Professional Documents
Culture Documents
Instrument Devices
Instrument Devices
Instrument Devices
Convention
2. Process Measurements
Temperature Measurements Pressure Measurements Flow Measurements Level Measurements
3. Control Valves
Valve Self-Actuated Solenoid
Introduction Actuators Valve Body Positioner Characteristics Valve Valve
5. Signal Transmission
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals.
TABLE OF CONTENTS
6. Control System
Basic Control Proportional Derivative
Introduction ON/OFF Control Integral Action
Principles Control Action
9. Wiring Diagram
Introduction Wiring Diagram Parts Wiring Diagram Legend Using Wiring Diagram
10.Safety
Introduction
INTRODUCTION
PART #1
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
The temperature is
now 84.9, it should be
85.0. I have to open
the valve a bit
In the field of industry, the following variables are mainly measured and called Process
Parameters: Process
❖ Temperature Parameter
❖ Pressure
❖ Flow
❖ Level
Process (Furnace)
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
Field
or
Site
Other Devices
Temperature Sensors Control Valves Solenoid Valve
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
Signals are transmitted between the Field Devices and the control room in one of the following ways
1. Pneumatic air pressure (3-15 psi) or (0.2-1 kg/cm2)
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
Signals are transmitted between the Field Devices and the control room in one of the following ways :
3. Digital Signal through cables or optical fiber
2. Electrical Signal (4 to 20 mA DC) through cables
(FOUNDATION Fieldbus, Modbus, etc.)
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
Signals are transmitted between the Field Devices and the control room in one of the following ways :
4. Wireless Signal
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
2. Cable Tray
Cable Tray: It is used to carry the secondary and main cables, and it comes in different sizes
according to the number and size of the cables.
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
3. Marshalling Cabinet
Marshalling Cabinet: It is used to arrange the cables connected from the field to be distributed to
the control devices or the System Cabinet. It also contains some devices such as Relays and Barriers.
1. INTRODUCTION
What is Process Field and Control Room Signal System
Field Devices
Instrumentation? Parameter Control Room Devices Transmission Wiring
4. System Cabinet
System Cabinet: In old systems, it contains control devices such as controllers,
indicators, and alarms. In modern systems, it contains PLC, DCS, or SIS.
MEASUREMENTS
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
where,
Rt = resistance of rtd at temperature t (ohm):
Rref:resistance of rtd at temperature of Tref
αo = temperature coefficient of resistance
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
2. Thermocouples (TC)
When two different metals are connected
from one end, a voltage will be generated at
the other end that is proportional to the
temperature.
2. Thermocouples (TC)
Note when trying to measure the voltage with a
voltmeter, other TC points will be generated
because the type of voltmeter wires differs from
the original TC wire type.
Several methods are used to get rid of this error, Special cables made of different alloys are used
but the basic idea is fixed, as another temperature to transmit the signal between the TC and the
sensor, type RTD, is placed, for example, at the measuring devices. Therefore, TC is one of the
meeting place of the wires, and the temperature expensive options, but it is more durable than
difference is subtracted from the measured RTD.
voltage.
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
2. Thermocouples (TC)
There are several types of TC covering different temperature ranges and suitable for different applications, and
each type has a special connecting wire.
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
Introduction
Pressure is one of the physical variables necessary to measure other variables such as
Flow, Level, density, and weight.
Pressure is measured in different units, but pounds per square inch (PSI) or Kg/cm2 are
used in industry.
Pressure Scales
There are two pressure scales depending on
the reference value:
Gauge pressure: The reference is atmospheric
pressure. It is marked with a letter (g) after
the unit of measurement, for example psi(g). Absolute Pressure= Gauge Pressure + atmospheric Pressure
Introduction
Level measurement methods can be divided into three
types:
Transparent
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
Hydrostatic pressure
The relationship between liquid column height
and pressure is as follows:
P = ρgh
Where
P: pressure
ρ : density of the liquid
H: height of the liquid column
g: ground acceleration
Orifice Plate
Orifice Plate: It is a thin metal plate (1.5 to 6
mm thick) that has a hole in the middle.
Variable-area flowmeters
Variable-area flowmeters work on the
principle of equalizing the forces between
the weight of a certain body and the
floating force resulting from the speed of
the material. The increase the flow
Proportional to the increase the body
height.
