If you have taken a tech call, or spent any time near someone who has, you may have heard of
the infamous “transformer Inrush”. If you would like to understand what that is and why it causes so
many tech calls, keep reading! If not, too bad you already opened the FAQ and now you must read the
whole thing!
In this picture, an AC voltage (Vp) is applied across the coil on the primary side of the
transformer. This causes a current (Ip) to flow through the turns of the coil. A current in a wire will
always create a magnetic field perpendicular to its direction of flow. In a transformer, the orientation of
the turns amplifies this magnetic field. The flow of this magnetic field is called “flux”. The number of
turns can be adjusted to change the total magnetic flux in the transformer. Too much flux can cause the
transformer to “saturate” which is the term used to describe when a transformer is magnetic flux is too
high for the size of the core. When at transformer is “saturated” it loses its ability to transfer energy to
the secondary effectively, usually causing excess heating. If there is too little magnetic flux, the
transformer will not be able to support the output voltage that is expected and the lightbulb in the above
picture will dim. Too little magnetic flux is what causes poor regulation in chargers. At high loads, the
transformer does not have enough energy stored as flux to keep the output voltage high enough.
Transformer Inrush Explained FAQ 1075 Saint John Street Easton, PA 18042-6661
Phone 610.330.9000 Fax 610.330.8510
www.hindlepowerinc.com
The flux shown above rotates through the core as shown by the directional arrows. When
turns are added as a secondary winding, like the light bulb picture from before, the flux is converted back
to current. This is called “mutual induction”. The turns ratio determines the voltage on the secondary
winding. If there are half as many turns on the secondary as the primary, the induced voltage will also be
half. It is important to note that transformers only work with alternating currents (AC). They will not
work with direct current (DC) applications because the constant current in one direction saturates the
transformer and does not allow for mutual induction.
1. When a current is applied through the breaker that is higher than its rated current, internal
components of the breaker overheat. This heat is monitored and when it exceeds an expected
value, the breaker opens. This process is very slow. It can take hours to trip a breaker that is
slightly overloaded.
2. When an exceptionally high current is detected, like a short, the breaker opens. This high current
is detected using the same ideas that the transformer depends on. The high spike of current
generates a strong magnetic field and the breaker’s components detect this spike (almost)
instantaneously.
Transformer Inrush Explained FAQ 2 of 5 Printed 3/26/2021 2:30 PM
Quality and Integrity - Our Passion INCORPORATED
Transformer Inrush Explained FAQ 1075 Saint John Street Easton, PA 18042-6661
Phone 610.330.9000 Fax 610.330.8510
www.hindlepowerinc.com
At this point, you may have already figured out the problem. If a transformer has a very high
inrush spike, the breaker open because of the magnetic field that current creates. This could cause a
situation where a charger loses AC power, and when that power comes back the input breaker opens
because of an inrush, leaving the charger unpowered until someone can manually reset the breaker. If
that charger is located somewhere far away, or just not monitored well, the batteries can go uncharged
for an unknown amount of time.
Transformer Inrush Explained FAQ 1075 Saint John Street Easton, PA 18042-6661
Phone 610.330.9000 Fax 610.330.8510
www.hindlepowerinc.com
Energizing the core of the transformer happens in just a few milliseconds. As you can see in the
60Hz sine wave, voltage varies from 100% to zero every 8.66 milliseconds. That means that the voltage
applied to the primary to energize the transformer changes very quickly, too quickly to perfectly repeat
by hand, so every time the transformer is turned on, it is at a different voltage level. If the transformer
happens to be energized at the peak of the AC waveform, the inrush current is very low. The amount of
energy required to energize the core stays the same which means that higher voltages will require less
current. The worse inrush happens when the AC waveform is crossing zero. At this moment, the
voltage levels are extremely low, requiring a lot of current to energize the core. Here is a picture of
what inrush looks like over time:
Transformer Inrush Explained FAQ 1075 Saint John Street Easton, PA 18042-6661
Phone 610.330.9000 Fax 610.330.8510
www.hindlepowerinc.com
1. Do not oversize the core. Larger transformers will run cooler and regulate better, but they
also cost much more, and the inrush is much higher. Try to keep the core as small as
possible without overheating or losing regulation.
2. If possible, move the primary windings to the outer layer of the coil. The farther the primary
is from the core, the less it induces flux on the core. This will barely affect the normal
operation of the transformer, but it will cut the inrush current by a lot. Typically,
transformers with primaries on the outer layers are HALF the inrush of transformers with the
primary close to the core. It takes longer to energize the core, but that’s a good thing.
3. Keep the number of primary turns high. Each turn amplifies the power transfer from the
winding to the core, so more turns mean less inrush. Think of it like filling a pool with
buckets of water. It is easier to fill a pool with buckets of water if you have a group of
people all filling it at the same time rather than one person.
There are things a customer can do to keep their inrush low as well. Here are some ideas:
1. Size the charger according to what is needed. If a larger charger is purchased, it can power
loads at a lower current by setting the current limit lower, but the inrush is always the same.
That means that running a charger at lower loads does not change the inrush. Purchasing an
800A charger and using for 100A loads is a bad idea.
2. Increase the source impedance. As mentioned before, the source impedance is a critical factor
in determining the inrush of a transformer. There are many times where power generation
plants purchase chargers and have inrush issues. This is because their source impedance is
extremely low. There is nothing that we can do to the design of a transformer to keep the
inrush low enough if the source impedance is too low. Remember, the theoretical max inrush
can be 3 times higher than the typical. The breakers we use are the slowest version available,
and they typically only allow for about 50% higher than the typical inrush. For example, a
transformer with a typical inrush of 500A would have a breaker that opens if the inrush hits
750A or so, and the theoretical max inrush with a low impedance source could be 1500A!
3. Ensure that the customer is feeding the charger with a breaker that has a slow trip response
capable of lasting through inrush. Most breakers are not designed for large inrush spikes. Most
inrush issues result from customers purchasing the wrong type of source breaker.
Fin