and
Standard No. 82, Standard for Incinerators Air-Conditioning Engineers
(sees. 8-23B and 9-17B) 50 cents United Engineer Center
345 East 47th Street
National Fire Protection Association (NFPA) New York, New York 10017
Standard No, 10, Standards! for the Installation
of Portable Fire Extinguishers (sees. 8-20A14 American Society for Testing and Materials
and 9-14A18) 60 cents 1916 Race Street
Philadelphia, Pennsylvania 19103
National Fire Protection Association (NFPA)
Standard No. 101, Life Safety_C_ode (sees. International Standards Organization
8-20A1 and9-14Al) $1.50 (USA Headquarters, United States of America
Standards Institute)
National Fire Protection Association (NFPA) 10 East 40th Street
Standaid No. 565, Standard for Nonflammable New York, New York 10016
Medical Gas Systems (sees. 8-23E6 and 9-
17E6) 50 cents National Electrical Manufacturers Association
155 East 44th Street
Public Health Service (PHS) Publication, Labor New York, New York 10017
Standards Provisions for Construction Grant
Programs (sec. 6-3B7) (Available only; at no National Fire Protection Association
charge from the Division of Hospital and Med- 60 Batterymarch Street
ical Facilities, Willste Building, Silver Spring, Boston, Massachusetts 02110
Maryland 20910)
Underwriters' Laboratories, Inc.
Public Health Service (PHS) Publication No. 934, 207 East Ohio Street
Food S e r v i ce_Sanitation .Manual, (sees 8-12
.
Chicago, Illinois 60611
and 9-7) 55 cents
America Standards
United States of Institute
Public Health Service (PHS) Publication No 1038,
.
(Formerly American Standards
Report of Public Health Service Technical Com- Association, Inc.)
mittee on Plumbing Standards (sees. 8-23Eand
;
10 East 40th Street
9-17E) 45 cents New York, New York 10016
Underwriters' Laboratories, Inc. (UL) Publi- Except as noted in the list, copies of Govern-
cation No. 181, Air_Ducts (sees. 8-23D2J and ment publications can be purchased from the
9-17D2h) No charge Superintendent of Documents, U.S. Government
Printing Off ice, Washington, D.C. 20402.
United States of America Standards Institute
(USASI) Standard No. A117. 1-1961, American
Standard Specifications for Making Buildings
and Facilities Accessible to, and Usable by,
the F li y s i c a 1 I y Handicapped (sees 8-1B and
.
9- IB) $2.00
8 GENERAL HOSPITAL
NOTE: General hospitals shall either contain the elements described herein or the narrative program
accompanying the application shall indicate the manner in which the needed services are to be available
to the hospital. When services are to be shared or purchased, appropriate modifications or deletions
in space requirements would be anticipated. When pediatric, psychiatric, and obstetrical services are
not included in the hospital, the narrative program should indicate where such services are available
in the community. Each element provided in the hospital must meet the construction requirements out-
lined herein.
A. Hospitals with a capacity of 50 beds or less 8. Cubicle curtains, or equivalent built-in de-
present special problems. The sizes of the vari- vices, for privacy for each patient in multibed
ous departments will depend upon the requirements rooms .
3. Hotplate.
5. An anteroom with adequate main- facilities to
4 .
Refrigerator .
10
GENERAL HOSPITAL
Seat-ion 8-6
A. Patient Rooms. Pediatric patient rooms shall 6. Storage for recreation and occupational therapy
conform to the same requirements as those for a equipment .
provided in nurseries.
cial requirements.)
If included as a separate nursing unit, it should in an area other than the surgical suite .)
be deslgnedas other nursingunits except that care
must be taken to provide for patients needing close D . Recovery Facilities . A separate room with
supervision to prevent the patient's escape, sui- charting space, medication storage and prepara-
cide, or hiding. The unit shall contain: tion space, and clinical sink is required. (May
be omitted hi hospitals with less than a minimum
A. Patient Room . Each patient room shall meet average of 10 surgical procedures per day.)
the following requirements:
E Service Areas in Bach Surgical Suite. The
.
1 . Minimum room
areas; 100 square feet inone- size ofeachservice area will depend onthe surgi-
bed rooms and 80 square feet per bed in rnultibed cal workload and shall include:
rooms .
1 .
Surgical supervisor station .
4. Dining room; minimum of 15 square feet per 6 Storage for sterile and unsterile supplies
. .
5. Dayroom; minimum of 40 square feet per pa- 7 . Anesthesia workroom . For cleaning and stor-
tient. age of equipment .
11
334-367 O-Gfl 3
GENERAL HOSPITAL
Section 8-8
8. Storage room for anesthetic agents. 4. Scrubup facilities , Adjacent to delivery room .
9. Nitrous oxide and oxygen facilities, (Provide 5. Soiled workroom. Shall contain counter, clin-
ical sink, waste receptacle, and soiled linen re-
storage room if these services are not piped in.)
ceptacles.
10. Clean workroom, For storage and assembly
of supplies; shall contain counter and sink. 6 . Storage for sterile and un sterile supplies .
11 .
Equipment storage room . For surgical and
7 . Anesthesia workroom . For cleaning and stor-
monitoring equipment.
age of equipment.
12. Janitor's closet. Floor receptor or service
sink and storage for housekeeping supplies and 8. Storage room for anesthetic agents.
equipment.
9. Nitrous oxide and oxygen facilities. (Provide
13. lockers, and toilet storage room if these services arc not piped in.)
Clothing change areas,
rooms. For doctors, nurses, orderlies, and other
10. Clean workroom. For storage and assembly
personnel .
A. General. The suite shall be located to pre- 13. Clothing change areas, lockers, and toilet
vent through traffic and shall be completely sepa- rooms. For doctors, nurses, orderlies, and oth-
rated from the surgical suite. (See sees. 8-20 er personnel.
and 8-24, for special requirements.)