Magnetic flowmeters
Magnetic flowmeters work based on
Faraday's principle. Where an electromotive
force is generated in a conductor if it moves
perpendicular to a magnetic field
E = B*V*D
Flow = V*A = V*D2/4*π
Flow=C.E
2. PROCESS MEASUREMENTS
Temperature Pressure Level Flow
Measurements Measurements Measurements Measurements
Ultrasonic flowmeters
Ultrasonic flowmeters use ultrasound to measure
flow.
The meter contains an ultrasound transmitter and
receiver. The waves are sent obliquely, so the
wave’s arrival speed in the direction of flow is
more than the wave’s speed against the flow. By
calculating the time difference, the speed of the
material can be measured, as the difference
increases with the increase in speed.
Coriolis flowmeters
Coriolis flowmeters are very accurate counters that
calculate the mass flow of matter and also measure
the material's heat and density.
Definition
Control Valve: It is the last control device
(Final Controlling Device) in the control Diaphragm
of fluids. Actuator
Indicator
Seat
3. CONTROL VALVE
Valve Self-Actuated
Introduction Actuators Valve Body Positioner Solenoid Valve
Characteristics Valve
Actuator Types
The purpose of the Actuator is to precisely place the
Valve Plug in proportion to the control signal.
Packing Ring
Plug
Cage
Cage Plug
Seat
3. CONTROL VALVE
Valve Self-Actuated
Introduction Actuators Valve Body Positioner Solenoid Valve
Characteristics Valve
What is Positioner?
Positioner: It is a device that compares the
position of the valve movement with the
control signal and changes the pressure
applied to the Actuator to correct the
position.
Regulator
The control signal is a pneumatic signal of Positioner
Regulator
3-15 psi or an electrical signal of 4-20 mA, Positioner
and the output of the Positioner is usually
3-15 psi.
DEVICES
4. CONTROL ROOM DEVICES
Indicators Recorders Controllers Annunciators system HMI
Introduction to Indicator
Indicator: It is one of the control devices
whose function is to display the reading of
(field devices) without recording them.
Indicator Setup
All modern Indicator devices need programming
(Set up), which is done either through a calculator
or by means of keys in the device itself.
The most important things to be programmed in
the Indicator are:
• Tag
• Input Type: (Voltage, current, TC, RTD, etc.)
• Input Range: (1-5V, 4-20mA, 100mVDC, etc.)
• Low Range
• High Range
• Function: (Linear, Square Root)
• Alarm Value (if exist)
4. CONTROL ROOM DEVICES
Indicators Recorders Controllers Annunciators system HMI
Introduction to Recorder
Recorder: It is one of the control devices whose function
is to display and record (store) readings of field devices.
Recorder Setup
The Recorder can contain an Alarm.
All modern Recorder devices need to be programmed (Set up), either via a calculator or by means
of keys in the device itself.
The most important things that must be programmed in the Recorder are the same data in the
Indicator, in addition to matters related to the recording speed (Chart Speed) and the display
method.
4. CONTROL ROOM DEVICES
Indicators Recorders Controllers Annunciators system HMI
Controller Programming
All modern controllers need programming (set up),
which is usually done through a PC , due to the large
number of data that must be entered.
Introduction to Annunciator
Annunciator: It is a device that alerts the operator in case a variable
deviates from the normal conditions of operation, such as an
increase or decrease in the level of a tank above the normal
situation.
The previous method is the most common method, but there are
other methods adopted by different companies that depend on the
severity of the process.
4. CONTROL ROOM DEVICES
Indicators Recorders Controllers Annunciators system HMI
Introduction to HMI
Modern control systems that depend on PLC or DCS contain
HMI monitoring screens that compensate for all previous
devices, in addition to providing a graphical interface that
Controller helps the operator to better monitor and control.
Indicator
Alarm
Recorder
(Trend)
SIGNAL PART #5
TRANSMISSION
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Introduction
Despite the development in the instrument industry,
pneumatic measuring and control devices (operating
with air pressure) are still used so far in certain
applications.
Scaling
To find the PV transmitter reading if the output pressure is known in psi units:
𝑃−3
PV=Zero + (Span – Zero)
15−3
To find the transmitter output pressure (in psi units) if its scale is known:
𝑃𝑉−𝑍𝑒𝑟𝑜
P=3+(15-3) *
(𝑆𝑝𝑎𝑛−𝑍𝑒𝑟𝑜)
Pressure Pressure
% of scale
(psi) (kg/cm2)
3 0.2 0
6 0.4 25
9 0.6 50
12 0.8 75
15 1.0 100
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Examples
مثال صمام مثال مرسلة
If the positioner's outlet pressure is 11.2psi, how An air pressure transmitter with a range of 5-15
large should the valve opening be? bar, and the reading of the pressure gauge next
to it was 13 bar, so what is the output pressure?
