Drawing 4

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Power input Normal 27.

43 Vdc

External voltage input Lightning Arrester


Lightning strike Direct
problem counter did not increase

PHRA-1A2B I/O Pack


Power supply damaged Input normal 27 Vdc
Problem

Indirect Induction

Possible solution:
1. Replace damaged board
2. Make sure LA Counter working properly
Convection 3. Review JSP grounding & earthing system
4. Study on possibility of spark gap & surge protection
device installation on MarkVIe panel grounding
5. TBD (Discussion)
Voltage elevation

Illustration
Check all BQ field instrument:
1. winding V temp CTF1
Normal all tight and
Bad termination
proper
2. GB Vib CTF1
3. Oil temp CTF1
4. GB Vib CTF2
5. Bearing DE temp CTF4
6. Bearing NDE temp CTF4
7. Winding U temp CTF4
All normal, No 8. Winding V temp CTF4
Bad field device 9. Winding W temp CTF4
abnormalities
10. Oil temp CTF4