14. Stretcher alcove.
B. Delivery Room. The number required shall
be based on the estimated annual birth late.
8-8 OUTPATIENT SUITE
C Labor Room. The number required shall be
.
based on the estimated annual birth rate. A pa- These facilities shall be located to prevent
room shall be provided adjomingeach
tients 'toilet outpatients from traversing inpatient areas and
labor room or conveniently accessible. shall include:
D .
Recovery Room . Sliall contain a minimum of A Well -Marked and Sheltered Entry with nearby
.
autoclave. Locate near delivery rooms. E. Emergency Room. Clinical sink. (See sees.
8-20 and 8-24 for special requirements . )
3. Facilities for storage and preparation of medi-
cation. F. Storage for Sterile Supplies
12
GENERAL HOSPITAL
Section 3-13
D. Potwashing Facilities
Area. For stretcher patients.
D. Blood Storage Room. (May be located in an M. Jan i tor's pi oset Storage for housekeeping
.
area other than the laboratory suite.) supplies and equipment; floor receptor or service
sink.
be located near the laboratory and contain a water N Toil ej Room. Conveniently accessible for di -
closet and lavatory. etary staff.
F .
Morgue and Autopsy Facilities . These facili-
ties shallbe provided within the hospital unless 8-13 ADMINISTRATION DEPARTMENT
otherwise available .
This department shall include:
'
14
GENERAL HOSPITAL
Section 8-20
D. MaintenanceJih op (s ) . At least one room shall tures with blade handles intended for handwashing
be provided .
purposes shall provide clearance necessary for
operation without use of hands. (See sec. 8-23
2. Such items as drinking fountains, telephone ray installations shall conform to NBS Handbooks,
booths, and vending machines shall be located so as follows:
that they do not project into the required width of
exit corridors, a. X-ray --Handbook 76.
b. Gamma-ray--Handbook 73.
3. All doors to patient-room toilets or patient-
room bathrooms shall be equipped with hardware 12. Celling heights
which will permit access in any emergency.
a. Boiler room. Not less than 2'6" above the
4 All doors opening onto corridors shall bo swing-
.
15
GENERAL HOSPITAL
Section 8-20
c. Corridors, storage rooms, patients' toilet 8. Ceilings shall be acoustically treated in corri-
rooms, and other minor rooms. Not less dors in patient areas, nurses' stations, labor
than 7'6". rooms, nourishment stations, dining areas, and
d. All other rooms. Not less than S'O", dayrooms.
Table 1. SOUND TRANSMISSION LIMITATIONS
13. Boiler rooms, food preparation centers, and
FOR PARTITIONS AND FLOORS IN
laundries shall be insulated and ventilated to pre-
GENERAL HOSPITALS
vent any floor surface above from exceeding a tem-
perature of 85F .
B. Finishes
16
GENERAL HOSPITAL
Section 8-SS
tion, patient dining, or therapy rooms are Located depths. Proper soil-bear ing values shallbe estab-
on other than the first floor, shall have electric or lished in accordance with recognized standards.
If solid ground is not encountered at practical
electrohydraulic elevators as follows:
depths, the structure shall be supported ondriven
1 . Number of elevators
piles or drilled piers designed to support the in-
At least tended load without detrimental settlement, except
a. hospital -type elevator shall be in-
1
that one-story buildings may rest ona fill designed
stalled where 1 to 59 patient beds are located
on any floor other than the first . (For pur- by a soils engineer When engineered fill isused,
.
entrance ) .
neer. The soils engineer shall issue a final re-
b. At least 2 hospital -type elevators shall be port on the grading operation and a certification
installed where 60 to 200 patient beds are of compliance with the job specifications Special .
located on floors other than the first, or review and approval by the Public Health Service
where inpatient facilities are located on a will be required for foundations supported on en-
floor other than that containing the patient gineered fill. All footings shall extend to a depth
beds. not less than one foot below the estimated maxi-
c. At least 3 hospital -type elevators shall be mum frost line .
where inpatient facilities are located on a shall be of not less than 1-hour fire -resistive
floor other than, that containing the patient constructionthroughout, with the following excep-
beds, tions :
mated vertical transportationrequirementa. and storage rooms of 100 square feet or greater
area shall be of 2- hour fire -resistive construction.
2 Cars and platforms
. Elevator cars and plat-
.
forms shallbe constructed ofnoncombustible ma- 2. Heavy timber construction may be used in
terial, except that fire -retard ant -treated material gymnasiums, chapels, auditoriums, andadminis-
may be used if all exterior surfaces of the car are tration areas provided that these areas are so lo-
covered with metal. Cars of hospital -type eleva- cated as to befreestandingbuildings or if attached
tors shall have inside dimensions that will accom- to the main building, are suitably fire separated
modate a patient's bed and attendants and shall be at therefrom, do not form a major circulation ele-
least 5'Q" wide by 7'6" deep. The car door shall ment in the facility, and do not serve as a required
have a clear opening of not less than 3'8" . means of egress.
4. Operation. Elevators (except freight ele- the structural framework and building elements
shall bean appropriately fire -resistive combi-
vators) shall be equipped with two-way special ser-
vice switch to permit cars to bypass all landing nation of materials using steel, concrete, or ma-
button calls and be dispatched directly to anyfloor. sonry. Load -bearing walls may be used only for
exterior walls firewalls, and vertical shafts.
,
B. Field Inspection ajidjrestSii The contractor
shallbe required to cause inspections and teststo
be made and shall deliver to the owner written cer-
tification that the installation meets the require-
2. Bearing walls and walls enclosing stairways,
elevator shafts, chutes and other vertical shafts,
ments set forth in this section and all pertinent
boiler rooms, and storage rooms of 100 square
safety requirements .
17
GENERAL HOSPITAL
Section 8-22
feet or greater area shall be of 2 -hour fire-resistive C. Sjeamjmd Hot Water Systems
constiuclion.
