Solutions Powerlogic Systems Terminology

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

POWERLOGIC

Volume 2 Issue 2 Solutions


In This Issue
we introduce and
POWERLOGIC System Terminology
discuss terms that
relate to harmonics. The Problem Contrast the sinusoidal waveforms in figure 1
A better understand- with those in figure 2. These are typical
ing of these terms Some POWERLOGIC system users— distorted voltage and current waveforms for
gives you greater unfamiliar with terminology or uncertain a pulse-width modulated (PWM) variable
ability to solve about the practical application of a quantity— frequency drive.
your harmonics have asked questions about certain power
problems. quality quantities. This issue of POWERLOGIC
Solutions describes a case study, related to power
factor, and defines additional terms that
commonly trigger inquiries.
We received a call from a customer who was Voltage
concerned about different power factors he Current
measured on two motors driving identical fan
loads. One was a two-speed induction motor, Figure 2: Pulse-width modulated (PWM) drive
voltage and current.
the other was an induction motor controlled
by an adjustable speed drive. Circuit monitors
connected to each load correctly measured the Figure 3 shows the fundamental (60 Hz)
same real power (kW), but measured strikingly component of the drive current compared to
different power factors. the total current:

Key Concepts and Terms


Traditionally, power factor represents the
degree to which voltage and current to a load
are out of phase. Calculating power factor Fundamental Current
from this perspective involves taking the cosine Total Current
of the angle (Θ) by which current lags voltage.
The waveforms in figure 1 are typical of Figure 3: PWM drive current including harmonics
current and voltage to an induction motor. (total current) and with harmonics removed
(fundamental current).

