Domestic Swimming Pool Type Heat Pump Water Heater Technical Service Manual V201500203
Domestic Swimming Pool Type Heat Pump Water Heater Technical Service Manual V201500203
Applicable Model:
LRSJ-60/NYN1
LRSJ-80/NYN1
LRSJ-120/NYN1
LRSJ-140/NYN1
Midea reserves the right to discontinue, or change specification or designs at any time without
notices and without incurring obligations.
1
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Content
1. General Information ........................................................................... 3
1.1 Measurements................................................................................................................3
2.1 Features..........................................................................................................................4
1. General Information
1.1 Measurements
1.3 Nomenclature
L RSJ - 60 / N Y N1
3
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
2.1 Features
Safety
2. No fuel tubes and storage, no potential danger from oil leakage, fire, explosion etc.
Environmental protection
Machine running parameter and the state can be checked quickly from the LCD display.
Automatic start-up and shutdown, automatic defrosting. Save you much extra operation.
The quadrate type can be easily installed in a corner of the verandah even if it’s very narrow.
All-the-weather running
Within the temperature range from -7 to 38℃, it will not be affected by night, overcast sky, rain and
snow.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Titanium-tube heat exchanger: Titanium-tube heat exchanger is use for heat exchange between
Fan: Axial fan with two speeds. The motor is supplied by Welling.
High Pressure Switch: When the discharge pressure of compressor is 4.4Mpa or higher, the
protection switch will be triggered, and if the discharge pressure is down to 3.2MPa, the protection
5
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
2.4 Specifications
Number of
5 5 8 8
circuits
Max.
MPa 0.4 0.4 0.4 0.4
pressure
3
The volume Min. value m /h 0.8 0.8 1.5 1.5
Controller KJRH-90B/E
Loading
20'/40'/40H Pcs 52/108/162 52/108/162 56/116/116 56/116/116
Quantity
Notes:
7
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Model: LRSJ-60/NYN1
Notes:
The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model: LRSJ-80/NYN1
Notes:
The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
9
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Model: LRSJ-120/NYN1
Notes:
The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model: LRSJ-140/NYN1
Notes:
The test conditions: inlet water temperature is 27℃,outlet water temperature is 29℃.
11
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Model: LRSJ-60/NYN1
Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 2.6m /h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model: LRSJ-80/NYN1
Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 3.5m /h.
13
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Model: LRSJ-120/NYN1
Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is 5.0m /h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model: LRSJ-140/NYN1
Notes:
3
The test conditions: inlet water temperature is 27℃, water flow volume is5.8m /h.
15
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
17
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
2.7 Installation
2.7.1 Transport
The main unit should be put down gently during transportation, and main unit should not be
Guard boards should be applied to avoid scratching and deforming of the unit surface.
After move onto installing site, please confirm the main unit is placed in horizontal.
Do not install the heat pump close to a road or path to protect the appliance against mud
splashing.
Avoid places that are subject to strong winds, in particular if the wind blows against the
A distance of no less than 200mm should be preserved between the bottom of the outdoor
unit and the ground or bracket for the installation of the duct pipe.
If the unit installed in an underground chamber, an indoor room or other hermetic place,
pay attention to where surrounding air, as well as which air exhaust and air circulating
system. For every signal unit, which circulating air volume shall no less than 2400m3/h.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
Model A B C D E F
LRSJ-60/NYN1
610 390 170 1015 385 705
LRSJ-80/NYN1
LRSJ-120/NYN1
590 333 165 1050 315 855
LRSJ-140/NYN1
19
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Water inlet and outlet pipes can be installed as long as the heat pump water heater has
been fixed.
Thermal insulation materials should be employed to seal up water outlet and inlet pipes.
The water inlet and outlet pipeline cannot be installed until the water heater is fixed well.
Before operation, please confirm that the specifications of connective pipes are correct,
and thermal insulation layer have been wrapped on pipes. It requires that all pipes have
Hydraulic connections
Connect the appliance’s PVC Φ 50 hose water inlet and outlet (according to label
Connection is established with a by-pass on the pool filtration circuit after the filter and
Hydraulic circuit test pressure: 0.3 MPa. Hydraulic circuit operating pressure: 0.15MPa.