1. Boilers. Boilers shall have the capacity, based
3. Nonload -bear ing corridor partitions shall be of
upon the published Steel Boiler Institute or Institute
1-hour fire -resistive construction.
of Boiler and Radiator Manufacturers' net rating,
4. Columns, girders, trusses, floor construction to supply the normal requirements of all systems
including beams, and roof construction including and equipment. The number and arrangement of
beams shall be of not less than 1 1/2-hour fire- boilers shall be such that when one boiler breaks
resistive construction. down or when routine maintenance requires that
one boiler be temporarily taken out of service, the
5. Beams supporting masonry shall be individually
capacity of the remaining boiler(s) shall be suffi-
protected with not less than 2-hour fire-resistive cient to operate all systems. (In areas in a design
construction.
temperature zone higher than +20F based on .
,
partitions shall be of 1-hour fire-resistive con- Handbook of Fundamentals, boiler capacity for
struction and may utilize fire-retardant-treated space heating, when one boiler is out of service,
wood studs. will not be required.)
product shall be determined by an independent test- 4. Covering. Boilers, smoke breeching, steam
ing laboratory in accordance with ASTM Standard supply piping, high pressure steam return piping,
No. E 84-61. and hotwater space heating supplyand ret urn pip-
ing shall be insulated with insulation having a flame
A. General
D. Air Conditioning, Heating, and
1 Prior to completion of the contract and final
. Ventilating Systems
acceptance of the facility, the architect and/or
1
engineer shall obtain from the contractor certifi- .
Temperatures and humidities
cation that all mechanical systems have been tested
and that the installation and performance of these a. The systems shall be designed to provide
systems conform to the requirements of the the temperatures and humidities shown be-
plans
and specifications. low.
18
GENERAL HOSPITAL
Section 8-2S
areas shall be located not less than 3 inches k . Acoustical lining materials shall not be usucl
in the interior of duct systems servingsen-
above the floor,
sitive areas such as operating and delivery
G, Corridors shall not be used to supply air to
or exhaust air from any room, except that rooms, nurseries, and isolation rooms.
exhaust air from corridors may be used to 1 , Ducts which pass through fire walls shall be
ventilate bathrooms, toilet rooms, or jani- provided with approved automatic fire doors
tor's closets opening directly on corridors, onbothsidesof the wall exceptthat 3/8-incli
f . Filters The ventilation systems serving
.
steel plates may be used in lieu of fire doors
sensitive areas such as operating rooms, for: openings not exceeding 1'6" in diameter ,
19
331-067 O-694
GENERAL HOSPITAL
Section 8-23
^ o o o o o i
OOOO
Z2ZZ OOOQOOQ OOOOOO
w
U
in
<J
.
'
en
CD
u in vi m in 10 ra wm.uioi. in
a
01
%
O >" ?H
'
U L.
+ + + + o-(-ooaoo i o i
K! <
oo o n
% s ?i s
a a1 co
c-l 01 IN CS
e
Q
M Q Q Q
m p CO CO CJ
m IN CS tN tN
W
A i
20
GENERAL HOSPITAL
Section 8-23
m. Cold -air duels shall be insulated wherever with the requirements of Appendix C, Hospital
necessary to maintain the efficiency of the Plumbing, inPHSPub. No. 1038.
system or to minimize condensation prob-
lems .
ventilate the food preparation areas only af- per square inch during maximum demand
ter it has passed through a filter with 80 per- periods .
b. Each water service main, branch main,
cent efficiency.
riser and branch to a group of fixtures shall
r. Exhaust hoods in food preparation centers
minimum exhaust rate of 100 be valved Stop valves shall be provided at
.
shall have a
cubic feet per minute per square fool of hood
each fixture .
face area. All hoods over cooking ranges c. Hot, cold, and chilled water piping, and
waste piping on which condensation may oc-
shall be equipped with fire extinguishing sys-
cur shall be insulated. Insulation of cold
tems and heat-actuated fan controls. Clean-
and chilled water lines shall include an ex-
out openings shall be provided every 20'0"
terior vapor barrier.
in horizontal exhaust duct systems serving
d. Backflow preventers shall be installed on
hoods .
21
GENERAL HOSPITAL
Section 8-83
with noncorrosive material. show that the equipment is correctly installed and
operates as planned or specified A written record .
tem is not available , a facility providing sew- a dry ventilated space devoid of corrosive fumes
age treatment which conforms to applicable or gases Overload protective devices shall be
.
local and State regulations is required. suitable for operating properly in the ambient tem-
perature conditions .
such as, central soiled linen holding rooms, main- ance panel boards shall be provided for the circuits
tenance shops, trash rooms, bulk storage rooms on each floor. This requirement does not apply
and adjacent corridors, attics accessible for stor- to emergency system circuits .
flammable medical gas system installations shall 2. Patients' bedrooms shall have general lighting
be in accordance with the requirements of NFPA and night lighting. A reading light shall be pro-
Standard No. 565. vided for each patient . At least one luminaire for
22
GENERAL HOSPITAL
Section 8-S4
night lighting shall be switched at the entrance to G. Equipment Installation in Special Areas
each patient room. Patients' reading lights and
other fixed lights not switched at the door shall 1 . Installation in h a z a r d o u s areas . In areas
have switch controls convenient for use atthclum- where flammable anesthetic agents are used, such
maire. All switches for control of lighting in pa- as operating, delivery, emergency, and anesthe-
tient areas shall be of the quiet operating type. sia induction rooms, and rooms for storage of
flammable gases, all electrical equipment and de-
vices including receptacles, wiring, and conduc-
3. Operating and delivery rooms shall have gen- tive flooring installations shall comply with NFPA
eral lighting for the room in additionto local light-
Standard No 56 . .
bath,
Single receptacles for equipment such as floor
calling station shall be provided for nurses' use
cleaning machines shall be installed approximately in each operating, delivery, recovery, emer-
SO'O" apart in all corridors and shall be polarized
gency, and intensive nursing care room; and in
to prevent use interchange with X-ray receptacles .
nurseries, supervised wards for mental patients ,
Duplex receptacles for general use shall be in- and rooms for children.
stalled approximately 50*0" apart in all corridors
and within 25'0" of ends of corridors .
dors shall be of safety type or shall be controlled of more than 5,000 square feet. In multistory
by switches located at a nurses' station or other buildings orm multibuilding facilities, the signal
shall be coded or otherwise arranged to indicate
supervised location.
