Start Do you receive

Alarm Which alarm is displayed?


Alarm / Message?
Temp. sensor give abnormal value. Sensor shorted Rotor failure Supply temp. low Fan failure Fire alarm
”Please wait…” is
Select Category No Message Is ”Starting up” displayed?
displayed?
Yes Temp. sensor provides no value. Sensor open Rotor temp. low Is supply sensor GT7 Is alarm triggered at Is correct fire sensor
Is there a key shown in Yes Yes installed correctly? the same time e.g. in type selected?
the bottom of the display? away-mode or pressure
The unit is initialized. After Does the unit respond to compensation?
booting, the unit switch to No Yes No No
any form of control from
REMOTE CONTROL normal operation. No Yes
The remote such as on/
Keylock activated.
/ALARM No Disable, push the left
off or change of fan
Which sensor give Disable water heating Is the water heating Is the alarm ”Rotor Install GT7 According to
Check the Yes
/MESSAGE speed? Yes Increase the fire sensor type.
button key down for 3 alarm? coil function coil function enabled? failure” also displayed? assembly instructions.
No Temperatures and the minimum speed.
sec.
rotor status is updated?
No
It is difficult to see the Does the unit get current? Yes No Reset of external
Yes
details on the display? See Fan Motors/EC. alarm is required before
No The remote does not Is ”Room regulation” Is a water heating coil starting the unit.
1- 4, 7 5, 6, 8 No
respond to key press? No type selected? installed? Is correct flow direction
Yes No Change flow direction.
selected?
No
Bad reception Yes Yes
Change filter!
Yes Check fuse, RCD and conditions. Yes
The remote is blank in Resetting the timer starts Filter timer
wiring. Check antenna and its Check the connection/
the display/does not Is the display image Is room sensor T8 Is anti-freezing sensor a new period.
No location. function of the faulty No
respond to key press mirrored / Upside down? installed? T5 installed? Has the supply air a very Insufficient heat
sensor.
despite new batteries? low temperature when Yes recovery. Check filter
Yes Yes unit alarms? and heater if fitted.
Yes
Yes
Yes Install Sensor Yes No
Remote control defect! Replace the batteries. Is the remote control Synkronisering
Synchronization
mellan Overheating Freeze protection
Contact your Installer/ Check the contrast synchronized with the fjärrkontroll
between the
ochremote
aggregat
The problem Insufficient heat
dealer. setings. unit? control
misslyckas?
and unit fails?
persists? Has the exhaust air low recovery. Check the
Yes
temperature? insulation on exhaust
Yes Has thermal protection Is sensor mounted on
No air duct.
No on electric heater the return pipe from the
Temperature sensor defective! Contact
No tripped? No heating coil?
Is it possible to start the Synchronize remote your Installer / Dealer. No
UNIT unit via remote control? control with unit.
Yes Yes
Yes Does the displayed
Yes temperature differ
significantly from real? Yes Check the temperature
Overheating alarm is Reset thermal No
Is correct temperature No on the supply pipe to the
Has the unit stopped and displayed? protection.
values Dispalyed when No Yes heating coil.
alarm is displayed? No
the unit is operating?
Check what is causing Can the problem be Rotor defect! Rotor motor defect! Yes
Yes No The shaft on rotor motor
the error. Make sure that No localized to the rotor Yes Contact your Yes Contact your
hangs / jams? Is the air flows adjusted? Yes For internal after heater; Connect jumper to
the rotor moves freely. shaft? Installer / Dealer. installer / dealer. Mount the sensor on
Is jumper connected to Aux and 0 on the relay
No the return pipe from the
No Aux and 0 on the relay card. See wiring
Yes No heating coil.
Check placement of the The temperature in the card? diagram.
ducts and isolation. ventilation system has not Adjust the air flows.
Check the selected flow stabilized yet. Clean rotor, belt and Rotor sensor defect! Is there voltage to rotor Yes
Is the rotor stuck No Check the quick
direction. Wait for 30 min. pulley. Replacement of Contact your motor when exchange No
somewhere? connectors and wiring.
belt may be necessary. Installer / Dealer. function is active?
