Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Midea Domestic Pool Type


Heat Pump Water Heater
Technical Manual

Applicable Model:

LRSJ-60/NYN1

LRSJ-80/NYN1

LRSJ-120/NYN1

LRSJ-140/NYN1
Midea reserves the right to discontinue, or change specification or designs at any time without
notices and without incurring obligations.

1
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Content
1. General Information ........................................................................... 3

1.1 Measurements................................................................................................................3

1.2 External appearance......................................................................................................3

1.3 Nomenclature .................................................................................................................3

2. Specification & performance ............................................................ 4

2.1 Features..........................................................................................................................4

2.2 Refrigerant circuit ..........................................................................................................5

2.3 Unit outlook ....................................................................................................................5

2.4 Specifications ................................................................................................................6

2.5 Performance diagram ....................................................................................................8

2.6 Wiring diagram.............................................................................................................16

2.7 Installation ....................................................................................................................18

2.8 Trial run ........................................................................................................................26

2.9 Maintenance .................................................................................................................26

2.10 Trouble shooting........................................................................................................27

2.11 Function ......................................................................................................................29

2.12 Wire controller ...........................................................................................................30

2.13 Spot check .................................................................................................................33

2.14 Accessories ................................................................................................................33

2.15 Resistance characteristic of temperature sensor ...................................................34


Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

1. General Information

1.1 Measurements

Model Net/Gross weight (kg) Dimension (mm, W×H×D) Power Supply


LRSJ-60/NYN1 64/73 1015×705×385 220-240V~, 50Hz, 1Ph
LRSJ-80/NYN1 66/75 1015×705×385 220-240V~, 50Hz, 1Ph
LRSJ-120/NYN1 75/85 1050×855×315 220-240V~, 50Hz, 1Ph
LRSJ-140/NYN1 75/85 1050×855×315 220-240V~, 50Hz, 1Ph

1.2 External appearance

1.3 Nomenclature

L RSJ - 60 / N Y N1

Refrigerant Type N1:R410A

Available for Pool

Water Cycle without Water Pump

Heating Capacity (Unit: ×100)

Midea Heat Pump Water Heater

Unit with Cooling Function

3
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2. Specification & performance

2.1 Features

 Titanium-tube heat exchanger

1. Titanium-tube heat exchanger has exceptional corrosion resistance, perfect anti-fouling

performance, high temperature resistance and microbe resistance.

2. High energy efficiency.

Titanium-tube heat exchanger LCD display

 Safety

1. Realize isolation between water and electricity. No electric shock problem.

2. No fuel tubes and storage, no potential danger from oil leakage, fire, explosion etc.

 Environmental protection

Environment friendly refrigerant R410A is used.

No discharge of poisonous gas. No pollution to atmosphere and environment

 Easy operation and automatic control

The system can be controlled simply through the wired controller.

Machine running parameter and the state can be checked quickly from the LCD display.

 Automatic start-up and shutdown, automatic defrosting. Save you much extra operation.

 Convenient installation and maintenance

The quadrate type can be easily installed in a corner of the verandah even if it’s very narrow.

 All-the-weather running

Within the temperature range from -7 to 38℃, it will not be affected by night, overcast sky, rain and

snow.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

2.2 Refrigerant circuit

 Compressor: Compressors are supplied by GMCC. PA145G1C-4FT1 is used in LRSJ-60/NYN1;

PA200X2CS-4KU1 is used in LRSJ-80/NYN1; PA290X3CS-4MU1 is used in LRSJ-120/NYN1;

PA330X3CS-4MU1 is used in LRSJ-140/NYN1.

 Evaporator: Copper tube and aluminum fin type heat exchanger.

 Titanium-tube heat exchanger: Titanium-tube heat exchanger is use for heat exchange between

refrigerant and water.

 Fan: Axial fan with two speeds. The motor is supplied by Welling.

 High Pressure Switch: When the discharge pressure of compressor is 4.4Mpa or higher, the
protection switch will be triggered, and if the discharge pressure is down to 3.2MPa, the protection

switch will be recovered.