23
GENERAL HOSPITAL
Section 8-24
the location of the station operated., Presignal sys- medication preparation area, and labor
tems will not be permitted. rooms .
terruption of the normal electric supply that could b. Equipment. Essential to life safety andfor
affect the medical care, treatment, or safety of protection of important equipment or vital
the occupants, an emergency source of electricity materials :
mal service is supplied by one or more cen- intended for issuing instruc-
systems if
tral station tiansmission lines .
tions during emergency conditions, and
b . An emergency generating set or a central alarms required for nonflammable medi-
station transmission line, when the normal calgas systems, if installed.
electric supply is generated on the premises .
(3) Fire pump, if installed.
(4) Receptacles for incubators for infants .
emergency generating set, including the prime (6) Sewerage or sump lift pump, if installed.
mover and generator, shall be located on the
(7) Receptacles for blood bank refrigerator.
premises and shall be reserved exclusively for
(8) Receptacles in operating, recovery, in-
supplying the emergency electrical system. Ex- tensive care, and delivery rooms except
ception: A system of prime movers which are those for X-ray. At least one duplexre-
ordinarily usedto operate other equipment and al-
ceptacle in each nursery.
ternately used to operate the emergency gener-
(9) Duplex receptacles in patient corridors,
ator (s) will be permitted provided that the number
(10) One elevator, where elevators are used
and arrangement of the prime movers is such that
de-
to transport patients to operating and
when one of them is out of service (due to break-
livery rooms or from these rooms to
down or for routine maintenance), the remaining
nursing areas on another floor .
4.
telephone service .
24
GENERAL HOSPITAL
SeaUon 8-34
book of Fundamentals; or (2) the hospital is corridors, recovery rooms, intensive care nurs-
supplied by at least two utility service feed- ing areas, and nurseries All other lighting and
.
ers, each supplied by separate generating equipment required to be connected to the emer-
sources, or a network distribution system gency system shall either be connected through
fed by two or more generators, with the hos- the above described primary automatic transfer
pital feeders so routed, connected, and pro- switching or shall be subsequently connected
tected that a fault any place between the gen- through other automatic or manual transfer
erators and the hospital will not likely cause switching. Receptacles connected to the emer-
an interruption of more than one of the hos- gency system shall be distinctively marked for
pital service feeders . identification. Storage-battery-powered lights,
provided to augment the emergency lighting or
5 . Details The.
emergency electrical system for continuity of lighting during the interim of
shall be so controlled that after interruption of the transfer switching immediately following an inter -
normal electric power supply, the generator is ruption of the normal service supply, shall not be
brought to full voltage and frequency and connected used as a substitute for the requirement of a gen-
within 10 seconds through one or more primary erator, Wherefuelis normally stored on the site,
automatic transfer switches to all emergency light- the storage capacity shall be sufficient for 24-
ing; all alarms; blood banks; nurses' call; equip- hour operation. Where fuel is normally piped
ment necessaryfor maintaining telephone ser- underground to the site from a utility distribution
vice; pump for central suction system; and re- system, storage facilities on the site will not be
ceptacles in operating and delivery rooms, patient required .
25
FACILITY FOR LONG-TERM CARE
Section 9-1
9-1 Si'ccivL CONSIDERATIONS 4. Window: Sill shall not be higher than 3'0" a-
bove the floor and shall be above grade.
A. Independent long-term care facilities with a
capacity of 50 beds or less present special prob- 5. Nurses' calling station(s). (See sec. 9-18F.)
lems. The sizes of the various departments will
In single and two-bed rooms, the
depend upon die requirements of the facilities. 6. Lavatory.
Some functions allotted separate spaces or rooms lavatory may be located in a private toilet room.
in these general standards may be combined pro-
vided that the resulting plan will not compromise
7.Wardrobe or closet for each patient. Mini-
the best standards of safety and of medical and
mum clear dimensions; I'lO" deep by 1'8" wide
nursing practices and the social needs of patients.
with full length hanging space provide clothes rod
;
In other respects, the general standards set forth
and shelf.
herein, including the area requirements, shall
apply.
8. Cubicle curtains, or equivalent built-in de-
vices, for privacy for each patient in multibed
B, Facilities shall be available to the public, staff, rooms .
9-2 NURSING UNIT of each service area will depend on the number
and types of beds within the unit and shall include :
A, Patient Rooms . Each patient room shall meet 3. Clean workroom. For storage and assembly
the following requirements of supplies for
;
nursing procedures; shall contain
work counter and sink.
1 . Maximum room capacity; 4 patients .
26
FACILITY FOR LONG-TERM CARE
Section 9-5
(May be a designated area within the clean work- one nursing unit onthe same floor. For consulta-
room .
) tion, examination and treatment., and therapeutic
and nursing procedures Provide lavatoiy, stor- .
7 . Nourishment station .
Storage and sink for age, and space for treatment table.
serving between -meal nourishments. (May serve
more than one nursing unit.) E. Room An autoclave shall be pio-
Ste r il i z ing .
ing facilities shall provide space for the private all beds in excess of 100. Additional space shall
use of the bathing fixture, for dressing, and for a be provided for outpatients if
they participate in
wheelchair and attendant Showers in central balh-
. a day care program .
10. Stretcher and wheelchair parking area or al- 9-4 PHYSICAL THERAPY UNIT
cove.