Θ PF = cos Θ Comparing the phase relation-


ships in figures 2 and 3, one
can see that the voltage and
fundamental current are
almost in phase; therefore,
Voltage
cos Θ ≈ 1, and you would also
Current
expect power factor to be 1.
Reading power factor from
Time (msec) the front panel of a circuit
monitor, however, indicates a
Figure 1: Θ represents the cosine of the angle by which current
lags voltage.
POWERLOGIC
Solutions
power factor of 80%. Does this mean the that capacitors may actually reduce total power
circuit monitor is incorrectly reporting power factor when harmonics are present.
factor? After all, PWM drives are touted as
having high input power factor. The truth is,
PWM drives do have high input power Waveform Terminology
factor — input displacement power factor.
System Manager Software can acquire a four-
The general definition for power factor is the cycle waveform capture from any circuit
ratio of real power to apparent power: monitor model 2250 or above. Double-click
the title bar of any waveform, and a data block,
PF = kW shown in figure 4, displays.
kVA
The values listed in the data block provide
This formula is equivalent to cos Θ only under valuable information about its associated
purely sinusoidal conditions, that is, no waveform. Terms in the data block are
harmonics are present. When power factor is described in the following paragraphs.
calculated using total (including harmonics)
real and apparent power, the result is the total
power factor (PF),
which is displayed on Title bar Data block
the front panel of
circuit monitors.
2 When only the
fundamental
component of real
and apparent power
are considered, the
result is displacement
power factor (dPF).
Like inductive
current, which
produces lagging
power factor,
harmonics reduce the
capacity of the power
system. The reduced
POWERLOGIC capacity is partly due
Solutions is a bimonthly to an increase in the Figure 4: Screen capture from System ManagerTM Software showing the current
effective value of the of a switch-mode power supply (typically found in most single-phase electronic
publication produced by loads). Double-click the title (“Phase A Current”) to display the data block.
current when
Square D Company’s
harmonics are present.
Power Management Another reason is increased thermal stress, due Fundamental value of voltage or current
Operation. Each issue to resistive skin effect, that harmonics impose corresponds to the portion of the signal at the
presents a problem that on transformer windings and conductors. power frequency. Usually the power frequency
might occur in typical is 60 Hz, but may be 50 Hz (Europe) or
Note that capacitors alone cannot improve the
power systems, and
component of total power factor caused by 400 Hz (aviation).
offers guidance on how harmonics. In fact, you may recall, from RMS value is the effective value, or equivalent
to solve it. POWERLOGIC Solutions Volume 1, Issue 4, dc value, of the voltage or current. Circuit
POWERLOGIC
Solutions
monitors are true rms sensing devices. Many rather than fundamental current:
hand-held meters are peak sensing or averaging XRMS-H
meters that are calibrated to report in rms. thd =
XRMS
These meters are very inaccurate when
measuring highly distorted signals. A peak
The European thd value can be logged in the
sensing meter will report an error on the order
circuit monitor on-board data logs, viewed on
of 200% when measuring load current such as
the circuit monitor front panel using a
that shown in figure 4.
diagnostic register read, or viewed using
RMS-H is the effective value of the harmonic System Manager software.
portion of voltage or current. This quantity
Total harmonic distortion indicates the degree
provides information about the actual level
to which a voltage or current signal is distorted.
(in volts or amps) of voltage or current
For example, the THD of the PWM drive
harmonics.
current in figure 2 is 57%. IEEE Standard 519-
Peak value of voltage or current is the 1992, IEEE Recommended Practices and
maximum, or minimum, crest value of the Requirements for Harmonic Control in Electrical
waveform. Equipment damage is possible if the Power Systems, recommends limits of harmonic
peak value becomes too great, even if the rms distortion in power systems. The standard
value is within allowable limits. recommends a limit of 5% total harmonic
distortion of voltage for general systems. Limits
CF (crest factor) of voltage or current is the on current distortion are based on demand
ratio of peak to rms values. Crest factor is equal current—usually the average current for 3
to 1.414 for a purely sinusoidal signal. The demand billing from the previous 12-month
load current of a desktop computer can have a period. Depending on the relative size of the
crest factor exceeding three (illustrated in figure load, current distortion limits vary from 5–
4), while some adjustable speed drives have 20%. Distortion is measured at the electrical
crest factors less than 1.4. Some manufac- interface between the utility and customer,
turers rate equipment, particularly power referred to as the point of common coupling
conditioners, at a maximum crest factor (PCC). IEEE standards are now being written
of current. to recommend limits for single-phase
ASUM is the arithmetic sum of the magnitudes electronic devices.
of the fundamental and individual harmonics TIF/IT is the telephone influence factor and
as opposed to the vectorial sum. IT product (which equals the TIF of the
THD (total harmonic distortion) is defined for current times the rms magnitude of the
both voltage and current. It is the ratio of current). Both terms are used to assess the
harmonic content to the fundamental: interference of power distribution circuits with
audio communications circuits. The value for
XRMS-H
THD = voltage waveforms is TIF, a variation of THD
X1 that weighs each harmonic according to its
where X is voltage or current. audible effect on the human ear. For current
waveforms, the value given is the IT product.
The above equation is the value displayed on
the front panel of the circuit monitor. Another The Harmonics (RMS) window lists the rms
variation of total harmonic distortion (thd), magnitude of individual harmonics from the
used widely in Europe, normalizes the total fundamental to the 31st. Distorted voltages
harmonic current to the total rms current and currents can be represented by a series of
POWERLOGIC
Solutions
sinusoidal signals whose frequencies are harmonic content of multiple loads on a
multiples of some fundamental frequency common premise wiring system), a transformer
(usually 60 Hz). For example, the 5th must be fully loaded to accurately measure the
harmonic represents the 300 Hz (five times required K-factor rating.
60 Hz) component of the distorted signal.
These values are added vectorially (square root Compared with a derated transformer, a
of the sum of the squares) to calculate RMS-H properly chosen K-factor transformer can
and RMS. significantly reduce load-generated harmonics.