2.3 Unit outlook

5
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.4 Specifications

Model LRSJ-60/NYN1 LRSJ-80/NYN1 LRSJ-120/NYN1 LRSJ-140/NYN1


Power supply Ph, V, Hz 1, 220-240~, 50

Water outlet Heating mode ℃ 20℃~35℃, default 28℃

Temperature Cooling mode ℃ 10℃~30℃, default 28℃

Capacity kW 6.00 8.00 12.00 14.00


Input kW 1.150 1.518 2.400 2.550
Water
Outdoor
heating ℃ -7~38 -7~38 -7~38 -7~38
ambient Temp.
COP kW/kW 5.22 5.27 5.00 5.49
Capacity kW 4.00 5.80 8.40 10.35
Input kW 1.25 1.50 2.40 2.90
Water
Outdoor
cooling ℃ 15~43 15~43 15~43 15~43
ambient Temp.
EER kW/kW 3.20 3.87 3.50 3.57
Max. current A 6.3 8.0 13.7 16.0
Max. power kW 1.45 1.90 3.30 3.50
Dimension
mm 1015×705×385 1015×705×385 1050×855×315 1050×855×315
(W×H×D)

Main unit Packing


mm 1095×840×445 1095×840×445 1160×980×410 1160×980×410
(W×H×D)

Net/gross weight kg 64/73 66/75 75/85 75/85

Outdoor noise level dB(A) 58 58 58 58


Refrigerant type/quantity kg R410a/1.0 R410a/1.25 R410a/1.6 R410a/1.85
Refrigerant design pressure MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
Water side heat exchanger Titanium-tube heat exchanger
Throttling type Capillary
Model PA145G1C-4FT1 PA200X2CS-4KU1 PA290X3CS-4MU1 PA330X3CS-4MU1
Type Rotary Rotary Rotary Rotary
Brand GMCC GMCC GMCC GMCC
Capacity kW 3.580 4.920 7.180 8.150
Input kW 1.240 1.670 2.430 2.760
Rated
A 5.82 7.81 11.40 13.10
current(RLA)
Compressor
Locked rotor
A 26.7 34.5 61 63
Amp(LRA)
Thermal Internal Internal Internal
Internal
protector (UP3QE0391-T39) (UP14SE5145) (UP14SE5145)

Capacitor 35μF/440-450V 50μF/440-450V 50μF/440-450V 55μF/450V

Refrigerant oil ml 400 750 950 1100


Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Model YDK85-6 YDK85-6 YDK75-6H-1 YDK75-6H-1


Brand Welling Welling Welling Welling
Input W 160/85 160/85 168/146 168/146
Speed r/min 835/470 835/470 877/749 877/749
Insulation
Fan motor B B B B
class
Safe class IPX4 IPX4 IPX4 IPX4
Locked rotor
A 1.15 1.15 1.414 1.414
Amp(LRA)
Capacitor 5μF/450V 5μF/450V 5μF/450V 5μF/450V
Number of
2 2 2 2
rows
Tube pitch(a)
mm 22×19 22×19 22×19 22×19
× row pitch(b)
Fin spacing mm 1.6 1.6 1.6 1.6
Evaporator Fin type Hydrophilic aluminum
coil Tube dia. mm ø7.94
Type Inner groove copper tube

Coil L × H mm 820×660 820×660 766×792 766×792

Number of
5 5 8 8
circuits

Water inlet pipe Φ50 Φ50 Φ50 Φ50

Water outlet pipe Φ50 Φ50 Φ50 Φ50


Water
pipeline Water circulating pipe Φ25 Φ25 Φ25 Φ25

Max.
MPa 0.4 0.4 0.4 0.4
pressure
3
The volume Min. value m /h 0.8 0.8 1.5 1.5

flow of water Max. value


3
m /h 20 20 20 20

Controller KJRH-90B/E
Loading
20'/40'/40H Pcs 52/108/162 52/108/162 56/116/116 56/116/116
Quantity
Notes:

1. The test conditions:


Water Heating:outdoor temperature 24/19℃(DB/WB), inlet water temperature 27℃,outlet water temperature
29℃
Water Cooling: outdoor temperature 35/24℃(DB/WB), inlet water temperature 27℃, water flow volumn have
been defined.
2. The noise of this unit is tested in semi-noisedamping lab as per Q/MDNT 005-2009 national requirments, which
error value is about ±3dB(A).
3. The specification may be changed for product improvement, please refer to the nameplate.