(May be omitted in facilities of less than 100 beds.)
11. Janitor's closet. Storage of housekeeping
supplies and equipment , Floor receptor or service The following shall be provided:
sink.
A. Office. (May also serve for occupational
G. Patient Toilet Rooms therapy .
)
by6'0".)
E- Toilet Room. Located for convenient access
2. Water closets must be easilyusable by wheel- byphyslcaltherapypatients. (May alsoserve oc-
chair patients Grab bars shall be provided at all
. cupational therapy patients.)
water closets ,
F. Wailing Space
3. At least one room shall be provided for toilet
27
FACILITY FOB LONG-TERM CARE
Section 9-5
B. Therapy Area . Provide sink or lavatory. M. Dietitian's Office. (May be omitted mfacili-
ties with less than 100 beds if desk space is pro-
vided in kitchen.)
C. Storage for Supplies and Equipment
A. Food Preparation Center . Provide lavatory but E . Public and Staff Toilet Room
do not provide mirror.
28
FACILITY FOR LONG -TERM CAlfE
Seatian 9-14
F. Janitor s
'
Cl o set
Storage for housekeeping
. I, Refuse Room Foi holding-trash prior to dis-
.
supplies and equipment; floor receptor or service posal . Shall be located convenient to service en-
sink. trance. (See sec. 9-14A13d.)
G. Storage for Laundry Supplies J Yard Equipment Storage Room. Foi yard
.
a. Operatory
E. Storage Roomjfor Building Maijrt^njutcja b. Laboratory and darkroom
Supplies .
(May be part of maintenance shop in fa- c. Lavatory
cilities of less than 100 beds.)
11. Chiropodist facilities .
29
FACILITY FOR LONG-TERM CARE
Section 9-14
avoided. All details and finishes shall meet the be designed as follows. (See also sec. 9-17B.)
following requirements:
a. Service openings -to chutes shall have ap-
shall be 2'0".
to patient toiletrooms and other rooms needing
d. Chutes shall terminate in or discharge di-
access for wheelchairs shall have a minimum width
room or linen chute
rectly into a refuse
of 2'10",
room separated from the incinerator or
2. Such items as drinking fountains, telephone laundry. Such rooms shall be of not less
booths, and vending machines shall be located so than 2-hour fire- resistive construction and
that they do not project into the required width of the entrance door shall be a class "B",
exit corridors . 1 1/2 -hour fire door.
30
FACILITY FOR LONG-'I'ERM CARS
Section 9-15
31
FACILJTX FOR LONG-TERM CARE
Section 9-15
on any floor other than the first. (For pur- depths. Proper soil bearing values shall be es-
first floor
poses of these requirements, the tablished in accordance with recognized standards.
is that floor first reached from the main front If solid ground is not encountered at
practical
entrance .
) depths, the structure shall be supported on driven
b. At least 2 elevators, 1 of which shall be piles or drilled piers designed to support the in-
hospital -type, shall be installed where 60 to tended load without detrimental settlement, except
200 patient beds are located on floors other that one -story buildings may rest on a fill des igned
than the first, or where inpatient facilities by a soils engineer. When engineered fill is used,
are located on a floor other than those con- site preparation and all grading shall be done un-
taming the patient beds .
der the direct full-time supervision of the soils
c. At least 3 elevators, 1 of which shall be engineer. The soils engineer shall issue a final
hospital -type, shall be installed where 201 report on the grading operation and a certification
to 350 patient beds are located on floors oth- of compliance with the job specifications . Special
er than the first, or where inpatient facili- review and approval by the Public Health Service
ties are located on a floor other than those will be required for foundations supported on en-
containing the patient beds . gineered fill. All footings shall extend to a depth
d. For facilities with more than 350 beds, the not less than one foot below the estimated maxi-
number of elevators shall be determined mum frost line.
from a study of the facility plan and the es-
timated vertical transportation require- B. One -Story Buildings. One-story
ments . buildings
shall be of not less than 1-hour fire-resistive con-
struction throughout, with the
2. Cars and platforms Elevator cars and plat-
. following excep-
tions:
forms shall be constructed ofnoncombustible ma-
terial, except thatf ire -retardant- treated materi-
1. Walls enclosing stairways, elevator shafts,
almay be used if all exterior surfaces of the car
are covered with metal. Cars of hospital -type ele- chutes and other vertical shafts, boiler rooms,
vators shall have inside dimensions that will ac- and storage rooms of 100 square feet or greater
commodate a patient's bed and attendants and shall area shall be of 2 -hour fire -resistive construc-
be at least 5'0"wide by 7'6" deep; cardoors shall tion.
4. Operation. Elevators
(except freight eleva-
G. Multistory Buildings
tors) shall be equipped with a two-way special ser-
vice switch to permit cars to
bypass all landing
button call sand be dispatched
I For all buildings more than one story in height
.
,
32
FACILITY FOR LONG-TERM CARE
Section 9-1?
testinglaboratory in accordance with ASTM Stan- 4. Covering. Boilers, smoke breeching, sLcam
dard No. E 84-61. supply piping, high pressure steam returnpiping,
and hot water space heating supply and returnpip-
ing shall Ix; insulated with insulation having a flame
9-17 MHCHANICAI, REQUIIWMKNTS spread rating of 25 or less and asmoke-developed
rating of 50 or less.
A. General
D. Air Conditioning, Heal Ing^and.^Ven^til^tJn^
1 Prior to completion ol the contract and final
.
SyjitcmiB.(For Chronic Disease Hospilals, see
acceptance of the facility, the architect and/or sec. 8-23D. The following requirements applyto
engineer shall obtain from the contractor certifi- nursing homes.)
cation that all mechanical systems have been tested
and
1 . Temperatures . A minimum temperature of
and
that the installation performance of these
75F. shall be provided for all occupied areas at
systems conform to the requirements of the plans
winter design conditions.
and specifications .