In fact, a transformer with 3%–5% impedance
Power Terminology will self-limit the K-factor at full load to
between 4 and 6. See POWERLOGIC Solutions
Harmonic power is determined by the circuit
Volume 2, Issue 1 for more detail.
monitor and can be useful for evaluating the
source of harmonics flowing in a power system.
Harmonic power is the difference between Other Misunderstood Terms
total power and fundamental (60 Hz) power. A Apparent current is a unique value, related to
negative value indicates harmonic power flow crest factor, that is reported by the circuit
out of the load, a positive value indicates monitor. Apparent current is defined as
harmonic power flow into the load. Ipeak
Iapp =
Harmonic power flow out of the load indicates √2
the load is a source of harmonics. The load
could be a variable frequency drive or battery This quantity reflects the value that would be 4
charging station. Harmonic power flow into reported by a peak-sensing rms-calibrated
the load indicates a sink for harmonics. ammeter or solid-state trip unit. Trip units that
Capacitors and motors are examples of measure peak current may operate prematurely
harmonic sinks, which appear as a low when serving non-linear loads. Comparing rms
impedance at harmonic frequencies. current with apparent current indicates the
level of error involved with this type of
K-factor relates the heating effect of a distorted protective device.
current in a transformer to a sinusoidal current
with the same rms magnitude. The term Since the introduction of the circuit monitor,
K-factor was coined by Underwriters harmonic factor has become synonymous with
Laboratories to describe a transformer’s ability THD. Some definitions express harmonic factor
to serve nonlinear loads without exceeding as a percentage, like THD, while others express it
rated temperature rise limits. in per unit. The circuit monitor defines harmonic
factor as total power factor divided by
Standard K-factor ratings for dry-type displacement power factor:
transformers are 4, 9, 13, 20, 30, 40, and 50.
PF
Greater K-factor indicates increased harmonic HF =
current capability. The use of K-factor rated dPF
transformers has become increasingly popular If no harmonics are present, this value will be 1.
as the number of electronic loads continues However, as voltage and current become more
to increase. distorted, the harmonic factor decreases.
Voltage unbalance is not related to harmonics as
While the K-factor of a given load is easily
are the previous terms, but it does manifest
measured, determining the required K-rating of
itself in a similar fashion. Like harmonics,
a transformer is not as simple. Transformer
voltage unbalance causes excessive motor
K-factor is defined only at rated load. Because
heating. Circuit monitors calculate voltage
harmonics from multiple sources are not 100%
additive (diversity and attenuation reduce the
POWERLOGIC
Solutions
unbalance for each phase, using the following
formula: About the Power Management
Vφ – VAVG Services Group
VUMB =
VAVG
From hardware and software, to
Total unbalance is reported as the maximum systems and solutions, the Power
phase unbalance. For example, phase voltages Management Services Group
to an induction motor measured VAB = 459V,
provides full service power
VBC = 466V, and VCA = 462V. The average
monitoring and control.
voltage is 462V. Therefore phase voltage
unbalance equals –0.7%, 0.9%, and 0%; and Systems — Experienced applica-
total unbalance is 0.9%. tion engineers integrate hardware,
software, communications, and
When voltage is unbalanced, a large negative
reports that allow customers to
sequence current flows in the stator windings
monitor important power parameters
of a motor. The resulting flux rotates opposite
the rotor, inducing a voltage that produces a from a central workstation.
120 Hz current in the rotor. Resistive skin Solutions — Power Management
effect increases the rotor resistance, producing Services will also monitor and
excessive heat. A 3% voltage unbalance can analyze system data to solve power
cause a motor to run 25% hotter, shortening quality problems, recommend ways
the expected 20-year life. to manage energy costs, or train 5
Current unbalance is computed in the same way customers on power quality and
as voltage unbalance. Current unbalance, energy management issues.
which produces voltage unbalance, may For additional information about
indicate a need to rebalance single-phase loads Power Management Services, contact
or a problem within a three-phase load. Donna Oakley in LaVergne,
Tennessee at (615) 287-3332.
Conclusions
As in the case of power factor under non-
sinusoidal conditions, you must know the
correct terminology when assessing or
discussing the quality of power within your
facility. The solution for low total power factor
of a PWM variable frequency drive is quite
different than for the low displacement power
factor of an induction motor.
In this issue, we discussed some of the
commonly used terms associated with power
quality. Future issues of POWERLOGIC
Solutions will discuss these and other power
quality related issues. If you need help
correcting power factor, investigating
harmonics or other power quality phenomena,
or managing energy usage, Power Management
Services engineers can provide the solutions.
POWERLOGIC
Solutions
Test Your Power Quotient
The following true-or-false questions will test life expectancy.
your understanding of the information in efficiency and shortening the
Volume 2, Issues 1 and 2 of this newsletter. The ing temperature of ac motors, reducing
first three questions cover information from the 6) True. Voltage unbalance increases the operat-
first issue. If you haven’t received a copy of this placement power factor will be 1.
issue, call (615) 287-3332. The answers are in the factor will be less than 1, although the dis-
right-hand column. 5) False. If harmonics are present, the total power
4) True (page 2).
1) Neutrals sized to the same ampacity as phase causes an increase in neutral current.
conductors are typically overloaded. (above 32% THD), balancing loads actually
2) A transformer with a K-factor rating greater 3) False. For highly distorted load currents
than 13 is seldom required. exceed 13.
3) Balancing phases always reduces neutral ments at the transformer terminals will rarely
current on three-phase systems with a 2) True. When fully loaded, K-factor measure-
shared neutral. of the cases described.
4) When power factor is calculated using NEC found overloaded neutrals in only 5%
6 only the fundamental components of 1) False. An ad hoc committee formed by the
real and apparent power, the result is
displacement power factor.
5) If fundamental voltage and current are in
phase, the total power factor is always 1.
6) 3% voltage unbalance causes ac motors to
run 25% hotter.

SQUARE D, , and POWERLOGIC are Registered Trademarks of Square D Company.


System Manager is a Trademark of Square D Company.

 1996 Square D All Rights Reserved


Order No. 3000HO9602 June 1996 7M DL 6/96

You might also like