7
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.5 Performance diagram

2.5.1 Unit capacity and energy efficiency diagram in heating mode

Model: LRSJ-60/NYN1

Notes:

The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Model: LRSJ-80/NYN1

Notes:

The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.

9
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Model: LRSJ-120/NYN1

Notes:

The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Model: LRSJ-140/NYN1

Notes:

The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.

11
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.5.2 Unit capacity and energy efficiency diagram in cooling mode

Model: LRSJ-60/NYN1

Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 2.6m /h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Model: LRSJ-80/NYN1

Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 3.5m /h.

13
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Model: LRSJ-120/NYN1

Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 5.0m /h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Model: LRSJ-140/NYN1

Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is5.8m /h.

15
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.6 Wiring diagram

Model: LRSJ-60/NYN1& LRSJ-80/NYN1


Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model: LRSJ-120/NYN1& LRSJ-140/NYN1

17
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.7 Installation

2.7.1 Transport

 Choose the correct way of conveying the equipment.

 Try to transport the equipment with the original package.

 The main unit should be put down gently during transportation, and main unit should not be

leaned more than 45 degree.

 Guard boards should be applied to avoid scratching and deforming of the unit surface.

2.7.2 Main unit installation

Location of outdoor installation

 After move onto installing site, please confirm the main unit is placed in horizontal.

 Do not install the heat pump close to inflammable gas source.

 Do not install the heat pump close to a road or path to protect the appliance against mud

splashing.

 Avoid places that are subject to strong winds, in particular if the wind blows against the

appliance’s air outlet.

 Ensure enough space for installation and maintenance.

 A distance of no less than 200mm should be preserved between the bottom of the outdoor

unit and the ground or bracket for the installation of the duct pipe.

 If the unit installed in an underground chamber, an indoor room or other hermetic place,

pay attention to where surrounding air, as well as which air exhaust and air circulating

system. For every signal unit, which circulating air volume shall no less than 2400m3/h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Space of foot screw bolts (unit: mm)

Model A B C D E F

LRSJ-60/NYN1
610 390 170 1015 385 705
LRSJ-80/NYN1
LRSJ-120/NYN1
590 333 165 1050 315 855
LRSJ-140/NYN1

19
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.7.3 Water system piping

Pipe installation notes


 During installation of pipe connection, make sure no dust or other impurities is intruded into

the pipeline system.

 Water inlet and outlet pipes can be installed as long as the heat pump water heater has

been fixed.

 Thermal insulation materials should be employed to seal up water outlet and inlet pipes.

 The water inlet and outlet pipeline cannot be installed until the water heater is fixed well.

 Before operation, please confirm that the specifications of connective pipes are correct,

and thermal insulation layer have been wrapped on pipes. It requires that all pipes have

been sealed up, and no water leakage has been detected.


Connecting diagram for the swimming pool water heater

No. Name Connective pipe specification

a Water outlet of main unit PVCΦ50

b Water inlet of main unit PVCΦ50

c Drain connector PVCΦ25

Hydraulic connections
 Connect the appliance’s PVC Φ 50 hose water inlet and outlet (according to label

instructions) to the renewable fittings provided with the heat pump.

 Connection is established with a by-pass on the pool filtration circuit after the filter and

before the water treatment device.


Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

Hydraulic circuit test pressure: 0.3 MPa. Hydraulic circuit operating pressure: 0.15MPa.

Average water flow 5.5m3/h-pressure drop 0.022MPa.

Water pump selection


Model Water flow Recommend flow
3 3
LRSJ-60/NYN1 0.8~20m /h 3m /h
3 3
LRSJ-80/NYN1 0.8~20m /h 4m /h
3 3
LRSJ-120/NYN1 1.5~20m /h 5m /h
3 3
LRSJ-140/NYN1 1.5~20m /h 5.8m /h
Water treatment
In order to use our appliances under the best conditions, the following parameters must be
respected:
 Maximum concentration of free chlorine is 2.5 mg/L.

 Maximum concentration of total bromine maximum is 5.5mg/L.

 PH value is between 6.9 and 8.0.

 If chemical or electrolyte disinfection systems are introduced, the installer and user must

contact the supplier to ensure they are compatible with our materials. These systems must

be installed after the heating system.