2 . Upon completion of the contract , the contractor 2 . VenUlalion system details . All air-supply and
be in accordance with Part III of the NFPA Standard as far away as practicable but not less than
No. 82. t
25 O" from the exhausts from any ventilating
33
FACILITY FOR LONG-TERM CARE
Section 9-1?
34
FACILITY FOR LONG-TERM CARE
Section Q-17
system or combustion equipment. The bot- for openings not exceeding 18 inches in di-
tom outdoor intakes serving central air
of ameter. An approved fire damper shall be
systems shall be located as high as possible provided on each opening through each fire
but not less than 8'0" above the ground level partition and on each opening through the
or, if installed through the roof, 3'0" above walls of a vertical shaft Ducts which pass
,
roof level .
through a required smoke barrier shall be
b. The ventilation systems shall be designed and provided with dampers which are actuated
balanced to provide the general pressure re- by products of combustion other than beat .
lationship to adjacent areas shown in table 4. Access for maintenance shall be provided
c. Room supply air inlets, recirculation, and at all dampers .
exhaust air outlets shall be located not less j , Cold air ducts shall be insulated wherever
than 3 inches above the floor. necessary to maintain the efficiency of the
di Corridors shall not be used to supply air to system or to minimize condensation prob-
or exhaust air from any room, except that lems .
exhaust air from corridors may be used to k, The air from dining areas may be used to
ventilate rooms such as bathrooms, toilet ventilate the food preparation areas only
rooms, or janitor's closets which open di- after it has passed through a filter with SO
rectly on corridors .
percent efficiency.
e. Filters. Central systems designed for re- 1 . Exhaust hoods in food preparation centers
circulation of air shall be equipped with a shall have a minimum exhaust rate of 10O
minimum of 2 filter beds. Filter bed #1 shall cubicfeetperminute per square foot of hood
be located upstream of the conditioning face area. All hoods over cooking ranges
equipment and shall have a minimum effi- shall be equipped with fire extinguishing
ciency of 30 percent . Filter bed #2 shall be systems and heat-actuated fan control s .
located downstream of the conditioning Cleanout openings shall be provided every
equipment and shall have a minimum effi- 20'0" in horizontal exhaust duct systems
ciency of 90 percent. serving hoods.
Central systems using 100 percent out- m, Boiler rooms shall be provided with suffi-
door air shall be provided with filters rated cient outdoor air to maintain combustion
at 80 percent efficiency. rates of equipment and reasonable tempera-
The above filter efficiencies shall be war- tures in the rooms and in adjoining areas .
ranted by the manufacturer and shall be based n . Sec sec 9- 14A17 for additional boiler
. room ,
on the National Bureau of Standards Dust Spot food preparation center, and laundry venti-
Test Method with Atmospheric Dust, lation requirements
Filter frames shall be durable and care-
E, Plumbing and Other Piping Systems. (For
fully dimensioned, and shall provide an air- Chronlc Disease Hospitals, see sec. 8-23E. The
with the enclosing ductwork. All
following requirements apply to nursing homes )
tight fit
.
joints between filter segments and the enclos- AIL plumbing systems shall be installed in accord-
1
ing ductwork shall be gasketecl or sealed to ance with the requirements of Appendix C, Hos-
provide a positive seal against air leakage. pital Plumbing, inPHS Pub. No. 1038,
f . A manometer shall be installed across each
bed serving central air systems
filter .
1 ,
Plumbing fixtures
g. Ducts shall bo constructed of iron, steel,
aluminum, or other approved metal or ma- a. The material used for plumbing fixtures
terials such as clay or asbestos cement. shall be of nonabsorptive acid -resistant ma-
h. Duct linings shall meet the Erosion Test terial .
35
FACILITY FOR LONG-TERM CAPE
Section 9-2?
per square inch during maximum demand sewage treatment which conforms to appli-
periods .
cable local and State regulations is required .
be insulated. Insulation of cold and chilled age, and laundry and trash chutes. Storage rooms
water lines shall include an exterior vapor of less than a 100 square foot area and spaces used
barrier .
for storage of nonhazardous materials are ex-
d. Backflow preventers (vacuum breakers) cluded from this requirement. Sprinkler heads
shall be installed on hose bibbs and on all shall be installed at the top and at alternate floor
fixtures to which hoses or tubing can be at- levels of trash and laundry chutes.
f .
Bedpan flushing devices shall be provided in
each patient toilet room and in the soiled
workroom .
9-18 ELECTRICAL REQUIREMENTS
g. Hot water distribution systems shall be ar-
ranged to provide hot water at each fixture (For Chronic Disease Hospitals, see Sec. 8-24.
at ail times .
The following requirements apply only to nursing
h .
Plumbing fixtures which require hot water homes.)
and which are intended for patient use shall
be supplied with water which is controlled to A. General
provide a maximum water temperature of
HOF. at the fixture. 1. All material including equipment, conductors ,
36
FACILITY FOR LONG-TERM CARE
Seat-ion 9-18
C , Distribution Panelboards .
Lighting and appl i
-
ance panelhoards shall be provided for the circuits G. Firc^ Alarms. A manually-operated, electri-
on each floor. This requirement does not apply to cally-supervised fire alarm system shall be in-
emergency system circuits, stalled in each facility that has a total floor area
of more than 5,000 square feet. In multistory
lights and other fixed lights not switched at the terruption of the normal electric supply that could
door shall have switch controls convenient for use affect the nursing care, treatment, or safety of
at the luminaire All switches for control of light-
. the occupants, an emergency source of electricity
ing In patient areas shall be of the quiet op crating shall be provided and connected to certain circuits
type. for lighting and power.
1, Bedroom. Each patient bedroom shall have du- a An emergency generating set, when the nor-
1
plex receptacles as follows: one on each side of mal service is supplied by one or more cen-
the head of each bed (for parallel adjacent beds,
tral station transmission lines.
only one receptacle is required between the beds); b. An emergency generating set or a central
receptacles for lumlnaires, television, and motor- station transmission line, when the normal
ized beds, if used; and one receptacle on another
electric supply is generated on the prem-
wall.
ises.