Answer :
Answer :
For the valve , Zero=0 وSpan=100 𝑃𝑉−𝑍𝑒𝑟𝑜
P=3+(15-3) * (𝑆𝑝𝑎𝑛−𝑍𝑒𝑟𝑜)
𝑃−3
PV=Zero + (Span – Zero) 13−5
15−3 P=3+(15-3) * = 12.6 𝑝𝑠𝑖
(15−5)
11.2−3
PV=0 + (100 – 0) = 68.33%
15−3
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Fitting
To connect the signal tubes are used
Special connections shown in the
figure
Next door is called Fitting.
Fittings come in different shapes and
sizes depending on the type of use,
the size of the pipe, and the material
it is made of.
Introduction
4-20mA is the most common way to transmit a
signal.
Scaling
To find the PV transmitter reading if the current is known : Current
Value
Voltage
Value
% of scale
𝑚𝐴−4
PV=Zero + (Span – Zero) 4 1 0
16
To find the transmitted current if its reading value is known: 8 2 25
𝑃𝑉−𝑍𝑒𝑟𝑜 12 3 50
mA=4+16*
(𝑆𝑝𝑎𝑛−𝑍𝑒𝑟𝑜) 16 4 75
20 5 100
To find the PV transmitter reading if the voltages are known:
𝑉−1
PV=Zero + (Span – Zero)
4
Examples
مثال صمام مثال مرسلة
PLC system, one of its outputs is connected to a Programmable temperature transmitter from
control valve of the ATO type, so if the current is 300ͦC to 500ͦC. And the output current is 4-20mA.
17.3mA, what is the position of the valve What is the value of the current if the
opening in the location? transmitter has a temperature of 432 Cͦ ?
Answer :
Answer :
𝑚𝐴−4 𝑃𝑉−𝑍𝑒𝑟𝑜
OP=Zero + (Span – Zero) mA=4+16 *
16 (𝑆𝑝𝑎𝑛−𝑍𝑒𝑟𝑜)
17.3−4 432−300
OP=0+ (100 – 0) 16 = 83.128% mA=4+16 * (500−300) = 14.56𝑚𝐴
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Current Failure
Modern transmitters are designed to distinguish between failure and saturation.
• Failure: means a problem with the transmitter or sensor.
• Saturated: means that the reading assigned to the transmitter is outside the programming range.
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Introduction
Modern devices can measure a large number of variables, for example, the Coriolis meter
can measure flow, density, temperature, etc., and modern Positioner devices can measure
valve opening, air source pressure, output pressure, and device temperature.
More wires can be used to transmit such signals, but it is not the most appropriate option.
Digital communication can transmit a very large number of signals, the only determinant of
the number of signals is the speed of communication.
The HART communication system appeared, which used 4-20mA wires to transmit data,
then several communication protocols appeared that used special wires such as Modbus,
Fieldbus, and others.
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Fieldbus Protocols
There are several communication systems (generally called Fieldbus) designed to communicate with industrial
equipment.:
Protocol Icon
HART
Modbus
FOUNDATION Fieldbus
Profibus
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
HART
HART (Highway Addressable Remote
Transducer): The main purpose of this
protocol is to transmit data using the same
wires used to transmit a 4-20mA signal.
MODBUS
MODBUS appeared for the first time in 1979,
and it is a method used to transfer data
between devices via Serial Communication.
Foundation Fieldbus
Foundation Fieldbus: It is a protocol that not
only enables devices to communicate with each
other, but also enables them to implement
different types of control such as PID, Ratio,
Cascade, and others.
It is of two types:
Foundation Fieldbus H1: Double wire communication, 31.25Kbps used when high
speed is not required.
Foundation Fieldbus HSE: It uses the Ethernet Protocol, its speed is 100Mbps. An
Ethernet cable or an optical cable can be used.
5. SIGNAL TRANSMISSION
Pneumatic Signals Electrical Signals Digital Signals Wireless Signals
Profibus
Fieldbus it is a type of digital communication.
There are two types:
Information
The signal can be transmitted wirelessly, thus
reducing the cost of wires and reducing the
implementation time. It is very suitable for devices
located in remote areas such as oil wells.
