1305
1310
Part A: Engineering APPENDICES
APPENDIX 5.7 DESIGN EXAMPLE FOR UPFLOW ANAEROBIC SLUDGE
BLANKET REACTOR
1 PROBLEM.
Design an upflow sludge blanket reactor for an average flow of S MLD of wastewater with the
following data:
1, COD of wastewater 400 mg/l
2. Design hydraulic residence time = 6 hrs
3. Design COD loading = 1-2kg CoDim'd
4, Velocity of rise of wastewater in the reactor through sludge bed = 0.75 mr
5. Velocity of wastewater in settling chamber < 1.5 mbr
6. Flow area covered by cach inlet = 1.2m
2 SOLUTION
2.1 DETERMINE THE DIMENSIONS OF UASBR
Volume of UASBR 5,000 * (6/24) 1,250 m?
Actual volumetric organic loading = [(5*400)/1,250] kg COD/m'd
1.6 [OK as itis between 1-2 kg COD/m'd]
Height of wastewater in reactor Rise velocityHRT
0.756 45m
Area of Reactor = [1250/4.5] 277.8 m?
Provide two reactors of 11.8 m*11.8 my5.25 m (height)
2.2 NO.OF INLETS
Assume that each inlet can serve 2.0 m? of flow area,
[138.92]=70
23 AREA OF SETTLING CHAMBER
Number of inlets in each reactor
Assuming a velocity of 1.2 mvbr in the settling zone
Area of settling chamber in each reactor = [5,0001(224%1.2)] = 86.8 m*
Final Draft Ast