Item Requirements

Free chlorine ≤2.5 mg/L

Total bromine ≤5.5 mg/L

PH value 6.9<PH<8

21
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.7.4 Electric connection

 The air source water heater shall have a specialized power supply, which in compliance

with rated voltage.

 If the unit needs to be installed on a metal part of the building, electric insulation must be

performed, and the installation must meet the relevant technical standards of electric

devices.

 Power supply circuit of the air source water heater should be earthed, the power cord

should be connected with the external earthing line in reliable state and all the external

earthing cables are effective.

 Wiring must be performed by professional technicians in accordance with the circuit

diagram.

 Power cord and the signal cable shall be laid out orderly and separately.

 The unit is not equipped with power cord. User could select power cable by reference to

power supply specifications. Shield wire must be employed for signal wire.

 Select the power supply capacity and wire size according to the Design Manual. The size

of the power cable of the unit should be bigger than that of ordinary motors.

 All wiring should be finished, before power is switched on to the unit, be confirm all

connection are correct.

 Check the subscriber grounding is effective.

Specifications of power cable

The power cable is as follows when power deliver to a certain wire individually (no power supply

device is used).
2
Min. wire size(mm )
Item (Metal pipe & synthetic resin Manual switch(A)
Power
pipe wire) RCCB
supply
Model Size (Continuous Ground
Capacity Fuse
length:≤30m) wire
LRSJ-60/NYN1
2.5 2.5 ≥20 16
LRSJ-80/NYN1 220-240V~, 30mA ≤
LRSJ-120/NYN1 50Hz 0.1sec
4 4 ≥32 25
LRSJ-140/NYN1
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

 No power supply device is used; the specifications depend on connected unit’s actual

status.

 Power supply device is used; the specifications can be derived from the above table

according the total horsepower of heat pump water heater.

 The power cord type designation is H07RN-F.

 Wire size and continuous wire length in the table above only available for the case of the

voltage decreasing range not exceeds than 2%.

 If the continuous wire length value larger than the one of the table, please choose its size

in compliance with the relevant rules.

Power supply device

Note: Although there is a leakage protector in the electric control box of the unit, for the

security reason, it is required that a leakage protector should be installed in the external

electric control box of the unit according to the requirement on the above diagram.

Cable diameter selection


 The power supply wiring refers to the wiring to the main line (a) from deconcentractor and

the auxiliary wiring (b) leading from deconcentrator and connected to the power supply

equipment. Please select the cable diameter according to the following methods:

 Diameter of the main line (a):

Diameter of the main line (a) is conducted by the horsepower of the water heater and

power cable table.

 Diameter of the wire (b)

Diameter of the wire (b) connected from deconcentrator to power supply device be

conducted by the horsepower of the water heater and power cable table:

23
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Electrical connection diagram

 Do not reverse connections of low voltage electric signal wire with heavy electric wire,

otherwise some of electric control elements will burned out.

 The photo of main control board.

PCB I/O Ports description

Code Part name Code Part name

N.C. No connect Tp Temperature sensor of compressor air exhaust

Tout Outlet water temperature sensor Pro_H High-pressure protect switch

T3 Heat-exchange temperature sensor Pro_L Low-pressure protect switch (reserve)

T4 Outdoor ambient temperature sensor Pro_Hyd.O Waterflow switch

T6 Inlet water temperature sensor


Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

25
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.8 Trial run

Checking list before trial-running:


 All the installation is complete.
 Water heater is installed correctly.
 The pipelines and wiring are correct.
 The accessories are installed correctly.
 The heat insulation is perfect.
 The ground wire is connected correctly.
 The power voltage is consistent with the rated voltage of the heater.
 No obstacle at the air inlet and outlet of the unit.

Trial operation check


 Whether the switch of the controller is normal.
 Whether the functional buttons of the controller are normal.
 Whether the indicators light up normal.
 Whether the manual operation buttons are normal.
 Whether the unit operates normally in the heating mode.
 Whether the outlet water temperature is normal.
 Whether there is vibration or abnormal sound when operating.
 Whether there is refrigerant leakage.

2.9 Maintenance

Before leave the unit idle for a long period, please make sure the following:
 Vacuum air completely inside the heat exchanger and water at pipelines, and turn off all
valves.
 Check and clean the internal components of the unit at a regular base.

