Professional Documents
Culture Documents
4-018 TSB
4-018 TSB
4-018 TSB
RD-4-018
06-27-02
Micro switches - cams and tower - friction lock-nut output transistor heat sink
The test device in the photos to follow is an OEM Tester, 57042822, designed in the
80’s to assist in troubleshooting problems in proportional control circuits in the DMH
product. The OEM tester is still in use today and has been revised to include the
capability to test proportional control circuits in DM45/50/L and DMM3 products. The
tester has a built-in 120 Vac 50/60 Hz. to 24Vdc power supply, use three prong male
power cord to connect into standard wall receptacle. 24Vdc can be supplied directly
via the two-wire alligator clip cable in the back compartment. There is a voltmeter to
verify the internal power supply is operating and to monitor the voltage out of a
controller. There is an ammeter to monitor the current going from the controller to the
load, either internal or external. Two internal power resistors are sized to the nominal
resistance value of the loads used in the proportional control circuits, such as Apitec
valves, Denison 5A pump control, Dynex actuators, and FEMA valve. The front
terminal strip provides the means to connect a controller and an external load to the
testing.
Connect the suspect controller or coil to the tester by matching terminal markings.
The coil will connect to the terminals marked “EXT LOAD” and will be connected to the
controller when the selector switch is in the appropriate position. The threshold and
maximum output adjustments need to be checked and verify settings can be changed.
Many times the adjustments are so far incorrect that the controller appears to be non-
adjustable. Check the max first, with the handle in maximum position, adjust max pot
until you see a change in current, then stop, slowly return the handle to center
position. As you move the handle from max position, the current should decrease, if
not, keep adjusting max pot. The goal is to see current change throughout the handle
movement. For threshold, move handle slowly from the center, off, position until you
here one switch activate in one direction and two activate in the other. This clicking
sound is the switches turning the control card on and determining output polarity, if
applicable. You should be able to set the threshold at 50 to 75 mA. How to determine
if the controller has an intermittent problem. While the controller is active and
providing at least 300 mA of current, monitor the ammeter while tapping on the
controller in different places with the handle end of a screw driver. Watch for
fluctuations of the ammeter, take note of the area of the controller affected.
ROTARY DRILL
RD-4-018
06-27-02
Shown here is the tester with a controller connected via the connection cable. Just match
the letters of the terminal strips. Connect the appropriate power cable. There is a main on/off
switch, below the fuse. The power supply check switch is to the left of the fuse. The load
selector switch is to the right of the fuse.
5 ROTARY DRILL
The photo below shows the tester connected to a controller and an Apitec pulsar
valve. The selector knob is used to connect the controller to one of the internal load
resistors or to an external load. Moving the controller handle will provide current to the
external load, as seen on the volt and ammeters.
This photo shows an example of a controller with three output trim potentiometers.
The threshold pot is used to determine the point at which action will take place, such
as rotation or movement of a cylinder.