2. Corridors. Single receptacles for equipment 3, Emergency generating The required set,
such as floor cleaning machines shall be installed emergency generating set, including the prime
approximately 50'0" apart inall corridors Duplex .
mover and generator, shall be located on the
receptacles for general use shall be installed ap- shall be reserved exclusively for
premises and
proximately 50 feet apart in all corridors and with-
in 25'0" of ends of corridors. supplying the emergency electrical system. Ex-
ception: A system of prime movers which are
37
FACILITY FOR WSG-TEm CARE
Section 9-28
(1) Exitways and all necessary ways of ap- hospital feeders so routed, connected, and
protected that a. fault any place between the
proach thereto including exit signs and
exit direction signs, exterior of exits, generators and the hospital will not likely
exit doorways, stairways, and corridors, cause an interruption of more than one of
rooms the hospital service feeders .
(2) Dining and recreation .
38
PUBLIC HEALTH CENTER
10 NURSES' RESIDENCE
NOTE; Requirements for details and finishes, elevators, construction (mcludingfire-resistance), me-
chanical systems, and electrical systems shall be the same as those for long-term care facilities
(Sec sees. 9-14, 9-15, 9-16, 9-17, and 9-18.)
Toilet room: With lavatories in bedrooms--
Rooms: 1 water closet for each 6 beds and 1 lavatory for
Waiting room .
For populations up to 30,000:
Public toilets .
Two examination rooms for maternal and
Office for public health nurses. child health, V.D. and TB clinics.
Staff toilets. Consultation room .
tent of such services, provided in the health center Consultation and viewing room.
39
PUBLIC HEALTH CENTER
tology, and dark field examinations for syph- in health centers and the elbow- or knee-
ilisand storage of biologicals furnished by the action lavatory and sink faucet handles will
State Health Department ,
be required only in clinical rooms of health
Where food control, sanitation and communi- centers .
cable disease work is contemplated another Spare boiler may not be required.
room shall be furnished for this purpose.
Emergency lighting as per local code .
Tuberculosis laboratory.
Director's office, Diagnostic laboratory.
Secretary's office. Incubator room .
40
STATE PUBLIC HEALTH LABORATORY
Sterile room .
Packaging room.
Culture media and reagent preparation room* Blood and blood products:
Glassware cleaning room .
Laboratory: Space and equipment for pro-
Acid cleaning unit. cessing.
Sterilizing room for culture media and clean Sterile room.
glassware only. Office (maybe shared with biologicals de-
Supply room for storage and issue of sterile partment).
supplies, general supplies, chemicals, and Adequate refrigeration (may be shared with
glassware. Adjacent tosterilizingandglass- biologfcals department).
ware cleaning room .
Storage room (may be shared with biologicals
Bulk storage room ,
department),
Janitor service room, Pathology department: Laboratory,
Maintenance and utilities unit; Provisions for Clinical laboratory department: Laboratory.
metal and woodwork, and glassblowing. Virology department: This department shall
Incinerator (animal). be efficiently isolated from oilier labora-
Animal quarters : tories including a separate mechanical ven-
Animal rooms. tilating system:
Room for cleaning and sterilizing cages . Office .
Preparation room for food and bedding, Laboratory: Cubicles for isolation work,
Operating and animal inoculation room. Sterile room ,
Sterilizing room ,
41
STATE PUBLIC HEALTH LABORATORY
to a point above the splash or spray line. the storage of open food containers and dishes
They shall be without cracks, and in con- shall be dust tight.
junction with floors shall be waterproof and Emergency quick acting cold water showers are
free of cracks and spaces which may harbor required at convenient points in chemical labora-
ants and roaches: tories .
Sterilizing rooms .
Emergency lighting and call systems will not be
Culture media rooms. required in laboratories, except as provided for
Glasswashing rooms . by local and State codes .
(a) General .
(1) The extent of the diagnostic, (c) Diagnos tic facilities (In certain types of
.
treatment, and ancillary facilities will be deter- specialized projects, such as mental health clin-
mined by the services contemplated and the esti- ics, the need for radiological and laboratory facili-
mated patient load. ties will be determined by the services contem-
(2) Where the
facility is to be an integral part plated .
}
of a hospital, the requirements of adjunct diag-
nostic and treatment facilities and outpatient de- Radiographic room with adjoining dark room.
partment of general hospital, shall apply. Utility and sterilizing facilities .
(3) Where a diagnostic or treatment center is Laboratory.
not to be an Integral part of a hospital, then the
facilities listedbelow must be provided unless (d) Diagnostic and treatment facilities. If
available for convenient use in an associated health medical examination and/or treatment are to be
facility. included the following shall be added:
(4) The planning of diagnostic or treatment
centers should provide for the privacy of the patient examinational treatment space
Consultation,
during interview, examination, and treatment. is required by the services contemplated .
42
REHABILITATION FACILITIES
REHABILITATION FACILITIES
NOTE: The following requirements for details and finishes shall be applicable lo all types of rehabili-
tation facilities.
using crutches, wheelchairs or wheel stretch- Toilet rooms: Toilet rooms adjacent to patients'
ers. rooms shall permit movement of wheelchairs
Doors: All doors through which patients will pass and shall have handrails on both sides.
shall be at least 3 feet 8 inches wide. Doors at Hardware; Hardware on water closet enclosures
least 3 feet wide will be permitted at individual shall be operable from outside.
toilets adjacent to patienLs bedrooms.
1
cated on a shelf convenient for patients in wheel- shall be provided at all bathtubs .
chairs. Doors to telephone booths are notrec- Showers; Showers should be approximately 4 feet
ommended .
square and should have handrails and curtains .