After leave the unit idle for a long period, please check the following:
 Inspect whether the air intake orifice or air outlet is blocked periodically. If any, remove the
foreign substance to let the air flow fluently.
 Check whether pipes, valves have damaged or blocked, whether connection sites have
leakage. If any, fix it properly.

Start the unit after a long period out of service


Start-up the unit after out of service for a long period (includes drive up a unit at the first
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

time), you would see rust mix up water in red, flow out from tap. That is normal, just keep
draining and the rust will disappear after a while.

Before asking for service or repairing, check the following points:


Condition Cause
 Air supply motor stop automatically to defrost.
 At the beginning and the end of defrost process, sound is
give out in motor valve.
 White aerosol or globule  During the process of just after have stopped, sound like
is give out water flow occur, which will be amplified at the first 2~3
Normal operation
 Make sound of “hiss” minutes, this is caused by the process of refrigerant current
every now and then or water.
 Slight “hiss” is caused by heat exchanger as temperature
changes. The sound give out because of heat expands and
cold contracts of heat exchanger.
 Stop operation or start up  Check the timer whether it is correctly set
automatically  Detect antifreezing mode is operating
 Whether the power is cut
 Whether the manual power supply switch is off
Please check
 Whether fuse is broken
that again  No operate
 Whether the protection device works (Operation lamp is
lightened)
 Whether it is the time set(Operation lamp is lightened)
 Inefficient heating Whether the inlet and outlet of heat pump units is blocked

In case of the flowing malfunctions, please cut off the manual power switch and contact the local
dealer or after service center:
 The fuse was burnt out frequently or the earth leakage protective device was broken up
frequently.
 Only the red indication will be flashed.

2.10 Trouble shooting

Code Explanation Solution


Check whether the communication wire is damaged.
Check whether the communication wire is correctly connected to the
Outdoor unit and wire controller motherboard.
E2
communication error Check whether voltage provided is too low.
Check whether the signal of communication wire is in strong
electromagnetic interference.
Check whether the Tout temperature sensor is damaged.

Outlet water temperature Check whether the Tout temperature sensor is correctly connected to the
E3 motherboard.
sensor Tout error
Check whether the signal of Tout sensor is in strong electromagnetic
interference.
Check whether the T6 temperature sensor is damaged.
Inlet water temperature sensor
E4 Check whether the T6 temperature sensor is correctly connected to the
T6 error
motherboard.

27
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Check whether the signal of T6 sensor is in strong electromagnetic


interference.
Check whether the T3 temperature sensor is damaged.

Evaporator pipe temperature Check whether the T3 temperature sensor is correctly connected to the
E5 motherboard.
sensor T3 error
Check whether the signal of T3 sensor is in strong electromagnetic
interference.
Check whether the T4 temperature sensor is damaged.

Ambient temperature sensor T4 Check whether the T4 temperature sensor is correctly connected to the
E7 motherboard.
error
Check whether the signal of T4 sensor is in strong electromagnetic
interference.
Check whether the water pump is damaged.
Shut down the unit and start until water in pipe flow fluently.

Waterflow switch error Check whether the waterlow switch is correctly connected to the
E9
motherboard.
Check whether the installation direction of waterlow switch is correct.
Check whether the waterlow switch is damaged.
Check whether the Tp temperature sensor is damaged.

Discharge pipe temperature Check whether the Tp temperature sensor is correctly connected to the
EE motherboard.
sensor Tp error
Check whether the signal of Tp sensor is in strong electromagnetic
interference.
Check whether the high pressure protection switch is damaged.
System high pressure protection
P0 ≥4.4MPa active, Check whether the refrigerant pipes is blocked
≤3.2MPa inactive Check whether the high pressure protection switch is correctly connected
to the motherboard.
Check whether the dial code S2 is correct.

Compressor current overhigh Check whether the voltage supplied is in the accepted voltage range.
P4
protection Check whether compressor is damaged.
Check whether the refrigerant pipes is blocked
Check whether the T3 temperature sensor is damaged.
Evaporator pipe temperature Check whether the T3 temperature sensor is correctly connected to the
P6
overhigh protection motherboard.
Check whether the fan is running normally.

Check whether the Tp temperature sensor is damaged.


Discharge pipe temperature
PF Check whether the system is short for refrigerant.
overhigh protection
Check whether the refrigerant pipes is blocked.