Introduction
The controller compares the measured value PV
with the required value SP and changes the valve
orifice to make PV=SP. But how does he do that?
2. The required level for fluid height is 50% which is SP (Set Point).
3. To control the level, the flow of the fluid entering or leaving the tank must be controlled. Thus,
the flow is MV (Manipulated Variable), or the output is called OP (Output).
6. CONTROL SYSTEM
Basic Control Proportional
Introduction ON/OFF Control Integral Action Derivative Action
Principles Control
Note that the control system takes action after an error occurs, so it is called feedback.
6. CONTROL SYSTEM
Basic Control Proportional
Introduction ON/OFF Control Integral Action Derivative Action
Principles Control
Open Loop
Closed Loop: The input is variable
depending on the output.
For example, the driver of the vehicle
Closed Loop
presses on the fuel so that he tries to
keep the speed constant.
6. CONTROL SYSTEM
Basic Control Proportional
Introduction ON/OFF Control Integral Action Derivative Action
Principles Control
Proportional Band
The neighboring figures show
the response of the system to
different values of PB.
PI Control
The problem with Proportional Control is that it
does not handle the Offset and therefore the
value cannot be SP=PV.
PID Control
In systems that are subjected to perturbations that
make the error gradually increase with time,
Proportional Control will change the output gradually
and thus we need a long time to control.
We can reduce the value of the offset and shorten the
time required to return to SP again if we add a
component to the output that is proportional to the
rate of change in the error.
PID Control
:باختصار
P Control: causes an Offset to
occur
I Control: Makes the error zero.
D Control: It leads to faster
system stability.
MODERN CONTROL PART #7
SYSTEM
7. MODERN CONTROL SYSTEM
PLC HMI DCS SCADA
Introduction
The old control systems were based on
relays and timers. These systems suffer
from the following main problems:
What is PLC
PLC (Programmable Logic Controller): It is an industrial
computer designed to control a system. It reads input
sensors, makes decisions based on the user's program,
and controls output devices.
Introduction
Despite the capabilities provided by the
PLC, the operator needs to monitor data
and control operational conditions.
Use of HMI
HMI is used for the following purposes:
ETC ☺
7. MODERN CONTROL SYSTEM
PLC HMI DCS SCADA
Introduction
HMI is used to display the data in the PLC
But the following problems will appear :
Operation Windows
Operating interfaces may include the
following windows:
What is SCADA?
SCADA (Supervisory Control And Data
Acquisition) is a type of industrial control
system that is very large systems covering
large areas, linked to PLC and DCS control
units and other HMI monitoring systems in
addition to software systems and analytical
tools.
The purpose of SCADA is to collect important
data from various control systems, and it
does not usually focus on operational
conditions, but is concerned with production,
economy, and important operational matters.
PROCESS AND INSTRUMENTATION
DIAGRAMS (P&ID)
PART #8
8. PROCESS AND INSTRUMENTATION DIAGRAMS (P&ID)
Purpose of P&ID P&ID Symbols Equipment Symbols Piping Symbols Instruments Symbols
Tag
The Tag is placed in a certain way so that it gives information about the thing assigned to it, for example if the
Tag is FIC 104
FIC 204 : Tag Number
FIC 204 : Loop Number
FIC 204 : Function
FIC 204 : First Letter
FIC 204 : Succeeding-Letters
Sometimes the tag contains other letters or numbers, such as:
Tag
Information about a specific Tag can be found using a special table as shown below:
8. PROCESS AND INSTRUMENTATION DIAGRAMS (P&ID)
Purpose of P&ID P&ID Symbols Equipment Symbols Piping Symbols Instruments Symbols
Indicator Symbols
8. PROCESS AND INSTRUMENTATION DIAGRAMS (P&ID)
Purpose of P&ID P&ID Symbols Equipment Symbols Piping Symbols Instruments Symbols
Valve Symbols
8. PROCESS AND INSTRUMENTATION DIAGRAMS (P&ID)
Purpose of P&ID P&ID Symbols Equipment Symbols Piping Symbols Instruments Symbols
2. Control Room
✓ Marshaling Cabinet
✓ System Cabinet
✓ Sometimes there are other
divisions such as Control
Function and others
9. WIRING DIAGRAM
Introduction Wiring Diagram Parts Wiring Diagram Legend Using Wiring Diagram
32.1 That is, the At the top and bottom of the paper there
link is on page 32
are divisions that help keep track of the
in the first
section charts more easily.