Drinking fountains: Drinking fountains shall be lo- Curbs shall be omilted ,
43
REHABILITATION FACILITIES
protection of walls against, damage caused by which are accessible to patients shall be sup-
wheelchairs, stretchers and carts. Such a plied with water which is thermostatically con-
wainscot is desirable but not mandatory in trolled to provide a maximum watertempera-
chronic disease hospitals and nursing; homes, ture of 110F, at the fixture.
A spare hojler may not be required for rehabili- Emergency lighting and call systems will not be
tation facilities Incinerators are recom-
,
required in separate rehabilitation facilities
mended in rehabilitation facilities. for outpatients only except as provided for by
Plumbing fixtures which require hot water and local and State codes.
(a) Wherever possible rehabilitation facili- (b) In determining the size of facilities for
ties should be located on the ground tloor. The should be con-
inpatient and outpatient services, it
evaluation and treatment facilities should be
sidered that the outpatient load is usually much
grouped to facilitate integration of the program
and located for convenient access by mpatients and larger than the inpatient load.
outpatients .
15 REHABILITATION FACILITIES
IN A HOSPITAL
(Multiple Disability)
NOTE: Exceptas noted herein, requirements for details and finishes, elevators, construction (includ-
ing fire-resistance), mechanical systems,, and electrical systems shall be the same as those for long-
term care facilities (See sees, 9-14, 9-15, 9-16, 9-17, and 9-18.)
.
Evaluation and treatment facilities shall include Thermotberapy and massage area.
medical facilities and, depending upon the pro- Storage for supplies and equipment.
gram, one or more of the following: psychological, Outdoor exercise area.^-
social or vocational, as listed below, Occupational therapy:
Office and work space for occupational ther-
Conference and library room. apy staff.
If required by program.
44
REHABILITATION FACILITIES (Multiple
Disability) IN A HOSPITAL
Storage space for supplies and equipment. Examination and treatment room.
Facilities for teaching activities of daily living. Floor pantry.
Speech and hearing facilities ;2 Solarium: Provide 25 square feel per bed for
Offices for therapists and space for examination 75 percent of beds on nursing unit.
and treatment, Dining room: Pi ovidc 25 square feet per bed
ArLificial appliance facilities; for 75 percent of 'beds on nursing unit.
Space for fitting and adjustment service. It is recommended that the dining and solarium
Psychological facilities ; area be adjaccntso that they can be combined
Office and workfor psychological testing eval-
-'
into one room for recreational and other group
uation and counseling. activity purposes.
Social service facilities: Toilet facilities:
Office space for private interview and coun- If centralized toilets are provided, a toilet
seling. room for eachsexalaradoof 1 water closet
Vocational facilities: to each 5 beds will be required. One of the
Office and work space for counseling, evalu- water closet enclosures in each toilet room
ation, prevocational programs and placement. should be at least 5 feel by 6 feet to permit
A prevocational area is not required for fa- toilet training.
cilities exclusively serving children under the If toilets provided adjacent to patients' rooms
age of 12 . are not large enough, a separate training
Special education: toilet, at leasts feet by 6 feet, should be
Schoolroom for children if children are in- provided ,
45
REHABILITATION FACILITIES (Multiple
Disability) Iff A HOSPITAL
Rehabilitation gymnasium for children if Minimum patients' room areas'. 100 square
children are included in program. 1 feet per bed in multi-bed patients' rooms .
Office and work space for occupational Examination and treatment room .
Size of nursing unit; Not more than 50 beds, patients' room shall be located on any floor
35 to 40 beds recommended. which is below grade ,
47
SEPARATE REHABILITATION FACILITY (Multiple
Disability) FOR INPATIENTS AND OUTPATIENTS
Size of nursing unit: Not more than '30 beds. Garbage disposal facilities.
Minimum patients' room areas: 100
square feet Day storage room.
per bed in 2-becl and 4-bed room. 80 square Personnel dining space. Provide 12 square
feet per bed recommended for crib room if pro- feet per person; may be designed for multi-
vided ,
ple seatings.
Service facilities in each nursing unit for children: Outpatients' dining facilities as required.
Nurses' station. Janitor's closet.
Nurses' toilet. Housekeeping facilities:
Utility room. Laundry; unless commercial or other laundry
Examination and treatment room. facilities are available, each rehabilitation
Floor pantry. facility shall have a laundry of sufficient ca-
'
Solarium: Provide 25 square feet per bed for pacity to process full 7 days laundry in work
75 percent of beds on nursing unit. week and contain the following areas:
Dining room: Provide 25 square feet per bed Sorting area .
by 6 feet, should be
toilet, at least 5 feet plumbing is recommended,
provided. Employees' facilities:
Bedpan facilities . Female staff and volunteers lockers:
Bathing facilities : Locker room .
Adequate refrigeration.
48
SEPARATE REHABILITATION FACILITY (Multiple
Disability) FOR OUTPATIENTS ONLY
NOTE: Except as noted herein, requirements for details and finishes, elevators, construction (includ-
ing fire-resistance), mechanical systems, and electrical systems shall be the same as those for long-
term core facilities . (See sees. 9-14, 9-15, 9-16, 9-17, and 9-18.)
Physical therapy:
Office and work space for physical therapy Dietary facilities .2
staff. Housekeepingfacilities: Clean and soiled linen
Rehabilitation gymnasium for adults. storage .
Storage space for supplies and equipment. Toilet and shower room .
49
SEPARATE EEUABILITATIOU FACILITY (Multiple
Disability) FOR OUTPATIENTS ONLX
The requirements for a single disability reha- the single disability rehabilitation facility will fol-
bilitation facility will be dependent upon the spe- low the pattern established for the multiple dis-
cific project program, which shall include, how-
ability rehabilitation facility. In other respects
ever, services in the four basic areas- -medical,
the general standards set forth herein shall apply.
psychological, social and vocational. In general
50
U S GOVERNMENT PRINTING OFFICE I 1969 0334-067