Check whether T6 and Tout are correctly connected to the motherboard.

Pb Anti-frozen protection Check whether T6 and Tout are damaged.


The detected temperature of T6 and Tout is lower than 5℃. Normal
protection, no need for treatment.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

2.11 Function

3-minute protection
Restart or open the manual switch after the unit stops, the unit will not start within three
minutes because of the self-protection function of the compressor.

Characteristics of heat pump heating operation


During operation, if outdoor temperature is higher than normal, the air supply motor will run
at low air volume or stop running.

Defrosting function perform at heating operation


 In case of the unit requiring deicing during heating operation, to prevent the heating
efficiency from decreasing, defrosting operation will turn on automatically (approx. 2~8
minutes).
 The fan motor will stop running when defrosting.
 During the defrost cycle a steam cloud (water vapour) may appear from the back of the unit
(after a defrost cycle, when the fans are restarted. This cloud is evacuated to the back of the
unit).

Operation condition of the heat pump water heater


 For proper using of water heater, please operate at the outdoor temperature -7℃~38℃.
 When water inlet pressure over than 0.4MPa, a pressure relief valve has to be mounted at
the water system.
 A sufficient water flow must pass into the heat pump.

About protection device


 When protection device operates, though the unit stops, the operating indicator of wire
control still will be blinking.
 When protection device operates, nixie indicator will display malfunction code (unit).
 Protection device will act when the following circumstances occur:
Air inlet or outlet is blocked.
Air in water or refrigerants system not completely exhausted.
Voltage is a little higher or lower compare to the voltage range (Exceeding the range of
207V~255V).

About Power off


 All operations stop when the power is off.
 At the next startup after power failure, the RUN indicator of wire controller will blink slowly

29
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

for several seconds for noting user.


 Mis-operation occur during unit working:
 In case mis-operation caused by lighting or vehicle radio, cut off the manual
power switch, and turn it on again, afterword press RUN/STOP key.
 It is forbidden to switch the power off if ambient temperature below -7℃. In
case of power failure or power need to be cut because of maintenance, please
open the drainage valves at the joints of water inlet and outlet pipes as soon
as possible to draining out all water. Otherwise, components inside of the units
may be damaged by freeze. Upon draining water, please close the water
drainage valves.

Shut-off memory
Every time when power is shut off, the controller will save the current operate status
automatically, when power come on the next time, controller will send the ON/OFF signal to
the water heater according to the memory before power shut off. The function keeps unit
always working on the mode which was set in the last time before power failure.

About RCCB
 Outdoor unit must use RCCB, be install a RCCB between in user power supply and the
outdoor unit. In case the unit cannot act but not attribute to power failure, please check
these RCCB switches at first. Before operate the RCCB, be ensure that the user installing
switch is break off.
 After the RCCB has serviced for a period of time, it is necessary to press the test button at
close circuit to check whether the performance of RCCB is work normally (Every time you
press this button, RCCB break up once). In case malfunction occurs, but no cause was
found, it is permit to delivering power to detect failure. If RCCB doesn’t work when being
powered, check out the cause by feature if necessary. If which is detected and confirmed as
its self-malfunction, consign a professional person repair it or replace it for a new one.

2.12 Wire controller

Wire controller KJRH-90B/E is used to accept the user’s order and to send it to main control board,
meanwhile receives operating states and display specifications.
 The wire length of the wire controller is 1m.
 After finish operating the wire-controller, the wire-controller’s waterproof box must be
covered to prevent rain damage.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

The appearance of controller

Name and function description of LCD screen of wire controller

① COOL indicator: When user sets the cooling mode, it lights up.
② HEAT indicator: When user sets the heating mode, it lights up.
③ PUMP indicator: When user sets the pump mode, it lights up.
④ POOL TEMP indicator: The outlet water temperature.
SET TEMP indicator: Show the setting temperature and blank when screen protection.

Codes are showed at the malfunction or protection time.
⑥ ALARM indicator: It will flashing at the malfunction or protection time.

Names of keys on the wire controller and the keypad operation description

⑦ MODE key, used to set different modes.