If chemical or electrolyte disinfection systems are introduced, the installer and user must
contact the supplier to ensure they are compatible with our materials. These systems must
Item Requirements
PH value 6.9<PH<8
21
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
The air source water heater shall have a specialized power supply, which in compliance
If the unit needs to be installed on a metal part of the building, electric insulation must be
performed, and the installation must meet the relevant technical standards of electric
devices.
Power supply circuit of the air source water heater should be earthed, the power cord
should be connected with the external earthing line in reliable state and all the external
diagram.
Power cord and the signal cable shall be laid out orderly and separately.
The unit is not equipped with power cord. User could select power cable by reference to
power supply specifications. Shield wire must be employed for signal wire.
Select the power supply capacity and wire size according to the Design Manual. The size
of the power cable of the unit should be bigger than that of ordinary motors.
All wiring should be finished, before power is switched on to the unit, be confirm all
The power cable is as follows when power deliver to a certain wire individually (no power supply
device is used).
2
Min. wire size(mm )
Item (Metal pipe & synthetic resin Manual switch(A)
Power
pipe wire) RCCB
supply
Model Size (Continuous Ground
Capacity Fuse
length:≤30m) wire
LRSJ-60/NYN1
2.5 2.5 ≥20 16
LRSJ-80/NYN1 220-240V~, 30mA ≤
LRSJ-120/NYN1 50Hz 0.1sec
4 4 ≥32 25
LRSJ-140/NYN1
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
No power supply device is used; the specifications depend on connected unit’s actual
status.
Power supply device is used; the specifications can be derived from the above table
Wire size and continuous wire length in the table above only available for the case of the
If the continuous wire length value larger than the one of the table, please choose its size
Note: Although there is a leakage protector in the electric control box of the unit, for the
security reason, it is required that a leakage protector should be installed in the external
electric control box of the unit according to the requirement on the above diagram.
the auxiliary wiring (b) leading from deconcentrator and connected to the power supply
equipment. Please select the cable diameter according to the following methods:
Diameter of the main line (a) is conducted by the horsepower of the water heater and
Diameter of the wire (b) connected from deconcentrator to power supply device be
conducted by the horsepower of the water heater and power cable table:
23
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Do not reverse connections of low voltage electric signal wire with heavy electric wire,
25
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
2.9 Maintenance
Before leave the unit idle for a long period, please make sure the following:
Vacuum air completely inside the heat exchanger and water at pipelines, and turn off all
valves.
Check and clean the internal components of the unit at a regular base.
After leave the unit idle for a long period, please check the following:
Inspect whether the air intake orifice or air outlet is blocked periodically. If any, remove the
foreign substance to let the air flow fluently.
Check whether pipes, valves have damaged or blocked, whether connection sites have
leakage. If any, fix it properly.
time), you would see rust mix up water in red, flow out from tap. That is normal, just keep
draining and the rust will disappear after a while.
In case of the flowing malfunctions, please cut off the manual power switch and contact the local
dealer or after service center:
The fuse was burnt out frequently or the earth leakage protective device was broken up
frequently.
Only the red indication will be flashed.
Outlet water temperature Check whether the Tout temperature sensor is correctly connected to the
E3 motherboard.
sensor Tout error
Check whether the signal of Tout sensor is in strong electromagnetic
interference.
Check whether the T6 temperature sensor is damaged.
Inlet water temperature sensor
E4 Check whether the T6 temperature sensor is correctly connected to the
T6 error
motherboard.
27
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Evaporator pipe temperature Check whether the T3 temperature sensor is correctly connected to the
E5 motherboard.
sensor T3 error
Check whether the signal of T3 sensor is in strong electromagnetic
interference.
Check whether the T4 temperature sensor is damaged.
Ambient temperature sensor T4 Check whether the T4 temperature sensor is correctly connected to the
E7 motherboard.
error
Check whether the signal of T4 sensor is in strong electromagnetic
interference.
Check whether the water pump is damaged.
Shut down the unit and start until water in pipe flow fluently.
Waterflow switch error Check whether the waterlow switch is correctly connected to the
E9
motherboard.
Check whether the installation direction of waterlow switch is correct.
