Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT: SITE :

UNIT.NO. : BUILDING :

GENERAL DATA
DUCT MATERIAL : G. I. Sheet
ROUGHNESS COEF. : 0.93
ALTITUDE : Meters
ALTITUDE COEF. :
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES BOARD
AS PER ASHRAE DUCT FITTING DATABASE

SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TOTAL
FLOW CFM 1906 1830 1182.0 282 212
FLOW M3/H 3240.2 3111 2009.4 479.4 360.4
LENGTH M 7.00 4.00 3.00 6.00 1.60 21.6 ml
DIAM. mm 474.01 399.61 322.23 299.07 188.85
DIAM. EQUIV. 474.01 399.61 322.23 299.07 188.85
WIDTH mm 650 450 350 300 200
HEIGHT mm 300 300 250 250 150
AREA M2 0.18 0.13 0.08 0.07 0.03
VELOCITY M/S 5.10 6.89 6.84 1.90 3.57
PD per Meter Pa 0.63 1.35 1.73 0.18 1.02
PD x LENGTH Pa 4.43 5.39 5.20 1.10 1.63 17.75 Pa

Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TOTAL
ELBOW 30° 0.07
ELBOW 45° 0.09
ELBOW 90° 0.15 2 1
TEE 45° 0.3
TEE 90° 1
END TEE 1.5
BRANCH TEE 0.05 1 1 1 3 1
TRANSITION 0.22 1 1 1 1 1
CONTRACTION 0.05
WIRE MESH 0.04

TOTAL Co 0.57 0.27 0.27 0.37 0.42 1.90


DUCTS PD Pa 8.08 6.99 6.89 0.72 2.92 25.61 Pa
PRESSURE DROP Pa 12.51 12.38 12.09 1.82 4.55 43.36 Pa

SPECIAL FITTING PRESSURE DROPS


0.62 W.g
DESIGNATION PD (PA) QTY TOTAL STATIC PRESSURE AT 100% 153 Pa
FIRE DAMPER 10 FLOW AT 100% 3240 m³/h
VOLUME DAMPER 10 1 10 * DUCTS PRESSURE DROP : 43 Pa
EXHAUST GRILLE 15 1 15 * FITTING PRESSURE DROP : 110 Pa
RETURN GRILLE 10
EXHAUST LOUVER 20 1 20
VAV BOX 100
ALUMINUM FILTER 80 Add 15% safety
BAG FILTER 150 0.71 W.g
PLENUM BOX 50 1 50 STATIC PRESSURE AT 115% 176 Pa
DUCT HEATER 5 FLOW AT 110%
DISC EXHAUST VALVE 70 * DUCTS PRESSURE DROP : 48 Pa
FLEXIBLE DUCT CONNECTION 15 1 15 * FITTING PRESSURE DROP : 121 Pa
SOUND ATTENUATOR 50
TOTAL 110 Pa

You might also like