⑧ UP key, used to add time or temperature.
⑨ DOWM key, used to abate time or temperature.
LIGHT indicator. Lighting: working. Light off: standby.
⑩ Light up is 0.2S and then off in 0.2S: reparable error.
Light up in 1S and then off in 1S: data storage chip error.
ON/OFF key, used to turn the unit on or off.
31
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

Application of wire controller


1) Preparation before running the unit
 When you run the unit for the first time, all the indicators on the wire controller will light for 3s,
and then, display the fiducial web page. After no operation for 40s, all indicators will go out
automatically except POOL TEMP indicator lighting.
 When the unit is running, if there is no operation or malfunction for 10s, the backlight of the
display will go out automatically. After 30s, all indicators will disappear except operation
MODE and POOL TEMP.

2) Mode Selection
 The unit is enhanced with three operation modes, Cool Mode, Heat Mode and Pump Mode.
Cool Mode: The unit cools down swimming pool water by compressor drive according to
heat-pump principle. Used when the swimming temperature is high in summer.
Heat Mode: The unit heats swimming pool water by compressor drive according to
heat-pump principle. Used when the ambient temperature is low.
Pump Mode: The pump run for circling the water. Used when trial run or other necessary
situation.
 By default, the unit operates Heat Mode. Change:

3) Temperature set
 SET TEMP indicator displays the setting water temperature.
Default is 28℃, the cool mode setting range is 10~30℃, the heat mode setting range is
20~35℃.
 Method for set:
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

4) Power on/Power off


Press ON/OFF button after all the above have finished and the system will run as the setting.
And simply press the same button to stop it.

5) Operation status display

2.13 Spot check

Main control board spot check

Sequence System operation parameters Remarks

1st Normal display Value of T6


2nd Mode code 0: 6KW; 1: 8KW; 2: 12KW; 3: 14KW

3rd Operate mode 1 Cooling; 16 Water heating;4 Pump; 8 standby

4th Fan speed 0: OFF 1: Low 2:High


5th Ambient temperature Value of T4
6th Compressor discharge temperature Value of Tp
7th Pipe temperature Value of T3
8th Inlet water temperature Value of T6
9th Outlet water temperature Value of Tout
10th Compressor current Value of current
11st Setting water temperature Value of Ts
12nd The last error code or protection code Display the latest error code or protection code

2.14 Accessories

Name Qty. Sharp Purpose

Installation & Owner’s Manual 1 Installation and use instruction.

Seal ring 1 Discharge condensate water

Water outlet joining pipe 1 Discharge condensate water

33
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual

2.15 Resistance characteristic of temperature sensor

 Resistance characteristic of ambient Temp., pipe Temp. and suction Temp. sensor.
Temp. Resistance Temp. Resistance Temp. Resistance Temp. Resistance
(°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ)
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.219 25 10 65 1.96532 105 0.54448
-14 79.311 26 9.55074 66 1.89627 106 0.52912
-13 74.536 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.486
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44 36 6.13059 76 1.34105 116 0.4006
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.2133 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.5705 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.3239
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.8795 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.2777
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.918 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203

 Resistance characteristic of discharge temperature sensor


Temp. Resistance Temp. Resistance Temp. Resistance Temp. Resistance
(°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ)
-20 542.7 20 68.66 60 13.59 100 3.702
-19 511.9 21 65.62 61 13.11 101 3.595
-18 483 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.86
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.94 112 2.63
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.3 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.82 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174
0 180.9 40 29.15 80 6.859 120 2.117
1 171.9 41 28 81 6.641 121 2.061
2 163.3 42 26.9 82 6.43 122 2.007
3 155.2 43 25.86 83 6.228 123 1.955
4 147.6 44 24.85 84 6.033 124 1.905
5 140.4 45 23.89 85 5.844 125 1.856
6 133.5 46 22.89 86 5.663 126 1.808
7 127.1 47 22.1 87 5.488 127 1.762
8 121 48 21.26 88 5.32 128 1.717
9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5 130 1.632
11 104.6 51 18.96 91 4.849
12 99.69 52 18.26 92 4.703
13 95.05 53 17.58 93 4.562
14 90.66 54 16.94 94 4.426
15 86.49 55 16.32 95 4.294 B(25/50)=3950K
16 82.54 56 15.73 96 4.167
17 78.79 57 15.16 97 4.045 R(90℃)=5KΩ+-3%
18 75.24 58 14.62 98 3.927
19 71.86 59 14.09 99 3.812