For external after heater; Overheating alarm is
Connect also the No need for
Is the pressure in the displayed, but after the
Yes Yes negative pressure output No supplementary heat is
No No Yes Yes duct enough to activate heater regulates the
to fresh air duct. required.
This is normal when the pressure switch? correct temperature?
unit don’t need to recover
The alarm ”Rotor failure” Check the capacitance
more heat for desired Has the unit just been Check air flow on supply Is it bad grip between Is the rotor motor weak/ No Yes No
No is displayed but the rotor Yes on the associated Yes
temperature. started? side. Check filter. the belt and pulley? powerless? Connect pressure
is operating good? capacitor!
switch positive pressure
For external after heater; After heater is active all
output to supply air duct. Is week timer enabled
Is external pressure the time and The
Yes Yes Yes No Connect pressure switch No and running schedule? No
switch plugged in and overheating alarm is
terminal 2 & 3 to relay
connected correctly? displayed?
card terminal 0 & AUX.
Is a high efficiency The unit display No
Is a low efficiency The alarm ”Rotor failure” See wiring diagram. No Yes
No displayed? E.g. 95- No gradually lower No Yes
displayed? E.g. 23%? is displayed? Yes
100%? efficiency?
Specific temperature Pulser defect!
Yes Heating symbol is
No criteria apply for after Contact your
displayed in the remote?
heater function. installer/dealer.
HEAT EXCHANGER
Replace the filters. Is correct flow given at Are the fan speeds Yes
Are the unit of type AC Is it wrong sequence of Replacing the capacitors Does the capacitors keep
Check the value of the Yes maximum (100%) (10V), Yes adjusted in the remote EC or EC?
AC the fan speeds? is necessary. the right capacitance?
filter pressure switches. see pressure/flow chart? control? Open circuit!
Yes After heater is enabled in
AIRFLOW Yes Activate after heater in Check circuit and
No service menu but not No connections for after
Yes No the service menu.
No Check the wiring. active? heater.
Replace the fuse.
No
Voltage range should be No
The unit provides Does any fan motor
adjusted. Contact your Check transformers at
FAN MOTORS gradually lower air flow?
installer / dealer.
Adjust each speed. Does the motors rotate No have very low speed, or
the relay card. No Connect after heat Connect after heater to
in correct direction? standing still?
Yes No control cable to the specific terminal block. Yes
Is the fuse on the relay correct terminals. See wiring diagram.
What type of fans? AC Yes card intact?
Yes No No
Yes
Yes No Yes
EC After heater is active Is after heat control Is after heater connected
though turned off in the Yes cable connected to the on specific terminal
Is control cable for the Is the power for the
Yes Is correct flow given at service menu? correct terminals? block?
Is the alarm ”Fan failure” exhaust fan connected exhaust fan connected Check any dampers, Is there voltage to the Change places of
Change flow direction. Yes maximum (120V / 230V), No Yes
displayed? to the correct terminal on at correct terminal on the grills, etc. quick connector? the fans.
see pressure/flow chart?
the relay card? relay card?
No No
No No Yes
Is the correct flow
Yes
Does the supply fan Fan motor defect! The same problem The problem could not be No fault could be identified.
direction selected? start first? See Remote Control, Connect cable to the Is the fuse on the relay
No Replace the fuse. Contact your No occurs with the second solved. For other questions, please
Alarms/Messages correct terminal. card intact? installer / dealer. fan motor?
Contact your Installer/dealer. contact your Installer/dealer.
No
Yes
No
Yes Yes
Does the exhaust fan
start first? Could the problem be
Fans and control cables No "System OK ..." appears Basic settings incorrect!
Check the quick
identified in quick Yes Does the motor start?
Warning!
connected the wrong Yes ”Please wait…” is connectors at the fans!
in the display, but both Yes No Contact your connector? Work on the unit and its peripherals must be performed by
channel on relay card. displayed?
The unit initiates. engines are stopped? installer / dealer. No Yes a qualified Electrician / Installer. Observe that rotating, hot
and electrical parts can cause severe injury upon contact.
No
See section "Installation and safety" in operation manual.
ELECTRIC HEATER