Check whether the waterlow switch is damaged.
Check whether the Tp temperature sensor is damaged.
Discharge pipe temperature Check whether the Tp temperature sensor is correctly connected to the
EE motherboard.
sensor Tp error
Check whether the signal of Tp sensor is in strong electromagnetic
interference.
Check whether the high pressure protection switch is damaged.
System high pressure protection
P0 ≥4.4MPa active, Check whether the refrigerant pipes is blocked
≤3.2MPa inactive Check whether the high pressure protection switch is correctly connected
to the motherboard.
Check whether the dial code S2 is correct.
Compressor current overhigh Check whether the voltage supplied is in the accepted voltage range.
P4
protection Check whether compressor is damaged.
Check whether the refrigerant pipes is blocked
Check whether the T3 temperature sensor is damaged.
Evaporator pipe temperature Check whether the T3 temperature sensor is correctly connected to the
P6
overhigh protection motherboard.
Check whether the fan is running normally.
2.11 Function
3-minute protection
Restart or open the manual switch after the unit stops, the unit will not start within three
minutes because of the self-protection function of the compressor.
29
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Shut-off memory
Every time when power is shut off, the controller will save the current operate status
automatically, when power come on the next time, controller will send the ON/OFF signal to
the water heater according to the memory before power shut off. The function keeps unit
always working on the mode which was set in the last time before power failure.
About RCCB
Outdoor unit must use RCCB, be install a RCCB between in user power supply and the
outdoor unit. In case the unit cannot act but not attribute to power failure, please check
these RCCB switches at first. Before operate the RCCB, be ensure that the user installing
switch is break off.
After the RCCB has serviced for a period of time, it is necessary to press the test button at
close circuit to check whether the performance of RCCB is work normally (Every time you
press this button, RCCB break up once). In case malfunction occurs, but no cause was
found, it is permit to delivering power to detect failure. If RCCB doesn’t work when being
powered, check out the cause by feature if necessary. If which is detected and confirmed as
its self-malfunction, consign a professional person repair it or replace it for a new one.
Wire controller KJRH-90B/E is used to accept the user’s order and to send it to main control board,
meanwhile receives operating states and display specifications.
The wire length of the wire controller is 1m.
After finish operating the wire-controller, the wire-controller’s waterproof box must be
covered to prevent rain damage.
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
① COOL indicator: When user sets the cooling mode, it lights up.
② HEAT indicator: When user sets the heating mode, it lights up.
③ PUMP indicator: When user sets the pump mode, it lights up.
④ POOL TEMP indicator: The outlet water temperature.
SET TEMP indicator: Show the setting temperature and blank when screen protection.
⑤
Codes are showed at the malfunction or protection time.
⑥ ALARM indicator: It will flashing at the malfunction or protection time.
Names of keys on the wire controller and the keypad operation description
2) Mode Selection
The unit is enhanced with three operation modes, Cool Mode, Heat Mode and Pump Mode.
Cool Mode: The unit cools down swimming pool water by compressor drive according to
heat-pump principle. Used when the swimming temperature is high in summer.
Heat Mode: The unit heats swimming pool water by compressor drive according to
heat-pump principle. Used when the ambient temperature is low.
Pump Mode: The pump run for circling the water. Used when trial run or other necessary
situation.
By default, the unit operates Heat Mode. Change:
3) Temperature set
SET TEMP indicator displays the setting water temperature.
Default is 28℃, the cool mode setting range is 10~30℃, the heat mode setting range is
20~35℃.
Method for set:
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203
2.14 Accessories
33
MCAC-RTSM-20150203 Midea Domestic Pool Type Technical Manual
Resistance characteristic of ambient Temp., pipe Temp. and suction Temp. sensor.
Temp. Resistance Temp. Resistance Temp. Resistance Temp. Resistance
(°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ) (°C) value (kΩ)
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.219 25 10 65 1.96532 105 0.54448
-14 79.311 26 9.55074 66 1.89627 106 0.52912
-13 74.536 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.486
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44 36 6.13059 76 1.34105 116 0.4006
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.2133 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.5705 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.3239
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.8795 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.2777
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.918 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231
Midea Domestic Pool Type Technical Manual MCAC-RTSM-20150203